This solicitation is for the furnishing and installation of a brand specific heat pump system in a historic building located in Skagway, Alaska. The National Park Service Alaska Region is seeking the supply and installation of a new heating system, including an air source heat pump indoor and outdoor unit, buffer tank, circulation pumps, and associated piping and controls. Bids are due by February 15, 2022, with work to be completed by June 30, 2022. The contractor will be responsible for all labor, equipment, and materials required to remove the existing system and install the new heat pumps and related components.

View the file

Other files

Show all 18

On GovTribe

Work with this file

  • Download the original file
  • Contacts named in this file
  • Similar government files
  • Ask GovTribe AI about this file

Text version

1 View Name 1/8" = 1'-0"A101

Room name

GENERAL SYMBOLS

NAME

NUMBER

SHEET LOCATION

SCALE

TRUE NORTH

GRID LINE

ROOM NAME

ROOM NUMBER

PLAN NORTH

REVISION

SEE DISCIPLINES FOR SPECIFIC SYMBOLS

PROJECT TEAM

OWNERS REPRESENTATIVE

NATIONAL PARK SERVICE

POINT OF CONTACT: CORY THOLE

P.O. BOX 517, SKAGWAY, AK, 99840

907 983-9263

CORY_THOLE@NPS.GOV

DESIGNERS REPRESENTATIVE

DESIGN ALASKA

POINT OF CONTACT: EMILY WINFIELD

601 COLLEGE ROAD, FAIRBANKS, AK 99701

907 452-1241

EMILYW@DESIGNALASKA.COM

VICINITY MAP

PROJECT

LOCATION

ALASKA MAP

PACIFIC OCEAN

ARCTIC OCEAN

BERING SEA

KODIAK

ARCTIC CIRCLE

SEWARD

SITKA

JUNEAU

HAINES

WHITEHORSE YT

DAWSON YT

HAINES

JCT

HOMER

ANCHORAGE

EAGLE

CORDOVA

VALDEZ

GLENNALLEN

TOK

NORTH

POLE

FAIRBANKS

NENANA

TANANA

CIRCLE

NOME

KOTZEBUE

UTQIAGVIK

(BARROW)

PRUDHOE BAY

U N

IT

E

D S

T A

T E

S

R U

S S

IA U

N

IT

E

D S

T A

T E

S C

A N

A D

A PROJECT

LOCATION

SKAGWAY

ISSUE DATE

COMM. NUMBER

DESIGNED BY

DRAWN BY

SCALE 0" 1"

Architects Engineers Surveyors 601 College Road Fairbanks AK 99701

907.452.1241 designalaska.com

17 DEC 2020

MASCOT SALOON

HEATING SYSTEM

CONVERSION

402003

AECC511

12/15/2020 8:45:15 AM

ECW

ECW

GENERAL

INFORMATION

G001

MASCOT SALOON HEATING SYSTEM CONVERSION

SKAGWAY, ALASKA

NATIONAL PARK SERVICE

GENERAL

G001 GENERAL INFORMATION

MECHANICAL

M001 MECHANICAL ABBREVIATIONS, AND LEGENDS - ALL OPTIONS

M002 MECHANICAL SCHEDULES

M100 FIRST FLOOR MECHANICAL DEMOLITION PLAN

M200 FIRST FLOOR MECHANICAL PLAN

M201 FIRST FLOOR RADIANT ZONING PLAN

M202 FIRST FLOOR RADIANT TUBING LAYOUT PLAN

M300 ENLARGED MECHANICAL ROOM PLAN

M400 MECHANICAL DETAILS

ELECTRICAL

E001 ELECTRICAL LEGEND AND SCHEDULES

E100 ELECTRICAL SITE PLAN

E200 FIRST FLOOR ELECTRICAL PLAN

E300 POWER RISER

ABBREVIATION FULL NAME

W WASTE

VENTV

CW COLD WATER

HW HOT WATER

RECIRCULATED HOT WATERRHW

GHS GLYCOL HEATING SUPPLY

GHR GLYCOL HEATING RETURN

EXISTING

EXISTING TO BE REMOVED

MECHANICAL - LINETYPES

RS REFRIGERANT SUPPLY

RR REFRIGERANT RETURN

PRESSURE REDUCING VALVE

DRAIN VALVE

PRESSURE RELIEF VALVE

UNION

HOSE BIBB

2-WAY CONTROL VALVE

THERMOMETER

PRESSURE GAUGE

MECHANICAL SYMBOLS

PIPE CONNECTION

PIPE ELBOW TURNED DOWN

PIPE ELBOW TURNED UP

PIPE TEE DOWN

PIPE FLOW ARROW

BALANCING COCK

CHECK VALVE

NON-SLAM CHECK VALVE

ISOLATION VALVE

AIR VENT

CONNECTION TO EXISTING

PRESSURE & TEMPERATURE TEST PORT

NS

ISSUE DATE

COMM. NUMBER

DESIGNED BY

DRAWN BY

SCALE 0" 1"

Architects Engineers Surveyors 601 College Road Fairbanks AK 99701

907.452.1241 designalaska.com

17 DEC 2020

MASCOT SALOON

HEATING SYSTEM

CONVERSION

402003

AECC511

12/17/2020 9:06:16 AM

ECW

BAB

MECHANICAL

ABBREVIATIONS,

AND LEGENDS -

ALL OPTIONS

M001

BALANCE COCK SCHEDULE

DIA (IN)

MINIMUM

GPM

1/2 1 3/4 3 1 4

1-1/4 10 1-1/2 15

2 34 2-1/2 55

3 92 4 180 6 440

PIPE SCHEDULE

DIA (IN)

