3-2026-03-16 TVM Final Construction Plan Set.pdf

PDF 35 MB Posted

Attached to
20260910 - ICB Operators
Solicitation number
Not on record
Issued by
Dauphin County, Pennsylvania

About this file

This is a Final Construction Plan Set for ticket vending machine (TVM) site preparation work being conducted by the Susquehanna Regional Transportation Authority (SRTA), operating as rabbittransit, across multiple counties in Pennsylvania including Adams, Cumberland, Dauphin, and York Counties. The project encompasses site preparation and electrical improvements at eight SRTA operational facilities: Cumberland County Courthouse in Carlisle, King Street Station in York, Red Lion Bus Stop in Red Lion, PHEAA Bus Stop in Harrisburg, Harrisburg Transfer Center in Harrisburg, HTC Shelters in Harrisburg, Middletown Train Station in Middletown, and Gettysburg Transfer Station in Gettysburg. The construction plan set, dated March 16, 2026, and prepared by JMT (220 St. Charles Way, Suite 200, York, PA 17402), includes detailed site plans, location maps, and technical specifications for all eight locations. The Invitation for Bids (IFB) requires submission of two separate contracts—one for electrical work and one for general trades construction (GTC)—with a bid deadline of 2:00 PM on May 11, 2026, via PennBid.net. The contract term and renewal options are not specified in the construction plan documents provided.

The construction plans detail specific site improvements required at each location, including TVM pad installations, conduit trench sections, concrete work, bollard installation, and utility protection measures. Work involves coordinating with rabbittransit for site access and obtaining all necessary local and partnering approvals prior to construction commencement. Contractors are responsible for all permits, traffic control, trench barricading, utility protection, and maintenance of existing infrastructure. The project is federally funded through the Federal Transit Administration (FTA) and subject to applicable Commonwealth and Federal laws. SRTA has established a 2.11% disadvantaged business enterprise (DBE) participation goal. All costs incurred by bidders in developing responses are the sole responsibility of bidding firms and will not be reimbursed by SRTA or any participating agency.

View the file

Other files

Show all 19

On GovTribe

Work with this file

  • Download the original file
  • Contacts named in this file
  • Similar government files
  • Ask GovTribe AI about this file

Text version

CUMBERLAND COUNTY

COURTHOUSE

KING STREET

STATION

RED LION BUS STOP

PHEAA BUS STOP

HARRISBURG TRANSFER

CENTER

HTC SHELTERS

MIDDLETOWN

TRAIN STATION

GETTYSBURG

TRANSFER STATION

REVISIONS

A

D

C

B

DATENO. DESCRIPTION

PROJECT:

PLAN SET:

PROJECT LOCATION:

PROJECT NUMBER:

DRAWING TITLE:

SCALE:

DRAWING NUMBER:

54321

54321

DATE:

PREPARED FOR:

SEAL:

SUBCONSULTANT:

c:

\p w w or ki ng \jm t\d

8\ C ov er

.d w g

/1 6/

P: (717) 741-1600 | www.jmt.com

220 ST. CHARLES WAY, SUITE 200 | YORK, PA 17402

CS-001

COVER SHEET

CONSTRUCTION PLAN

03/16/2026

24-00558-007

TICKET VENDING

MACHINE SITE

PREPARATION

AS NOTED

TICKET VENDING MACHINE SITE PREPARATION

CONSTRUCTION PLANS

MARCH 16, 2026

INDEX OF DRAWINGS

SCALE: 1" = 2,000'

2023 PENNDOT TYPE 10 MAPLOCATION MAP - ADAMS COUNTY SCALE: 1" = 2,000'

2023 PENNDOT TYPE 10 MAPLOCATION MAP - DAUPHIN COUNTY

SCALE: 1" = 2,000'

2023 PENNDOT TYPE 10 MAPLOCATION MAP - CUMBERLAND COUNTY SCALE: 1" = 2,000'

2023 PENNDOT TYPE 10 MAPLOCATION MAP - YORK COUNTY

3/16/2026

W Broa dw ay

Railroad Ln

Cha rle s L n

S Pine St

EXISTING SPARE /

PROPOSED CONDUIT.

REFER TO ELECTRICAL

SHEETS FOR MORE

DETAIL.

EXISTING 5'X5' LEVEL AREA

REMOVE EXISTING GUIDERAIL

SEGMENT BETWEEN

EXISTING POSTS. REMOVE

EXISTING CONCRETE CURB

(6'-4" LENGTH). SEE SHEET

C-501 FOR MORE DETAIL.

5'

4'

TVM PAD TO BE INSTALLED FLUSH

WITH BACK OF EXISTING SIDEWALK

C-501TVM BASE

C-501 PLAIN CEMEMNT CONCRETE CURB

C-501 CONDUIT TRENCH SECTION

BACK OF CURB TO BE POURED

FLUSH WITH ADJACENT BITUMINOUS

PARKING LOT SURFACE. CURB

REVEAL VARIES TO PROVIDE LEVEL

PAD SURFACE (6" MAXIMUM REVEAL).

C-501FIXED BOLLARD

REVISIONS

A

D

C

B

DATENO. DESCRIPTION

PROJECT:

PLAN SET:

PROJECT LOCATION:

PROJECT NUMBER:

DRAWING TITLE:

SCALE:

DRAWING NUMBER:

54321

54321

DATE:

PREPARED FOR:

SEAL:

SUBCONSULTANT:

c:

\p w w or ki ng \jm t\d

0\ R ed L io n

Si te

L ay ou t.d w g

/1

7/

P: (717) 741-1600 | www.jmt.com

220 ST. CHARLES WAY, SUITE 200 | YORK, PA 17402

C-101

RED LION BUS STOP -

SITE PLAN

CONSTRUCTION PLAN

03/16/2026

24-00558-007

33 W BROADWAY

RED LION, PA 17356

TICKET VENDING

MACHINE SITE

PREPARATION

AS NOTED

C-101

OVERALL LOCATION PLAN - RED LION BUS STOP

SCALE: 1" - 20'

C-101

TVM SITE PLAN - RED LION BUS STOP

SCALE: 1" - 5'

C-101TVM SITE PLAN - RED LION BUS STOP

1 INCH = 5 FEET

5 0 5 10

1 INCH = 20 FEET

20 0 20 40

GENERAL NOTES

1. THE PURPOSE OF THIS PLAN IS TO CONSTRUCT SITE AND ELECTRICAL IMPROVEMENTS FOR THE INSTALLATION (BY OTHERS) OF TICKET VENDING MACHINES

AT VARIOUS SRTA OPERATIONAL FACILITIES.

2. CONTRACTOR TO COORDNATE WITH RABBITTRANIT TO OBTAIN PROJECT SITE ACCESS AND ENSURE ALL LOCAL AND PARTNERING APPROVALS ARE IN PLACE

PRIOR TO THE START OF WORK.

3. EACH TVM LOCATION WORK IS TO BE STARTED AND CONTIOUSLY PERFORMED UNTIL ALL WORK IS COMPLETE AND ACCEPTED BY RABBITRANSIT.

4. THE CONTRACTOR SHALL TAKE ALL NECESSARY PRECAUTIONS TO PROTECT THE EXISTING UTILITIES AND MAINTAIN UNINTERRUPTED SERVICE, UNLESS SPECIFICALLY INDICATED ON THE PLANS AS A UTILITY DISCONNECTION OR ABANDONMENT. ANY DAMAGE CAUSED BY THEIR NEGLIGENCE SHALL BE

IMMEDIATELY AND COMPLETELY REPAIRED AT THE CONTRACTOR'S EXPENSE.

5. THE CONTRACTOR SHALL CHECK AND VERIFY ALL EXISTING CONDITIONS PRIOR TO CONSTRUCTION.

6. UNLESS OTHERWISE INDICATED, THE CONTRACTOR SHALL BE RESPONSIBLE FOR OBTAINING ALL PERMITS.

7. THE CONTRACTOR SHALL BE RESPONSIBLE FOR ALL TRAFFIC CONTROL, TRENCH BARRICADING, COVERING, SHEETING AND SHORING, IN ACCORDANCE WITH APPLICABLE FEDERAL, STATE AND LOCAL REGULATIONS. MAINTENANCE AND PROTECTION OF TRAFFIC ON EXISTING SIDEWALKS AND ROADS NEIGHBORING

THE PROJECT IS THE SOLE RESPONSIBILITY OF THE CONTRACTOR.

8. THE CONTRACTOR IS SOLELY RESPONSIBLE FOR THE CONSTRUCTION MEANS, METHODS, TECHNIQUES, SEQUENCES, PROCEDURES, AND SAFETY

PRECAUTIONS AND PROGRAMS.

9. WHERE IT IS NECESSARY TO CONNECT TO, OR EXTEND TO, EXISTING PAVING, SAW CUT THE EXISTING EDGE OF PAVEMENT NEAT AND SQUARE AND MILL MINIMUM 24" KEY WAY AND OVERLAY AT THE POINT OF TIE-IN TO ENSURE A SMOOTH TRANSITION AND POSITIVE DRAINAGE.

N/F

CODO 200, LP

DEED BOOK 1956; PG 2351

PLAN BOOK DD; PAGE 230

04-066-01-0001.00-00000

N/F

NORTHERN CENTRAL RAILWAY COMPANY

(NO RIGHT-OF-WAY WIDTH RECOVERED)

UT

UT

UT

UT

UT

UT

UT

UT

UT

UT

UT

UT

UC

UC

UC

UC

UC

UC

UC UC UC UC UC UC

UE

UE

UE

UE

UE

UE UE UE UE UE UE UE

SS

SS

SS

SS

SS

SS

SS

SS

SS

SS

SS

SS

SS

SS

SS

SS

SS

SS

SS

SS

SS

TICKET VENDING MACHINE

TO BE SURFACE MOUNTED

TO EXISTING SIDEWALK

SURFACE (BY OTHERS).

