This solicitation is for the furnishing and installation of a brand specific heat pump system in a historic building located in Skagway, Alaska. The National Park Service Alaska Region is seeking to replace the existing heating system in the Mascot Saloon with a new heat pump system. Offerors should be able to provide a complete turnkey solution, including all necessary equipment, materials, labor and commissioning to install a functioning system. The historic nature of the building requires special consideration for the new mechanical system. The response deadline and award date are not specified in the document provided.
View the file
Other files
Show all 18
On GovTribe
Work with this file
- Download the original file
- Contacts named in this file
- Similar government files
- Ask GovTribe AI about this file
Text version
1 View Name 1/8" = 1'-0"A101
Room name
GENERAL SYMBOLS
NAME
NUMBER
SHEET LOCATION
SCALE
TRUE NORTH
GRID LINE
ROOM NAME
ROOM NUMBER
PLAN NORTH
REVISION
SEE DISCIPLINES FOR SPECIFIC SYMBOLS
PROJECT TEAM
OWNERS REPRESENTATIVE
NATIONAL PARK SERVICE
POINT OF CONTACT: CORY THOLE
P.O. BOX 517, SKAGWAY, AK, 99840
907 983-9263
CORY_THOLE@NPS.GOV
DESIGNERS REPRESENTATIVE
DESIGN ALASKA
POINT OF CONTACT: EMILY WINFIELD
601 COLLEGE ROAD, FAIRBANKS, AK 99701
907 452-1241
EMILYW@DESIGNALASKA.COM
VICINITY MAP
PROJECT
LOCATION
ALASKA MAP
PACIFIC OCEAN
ARCTIC OCEAN
BERING SEA
KODIAK
ARCTIC CIRCLE
SEWARD
SITKA
JUNEAU
HAINES
WHITEHORSE YT
DAWSON YT
HAINES
JCT
HOMER
ANCHORAGE
EAGLE
CORDOVA
VALDEZ
GLENNALLEN
TOK
NORTH
POLE
FAIRBANKS
NENANA
TANANA
CIRCLE
NOME
KOTZEBUE
UTQIAGVIK
(BARROW)
PRUDHOE BAY
U N
IT
E
D S
T A
T E
S
R U
S S
IA U
N
IT
E
D S
T A
T E
S C
A N
A D
A PROJECT
LOCATION
SKAGWAY
ISSUE DATE
COMM. NUMBER
DESIGNED BY
DRAWN BY
SCALE 0" 1"
Architects Engineers Surveyors 601 College Road Fairbanks AK 99701
907.452.1241 designalaska.com
17 DEC 2020
MASCOT SALOON
HEATING SYSTEM
CONVERSION
402003
AECC511
12/15/2020 8:45:15 AM
ECW
ECW
GENERAL
INFORMATION
G001
MASCOT SALOON HEATING SYSTEM CONVERSION
SKAGWAY, ALASKA
NATIONAL PARK SERVICE
GENERAL
G001 GENERAL INFORMATION
MECHANICAL
M001 MECHANICAL ABBREVIATIONS, AND LEGENDS - ALL OPTIONS
M002 MECHANICAL SCHEDULES
M100 FIRST FLOOR MECHANICAL DEMOLITION PLAN
M200 FIRST FLOOR MECHANICAL PLAN
M201 FIRST FLOOR RADIANT ZONING PLAN
M202 FIRST FLOOR RADIANT TUBING LAYOUT PLAN
M300 ENLARGED MECHANICAL ROOM PLAN
M400 MECHANICAL DETAILS
ELECTRICAL
E001 ELECTRICAL LEGEND AND SCHEDULES
E100 ELECTRICAL SITE PLAN
E200 FIRST FLOOR ELECTRICAL PLAN
E300 POWER RISER
ABBREVIATION FULL NAME
W WASTE
VENTV
CW COLD WATER
HW HOT WATER
RECIRCULATED HOT WATERRHW
GHS GLYCOL HEATING SUPPLY
GHR GLYCOL HEATING RETURN
EXISTING
EXISTING TO BE REMOVED
MECHANICAL - LINETYPES
RS REFRIGERANT SUPPLY
RR REFRIGERANT RETURN
PRESSURE REDUCING VALVE
DRAIN VALVE
PRESSURE RELIEF VALVE
UNION
HOSE BIBB
2-WAY CONTROL VALVE
THERMOMETER
PRESSURE GAUGE
MECHANICAL SYMBOLS
PIPE CONNECTION
PIPE ELBOW TURNED DOWN
PIPE ELBOW TURNED UP
PIPE TEE DOWN
PIPE FLOW ARROW
BALANCING COCK
CHECK VALVE
NON-SLAM CHECK VALVE
ISOLATION VALVE
AIR VENT
CONNECTION TO EXISTING
PRESSURE & TEMPERATURE TEST PORT
NS
ISSUE DATE
COMM. NUMBER
DESIGNED BY
DRAWN BY
SCALE 0" 1"
Architects Engineers Surveyors 601 College Road Fairbanks AK 99701
907.452.1241 designalaska.com
17 DEC 2020
MASCOT SALOON
HEATING SYSTEM
CONVERSION
402003
AECC511
12/17/2020 9:06:16 AM
ECW
BAB
MECHANICAL
ABBREVIATIONS,
AND LEGENDS -
ALL OPTIONS
M001
BALANCE COCK SCHEDULE
DIA (IN)
MINIMUM
GPM
1/2 1 3/4 3 1 4
1-1/4 10 1-1/2 15
2 34 2-1/2 55
3 92 4 180 6 440
PIPE SCHEDULE
DIA (IN)
MAX DESIGN
GPM
3/4 3 1 7
1-1/4 13 1-1/2 21
2 46 2-1/2 82
3 132 4 280 6 800
MECHANICAL ABBREVIATIONS
KEY NAME MECHANICAL ABBREVIATIONS
MECH MECHANICAL
MIN MINIMUM
MTR MOTOR
NC NORMALLY CLOSED
NG NATURAL GAS
NIC NOT IN CONTRACT
NO NORMALLY OPEN
NPS NATIONAL PARK SERVICE
NPSH NET PUMP SUCTION HEAD
NTS NOT TO SCALE
OAT OUTSIDE AIR TEMPERATURE
OBVD OPPOSED BLADE VOLUME DAMPER
OC ON CENTER
OD OUTSIDE DIAMETER
ODU OUTDOOR UNIT
OFCI OWNER FURNISHED, CONTRACTOR INSTALLED
OFOI OWNER FURNISHED, OWNER INSTALLED
ORD OVERFLOW ROOF DRAIN
ORL OVERFLOW RAIN LEADER
OSA OUTSIDE AIR
P&T PRESSURE AND TEMPERATURE
PD PRESSURE DROP
PH PHASE
PRDV PRESSURE REDUCING VALVE
PRV PRESSURE RELIEF VALVE
RA RETURN AIR
RD ROOF DRAIN
RHW RECIRCULATING HOT WATER
RL RAIN LEADER
RP RADIANT PANEL
RPM REVOLUTIONS PER MINUTE
S/M SHEET METAL
S/S START/STOP
SH SHOWER
SIM SIMILAR
SP STATIC PRESSURE