MAX DESIGN

GPM

3/4 3 1 7

1-1/4 13 1-1/2 21

2 46 2-1/2 82

3 132 4 280 6 800

MECHANICAL ABBREVIATIONS

KEY NAME MECHANICAL ABBREVIATIONS

MECH MECHANICAL

MIN MINIMUM

MTR MOTOR

NC NORMALLY CLOSED

NG NATURAL GAS

NIC NOT IN CONTRACT

NO NORMALLY OPEN

NPS NATIONAL PARK SERVICE

NPSH NET PUMP SUCTION HEAD

NTS NOT TO SCALE

OAT OUTSIDE AIR TEMPERATURE

OBVD OPPOSED BLADE VOLUME DAMPER

OC ON CENTER

OD OUTSIDE DIAMETER

ODU OUTDOOR UNIT

OFCI OWNER FURNISHED, CONTRACTOR INSTALLED

OFOI OWNER FURNISHED, OWNER INSTALLED

ORD OVERFLOW ROOF DRAIN

ORL OVERFLOW RAIN LEADER

OSA OUTSIDE AIR

P&T PRESSURE AND TEMPERATURE

PD PRESSURE DROP

PH PHASE

PRDV PRESSURE REDUCING VALVE

PRV PRESSURE RELIEF VALVE

RA RETURN AIR

RD ROOF DRAIN

RHW RECIRCULATING HOT WATER

RL RAIN LEADER

RP RADIANT PANEL

RPM REVOLUTIONS PER MINUTE

S/M SHEET METAL

S/S START/STOP

SH SHOWER

SIM SIMILAR

SP STATIC PRESSURE

SPEC SPECIFICATIONS

SS STAINLESS STEEL

ST STEAM

SWSI SINGLE WIDTH, SINGLE INLET

TDH TOTAL DYNAMIC HEAD

THW TEMPERED HOT WATER

TP TRAP PRIMER

TYP TYPICAL

V VENT

VAV VARIABLE AIR VOLUME

VERT VERTICAL

VFD VARIABLE FREQUENCY DRIVE

VOL VOLUME

VTR VENT THROUGH ROOF

W WASTE

W/ WITH

W/O WITHOUT

WB WETBULB

WCO WALL CLEAN OUT

WHA WATER HAMMER ARRESTOR

MECHANICAL ABBREVIATIONS

KEY NAME MECHANICAL ABBREVIATIONS

# NUMBER

& AND

@ AT

A AIR

AFF ABOVE FINISHED FLOOR

AGT AVERAGE GLYCOL TEMPERATURE

AHU AIR HANDLING UNIT

APD AIR PRESSURE DROP

APPR APPROVED

APPROX APPROXIMATE

ARCH ARCHITECTURAL

ASSOC ASSOCIATED

AUTO AUTOMATIC

BAL BALANCING

BFF BELOW FINISHED FLOOR

BFP BACKFLOW PREVENTOR

C COMMON

CI CAST IRON

CLG COOLING

CO CLEAN OUT

CR CONDENSATE RETURN

Cv VALVE COEFFICIENT

CW COLD WATER

DB DECIBEL

DB DRYBULB

DI DUCTILE IRON

DIA DIAMETER

DN DOWN

DWDI DOUBLE WIDTH, DOUBLE INLET

EA EXHAUST AIR

EAT ENTERING AIR TEMPERATURE

EF EXHAUST FAN

EGT ENTERING GLYCOL TEMPERATURE

ELEC ELECTRICAL

ESP EXTERNAL STATIC PRESSURE

EWT ENTERING WATER TEMPERATURE

EXIST EXISTING

FC FORWARD CURVED

FD FLOOR DRAIN

FLA FULL LOAD AMPERAGE

FLEX FLEXIBLE

FP FIRE PROTECTION

GA GAUGE

GALV GALVANIZED

GHR GLYCOL HEATING RETURN

GHS GLYCOL HEATING SUPPLY

GHS&R GLYCOL HEATING SUPPLY & RETURN

GI GALVANIZED IRON

HB HOSE BIBB

HW HOT WATER

ID INSIDE DIAMETER

IDU INDOOR UNIT

IE INVERT ELEVATION

INSUL INSULATION

IPS IRON PIPE SIZE

LAT LEAVING AIR TEMPERATURE

LGT LEAVING GLYCOL TEMPERATURE

MAX MAXIMUM

SEQUENCE OF OPERATION

AIR SOURCE HEAT PUMP: THE ASHP ENABLES P-4 AND STAGES THE HEAT PUMP COMPRESSORS

AND BUFFER TANK AUXILARY HEATER TO MAINTAIN THE BUFFER TANK TEMPERATURE SETPOINT

PER THE FOLLOWING SCHEDULE:

STAGE SOURCE ON TEMP OFF TEMP

ASHP

ASHP

BT

80F

75F

60F

90F

85F

70F

WATER SOURCE HEAT PUMP: THE WSHP ENABLES P-2 AND P-3 AND STAGES THE HEAT PUMP

COMPRESSOR AND BUFFER TANK AUXILIARY HEATER TO MAINTAIN THE BUFFER TANK

TEMPERATURE SETPOINT PER THE FOLLOWING SCHDULE:

STAGE SOURCE ON TEMP OFF TEMP

WSHP

BT

150F

140F

155F

155F

BUILDING PUMP P-1A & P-1B: PUMPS ARE CONTROLLED IN A LEAD/LAG CONFIGURATION USING TEKMAR 132 PUMP SEQUENCER. SET EACH PUMP TO MAINTAIN CONSTANT PRESSURE OF 27' HEAD.

AIR SOURCE HEAT PUMP SETTINGS

GENERAL

ANTI-SHORT CYCLE: 5 MINUTES

COMPRESSOR START DELAY: 0 MINUTES

OUTDOOR FAN SPEED: 100%

SETPOINT CONTROL

CONTROL SOURCE HYD: SETPOINTS

SETPOINTS METHOD: EXTERNAL

STAGING SETPOINTS

STAGE 1: ON AT 80F; OFF AT 90F

STAGE 2: ON AT 75F; OFF AT 85F

OUTDOOR RESET: DISABLED

HYDRONIC AUXILIARY IN DEFROST: DISABLED

TOP UP S1: DISABLED

BUFFER TANK SETTINGS

SET TOGGLE SWITCH ON BACK OF CONTROLLER TO "ELECTRIC" MODE.

SET TO "JOIST HEAT" MODE

CONTROL IS PROVIDED BY THE RESPECTIVE HEAT PUMP

2 WSHP 145F 155F

AKAF AL

TS

TA E O

49 TH

S

Emily C. Winfield

ME 109592

REGISTERED PROFESSIONAL ENGIN

EE

R

16-DEC-2020

WATER SOURCE HEAT PUMP SETTINGS

SET POINT CONTROL

CONTROL SOURCE HYD: SETPOINTS

SETPOINTS METHOD: EXTERNAL

STAGING SETPOINTS

STAGE 1: ON AT 150F; OFF AT 155F

STAGE 2 (AUXILIARY): ON AT 145F; OFF AT 155F; DELAY 5 MINUTES

OUTDOOR RESET: ENABLED: RESET FACTOR: 2F

MISCELLANEOUS EQUIPMENT SCHEDULE

SYMBOL ITEM CAPACITY / SIZE MOTOR

DATA

OPERATING

WEIGHT {1} (LB)

BASIS OF DESIGN REMARKS

ASHP-1

IDU

AIR SOURCE HEAT PUMP

INDOOR UNIT

AS-1 HEATING SYSTEM AIR

SEPARATOR

BT-1 BUFFER TANK/ELECTRIC

BOILER

{1} OPERATING WEIGHT INDICATED. PLUS 10% IS MAXIMUM ALLOWED WEIGHT IF USING A SEISMIC DETAIL PROVIDED AS PART OF CONTRACT DOCUMENTS.

{2} CAPACITY OF 240V EQUIPMENT CONNECTED TO 208V SYSTEMS SHALL BE MULTIPLIED BY 75%

BT-2

38.3 MBH GROSS OUTPUT,

71 GALLON

208/1/60 11.3kW 54.7A

975 THERMO 2000 T2

ALTSOURCE 70-15

1. CHARGE W/ 134A REFRIGERANT

1. HEATING CAPACITY DERATED: 240V EQUIPMENT CONNECTED TO

208V SYSTEM

28.4 MBH MIN HEATING OUTPUT

AT 1°F, 105°F LGT, 96°F EGT

375 NORDIC ATW-75 IDU 1.

2.

CHARGE W/ R410A REFRIGERANT

SINGLE POINT ELECTRICAL CONNECTION

208/3/60 25.4A

WH-1

(EXISTING)

MASCOT ELECTRIC

WATER HEATER

30 GALLON STORAGE CAPACITY

18 GPH RECOVERY AT 100°F RISE

208/1/60 3.4kW

--- RELIANCE

630DORT

1.

2.

EXISTING WATER HEATER TO REMAIN

HEATING CAPACITY DERATED: 240V EQUIPMENT CONNECTED TO

208V SYSTEM

WH-2

(EXISTING)

HERN/CLIPPER ELECTRIC

WATER HEATER

6 GALLON STORAGE CAPACITY

24 GPH RECOVERY AT 100°F RISE

208/1/60 6kW

--- RHEEM

EGSP6

1. EXISTING WATER HEATER TO REMAIN

2" THREADED, 40 GPM FLOW ----- 8.5 SPIROTHERM SPIROVENT

JR VJR200TM

BTU-1 BTU METER 2% ACCURACY, 140F-212F

TEMPERATURE RANGE

--- --- ONICON

SYSTEM-10

1.

2.

METERING FOR HERN CLIPPER LEASE SPACE

PROVIDE W/THERMOWELL KIT AND F-1100 TURBINE FLOW METER

CIRCULATING PUMP SCHEDULE

SERVICESYMBOL STYLE

P-1A,B GLYCOL HEATING

P-4 ASHP

CIRCULATION

GPM HEAD

(FT H2O)

RPM MOTOR

DATA

BASIS OF DESIGN MAX

BHP

REMARKS

34 27 3/4 HP

208V/1Ø/60

TACO 1915E-F -----

16 10 170 W 208V/1Ø/60

TACO 0034E-F2 -----

IN-LINE

IN-LINE

1. PROVIDE W/ TEKMAR 132 LEAD/LAG CONTROLLER

{1} SELECTION AND PRESSURE DROP BASED ON 30% PROPYLENE GLYCOL / 70% WATER UNLESS OTHERWISE NOTED.