EXISTING 5'X5' LEVEL AREA

REMOVE AND RELOCATE

EXISTING SIGN

C-102

KING STREET STATION

- SITE PLAN

CONSTRUCTION PLAN

03/16/2026

24-00558-007

226 W KING STREET

YORK, PA 17401

TICKET VENDING

MACHINE SITE

PREPARATION

AS NOTED

C-102

OVERALL SITE PLAN - KING STREET STATION

SCALE: 1" - 20'

C-102

TVM SITE PLAN - KING STREET STATION

SCALE: 1" - 5'

REVISIONS

A

D

C

B

DATENO. DESCRIPTION

PROJECT:

PLAN SET:

PROJECT LOCATION:

PROJECT NUMBER:

DRAWING TITLE:

SCALE:

DRAWING NUMBER:

54321

54321

DATE:

PREPARED FOR:

SEAL:

SUBCONSULTANT:

c:

\p w w or ki ng \jm t\d

0\ Ki ng S tre et

S ta tio n

Si te

L ay ou t.d w g

/1

6/

P: (717) 741-1600 | www.jmt.com

220 ST. CHARLES WAY, SUITE 200 | YORK, PA 1740202

C-102 TVM SITE PLAN - KING STREET STATION

1 INCH = 20 FEET

20 0 20 40

1 INCH = 5 FEET

5 0 5 10

TICKET VENDING MACHINE

TO BE SURFACE MOUNTED

TO EXISTING SIDEWALK

SURFACE (BY OTHERS).

EXISTING 5'X5' LEVEL AREA

C-103

GETTYSBURG

TRANSFER CENTER -

SITE PLAN

CONSTRUCTION PLAN

03/16/2026

24-00558-007

103 CARLISLE STREET

GETTYSBURG, PA 17325

TICKET VENDING

MACHINE SITE

PREPARATION

AS NOTED

C-103

OVERALL LOCATION PLAN - GETTYSBURG TRANSFER CENTER

SCALE: 1" - 20'

C-103

TVM SITE PLAN - GETTYSBURG TRANSFER CENTER

SCALE: 1" - 5'

REVISIONS

A

D

C

B

DATENO. DESCRIPTION

PROJECT:

PLAN SET:

PROJECT LOCATION:

PROJECT NUMBER:

DRAWING TITLE:

SCALE:

DRAWING NUMBER:

54321

54321

DATE:

PREPARED FOR:

SEAL:

SUBCONSULTANT:

c:

\p w w or ki ng \jm t\d

0\ G et ty sb ur g St at io n Si te L ay ou t.d w g

/1 6/

P: (717) 741-1600 | www.jmt.com

220 ST. CHARLES WAY, SUITE 200 | YORK, PA 17402

C-103 TVM SITE PLAN - GETTYSBURG TRANSFER CENTER

1 INCH = 5 FEET

5 0 5 10

1 INCH = 20 FEET

20 0 20 40

S 2nd St

Market St

N nd S t

TICKET VENDING MACHINE TO BE

SURFACE MOUNTED TO

EXISTING CONCRETE SLAB. FRONT

OF MACHINE TO BE FLUSH WITH

THE SOUTHERN EDGE OF EXISTING

SLAB (BY OTHERS).

EXISTING 5'X5' LEVEL AREA

RELOCATE EXISTING

TRASH RECEPTACLE.

ANCHOR TO EXISTING

CONCRETE PAD.

REVISIONS

A

D

C

B

DATENO. DESCRIPTION

PROJECT:

PLAN SET:

PROJECT LOCATION:

PROJECT NUMBER:

DRAWING TITLE:

SCALE:

DRAWING NUMBER:

54321

54321

DATE:

PREPARED FOR:

SEAL:

SUBCONSULTANT:

c:

\p w w or ki ng \jm t\d

0\ H ar ris bu rg

T ra ns fe r C en te r.d w g

/1

6/

P: (717) 741-1600 | www.jmt.com

220 ST. CHARLES WAY, SUITE 200 | YORK, PA 17402

C-104

HARRISBURG

TRANSFER CENTER -

SITE PLAN

CONSTRUCTION PLAN

03/16/2026

24-00558-007

200 MARKET STREET

HARRISBURG, PA 17101

TICKET VENDING

MACHINE SITE

PREPARATION

AS NOTED

C-104

OVERALL LOCATION PLAN - HARRISBURG TRANSFER CENTER

SCALE: 1" - 20'

C-104

TVM SITE PLAN - HARRISBURG TRANSFER CENTER

SCALE: 1" - 5'

C-104 TVM SITE PLAN - HARRISBURG TRANSFER CENTER

1 INCH = 5 FEET

5 0 5 10

1 INCH = 20 FEET

Aberdeen St

Grace St

M ar ke t S t

Bl ac kb er ry A lle y

S 4th St

TICKET VENDING MACHINE TO BE

SURFACE MOUNTED TO

EXISTING CONCRETE SIDEWALK

(BY OTHERS).

EXISTING 5'X5' LEVEL AREA

REVISIONS

A

D

C

B

DATENO. DESCRIPTION

PROJECT:

PLAN SET:

PROJECT LOCATION:

PROJECT NUMBER:

DRAWING TITLE:

SCALE:

DRAWING NUMBER:

54321

54321

DATE:

PREPARED FOR:

SEAL:

SUBCONSULTANT:

c:

\p w w or ki ng \jm t\d

0\ H

TC

S he lte rs .d w g

/1

6/

P: (717) 741-1600 | www.jmt.com

220 ST. CHARLES WAY, SUITE 200 | YORK, PA 17402

C-105

HARRISBURG TRAIN

STATION - SITE PLAN

CONSTRUCTION PLAN

03/16/2026

24-00558-007

15 ABERDEEN STREET

HARRISBURG, PA 17101

TICKET VENDING

MACHINE SITE

PREPARATION

AS NOTED

C-105

OVERALL LOCATION PLAN - HTC SHELTERS

SCALE: 1" - 20'

C-105

TVM SITE PLAN - HTC SHELTERS

SCALE: 1" - 5'

C-105 TVM SITE PLAN - HTC SHELTERS

1 INCH = 5 FEET

5 0 5 10

1 INCH = 20 FEET

W Emaus St

W M ain St

EXISTING 5'X5"' LEVEL AREA

TICKET VENDING MACHINE

TO BE SURFACE MOUNTED

TO EXISTING CONCRETE SLAB

(BY OTHERS).

EXISTING ELECTRICAL

BOX.

REVISIONS

A

D

C

B

DATENO. DESCRIPTION

PROJECT:

PLAN SET:

PROJECT LOCATION:

PROJECT NUMBER:

DRAWING TITLE:

SCALE:

DRAWING NUMBER:

54321

54321

DATE:

PREPARED FOR:

SEAL:

SUBCONSULTANT:

c:

\p w w or ki ng \jm t\d

0\ M id dl et ow n Tr ai n

St at io n.

dw g

/1

6/

P: (717) 741-1600 | www.jmt.com

220 ST. CHARLES WAY, SUITE 200 | YORK, PA 17402

C-106

MIDDLETOWN TRAIN

STATION - SITE PLAN

CONSTRUCTION PLAN

03/16/2026

24-00558-007

270 W EMAUS STREET

MIDDLETOWN, PA 17057

TICKET VENDING

MACHINE SITE

PREPARATION

AS NOTED

C-106

OVERALL LOCATION PLAN - MIDDLETOWN TRAIN STATION

SCALE: 1" - 20'

C-106

TVM SITE PLAN - MIDDLETOWN TRAIN STATION

SCALE: 1" - 5'

C-106 TVM SITE PLAN - MIDDLETOWN TRAIN STATION

1 INCH = 5 FEET

5 0 5 10

1 INCH = 20 FEET

N 7th St

TICKET VENDING MACHINE

TO BE SURFACE MOUNTED

TO PROPOSED TVM BASE

(BY OTHERS).

EXISTING 5'X5' LEVEL AREA

C-107

HARRISBURG PHEAA -

SITE PLAN

CONSTRUCTION PLAN

03/16/2026

24-00558-007

1200 N 7TH STREET

HARRISBURG, PA 17102

TICKET VENDING

MACHINE SITE

PREPARATION

AS NOTED

REVISIONS

A

D

C

B

DATENO. DESCRIPTION

PROJECT:

PLAN SET:

PROJECT LOCATION:

PROJECT NUMBER:

DRAWING TITLE:

SCALE:

DRAWING NUMBER:

54321

54321

DATE:

PREPARED FOR:

SEAL:

SUBCONSULTANT:

c:

\p w w or ki ng \jm t\d

0\

PH

EA

A.

dw g

/1

6/

P: (717) 741-1600 | www.jmt.com

220 ST. CHARLES WAY, SUITE 200 | YORK, PA 17402

C-107

OVERALL LOCATION PLAN - PHEAA BUS STOP

SCALE: 1" - 20'

C-107

TVM SITE PLAN - PHEAA BUS STOP

SCALE: 1" - 5'

C-107 TVM SITE PLAN - PHEAA BUS STOP

1 INCH = 5 FEET

5 0 5 101 INCH = 20 FEET

20 0 20 40

C-501TVM BASE

C-501 CONDUIT TRENCH SECTION

LIBERTY ST

S H

AN

O

VER

ST

E HIGH ST

EXISTING 5'X5' LEVEL AREA

TICKET VENDING MACHINE

TO BE SURFACE MOUNTED

TO EXISTING CONCRETE

(BY OTHERS).

