01913-2FX102-E2 Fire Protection.pdf

PDF 371 KB Posted

Attached to
Z2DZ--Design Build Project 629-22-135 Site Prep For Dual Energy CT - 36C25622R0075
Solicitation number
629-22-135
Issued by

About this file

This document contains a fire protection plan drawing and related federal contract opportunity. The fire protection plan drawing provides details for a second floor area of Building 2 at a new Orleans, Louisiana medical center replacement project. It includes a legend noting hazard designations, sprinkler piping requirements, sprinkler head types for different areas, and other fire suppression notes.

The related federal contract opportunity is a solicitation from the Department of Veterans Affairs for a design-build project involving site preparation work for a dual energy CT scanner. The opportunity type is listed as a solicitation, with an attached RFP document seeking proposals for the site prep work associated with installation of the CT scanner under contract number 629-22-135. No other details on technical requirements, pricing, response dates or awards are provided in the brief description.

View the file

Other files

Show all 25

On GovTribe

Work with this file

  • Download the original file
  • Contacts named in this file
  • Similar government files
  • Ask GovTribe AI about this file

Text version

OH/GR2

OH/GR2

2E2

FIRE HOSE

VALVE CABINET

FIRE HOSE

VALVE

CABINET

02 H

C

F.9

G 02 F

02 E 02 D

02 5

5.3

02 6

02 7

7.6

02 8

8.1

8.3

FIRE HOSE

VALVE CABINET

FIRE HOSE

VALVE CABINET

FIRE HOSE

VALVE

CABINET

FIRE HOSE VALVE

CABINET

FIRE HOSE

VALVE CABINET

NURSE

MANAGER

2E181

S3

MH-1

2E186

C33

MH-2

2E187

C33

ISO/GYN

ACUTE-10

2E159

C31B

HK

2E170

C3

T

2E167A

T3

FAST

TRACK-7

2E194

C30F

FAST

TRACK-6

2D115

C30E

MH

WORK/OFFICE

2E188

S17

PHARMACY

2E190

C51

BLOOD

GAS

2E164

C6

CONSULT

2E180

P8

RES

CONF/WORK

2E193

S12

AOD

OFFICE

2E183

S2

ST

2E192

T4

HC

PATIENT

T/S

2E169

T6

MH T

2E168

T8

WC/STRETCH

STOR

2E179

C17

T

2D111

T3

SUB

WAIT

2D113

C11

FAST

TRACK-8

2E195

C30FCOPY/WORK

2E182

S18

PHARM

PICK-UP

2E191

CORR73

CORR

2E-C07

CORR73

CORR

2E-C12

CORR72

CORR

2E-C04

CORR73

MH-RESTRAINT

2E189

C33

ACUTE-9

2E158

C30

ACUTE-2

2E146

C30

DECONTAM

2E178

C2A

WORK

2E152B

M5

RADIOLOGY

2E130

C23

T/D

2E126

T3

CT

SCAN

2E129

C12

CONTROL

2E128

C16A

SCR

2E109

C4

ALCOVE

2E160

C35

ACUTE-11

2E166

C30

ACUTE-3

2E145

C30

ACUTE-4

2E144

C30

ACUTE-5

2E140

C30

ACUTE-6

2E155

C30

ACUTE-7

2E156

C30

ACUTE-8

2E157

C30

MEDS

2E154

C1

WORK

2E152C

M5

PACS

2E152E

M5

MULTI-PURPOSE

2E175

S11

CLEAN

2E149

C6

TRIAGE

2E150

C30

SCR

2E137

C4A

NURSE

STATION

2E152A

M5F

ISO

ACUTE-12

2E167

C31E

T

2E148

T3

HK

2E138

C3

STAFF

WORK

2E136

C16B

DRESS

2E115

C34

CC

2E139

C35

T

2E159A

T3

EC

2E174

G2

ALCOVE

2E151

C35

NURSE

STATION

2E152D

M5F

COPY/WORK

2E153

S18

DRESS

2E116

C34

CORR

2E-C05

CORR76A

CORR

2E-C09

CORR76

CORR

2E-C10

CORR76

CORR

2E-C11

CORR76

CORR

2E-C06

CORR70

ENTRANCE

VESTIBULE

2E176

P10D

CT

SCAN

2E108

C12

CT

SCAN

2E110

C12

CONTROL

2E111

C16A

CT

PREP/WORK

2E114

CORR76A

CT

PREP

2E127

C16C

COMPLEX

TREATMENT

2E165

C31E

ACUTE-1

2E147

C30

CORR

2E-C08

CORR76

DRESS

2E117

C34

T/D

2F108

T3

T/D

2F107

T3

T/D

2F106

T3

RADIOLOGY

2F105

C23

RADIOLOGY

2F104

C23

R/F

2F103

C23

2FX102-E2

2FX102-F2

2FX102-D2

2FX102-E2

2FX102-E1

2FX102-F1

2FX102-D1

2FX102-E1

2 1/2"ø

4"ø

2 1/2"ø

2 1/2"ø

4"ø

2 1/2"ø

2 1/2"ø

4"ø

4"ø

OH/GR1

OH/GR1

HAZARD DESIGNATION

OH/GR1 ORDINARY HAZARD GROUP 1

FIRE PROTECTION GENERAL NOTES & LEGEND

ALL BUILDING AREAS TO BE LIGHT HAZARD

UNLESS OTHERWISE NOTED.