SPEC SPECIFICATIONS
SS STAINLESS STEEL
ST STEAM
SWSI SINGLE WIDTH, SINGLE INLET
TDH TOTAL DYNAMIC HEAD
THW TEMPERED HOT WATER
TP TRAP PRIMER
TYP TYPICAL
V VENT
VAV VARIABLE AIR VOLUME
VERT VERTICAL
VFD VARIABLE FREQUENCY DRIVE
VOL VOLUME
VTR VENT THROUGH ROOF
W WASTE
W/ WITH
W/O WITHOUT
WB WETBULB
WCO WALL CLEAN OUT
WHA WATER HAMMER ARRESTOR
MECHANICAL ABBREVIATIONS
KEY NAME MECHANICAL ABBREVIATIONS
# NUMBER
& AND
@ AT
A AIR
AFF ABOVE FINISHED FLOOR
AGT AVERAGE GLYCOL TEMPERATURE
AHU AIR HANDLING UNIT
APD AIR PRESSURE DROP
APPR APPROVED
APPROX APPROXIMATE
ARCH ARCHITECTURAL
ASSOC ASSOCIATED
AUTO AUTOMATIC
BAL BALANCING
BFF BELOW FINISHED FLOOR
BFP BACKFLOW PREVENTOR
C COMMON
CI CAST IRON
CLG COOLING
CO CLEAN OUT
CR CONDENSATE RETURN
Cv VALVE COEFFICIENT
CW COLD WATER
DB DECIBEL
DB DRYBULB
DI DUCTILE IRON
DIA DIAMETER
DN DOWN
DWDI DOUBLE WIDTH, DOUBLE INLET
EA EXHAUST AIR
EAT ENTERING AIR TEMPERATURE
EF EXHAUST FAN
EGT ENTERING GLYCOL TEMPERATURE
ELEC ELECTRICAL
ESP EXTERNAL STATIC PRESSURE
EWT ENTERING WATER TEMPERATURE
EXIST EXISTING
FC FORWARD CURVED
FD FLOOR DRAIN
FLA FULL LOAD AMPERAGE
FLEX FLEXIBLE
FP FIRE PROTECTION
GA GAUGE
GALV GALVANIZED
GHR GLYCOL HEATING RETURN
GHS GLYCOL HEATING SUPPLY
GHS&R GLYCOL HEATING SUPPLY & RETURN
GI GALVANIZED IRON
HB HOSE BIBB
HW HOT WATER
ID INSIDE DIAMETER
IDU INDOOR UNIT
IE INVERT ELEVATION
INSUL INSULATION
IPS IRON PIPE SIZE
LAT LEAVING AIR TEMPERATURE
LGT LEAVING GLYCOL TEMPERATURE
MAX MAXIMUM
SEQUENCE OF OPERATION
AIR SOURCE HEAT PUMP: THE ASHP ENABLES P-4 AND STAGES THE HEAT PUMP COMPRESSORS
AND BUFFER TANK AUXILARY HEATER TO MAINTAIN THE BUFFER TANK TEMPERATURE SETPOINT
PER THE FOLLOWING SCHEDULE:
STAGE SOURCE ON TEMP OFF TEMP
ASHP
ASHP
BT
80F
75F
60F
90F
85F
70F
WATER SOURCE HEAT PUMP: THE WSHP ENABLES P-2 AND P-3 AND STAGES THE HEAT PUMP
COMPRESSOR AND BUFFER TANK AUXILIARY HEATER TO MAINTAIN THE BUFFER TANK
TEMPERATURE SETPOINT PER THE FOLLOWING SCHDULE:
STAGE SOURCE ON TEMP OFF TEMP
WSHP
BT
150F
140F
155F
155F
BUILDING PUMP P-1A & P-1B: PUMPS ARE CONTROLLED IN A LEAD/LAG CONFIGURATION USING TEKMAR 132 PUMP SEQUENCER. SET EACH PUMP TO MAINTAIN CONSTANT PRESSURE OF 27' HEAD.
AIR SOURCE HEAT PUMP SETTINGS
GENERAL
ANTI-SHORT CYCLE: 5 MINUTES
COMPRESSOR START DELAY: 0 MINUTES
OUTDOOR FAN SPEED: 100%
SETPOINT CONTROL
CONTROL SOURCE HYD: SETPOINTS
SETPOINTS METHOD: EXTERNAL
STAGING SETPOINTS
STAGE 1: ON AT 80F; OFF AT 90F
STAGE 2: ON AT 75F; OFF AT 85F
OUTDOOR RESET: DISABLED
HYDRONIC AUXILIARY IN DEFROST: DISABLED
TOP UP S1: DISABLED
BUFFER TANK SETTINGS
SET TOGGLE SWITCH ON BACK OF CONTROLLER TO "ELECTRIC" MODE.
SET TO "JOIST HEAT" MODE
CONTROL IS PROVIDED BY THE RESPECTIVE HEAT PUMP
2 WSHP 145F 155F
AKAF AL
TS
TA E O
49 TH
S
Emily C. Winfield
ME 109592
REGISTERED PROFESSIONAL ENGIN
EE
R
16-DEC-2020
WATER SOURCE HEAT PUMP SETTINGS
SET POINT CONTROL
CONTROL SOURCE HYD: SETPOINTS
SETPOINTS METHOD: EXTERNAL
STAGING SETPOINTS
STAGE 1: ON AT 150F; OFF AT 155F
STAGE 2 (AUXILIARY): ON AT 145F; OFF AT 155F; DELAY 5 MINUTES
OUTDOOR RESET: ENABLED: RESET FACTOR: 2F
MISCELLANEOUS EQUIPMENT SCHEDULE
SYMBOL ITEM CAPACITY / SIZE MOTOR
DATA
OPERATING
WEIGHT {1} (LB)
BASIS OF DESIGN REMARKS
ASHP-1
IDU
AIR SOURCE HEAT PUMP
INDOOR UNIT
AS-1 HEATING SYSTEM AIR
SEPARATOR
BT-1 BUFFER TANK/ELECTRIC
BOILER
{1} OPERATING WEIGHT INDICATED. PLUS 10% IS MAXIMUM ALLOWED WEIGHT IF USING A SEISMIC DETAIL PROVIDED AS PART OF CONTRACT DOCUMENTS.
{2} CAPACITY OF 240V EQUIPMENT CONNECTED TO 208V SYSTEMS SHALL BE MULTIPLIED BY 75%
BT-2
38.3 MBH GROSS OUTPUT,
71 GALLON
208/1/60 11.3kW 54.7A
975 THERMO 2000 T2
ALTSOURCE 70-15
1. CHARGE W/ 134A REFRIGERANT
1. HEATING CAPACITY DERATED: 240V EQUIPMENT CONNECTED TO
208V SYSTEM
28.4 MBH MIN HEATING OUTPUT
AT 1°F, 105°F LGT, 96°F EGT
375 NORDIC ATW-75 IDU 1.
2.
CHARGE W/ R410A REFRIGERANT
SINGLE POINT ELECTRICAL CONNECTION
208/3/60 25.4A
WH-1
(EXISTING)
MASCOT ELECTRIC
WATER HEATER
30 GALLON STORAGE CAPACITY
18 GPH RECOVERY AT 100°F RISE
208/1/60 3.4kW
--- RELIANCE
630DORT
1.
2.
EXISTING WATER HEATER TO REMAIN
HEATING CAPACITY DERATED: 240V EQUIPMENT CONNECTED TO
208V SYSTEM
WH-2
(EXISTING)
HERN/CLIPPER ELECTRIC
WATER HEATER
6 GALLON STORAGE CAPACITY
24 GPH RECOVERY AT 100°F RISE
208/1/60 6kW
--- RHEEM
EGSP6
1. EXISTING WATER HEATER TO REMAIN
2" THREADED, 40 GPM FLOW ----- 8.5 SPIROTHERM SPIROVENT
JR VJR200TM
BTU-1 BTU METER 2% ACCURACY, 140F-212F
TEMPERATURE RANGE
--- --- ONICON
SYSTEM-10
1.