REVISIONS

A

D

C

B

DATENO. DESCRIPTION

PROJECT:

PLAN SET:

PROJECT LOCATION:

PROJECT NUMBER:

DRAWING TITLE:

SCALE:

DRAWING NUMBER:

54321

54321

DATE:

PREPARED FOR:

SEAL:

SUBCONSULTANT:

c:

\p w w or ki ng \jm t\d

0\ C um be rla nd

C ity

C ou rth ou se S ite L ay ou t.d w g

/1 6/

P: (717) 741-1600 | www.jmt.com

220 ST. CHARLES WAY, SUITE 200 | YORK, PA 17402

C-108

CUMBERLAND

COUNTY

COURTHOUSE - SITE

PLAN

CONSTRUCTION PLAN

03/16/2026

24-00558-007

1 COURTHOUSE SQUARE

CARLISLE, PA 17013

TICKET VENDING

MACHINE SITE

PREPARATION

AS NOTED

C-108

OVERALL LOCATION PLAN - CUMBERLAND COUNTY COURTHOUSE

SCALE: 1" - 20'

C-108

TVM SITE PLAN - CUMBERLAND COUNTY COURTHOUSE

SCALE: 1" - 5'

C-108 TVM SITE PLAN - CUMBERLAND COUNTY COURTHOUSE

1 INCH = 5 FEET

5 0 5 10

1 INCH = 20 FEET

20 0 20 40

C-501 CONDUIT TRENCH SECTION

CORE DRILL EXISTING SITE

WALLS. PROVIDE MINIMUM

REQUIRED DIAMETER TO

ACCEPT 1-1" CONDUIT.

PROVIDE MASONRY

COMPATIBLE EXTERIOR

SILICONE SEALANT

AROUND ANNULAR SPACE.

REVISIONS

A

D

C

B

DATENO. DESCRIPTION

PROJECT:

PLAN SET:

PROJECT LOCATION:

PROJECT NUMBER:

DRAWING TITLE:

SCALE:

DRAWING NUMBER:

54321

54321

DATE:

PREPARED FOR:

SEAL:

SUBCONSULTANT:

c:

\p w w or ki ng \jm t\d

8\ D et ai ls .d w g

/1

7/

P: (717) 741-1600 | www.jmt.com

220 ST. CHARLES WAY, SUITE 200 | YORK, PA 17402

C-501

SITE DETAILS

CONSTRUCTION PLAN

03/16/2026

24-00558-007

TICKET VENDING

MACHINE SITE

PREPARATION

AS NOTED

4" PENNDOT CLASS A CEMENT CONCRETE

2" EXPANSION JOINT WITH SEALANT

BROOM FINISH

SUBBASE, 4" DEPTH (NO. 2A)

TOOL JOINT, 12" DEPTH MIN.,

16" TOP WIDTH

COMPACTED SUBGRADE

4"

4"

6"

12" (TYP)

TRENCH WIDTH

" M

IN

IM

U M

C O

VE

R

FO

R

E

LE

C

TR

IC

LI

G

H

TI

N G

C O

N D

U

IT

D

U C

TB

AN

K

1. WITHIN LAWN AREAS, BACKFILL WITH MECHANICALLY COMPACTED MATERIAL FROM

EXCAVATION. COMPACT IN 12" MAXIMUM LAYERS.

2. WITHIN EXISTING OR PROPOSED PAVEMENT, BACKFILL WITH PENNDOT 2A STONE

AGGREGATE.

3. WITHIN LAWN AREAS, RESTORE SURFACE WITH 6" TOPSOIL, SEED, AND MULCH.

WITHIN LANDSCAPE BED, RESTORE SURFACE WITH 6" TOPSOIL AND HARDWOOD

MULCH.

4. INSTALL 6" WIDE UNDERGROUND DETECTABLE WARNING TAPE. PLACE 1'-0" ABOVE

TOP OF PIPE.

5. FOR INSTALLATION UNDER SIDEWALK FOR SURFACE RESTORATION, SEE FIBER

REINFORCED CONCRETE SIDEWALK DETAIL (01/C-501).

NOTES

12"

WITHIN LAWN / LANDSCAPE BED WITHIN PAVEMENT

BY G.C.

BITUMINOUS PAVEMENT PATCH

FINISHED GRADE

SEE NOTE 3

FULL DEPTH SAWCUT

NEAT AND SQUARE.

TACK PRIOR TO PAVING.

SEE NOTES 1 & 2

O.D. CONDUIT

3" MINIMUM

PROVIDE SHEETING AND SHORING

AS REQUIRED TO CONSTRUCT PIPE

SAND BEDDING

6" PENNDOT CLASS A CEMENT CONCRETE

BROOM FINISH

SUBBASE, 4" DEPTH (NO. 2A)

COMPACTED SUBGRADE

4"

6"

38" X 28"

NOT TO SCALE

C-501

CONDUIT TRENCH SECTION

NOT TO SCALE

C-501

TVM BASE

NOT TO SCALE

C-501

FIBER REINFORCED CONCRETE SIDEWALK

NOTE: 1

2" THICK EXPANSION JOINTS

SHALL BE PROVIDED AT 60' INTERVALS,

AT THE END OF EACH POUR, AT THE

BEGINNING AND END OF ALL RADII, AND

AT ADJACENT STRUCTURES/INLETS.

8"

6"

1"7"

CURB TYPICAL

CROSS SECTION

PENNDOT CLASS A

CEMENT CONCRETE

4" RADIUS

4" RADIUS

CONTRACTION JOINT SPACING

20'-0" M

AX. TO 4'-0" M

IN.

2" DEEP

DETAIL A

CONTRACTION JOINT

NOT TO SCALE

C-501

PLAIN CEMEMNT CONCRETE CURB

38"

SECTION

PLAN

SUPERPAVE ASPHALT MIXTURE DESIGN,

WMA WEARING COURSE, PG 64-22, 0.3

MILLION TO <3 MILLION ESALS, 9.5 MM MIX,

2" DEPTH, SRL-H (OVERLAY)

BITUMINOUS TACK COAT

FULL DEPTH SAW CUT NEAT AND SQUARE

AND TACK PRIOR TO PAVING

PG 64-22 (TYP.)

SUPERPAVE ASPHALT MIXTURE DESIGN,

FLEXIBLE BASE REPLACEMENT, PG 64-22, 0.3

MILLION TO <3 MILLION ESALS, 25 MM MIX,

5" DEPTH

EXISTING BITUMINOUS PAVEMENT

GEOTEXTILE, CLASS 4, TYPE A

COMPACTED SUBGRADE

2'

NOT TO SCALE

C-501

BITUMINOUS PAVEMENT PATCH

NOTE:

1. PAD SIZE TO BE 48"

X 60" AT THE RED

LION SITE. REFER

TO SHEET C-101.

NOT TO SCALE

C-501

RED LION DEMO

REMOVE EXISTING 2X12 BOARDS

FROM GUIDERAIL. CUT AND REMOVE

ALONG ADJACENT I-BEAM POSTS.

SAW CUT AND REMOVE EXISTING

BITUMINOUS PAVEMENT AS

REQUIRED TO INSTALL PROPOSED

CURB, TVM BASE, AND CONDUIT

SAW CUT AND REMOVE 6'-4" OF

EXISTING CONCRETE CURB.

CENTER POINT OF CURB TO

MATCH THE CENTER POINT

OF THE LANDING AREA

OF ADJACENT ADA RAMP.

6" SCHEDULE 40

STEEL PIPE FILLED

WITH PENNDOT

CLASS A CONCRETE

COMPACTED

SUBGRADE.

PAVEMENT

1/8" THICK, HDPE, DOMED

TOP BOLLARD COVER.

COLOR: YELLOW

3' -6

CL

3' -6

6"

6"

12" (MIN.)

PENNDOT CLASS A CONCRETE

FOOTING WITH 1" DOME

FINISHED GRADE

COMPACTED OR

UNDISTURBED SUBGRADE.

NOT TO SCALE

C-501

FIXED BOLLARD

NOT TO SCALE

C-501

TYPICAL FOOTING

C-501 FIXED BOLLARD

JOSEPH W. LAG

Q

SON

LS Letiapie[ac

A

D

C

B

DATENO. DESCRIPTION

PROJECT:

PLAN SET:

PROJECT LOCATION:

PROJECT NUMBER:

DRAWING TITLE:

SCALE:

DRAWING NUMBER:

54321

54321

DATE:

PREPARED FOR:

SEAL:

SUBCONSULTANT:

\\j m t.c or p.

lo ca l\j m td fs \2

4\

8_

7_

Ti ck et _V en di ng _M ac hi

\C

AD

D \E le ct ric al

\E -1

R ed

L io n

- B

S.

dw g

/1 6/

P: (717) 741-1600 | www.jmt.com

220 ST. CHARLES WAY, SUITE 200 | YORK, PA 17402

CONSTRUCTION PLAN

03/16/2026

24-00558-007

TICKET VENDING

MACHINE SITE

PREPARATION

AS NOTED

E-101

RED LION BUS STOP -

ELECTRICAL PLAN

33 W BROADWAY,

RED LION, PA 17356

1. INFORMATION SHOWN ON THIS DRAWING PERTAINING TO EXISTING CONDITIONS HAS BEEN OBTAINED FROM AVAILABLE BUILDING DRAWINGS OR GENERAL FIELD OBSERVATIONS AND MAY NOT INDICATE ACTUAL EXISTING CONDITIONS IN DETAIL OR DIMENSION. THE CONTRACTOR IS RESPONSIBLE FOR DETERMINING THE ACTUAL EXISTING CONDITIONS PRIOR TO FABRICATION OR PERFORMANCE OF ANY WORK. SHOULD CONDITIONS BE DISCOVERED THAT PREVENT EXECUTION OF THE WORK AS INDICATED, THE CONTRACTOR SHALL IMMEDIATELY NOTIFY THE ENGINEER IN WRITING AND AWAIT DIRECTION

BEFORE PROCEEDING WITH THE WORK.