OH/GR2 ORDINARY HAZARD GROUP 2

ZONE BOUNDARY

1A1 ZONE DESIGNATION

PROVIDE BRANCH TAKE OFFS AS REQUIRED FROM 4"

FIRE MAIN LOOP. RESTRICT BRANCH TAKE OFFS SIZE TO

2" MAXIMUM.

SPRINKLER PIPING SHALL NOT PASS THROUGH

ELECTRICAL, TELEPHONE AND DATA ROOMS TO SERVE

OTHER AREAS.

PROVIDE BRANCH PIPE DOWN TO VACUUM SYSTEM

LOADING STATION. PROVIDE, INSTALL AND CONNECT

TO SPRINKLER HEAD LOCATED IN FIRE SPRINKLER

ENCLOSURE SUPPLIED BY VACUUM SYSTEM DRAWINGS

AND SPECIFICATIONS.

PROVIDE INSTITUTIONAL

SPRINKLER HEADS THIS AREA

PROVIDE DRY PENDANT SPRINKLER IN WALK-IN

FREEZERS AND COLD ROOMS

KEYED NOTES

PROVIDE SPRINKLERS TO PROTECT OPENINGS IN THE

EXTERIOR WALL FOR A DISTANCE OF 10'-0".

AREA OF PROTECTED OPENINGS

PROVIDE BRASS SPRINKLER HEADS IN MRI ROOMS.

PIPING WITHIN MRI ROOM SHALL BE COPPER. EXTEND

COPPER PIPING TO DIELECTRIC CONNECTION TO STEEL

PIPE 1'-0" BEYOND MRI ROOM. PROVIDE WAVE GUIDES

AT PIPE PENETRATIONS THROUGH MRI PARTITIONS.

Q

D2 D1

E2 E1

F2 F1

G2 G1

A2

A4

A5

A1

A6

B1

C1 C2

B2

H

J1 J2

L

K

M1 M2 M3

P

N1 N2

A7

D3

E3

F3

R1

R4

R2 R3

A3

PLAN

NORTH

DATE

LOCATION

CHECKED DRAWN

PROJECT TITLE PROJECT NUMBER

DOCUMENT SET PACKAGE

DRAWING NUMBERAPPROVED: PROJECT DIRECTOR

DRAWING TITLEARCHITECT/ENGINEERS:CONSULTANTS:

REVISIONS: DATE

B

A

D

C

E

VA FORM 08-6231

O N

E

EI

G H

T

IN

C H

O

N E

FO

O

T O

N E

Q U

AR

TE

R

IN

C H

O

N E

FO

O

T O

N E

H A L

F

IN

C H

O

N E

FO

O

T

TH

R

EE

Q U

AR

TE

R S

IN

C

H

O N

E

FO

O T

TH

R

EE

IN

C H

ES

O N

E

FO

O T

O N

E

IN

C H

F

O R

TY

F

E E T

(1

0'

6"

6"

0'

0'

123456

F

B

A

D

C

E

F

O N

E

SI

X T

EE

N

TH

IN

C

H

O N

E

FO

O T

O N

E

AN

D O

N E

H

AL

F

IN

C H

ES

O N

E

FO

O T

6"

BUILDING NUMBER

NEW ORLEANS, LOUISIANA

2FX102-E2

BLDG 2 SECOND FLOOR FIRE PROTECTION

PLAN - AREA E2

CRS MJFebruary 29, 2012

02629-HS2-401SLVHCS REPLACEMENT MEDICAL

CENTER

SCHRENK & PETERSON CONSULTING ENGINEERS / CIVIL

KORDA/NEMETH / STRUCTURAL

BR+A CONSULTING ENGINEERS / MECH, ELECT, PLUMBING, LOW VOLTAGE

ARCHITECTURAL ENGINEERING / PLUMBING

SCALES ASSOCIATES / FIRE PROTECTION

COMMUNICATIONS DESIGN GROUP / LOW VOLTAGE

DESMAN ASSOCIATES / PARKING

CODE CONSULTANTS, INC. / CODE CONSULTANT

THE SEXTANT GROUP / AV & ACOUSTICAL

HAMMER DESIGN ASSOCIATES / FOOD SERVICE

PYBURN & ODOM / ABATEMENT

TATA & HOWARD / TANK CONSULTANT

I.S.C. GROUP, INC. / IRRIGATION

DAN EUSER WATER ARCHITECTURE, INC. / WATER FEATURE

Department of

Veteran Affairs

OFFICE OF

CONSTRUCTION

AND FACILITIES

MANAGEMENT

WP_08

CONSTRUCTION DOCUMENTS 1

FULLY SPRINKLERED

1/8" = 1'-0"

BLDG 2 SECOND FLOOR FIRE PROTECTION PLAN - AREA E2

THIS DRAWING HAS BEEN AFFECTED BY THE BIM

COORDINATION PROCESS. PLEASE REFER TO THE

BIM COORDINATED SHOP DRAWINGS FOR DETAILS.