2.
METERING FOR HERN CLIPPER LEASE SPACE
PROVIDE W/THERMOWELL KIT AND F-1100 TURBINE FLOW METER
CIRCULATING PUMP SCHEDULE
SERVICESYMBOL STYLE
P-1A,B GLYCOL HEATING
P-4 ASHP
CIRCULATION
GPM HEAD
(FT H2O)
RPM MOTOR
DATA
BASIS OF DESIGN MAX
BHP
REMARKS
34 27 3/4 HP
208V/1Ø/60
TACO 1915E-F -----
16 10 170 W 208V/1Ø/60
TACO 0034E-F2 -----
IN-LINE
IN-LINE
1. PROVIDE W/ TEKMAR 132 LEAD/LAG CONTROLLER
{1} SELECTION AND PRESSURE DROP BASED ON 30% PROPYLENE GLYCOL / 70% WATER UNLESS OTHERWISE NOTED.
GMT-1 GLYCOL MAKEUP TANK 115/1/60
50W
120 AXIOM
MF300
17 GALLON CAPACITY ---
ET-1 HEATING SYSTEM DIAPHRAGM
EXPANSION TANK
10.3 GALLON VOLUME
10.3 GALLON ACCEPTANCE VOLUME
----- 23 AMTROL THERM-X-TROL
ST-25V
1.
2.
12 PSIG PRECHARGE
264 GALLON ESTIMATED SYSTEM VOLUME
CABINET UNIT HEATER/UNIT HEATER SCHEDULE
CAPACITY
(MBH)
SYMBOL MAX FLOW
(GPM)
MAX PD
(FT H2O) {1}
BASIS OF DESIGNEAT (F) REMARKS
{1} SELECTION AND PRESSURE DROP BASED ON 30% PROPYLENE GLYCOL / 70% WATER UNLESS OTHERWISE NOTED.
{2} CAPACITY OF 240V EQUIPMENT CONNECTED TO 208V SYSTEMS SHALL BE MULTIPLIED BY 75%
LOCATION STYLE EGT (F) MIN
CFM
MOTOR
DATA
7.5EUH-1 MASCOT
MECHANICAL RM.
HORIZONTAL BLOW --- 65---- --- 350 2.2 KW
208V/1Ø/60
QMARK
MUH03-21
B-2 BOILER SERVING
HERN/CLIPPER
215,700 BTUH ---- ----- WEIL MCLAIN B768 VW 1. EXISTING, TO REMAIN
WSHP-1 WATER SOURCE HEAT PUMP 114.1 MBH GROSS OUTPUT
160°F LGT
208/3/60 32.8A
950 NORDIC WH-150-H
BUFFER TANK/ELECTRIC
BOILER
98.9 MBH GROSS OUTPUT,
71 GALLON
240/1/60 29.0kW 120A
975 THERMO 2000 T2
ALTSOURCE 70-29
1.
2.
PROVIDE W/ OPTIONAL COPPER COIL FOR DHW HEATING
CONNECT TO BUCK-BOOST TRANSFORMER SUPPLYING 240V
P-2 WSHP
CIRCULATION
36 9 170 W 208V/1Ø/60
TACO 0034E-F2 -----IN-LINE ----- 1. OPERATE ON LOW SPEED SETTING
P-3 WSHP
CIRCULATION
36 9 170 W 208V/1Ø/60
TACO 0034E-F2 -----IN-LINE ----- 1. OPERATE ON LOW SPEED SETTING
1. OPERATE ON LOW SPEED SETTING
1. HEATING CAPACITY DERATED: 240V EQUIPMENT
CONNECTED TO 208V SYSTEM
ASHP-1
ODU
AIR SOURCE HEAT PUMP
OUTDOOR UNIT
28.4 MBH MIN HEATING OUTPUT
AT 1°F, 105°F LGT, 96°F EGT
300 NORDIC ATW-75 ODU 1.
2.
CHARGE W/ R410A REFRIGERANT
PROVIDE W/ LEG KIT
ISSUE DATE
COMM. NUMBER
DESIGNED BY
DRAWN BY
SCALE 0" 1"
Architects Engineers Surveyors 601 College Road Fairbanks AK 99701
907.452.1241 designalaska.com
17 DEC 2020
MASCOT SALOON
HEATING SYSTEM
CONVERSION
402003
AECC511
12/17/2020 9:06:17 AM
ECW
BAB
MECHANICAL
SCHEDULES
M002
AKAF AL
TS
TA E O
49 TH
S
Emily C. Winfield
ME 109592
REGISTERED PROFESSIONAL ENGIN
EE
R
16-DEC-2020
DN
DEMOLISH EXISTING FINNED TUBE AND
CABINET. DEMOLISH ASSOC BRANCH LINES
BACK TO HYDRONIC MAINS & CAP.
EXISTING UNIT HEATER
TO REMAIN, TYP 2
EXISTING RECESSED FINNED
TUBE TO REMAIN
EXISTING FINNED TUBE TO REMAIN, TYP.
EXCEPT WHERE NOTED
DEMOLITION OF EXISTING CAST IRON SECTIONAL BOILER,
FUEL OIL PIPING, BOILER STACK, GLYCOL MAKEUP TANK,
PIPING FROM BOILER TO CONTROL VALVES, AND REPAIR
OF STACK PENETRATION BY NATIONAL PARK SERVICE.
EXISTING HERN/CLIPPER HEATING
SYSTEM TO REMAIN.
MASCOT MECHANICAL 117
EQUIPMENT SIZED FOR FUTURE
CONNECTION OF HERN/CLIPPER
BOARD WALK DEMOLITION BY NATIONAL
PARK SERVICE AS REQUIRED TO INSTALL
REFRIGERANT LINES
COMMERCIAL
MULTI-USE
COMMERCIAL
MULTI-USE
CLIPPER
MECHANICAL
MASCOT
MECHANICAL
STORAGE
OPEN
CLOSET
JANITOR
CLOSET
INTERPRETATION
MEN
106A
WOMEN
106B
STAIR
STORAGE
VESTIBULE
CORRIDOR
CURATORIAL
WORKSHOP
EXISTING FINNED
TUBE TO REMAIN, TYP
EXISTING RECESSED
FINNED TUBE TO REMAIN
EXISTING CABINET UNIT
HEATER TO REMAIN, TYP 2
MASCOT
CUSTODIAL
WH-1
EXISTING WATER
HEATER TO REMAIN
MASCOT SALOON HYDRONIC MAINS SERVING
FIRST FLOOR LOCATED BELOW FLOOR, TYP
HERN/CLIPPER HYDRONIC MAINS SERVING
FIRST FLOOR LOCATED BELOW FLOOR, TYP
WH-2
DEMOLISH EXISTING CW
CONNECTION TO WH-1 AND
WH-2 BACK TO MAIN AND CAP
ISSUE DATE
COMM. NUMBER
DESIGNED BY
DRAWN BY
SCALE 0" 1"
Architects Engineers Surveyors 601 College Road Fairbanks AK 99701
907.452.1241 designalaska.com
17 DEC 2020
MASCOT SALOON
HEATING SYSTEM
CONVERSION
402003
AECC511
12/17/2020 9:06:19 AM
ECW
BAB
FIRST FLOOR
MECHANICAL
DEMOLITION PLAN
M100M100 1/4" = 1'-0"
1 FIRST FLOOR MECHANICAL DEMOLITION PLAN
AKAF AL
TS
TA E O
49 TH
S
Emily C. Winfield
ME 109592
REGISTERED PROFESSIONAL ENGIN
EE
COMMERCIAL
MULTI-USE
COMMERCIAL
MULTI-USE
STORAGE
CLIPPER
MECHANICAL
MASCOT
CUSTODIAL
OPEN
CLOSET
RESTROOM
INTERPRETATION
STORAGE
STAIR
VESTIBULE
CORRIDOR
MEN
106A
WOMEN
106B
CURATORIAL
WORKSHOP
MASCOT
MECHANICAL
EXISTING CABINET UNIT
HEATER TO REMAIN, TYP 2
APPROXIMATE LOCATION OF ASHP-1 ODU ON
CONCRETE HOUSEKEEPING PAD.