2. UNLESS OTHERWISE NOTED, ELECTRICAL ITEMS SHOWN HEAVY SOLID ( ) SHALL BE NEW,

AND ELECTRICAL ITEMS SHOWN LIGHT SOLID ( ) SHALL BE EXISTING TO REMAIN.

3. REFER TO SHEET E-001 FOR TYPICAL INSTALLATION DETAILS.

GENERAL SHEET NOTES:

SHEET KEYNOTES:

CONTRACTOR SHALL COORDINATE WITH OWNER AND UTILITY COMPANY TO DETERMINE POWER

SOURCE IN DISTRIBUTION CABINET. PROVIDE 20A/1P CIRCUIT BREAKER IN DETERMINED POWER SOURCE. TVM EQUIPMENT SHALL BE SUPPLIED FROM NEW 20A/1P CIRCUIT BREAKER WITH 2#10 AND

1#10 GROUND THROUGH EXISTING CONDUIT.

CONTRACTOR SHALL INSPECT SPARE CONDUIT AND FIELD-VERIFY ROUTING. CONTRACTOR SHALL PROVIDE NEW 1-1/4" DIRECT-BURIED POWER CONDUIT AS REQUIRED FOR FUTURE TVM CONNECTION.

CONTRACTOR SHALL PROVIDE A TEMPORARY SURFACE-MOUNTED NEMA 3R JUNCTION BOX OVER

CONDUIT STUB AND FASTEN TO CONCRETE GRADE WITH TEMPORARY FASTENERS. 6'-0" OF WIRING SLACK SHALL BE PULLED TO PROPOSED TVM LOCATION AND COILED IN TEMPORARY BOX FOR FUTURE INSTALLATION OF TVM EQUIPMENT AND ASSOCIATED CONNECTIONS BY RABBITTRANSIT VENDOR.

TEMPORARY BOX SHALL BE REMOVED BY OTHERS AT TIME OF TVM INSTALLATION.

CONTRACTOR SHALL INTERCEPT AND REMOVE EXISTING STUB-UP LOCATION, AND EXTEND NEW

CONDUIT TO NEW STUB-UP AT PROPOSED TICKET VENDING MACHINE LOCATION.

CONTRACTOR SHALL INTERCEPT AND REMOVE EXISTING STUB-UP LOCATION, AND PROVIDE NEW 12" X 24" ELECTRICAL POWER HANDHOLE IN PLACE. EXISTING SPARE CONDUIT SHALL BE MODIFIED TO TERMINATE AT NEW HANDHOLE; FIELD-VERIFY AND COORDINATE EXACT LOCATION OF HANDHOLE WITH

LOCATION OF EXISTING CONDUIT STUB-UPS.

1" = 10'-0"

ELECTRICAL PLAN - NEW WORK

PLAN NORTH

5'

SCALE: 1"= 10'-0"

0 5' 10'

NEW TICKET

VENDING MACHINE

EXISTING CONDUIT STUB-UP

EXISTING

UTILITY POLE

EXISTING LIGHT POLE

E-101

NEW CONDUIT STUB-UP 3

NEW TICKET VENDING

MACHINE LOCATION

NOT TO SCALE

SITE PHOTO - ETR DISTRIBUTION CABINET4

E-101

ETR DISTRIBUTION

CABINET W/

UTILITY METER

EXISTING LIGHT POLES

EXISTING PARKING LOT

LIGHTING EQUIPMENT

EXISTING WALKWAY

LIGHTING POLE

EXISTING WALKWAY

LIGHTING POLE

EXISTING WALKWAY

LIGHTING POLE

EXISTING WALKWAY

LIGHTING POLE

EXISTING

UTILITY POLES

NOT TO SCALE

SITE PHOTO - TVM LOCATION2

E-101

ETR DISTRIBUTION

CABINET W/

UTILITY METERS

EXISTING CONDUIT

STUB-UP LOCATION

NEW CONDUIT STUB-UP

APPROXIMATE LOCATION OF EXISTING SPARE 1-1/4" CONDUIT

ROUTED TO ETR DISTRIBUTION CABINET. CONTRACTOR

SHALL COORDINATE WITH SITE OWNER AND VERIFY

LOCATION AND SPARE CONDUIT FILL CAPACITY.

APPROXIMATE LOCATION OF

EXISTING CONDUIT STUB-UPS

APPROXIMATE LOCATION OF

EXISTING CONDUIT STUB-UPS

APPROXIMATE LOCATION OF

EXISTING CONDUIT STUB-UPS

NOT TO SCALE

SITE PHOTO - TYPICAL EXISTING CONDUIT STUB-UPS3

E-101 NOT TO SCALE

SITE PHOTO - ETR DISTRIBUTION CABINET INTERIOR5

E-101

TYPICAL EXISTING

CONDUIT STUB-UPS IN

EXISTING PATHWAY TO

DISTRIBUTION CABINET

ASSUMED LOCATION OF EXISTING

SPARE 1-1/4" CONDUIT ROUTED TO

EXISTING STUB-UP AT OPPOSITE

END OF LOT.

PARKING LOT PANEL

EP2: #13

REVISIONS

A

D

C

B

DATENO. DESCRIPTION

PROJECT:

PLAN SET:

PROJECT LOCATION:

PROJECT NUMBER:

DRAWING TITLE:

SCALE:

DRAWING NUMBER:

54321

54321

DATE:

PREPARED FOR:

SEAL:

SUBCONSULTANT:

\\j m t.c or p.

lo ca l\j m td fs \2

4\

8_

7_

Ti ck et _V en di ng _M ac hi

\C

AD

D \E le ct ric al

\E -1

Yo rk

KS

.d w g

/1 6/

P: (717) 741-1600 | www.jmt.com

220 ST. CHARLES WAY, SUITE 200 | YORK, PA 17402

CONSTRUCTION PLAN

03/16/2026

24-00558-007

TICKET VENDING

MACHINE SITE

PREPARATION

AS NOTED

E-102

KING STREET STATION

- ELECTRICAL PLAN

213 W KING STREET,

YORK, PA 17401

1. INFORMATION SHOWN ON THIS DRAWING PERTAINING TO EXISTING CONDITIONS HAS BEEN OBTAINED FROM AVAILABLE BUILDING DRAWINGS OR GENERAL FIELD OBSERVATIONS AND MAY NOT INDICATE ACTUAL EXISTING CONDITIONS IN DETAIL OR DIMENSION. THE CONTRACTOR IS RESPONSIBLE FOR DETERMINING THE ACTUAL EXISTING CONDITIONS PRIOR TO FABRICATION OR PERFORMANCE OF ANY WORK. SHOULD CONDITIONS BE DISCOVERED THAT PREVENT EXECUTION OF THE WORK AS INDICATED, THE CONTRACTOR SHALL IMMEDIATELY NOTIFY THE ENGINEER IN WRITING AND AWAIT DIRECTION

BEFORE PROCEEDING WITH THE WORK.

2. UNLESS OTHERWISE NOTED, ELECTRICAL ITEMS SHOWN HEAVY SOLID ( ) SHALL BE NEW,

AND ELECTRICAL ITEMS SHOWN LIGHT SOLID ( ) SHALL BE EXISTING TO REMAIN.

3. REFER TO SHEET E-001 FOR TYPICAL INSTALLATION DETAILS.

GENERAL SHEET NOTES:

SHEET KEYNOTES:

EXISTING SPARE CIRCUIT WIRING IN SPARE CONDUIT AND TERMINATED IN EXISTING JUNCTION BOX AT

LOCATION SHALL BE RE-USED FOR CONNECTIONS TO NEW TICKET VENDING MACHINE.

CONTRACTOR SHALL FULLY INSPECT AND PERFORM END-TO-END TESTING FOR ALL EXISTING TO REMAIN WIRING TO BE CONNECTED TO NEW DEVICES. CONTRACTOR SHALL REPLACE DAMAGED OR DEFECTIVE CABLING WITH NEW. INSPECTION AND TESTING SHALL BE INCLUDED UNDER BASE BID. REPLACEMENT OF

WIRING SHALL BE PAID OUT UNDER ALLOWANCE.

INSTALLATION OF TVM EQUIPMENT AND ASSOCIATED CONNECTIONS SHALL BE BY RABBITTRANSIT

VENDOR.

CONTRACTOR SHALL EXTEND AND COIL WIRING IN BOX AS REQUIRED TO ALLOW 6'-0" OF WIRING SLACK FOR FUTURE INSTALLATION OF TVM EQUIPMENT AND ASSOCIATED CONNECTIONS BY RABBITTRANSIT

VENDOR. TEMPORARY BOX SHALL BE REMOVED BY OTHERS AT TIME OF TVM INSTALLATION.

