About this file

This document contains a second floor plumbing plan for a medical facility renovation project and the related federal contract opportunity solicitation. The plumbing plan details the layout and specifications of domestic water, sanitary, storm, and medical gas piping for an area of approximately 14,100 square feet. Piping includes sizes from 1/2 inch to 12 inches in diameter with associated valves, manifolds, and fixtures. The federal contract opportunity is a request for proposal to provide site preparation work for installation of a new dual energy CT scanner, with responses due by June 15, 2022. The awarded firm will be responsible for demolition, excavation, and installation of underground utilities to support the new medical imaging equipment.

View the file

Other files

File Type Posted
36C25622R0075 0001.docx DOCX document
2PG102-E Interstitial Piping.pdf PDF
2PG102-E Medical Gas.pdf PDF
2EP102-E2 Power Plan.pdf PDF
01913-2FX102-E2 Fire Protection.pdf PDF
01963-2FA102-E2 Fire Alarm.pdf PDF
02049-2PL701-E Supply Riser.pdf PDF
ICRA ILSM NEPA FY 21-1 CT Scanner Project 03222022.xlsx XLSX spreadsheet
36C25622R0075 Wage Determination.pdf PDF
02157-2MH102-E2 Ductwork.pdf PDF
36C25622R0075 - Proj 629-22-135 VHA Supplemental Contract Rqts for Combatting COVID-19.docx DOCX document
2AI102-E2 BLDG 2- SECOND FLOOR -AREA E1 AND E2.pdf PDF
2PL801-E Drainage Riser.pdf PDF
0073-2SB101-E Floor Plan.pdf PDF
0089-2SF102-E Framing Plan.pdf PDF
S02 Solicitation 36C25622R0075.pdf PDF
01841-2AF601 Room Finishes.pdf PDF
FINAL SPECS-Site Prep for Dual Energy CT-03312022.docx DOCX document
02098-2PG102-E Medical Gas.pdf PDF
36C25622R0075 Exhibit A Contractor Evaluation Form - Construction Safety.docx DOCX document
01756-2AI422-1 Enlarged View.pdf PDF
Aquilion One PRISM Edition-Site Specific Drawing.pdf PDF
02338-2EL102-E2 Lighting Plan.pdf PDF
Aquilion One PRISM 320-640 HCE Couch Drawings.pdf PDF
02456-2EP418 Enlarged Image n Intervnt Plan.pdf PDF
Show all 25

On GovTribe

Work with this file

  • Download the original file
  • Contacts named in this file
  • Similar government files
  • Ask GovTribe AI about this file