GMT-1 GLYCOL MAKEUP TANK 115/1/60

50W

120 AXIOM

MF300

17 GALLON CAPACITY ---

ET-1 HEATING SYSTEM DIAPHRAGM

EXPANSION TANK

10.3 GALLON VOLUME

10.3 GALLON ACCEPTANCE VOLUME

----- 23 AMTROL THERM-X-TROL

ST-25V

1.

2.

12 PSIG PRECHARGE

264 GALLON ESTIMATED SYSTEM VOLUME

CABINET UNIT HEATER/UNIT HEATER SCHEDULE

CAPACITY

(MBH)

SYMBOL MAX FLOW

(GPM)

MAX PD

(FT H2O) {1}

BASIS OF DESIGNEAT (F) REMARKS

{1} SELECTION AND PRESSURE DROP BASED ON 30% PROPYLENE GLYCOL / 70% WATER UNLESS OTHERWISE NOTED.

{2} CAPACITY OF 240V EQUIPMENT CONNECTED TO 208V SYSTEMS SHALL BE MULTIPLIED BY 75%

LOCATION STYLE EGT (F) MIN

CFM

MOTOR

DATA

7.5EUH-1 MASCOT

MECHANICAL RM.

HORIZONTAL BLOW --- 65---- --- 350 2.2 KW

208V/1Ø/60

QMARK

MUH03-21

B-2 BOILER SERVING

HERN/CLIPPER

215,700 BTUH ---- ----- WEIL MCLAIN B768 VW 1. EXISTING, TO REMAIN

WSHP-1 WATER SOURCE HEAT PUMP 114.1 MBH GROSS OUTPUT

160°F LGT

208/3/60 32.8A

950 NORDIC WH-150-H

BUFFER TANK/ELECTRIC

BOILER

98.9 MBH GROSS OUTPUT,

71 GALLON

240/1/60 29.0kW 120A

975 THERMO 2000 T2

ALTSOURCE 70-29

1.

2.

PROVIDE W/ OPTIONAL COPPER COIL FOR DHW HEATING

CONNECT TO BUCK-BOOST TRANSFORMER SUPPLYING 240V

P-2 WSHP

CIRCULATION

36 9 170 W 208V/1Ø/60

TACO 0034E-F2 -----IN-LINE ----- 1. OPERATE ON LOW SPEED SETTING

P-3 WSHP

CIRCULATION

36 9 170 W 208V/1Ø/60

TACO 0034E-F2 -----IN-LINE ----- 1. OPERATE ON LOW SPEED SETTING

1. OPERATE ON LOW SPEED SETTING

1. HEATING CAPACITY DERATED: 240V EQUIPMENT

CONNECTED TO 208V SYSTEM

ASHP-1

ODU

AIR SOURCE HEAT PUMP

OUTDOOR UNIT

28.4 MBH MIN HEATING OUTPUT

AT 1°F, 105°F LGT, 96°F EGT

300 NORDIC ATW-75 ODU 1.

2.

CHARGE W/ R410A REFRIGERANT

PROVIDE W/ LEG KIT

ISSUE DATE

COMM. NUMBER

DESIGNED BY

DRAWN BY

SCALE 0" 1"

Architects Engineers Surveyors 601 College Road Fairbanks AK 99701

907.452.1241 designalaska.com

17 DEC 2020

MASCOT SALOON

HEATING SYSTEM

CONVERSION

402003

AECC511

12/17/2020 9:06:17 AM

ECW

BAB

MECHANICAL

SCHEDULES

M002

AKAF AL

TS

TA E O

49 TH

S

Emily C. Winfield

ME 109592

REGISTERED PROFESSIONAL ENGIN

EE

R

16-DEC-2020

DN

DEMOLISH EXISTING FINNED TUBE AND

CABINET. DEMOLISH ASSOC BRANCH LINES

BACK TO HYDRONIC MAINS & CAP.

EXISTING UNIT HEATER

TO REMAIN, TYP 2

EXISTING RECESSED FINNED

TUBE TO REMAIN

EXISTING FINNED TUBE TO REMAIN, TYP.

EXCEPT WHERE NOTED

DEMOLITION OF EXISTING CAST IRON SECTIONAL BOILER,

FUEL OIL PIPING, BOILER STACK, GLYCOL MAKEUP TANK,

PIPING FROM BOILER TO CONTROL VALVES, AND REPAIR

OF STACK PENETRATION BY NATIONAL PARK SERVICE.

EXISTING HERN/CLIPPER HEATING

SYSTEM TO REMAIN.

MASCOT MECHANICAL 117

EQUIPMENT SIZED FOR FUTURE

CONNECTION OF HERN/CLIPPER

BOARD WALK DEMOLITION BY NATIONAL

PARK SERVICE AS REQUIRED TO INSTALL

REFRIGERANT LINES

COMMERCIAL

MULTI-USE

COMMERCIAL

MULTI-USE

CLIPPER

MECHANICAL

MASCOT

MECHANICAL

STORAGE

OPEN

CLOSET

JANITOR

CLOSET

INTERPRETATION

MEN

106A

WOMEN

106B

STAIR

STORAGE

VESTIBULE

CORRIDOR

CURATORIAL

WORKSHOP

EXISTING FINNED

TUBE TO REMAIN, TYP

EXISTING RECESSED

FINNED TUBE TO REMAIN

EXISTING CABINET UNIT

HEATER TO REMAIN, TYP 2

MASCOT

CUSTODIAL

WH-1

EXISTING WATER

HEATER TO REMAIN

MASCOT SALOON HYDRONIC MAINS SERVING

FIRST FLOOR LOCATED BELOW FLOOR, TYP

HERN/CLIPPER HYDRONIC MAINS SERVING

FIRST FLOOR LOCATED BELOW FLOOR, TYP

WH-2

DEMOLISH EXISTING CW

CONNECTION TO WH-1 AND

WH-2 BACK TO MAIN AND CAP

ISSUE DATE

COMM. NUMBER

DESIGNED BY

DRAWN BY

SCALE 0" 1"

Architects Engineers Surveyors 601 College Road Fairbanks AK 99701

907.452.1241 designalaska.com

17 DEC 2020

MASCOT SALOON

HEATING SYSTEM

CONVERSION

402003

AECC511

12/17/2020 9:06:19 AM

ECW

BAB

FIRST FLOOR

MECHANICAL

DEMOLITION PLAN

M100M100 1/4" = 1'-0"

1 FIRST FLOOR MECHANICAL DEMOLITION PLAN

AKAF AL

TS

TA E O

49 TH

S

Emily C. Winfield

ME 109592

REGISTERED PROFESSIONAL ENGIN

EE

COMMERCIAL

MULTI-USE

COMMERCIAL

MULTI-USE

STORAGE

CLIPPER

MECHANICAL

MASCOT

CUSTODIAL

OPEN

CLOSET

RESTROOM

INTERPRETATION

STORAGE

STAIR

VESTIBULE

CORRIDOR

MEN

106A

WOMEN

106B

CURATORIAL

WORKSHOP

MASCOT

MECHANICAL

EXISTING CABINET UNIT

HEATER TO REMAIN, TYP 2

APPROXIMATE LOCATION OF ASHP-1 ODU ON

CONCRETE HOUSEKEEPING PAD.