1" = 10'-0"

ELECTRICAL PLAN - NEW WORK

PLAN NORTH

5'

SCALE: 1"= 10'-0"

0 5' 10'

NEW TICKET

VENDING MACHINE

ETR PANEL 'EP2'

ETR PANEL 'EP1'

EXISTING CONDUIT

STUB-UP AND WIRING

E-102

NOT TO SCALE

SITE PHOTO - EXISTING ABOVE-GROUND JUNCTION BOX2

E-102 NOT TO SCALE

SITE PHOTO - EXISTING CONDUIT STUB-UP & WIRING3

E-102

ETR JUNCTION BOX

ETR CONDUIT

STUB-UP IN BOX

NEW TICKET VENDING

MACHINE LOCATION

JOSEPH W. LAG

Q

WAITING

TICKETING

OFFICE

SAFE

TOILET

CORRIDOR

WOMEN'S

TOILET

JANITOR

MEN'S

TOILET

MEETING RM

RP: #35

REVISIONS

A

D

C

B

DATENO. DESCRIPTION

PROJECT:

PLAN SET:

PROJECT LOCATION:

PROJECT NUMBER:

DRAWING TITLE:

SCALE:

DRAWING NUMBER:

54321

54321

DATE:

PREPARED FOR:

SEAL:

SUBCONSULTANT:

\\j m t.c or p.

lo ca l\j m td fs \2

4\

8_

7_

Ti ck et _V en di ng _M ac hi

\C

AD

D \E le ct ric al

\E -1

G et ty sb ur g

- T C

.d w g

/1 6/

P: (717) 741-1600 | www.jmt.com

220 ST. CHARLES WAY, SUITE 200 | YORK, PA 17402

CONSTRUCTION PLAN

03/16/2026

24-00558-007

TICKET VENDING

MACHINE SITE

PREPARATION

AS NOTED

E-103

GETTYSBURG

TRANSIT CENTER -

ELECTRICAL PLAN

103 CARLISLE STREET,

GETTYSBURG, PA 17325

1. INFORMATION SHOWN ON THIS DRAWING PERTAINING TO EXISTING CONDITIONS HAS BEEN OBTAINED FROM AVAILABLE BUILDING DRAWINGS OR GENERAL FIELD OBSERVATIONS AND MAY NOT INDICATE ACTUAL EXISTING CONDITIONS IN DETAIL OR DIMENSION. THE CONTRACTOR IS RESPONSIBLE FOR DETERMINING THE ACTUAL EXISTING CONDITIONS PRIOR TO FABRICATION OR PERFORMANCE OF ANY WORK. SHOULD CONDITIONS BE DISCOVERED THAT PREVENT EXECUTION OF THE WORK AS INDICATED, THE CONTRACTOR SHALL IMMEDIATELY NOTIFY THE ENGINEER IN WRITING AND AWAIT DIRECTION

BEFORE PROCEEDING WITH THE WORK.

2. UNLESS OTHERWISE NOTED, ELECTRICAL ITEMS SHOWN HEAVY SOLID ( ) SHALL BE NEW,

AND ELECTRICAL ITEMS SHOWN LIGHT SOLID ( ) SHALL BE EXISTING TO REMAIN.

3. REFER TO SHEET E-001 FOR TYPICAL INSTALLATION DETAILS.

4. FOR CONDUITS SUPPORTED FROM WOOD TRUSSES, SUPPORT CONDUITS FROM BOTTOM CHORD

WHERE DIAGONAL MEMBERS FRAME INTO THE BOTTOM CHORD.

GENERAL SHEET NOTES:

SHEET KEYNOTES:

PROVIDE 2#12 + 1#12G IN 3/4" CONDUIT FROM SPARE 20A/1P CIRCUIT BREAKER IN PANEL 'RP' TO LOCATION OF NEW TICKET VENDING MACHINE. CONTRACTOR SHALL METER EXISTING PANEL AND

FIELD-VERIFY SPARE CAPACITY FOR ADDITION OF 960VA LOAD.

CONTRACTOR SHALL PROVIDE CONDUIT AT CANOPY COLUMN BASE AS PER DETAIL 3 ON SHEET E-001

TO ALLOW REAR-ENTRY TO TICKET VENDING MACHINE.

BASIS OF DESIGN PAINT SYSTEM FOR EXTERIOR GALVANIZED METAL SURFACES:

PRIME COAT: B66-1300 SERIES - PRO INDUSTRIAL PRO-CRYL UNIVERSAL ACRYLIC PRIMER,

INTERMEDIATE COAT: B66-1050 SERIES - PRO INDUSTRIAL DTM ACRYLIC - SEMI-GLOSS

TOP COAT: B66-1050 SERIES - PRO INDUSTRIAL DYM ACRYLIC - SEMI-GLOSS

CONTRACTOR SHALL PROVIDE A TEMPORARY SURFACE-MOUNTED NEMA 3R JUNCTION BOX OVER

CONDUIT TERMINATION AND FASTEN TO CONCRETE GRADE WITH TEMPORARY FASTENERS. 6'-0" OF WIRING SLACK SHALL BE PULLED TO PROPOSED TVM LOCATION AND COILED IN TEMPORARY BOX FOR

FUTURE INSTALLATION OF TVM EQUIPMENT AND ASSOCIATED CONNECTIONS BY RABBITTRANSIT

VENDOR. TEMPORARY BOX SHALL BE REMOVED BY OTHERS AT TIME OF TVM INSTALLATION.

1" = 10'-0"

ELECTRICAL PLAN - NEW WORK

CONDUIT SHALL BE

SURFACE-MOUNTED

TO STRUCTURAL BEAM.

(SEE VIEWS 4 & 5 ON

THIS SHEET)

PLAN NORTH

5'

SCALE: 1"= 10'-0"

0 5' 10'

NEW TICKET

VENDING MACHINE

ETR PANEL 'RP'

CONDUIT SHALL BE

SURFACE-MOUNTED TO WALL.

(SEE VIEWS 3 & 4 ON THIS SHEET)

WALL PENETRATION SHALL BE

SEALED TO MATCH FIRE-RATING

OF EXISTING STRUCTURE.

CONDUIT SHALL BE SURFACE-MOUNTED TO HORIZONTAL

CANOPY BEAM AND ROUTED DOWN COLUMN TO TVM

LOCATION. CONDUIT SHALL BE PAINTED FULLY BEFORE

INSTALLATION TO MATCH EXISTING STEEL FRAMING FINISH.

(SEE VIEW 2 ON THIS SHEET)

E-103

NOT TO SCALE

SITE PHOTO - PROPOSED CONDUIT ROUTING2

E-103 NOT TO SCALE

SITE PHOTO - PROPOSED CONDUIT ROUTING3

E-103 NOT TO SCALE

SITE PHOTO - PROPOSED CONDUIT ROUTING4

E-103

PROPOSED NEW

CONDUIT ROUTING

NEW TICKET VENDING

MACHINE LOCATION

PROPOSED NEW

WALL PENETRATION

PROPOSED NEW

CONDUIT ROUTING

PROPOSED NEW

CONDUIT ROUTING

PROPOSED NEW

CONDUIT ROUTING

TO ELECTRICAL

CLOSET

NOT TO SCALE

SITE PHOTO - PROPOSED CONDUIT ROUTING5

E-103

JOSEPH W. LAG

Q

SON

SHERWIN WILLIAMS

A

D

C

B

DATENO. DESCRIPTION

PROJECT:

PLAN SET:

PROJECT LOCATION:

PROJECT NUMBER:

DRAWING TITLE:

SCALE:

DRAWING NUMBER:

54321

54321

DATE:

PREPARED FOR:

SEAL:

SUBCONSULTANT:

\\j m t.c or p.

lo ca l\j m td fs \2

4\

8_

7_

Ti ck et _V en di ng _M ac hi

\C

AD

D \E le ct ric al

\E -1

H ar ris bu rg

TC

.d w g

/1

6/

P: (717) 741-1600 | www.jmt.com

220 ST. CHARLES WAY, SUITE 200 | YORK, PA 17402

CONSTRUCTION PLAN

03/16/2026

24-00558-007

TICKET VENDING

MACHINE SITE

PREPARATION

AS NOTED

E-104

HARRISBURG

TRANSFER CENTER -

ELECTRICAL PLAN

2ND STREET / MARKET STREET,

HARRISBURG, PA 17101

1. INFORMATION SHOWN ON THIS DRAWING PERTAINING TO EXISTING CONDITIONS HAS BEEN OBTAINED FROM AVAILABLE BUILDING DRAWINGS OR GENERAL FIELD OBSERVATIONS AND MAY NOT INDICATE ACTUAL EXISTING CONDITIONS IN DETAIL OR DIMENSION. THE CONTRACTOR IS RESPONSIBLE FOR DETERMINING THE ACTUAL EXISTING CONDITIONS PRIOR TO FABRICATION OR PERFORMANCE OF ANY WORK. SHOULD CONDITIONS BE DISCOVERED THAT PREVENT EXECUTION OF THE WORK AS INDICATED, THE CONTRACTOR SHALL IMMEDIATELY NOTIFY THE ENGINEER IN WRITING AND AWAIT DIRECTION

BEFORE PROCEEDING WITH THE WORK.

2. UNLESS OTHERWISE NOTED, ELECTRICAL ITEMS SHOWN HEAVY SOLID ( ) SHALL BE NEW,

AND ELECTRICAL ITEMS SHOWN LIGHT SOLID ( ) SHALL BE EXISTING TO REMAIN.

