20 1 #12 1/2
30 1 #10 3/4
40 1 #8 1
50 1 #6 1-1/4
60 1 #4 1-1/4
70 1 #4 1-1/4
80 1 #3 1-1/2
90 1 #2 1-1/2
100 1 #1 2
125 1 #1/0 2
150 1 #1/0 2
175 1 #2/0 2-1/2
200 1 #3/0 2-1/2
225 1 #4/0 3
250 1 #250 3
300 1 #350 3-1/2
350 1 #500 4
400 2 #3/0 2-1/2
500 2 #250 3
600 2 #350 3-1/2
700 2 #400 3-1/2
800 2 #500 4
1000 3 #400 3-1/2
1200 4 #350 3-1/2
1600 5 #500 4
2000 6 #500 4
2500 7 #500 4
#12
#10
#10
#10
#10
#8
#8
#8
#6
#6
#6
#6
#4
#4
#4
#3
#3
#3
#2
#1
#1/0
#1/0
#2/0
#3/0
#4/0
#250
#350
EACH FEEDER DESIGNATION REPRESENTS (3) PHASE CONDUCTORS, (1) NEUTRAL
CONDUCTOR, (1) EQ. GRD. UNLESS NOTED OTHERWISE.
30 50 #6100
45 70 #6150
75 125 #2250
112.5 175 #1/0400
NOTES:
1. PRIMARY FEEDER IS (3) PHASE CONDUCTORS.
2. CIRCUIT BREAKER IS 3-POLE BREAKER RATED FOR VOLTAGE AS SHOWN IN SCHEDULE.
3. SECONDARY FEEDER IS (3) PHASE CONDUCTORS, (1) NEUTRAL CONDUCTOR, (1) EQ. CONDUCTOR.
REFER TO FEEDER SCHEDULE FOR CONDUCTOR & CONDUIT SIZES.