2D RLP 36C10F25R0035 Appendix A3 Room Data Matrix RDM Port St Lucie FL OPC.pdf

PDF 935 KB Posted

Attached to
X1DB--Port St. Lucie, Fl. Outpatient Clinic 142, 811 ANSI/BOMA Amendment
Solicitation number
36C10F25R0035
Issued by

About this file

The document is a comprehensive Room Data Matrix (RDM) for the Port St. Lucie, Florida Outpatient Clinic (OPC) project, detailing specifications for numerous rooms across multiple functional areas. The matrix provides extensive technical details for each room, including room codes, quantities, floor and wall finishes, mechanical and electrical requirements, door hardware, temperature and humidity specifications, and power/receptacle configurations.

The Room Data Matrix covers multiple functional areas including Community Based Outpatient Clinic (CBOC), Ambulatory Surgery Center (ASC), Sterile Processing Service (SPS), and various clinical and support spaces such as primary care, mental health, audiology, dental, eye clinic, imaging, laboratory, pharmacy, and staff support areas. Each room entry specifies precise requirements for construction materials, environmental conditions, air exchange rates, noise levels, and electrical infrastructure, providing a comprehensive blueprint for the facility's interior design and technical specifications.

View the file

Other files

File Type Posted
Port St Lucie FL OPC - RLP Amendment 8 31 2026.pdf PDF
Port St Lucie FL OPC OpEx cost details 8 31 2026.xlsx XLSX spreadsheet
GSA Template 3517B - General Clauses April 2026.pdf PDF
36C10F25R0035 0001.docx DOCX document
Attachment 1 RLP 36C10F25R0035 Port St Lucie FL OPC Q and A Matrix.pdf PDF
Port St Lucie FL OPC RLP 36C10F25R0035 Amendment No 1.pdf PDF
Attachment 2 RLP 36C10F25R0035 Port St Lucie FL OPC Pre bid transcript.pdf PDF
2B RLP 36C10F25R0035 Appendix A1 Project Room Contents List PRC Port St Lucie FL OPC.pdf PDF
1 RLP 36C10F25R0035 Lease Port St Lucie FL OPC.pdf PDF
20 RLP 36C10F25R0035 FAR 52 204 24 Representation Regarding Certain Telecom Port St Lucie FL OPC.pdf PDF
8 RLP 36C10F25R0035 Attachment No 1 to GSA Form 1364 Port St Lucie FL OPC.xlsx XLSX spreadsheet
21 RLP 36C10F25R0035 PreBid Registration Form Port St Lucie FL OPC.pdf PDF
19 RLP 36C10F25R0035 DOL County Wage Determination St Lucie County Port St Lucie FL OPC.pdf PDF
9 RLP 36C10F25R0035 GSA Form 1217 Lessors Annual Cost Statement Port St Lucie FL OPC.pdf PDF
2E1 RLP 36C10F25R0035 Appendix A4 OIT Data Center Design Narrative Port St Lucie FL OPC.pdf PDF
2 RLP 36C10F25R0035 Cover Page for Agency Specific Requirements ASRs Port St Lucie FL OPC.pdf PDF
14 RLP 36C10F25R0035 VA Handbook 6500 6 Port St Lucie FL OPC.pdf PDF
6 RLP 36C10F25R0035 Offeror Proposal Compliance Matrix Port St Lucie FL OPC.pdf PDF
2F RLP 36C10F25R0035 Appendix A5 Facility Security Level II Port St Lucie FL OPC.pdf PDF
17 RLP 36C10F25R0035 Prelease FPLS Evaluation Form 12000 Part A and Part B Port St Lucie FL OPC.pdf PDF
16 RLP 36C10F25R0035 3517B General Clauses Port St Lucie FL OPC.pdf PDF
0 RLP 36C10F25R0035 RLP Port St Lucie FL OPC.pdf PDF
18 RLP 36C10F25R0035 Certification of Building Energy Performance Port St Lucie FL OPC.pdf PDF
3 RLP 36C10F25R0035 Appendix A6 Conceptual Floor Plans Port St Lucie FL OPC.pdf PDF
15 RLP 36C10F25R0035 3516 Solicitation Provisions Port St Lucie FL OPC.pdf PDF
36C10F25R0035.docx DOCX document
13 RLP 36C10F25R0035 GSA Form 527 Contractors Quals and Financial Info Port St Lucie FL OPC.pdf PDF
5 RLP 36C10F25R0035 Offering Entity Acknowledgement Form Port St Lucie FL OPC.pdf PDF
2E RLP 36C10F25R0035 Appendix A4 VA CBOC Info Transp Sys Specs Port St Lucie FL OPC.pdf PDF
2C RLP 36C10F25R0035 Appendix A2 Lease Design Narrative LDN Port St Lucie FL OPC.pdf PDF
11 RLP 36C10F25R0035 Past Performance Questionnaire Form for VA Port St Lucie FL OPC.pdf PDF
2A RLP 36C10F25R0035 Appendix A Program for Design PFD Port St Lucie FL OPC.pdf PDF
10 RLP 36C10F25R0035 10091 VA Vendor File Request Form Port St Lucie FL OPC.pdf PDF
4 RLP 36C10F25R0035 Appendix B Lease Service Narrative LSN Port St Lucie FL OPC.pdf PDF
12 RLP 36C10F25R0035 SF 330 Architect Engineer Qualifications Port St Lucie FL OPC.pdf PDF
7 RLP 36C10F25R0035 Proposal to Lease Space GSA Form 1364 Port St Lucie FL OPC.pdf PDF
Show all 36

On GovTribe

Work with this file

  • Download the original file
  • Contacts named in this file
  • Similar government files
  • Ask GovTribe AI about this file

Text version

NOTES

Department Number &

Name

Functional Area Number

& Name

Room

Code

Known

Legacy

Room

Code

Project Room Name

Quantity of This

Room

FGI Equivalent for ASHRAE 170

FGI Equivalent for Table 1-2-5

Minimum

Sound Isolation

F lo o r

F in is h

B a se

W a ll F in is h

W a ll F in is h A lt e rn a te

W a in sc o t

M a te ri a l

W a in sc o t

H e ig h t

S T

C

C e il in g H e ig h t

C e il in g F in is h

N o te s

S iz e

W id th

H e ig h t

T y p e

M a te ri a l

G la zi n g

R a ti n g

H a rd w a re

G ro u p

H a rd w a re

N o te s

In d o o r T e m p e ra tu re C o o li n g

F

In d o o r T e m p e ra tu re H e a ti n g

F

In d o o r R e la ti v e H u m id it y

R H

M a x

In d o o r R e la ti v e H u m id it y in

M in im u m T o ta l A

C H

M in im u m O u ts id e

A ir

C h a n g e te

M in im u m O

A A

C H

R o o m

A ir

R e tu rn

G e n E x h

G S p e c

E x h S

M in im u m N o is e L e v e l

N C

R o o m

A ir

B a la n ce

H V

A C

N o te s

D u p le x

R e ce p ta cl e s

Q u a d R e ce p ta cl e s

P o w e r

N o te s

F ix tu re

T y p e

C o n tr o ls

Li g h ti n g

S p e ci a l R e q u ir e m e n ts

Li g h ti n g

N o te s

SB101 CBOC Veteran Drop-off, Bldg Sprt 1 N/A N/A N/A N/A N/A N/A N/A N/A N/A N/A N/A N/A N/A N/A N/A N/A N/A N/A N/A N/A N/A N/A N/A N/A N/A N/A N/A N/A N/A N/A 1 weather proof cover Surface mount