ROUTE REFRIGERATION PIPING UNDER BOARD WALK

TO MASCOT MECHANICAL 117. INSTALL IN ACCORDANCE

WITH MANUFACTURER'S INSTRUCTIONS

REPLACE BALANCE COCK

AND INCREASE UNIT HEATER

FLOW RATE TO 2.5 GPM, TYP 2

BOARD WALK REINSTALLATION BY

NATIONAL PARK SERVICE

TO SECOND FLOOR

1" GHR

3/4" GHR

3/4" GHS1" GHS

3/4" GHR

1" GHR

1" GHR

3/4" GHR

3/4" GHS

1" GHS

3/4" GHS&R

1" GHR

1 1/4" GHS

1" GHS1" GHR

3/4" GHR

3/4" GHS

3/4" GHS

3/4" GHR

3/4" GHS

3/4" GHR

EXISTING FINNED

TUBE TO REMAIN

EXISTING CLIPPER MECHANICAL

ROOM. EQUIPMENT FOR FUTURE

DEMOLITION BY NPS

M300

1 1/4" GHR

WH-1

CONTRACTOR TO INSTALL REFRIGERANT

PIPING AND ELECTRICAL ABOVE GRADE

AND BELOW THE BOARDWALK SURFACE IN

SPACE BELOW SURFACE REMOVED BY NPS

M400

EXISTING RECESSED

FINNED TUBE TO REMAIN

EXISTING RECESSED

FINNED TUBE TO REMAIN

EXISTING FINNED

TUBE TO REMAIN

WH-2

EXISTING FINNED

TUBE TO REMAIN

EXISTING FINNED

TUBE TO REMAIN

ISSUE DATE

COMM. NUMBER

DESIGNED BY

DRAWN BY

SCALE 0" 1"

Architects Engineers Surveyors 601 College Road Fairbanks AK 99701

907.452.1241 designalaska.com

17 DEC 2020

MASCOT SALOON

HEATING SYSTEM

CONVERSION

402003

AECC511

12/17/2020 9:06:22 AM

ECW

BAB

FIRST FLOOR

MECHANICAL

PLAN

M200M200 1/4" = 1'-0"

1 FIRST FLOOR MECHANICAL PLAN

SHEET SPECIFIC NOTES

EXISTING FINNED TUBE FOR FUTURE DEMOLITION BY NPS. REMAINS

ACTIVE UNTIL RADIANT TUBING IN THE AREA SERVED IS FUNCTIONAL

AKAF AL

TS

TA E O

49 TH

S

Emily C. Winfield

ME 109592

REGISTERED PROFESSIONAL ENGIN

EE

R

EXISTING PIPING SERVING 2ND FLOOR TO REMAIN2

MULTI-USE

COMMERCIAL

MULTI-USE

STORAGE

CLIPPER

MECHANICAL

MASCOT

CUSTODIAL

INTERPRETATION

STORAGE

STAIR

VESTIBULE

CORRIDOR

MEN

106A

WOMEN

106B

MASCOT

MECHANICAL

PROVIDE

RADIANT ZONE 1B

1 LOOP, AVG LOOP LENGTH 135FT

PROVIDE

RADIANT ZONE 1C

1 LOOP, AVG LOOP LENGTH 100FT

FUTURE RADIANT ZONE 2

3 LOOPS, AVG LOOP LENGTH 235FT

NO WORK REQUIRED

FUTURE RADIANT ZONE 3A

1 LOOP, AVG LOOP LENGTH 200FT

NO WORK REQUIRED

FUTURE RADIANT ZONE 3B

1 LOOP, AVG LOOP LENGTH 165FT

NO WORK REQUIRED

LOOP 1, 0.5 GPM

(2) 16'-3" RAUPLATE

RADIANT PANEL

LOOP 2, 0.5 GPM

(2) 17'-6" RAUPLATE

RADIANT PANEL

LOOP 3, 0.5 GPM

(2) 18'-9" RAUPLATE

RADIANT PANEL

LOOP 4, 0.5 GPM

(2) 20'-0" RAUPLATE

RADIANT PANEL

LOOP 1, 0.5 GPM

(6) 8'-9" RAUPLATE

RADIANT PANEL

LOOP 2, 0.5 GPM

(6) 9'-9" RAUPLATE

RADIANT PANEL

LOOP 8, 0.5 GPM

(2) 10'-0" RAUPLATE

RADIANT PANEL

LOOP 3, 0.5 GPM

(3) 18'-6" RAUPLATE

RADIANT PANEL

LOOP 1, 1.0 GPM

(6) 11'-0" RAUPLATE

RADIANT PANEL

LOOP 1, 1.0 GPM

(8) 7'-6" RAUPLATE

RADIANT PANEL

JOIST, TYP

LOOP 7, 0.5 GPM

(4) 10'-0" RAUPLATE

RADIANT PANEL

LOOP 6, 0.5 GPM

(2) 22'-6" RAUPLATE

RADIANT PANEL

CURATORIAL

WORKSHOP

LOOP 5, 0.5 GPM

(2) 21'-3" RAUPLATE

RADIANT PANEL

PROVIDE

RADIANT ZONE 1A

5 LOOPS, AVG LOOP LENGTH 175FT

ISSUE DATE

COMM. NUMBER

DESIGNED BY

DRAWN BY

SCALE 0" 1"

Architects Engineers Surveyors 601 College Road Fairbanks AK 99701

907.452.1241 designalaska.com

17 DEC 2020

MASCOT SALOON

HEATING SYSTEM

CONVERSION

402003

AECC511

12/17/2020 9:06:23 AM

ECW

BAB

FIRST FLOOR

RADIANT ZONING

PLAN

M201M201 1/4" = 1'-0"

1 FIRST FLOOR RADIANT ZONING PLAN

AKAF AL

TS

TA E O

49 TH

S

Emily C. Winfield

ME 109592

REGISTERED PROFESSIONAL ENGIN

EE

R

16-DEC-2020

GENERAL SHEET NOTES

1. CONTRACTOR TO PROVIDE ALL MATERIAL FOR RADIANT TUBING INSTALLATION. NPS WILL

PROVIDE ALL LABOR FOR RADIANT TUBING INSTALLATION.

MULTI-USE

COMMERCIAL

MULTI-USE

STORAGE

CLIPPER

MECHANICAL

MASCOT

CUSTODIAL

RESTROOM

INTERPRETATION

VESTIBULE

104 CORRIDOR

MEN

106A

WOMEN

106B

MASCOT

MECHANICAL

UTILITY

CORRIDOR

106C

HEAT TUBE

CROSSING, TYP

CURATORIAL

WORKSHOP

M400

ISSUE DATE

COMM. NUMBER

DESIGNED BY

DRAWN BY

SCALE 0" 1"

Architects Engineers Surveyors 601 College Road Fairbanks AK 99701

907.452.1241 designalaska.com

17 DEC 2020

MASCOT SALOON

HEATING SYSTEM

CONVERSION

402003

AECC511

12/17/2020 9:06:24 AM

ECW

BAB

FIRST FLOOR

RADIANT TUBING

LAYOUT PLAN

M202M202 1/4" = 1'-0"

1 FIRST FLOOR RADIANT TUBING LAYOUT PLAN

GENERAL SHEET NOTES

1.

2.

3.

4.

PROVIDE ADEQUATE SUPPORT TO RADIANT TUBING TO ELIMINATE ALL DIPS OR SAGS TO

AVOID AIR LOCK WHEN FILLING THE SYSTEM.

ROUTE TUBING LOOPS BACK TO MECHANICAL ROOM AND PENETRATE FLOOR FRAMING

PER 5/M400.

ALL RADIANT TUBING IS 1/2" PEX-A.

REMOVE AND REPLACE EXISTING BATT INSULATION IN JOIST BAYS TO ACCOMMODATE

INSTALLATION.

AKAF AL

TS

TA E O

49 TH

S

Emily C. Winfield

ME 109592

REGISTERED PROFESSIONAL ENGIN

EE

BT-1

BT-2

ASHP-1

GMT-1

P-4

WSHP-1

P-1A/B STACKED ON

WALL W/ ET-1 BELOW

EXISTING ELECTRICAL

PANEL, TO REMAIN

MASCOT

MECHANICAL

EUH-1

WH-1

BTU-1

P-2 & P-3 STACKED

ON WALL

NEW ELECTRICAL PANEL

ELECTRICAL CLEARANCE, TYP.

WH-2

TRANSFORMER PER

ELECTRICAL

ISSUE DATE

COMM. NUMBER

DESIGNED BY

DRAWN BY

SCALE 0" 1"

Architects Engineers Surveyors 601 College Road Fairbanks AK 99701

907.452.1241 designalaska.com

17 DEC 2020

MASCOT SALOON

HEATING SYSTEM

CONVERSION

402003

AECC511

4/22/2021 1:34:35 PM

ECW

BAB

ENLARGED

MECHANICAL

ROOM PLAN

M300M300 1/2" = 1'-0"

1 ENLARGED MECHANICAL ROOM PLAN

AKAF AL

TS

TA E O

49 TH

S

Emily C. Winfield

ME 109592

REGISTERED PROFESSIONAL ENGIN

EE

R

22 APR 2021

1 EQUIPMENT LAYOUT 27 APR 2021

SEISMIC LAG SCREW SCHEDULE

EQUIPMENT

SYMBOL

LAG SCREW OR

ANCHOR BOLT

DIAMETER (IN)

NUMBER OF

BOLTS PER SIDE

MINIMUM

EMBEDMENT (IN)

MINIMUM

HOUSEKEEPING PAD

THICKNESS (IN)

MINIMUM EDGE

DISTANCE (IN)

MINIMUM SPACE

BETWEEN ANCHORS(IN)

WSHP-1

ASHP-1 ODU

2 3 3.25 4 4

2 4

REMARKS

1.