Text version

UP

P-414 P-414

P-414

P-104A

P-414

P-414

P-528

P-414

P-414

P-414

P-414

P-414

P-414

P-414P-414

P-504

P-414 P-104A

P-701

P-414

P-104A

P-414

P-414

P-414

2P102-D

2P102-E

2P102-E

2P102-F

P-104

P-414

INTERVIEW

2F101

CORR

2E-C12

CORR

2E-C02

CORR

2E-C05

CORR

2E-C09

CORR

2E-C10

CORR

2E-C11

CORR

2E-C06

CORR

2E-C01

ACUTE-2

2E146

REF:2E157

DECONTAM

2E178

WORK

2E152B

ACUTE-1

2E147

REF:2E157

T/D

2E125

RADIOLOGY

2E132

RADIOLOGY

2E130

T/D

2E126

CT

SCAN

2E129

CONTROL

2E128

REF:2E107

SCR

2E109

CONTROL

2E107

HK

2E170

REF:1D217

T

2E167A

ALCOVE

2E160

ACUTE-11

2E166

REF:2E157

ACUTE-3

2E145

REF:2E157

ACUTE-4

2E144

REF:2E157

ACUTE-5

2E140

REF:2E157

ACUTE-6

2E155

ACUTE-7

2E156

REF:2E157

ACUTE-8

2E157

MEDS

2E154

WORK

2E152C

BLOOD

GAS

2E164

CONSULT

2E180

PACS

2E152E

MULTI-PURPOSE

2E175

CLEAN

2E149

TRIAGE

2E150

SCR

2E137

REF:2E109

HC

PATIENT

T/S

2E169

NURSE

STATION

2E152A

ISO

ACUTE-12

2E167

T

2E148

HK

2E138

REF:1D217 SIM

RAD

EQUIP

2E106

MH T

2E168

RAD

STRETCHER/WC

2E134

W C

/S T

R E

T C

H

S T

O R

E

STAFF

WORK

2E136

DRESS

2E115

REF:2E117

CC

2E139

RAD

ELEC

RM

2E105

EC

2E174

ALCOVE

2E151

NURSE

STATION

2E152D

COPY/WORK

2E153

REF:3G179

DRESS

2E116

REF:2E117

HK

2E104

REF:1D217

ACUTE-9

2E158

REF:2E157

ISO/GYN

ACUTE-10

2E159

T

2E159A

ENTRANCE

VESTIBULE

2E176

EQUIP

2E135

EQUIPMENT

2E133

CT

SCAN

2E108

CT

SCAN

2E110

CONTROL

2E111

REF:2E107

CT

PREP/WORK

2E114

CT

PREP

2E127

DRESS

2E118

REF:2E117

DRESS

2E119

REF:2E117

T/D

2E124

T/D

2E120

TELECOM

2E227A

NORM

ELEC

2E227C

EMER

ELEC

2E227D

SCRUB

VENDING

2E101C

SECURITY

2E227B

CLEAN

2E102

REF:2D161

ST

2E101A

LOCKER

ROOM

2E101

ST

2E101B

INTERVIEW

2E103A

INTERVIEW

2E103B

COMPLEX

TREATMENT

2E165

NURSE

MANAGER

2E181

COPY/WORK

2E182

MH-2

2E187

MH-RESTRAINT

2E189

RES

CONF/WORK

2E193

FAST

TRACK-8

2E195

CORR

2E-C07

CORR

2E-C08

DRESS

2E117

SHAFT

SHE06

SHAFT

SHE07

6"SS UP & DN

4"VS UP & DN

4"DCWL UP & 3"DN

2 1/2"DHWL UP & 1 1/2"DN

1 1/4"DHWLR UP & 3/4"DN

2"W UP

2"W UP

2"W UP

2"W UP

2"W UP

2"W UP

2"W UP

2"W UP

2"W UP

2"W UP

2"W UP

2"W UP

2"W UP

2"W UP

4"S UP

4"S UP

2"W UP 2"W UP

4"S UP

10"RL UP (14,100 SQ.FT.)

& 12"DN (22,870 SQ.FT.)

1/2"DHWL DROP

2"W DN & V RISE

1/2"DCWL DROP

P-414

P-414 P-414

P-414

P-414

P-414

P-414

P-414

P-504

P-414

P-414

P-504 P-414

P-414

P-104A

P-414

P-104A

P-414

P-104A

P-414

P-104A

P-414

P-414

1 1/4" DHWL1 1/4" DHWL

1/2" DCWL

1/2"DHWL DROP

2"W DN & V RISE

1/2"DCWL DROP

1/2"DCWL DROP

2"W DN & V RISE

1/2"DHWL DROP

4"S DN & 2" V RISE

2"DCWL DROP

1/2"DHWL DROP

2"W & V RISE

1/2"DCWL DROP

2"W DN & V RISE

1/2"DHWL DROP

1/2"DHWL DROP

2"W DN & V RISE

1/2"DCWL DROP

1/2"DCWL DROP

2"W DN & V RISE

1/2"DHWL DROP

1/2" DCWL

1/2"DHWL DROP

2"W DN & V RISE

1/2"DCWL DROP

1/2"DHWL DROP

2"W DN & V RISE

1/2"DCWL DROP

1/2"DHWL DROP

2"W DN & V RISE

1/2"DCWL DROP

1/2" DCWL

2" D

C W

L

2" DCWL

2" D

C W

L

1/2"DCWL DROP

2"W DN & V RISE

1/2"DHWL DROP

1/2"DHWL DROP

2"W DN & V RISE

1/2"DCWL DROP

1/2"DHWL DROP

2"W DN & V RISE

1/2"DCWL DROP

4"S DN & 2" V RISE

2"DCWL DROP

2"W & V RISE

1/2"DHWL DROP

1/ 2"