Comply with

AHRAE/UFC 3-530-1

SB102 LOVP1

CBOC Valet Parking Station, Bldg

Sprt 1 N/A N/A N/A N/A N/A N/A N/A N/A N/A N/A N/A N/A N/A N/A N/A N/A N/A N/A N/A N/A N/A N/A N/A N/A N/A N/A N/A N/A N/A N/A 1 weather proof cover

Surface mount

Comply with

AHRAE/UFC 3-530-1

SB103 CBOC Bicycle Rack Area, Bldg Sprt 1 N/A N/A N/A N/A N/A N/A N/A N/A N/A N/A N/A N/A N/A N/A N/A N/A N/A N/A N/A N/A N/A N/A N/A N/A N/A N/A N/A N/A N/A N/A 1 weather proof cover Surface mount

Comply with

AHRAE/UFC 3-530-1

SB104

CBOC Service Dog Walk Area, Bldg

Sprt 1 N/A N/A N/A N/A N/A N/A N/A N/A N/A N/A N/A N/A N/A N/A N/A N/A N/A N/A N/A N/A N/A N/A N/A N/A N/A N/A N/A N/A N/A N/A 1 weather proof cover

Surface mount

Comply with

AHRAE/UFC 3-530-1

SB253

CBOC Gurney Corral / Parking, Clncl Sprt 1 N/A m:LVT m:RB h:4" m:GWB f:SC N/A N/A N/A N/A 9'-0" m: AT N/A N/A 7'-0" m: Open N/A N/A N/A 75 72 60 N/A N/A STD 62 STD 62 N/A N/A N/A N/A 4 2x4 D/I

Dimming-Comply with

AHRAE/UFC 3-530-1

SB262 SRLW1

CBOC Wheelchair Corral / Parking, Clncl Sprt 1 N/A m:LVT m:RB h:4" m:GWB f:SC N/A N/A N/A N/A 9'-0" m: AT N/A N/A 7'-0" m: Open N/A N/A N/A 75 72 60 N/A N/A STD 62 STD 62 N/A N/A N/A N/A 4 2x4 D/I

Dimming-Comply with

AHRAE/UFC 3-530-1

SC093 CSPL1

CBOC Mobile Lift Corral / Parking, Clncl Sprt 1 N/A m:LVT m:RB h:4" m:GWB f:SC N/A N/A N/A N/A 9'-0" m: AT N/A N/A 7'-0" m: Open N/A N/A N/A 75 72 60 N/A N/A STD 62 STD 62 N/A N/A N/A N/A 4 2x4 D/I

Dimming-Comply with

AHRAE/UFC 3-530-1

CWV02 LAC01 CBOC Lactation Room, Wm Vet Svc 1 N/A m:LVT m:RB h:4" m:GWB f:P N/A N/A N/A N/A 9'-0" m: AT 3'-0" 7'-0" 19 m: Wood N/A hw: 2G 75 72 60 N/A N/A STD 62 STD 62 N/A N/A N/A N/A 4 2x4 D/I

Dimming-Comply with

AHRAE/UFC 3-530-1

OCB16 SRS01 Travel /ROI Office 1 N/A m:LVT or m:CPT m:RB h:4" m:GWB f:P N/A N/A N/A 40 9'-0" m: AT 3'-0" 7'-0" 1 m: Wood T hw: 3E 75 72 60 N/A N/A STD 62 STD 62 N/A N/A N/A N/A 4 2x4 D/I

Dimming-Comply with

AHRAE/UFC 3-530-1

OCB18 SRS01

Veteran Information / Welcome

Area Storage Room, CBOC 1 N/A m:VT m: RB h:4" m:GWB f:SC N/A m:RWC h:4'-0" 35 9'-0" m: AT 3'-6" 7'-0" 11 m: Wood F hw: 5 75 72 60 N/A N/A STD 62 STD 62 N/A N/A N/A N/A 4 2x4 D/I

Dimming-Comply with

AHRAE/UFC 3-530-1

SB051 WTF01 Family Seating, Bldg Sprt 1 N/A m:CPT or m:LVT m:RB h:4" m:GWB f:P N/A m:RWC h:4'-0" 40 9'-0" m: AT N/A 7'-0" m: Open N/A N/A N/A 75 72 60 N/A N/A STD 62 STD 62 N/A N/A N/A N/A 4 2x4 D/I

Comply with

AHRAE/UFC 3-530-1

SB131 Information/Welcome Desk 1 N/A m:LVT m:RB h:4" m:GWB f:P N/A N/A N/A 40 9'-0" m: AT N/A 7'-0" m: Open N/A N/A N/A 75 72 60 N/A N/A STD 62 STD 62 N/A N/A N/A N/A 4 2x4 D/I

Dimming-Comply with

AHRAE/UFC 3-530-1

SB163 TPB01 Bariatric Patient Toilet, Bldg Sprt 1 N/A Aligns with FGI m:PT or m:RES m: PT or

RES H:4"

m:GWB f:SC N/A m:PT or

CT or S 4'-0" 45 9'-0" m: GWB f: SC 3'-6" 7'-0" 1 m: Wood N/A hw:2H 2 or 4U 75 72 60 N/A N/A STD 62 STD 62 N/A N/A N/A N/A 1 2x4 D/I

Dimming-Comply with

AHRAE/UFC 3-530-1

SC170 My HealtheVet Connect Station 2 N/A m:CPT or m:LVT m: RB h:

4" m:GWB f:P N/A N/A N/A 40 9'-0" m: AT 3'-0" 7'-0" 19 m: Wood S hw:2H 75 72 60 N/A N/A STD 62 STD 62 N/A N/A N/A N/A 4 2x4 D/I

Dimming-Comply with

AHRAE/UFC 3-530-1

CBOC Patient Advocate Office, Stff

Sprt 1 N/A m:LVT or m:CPT m:RB h:4" m:GWB f:P N/A N/A N/A 40 9'-0" m: AT 3'-0" 7'-0" 1 m: Wood T hw:2H 75 72 60 N/A N/A STD 62 STD 62 N/A N/A N/A N/A 5 1 2x4 D/I

Dimming-Comply with

AHRAE/UFC 3-530-1

CBOC Patient Enrollment Office, Stff Sprt 1 N/A m:CPT m:RB h:4" m:GWB f:P N/A N/A N/A 35 9'-0" m: AT 3'-0" 7'-0" 1 m: Wood T hw:2H 75 72 60 N/A N/A STD 62 STD 62 N/A N/A N/A N/A 5 1 2x4 D/I

Dimming-Comply with

AHRAE/UFC 3-530-1

SB207 CBOC Outdoor Seating, Bldg Sprt 1 N/A N/A N/A N/A N/A N/A N/A N/A N/A N/A N/A N/A N/A N/A N/A N/A N/A hw:2H N/A 75 72 60 N/A N/A STD 62 STD 62 N/A N/A N/A N/A 4 2x4 D/I Comply with

AHRAE/UFC 3-530-1

SV381 NCWD4

CBOC Refreshment Station, Bldg

Sprt 1 N/A m:LVT m:RB h:4" m:GWB f:P N/A N/A 40 9'-0" m: AT N/A 7'-0" m: Open N/A N/A N/A 75 72 60 N/A N/A STD 62 STD 62 N/A N/A N/A N/A 4 2x4 D/I