ROUTE REFRIGERATION PIPING UNDER BOARD WALK
TO MASCOT MECHANICAL 117. INSTALL IN ACCORDANCE
WITH MANUFACTURER'S INSTRUCTIONS
REPLACE BALANCE COCK
AND INCREASE UNIT HEATER
FLOW RATE TO 2.5 GPM, TYP 2
BOARD WALK REINSTALLATION BY
NATIONAL PARK SERVICE
TO SECOND FLOOR
1" GHR
3/4" GHR
3/4" GHS1" GHS
3/4" GHR
1" GHR
1" GHR
3/4" GHR
3/4" GHS
1" GHS
3/4" GHS&R
1" GHR
1 1/4" GHS
1" GHS1" GHR
3/4" GHR
3/4" GHS
3/4" GHS
3/4" GHR
3/4" GHS
3/4" GHR
EXISTING FINNED
TUBE TO REMAIN
EXISTING CLIPPER MECHANICAL
ROOM. EQUIPMENT FOR FUTURE
DEMOLITION BY NPS
M300
1 1/4" GHR
WH-1
CONTRACTOR TO INSTALL REFRIGERANT
PIPING AND ELECTRICAL ABOVE GRADE
AND BELOW THE BOARDWALK SURFACE IN
SPACE BELOW SURFACE REMOVED BY NPS
M400
EXISTING RECESSED
FINNED TUBE TO REMAIN
EXISTING RECESSED
FINNED TUBE TO REMAIN
EXISTING FINNED
TUBE TO REMAIN
WH-2
EXISTING FINNED
TUBE TO REMAIN
EXISTING FINNED
TUBE TO REMAIN
ISSUE DATE
COMM. NUMBER
DESIGNED BY
DRAWN BY
SCALE 0" 1"
Architects Engineers Surveyors 601 College Road Fairbanks AK 99701
907.452.1241 designalaska.com
17 DEC 2020
MASCOT SALOON
HEATING SYSTEM
CONVERSION
402003
AECC511
12/17/2020 9:06:22 AM
ECW
BAB
FIRST FLOOR
MECHANICAL
PLAN
M200M200 1/4" = 1'-0"
1 FIRST FLOOR MECHANICAL PLAN
SHEET SPECIFIC NOTES
EXISTING FINNED TUBE FOR FUTURE DEMOLITION BY NPS. REMAINS
ACTIVE UNTIL RADIANT TUBING IN THE AREA SERVED IS FUNCTIONAL
AKAF AL
TS
TA E O
49 TH
S
Emily C. Winfield
ME 109592
REGISTERED PROFESSIONAL ENGIN
EE
R
EXISTING PIPING SERVING 2ND FLOOR TO REMAIN2
MULTI-USE
COMMERCIAL
MULTI-USE
STORAGE
CLIPPER
MECHANICAL
MASCOT
CUSTODIAL
INTERPRETATION
STORAGE
STAIR
VESTIBULE
CORRIDOR
MEN
106A
WOMEN
106B
MASCOT
MECHANICAL
PROVIDE
RADIANT ZONE 1B
1 LOOP, AVG LOOP LENGTH 135FT
PROVIDE
RADIANT ZONE 1C
1 LOOP, AVG LOOP LENGTH 100FT
FUTURE RADIANT ZONE 2
3 LOOPS, AVG LOOP LENGTH 235FT
NO WORK REQUIRED
FUTURE RADIANT ZONE 3A
1 LOOP, AVG LOOP LENGTH 200FT
NO WORK REQUIRED
FUTURE RADIANT ZONE 3B
1 LOOP, AVG LOOP LENGTH 165FT
NO WORK REQUIRED
LOOP 1, 0.5 GPM
(2) 16'-3" RAUPLATE
RADIANT PANEL
LOOP 2, 0.5 GPM
(2) 17'-6" RAUPLATE
RADIANT PANEL
LOOP 3, 0.5 GPM
(2) 18'-9" RAUPLATE
RADIANT PANEL
LOOP 4, 0.5 GPM
(2) 20'-0" RAUPLATE
RADIANT PANEL
LOOP 1, 0.5 GPM
(6) 8'-9" RAUPLATE
RADIANT PANEL
LOOP 2, 0.5 GPM
(6) 9'-9" RAUPLATE
RADIANT PANEL
LOOP 8, 0.5 GPM
(2) 10'-0" RAUPLATE
RADIANT PANEL
LOOP 3, 0.5 GPM
(3) 18'-6" RAUPLATE
RADIANT PANEL
LOOP 1, 1.0 GPM
(6) 11'-0" RAUPLATE
RADIANT PANEL
LOOP 1, 1.0 GPM
(8) 7'-6" RAUPLATE
RADIANT PANEL
JOIST, TYP
LOOP 7, 0.5 GPM
(4) 10'-0" RAUPLATE
RADIANT PANEL
LOOP 6, 0.5 GPM
(2) 22'-6" RAUPLATE
RADIANT PANEL
CURATORIAL
WORKSHOP
LOOP 5, 0.5 GPM
(2) 21'-3" RAUPLATE
RADIANT PANEL
PROVIDE
RADIANT ZONE 1A
5 LOOPS, AVG LOOP LENGTH 175FT
ISSUE DATE
COMM. NUMBER
DESIGNED BY
DRAWN BY
SCALE 0" 1"
Architects Engineers Surveyors 601 College Road Fairbanks AK 99701
907.452.1241 designalaska.com
17 DEC 2020
MASCOT SALOON
HEATING SYSTEM
CONVERSION
402003
AECC511
12/17/2020 9:06:23 AM
ECW
BAB
FIRST FLOOR
RADIANT ZONING
PLAN
M201M201 1/4" = 1'-0"
1 FIRST FLOOR RADIANT ZONING PLAN
AKAF AL
TS
TA E O
49 TH
S
Emily C. Winfield
ME 109592
REGISTERED PROFESSIONAL ENGIN
EE
R
16-DEC-2020
GENERAL SHEET NOTES
1. CONTRACTOR TO PROVIDE ALL MATERIAL FOR RADIANT TUBING INSTALLATION. NPS WILL
PROVIDE ALL LABOR FOR RADIANT TUBING INSTALLATION.
MULTI-USE
COMMERCIAL
MULTI-USE
STORAGE
CLIPPER
MECHANICAL
MASCOT
CUSTODIAL
RESTROOM
INTERPRETATION
VESTIBULE
104 CORRIDOR
MEN
106A
WOMEN
106B
MASCOT
MECHANICAL
UTILITY
CORRIDOR
106C
HEAT TUBE
CROSSING, TYP
CURATORIAL
WORKSHOP
M400
ISSUE DATE
COMM. NUMBER
DESIGNED BY
DRAWN BY
SCALE 0" 1"
Architects Engineers Surveyors 601 College Road Fairbanks AK 99701
907.452.1241 designalaska.com
17 DEC 2020
MASCOT SALOON
HEATING SYSTEM
CONVERSION
402003
AECC511
12/17/2020 9:06:24 AM
ECW
BAB
FIRST FLOOR
RADIANT TUBING
LAYOUT PLAN
M202M202 1/4" = 1'-0"
1 FIRST FLOOR RADIANT TUBING LAYOUT PLAN
GENERAL SHEET NOTES
1.