D H

W L

1/2" DCWL

3/ 4"

D C

W L

3/ 4"

D C

W L

1/2"DCWL DROP

2"W DN & V RISE

1/2"DHWL DROP

1/2"DCWL DROP

2"W DN & V RISE

1/2"DHWL DROP

1/ 2"

D H

W L

1/

4" D

C W

L

1/2"DCWL DROP

2"W DN & V RISE

1/2"DHWL DROP

2" D

C W

L 3/

4" D

C W

L

1/ 2"

D H

W L

1/2"DCWL DROP

2"W DN & V RISE

1/2"DHWL DROP

2"V DN & RISE

3"W DN

3/4"DCWL DROP

3/4"DHWL DROP

1/2"DHWL DROP

2"W DN & V RISE

1/2"DCWL DROP

1/2"DHWL DROP

2"W DN & V RISE

1/2"DCWL DROP

3/4" DCWL

3/ 4"

D H

W L

1 1/4" DHWL

2"W UP

2"W UP

1/

2" D

C W

L

4"VS UP & DN

4"SS UP & DN

3"V DN & RISE

2"W UP

1/2"DHWL DROP

2"W DN & V RISE

1/2"DCWL DROP

1/2"DCWL DROP

2"W DN & V RISE

1/2"DHWL DROP

2"W UP

2"W UP

2"W UP

TMV

2"W & V RISE

1/2"DHWL DROP

2"DCWL DROP

4"S DN & 2" V RISE

4"S UP

3/4"DCWL DROP

2"V DN & RISE

3"W DN

3/4"DHWL DROP

1/2"DHWL DROP

2"W DN & V RISE

1/2"DCWL DROP

2"W DN & V RISE

1/2"DHWL DROP

1 1/2"DCWL DROP

4"S DN & 2" V RISE

4"SS UP&DN

4"VS UP&DN

4"SS UP&DN

4"VS UP&DN

4"S DN & 2" V RISE

2"DCWL DROP

2"W DN & V RISE

1/2"DHWL DROP

1/2"DCWL DROP

2"W DN & V RISE

1/2"DHWL DROP

2"W UP

1/2"DHWL DROP

2"V DN & RISE

2"W DN

1/2"DCWL DROP

4"S DN & 2" V RISE

2"DCWL DROP

2"W & V RISE

1/2"DHWL DROP

2" DHWL

1 1/4" DCWL

1 1/4" DHWL

1" DHWL

1" DHWL

1" D

H W

L

1" DHWL

1 1/4" DHWL

3/ 4"

D C

W L

3" DCWL

1 1/4" DHWL

3/ 4"

D C

W L

2" D

C W

L

3/ 4"

D C

W L

1" DHWL 1" DHWL

3/ 4"

D C

W L

2" D

C W

L

1 1/4" DHWL

1 1/2" DCWL

1 1/4" DHWL

P-104A

P-519A

3" DCWL

2" V

2" V

2" V

2" V

2" V

2" V

4"FD-B

4"FD-B

(2)4"V DN&RISE

4"W&T UP

4"V UP

4"V UP

4"W&T UP

(2)1/2"TP UP

TO MANIFOLD

TP MANIFOLD

3/4"DCWL DROP

(2)1/2"TP DN

TO FD'S

1 1/4"DCWL DROP

2"W DN & V RISE

TMV

1 1/2"TW RISE

1-1/4"DHWL DROP

1/2" TP

1/2" TP

4" SAN (M.C.)