Comply with

AHRAE/UFC 3-530-1

SV626

CBOC Cafe / Bistro/Mini Mart, VC

Svc 1 N/A m:LVT m:RB h:4" m:GWB f:P N/A N/A 40 9'-0" m: AT N/A 7'-0" m: Open N/A N/A N/A 75 72 60 N/A N/A STD 62 STD 62 N/A N/A N/A N/A 4 2x4 D/I

Comply with

AHRAE/UFC 3-530-1

SV627 SRS01

CBOC Cafe / Bistro Storage Room, VC Svc 1 N/A m:VT m:RB h:4" m:GWB f:P m:RWC h:4'-0" 40 9'-0" m: AT 3'-8" 7'-0" 11 m: Wood F hw: 5 75 72 60 N/A N/A STD 62 STD 62 N/A N/A N/A N/A 4 2x4 D/I

Comply with

AHRAE/UFC 3-530-1

CBOC Cafe / Bistro Seating, VC Svc 1 N/A m:LVT m:RB h:4" m:GWB f:P N/A N/A 40 9'-0" m: AT N/A 7'-0" m: Open N/A N/A N/A 75 72 60 N/A N/A STD 62 STD 62 N/A N/A N/A N/A 4 2x4 D/I

Comply with

AHRAE/UFC 3-530-1

CBOC Refreshment Seating, VC Svc 1 N/A m:LVT m:RB h:4" m:GWB f:P N/A N/A 40 9'-0" m: AT N/A 7'-0" m: Open N/A N/A N/A 75 72 60 N/A N/A STD 62 STD 62 N/A N/A N/A N/A 4 2x4 D/I

Comply with

AHRAE/UFC 3-530-1

SV692 BX002

CBOC Vending Area, Blind Veteran

Vender/VCS 1 N/A m:LVT m:RB h:4" m:GWB f:P N/A N/A 40 9'-0" m: AT N/A 7'-0" m: Open N/A N/A N/A 75 72 60 N/A N/A STD 62 STD 62 N/A N/A N/A N/A 4 2x4 D/I

Comply with

AHRAE/UFC 3-530-1

OCB21 CFR02

Shared Group / Multifunction

Room, CBOC 1 N/A m:CPT or m:LVT m:RB h:4" m:GWB f:P N/A N/A 40 9'-0" m: GWB f: P or m: AT

3'-6" 7'-0" 19 m: Wood N/A hw: 4N 75 72 60 N/A N/A STD 62 STD 62 N/A N/A N/A N/A 4 2x4 D/I

Comply with

AHRAE/UFC 3-530-1

OCB24 SRS01

Shared Group / Multifunction

Storage Room, CBOC 1 N/A m:VT m:RB h:4" m:GWB f:P m:RWC h:4'-0" 40 9'-0" m: AT 3'-8" 7'-0" 11 m: Wood F hw: 5 75 72 60 N/A N/A STD 62 STD 62 N/A N/A N/A N/A 4 2x4 D/I

Comply with

AHRAE/UFC 3-530-1

SC276

CBOC Demonstration Kitchen, Clncl

Sprt 1 N/A m:PT or m:RES m: PT or

RES H:4"

m:GWB f:SC m:PT or

CT or S 4'-0" 40 9'-0" m: GWB f: SC 3'-6" 7'-0" 1 m: Wood N/A hw:2H 2 or 4U 75 72 60 N/A N/A STD 62 STD 62 G N/A N/A N/A 4 2x4 D/I

Comply with

AHRAE/UFC 3-530-1

CEY62 OPIM2

CBOC Tele Retinal Imaging Patient

Care Room 1 N/A Aligns with FGI m:WSF or m:LVT m:RB or m:WSF h:4" m:GWB f:P N/A N/A 55 9'-0" m: AT or GWB f: P

N/A 7'-0" m: Open N/A N/A N/A 75 72 60 N/A N/A STD 62 STD 62 N/A N/A N/A N/A 4 2x4 D/I

Dimming-Comply with

AHRAE/UFC 3-530-1

CT024 Multipurpose Group Room 1 N/A m:CPT or m:LVT m:RB h:4" m:GWB f:P N/A N/A 40 9'-0" m: GWB f: P or m: AT

3'-6" 7'-0" 19 m: Wood N/A hw: 4N 75 72 60 N/A N/A STD 62 STD 62 N/A N/A N/A N/A 4 2x4 D/I

Dimming-Comply with

AHRAE/UFC 3-530-1

CT025 Group Room Storage Room 1 N/A m:VT m:RB h:4" m:GWB f:P m:RWC h:4'-0" 40 9'-0" m: AT 3'-8" 7'-0" 11 m: Wood F hw: 5 75 72 60 N/A N/A STD 62 STD 62 N/A N/A N/A N/A 4 2x4 D/I

Comply with

AHRAE/UFC 3-530-1

CWV16 EXW01

Women Veteran Patient Care

Room 1 N/A m:LVT m: RB h:4" m:GWB f:P m:RWC h:4'-0" 35 9'-0" m: AT 3'-6" 7'-0" 19 m: Wood N/A hw: 1Q 75 72 60 N/A N/A STD 62 STD 62 N/A N/A N/A N/A 4 2x4 D/I

Dimming-Comply with

AHRAE/UFC 3-530-1

OCB31 EXRG3

General Patient Care

Room/Exam/Consult 19 N/A Aligns with FGI m:LVT m:RB h:4" m:GWB f:P m:RWC h:4'-0" 50 9'-0" m: AT 3'-6" 7'-0" 19 m: Wood N/A hw: 1L 75 72 60 N/A N/A STD 62 STD 62 N/A N/A N/A N/A 4 2x4 D/I

Dimming-Comply with

AHRAE/UFC 3-530-1

OCB37 EXEB1

Multi-Use / Bariatric Patient Care

Room/Procedure/Treatment/Fami ly Consult, CBOC

1 N/A Aligns with FGI m:WSF or m:RESIN m:WSF or m:RESIN h:4" m:GWB f:SC m:RWC h:4'-0" 50 9'-0" m: AT 4'-0" 7'-0" 19 m: Wood T hw: 13 75 72 60 N/A N/A STD 62 STD 62 N/A N/A N/A N/A 4 2x4 D/I

Dimming-Comply with

AHRAE/UFC 3-530-1

SB003 WRC01 General Waiting 1 N/A m:CPT or m:LVT m:RB h:4" m:GWB f:P m:RWC h:4'-0" 40 9'-0" m: AT N/A 7'-0" m: Open N/A N/A N/A 75 72 60 N/A N/A STD 62 STD 62 N/A N/A N/A N/A 4 2x4 D/I

Comply with

AHRAE/UFC 3-530-1

SB159 TLTF2

CBOC Women Veteran Patient

Toilet 1 N/A Aligns with FGI m:PT or m:RES m: PT or

RES H:4"

m:GWB f:SC m:PT or

CT or S 4'-0" 45 9'-0" m: GWB f: SC 3'-6" 7'-0" 1 m: Wood N/A hw:2H 2 or 4U 75 72 60 N/A N/A STD 62 STD 62 G N/A (-) N/A 0

DL/VANI

TY

Comply with

AHRAE/UFC 3-530-1

SB191 TNPG1 Universal Non-Patient/Staff Toilet 2 N/A Aligns with FGI m:PT or m:RES m: PT or