2.

WOOD HOUSEKEEPING PAD

A309 LAG SCREWS

1.

2.

3.

CONCRETE HOUSEKEEPING PAD

HILTI KWIK BOLT TZ SS

TORQUE TO 25 FT*LBS

3/8

3/8

3 3.25 4

ASHP-1 IDU 2 3 3.25 4 4 1.

2.

WOOD HOUSEKEEPING PAD

A309 LAG SCREWS

3/8

CENTER NOTCH

D

D/6 MAX

L

L/3 L/3 L/3

NOTCHES PROHIBITED IN MIDDLE

THIRD OF MEMBER SPAN

D/3 MAX

D/6 MAX

D/4 MAX

END NOTCH

D/3 Ø MAX

NOTCHES PROHIBITED

ON BOTTOM OF MEMBER

HOLES PROHIBITED WITHIN 2" OF THE

TOP OR BOTTOM OF THE MEMBER

AND ANY OTHER HOLE OR NOTCH

SOLID LUMBER BEAM OR JOIST

DETAIL SPECIFIC NOTES

HOUSEKEEPING PAD PLAN DIMENSIONS ARE DEPENDENT ON EQUIPMENT.

6X6-W1.4XW1.4 WELDED WIRE REINFORCEMENT CENTERED IN PAD.

#3 DOWELS WITH 6" HORIZONTAL LEGS AT 24" ON CENTER. HORIZONTAL LEGS TO

BE AT SAME ELEVATION AS WELDED WIRE REINFORCEMENT. DRILL AND EPOXY

WITH HILTI-HY 200 EPOXY OR APPROVED EQUAL WITH 2-1/2" EMBEDMENT.

CHAMFER EXPOSED EDGES 3/4".

BASE SLAB.

3" EDGE DISTANCE FOR DOWELS.

6" (ACTUAL) PAD THICKNESS UNLESS NOTED OTHERWISE.

PLAN

SECTION A-A

24" TYP

A A

6 2

HOUSEKEEPING PAD PLAN DIMENSIONS ARE DEPENDENT ON EQUIPMENT.

SEE MECHANICAL ANCHOR BOLT SCHEDULE FOR MINIMUM EDGE

DISTANCE REQUIREMENTS.

3 LAYERS OF 1 1/8" PLYWOOD. ATTACH BOTTOM LAYER AND SUBSEQUENT

LAYERS TO LAYER BELOW W/ 2-1/2" WOOD SCREWS AT MAX 12" OC EACH

WAY BUT NOT LESS THAN THREE IN EACH DIRECTION

EXISTING FLOOR FRAMING PER PLAN

DETAIL SPECIFIC NOTES

ASHP-1 ODU

MASCOT

MECHANICAL

ASHP-1 IDU

SEAL PENETRATIONS

WATER TIGHT

3/4" RS

3/8" RR

BT-1

WSHP-1

BT-2

PLYWOOD HOUSEKEEPING

PAD, TYP

EXISTING

1-1/4" CW

GMT-1

2" GHR

2" GHS

P-4

P-2

P-3

16 GPM

36 GPM

WH-1

MASCOT

CUSTODIAL

WH-2

CLIPPER

MECHANICAL

3/4" HW

FROM BT-2

36 GPM

2" GHR

2" GHS

1-1/2" GHS

3/4" GHS

P-1B

P-1A

32 GPM

AS-1

3/4" GHS TO

GMT-1 AND ET-1

2" GHR

ET-1

FUTURE TO WH-2

TO WH-1

SUPPLY

RETURN

RADIANT

MANIFOLD 1

TYP

TYP

SUPPLY

RETURN

RADIANT

MANIFOLD 2

SUPPLY

RETURN

RADIANT

MANIFOLD 3

REHAU PRO BALANCE

MANIFOLD, TYP

1-1/4" HW

FROM BT-2

M400

M400

CONCRETE HOUSEKEEPING PAD

1-1/2" GHR

3/4" GHS TO LOW

TEMP SYSTEM

2" GHR

2" GHS, TYP 2

3/4" GHS&R

3/4" GHS&R

1-1/4" GHR

1" GHS&R

1-1/4" GHS

MIN 2'-0"

3/4" HW

1-1/4" HW

1-1/4" HW

3/4" HW

1-1/4" HW

1-1/4" CW

PLAN

ELEVATION

1-1/2" 16 GAUGE STRAP, TYP.

INSTALL STRAPS AT ONE THIRD

EQUIPMENT HEIGHT

INCRIMENTS, UNLESS HEIGHT

ADJUSTMENT IS REQUIRED TO

ACCOMMODATE TANK

MOUNTED ACCESSORIES

1/2" FASTENERS,

TYP

CHANNEL

STRUT, TYP

SECURE CHANNEL

STRUT TO ATTACH TO

MIN OF 2 WALL STUDS

ISSUE DATE

COMM. NUMBER

DESIGNED BY

DRAWN BY

SCALE 0" 1"

Architects Engineers Surveyors 601 College Road Fairbanks AK 99701

907.452.1241 designalaska.com

17 DEC 2020

MASCOT SALOON

HEATING SYSTEM

CONVERSION

402003

AECC511

12/17/2020 9:06:27 AM

ECW

BAB

MECHANICAL

DETAILS

M400

SHEET SPECIFIC NOTES

LINE SIZE PRV DISCHARGE SET TO 30 PSI, EXTEND PRV DISCHARGE TO 6" ABOVE FLOOR1

LINE SIZE AS-1 DISCHARGE, SLOPE PIPE TO GMT-12

TAPS FOR CONNECTION TO BTU-13

EXISTING HOT WATER SUPPLY TO FIXTURES4

ROUTE REFRIGERANT PIPING UNDER BOARDWALK, THROUGH FOUNDATION WALL AND

UP THROUGH FLOOR INTO MASCOT MECHANICAL 117

GENERAL SHEET NOTES

1. SEISMICALLY BRACE BT-1, BT-2, ET-1, AND GMT-1 PER 5/M400

RADIANT TUBING INSTALLED BY NPS PRIOR TO CONTRACTOR WORK. CONTRACTOR TO

CONNECT RADIANT TUBING TO MANIFOLD PROVIDED BY CONTRACTOR

CONNECT TO EXISTING GHS&R MAINS SERVING EXISTING TERMINAL UNITS, MATCH

EXISTING PIPE SIZE. PROVIDE NEW CONTROL VALVES, TYP 5

PROVIDE STUB AND CAP FOR FUTURE CONNECTION TO EXISTING HERN/CLIPPER

FIRST FLOOR GHS&R MAIN. MATCH EXISTING GHS&R MAIN PIPE SIZE.