2.
3.
4.
PROVIDE ADEQUATE SUPPORT TO RADIANT TUBING TO ELIMINATE ALL DIPS OR SAGS TO
AVOID AIR LOCK WHEN FILLING THE SYSTEM.
ROUTE TUBING LOOPS BACK TO MECHANICAL ROOM AND PENETRATE FLOOR FRAMING
PER 5/M400.
ALL RADIANT TUBING IS 1/2" PEX-A.
REMOVE AND REPLACE EXISTING BATT INSULATION IN JOIST BAYS TO ACCOMMODATE
INSTALLATION.
AKAF AL
TS
TA E O
49 TH
S
Emily C. Winfield
ME 109592
REGISTERED PROFESSIONAL ENGIN
EE
BT-1
BT-2
ASHP-1
GMT-1
P-4
WSHP-1
P-1A/B STACKED ON
WALL W/ ET-1 BELOW
EXISTING ELECTRICAL
PANEL, TO REMAIN
MASCOT
MECHANICAL
EUH-1
WH-1
BTU-1
P-2 & P-3 STACKED
ON WALL
NEW ELECTRICAL PANEL
ELECTRICAL
CLEARANCE, TYP
WH-2 ISSUE DATE
COMM. NUMBER
DESIGNED BY
DRAWN BY
SCALE 0" 1"
Architects Engineers Surveyors 601 College Road Fairbanks AK 99701
907.452.1241 designalaska.com
17 DEC 2020
MASCOT SALOON
HEATING SYSTEM
CONVERSION
402003
AECC511
12/17/2020 9:06:26 AM
ECW
BAB
ENLARGED
MECHANICAL
ROOM PLAN
M300M300 1/2" = 1'-0"
1 ENLARGED MECHANICAL ROOM PLAN
AKAF AL
TS
TA E O
49 TH
S
Emily C. Winfield
ME 109592
REGISTERED PROFESSIONAL ENGIN
EE
SEISMIC LAG SCREW SCHEDULE
EQUIPMENT
SYMBOL
LAG SCREW OR
ANCHOR BOLT
DIAMETER (IN)
NUMBER OF
BOLTS PER SIDE
MINIMUM
EMBEDMENT (IN)
MINIMUM
HOUSEKEEPING PAD
THICKNESS (IN)
MINIMUM EDGE
DISTANCE (IN)
MINIMUM SPACE
BETWEEN ANCHORS(IN)
WSHP-1
ASHP-1 ODU
2 3 3.25 4 4
2 4
REMARKS
1.
2.
WOOD HOUSEKEEPING PAD
A309 LAG SCREWS
1.
2.
3.
CONCRETE HOUSEKEEPING PAD
HILTI KWIK BOLT TZ SS
TORQUE TO 25 FT*LBS
3/8
3/8
3 3.25 4
ASHP-1 IDU 2 3 3.25 4 4 1.
2.
WOOD HOUSEKEEPING PAD
A309 LAG SCREWS
3/8
CENTER NOTCH
D
D/6 MAX
L
L/3 L/3 L/3
NOTCHES PROHIBITED IN MIDDLE
THIRD OF MEMBER SPAN
D/3 MAX
D/6 MAX
D/4 MAX
END NOTCH
D/3 Ø MAX
NOTCHES PROHIBITED
ON BOTTOM OF MEMBER
HOLES PROHIBITED WITHIN 2" OF THE
TOP OR BOTTOM OF THE MEMBER
AND ANY OTHER HOLE OR NOTCH
SOLID LUMBER BEAM OR JOIST
DETAIL SPECIFIC NOTES
HOUSEKEEPING PAD PLAN DIMENSIONS ARE DEPENDENT ON EQUIPMENT.
6X6-W1.4XW1.4 WELDED WIRE REINFORCEMENT CENTERED IN PAD.
#3 DOWELS WITH 6" HORIZONTAL LEGS AT 24" ON CENTER. HORIZONTAL LEGS TO
BE AT SAME ELEVATION AS WELDED WIRE REINFORCEMENT. DRILL AND EPOXY
WITH HILTI-HY 200 EPOXY OR APPROVED EQUAL WITH 2-1/2" EMBEDMENT.
CHAMFER EXPOSED EDGES 3/4".
BASE SLAB.
3" EDGE DISTANCE FOR DOWELS.
6" (ACTUAL) PAD THICKNESS UNLESS NOTED OTHERWISE.
PLAN
SECTION A-A
24" TYP
A A
6 2
HOUSEKEEPING PAD PLAN DIMENSIONS ARE DEPENDENT ON EQUIPMENT.
SEE MECHANICAL ANCHOR BOLT SCHEDULE FOR MINIMUM EDGE
DISTANCE REQUIREMENTS.
3 LAYERS OF 1 1/8" PLYWOOD. ATTACH BOTTOM LAYER AND SUBSEQUENT
LAYERS TO LAYER BELOW W/ 2-1/2" WOOD SCREWS AT MAX 12" OC EACH
WAY BUT NOT LESS THAN THREE IN EACH DIRECTION
EXISTING FLOOR FRAMING PER PLAN
DETAIL SPECIFIC NOTES
ASHP-1 ODU
MASCOT
MECHANICAL
ASHP-1 IDU
SEAL PENETRATIONS
WATER TIGHT
3/4" RS
3/8" RR
BT-1
WSHP-1
BT-2
PLYWOOD HOUSEKEEPING
PAD, TYP
EXISTING
1-1/4" CW
GMT-1
2" GHR
2" GHS
P-4
P-2
P-3
16 GPM
36 GPM
WH-1
MASCOT
CUSTODIAL
WH-2
CLIPPER
MECHANICAL
3/4" HW
FROM BT-2
36 GPM
2" GHR
2" GHS
1-1/2" GHS
3/4" GHS
P-1B
P-1A
32 GPM
AS-1
3/4" GHS TO
GMT-1 AND ET-1
2" GHR
ET-1
FUTURE TO WH-2
TO WH-1
SUPPLY
RETURN
RADIANT
MANIFOLD 1
TYP
TYP
SUPPLY
RETURN
RADIANT
MANIFOLD 2
SUPPLY
RETURN
RADIANT
MANIFOLD 3
REHAU PRO BALANCE
MANIFOLD, TYP
1-1/4" HW
FROM BT-2
M400
M400
CONCRETE HOUSEKEEPING PAD
1-1/2" GHR
3/4" GHS TO LOW
TEMP SYSTEM
2" GHR
2" GHS, TYP 2
3/4" GHS&R
3/4" GHS&R
1-1/4" GHR
1" GHS&R
1-1/4" GHS
MIN 2'-0"
3/4" HW
1-1/4" HW
1-1/4" HW
3/4" HW
1-1/4" HW
1-1/4" CW
PLAN
ELEVATION
1-1/2" 16 GAUGE STRAP, TYP.