2" SAN (M.C.)

3" SAN (M.C.) 3" SAN (M.C.)

2" S

A N

(M .C

3/ 4"

D C

W L

P-804

AHU BY HVAC

AHU BY HVAC

3/4"DCWL DROP

4"S DN & 2" V RISE

2"DCWL DROP

1/2"DHWL DROP

2"W & V RISE

1/2"DHWL DROP

2"W & V RISE

2"DCWL DROP

4"S DN & 2"V RISE

1/2"DCWL DROP

2"W DN & V RISE

1/2"DHWL DROP

3" V

2" V

1/ 2"

D C

W L

8"RL UP

(8,770 S.F.)

1/ 2"

D H

W L

1/

2" D

C W

L

1 1/2" DCWL

1/

4" D

H W

L

2" DHWL 2" DHWL 2" DHWL

2" DHWL

2" D

C W

L

1 1/4"DCWL DROP

1 1/4"TW RISE

1 1/4"DHWL DROP

2" DHWL

2" D

H W

L

1/2" DCWL

2" V

3" DCWL 3" DCWL

2"DCWL DN

1 1/2"DHWL DN

2"DCWL DN

1 1/2"DHWL DN

P-801

P-801

2" S

A N

(M .C

CHEMICAL DISPENSING

SYSTEM SEE DETAIL

ON DWG OP508

DSP-1

CHEMICAL DISPENSING

SYSTEM SEE DETAIL

ON DWG 0P508

DSP-1

CHEMICAL DISPENSING

SYSTEM SEE DETAIL

ON DWG OP508

DSP-1

2" S

A N

(M .C

8" R

L

8" RL

2" V

2" V

1 1/2" DHWL

NC BYPASS VALVE

NC BYPASS VALVE

3/4" DCWL

3/4"DCWL DROP

3/4" DCWL

3/ 4"

D C

W L

4" FD-B

1/2" DCWL

4”FD-B

1"DCWL DROP

1"RPBP

2"V DN & RISE

TP MANIFOLD

3/4"DCWL DROP

1/2"TP DN TO FD'S

TP MANIFOLD

3/4"DCWL DROP

1/2"TP DN TO FD'S

2"V DN & RISE

1"DCWL DROP

1"RPBP

1/2" DCWL

1/2" DCWL

2"DCWL DROP

4"W DN & 2"V RISE

2"DCWL DROP

4"W DN & 2"V RISE

1/2"DCWL DROP

2"W DN & V RISE

1/2"DHWL DROP

3" V

3" SAN (M.C.)

4" S

A N

(M .C

2" V

4" SAN (M.C.)

3" SAN (M.C.)

3" V

2" V

2" V

3" V

2" V

4" SAN (M.C.)

4" S

A N

(M .C

2" S

A N

(M .C

2"V UP

3"W&T UP

4"S UP

2"V UP

2" SAN (M.C.)

4" S

A N

(M .C

4"SS UP&DN

4"VS UP&DN

2" SAN (M.C.)

4"SS UP&DN

4"VS UP&DN

P-104A

P-414

P-414

P-104A

P-528

1/2"DHWL DROP

2"W DN&V RISE

1/2"DCWL DROP

1/2"DHWL DROP

2"W DN&V RISE

1/2"DCWL DROP

2"DCWL DROP

4"W DN&2"V RISE

6" R

L 6"

R L

4" R

L

6" R

L

2"W UP

2" V 2" V

P-712

1/

4" D

H W

L

1/

2" D

C W

L

PROVIDE EXPANSION JOINT ASSEMBLIES

(FLEXIBLE CONNECTIONS) IN ALL PIPING

SYSTEMS

PROVIDE EXPANSION JOINT ASSEMBLIES

(FLEXIBLE CONNECTIONS) IN ALL PIPING

SYSTEMS

2" D

H W

L

2" DCWL

1 1/2" DHWL

1/2" DCWL

3" D

C W

L

2" SAN (M.C.)