RES H:4"

m:GWB f:SC m:PT or

CT or S 4'-0" 45 9'-0" m: GWB f: SC 3'-6" 7'-0" 1 m: Wood N/A hw:2H 2 or 4U 75 72 60 N/A N/A STD 62 STD 62 G N/A (-) N/A 1

DL/VANI

TY

Comply with

AHRAE/UFC 3-530-1

SB201 TPG01 CBOC Patient Toilet 3 N/A Aligns with FGI m:PT or m:RES m: PT or

RES H:4"

m:GWB f:SC m:PT or

CT or S 4'-0" 45 9'-0" m: GWB f: SC 3'-6" 7'-0" 1 m: Wood N/A hw:2H 2 or 4U 75 72 60 N/A N/A STD 62 STD 62 G N/A (-) N/A 0

DL/VANI

TY

Comply with

AHRAE/UFC 3-530-1

SB721 STEQ1 Medical Equipment Storage Room 1 N/A m:VT m:RB h:4" m:GWB f:P m:RWC h:4'-0" 35 9'-0" m: AT 3'-8" 7'-0" 11 m: Wood F hw: 5 75 72 60 N/A N/A STD 62 STD 62 N/A N/A N/A N/A 4 2x4 D/I

Comply with

AHRAE/UFC 3-530-1

SB737 UCCL1 Clean Utility Room 1 N/A m:WSF m:WSF h:4" m:GWB f:SC m:RWC h:4'-0" 35 9'-0" m: AT f:SP 3'-8" 7'-0" 11 m: Wood F SH-3C ds:YES 75 72 60 N/A N/A STD 62 STD 62 N/A N/A (+) N/A 4 2x4 D/I

Comply with

AHRAE/UFC 3-530-1

SB743 USCL1 Soiled Holding Room 1 N/A m:WSF m:WSF h:4" m:GWB f:SC m:RWC h:4'-0" 35 9'-0" m: AT f:SP 3'-8" 7'-0" 11 m: Wood F SH-3C ds:YES 75 72 60 N/A N/A STD 62 STD 62 G N/A (-) N/A 4 2x4 D/I

Comply with

AHRAE/UFC 3-530-1

SC066 PEHW2

CBOC Accessible Patient Height &

Weight Station 2 N/A m:LVT m:RB h:4" m:GWB f:P N/A N/A 40 9'-0" m: AT N/A 7'-0" m: Open N/A N/A N/A 75 72 60 N/A N/A STD 62 STD 62 N/A N/A N/A N/A 1 DL

Comply with

AHRAE/UFC 3-530-1

SC083 CSMP1

Medication Alcove, Automated

Dispensing Unit 1 N/A m:VT m:RB h:4" m:GWB f:P m:RWC h:4'-0" 40 9'-0" m: AT 3'-8" 7'-0" 11 m: Wood F hw: 5 75 72 60 N/A N/A STD 62 STD 62 N/A N/A N/A N/A 1 Provide dedicated circuit for med dispenser machine DL

Comply with

AHRAE/UFC 3-530-1

SC183 RCP01 Reception 1 N/A m:LVT or m:CPT m: RB h:4" m:GWB f:P N/A N/A 40 9'-0" m: AT

3'-0" or

OPEN

7'-0" or

OPEN

1 OR

OPEN

m: Wood

3E or

OPEN

hw: 3E or N/A 75 72 60 N/A N/A STD 62 STD 62 N/A N/A N/A N/A 4 1 2x4 D/I

Comply with

AHRAE/UFC 3-530-1

SC243 PACT Team Room (2 workstations) 12 N/A m:CPT or m:LVT m:RB h:

4" m:GWB f:P N/A N/A 40 9'-0" m: AT N/A 7'-0" m: Open N/A N/A N/A 75 72 60 N/A N/A STD 62 STD 62 N/A N/A N/A N/A 4 2 2x4 D/I

Dimming-Comply with

AHRAE/UFC 3-530-1

SC281 CBOC Point of Use Supply Alcove 1 N/A m:CPT or m:LVT m:RB h:4" m:GWB f:P N/A N/A 35 9'-0" m: AT or GWB f: P

N/A 7'-0" m: Open N/A N/A N/A 75 72 60 N/A N/A STD 62 STD 62 N/A N/A N/A N/A 0 DL

Comply with

AHRAE/UFC 3-530-1

Office, HAS Supervisor Office 1 N/A m:LVT or m:CPT m:RB h:4" m:GWB f:P N/A N/A 40 9'-0" m: AT 3'-0" 7'-0" 1 m: Wood T hw: 3E 75 72 60 N/A N/A STD 62 STD 62 N/A N/A N/A N/A 5 1 2x4 D/I

Dimming-Comply with

AHRAE/UFC 3-530-1

Office, Nurse Manager, Primary

Care 1 N/A m:LVT or m:CPT m:RB h:4" m:GWB f:P N/A N/A 40 9'-0" m: AT 3'-0" 7'-0" 1 m: Wood T hw: 3E 75 72 60 N/A N/A STD 62 STD 62 N/A N/A N/A N/A 5 1 2x4 D/I

Dimming-Comply with

AHRAE/UFC 3-530-1

SS205 OFA09

01 - COMMUNITY BASED

OUTPATIENT CLINIC

(CBOC) (265)

05 - VETERAN

EDUCATION / GROUP

CARE AREA

01 - COMMUNITY BASED

OUTPATIENT CLINIC

(CBOC) (265)

06 - PATIENT CARE AREA:

PRIMARY CARE-PACT -

MODULE 1

01 - COMMUNITY BASED

OUTPATIENT CLINIC

(CBOC) (265)

01 - COMMUNITY BASED

OUTPATIENT CLINIC

(CBOC) (265)

01 - OUTDOOR PUBLIC

AREA

02 - INDOOR PUBLIC

AREA

01 - COMMUNITY BASED

OUTPATIENT CLINIC

(CBOC) (265)

03 - VETERAN WELCOME

AREA / MAIN STREET

01 - COMMUNITY BASED

OUTPATIENT CLINIC

(CBOC) (265)

SS203 OFA04

SV628 FSCD1

04 - CAFE /

REFRESHMENT AREA

ROOM DATA MATRIX INTERIOR CONSTRUCTION DOORS AND HARDWARE MECHANICAL ELECTRICAL

Note: Use parameters within FGI Guidelines for the noted FGI Equivalent category unless otherwise noted. FGI is required for

Ambulatory Surgical Center ASHRAE Standard 170 and the balance of other spaces outdoor ventilation and exhaust would fall under the requirments of ASHRAE Standard 62.

Minimum receptacle quantities provided in this matrix. Equipment layouts must be assessed for each room to provide the correct receptacle and hardwire connection quantity. Where required by ASHRAE 90.1 and UFC 3-520-01, all workstations and work areas must have controlled and non-controlled outlets. All office, staff-support spaces, and other workstation locations require a minimum of two duplex receptacles, one double duplex, or one quadraplex receptacle for each workstation. Provide GFCI receptacles as required by NFPA 70. Receptacle layout and quantities must meet UFC 3-520-01 requirements.

POWER

Lighting fixture quantity and type provided are an estimate to meet minimum requirements.