INSTALL STRAPS AT ONE THIRD
EQUIPMENT HEIGHT
INCRIMENTS, UNLESS HEIGHT
ADJUSTMENT IS REQUIRED TO
ACCOMMODATE TANK
MOUNTED ACCESSORIES
1/2" FASTENERS,
TYP
CHANNEL
STRUT, TYP
SECURE CHANNEL
STRUT TO ATTACH TO
MIN OF 2 WALL STUDS
ISSUE DATE
COMM. NUMBER
DESIGNED BY
DRAWN BY
SCALE 0" 1"
Architects Engineers Surveyors 601 College Road Fairbanks AK 99701
907.452.1241 designalaska.com
17 DEC 2020
MASCOT SALOON
HEATING SYSTEM
CONVERSION
402003
AECC511
12/17/2020 9:06:27 AM
ECW
BAB
MECHANICAL
DETAILS
M400
SHEET SPECIFIC NOTES
LINE SIZE PRV DISCHARGE SET TO 30 PSI, EXTEND PRV DISCHARGE TO 6" ABOVE FLOOR1
LINE SIZE AS-1 DISCHARGE, SLOPE PIPE TO GMT-12
TAPS FOR CONNECTION TO BTU-13
EXISTING HOT WATER SUPPLY TO FIXTURES4
ROUTE REFRIGERANT PIPING UNDER BOARDWALK, THROUGH FOUNDATION WALL AND
UP THROUGH FLOOR INTO MASCOT MECHANICAL 117
GENERAL SHEET NOTES
1. SEISMICALLY BRACE BT-1, BT-2, ET-1, AND GMT-1 PER 5/M400
RADIANT TUBING INSTALLED BY NPS PRIOR TO CONTRACTOR WORK. CONTRACTOR TO
CONNECT RADIANT TUBING TO MANIFOLD PROVIDED BY CONTRACTOR
CONNECT TO EXISTING GHS&R MAINS SERVING EXISTING TERMINAL UNITS, MATCH
EXISTING PIPE SIZE. PROVIDE NEW CONTROL VALVES, TYP 5
PROVIDE STUB AND CAP FOR FUTURE CONNECTION TO EXISTING HERN/CLIPPER
FIRST FLOOR GHS&R MAIN. MATCH EXISTING GHS&R MAIN PIPE SIZE.
M400 NO SCALE
1 ALLOWABLE FLOOR FRAMING PENETRATION DETAIL
NC VALVE TO BYPASS DHW COIL IN THE EVENT OF HEAT PUMP FAILURE9
AKAF AL
TS
TA E O
49 TH
S
Emily C. Winfield
ME 109592
REGISTERED PROFESSIONAL ENGIN
EE
R
16-DEC-2020
MAKE LOW TEMPERATURE SIDE CONNECTION WITH ET-1/GMT-1 MIN 2'-0" LOWER THAN
HIGH TEMPERATURE CONNECTION TO PREVENT BUOYANT MIXING OF THE SYSTEMS
M400 NO SCALE
3 SEISMIC - HOUSKEEPING PAD DETAIL
M400 NO SCALE
4 TYPICAL HOUSEKEEPING PAD - WOOD
M400 NO SCALE
2 CASCADING HEAT PUMP DIAGRAM
M400 NO SCALE
5 SEISMIC - WALL MOUNTED TANK
RADIANT TUBING INSTALLED BY NPS IN FUTURE PROJECT. MANIFOLD PROVIDED BY
CONTRACTOR
ELECTRICAL SYMBOL LEGEND
MOTOR (HP, VOLTAGE & PHASE NOTED ON DRAWING)
EQUIPMENT CONNECTION
PANELBOARD
POWER SYMBOLS
M
ANNOTATION SYMBOLS
L1-12
L1-12
AHU-1
PANEL & CIRCUIT IDENTIFICATION
PANEL & CIRCUIT IDENTIFICATION
B LIGHTING FIXTURE TAG
'L1' DENOTES PANEL NAME, '24' DENOTES CIRCUIT NUMBERL1-24
LIGHTING FIXTURE TAG (SEE LIGHTING FIXTURE SCHEDULE)B2
SPECIFIC NOTE KEY
(REFERENCE # UNDER 'SPECIFC NOTES' ON EACH SHEET)
a
SWITCH IDENTIFICATION TAG
a SWITCH IDENTIFIER
EQUIPMENT IDENTIFIER, SEE MECHANICAL ELECTRICAL
SCHEDULE
ABBREVIATIONS
ABOVE FINISHED FLOOR
EXISTING
UNLESS OTHERWISE NOTED
AFF
(E)
UON
SERVICE SIZE
12 MONTH MAXIMUM DEMAND READING (02/2019-12/2020)
ASSUMED POWER FACTOR
MAXIMUM DEMAND
x125% (BASELINE PER NEC 220.87)
ADDED LOAD
NEW 400A PANEL
SERVICE VOLTAGE 208Y/120
4.843
0.8
6.054
7.567
V
A kW kVA kVA
UTILITY AP&T
76.818 kVA
TOTAL CALCULATED LOAD (BASELINE + ADDED) 84.385 kVA
TOTAL CALCULATED CURRENT 234.23 A
SERVICE SIZE SPARE CAPACITY 41 %
SERVICE LOAD CALCULATION
75 KVA TRANSFORMER (1.6% Z)
500 KCMIL CABLE (CU), 60 FEET
400 A CTS, 400 A MAIN DISCONNECT
ASYMETRIC MOTOR CONTRIBUTION, TOTAL RLA = 78.43 A
SYMMETRIC SHORT CIRCUIT CURRENT AVAILABLE AT PANEL 'M'
SOURCE
DESCRIPTION
SHORT CIRCUIT CALCULATION
SHORT CIRCUIT
AMPS L-L
12,965
10,041
9,583
500 KCMIL CABLE (CU), 65 FEET 7,768
8,160
8,160
SEE ELECTRICAL ONE-LINE DIAGRAM ON E300
ISSUE DATE
COMM. NUMBER
DESIGNED BY
DRAWN BY
SCALE 0" 1"
Architects Engineers Surveyors 601 College Road Fairbanks AK 99701
907.452.1241 designalaska.com
17 DEC 2020
MASCOT SALOON
HEATING SYSTEM
CONVERSION
402003
AECC511
12/17/2020 4:09:12 PM
RSG
JCC
ELECTRICAL
LEGEND AND
SCHEDULES
E001
GENERAL SHEET NOTES
1.
2.
3.
4.
5.
SEE MECHANICAL SHEETS FOR MORE DETAILS REGARDING MOTORS AND EQUIPMENT. MECHANICAL EQUIPMENT CONNECTIONS AND THEIR ASSOCIATED DISCONNECT/CONTROLLER LOCATIONS SHOWN ARE APPROXIMATE ONLY. COORDINATE WITH ACTUAL MECHANICAL EQUIPMENT PROVIDED DURING THE SUBMITTAL PROCESS AND ADJUST DISCONNECT CONTROL TYPE, THERMAL OVERLOADS, CONDUCTORS, AND CONDUIT BEFORE SUBMITTAL APPROVAL. COORDINATE WITH MECHANICAL ON FINAL EQUIPMENT
CONFIGURATION AND LOCATION.
IN GENERAL, CIRCUITING FOR OUTLETS IS NOT SHOWN, BUT THE INTENDED CIRCUIT TO BE CONNECTED
TO IS SHOWN. CIRCUITING SHALL BE PROVIDED PER CONTRACTOR MEANS AND METHODS.
WHERE NOTED, ALL MEASUREMENTS SHALL MEAN TO CENTER OF DEVICE/EQUIPMENT. EX. +4'-0" AFF UON
MEANS THE CENTER OF THE OUTLET IS 4'-0" ABOVE THE FIXED FLOOR.
PROVIDE A SEPARATE GROUNDED CONDUCTOR (NEUTRAL) FOR EACH BRANCH CIRCUIT. SHARED
NEUTRALS ARE NOT PERMITTED.
INSTALL AN EQUIPMENT GROUNDING CONDUCTOR, SIZED IN ACCORDANCE WITH THE NEC FOR ALL
FEEDER AND BRANCH CIRCUIT CONDUITS.