M400 NO SCALE

1 ALLOWABLE FLOOR FRAMING PENETRATION DETAIL

NC VALVE TO BYPASS DHW COIL IN THE EVENT OF HEAT PUMP FAILURE9

AKAF AL

TS

TA E O

49 TH

S

Emily C. Winfield

ME 109592

REGISTERED PROFESSIONAL ENGIN

EE

R

16-DEC-2020

MAKE LOW TEMPERATURE SIDE CONNECTION WITH ET-1/GMT-1 MIN 2'-0" LOWER THAN

HIGH TEMPERATURE CONNECTION TO PREVENT BUOYANT MIXING OF THE SYSTEMS

M400 NO SCALE

3 SEISMIC - HOUSKEEPING PAD DETAIL

M400 NO SCALE

4 TYPICAL HOUSEKEEPING PAD - WOOD

M400 NO SCALE

2 CASCADING HEAT PUMP DIAGRAM

M400 NO SCALE

5 SEISMIC - WALL MOUNTED TANK

RADIANT TUBING INSTALLED BY NPS IN FUTURE PROJECT. MANIFOLD PROVIDED BY

CONTRACTOR

ELECTRICAL SYMBOL LEGEND

MOTOR (HP, VOLTAGE & PHASE NOTED ON DRAWING)

EQUIPMENT CONNECTION

PANELBOARD

POWER SYMBOLS

M

ANNOTATION SYMBOLS

L1-12

L1-12

AHU-1

PANEL & CIRCUIT IDENTIFICATION

PANEL & CIRCUIT IDENTIFICATION

B LIGHTING FIXTURE TAG

'L1' DENOTES PANEL NAME, '24' DENOTES CIRCUIT NUMBERL1-24

LIGHTING FIXTURE TAG (SEE LIGHTING FIXTURE SCHEDULE)B2

SPECIFIC NOTE KEY

(REFERENCE # UNDER 'SPECIFC NOTES' ON EACH SHEET)

a

SWITCH IDENTIFICATION TAG

a SWITCH IDENTIFIER

EQUIPMENT IDENTIFIER, SEE MECHANICAL ELECTRICAL

SCHEDULE

ABBREVIATIONS

ABOVE FINISHED FLOOR

EXISTING

UNLESS OTHERWISE NOTED

AFF

(E)

UON

SERVICE SIZE

12 MONTH MAXIMUM DEMAND READING (02/2019-12/2020)

ASSUMED POWER FACTOR

MAXIMUM DEMAND

x125% (BASELINE PER NEC 220.87)

ADDED LOAD

NEW 400A PANEL

SERVICE VOLTAGE 208Y/120

4.843

0.8

6.054

7.567

V

A kW kVA kVA

UTILITY AP&T

76.818 kVA

TOTAL CALCULATED LOAD (BASELINE + ADDED) 84.385 kVA

TOTAL CALCULATED CURRENT 234.23 A

SERVICE SIZE SPARE CAPACITY 41 %

SERVICE LOAD CALCULATION

300 KVA TRANSFORMER (1.7% Z)

500 KCMIL CABLE (CU), 110 FEET

400 A CTS, 400 A MAIN DISCONNECT

ASYMMETRIC MOTOR CONTRIBUTION, TOTAL RLA = 81.04 A

SYMMETRIC SHORT CIRCUIT CURRENT AVAILABLE AT PANEL 'M'

SOURCE

DESCRIPTION

SHORT CIRCUIT CALCULATION

SHORT CIRCUIT

AMPS L-L

48,250

16,131

15,769

500 KCMIL CABLE (CU), 100 FEET 9,907

10,312

10,312

SEE ELECTRICAL ONE-LINE DIAGRAM ON E3.00

ISSUE DATE

COMM. NUMBER

DESIGNED BY

DRAWN BY

SCALE 0" 1"

Architects Engineers Surveyors 601 College Road Fairbanks AK 99701

907.452.1241 designalaska.com

17 DEC 2020

MASCOT SALOON

HEATING SYSTEM

CONVERSION

402003

AECC511

4/26/2021 1:10:14 PM

RSG

JCC

ELECTRICAL

LEGEND AND

SCHEDULES

E001

GENERAL SHEET NOTES

1.

2.

3.

4.

5.

SEE MECHANICAL SHEETS FOR MORE DETAILS REGARDING MOTORS AND EQUIPMENT. MECHANICAL EQUIPMENT CONNECTIONS AND THEIR ASSOCIATED DISCONNECT/CONTROLLER LOCATIONS SHOWN ARE APPROXIMATE ONLY. COORDINATE WITH ACTUAL MECHANICAL EQUIPMENT PROVIDED DURING THE SUBMITTAL PROCESS AND ADJUST DISCONNECT CONTROL TYPE, THERMAL OVERLOADS, CONDUCTORS, AND CONDUIT BEFORE SUBMITTAL APPROVAL. COORDINATE WITH MECHANICAL ON FINAL EQUIPMENT

CONFIGURATION AND LOCATION.

IN GENERAL, CIRCUITING FOR OUTLETS IS NOT SHOWN, BUT THE INTENDED CIRCUIT TO BE CONNECTED

TO IS SHOWN. CIRCUITING SHALL BE PROVIDED PER CONTRACTOR MEANS AND METHODS.

WHERE NOTED, ALL MEASUREMENTS SHALL MEAN TO CENTER OF DEVICE/EQUIPMENT. EX. +4'-0" AFF UON

MEANS THE CENTER OF THE OUTLET IS 4'-0" ABOVE THE FIXED FLOOR.

PROVIDE A SEPARATE GROUNDED CONDUCTOR (NEUTRAL) FOR EACH BRANCH CIRCUIT. SHARED

NEUTRALS ARE NOT PERMITTED.

INSTALL AN EQUIPMENT GROUNDING CONDUCTOR, SIZED IN ACCORDANCE WITH THE NEC FOR ALL

FEEDER AND BRANCH CIRCUIT CONDUITS.

ELECTRIC MOTOR AND EQUIPMENT SCHEDULE

TAG DESCRIPTION RATING PHASE FLA MOPD

CONTROLLER

MOTOR DISCONNECT

MINIMUM CONDUCTOR AND

RACEWAY

PANEL -

CIRCUIT COMMENTS

TYPE DISCONNECT

120 V GMT-1 GLYCOL MAKEUP TANK 50 W 1 0.4 A 15 A INTEGRAL GFCI 5-20R GFCI 5-20R (2) #12 AWG, #12 GND, 1/2" C M - 37

208 V

(E) WH-1 ELECTRIC WATER HEATER 3 KVA 1 16.2 A 30 A A - 35,37 EXISTING EQUIPMENT RATED FOR 240V CONNECTED TO

208V (208V RATING PROVIDED)

(E) WH-2 ELECTRIC WATER HEATER 6 KW 1 28.9 A 40 A B-1 - 16,18 EXISTING EQUIPMENT RATED FOR 240V CONNECTED TO

208V (208V RATING PROVIDED)

ASHP-1 IDU AIR SOURCE HEAT PUMP - INDOOR

UNIT

9 KVA 3 25.4 A 40 A INTEGRAL CIRCUIT BREAKER CIRCUIT BREAKER (3) #8 AWG, #10 GND, 3/4" C M - 26,28,30

ASHP-1 ODU AIR SOURCE HEAT PUMP - OUTDOOR

UNIT

1 0.0 A 0 A OUTDOOR UNIT SUB-FED FROM INDOOR UNIT

PROVIDE INTERCONNECTING POWER/SIGNAL CABLES AND

CONDUIT PER MANUFACTURER'S INSTRUCTIONS

BT-1 BUFFER TANK/ELECTRIC BOILER 11 KW 1 54.6 A 70 A INTEGRAL CIRCUIT BREAKER CIRCUIT BREAKER (2) #4 AWG, #8 GND,3/4" C M - 13,15 EQUIPMENT RATED FOR 240V CONNECTED TO 208V (208V

RATING PROVIDED)

EUH-1 ELECTRIC UNIT HEATER 2 KW 1 11.0 A 20 A T-STAT T-STAT OFF CIRCUIT BREAKER (2) #12 AWG, #12 GND, 1/2" C M - 8,10 P-1A GLYCOL HEATING PUMP 3/4 HP 1 7.6 A 20 A INTEGRAL CIRCUIT BREAKER CIRCUIT BREAKER (2) #12 AWG, #12 GND, 1/2" C M - 2,4 P-1B GLYCOL HEATING PUMP 3/4 HP 1 7.6 A 20 A INTEGRAL CIRCUIT BREAKER CIRCUIT BREAKER (2) #12 AWG, #12 GND, 1/2" C M - 7,9 REDUNDANT PUMP P-2 WSHP CIRCULATION PUMP 170 W 1 0.8 A 15 A INTEGRAL CIRCUIT BREAKER CIRCUIT BREAKER (2) #12 AWG, #12 GND, 1/2" C M - 14,16 P-3 WSHP CIRCULATION PUMP 170 W 1 0.8 A 15 A INTEGRAL CIRCUIT BREAKER CIRCUIT BREAKER (2) #12 AWG, #12 GND, 1/2" C M - 1,3 P-4 ASHP CIRCULATION PUMP 170 W 1 0.8 A 15 A INTEGRAL CIRCUIT BREAKER CIRCUIT BREAKER (2) #12 AWG, #12 GND, 1/2" C M - 31,33 WSHP-1 WATER SOURCE HEAT PUMP 15 KVA 3 41.6 A 60 A INTEGRAL CIRCUIT BREAKER CIRCUIT BREAKER (3) #6 AWG, #10 GND, 3/4" C M - 25,27,29