Ceiling material selection will affect fixture type and size. Provide computer-generated photometric plans for each space to verify proposed lighting design meets the required performance criteria using the applicable light loss factor (LLF). All interior and exterior lighting design shall meet all UFC 3-530-1 and ASHRAE requirements. Egress lighting and controls shall comply with NFPA 101 and UFC 3-530-1. LIGHTING

ROOM IDENTIFICATION FACILITY GUIDELINES INSTITUTE FLOOR WALLS CEILING

Lessor: ________ VA:________

Name

Functional Area Number

& Name

Room

Code

Known

Legacy

Room

Code

Project Room Name

Quantity of This

Room

FGI Equivalent for ASHRAE 170

FGI Equivalent for Table 1-2-5

Minimum

Sound Isolation

F lo o r

F in is h

B a se

W a ll F in is h

W a ll F in is h A lt e rn a te

W a in sc o t

M a te ri a l

W a in sc o t

H e ig h t

S T

C

C e il in g H e ig h t

C e il in g F in is h

N o te s

S iz e

W id th

H e ig h t

T y p e

M a te ri a l

G la zi n g

R a ti n g

H a rd w a re

G ro u p

H a rd w a re

N o te s

In d o o r T e m p e ra tu re C o o li n g

F

In d o o r T e m p e ra tu re H e a ti n g

F

In d o o r R e la ti v e H u m id it y x

In d o o r R e la ti v e H u m id it y

M in im u m T o ta l A

C H

M in im u m O u ts id e

A ir

C h a n te

M in im u m O

A A

C H

R o o m

A ir

R e tu rn

G e n E x h

G S p e c

E x h S

M in im u m N o is e L e v e l

N C

R o o m

A ir

B a la n ce

H V

A C

N o te s

D u p le x

R e ce p ta cl e s

Q u a d R e ce p ta cl e s

P o w e r

N o te s

F ix tu re

T y p e

C o n tr o ls

Li g h ti n g

S p e ci a l R e q u ir e m e n ts

Li g h ti n g

N o te s

ROOM DATA MATRIX INTERIOR CONSTRUCTION DOORS AND HARDWARE MECHANICAL ELECTRICAL

Note: Use parameters within FGI Guidelines for the noted FGI Equivalent category unless otherwise noted. FGI is required for

Ambulatory Surgical Center ASHRAE Standard 170 and the balance of other spaces outdoor ventilation and exhaust would fall under the requirments of ASHRAE Standard 62.

Minimum receptacle quantities provided in this matrix. Equipment layouts must be assessed for each room to provide the correct receptacle and hardwire connection quantity. Where required by ASHRAE 90.1 and UFC 3-520-01, all workstations and work areas must have controlled and non-controlled outlets. All office, staff-support spaces, and other workstation locations require a minimum of two duplex receptacles, one double duplex, or one quadraplex receptacle for each workstation. Provide GFCI receptacles as required by NFPA 70. Receptacle layout and quantities must meet UFC 3-520-01 requirements.

POWER

Lighting fixture quantity and type provided are an estimate to meet minimum requirements.

Ceiling material selection will affect fixture type and size. Provide computer-generated photometric plans for each space to verify proposed lighting design meets the required performance criteria using the applicable light loss factor (LLF). All interior and exterior lighting design shall meet all UFC 3-530-1 and ASHRAE requirements. Egress lighting and controls shall comply with NFPA 101 and UFC 3-530-1. LIGHTING

ROOM IDENTIFICATION FACILITY GUIDELINES INSTITUTE FLOOR WALLS CEILING

SS217 OFA07 CBOC Hoteling Workstation 2 N/A m:CPT or m:LVT m:RB h:

4" m:GWB f:P N/A N/A 40 9'-0" m: AT N/A 7'-0" m: Open N/A N/A N/A 75 72 60 N/A N/A STD 62 STD 62 N/A N/A N/A N/A 4 1 2x4 D/I

Dimming-Comply with

AHRAE/UFC 3-530-1

SS268 RPR03 CBOC Team Copy / Supply Alcove 1 N/A m:CPT or m:LVT m:RB h:4" m:GWB f:P N/A N/A 40 9'-0" m: AT or GWB f: P

N/A 7'-0" m: Open N/A N/A N/A 75 72 60 N/A N/A STD 62 STD 62 N/A N/A N/A N/A 0 1 provide dedicated circuit for copy machine DL

Comply with

AHRAE/UFC 3-530-1

SS282 LR001 Universal Locker Room 1 N/A m:PT or m:RES m:PT or m:RES h:4" m:GWB f:SC m:PT or m:CT h:4'-0" 40 9'-0" m: AT 3'-0" 7'-0" 19 m: Wood N/A hw: 4U 75 72 60 N/A N/A STD 62 STD 62 N/A N/A N/A N/A 1 2x4 D/I

Comply with

AHRAE/UFC 3-530-1

SS291 CFR01 CBOC Huddle Space 1 N/A m:CPT m:RB h:4" m:GWB f:P N/A N/A 36 9'-0" m: AT 3'-8" 7'-0" 19 m: Wood T hw: 3G 75 72 60 N/A N/A STD 62 STD 62 N/A N/A N/A N/A 4 2x4 D/I

Comply with

AHRAE/UFC 3-530-1

CT024 Multipurpose Group Room 1 N/A m:CPT or m:LVT m:RB h:4" m:GWB f:P N/A N/A 40 9'-0" m: GWB f: P or m: AT

3'-6" 7'-0" 19 m: Wood N/A hw: 4N 75 72 60 N/A N/A STD 62 STD 62 N/A N/A N/A N/A 4 2x4 D/I

Comply with

AHRAE/UFC 3-530-1

CT025 Group Room Storage Room 1 N/A m:VT m:RB h:4" m:GWB f:P m:RWC h:4'-0" 40 9'-0" m: AT 3'-8" 7'-0" 11 m: Wood F hw: 5 75 72 60 N/A N/A STD 62 STD 62 N/A N/A N/A N/A 4 2x4 D/I

Comply with

AHRAE/UFC 3-530-1

CWV16 EXW01

Women Veteran Patient Care

Room 1 N/A m:LVT m: RB h:4" m:GWB f:P m:RWC h:4'-0" 35 9'-0" m: AT 3'-6" 7'-0" 19 m: Wood N/A hw: 1Q 75 72 60 N/A N/A STD 62 STD 62 N/A N/A N/A N/A 4 2x4 D/I

Dimming-Comply with

AHRAE/UFC 3-530-1

OCB31 EXRG3

General Patient Care

Room/Exam/Consult 19 N/A Aligns with FGI m: LVT m:RB h:4" m:GWB f:P N/A N/A 50 9'-0" m: GWB f: P or m: AT

4'-0" 7'-0" 19 m: Wood N/A hw: 1L 4N 75 72 60 N/A N/A STD 62 STD 62 N/A N/A N/A N/A 4 2x4 D/I

Dimming-Comply with

AHRAE/UFC 3-530-1

OCB37 EXEB1

Multi-Use / Bariatric Patient Care

Room/Procedure/Treatment/Fami ly Consult, CBOC

1 N/A Aligns with FGI m:WSF m:WSF h:4" m:GWB f:P N/A N/A 50 9'-0" m: GWB f: P or m: AT

3'-6" 7'-0" 19 m: Wood N/A hw: 4N 75 72 60 N/A N/A STD 62 STD 62 N/A N/A N/A N/A 4 2x4 D/I