3. REFER TO SHEET E-001 FOR TYPICAL INSTALLATION DETAILS.

GENERAL SHEET NOTES:

SHEET KEYNOTES:

CONTRACTOR SHALL INSPECT SPARE CONDUIT AND FIELD-VERIFY ROUTING TO ADJACENT EQUIPMENT

ENCLOSURE.

PROVIDE 2#12 + 1#12G IN EXISTING SPARE 2" CONDUIT FROM EXISTING LOAD CENTER IN TRANSFER CENTER DISTRIBUTION ENCLOSURE TO LOCATION OF NEW TICKET VENDING MACHINE. CIRCUIT SHALL BE SERVED FROM NEW 20A/1P CIRCUIT BREAKER IN PANEL; CONTRACTOR SHALL PROVIDE NEW BREAKER TO MATCH EXISTING CIRCUIT BREAKER'S TYPE AND AIC RATING. CONTRACTOR SHALL METER EXISTING

PANEL AND FIELD-VERIFY SPARE CAPACITY FOR ADDITION OF 960VA LOAD.

CONTRACTOR SHALL PROVIDE A TEMPORARY SURFACE-MOUNTED NEMA 3R JUNCTION BOX OVER

CONDUIT STUB AND FASTEN TO CONCRETE GRADE WITH TEMPORARY FASTENERS. 6'-0" OF WIRING SLACK SHALL BE PULLED TO PROPOSED TVM LOCATION AND COILED IN TEMPORARY BOX FOR FUTURE INSTALLATION OF TVM EQUIPMENT AND ASSOCIATED CONNECTIONS BY RABBITTRANSIT VENDOR.

TEMPORARY BOX SHALL BE REMOVED BY OTHERS AT TIME OF TVM INSTALLATION.

1" = 10'-0"

ELECTRICAL PLAN - NEW WORK

PLAN NORTH

5'

SCALE: 1"= 10'-0"

0 5' 10'

NEW TICKET

VENDING MACHINE

EXISTING 2"

CONDUIT STUB-UP

EXISTING DISTRIBUTION

ENCLOSURE W/ UTILITY

METER, DISCONNECT, AND

INTERIOR LOAD CENTER

E-104

EXISTING DISTRIBUTION

ENCLOSURE WITH LOAD CENTER

NEW TICKET VENDING

MACHINE LOCATION

NOT TO SCALE

SITE PHOTO - TVM LOCATION2

E-104

EXISTING CONDUIT

STUB-UP LOCATION

NOT TO SCALE

SITE PHOTO - DISTRIBUTION ENCLOSURE INTERIOR3

E-104

JOSEPH W. LAG

Q

J

A

D

C

B

DATENO. DESCRIPTION

PROJECT:

PLAN SET:

PROJECT LOCATION:

PROJECT NUMBER:

DRAWING TITLE:

SCALE:

DRAWING NUMBER:

54321

54321

DATE:

PREPARED FOR:

SEAL:

SUBCONSULTANT:

\\j m t.c or p.

lo ca l\j m td fs \2

4\

8_

7_

Ti ck et _V en di ng _M ac hi

\C

AD

D \E le ct ric al

\E -1

H ar ris bu rg

TS

.d w g

/1

6/

P: (717) 741-1600 | www.jmt.com

220 ST. CHARLES WAY, SUITE 200 | YORK, PA 17402

CONSTRUCTION PLAN

03/16/2026

24-00558-007

TICKET VENDING

MACHINE SITE

PREPARATION

AS NOTED

E-105

HARRISBURG TRAIN

STATION -

ELECTRICAL PLAN

413 ABERDEEN STREET,

HARRISBURG, PA 17101

1. INFORMATION SHOWN ON THIS DRAWING PERTAINING TO EXISTING CONDITIONS HAS BEEN OBTAINED FROM AVAILABLE BUILDING DRAWINGS OR GENERAL FIELD OBSERVATIONS AND MAY NOT INDICATE ACTUAL EXISTING CONDITIONS IN DETAIL OR DIMENSION. THE CONTRACTOR IS RESPONSIBLE FOR DETERMINING THE ACTUAL EXISTING CONDITIONS PRIOR TO FABRICATION OR PERFORMANCE OF ANY WORK. SHOULD CONDITIONS BE DISCOVERED THAT PREVENT EXECUTION OF THE WORK AS INDICATED, THE CONTRACTOR SHALL IMMEDIATELY NOTIFY THE ENGINEER IN WRITING AND AWAIT DIRECTION

BEFORE PROCEEDING WITH THE WORK.

2. UNLESS OTHERWISE NOTED, ELECTRICAL ITEMS SHOWN HEAVY SOLID ( ) SHALL BE NEW,

AND ELECTRICAL ITEMS SHOWN LIGHT SOLID ( ) SHALL BE EXISTING TO REMAIN.

3. REFER TO SHEET E-001 FOR TYPICAL INSTALLATION DETAILS.

GENERAL SHEET NOTES:

SHEET KEYNOTES:

CONTRACTOR SHALL EXTEND EXISTING 120V CIRCUIT IN BUS SHELTER JUNCTION BOX TO LOCATION OF NEW TICKET VENDING MACHINE; PROVIDE 2#12 + 1#12G IN 3/4" CONDUIT AS REQUIRED. CONTRACTOR SHALL METER EXISTING CIRCUIT AND FIELD-VERIFY SPARE CAPACITY FOR ADDITION OF 960VA LOAD.

CONTRACTOR SHALL PROVIDE CONDUIT AT CANOPY COLUMN BASE AS PER DETAIL 3 ON SHEET E-001

TO ALLOW SIDE-ENTRY TO TICKET VENDING MACHINE.

CONTRACTOR SHALL COORDINATE WITH OWNER FOR EXACT LOCATION OF BREAKER SERVING

SHELTER CIRCUIT.

CONTRACTOR SHALL PROVIDE A TEMPORARY SURFACE-MOUNTED NEMA 3R JUNCTION BOX OVER

CONDUIT TERMINATION AND FASTEN TO CONCRETE GRADE WITH TEMPORARY FASTENERS. 6'-0" OF WIRING SLACK SHALL BE PULLED TO PROPOSED TVM LOCATION AND COILED IN TEMPORARY BOX FOR

FUTURE INSTALLATION OF TVM EQUIPMENT AND ASSOCIATED CONNECTIONS BY RABBITTRANSIT

VENDOR. TEMPORARY BOX SHALL BE REMOVED BY OTHERS AT TIME OF TVM INSTALLATION.

BASIS OF DESIGN PAINT SYSTEM FOR EXTERIOR GALVANIZED METAL SURFACES:

PRIME COAT: B66-1300 SERIES - PRO INDUSTRIAL PRO-CRYL UNIVERSAL ACRYLIC PRIMER,

INTERMEDIATE COAT: B66-1050 SERIES - PRO INDUSTRIAL DTM ACRYLIC - SEMI-GLOSS

TOP COAT: B66-1050 SERIES - PRO INDUSTRIAL DYM ACRYLIC - SEMI-GLOSS

1" = 10'-0"

ELECTRICAL PLAN - SHELTER B - NEW WORK

PLAN NORTH

5'

SCALE: 1"= 10'-0"

0 5' 10'

NEW TICKET

VENDING MACHINE

ETR 120V JUCTION BOX MOUNTED

TO BUS SHELTER CANOPY COLUMN

(SEE VIEW 3 ON THIS SHEET)

CONDUIT SHALL BE PAINTED FULLY BEFORE

INSTALLATION TO MATCH EXISTING FINISH AND SHALL

BE SURFACE-MOUNTED TO HORIZONTAL CANOPY BEAM

AND ROUTED DOWN COLUMN TO TVM LOCATION.

(SEE VIEWS 3 & 4 ON THIS SHEET)

CONDUIT SHALL BE ROUTED DOWN COLUMN

TO TVM LOCATION; CONDUIT SHALL BE

PAINTED FULLY BEFORE INSTALLATION TO

MATCH EXISTING COLUMN FINISH.

(SEE VIEW 5 ON THIS SHEET)

E-105

NEW TICKET VENDING

MACHINE LOCATION

NOT TO SCALE

SITE PHOTO - PROPOSED CONDUIT ROUTING3

E-105 NOT TO SCALE

SITE PHOTO - PROPOSED CONDUIT ROUTING4

E-105 NOT TO SCALE

SITE PHOTO - PROPOSED CONDUIT ROUTING5

E-105

ETR JUNCTION BOX

PROPOSED NEW

CONDUIT ROUTING

PROPOSED NEW

CONDUIT ROUTING

PROPOSED NEW

CONDUIT ROUTING

ASSUMED LOCATION OF EXISTING

PANEL SERVING SHELTER B CIRCUIT3

EXISTING SHELTER B

1" = 30'-0"

ELECTRICAL SITE PLAN OVERVIEW2

E-105

SCALE: 1"= 30'-0"

15' 15'0 30'

JOSEPH W. LAG

Q

SON

SHERWIN WILLIAMS

JNTPP-3: #13 NTPP-3: #13

A

D

C

B

DATENO. DESCRIPTION

PROJECT:

PLAN SET:

PROJECT LOCATION:

PROJECT NUMBER:

DRAWING TITLE:

SCALE:

DRAWING NUMBER:

54321

54321

DATE:

PREPARED FOR:

SEAL:

SUBCONSULTANT:

\\j m t.c or p.

lo ca l\j m td fs \2

4\

8_

7_

Ti ck et _V en di ng _M ac hi

\C

AD

D \E le ct ric al

\E -1

M id dl et ow n

- T S.

dw g

/1

6/

P: (717) 741-1600 | www.jmt.com

220 ST. CHARLES WAY, SUITE 200 | YORK, PA 17402

CONSTRUCTION PLAN

03/16/2026

24-00558-007

TICKET VENDING

MACHINE SITE

PREPARATION

AS NOTED

E-106

MIDDLETOWN TRAIN

STATION -

ELECTRICAL PLAN

270 W EMAUS STREET,

MIDDLETOWN PA 17057

1. INFORMATION SHOWN ON THIS DRAWING PERTAINING TO EXISTING CONDITIONS HAS BEEN OBTAINED FROM AVAILABLE BUILDING DRAWINGS OR GENERAL FIELD OBSERVATIONS AND MAY NOT INDICATE ACTUAL EXISTING CONDITIONS IN DETAIL OR DIMENSION. THE CONTRACTOR IS RESPONSIBLE FOR DETERMINING THE ACTUAL EXISTING CONDITIONS PRIOR TO FABRICATION OR PERFORMANCE OF ANY WORK. SHOULD CONDITIONS BE DISCOVERED THAT PREVENT EXECUTION OF THE WORK AS INDICATED, THE CONTRACTOR SHALL IMMEDIATELY NOTIFY THE ENGINEER IN WRITING AND AWAIT DIRECTION

BEFORE PROCEEDING WITH THE WORK.