240 V BT-2 BUFFER TANK/ELECTRIC BOILER 29 KW 1 120.0 A 175 A INTEGRAL CIRCUIT BREAKER CIRCUIT BREAKER (2) #1/0 AWG, #6 GND,1 1/4" C M - 40,42 EQUIPMENT RATED FOR 240V CONNECTED TO 208V

THROUGH BUCK-BOOST TRANSFORMER. (240V RATING

PROVIDED)

(1) PROVIDE SUB-FEED BREAKER FOR THIS CIRCUIT

NOTES:

CH CHILLER [NEC 2017, ARTICLE 440.33] 0 VA 0.00% 0 VA

H HBO [NEC 2017, ARTICLE 220.14(A)] 0 VA 0.00% 0 VA

A APPLIANCE [NEC 2017, ARTICLE 220.56] 0 VA 0.00% 0 VA

M MOTOR [NEC 2017, ARTICLE 430.24] 29,195 VA 112.83% 32,942 VA

R RECEPTACLES [NEC 2017, ARTICLE 220.44] 10,980 VA 95.54% 10,490 VA

L LIGHTING [NEC 2017, ARTICLE 215.2(A)(1)] 8,786 VA 125.00% 10,983 VA DEMAND LOAD: 106,799 VA 296 A

E NON-CONTINUOUS [NEC 2017, ARTICLE 215.2(A)(1)] 52,385 VA 100.00% 52,385 VA CONNECTED LOAD: 101,346 VA 281 A

C CONTINUOUS [NEC 2017, ARTICLE 215.2(A)(1)] 0 VA 0.00% 0 VA LOAD AMPS

LOAD CLASSIFICATION CONNECTED LOAD DEMAND FACTOR DEMAND LOAD PANEL TOTALS

TOTAL AMPS: 263 A 259 A 323 A

TOTAL LOAD: 31,518 VA 31,104 VA 38,724 VA

41 14,400 42

39 14,400

2 175 E (1) SUB FEED BREAKER - RM 117 - BT-2 (29 KW)

37 RM 117 - GMT-1 M 15 1 50 38

35 36

33 84 34

RM 117 - P-4 (170 W) M 15 2

84 32

29 4,996 3,050 30

27 4,996 3,050 28

RM 117 - WSHP-1 (15 KVA) M 60 3

4,996 3,050

3 40 M RM 117 - ASHP-1 (9 KVA)

23 0 -- -- -- SPACE FOR ADJ PANEL 'A' BREAKER 24

21 0 -- -- -- SPACE FOR ADJ PANEL 'A' BREAKER 22

19 14,764 20

17 16,278 2 150

L; M; R;

E PANEL 'A' - RM 117

15 5,680 84 16

RM 117 - BT-1 (11 KW) E 70 2

5,680 84

2 15 M RM 117 - P-2 (170 W)

11 12

9 790 1,144 10

RM 117 - P-1B (3/4 HP) M 20 2

790 1,144

2 20 E RM 117 - EUH-1 (2 KW)

5 6

3 84 790 4

RM 117 - P-3 (170 W) M 15 2

84 790

2 20 M RM 117 - P-1A (3/4 HP)

CKT CIRCUIT DESCRIPTION LOAD

CLASS TRIP P A B C P TRIP LOAD

CLASS CIRCUIT DESCRIPTION CKT

ENCLOSURE: TYPE 1 PANELBOARD FEEDER CB RATING: 400 A

MOUNTING: SURFACE WIRES: 4 MAINS RATING: 400 A

SUPPLY FROM: PHASES: 3 MAINS TYPE: MCB

LOCATION: MASCOT MECHANICAL 117 VOLTS: 208Y/120V A.I.C. RATING: 22,000

PANEL: M

1 REVISED SERVICE

ENTRANCE

27 APR 2021

AKAF AL

TS

TA E O

49 TH

S

REGISTERED PROFESSIONAL ENGIN

EE

RRobert S. Gras

No. EE 7352

27-APR-2021 - -

SPECIFIC SHEET NOTES

1 PROVIDE CIRCUIT BREAKERS AND CONNECTIONS TO EQUIPMENT AS SHOWN IN PANEL SCHEDULE. PANEL 'M', 150/2 CIRCUIT BREAKER, AND CONNECTION TO PANEL 'A' PROVIDED UNDER SEPARATE CONTRACT.

MASCOT SALOON

BOAS TAILOR &

FURRIER

VERBAUWHEDE'S CIGAR STORE

& CONFECTIONERY

(E) CONCRETE PAD

NEW CT ENCLOSURE WITH

METER AND 400A SERVICE

DISCONNECT MOUNTED ON H-

FRAME. PERFORM ALL WORK IN

ACCORDANCE WITH SERVICE

UTILITY STANDARDS.

(E) METER PACK

ENCLOSURE

(E) PNL 'A'

PNL 'M'

DEMOLISH EXISTING PNL 'A'

CONDUCTORS. CUT CONDUIT

BACK TO MAXIMUM EXTENT

POSSIBLE, PROVIDE GROUT

SEAL, AND ABANDON

CONDUIT IN PLACE. METER

AND SERVICE DISCONNECT

EXISTING TO REMAIN, RE-

LABEL AS SPARE.

(4) 500 KCMIL, #3 GND, 3" C.

WESTMARK

HOTEL

(E) FEEDER

(E) UTILITY POLE, (E) MAIN DISCONNECT FOR 6

METER PACK. PROVIDE NEW STANDOFF

BRACKETS SIZED TO ACCOMMODATE NEW RISER

FOR NEW SERVICE. TAP (E) O/H UTILITY

SECONDARY AT POLE FOR NEW SERVICE.

TO (E) PLATFORM

MOUNTED UTILITY

TRANSFORMERS.

CONTRACTOR MAY INTERCEPT

AND RE-USE EXISTING

CONDUIT TO RE-FEED

EXISTING PANEL 'A' FROM NEW

PANEL 'M'.

ELECTRICAL SERVICE DISCONNECT FOR MASCOT

SALOON LOCATED ON H-FRAME LOCATED AT

ALLEY WAY ENTRANCE ADJACENT TO HOTEL.

ELECTRICAL SERVICE

DISCONNECT FOR MASCOT

SALOON

MASCOT SALOON BUILDING PLACARD

SERVICE DISCONNECT ENCLOSURE PLACARD

ISSUE DATE

COMM. NUMBER

DESIGNED BY

DRAWN BY

SCALE 0" 1"

Architects Engineers Surveyors 601 College Road Fairbanks AK 99701

907.452.1241 designalaska.com

17 DEC 2020

MASCOT SALOON

HEATING SYSTEM

CONVERSION

402003

AECC511

4/26/2021 1:10:14 PM

RSG

JCC

ELECTRICAL SITE

PLAN

E100

1" = 10'-0"E100

1 ELECTRICAL SITE PLAN

1 REVISED SERVICE

ENTRANCE

27 APR 2021

SPECIFIC SHEET NOTES

1 PROVIDE PLACARD AT THIS LOCATION INDICATING BUILDING

SERVICE DISCONNECT LOCATION. PLACARDS TO BE IN

ACCORDANCE WITH ANSI Z535.4. REFER TO DETAIL 2/E100.

E100 NO SCALE

2 PLACARD DETAILS

HATCHED AREAS NOT IN CONTRACT

GENERAL SHEET NOTES

1.

2.

PANEL 'M', CONNECTION TO PANEL 'A' INCLUDING 150/2 CIRCUIT BREAKER, AND CONDUIT AND CONDUCTORS FROM NEW SERVICE EQUIPMENT TO PANEL 'M' PROVIDED UNDER SEPARATE CONTRACT.