ELECTRIC MOTOR AND EQUIPMENT SCHEDULE
TAG DESCRIPTION RATING PHASE FLA MOPD
CONTROLLER
MOTOR DISCONNECT
MINIMUM CONDUCTOR AND
RACEWAY
PANEL -
CIRCUIT COMMENTS
TYPE DISCONNECT
120 V GMT-1 GLYCOL MAKEUP TANK 50 W 1 0.4 A 15 A INTEGRAL GFCI 5-20R GFCI 5-20R (2) #12 AWG, #12 GND, 1/2" C M - 37
208 V
(E) WH-1 ELECTRIC WATER HEATER 3 KVA 1 16.2 A 30 A A - 35,37 EXISTING EQUIPMENT RATED FOR 240V CONNECTED TO
208V (208V RATING PROVIDED)
(E) WH-2 ELECTRIC WATER HEATER 6 KW 1 28.9 A 40 A B-1 - 16,18 EXISTING EQUIPMENT RATED FOR 240V CONNECTED TO
208V (208V RATING PROVIDED)
ASHP-1 IDU AIR SOURCE HEAT PUMP - INDOOR
UNIT
9 KVA 3 25.4 A 40 A INTEGRAL CIRCUIT BREAKER CIRCUIT BREAKER (3) #8 AWG, #10 GND, 3/4" C M - 22,24,26
ASHP-1 ODU AIR SOURCE HEAT PUMP - OUTDOOR
UNIT
1 0.0 A 0 A OUTDOOR UNIT SUB-FED FROM INDOOR UNIT
PROVIDE INTERCONNECTING POWER/SIGNAL CABLES AND
CONDUIT PER MANUFACTURER'S INSTRUCTIONS
BT-1 BUFFER TANK/ELECTRIC BOILER 11 KW 1 54.6 A 70 A INTEGRAL CIRCUIT BREAKER CIRCUIT BREAKER (2) #4 AWG, #8 GND,3/4" C M - 13,15 EQUIPMENT RATED FOR 240V CONNECTED TO 208V (208V
RATING PROVIDED)
EUH-1 ELECTRIC UNIT HEATER 2 KW 1 11.0 A 20 A T-STAT T-STAT OFF CIRCUIT BREAKER (2) #12 AWG, #12 GND, 1/2" C M - 8,10 P-1A GLYCOL HEATING PUMP 3/4 HP 1 7.6 A 20 A INTEGRAL CIRCUIT BREAKER CIRCUIT BREAKER (2) #12 AWG, #12 GND, 1/2" C M - 2,4 P-1B GLYCOL HEATING PUMP 3/4 HP 1 7.6 A 20 A INTEGRAL CIRCUIT BREAKER CIRCUIT BREAKER (2) #12 AWG, #12 GND, 1/2" C M - 7,9 REDUNDANT PUMP P-2 WSHP CIRCULATION PUMP 170 W 1 0.8 A 15 A INTEGRAL CIRCUIT BREAKER CIRCUIT BREAKER (2) #12 AWG, #12 GND, 1/2" C M - 14,16 P-3 WSHP CIRCULATION PUMP 170 W 1 0.8 A 15 A INTEGRAL CIRCUIT BREAKER CIRCUIT BREAKER (2) #12 AWG, #12 GND, 1/2" C M - 1,3 P-4 ASHP CIRCULATION PUMP 170 W 1 0.8 A 15 A INTEGRAL CIRCUIT BREAKER CIRCUIT BREAKER (2) #12 AWG, #12 GND, 1/2" C M - 31,33 WSHP-1 WATER SOURCE HEAT PUMP 15 KVA 3 41.6 A 60 A INTEGRAL CIRCUIT BREAKER CIRCUIT BREAKER (3) #6 AWG, #10 GND, 3/4" C M - 21,23,25
240 V BT-2 BUFFER TANK/ELECTRIC BOILER 29 KW 1 120.0 A 175 A INTEGRAL CIRCUIT BREAKER CIRCUIT BREAKER (2) #1/0 AWG, #6 GND,1 1/4" C M - 40,42 EQUIPMENT RATED FOR 240V CONNECTED TO 208V
THROUGH BUCK-BOOST TRANSFORMER. (240V RATING
PROVIDED)
(1) PROVIDE SUB-FEED BREAKER FOR THIS CIRCUIT
NOTES:
CH CHILLER [NEC 2017, ARTICLE 440.33] 0 VA 0.00% 0 VA
H HBO [NEC 2017, ARTICLE 220.14(A)] 0 VA 0.00% 0 VA
A APPLIANCE [NEC 2017, ARTICLE 220.56] 0 VA 0.00% 0 VA
M MOTOR [NEC 2017, ARTICLE 430.24] 29,195 VA 112.83% 32,942 VA
R RECEPTACLES [NEC 2017, ARTICLE 220.44] 10,980 VA 95.54% 10,490 VA
L LIGHTING [NEC 2017, ARTICLE 215.2(A)(1)] 8,786 VA 125.00% 10,983 VA DEMAND LOAD: 106,799 VA 296 A
E NON-CONTINUOUS [NEC 2017, ARTICLE 215.2(A)(1)] 52,385 VA 100.00% 52,385 VA CONNECTED LOAD: 101,346 VA 281 A
C CONTINUOUS [NEC 2017, ARTICLE 215.2(A)(1)] 0 VA 0.00% 0 VA LOAD AMPS
LOAD CLASSIFICATION CONNECTED LOAD DEMAND FACTOR DEMAND LOAD PANEL TOTALS
TOTAL AMPS: 263 A 259 A 323 A
TOTAL LOAD: 31,518 VA 31,104 VA 38,724 VA
41 14,400 42
39 14,400
2 175 E (1) RM 117 - BT-2 (29 KW)
37 RM 117 - GMT-1 M 15 1 50 38
35 36
33 84 34
RM 117 - P-4 (170 W) M 15 2
84 32
29 30
27 28
25 4,996 3,050 26
23 4,996 3,050 24
RM 117 - WSHP-1 (15 KVA) M 60 3
4,996 3,050
3 40 M RM 117 - ASHP-1 (9 KVA)
19 SPACE FOR ADJ PANEL 'A' BREAKER -- -- -- 0 14,764 20
17 SPACE FOR ADJ PANEL 'A' BREAKER -- -- -- 0 16,278
2 150
L; M; R;
E PANEL 'A' - RM 117
15 5,680 84 16
RM 117 - BT-1 (11 KW) E 70 2
5,680 84
2 15 M RM 117 - P-2 (170 W)
11 12
9 790 1,144 10
RM 117 - P-1B (3/4 HP) M 20 2
790 1,144
2 20 E RM 117 - EUH-1 (2 KW)
5 6
3 84 790 4
RM 117 - P-3 (170 W) M 15 2
84 790
2 20 M RM 117 - P-1A (3/4 HP)
CKT CIRCUIT DESCRIPTION LOAD
CLASS TRIP P A B C P TRIP LOAD
CLASS CIRCUIT DESCRIPTION CKT
ENCLOSURE: TYPE 1 PANELBOARD FEEDER CB RATING: 400 A
MOUNTING: SURFACE WIRES: 4 MAINS RATING: 400 A
SUPPLY FROM: PHASES: 3 MAINS TYPE: MLO
LOCATION: MASCOT MECHANICAL 117 VOLTS: 208Y/120V A.I.C. RATING: 10,000
PANEL: M
AKAF AL
TS
TA E O
49 TH
S
REGISTERED PROFESSIONAL ENGIN
EE
RRobert S. Gras
No. EE 7352
17-DEC-2020 - -
MASCOT SALOON
BOAS TAILOR &
FURRIER
VERBAUWHEDE'S CIGAR STORE
& CONFECTIONERY
NEW PAD MOUNTED 75 KVA
TRANSFORMER BY UTILITY
NEW METER, CT ENCLOSURE,
AND 400A SERVICE DISCONNECT
EXISTING METER
PACK ENCLOSURE
(E) PNL 'A'
PNL 'M'
DEMOLISH EXISTING PNL 'A'
FEEDER. METER AND
SERVICE DISCONNECT
EXISTING TO REMAIN, RE-
LABEL AS SPARE.