2. UNLESS OTHERWISE NOTED, ELECTRICAL ITEMS SHOWN HEAVY SOLID ( ) SHALL BE NEW,

AND ELECTRICAL ITEMS SHOWN LIGHT SOLID ( ) SHALL BE EXISTING TO REMAIN.

3. REFER TO SHEET E-001 FOR TYPICAL INSTALLATION DETAILS.

GENERAL SHEET NOTES:

SHEET KEYNOTES:

CONTRACTOR SHALL EXTEND EXISTING 120V CIRCUIT FROM BUS SHELTER JUNCTION BOX TO LOCATION

OF NEW TICKET VENDING MACHINE; PROVIDE 2#12 + 1#12G IN 3/4" CONDUIT AS REQUIRED.

CONTRACTOR SHALL METER EXISTING CIRCUIT AND FIELD-VERIFY SPARE CAPACITY FOR ADDITION OF

960VA LOAD.

CONTRACTOR SHALL PROVIDE CONDUIT FROM EXISTING JUNCTION BOX AS PER DETAIL 3 ON SHEET

E-001 TO ALLOW REAR-ENTRY TO TICKET VENDING MACHINE.

CONTRACTOR SHALL COORDINATE WITH OWNER FOR EXACT LOCATION OF BREAKER SERVING

SHELTER CIRCUIT.

CONTRACTOR SHALL PROVIDE A TEMPORARY SURFACE-MOUNTED NEMA 3R JUNCTION BOX OVER

CONDUIT STUB AND FASTEN TO CONCRETE GRADE WITH TEMPORARY FASTENERS. 6'-0" OF WIRING SLACK SHALL BE PULLED TO PROPOSED TVM LOCATION AND COILED IN TEMPORARY BOX FOR FUTURE INSTALLATION OF TVM EQUIPMENT AND ASSOCIATED CONNECTIONS BY RABBITTRANSIT VENDOR.

TEMPORARY BOX SHALL BE REMOVED BY OTHERS AT TIME OF TVM INSTALLATION.

1" = 10'-0"

ELECTRICAL PLAN - WEST SHELTER - NEW WORK

5'

SCALE: 1"= 10'-0"

0 5' 10'

PLAN NORTH

NEW TICKET

VENDING MACHINE

ETR JUNCTION

BOX MOUNTED TO

CANOPY COLUMN

ETR SHELTER

RECEPTACLE

1 2

E-106

NOT TO SCALE

SITE PHOTO - TVM LOCATION2

E-106

NEW TICKET VENDING

MACHINE LOCATION

ETR JUNCTION BOX

1" = 30'-0"

ELECTRICAL SITE PLAN OVERVIEW3

E-106

ASSUMED LOCATION OF EXISTING PANEL

NTPP-3 SERVING WEST SHELTER CIRCUIT 3

EXISTING WEST

SHELTER

SCALE: 1"= 30'-0"

15' 15'0 30'

JOSEPH W. LAG

Q

GB: #9

A

D

C

B

DATENO. DESCRIPTION

PROJECT:

PLAN SET:

PROJECT LOCATION:

PROJECT NUMBER:

DRAWING TITLE:

SCALE:

DRAWING NUMBER:

54321

54321

DATE:

PREPARED FOR:

SEAL:

SUBCONSULTANT:

\\j m t.c or p.

lo ca l\j m td fs \2

4\

8_

7_

Ti ck et _V en di ng _M ac hi

\C

AD

D \E le ct ric al

\E -1

H ar ris bu rg

P.

dw g

/1 6/

P: (717) 741-1600 | www.jmt.com

220 ST. CHARLES WAY, SUITE 200 | YORK, PA 17402

CONSTRUCTION PLAN

03/16/2026

24-00558-007

TICKET VENDING

MACHINE SITE

PREPARATION

AS NOTED

E-107

HARRISBURG PHEAA -

ELECTRICAL PLAN

1200 N 7TH STREET,

HARRISBURG, PA 17102

1. INFORMATION SHOWN ON THIS DRAWING PERTAINING TO EXISTING CONDITIONS HAS BEEN OBTAINED FROM AVAILABLE BUILDING DRAWINGS OR GENERAL FIELD OBSERVATIONS AND MAY NOT INDICATE ACTUAL EXISTING CONDITIONS IN DETAIL OR DIMENSION. THE CONTRACTOR IS RESPONSIBLE FOR DETERMINING THE ACTUAL EXISTING CONDITIONS PRIOR TO FABRICATION OR PERFORMANCE OF ANY WORK. SHOULD CONDITIONS BE DISCOVERED THAT PREVENT EXECUTION OF THE WORK AS INDICATED, THE CONTRACTOR SHALL IMMEDIATELY NOTIFY THE ENGINEER IN WRITING AND AWAIT DIRECTION

BEFORE PROCEEDING WITH THE WORK.

2. UNLESS OTHERWISE NOTED, ELECTRICAL ITEMS SHOWN HEAVY SOLID ( ) SHALL BE NEW,

AND ELECTRICAL ITEMS SHOWN LIGHT SOLID ( ) SHALL BE EXISTING TO REMAIN.

3. REFER TO SHEET E-001 FOR TYPICAL INSTALLATION DETAILS.

GENERAL SHEET NOTES:

SHEET KEYNOTES:

CONTRACTOR SHALL PROVIDE NEW BREAKER TO MATCH EXISTING CIRCUIT BREAKER'S TYPE AND AIC

RATING.

CONTRACTOR SHALL PROVIDE NEW 1" DIRECT-BURIED POWER CONDUIT WITH ASSOCIATED WIRING

FROM GUARD BOOTH TO TICKET VENDING MACHINE ENCLOSURE LOCATION.

PROVIDE 2#12 + 1#12G IN 1" CONDUIT FROM NEW 20A/1P CIRCUIT BREAKER IN PANEL 'GB' TO LOCATION OF NEW TICKET VENDING MACHINE. CONTRACTOR SHALL METER EXISTING PANEL AND FIELD-VERIFY

SPARE CAPACITY FOR ADDITION OF 960VA LOAD.

CONDUIT AT TICKET VENDING MACHINE LOCATION SHALL STUB-UP BETWEEN 1/4" AND 1/2" ABOVE

FINISHED GRADE.

CONTRACTOR SHALL PROVIDE A TEMPORARY SURFACE-MOUNTED NEMA 3R JUNCTION BOX OVER

CONDUIT STUB AND FASTEN TO CONCRETE GRADE WITH TEMPORARY FASTENERS. 6'-0" OF WIRING SLACK SHALL BE PULLED TO PROPOSED TVM LOCATION AND COILED IN TEMPORARY BOX FOR FUTURE INSTALLATION OF TVM EQUIPMENT AND ASSOCIATED CONNECTIONS BY RABBITTRANSIT VENDOR.

TEMPORARY BOX SHALL BE REMOVED BY OTHERS AT TIME OF TVM INSTALLATION.

1" = 10'-0"

ELECTRICAL PLAN - NEW WORK

PLAN NORTH

5'

SCALE: 1"= 10'-0"

0 5' 10'

NEW TICKET

VENDING MACHINE

ETR PANEL 'GB' IN

GUARD BOOTH 1

2 3

NEW CONDUIT

STUB-UP AT

EQUIPMENT PAD

E-107

NOT TO SCALE

SITE PHOTO - TVM LOCATION2

E-107

NEW TICKET VENDING

MACHINE LOCATION

NOT TO SCALE

SITE PHOTO - PANEL LOCATION3

E-107

ETR GUARD

BOOTH PANELETR GUARD BOOTH

ETR GUARD BOOTH

CONDUIT SHALL EMERGE ABOVE-GROUND AND ENTER GUARD

BOOTH VIA NEW WALL PENETRATION; PENETRATION SHALL BE

SEALED TO MATCH RATINGS OF EXISTING STRUCTURE. SEAL

PENETRATION WITH DOWSIT 795 OR EQUAL NEUTRAL

ONE-PART SILICONE SEALANT WITH +/-50% MOVEMENT.