CONTRACTOR TO PROVIDE CIRCUIT BREAKERS FOR PANEL 'M' AS SHOWN IN PANEL SCHEDULE ON E001.

WORK SHOWN IN HATCHED AREAS PERFORMED UNDER SEPARATE CONTRACT.

AKAF AL

TS

TA E O

49 TH

S

REGISTERED PROFESSIONAL ENGIN

EE

RRobert S. Gras

No. EE 7352

27-APR-2021

M

M

M

M

M

MM

M

INTERPRETATION

COMMERCIAL

MULTI-USE

COMMERCIAL

MULTI-USE

VESTIBULE

STORAGE

STAIR

MASCOT

CUSTODIAL

MEN

106A

CORRIDOR

WOMEN

106B

CURATORIAL

WORKSHOP

MASCOT

MECHANICAL

CLIPPER

MECHANICAL

STORAGE

OPEN

CLOSET

JANITOR

CLOSET

STORAGE

109B

STAIR

109A

P N

L M

M-37

M-40,42

B-1-16,18

M-2,4

M-7,9

M-25,27,29

M-8,10M-14,16

M-1,3

M-13,15

M-31,33

M-26,28,30GMT-1

BT-2

(E) WH-2

P-1A

P-1B

WSHP-1

EUH-1P-2

P-3

BT-1

P-4

ASHP-1 IDU

(E) WH-1

A-35,37

(E

P N

L A

(E) PNL H

(E) PNL C

2ND FLOOR

ASHP-1 ODU

(E

P N

L B

-1

ISSUE DATE

COMM. NUMBER

DESIGNED BY

DRAWN BY

SCALE 0" 1"

Architects Engineers Surveyors 601 College Road Fairbanks AK 99701

907.452.1241 designalaska.com

17 DEC 2020

MASCOT SALOON

HEATING SYSTEM

CONVERSION

402003

AECC511

4/26/2021 1:10:16 PM

RSG

JCC

FIRST FLOOR

ELECTRICAL PLAN

E200 1/4" = 1'-0"E200

1 FIRST FLOOR ELECTRICAL PLAN

SPECIFIC SHEET NOTES

1 LOW-VOLTAGE DRY-TYPE BUCK-BOOST TRANSFORMER. 5 KVA

TRANSFORMER TO BOOST 208V INPUT TO 240V, 32.5 KVA

OUTPUT. FOR INLINE CONNECTION TO FEED BT-2. CONNECT

TO PANEL M VIA (3) #2/0 AWG, #6 GND, 2"C. BASIS OF DESIGN:

EATON S10N06A05N.

2 RELOCATE EXISTING TELECOMMUNICATIONS EQUIPMENT AS

REQUIRED TO LOCATE NEW PANEL AND MAINTAIN NEC

WORKING CLEARANCE.

1 REVISED SERVICE

ENTRANCE

27 APR 2021

AKAF AL

TS

TA E O

49 TH

S

REGISTERED PROFESSIONAL ENGIN

EE

RRobert S. Gras

No. EE 7352

27-APR-2021

HATCHED AREAS NOT IN CONTRACT

XX,XXX = AVAILABLE SYMMETRICAL THREE PHASE FAULT CURRENT UNDER THE

FOLLOWING ASSUMPTIONS:

INFINITE BUS ON MV PRIMARY SIDE

1.6%Z SERVICE TRANSFORMER

110 LINEAR FEET OF SECONDARY FROM TRANSFORMERS TO RISER

EXISTING PANEL 'A' HAS 10K AIC

RATING. VERIFY THAT EXISTING

RATING WILL BE COMPATIBLE WITH

NEW SERVICE ARRANGEMENT

VERIFY NEUTRAL/GROUND

BONDING IN EXISTING PANEL 'A'.

REMOVE IF PRESENT.

NEMA 3R CT

ENCLOSURE &

METER MOUNTED

ON NEW H-FRAME

ADJACENT TO POLE

10,312

<10,000 <10,000<10,000

(E) UTILITY POLE

SECONDARY

FEEDERS

NEW 3" RISER

FROM (3) EXISTING 100 KVA

PLATFORM MOUNTED

TRANSFORMERS LOCATED

ADJACENT TO WESTMARK

HOTEL

kwh

400/3

(2) 3/4" X 10' GROUND

RODS

12,538

(E) RISER

kwh

225/2

(E) METER/MAIN

DISCONNECT NEMA 3R

ENCLOSURE

kwh

150/2 kwh

150/2 kwh

50/2 kwh

150/2 kwh

EXISTING TO REMAIN

(E) MASCOT SALOON

SERVICE DISCONNECT.

RE-LABEL AS SPARE

(E) 400/3 FUSED DISCONNECT ON

POLE. ROUTE NEW CONDUCTORS

THROUGH EXISTING DISCONNECT

IF SUFFICIENT WIRING SPACE IS

PRESENT IN ACCORDANCE WITH

NEC ARTICLE 312.8.

13,144

(E) UTILITY O/H

SECONDARY

400 AMP MAIN

DISCONNECT NEMA 3R

ENCLOSURE MOUNTED

ON NEW H-FRAME

ADJACENT TO POLE.

M

PROVIDE SEPARATE

ENERGY MONITORING

FOR PANEL 'A'. BASIS OF

DESIGN: SQUARE D

POWERLOGIC PM3200

400AF

(E)

#2 AWG

B.C. GRND

(2) 3/4" X 10' GROUND

RODS. CONNECT TO

EQUIPMENT GROUND

ONLY PER NEC 250.32

RM 117

(E) PANEL 'C'

100A MLO

120/208 V

1 PH, 3 W

(E) PANEL 'H'

100A MLO

120/208 V

1 PH, 3 W

PANEL 'M'

400A MLO

208Y/120 V

3 PH, 4 W

(E) PANEL

'A' 150A MLO

120/208 V

1 PH, 3 W

RM 117

(4) 500 KCMIL,

#3 GND,

3" C.

(3) 1/0,

(1) #6 GND,

1 1/2" C.

EXISTING TO

REMAIN

150/2

100/2

100/2150/2

RM 211 RM 105

(E) VALVE

PIT PANEL 'F'

(E) BOAS

BLDG. 1ST

FLOOR PANEL

'D-1'

(E) SUB

PANEL 2ND

FLOOR

PANEL 'D-2'

(E) PACIFIC

CLIPPER 1ST FLOOR

PANEL 'B-1'

(E) SUB

PANEL 2ND

FLOOR PANEL

'B-2'

(E) VERBAUWHEDE

BLDG. FRONT

PANEL 'E'

(E) VERBAUWHEDE

BLDG.REAR

PANEL 'G'

100/2 150/2

400/3 ISSUE DATE

COMM. NUMBER

DESIGNED BY

DRAWN BY

SCALE 0" 1"

Architects Engineers Surveyors 601 College Road Fairbanks AK 99701

907.452.1241 designalaska.com

17 DEC 2020

MASCOT SALOON

HEATING SYSTEM

CONVERSION

402003

AECC511

4/26/2021 1:10:16 PM

RSG

JCC

POWER RISER

E300

NOT TO SCALEE300

1 ELECTRICAL ONE-LINE DIAGRAM

1 REVISED SERVICE

ENTRANCE

27 APR 2021

HATCHED AREAS NOT IN CONTRACT

GENERAL SHEET NOTES

1.

2.

CONTRACTOR TO PROVIDE CIRCUIT BREAKERS FOR PANEL 'M' AS SHOWN IN PANEL SCHEDULE ON SHEET E001. 150/2 CIRCUIT BREAKER AND FEED TO PANEL 'A' ARE PROVIDED UNDER SEPARATE CONTRACT.

WORK SHOWN IN HATCHED AREAS PERFORMED UNDER SEPARATE CONTRACT.

AKAF AL

TS

TA E O

49 TH

S

REGISTERED PROFESSIONAL ENGIN

EE

RRobert S. Gras

No. EE 7352

27-APR-2021

G001
M001
M002
M100
M200
M201
M202
M300
M400
E001
E100
E200
E300