3" SAN (M.C.)

3" S

A N

(M .C

3"FD-C

2"V DN&RISE

TP MANIFOLD

3/4"DCWL DROP

1/2"TP DN

TO FD'S

02 E G

02 D C

02 B

02 7

8.3

F.9

A.5

AA

5.3

AA.2

7.6

8.1

6.1

EJ 2

A

02 F

02 8

EJ

2.9

C.5

2" DCWL

1 1/2" DHWL

1/ 2"

D C

W L

1/

2" D

H W

L

3/4" DHWL

2" DCWL

SL

1B

3" V

3" V3" V3" V

2" V

2" V

2" V

2" V

3" V

2" V

3" V

2" V

3" V2" V

2" V

2" V

3" V

2" SAN (M.C.)

2" S

A N

(M .C

3" V

2" V

SS

2A

VS

2A

SS

2B

VS

2B

SS

2C

VS

2C

SS

2D

VS

2D

SS

2F

VS

2F

SS

2E

VS

2E

2"FD-C

4"W & T UP

2"V UP

4" SAN (M.C.)

(2)4"W& T UP

(2)2"V UP

9.6

XA

9.2

Q D2 D1

E2 E1

F2 F1

G2 G1

A2

A4

A5

A1

A6

B1

C1 C2

B2

H

J1 J2

L

K

M1 M2 M3

N1 N2

A7

D3

E3

F3

R1

R4

R2 R3

A3

08 P

PLAN

NORTH

DATE

LOCATION

CHECKED DRAWN

PROJECT TITLE PROJECT NUMBER

DOCUMENT SET PACKAGE

DRAWING NUMBERAPPROVED: PROJECT DIRECTOR

DRAWING TITLEARCHITECT/ENGINEERS:CONSULTANTS:

REVISIONS: DATE

B

A

D

C

E

VA FORM 08-6231

O N

E

EI

G H

T

IN

C H

O

N E

FO

O

T O

N E

Q U

AR

TE

R

IN

C H

O

N E

FO

O

T O

N E

H

AL

F

IN

C H

O

N E

FO

O

T

TH

R

EE

Q U

AR

TE

R S

IN

C

H

O N

E

FO

O T

TH

R

EE

IN

C H

ES

O N

E

FO

O T

O N

E

IN

C H

F

O R

TY

F

EE

T

(1

0'

6"

6"

0'

0'

123456

F

B

A

D

C

E

F

O N

E

SI

XT

EE

N

TH

IN

C

H

O N

E

FO

O T

O N

E

AN

D O

N E

H

AL

F

IN

C H

ES

O N

E

FO

O T

6"

BUILDING NUMBER

2PL102-E

BLDG 2 SECOND FLOOR PLUMBING PLAN - AREA E

RVD CADDFebruary 29, 2012

02629-HS2-401SLVHCS REPLACEMENT MEDICAL

CENTER PROJECT

NEW ORLEANS, LOUISIANA

SCHRENK & PETERSON CONSULTING ENGINEERS / CIVIL

KORDA/NEMETH ENGINEERING / STRUCTURAL

BR+A CONSULTING ENGINEERS / MECH, ELECT, PLUMBING, LOW VOLTAGE

ARCHITECTURAL ENGINEERING/ PLUMBING

SCALES ASSOCIATES / FIRE PROTECTION

DESMAN ASSOCIATES / PARKING

CODE CONSULTANTS, INC. / CODE CONSULTANT

THE SEXTANT GROUP / AV & ACOUSTICAL

HAMMER DESIGN ASSOCIATES / FOOD SERVICE

PYBURN & ODOM / ABATEMENT

TATA & HOWARD / TANK CONSULTANT

Department of

Veterans Affairs

OFFICE OF

CONSTRUCTION

AND FACILITIES

MANAGEMENT

WP_08

CONSTRUCTION DOCUMENTS 1

FULLY SPRINKLERED

1. ALL HORIZONTAL PIPING SHALL BE INSTALLED IN THE INTERSTITIAL

SPACE UNLESS OTHERWISE NOTED. CONTRACTOR SHALL OWN ALL

REQUIRED CORING, SLEEVING, FIRESTOPPING, ETC. REFER TO

ARCHITECTURAL PLANS FOR INTERSITIAL SLAB CONSTRUCTION.