JOSEPH W. LAG

Q

TELECOM

STORAGE

RECEIVING

REVISIONS

A

D

C

B

DATENO. DESCRIPTION

PROJECT:

PLAN SET:

PROJECT LOCATION:

PROJECT NUMBER:

DRAWING TITLE:

SCALE:

DRAWING NUMBER:

54321

54321

DATE:

PREPARED FOR:

SEAL:

SUBCONSULTANT:

\\j m t.c or p.

lo ca l\j m td fs \2

4\

8_

7_

Ti ck et _V en di ng _M ac hi

\C

AD

D \E le ct ric al

\E -1

C ar lis le

C

C C

.d w g

/1 6/

P: (717) 741-1600 | www.jmt.com

220 ST. CHARLES WAY, SUITE 200 | YORK, PA 17402

CONSTRUCTION PLAN

03/16/2026

24-00558-007

TICKET VENDING

MACHINE SITE

PREPARATION

AS NOTED

E-108

CUMBERLAND

COUNTY

COURTHOUSE -

ELECTRICAL PLAN

1 COURTHOUSE SQUARE,

CARLISLE, PA 17013

1. INFORMATION SHOWN ON THIS DRAWING PERTAINING TO EXISTING CONDITIONS HAS BEEN OBTAINED FROM AVAILABLE BUILDING DRAWINGS OR GENERAL FIELD OBSERVATIONS AND MAY NOT INDICATE ACTUAL EXISTING CONDITIONS IN DETAIL OR DIMENSION. THE CONTRACTOR IS RESPONSIBLE FOR DETERMINING THE ACTUAL EXISTING CONDITIONS PRIOR TO FABRICATION OR PERFORMANCE OF ANY WORK. SHOULD CONDITIONS BE DISCOVERED THAT PREVENT EXECUTION OF THE WORK AS INDICATED, THE CONTRACTOR SHALL IMMEDIATELY NOTIFY THE ENGINEER IN WRITING AND AWAIT DIRECTION BEFORE PROCEEDING WITH THE WORK.

2. UNLESS OTHERWISE NOTED, ELECTRICAL ITEMS SHOWN HEAVY SOLID ( ) SHALL BE NEW, AND

ELECTRICAL ITEMS SHOWN LIGHT SOLID ( ) SHALL BE EXISTING TO REMAIN.

3. REFER TO SHEET E-001 FOR TYPICAL INSTALLATION DETAILS.

GENERAL SHEET NOTES:

SHEET KEYNOTES:

CONTRACTOR SHALL PROVIDE NEW BREAKER TO MATCH EXISTING CIRCUIT BREAKER'S TYPE AND AIC RATING.

CONTRACTOR SHALL PROVIDE NEW 1" DIRECT-BURIED POWER CONDUIT WITH ASSOCIATED WIRING FROM COURTHOUSE BUILDING TO TICKET VENDING MACHINE ENCLOSURE LOCATION. CONDUIT SHALL BE ROUTED

THROUGH RAISED PLANTER BED AND SHALL AVOID EXISTING OBSTRUCTIONS.

PROVIDE 2#12 + 1#12G IN 1" CONDUIT FROM NEW 120V/20A/1P CIRCUIT BREAKER IN ETR COURTHOUSE BUILDING TELECOM PANEL TO LOCATION OF NEW TICKET VENDING MACHINE. CONTRACTOR SHALL METER

EXISTING PANEL AND FIELD-VERIFY SPARE CAPACITY FOR ADDITION OF 960VA LOAD.

CONTRACTOR SHALL PROVIDE CONDUIT AT PLANTER WALL BASE AS PER DETAIL 3 ON SHEET E-001 TO ALLOW

REAR-ENTRY TO TICKET VENDING MACHINE.

OBTAIN APPROVAL FOR PROPOSED WORK FROM RABBITTRANSIT AND BUILDING OWNER PRIOR TO

PERFORMANCE OF WORK.

CONDUIT SHALL POKE-THROUGH PLANTER WALL AND BE SURFACE-MOUNTED ALONG WALKWAY WALL.

CONDUIT SHALL BE ROUTED UNDER RAISED EQUIPMENT PAD TO BUILDING.

(SEE VIEWS 3 & 4 ON THIS SHEET)

EXTERIOR WALL PENETRATION SHALL BE SEALED TO MATCH FIRE-RATING OF EXISTING STRUCTURE.

(SEE VIEW 4 ON THIS SHEET)

CONDUIT SHALL POKE-THROUGH INTO BUILDING AND BE ROUTED INTO STORAGE CLOSET. CONDUIT SHALL BE SURFACE-MOUNTED TO CEILING AND WALL AND SHALL BE ROUTED ALONG EXISTING CONDUITS INTO TELECOM ROOM VIA EXISTING INTERIOR WALL PENETRATIONS. (SEE VIEWS 5, 6, & 7 ON THIS SHEET)

CONTRACTOR SHALL PROVIDE A TEMPORARY SURFACE-MOUNTED NEMA 3R JUNCTION BOX OVER CONDUIT TERMINATION AND FASTEN TO PLANTER WALL WITH TEMPORARY FASTENERS. 6'-0" OF WIRING SLACK SHALL BE PULLED TO PROPOSED TVM LOCATION AND COILED IN TEMPORARY BOX FOR FUTURE INSTALLATION OF TVM EQUIPMENT AND ASSOCIATED CONNECTIONS BY RABBITTRANSIT VENDOR. TEMPORARY BOX SHALL BE

REMOVED BY OTHERS AT TIME OF TVM INSTALLATION.

1" = 10'-0"

ELECTRICAL PLAN - NEW WORK

5'

SCALE: 1"= 10'-0"

0 5' 10'

PLAN NORTH

NEW TICKET

VENDING MACHINE

E-108

CONDUIT SHALL POKE-

THROUGH PLANTER WALL AT

EQUIPMENT LOCATION.

(SEE VIEW 2 ON THIS SHEET)

EXISTING BUILDING TO

SERVE NEW TICKET

VENDING MACHINE

12 3

ETR GROUND-MOUNTED

LIGHTING FIXTURE

ETR GROUND-MOUNTED

LIGHTING FIXTURE

ETR BUS SHELTER

ETR MECHANICAL

EQUIPMENT PADS

NEW TICKET VENDING

MACHINE LOCATION

NOT TO SCALE

SITE PHOTO - PROPOSED CONDUIT ROUTING4

E-108

ETR PANEL 'TELECOM'

ETR UNDERGROUND TANK

ETR DRAINAGE

PIPE

NOT TO SCALE

SITE PHOTO - PROPOSED CONDUIT ROUTING5

E-108 NOT TO SCALE

SITE PHOTO - PROPOSED CONDUIT ROUTING6

E-108 NOT TO SCALE

SITE PHOTO - PROPOSED CONDUIT ROUTING7

E-108

NOT TO SCALE

SITE PHOTO - PROPOSED CONDUIT ROUTING2

E-108 NOT TO SCALE

SITE PHOTO - PROPOSED CONDUIT ROUTING3

E-108

PROPOSED NEW

CONDUIT ROUTING

PROPOSED NEW

CONDUIT ROUTING

PROPOSED NEW

CONDUIT ROUTING

PROPOSED NEW

CONDUIT ROUTING

PROPOSED NEW

CONDUIT ROUTING

PROPOSED NEW PLANTER

WALL PENETRATION

PROPOSED NEW PLANTER

WALL PENETRATION

PROPOSED NEW

EXTERIOR WALL

PENETRATION

INTO CHASE

ETR INTERIOR WALL

PENETRATION

FROM CHASE

ETR INTERIOR WALL

PENETRATION INTO

TELECOM ROOM

ETR INTERIOR WALL

PENETRATION FROM CLOSET

JOSEPH W. LAG

Q

Sheets and Views
CS-001 COVER SHEET
C-101 RED LION BUS STOP - SITE PLAN
OVERALL LOCATION PLAN - RED LION STATION
TVM SITE PLAN - RED LION STATION
C-102 KING STREET STATION - SITE PLAN
OVERALL SITE PLAN - KING STREET STATION
TVM SITE PLAN - KING STREET STATION
C-103 Gettysburg TRANSFER CENTER - SITE PLAN
OVERALL LOCATION PLAN - GETTYSBURG STATION
TVM SITE PLAN - GETTYSBURG STATION
C-104 HARRISBURG TRANSFER CENTER - SITE PLAN
OVERALL LOCATION PLAN - HARRISBURG TRANSFER STATION
TVM SITE PLAN - HARRISBURG TRANSFER STATION
C-105 HARRISBURG TRAIN STATION - SITE PLAN
OVERALL LOCATION PLAN - HTC SHELTERS
TVM SITE PLAN - HTC SHELTERS
C-106 MIDDLETOWN TRAIN STATION - SITE PLAN
OVERALL LOCATION PLAN - MIDDLETOWN TRAIN STATION
TVM SITE PLAN - MIDDLETOWN TRAIN STATION
C-107 HARRISBURG PHEAA - SITE PLAN
OVERALL LOCATION PLAN - PHEAA STATION
TVM SITE PLAN - PHEAA BUS STOP
C-108 Cumberland County Courthouse - SITE PLAN
OVERALL LOCATION PLAN - CUMBERLAND CITY COURTHOUSE
TVM SITE PLAN - CUMBERLAND CITY COURTHOUSE
C-501 SITE DETAILS
FIBER REINFORCED CONCRETE SIDEWALK
CONDUIT & DUCTBANK TRENCH SECTION
TVM Base
PLAIN CEMEMNT CONCRETE CURB
BITUMINOUS PAVEMENT PATCH
RED LION DEMO