Dimming-Comply with

AHRAE/UFC 3-530-1

SB003 WRC01 General Waiting 1 N/A m:CPT or m:LVT m:RB h:4" m:GWB f:P m:RWC h:4'-0" 40 9'-0" m: AT N/A 7'-0" m: Open N/A N/A N/A 75 72 60 N/A N/A STD 62 STD 62 N/A N/A N/A N/A 4 2x4 D/I

Comply with

AHRAE/UFC 3-530-1

SB159 TLTF2

CBOC Women Veteran Patient

Toilet 1 N/A Aligns with FGI m:PT or m:RES m: PT or

RES H:4"

m:GWB f:SC m:PT or m:CT 4'-0" 45 9'-0" 3'-0" 7'-0" 19 m: Wood N/A hw: 2G or 4B

75 72 60 N/A N/A STD 62 STD 62 G N/A (-) N/A 0

DL/VANI

TY

Comply with

AHRAE/UFC 3-530-1

SB191 TNPG1 Universal Non-Patient/Staff Toilet 2 N/A Aligns with FGI m:PT or m:RES m: PT or

RES H:4"

m:GWB f:SC m:PT or m:CT 4'-0" 45 9'-0" 3'-0" 7'-0" 19 m: Wood N/A hw: 2G or 4B

75 72 60 N/A N/A STD 62 STD 62 G N/A (-) N/A 1

DL/VANI

TY

Comply with

AHRAE/UFC 3-530-1

SB201 TPG01 CBOC Patient Toilet 2 N/A Aligns with FGI m:PT or m:RES m: PT or

RES H:4"

m:GWB f:SC m:PT or m:CT 4'-0" 45 9'-0" 3'-0" 7'-0" 19 m: Wood N/A hw: 2G or 4B

75 72 60 N/A N/A STD 62 STD 62 G N/A (-) N/A 0

DL/VANI

TY

Comply with

AHRAE/UFC 3-530-1

SB721 STEQ1 Medical Equipment Storage Room 1 N/A m:VT m:RB h:4" m:GWB f:P m:RWC h:4'-0" 40 9'-0" m: AT 3'-8" 7'-0" 11 m: Wood F hw: 5 75 72 60 N/A N/A STD 62 STD 62 G N/A (-) N/A 4 2x4 D/I

Comply with

AHRAE/UFC 3-530-1

SB737 UCCL1 Clean Utility Room 1 N/A m:WSF m:WSF h:4" m:GWB f:SC m:RWC h:4'-0" 35 9'-0" m: AT f:SP 3'-8" 7'-0" 11 m: Wood F SH-3C ds:YES 75 72 60 N/A N/A STD 62 STD 62 N/A N/A (+) N/A 4 2x4 D/I

Comply with

AHRAE/UFC 3-530-1

SB743 USCL1 Soiled Utility Room 1 N/A m:WSF m:WSF h:4" m:GWB f:SC m:RWC h:4'-0" 35 9'-0" m: AT f:SP 3'-8" 7'-0" 11 m: Wood F SH-3C ds:YES 75 72 60 N/A N/A STD 62 STD 62 G N/A (-) N/A 4 2x4 D/I

Comply with

AHRAE/UFC 3-530-1

SC066 PEHW2

CBOC Accessible Patient Height &

Weight Station 1 N/A m:WSF or m:LVT m:RB or m:WSF h:4" m:GWB f:P N/A N/A 40 9'-0" m: AT or GWB f: P

N/A 7'-0" m: Open N/A N/A N/A 75 72 60 N/A N/A STD 62 STD 62 N/A N/A N/A N/A 1 2x4 D/I

Comply with

AHRAE/UFC 3-530-1

SC079 CSME1

CBOC Point of Use Equipment

Alcove 1 N/A m:WSF or m:LVT m:RB or m:WSF h:4" m:GWB f:P N/A N/A 40 9'-0" m: AT or GWB f: P

N/A 7'-0" m: Open N/A N/A N/A 75 72 60 N/A N/A STD 62 STD 62 N/A N/A N/A N/A 0 DL

Comply with

AHRAE/UFC 3-530-1

SC083 CSMP1

Medication Alcove, Automated

Dispensing Unit 1 N/A m:WSF or m:LVT m:RB or m:WSF h:4" m:GWB f:P N/A N/A 40 9'-0" m: AT or GWB f: P

N/A 7'-0" m: Open N/A N/A N/A 75 72 60 N/A N/A STD 62 STD 62 N/A N/A N/A N/A 1 Provide dedicated circuit for med dispenser machine DL

Comply with

AHRAE/UFC 3-530-1

SC183 RCP01 Reception 1 N/A m:LVT or m:CPT m: RB h:4" m:GWB f:P N/A N/A 40 9'-0" m: AT

3'-0" or

OPEN

7'-0" or

OPEN

1 OR

OPEN

m: Wood

3E or

OPEN

hw: 3E or N/A 75 72 60 N/A N/A STD 62 STD 62 N/A N/A N/A N/A 4 1 2x4 D/I

Comply with

AHRAE/UFC 3-530-1

SC243 PACT Team Room (2 workstations) 12 N/A m:CPT or m:LVT m:RB h:

4" m:GWB f:P N/A N/A 40 9'-0" m: AT N/A 7'-0" m: Open N/A N/A N/A 75 72 60 N/A N/A STD 62 STD 62 N/A N/A N/A N/A 4 2 2x4 D/I

Dimming-Comply with

AHRAE/UFC 3-530-1

SC281 CBOC Point of Use Supply Alcove 1 N/A m:WSF or m:LVT m:RB or m:WSF h:4" m:GWB f:P N/A N/A 40 9'-0" m: AT or GWB f: P

N/A 7'-0" m: Open N/A N/A N/A 75 72 60 N/A N/A STD 62 STD 62 N/A N/A N/A N/A 0 DL

Comply with

AHRAE/UFC 3-530-1

SS217 OFA07 CBOC Hoteling Workstation 2 N/A m:CPT or m:LVT m:RB h:

4" m:GWB f:P N/A N/A 40 9'-0" m: AT N/A 7'-0" m: Open N/A N/A N/A 75 72 60 N/A N/A STD 62 STD 62 N/A N/A N/A N/A 4 1 2x4 D/I

Dimming-Comply with

AHRAE/UFC 3-530-1

SS268 RPR03 CBOC Team Copy / Supply Alcove 1 N/A m:CPT or m:LVT m:RB h:4" m:GWB f:P N/A 40 9'-0" m: AT or GWB f: P

N/A 7'-0" m: Open N/A N/A N/A 75 72 60 N/A N/A STD 62 STD 62 N/A N/A N/A N/A 0 1 provide dedicated circuit for copy machine DL

Comply with

AHRAE/UFC 3-530-1

SS282 LR001 Universal Locker Room 1 N/A m:PT or m:RES m:PT or m:RES h:4" m:GWB f:SC m:PT or m:CT h:4'-0" 40 9'-0" m: AT 3'-0" 7'-0" 19 m: Wood N/A hw: 4U 75 72 60 N/A N/A STD 62 STD 62 N/A N/A N/A N/A 1 2x4 D/I

Comply with

AHRAE/UFC 3-530-1

SS291 CFR01 CBOC Huddle Space 1 N/A m:CPT or m:LVT m:RB h:4" m:GWB f:P N/A N/A 40 9'-0" m: AT or GWB f: P