2. ALL DOMESTIC (POTABLE)AND NON DOMESTIC (NONPOTABLE) HOT,

COLD, AND HOT WATER CIRCULATION PIPING SHALL BE INSTALLED AT

THE INTERSTITIAL SPACE FLOOR IN ORDER TO MAINTAIN HOT WATER

TEMPERATURE TO ALL FIXTURES. IF PIPING CAN'T BE INSTALLED AT

THE INTERSTITIAL SPACE FLOOR, PIPING SHALL BE INSTALLED

BETWEEN THE INTERSTITIAL SPACE FLOOR AND THE CEILING AND THE

PIPING SHALL BE LOOPED TO ALLOW CONTINUOS HOT WATER

CIRCULATION.

3. ALL STACKS AND RISERS SHALL BE SUPPORTED AT THE INTERSTITIAL

SPACE FLOOR OR JUST ABOVE THE CEILING WHERE THE INTERSTIAL

SPACE DOES NOT EXIST. SEE DETAILS ON DWG 0P506.

4. PROVIDE A BALL VALVE IN THE OPEN POSITION WITH A LOCK AND CHAIN

AT ALL EMERGENCY SHOWERS

5. DRAIN VALVES SHALL BE PROVIDED AT THE BASE OF ALL PLUMBING

RISERS

6. ALL ISOLATION VALVES AT RISERS SHALL BE INSTALLED IN AN

ACCESSIBLE LOCATION, NO MORE THAN 12" ABOVE FINISHED CEILING

7. ALL MIXING VALVE AT SHOWERS SHALL HAVE THE TEMPATURE LIMIT

STOP ADJUSTED TO THE REQUIRED VA STANDARDS

GENERAL NOTES

1 Addendum 01 5/23/12

30 BULLETIN 029C-IMAGING 7/23/14

32 BULLETIN 029D-IMAGING 10/16/14

REFER TO SKETCH:

SK-8-1-NJ-2-PL-102-E-1

Correspondence No. 04924: Trap Primers have been deleted and Trap Guards installed.

Correspondence No. 04924: Trap Primers have been deleted and Trap Guards installed.

Correspondence No. 04924: Trap Primers have been deleted and Trap Guards installed.

RFI 01757: MOVE

WALL NORTH 2"

RFI 01707: FUR OUT

PARTITION BEHIND

FIXTURE AND

CASEWORK 5'-2" IN

LENGTH

RFI 01707: FUR

WALL FOR FIXTURE

RFI 01707: FUR

OUT WALL

BEHIND FIXTURE

5'-2" IN LENGTH

RFI 01707: FUR WALL

BEHIND FIXTURE

INTO 2E133

RFI 01707: CREATE

BUMP OUT BY

FURRING OUT

WALL BEHIND LAV

TO WALL IN 2E114

RFI 01809.1: DELETE (1) 4" FD-B, (1) P-804,

(1) P-712 ((1) 4" FD-B to remain for humidifier and (1) 4" OED to be added)

THIS DRAWING HAS BEEN AFFECTED BY THE BIM

COORDINATION PROCESS. PLEASE REFER TO THE

BIM COORDINATED SHOP DRAWINGS FOR DETAILS.

GRAVITY PLUMBING PRESSURE PLUMBING

RFI:01904.1 -

Relocate Drops to 6" Partition on West side of Triage 2E150

RFI 07322: Add floor drain and associated drainage piping

RFI 07968Relocate Floor Drain

File details come from the government source that posted it. Updated .