(4) 500 KCMIL, #3 GND, 3" C.
(4) 500 KCMIL, 3" C.
ISSUE DATE
COMM. NUMBER
DESIGNED BY
DRAWN BY
SCALE 0" 1"
Architects Engineers Surveyors 601 College Road Fairbanks AK 99701
907.452.1241 designalaska.com
17 DEC 2020
MASCOT SALOON
HEATING SYSTEM
CONVERSION
402003
AECC511
12/17/2020 4:09:13 PM
RSG
JCC
ELECTRICAL SITE
PLAN
E100
1" = 10'-0"E100
1 ELECTRICAL SITE PLAN
AKAF AL
TS
TA E O
49 TH
S
REGISTERED PROFESSIONAL ENGIN
EE
RRobert S. Gras
17-DEC-2020
M
M
M
M
M
MM
M
INTERPRETATION
COMMERCIAL
MULTI-USE
COMMERCIAL
MULTI-USE
VESTIBULE
STORAGE
STAIR
MASCOT
CUSTODIAL
MEN
106A
CORRIDOR
WOMEN
106B
CURATORIAL
WORKSHOP
MASCOT
MECHANICAL
CLIPPER
MECHANICAL
STORAGE
OPEN
CLOSET
JANITOR
CLOSET
STORAGE
109B
STAIR
109A
P N
L M
M-37
M-40,42
B-1-16,18
M-2,4
M-7,9
M-21,23,25
M-8,10 M-14,16
M-1,3
M-13,15
M-31,33
M-22,24,26
GMT-1
BT-2
(E) WH-2
P-1A
P-1B
WSHP-1
EUH-1
P-2
P-3
BT-1
P-4
ASHP-1 IDU
(E) WH-1
A-35,37
(E
P N
L A
(E) PNL H
(E) PNL C
2ND FLOOR
ASHP-1 ODU
(E
P N
L B
-1
ISSUE DATE
COMM. NUMBER
DESIGNED BY
DRAWN BY
SCALE 0" 1"
Architects Engineers Surveyors 601 College Road Fairbanks AK 99701
907.452.1241 designalaska.com
17 DEC 2020
MASCOT SALOON
HEATING SYSTEM
CONVERSION
402003
AECC511
12/17/2020 4:09:14 PM
RSG
JCC
FIRST FLOOR
ELECTRICAL PLAN
E200 1/4" = 1'-0"E200
1 FIRST FLOOR ELECTRICAL PLAN
SPECIFIC SHEET NOTES
1 LOW-VOLTAGE DRY-TYPE BUCK-BOOST TRANSFORMER. 5 KVA
TRANSFORMER TO BOOST 208V INPUT TO 240V, 32.5 KVA
OUTPUT. FOR INLINE CONNECTION TO FEED BT-2. CONNECT
TO PANEL M VIA (3) #2/0 AWG, #6 GND, 2"C. BASIS OF DESIGN:
EATON S10N06A05N.
2 RELOCATE EXISTING TELECOMMUNICATIONS EQUIPMENT AS
REQUIRED TO LOCATE NEW PANEL AND MAINTAIN NEC
WORKING CLEARANCE.
AKAF AL
TS
TA E O
49 TH
S
REGISTERED PROFESSIONAL ENGIN
EE
RRobert S. Gras
400/3
NEMA 3R FUSED
DISCONNECT400AF
208Y/120 V
4W, 3PH
UNDERGROUND
SECONDARY
FROM UTILITY
kwh
225/2
EXISTING METER/MAIN
DISCONNECT NEMA 3R
ENCLOSURE
kwh
150/2 kwh
150/2 kwh
50/2 kwh
150/2 kwh
EXISTING TO REMAIN
(E) MASCOT SALOON
SERVICE DISCONNECT
EXISTING PANEL 'A' HAS 10K AIC
RATING. VERIFY THAT EXISTING
RATING WILL BE COMPATIBLE WITH
NEW SERVICE ARRANGEMENT
VERIFY NEUTRAL/GROUND
BONDING IN EXISTING PANEL 'A'
XX,XXX = AVAILABLE SYMMETRICAL THREE PHASE FAULT CURRENT UNDER THE
FOLLOWING ASSUMPTIONS:
INFINITE BUS ON MV PRIMARY SIDE
1.6%Z SERVICE TRANSFORMER
60 LINEAR FEET OF SECONDARY
NEW PAD MOUNTED
75 kVA LOOP FEED TRANSFORMER
12,470GRDY/7,200 V. WYE-PRI
208Y/120 V. WYE-SEC
PADS/VAULTS
PER UTILITIES
REQUIREMENTS
GROUND SERVICE
TRANSFORMERS PER
UTILITIES STANDARDS.
PRIMARY FROM
UTILITY
400/3
GROUND ELECTRODE
SYSTEM PER UTILITIES
STANDARDS
400 AMP MAIN DISCONNECT
NEMA 3R ENCLOSURE
kwh
NEMA 3R CT
ENCLOSURE &
METER
9,583
8,160 <10,000 <10,000<10,000RM 117
(E) PANEL 'C'
100A MLO
120/208 V
1 PH, 3 W
(E) PANEL 'H'
100A MLO
120/208 V
1 PH, 3 W
PANEL 'M'
400A MLO
208Y/120 V
3 PH, 4 W
(E) PANEL
'A' 150A MLO
120/208 V
1 PH, 3 W
(E) VERBAUWHEDE
BLDG. FRONT
PANEL 'E'
(E) VERBAUWHEDE
BLDG.REAR
PANEL 'G'
(E) VALVE
PIT PANEL 'F'
(E) BOAS
BLDG. 1ST
FLOOR PANEL
'D-1'
(E) SUB
PANEL 2ND
FLOOR
PANEL 'D-2'
(E) PACIFIC
CLIPPER 1ST FLOOR
PANEL 'B-1'
(E) SUB
PANEL 2ND
FLOOR PANEL
'B-2'
RM 117
(4) 500 KCMIL,
#3 GND,
3" C.
(3) 1/0,
(1) #6 GND,
1 1/2" C.
EXISTING TO
REMAIN
150/2
100/2
100/2150/2
100/2 150/2
RM 211 RM 105
(4) 500 KCMIL,
3" C.
ISSUE DATE
COMM. NUMBER
DESIGNED BY
DRAWN BY
SCALE 0" 1"
Architects Engineers Surveyors 601 College Road Fairbanks AK 99701
907.452.1241 designalaska.com
17 DEC 2020
MASCOT SALOON
HEATING SYSTEM
CONVERSION
402003
AECC511
12/17/2020 4:09:15 PM
RSG
JCC
POWER RISER
E300
NOT TO SCALEE300
1 ELECTRICAL ONE-LINE DIAGRAM
AKAF AL
TS
TA E O
49 TH
S
REGISTERED PROFESSIONAL ENGIN
EE
RRobert S. Gras
| G001 |
| M001 |
| M002 |
| M100 |
| M200 |
| M201 |
| M202 |
| M300 |
| M400 |
| E001 |
| E100 |
| E200 |