N/A 7'-0" m: Open N/A N/A N/A 75 72 60 N/A N/A STD 62 STD 62 N/A N/A N/A N/A 4 2x4 D/I

Comply with

AHRAE/UFC 3-530-1

CCD31 OPTM1 Stress Testing Treadmill Room 1 N/A m:LVT m:RB h:4" m:GWB f:P N/A N/A 40 9'-0" m: AT 4'-0" 7'-0" 19 m:Wood T hw: 4J 75 72 60 N/A N/A STD 62 STD 62 N/A N/A N/A N/A 4 provide dedicated circuit for treadmill 2x4 D/I

Comply with

AHRAE/UFC 3-530-1

CPL42 SRS01 Oxygen Cylinder Storage Room 1 N/A m:CPT or m:LVT m:RB h:4" m:GWB f:P N/A N/A 40 9'-0" m: AT or GWB w/ P

N/A 7'-0" m: Open N/A N/A N/A 75 72 60 N/A N/A STD 62 STD 62 N/A N/A N/A N/A 4 2x4 D/I

Comply with

AHRAE/UFC 3-530-1

CT024 Multipurpose Group Room 1 N/A m:CPT m:RB h:4" m:GWB f:P N/A N/A 40 9'-0" m: GWB 3'-6" 7'-0" 19 m: Wood N/A hw: 4N 75 72 60 N/A N/A STD 62 STD 62 N/A N/A N/A N/A 4 2x4 D/I

Comply with

AHRAE/UFC 3-530-1

CT025 Group Room Storage Room 1 N/A m:CPT or m:LVT m:RB h:4" m:GWB f:P N/A N/A 40 9'-0" m: AT or GWB w/ P

N/A 7'-0" m: Open N/A N/A N/A 75 72 60 N/A N/A STD 62 STD 62 N/A N/A N/A N/A 4 2x4 D/I

Comply with

AHRAE/UFC 3-530-1

CWV16 EXW01

Women Veteran Patient Care

Room 1 N/A m:LVT m: RB h:4" m:GWB f:P m:RWC h:4'-0" 35 9'-0" m: AT 3'-6" 7'-0" 19 m: Wood hw: 1Q 75 72 60 N/A N/A STD 62 STD 62 N/A N/A N/A N/A 4 2x4 D/I

Dimming-Comply with

AHRAE/UFC 3-530-1

OCB31 EXRG3

General Patient Care

Room/Exam/Consult - PACT &

Multi-specialty

18 N/A Aligns with FGI m: LVT m:RB h:4" m:GWB f:P N/A N/A 50 9'-0" m: GWB f: P or m: AT

3'-6" 7'-0" 19 m: Wood N/A hw: 4N 75 72 60 N/A N/A STD 62 STD 62 N/A N/A N/A N/A 4 2x4 D/I

Dimming-Comply with

AHRAE/UFC 3-530-1

OCB37 EXEB1

Multi-Use / Bariatric Patient Care

Room/Procedure/Treatment/Fami ly Consult, CBOC

2 N/A Aligns with FGI m:WSF m:WSF h:4" m:GWB f:P N/A N/A 50 9'-0" m: GWB f: P or m: AT

3'-6" 7'-0" 19 m: Wood N/A hw: 4N 75 72 60 N/A N/A STD 62 STD 62 N/A N/A N/A N/A 4 2x4 D/I

Dimming-Comply with

AHRAE/UFC 3-530-1

OCB37 EXEB1

Dermatology

Procedure/Treatment 1 N/A Aligns with FGI m:WSF m:WSF h:4" m:GWB f:P N/A N/A 50 9'-0" m: GWB f: P or m: AT

3'-6" 7'-0" 19 m: Wood N/A hw: 4N 75 72 60 N/A N/A STD 62 STD 62 N/A N/A N/A N/A 4 2x4 D/I

Dimming-Comply with

AHRAE/UFC 3-530-1

OCB41 EXP01 Podiatry Patient Care Room 3 N/A m:LVT m:RB h:4" m:GWB f:P N/A N/A 40 9'-0" m: GWB f: P or m: AT

3'-6" 7'-0" 19 m: Wood N/A hw: 4N 75 72 60 N/A N/A STD 62 STD 62 N/A N/A N/A N/A 4 2x4 D/I

Dimming-Comply with

AHRAE/UFC 3-530-1

SB003 WRC01 General Waiting 1 N/A m:CPT or m:LVT m:RB h:4" m:GWB f:P m:RWC h:4'-0" 40 9'-0" m: AT N/A 7'-0" m: Open N/A N/A N/A 75 72 60 N/A N/A STD 62 STD 62 N/A N/A N/A N/A 4 2x4 D/I

Comply with

AHRAE/UFC 3-530-1

SB159 TLTF2

CBOC Women Veteran Patient

Toilet 1 N/A Aligns with FGI m:PT or m:RES m: PT or

RES H:4"

m:GWB f:SC m:PT or m:CT 4'-0" 45 9'-0" 3'-0" 7'-0" 19 m: Wood N/A hw: 2G or 4B

75 72 60 N/A N/A STD 62 STD 62 N/A N/A N/A N/A 0

DL/VANI

TY

Comply with

AHRAE/UFC 3-530-1

SB191 TNPG1 Universal Non-Patient/Staff Toilet 2 N/A Aligns with FGI m:PT or m:RES m: PT or

RES H:4"

m:GWB f:SC m:PT or m:CT 4'-0" 45 9'-0" 3'-0" 7'-0" 19 m: Wood N/A hw: 2G or 4B

75 72 60 N/A N/A STD 62 STD 62 N/A N/A N/A N/A 1

DL/VANI

TY

Comply with

AHRAE/UFC 3-530-1

SB201 TPG01 CBOC Patient Toilet 3 N/A Aligns with FGI m:PT or m:RES m: PT or

RES H:4"

m:GWB f:SC m:PT or m:CT 4'-0" 45 9'-0" 3'-0" 7'-0" 19 m: Wood N/A hw: 2G or 4B

75 72 60 N/A N/A STD 62 STD 62 G N/A (-) N/A 0

DL/VANI

TY

Comply with

AHRAE/UFC 3-530-1

SB721 STEQ1 Medical Equipment Storage 2 N/A m:VT m:RB h:4" m:GWB f:P m:RWC h:4'-0" 40 9'-0" m: AT 3'-8" 7'-0" 11 m: Wood F hw: 5 75 72 60 N/A N/A STD 62 STD 62 N/A N/A N/A N/A 4 2x4 D/I

Comply with

AHRAE/UFC 3-530-1

SB737 UCCL1 Clean Utility Room 1 N/A m:WSF m:WSF h:4" m:GWB f:SC m:RWC h:4'-0" 35 9'-0" m: AT f:SP 3'-8" 7'-0" 11 m: Wood F SH-3C ds:YES 75 72 60 N/A N/A STD 62 STD 62 N/A N/A (+) N/A 4 2x4 D/I

Comply with

AHRAE/UFC 3-530-1

SB743 USCL1 Soiled Utility Room 1 N/A m:WSF m:WSF h:4" m:GWB f:SC m:RWC h:4'-0" 35 9'-0" m: AT f:SP 3'-8" 7'-0" 11 m: Wood F SH-3C ds:YES 75 72 60 N/A N/A STD 62 STD 62 G N/A (-) N/A 4 2x4 D/I

Comply with

AHRAE/UFC 3-530-1

SC066 PEHW2

CBOC Accessible Patient Height &

Weight Station 1 N/A m:LVT m:RB h:4" m:GWB f:P m:RWC h:4'-0" 40 9'-0" m: AT 3'-6" 7'-0" 19 m: Wood N/A hw: 3E 75 72 60 N/A N/A STD 62 STD 62 N/A N/A N/A N/A 1 2x4 D/I

Comply with

AHRAE/UFC 3-530-1

SC079 CSME1

CBOC Point of Use Equipment

Alcove 1 N/A m:CPT or m:LVT m:RB h:4" m:GWB f:P N/A N/A 40 9'-0" m: AT or GWB f: P

N/A 7'-0" m: Open N/A N/A N/A 75 72 60 N/A N/A STD 62 STD 62 N/A N/A N/A N/A 0 DL

Comply with

AHRAE/UFC 3-530-1

SC083 CSMP1 Medication Room 1 N/A m:VT m:RB h:4" m:GWB f:P N/A N/A 40 9'-0" m: AT 3'-0" 7'-0" 1 m: Wood T SH-3C ds:YES 75 72 60 N/A N/A STD 62 STD 62 N/A N/A N/A N/A 4 Provide dedicated circuit for med dispenser machine 2x4 D/I

Comply with

AHRAE/UFC 3-530-1

01 - COMMUNITY BASED

OUTPATIENT CLINIC

(CBOC) (265)

08 - PATIENT CARE AREA:

MULTI-SPECIALTY AND

ONE PACT TEAMLET

01 - COMMUNITY BASED

OUTPATIENT CLINIC

(CBOC) (265)

07 - PATIENT CARE AREA:

PRIMARY CARE-PACT -

MODULE 2

Name

Functional Area Number

& Name

Room

Code

Known

Legacy

Room

Code

Project Room Name

Quantity of This

Room

FGI Equivalent for ASHRAE 170

FGI Equivalent for Table 1-2-5

Minimum

Sound Isolation

F lo o r

F in is h

B a se

W a ll F in is h

W a ll F in is h A lt e rn a te

W a in sc o t

M a te ri a l

W a in sc o t

H e ig h t

S T

C

C e il in g H e ig h t

C e il in g F in is h

N o te s

S iz e

W id th

H e ig h t

T y p e

M a te ri a l

G la zi n g

R a ti n g

H a rd w a re

G ro u p

H a rd w a re

N o te s

In d o o r T e m p e ra tu re C o o li n g

F

In d o o r T e m p e ra tu re H e a ti n g

F

In d o o r R e la ti v e H u m id it y x

In d o o r R e la ti v e H u m id it y

M in im u m T o ta l A

C H

M in im u m O u ts id e

A ir

C h a n te

M in im u m O

A A

C H

R o o m

A ir

R e tu rn

G e n E x h

G S p e c

E x h S

M in im u m N o is e L e v e l

N C

R o o m

A ir

B a la n ce

H V

A C

N o te s

D u p le x

R e ce p ta cl e s

Q u a d R e ce p ta cl e s

P o w e r

N o te s

F ix tu re

T y p e

C o n tr o ls

Li g h ti n g

S p e ci a l R e q u ir e m e n ts

Li g h ti n g

N o te s

ROOM DATA MATRIX INTERIOR CONSTRUCTION DOORS AND HARDWARE MECHANICAL ELECTRICAL

Note: Use parameters within FGI Guidelines for the noted FGI Equivalent category unless otherwise noted. FGI is required for

Ambulatory Surgical Center ASHRAE Standard 170 and the balance of other spaces outdoor ventilation and exhaust would fall under the requirments of ASHRAE Standard 62.

Minimum receptacle quantities provided in this matrix. Equipment layouts must be assessed for each room to provide the correct receptacle and hardwire connection quantity. Where required by ASHRAE 90.1 and UFC 3-520-01, all workstations and work areas must have controlled and non-controlled outlets. All office, staff-support spaces, and other workstation locations require a minimum of two duplex receptacles, one double duplex, or one quadraplex receptacle for each workstation. Provide GFCI receptacles as required by NFPA 70. Receptacle layout and quantities must meet UFC 3-520-01 requirements.

POWER

Lighting fixture quantity and type provided are an estimate to meet minimum requirements.

Ceiling material selection will affect fixture type and size. Provide computer-generated photometric plans for each space to verify proposed lighting design meets the required performance criteria using the applicable light loss factor (LLF). All interior and exterior lighting design shall meet all UFC 3-530-1 and ASHRAE requirements. Egress lighting and controls shall comply with NFPA 101 and UFC 3-530-1. LIGHTING

ROOM IDENTIFICATION FACILITY GUIDELINES INSTITUTE FLOOR WALLS CEILING

SC183 RCP01 Reception 2 N/A m:LVT or m:CPT m: RB h:4" m:GWB f:P N/A N/A 40 9'-0" m: AT

3'-0" or

OPEN

7'-0" or

OPEN

1 OR

OPEN

m: Wood

3E or

OPEN

hw: 3E or N/A 75 72 60 N/A N/A STD 62 STD 62 N/A N/A N/A N/A 4 1 2x4 D/I

Comply with

AHRAE/UFC 3-530-1

SC243 PACT Team Room (2 workstations) 12 N/A m:CPT or m:LVT m:RB h:

4" m:GWB f:P N/A N/A 40 9'-0" m: AT N/A 7'-0" m: Open N/A N/A N/A 75 72 60 N/A N/A STD 62 STD 62 N/A N/A N/A N/A 4 2 2x4 D/I

Dimming-Comply with

AHRAE/UFC 3-530-1

SC281 CBOC Point of Use Supply Alcove 1 N/A m:CPT or m:LVT m:RB h:4" m:GWB f:P N/A N/A 40 9'-0" m: AT or GWB f: P

N/A 7'-0" m: Open N/A N/A N/A 75 72 60 N/A N/A STD 62 STD 62 N/A N/A N/A N/A 0 DL

Comply with

AHRAE/UFC 3-530-1

SS205 OFA09

Office, Nurse Manager, Specialty

Care 1 N/A m:LVT or m:CPT m:RB h:4" m:GWB f:P N/A N/A 40 9'-0" m: AT 3'-0" 7'-0" 1 m: Wood T hw: 3E 75 72 60 N/A N/A STD 62 STD 62 N/A N/A N/A N/A 5 1 2x4 D/I

Dimming-Comply with

AHRAE/UFC 3-530-1

SS217 OFA07 CBOC Hoteling Workstation 2 N/A m:CPT or m:LVT m:RB h:

4" m:GWB f:P N/A N/A 40 9'-0" m: AT N/A 7'-0" m: Open N/A N/A N/A 75 72 60 N/A N/A STD 62 STD 62 N/A N/A N/A N/A 4 1 2x4 D/I

Dimming-Comply with

AHRAE/UFC 3-530-1

SS268 RPR03 CBOC Team Copy / Supply Alcove 1 N/A m:CPT or m:LVT m:RB h:4" m:GWB f:P N/A N/A 40 9'-0" m: AT or GWB f: P

N/A 7'-0" m: Open N/A N/A N/A 75 72 60 N/A N/A STD 62 STD 62 N/A N/A N/A N/A 0 1 provide dedicated circuit for copy machine DL

Comply with

AHRAE/UFC 3-530-1

SS282 LR001 Universal Locker Room 1 N/A m:PT or m:RES m:PT or m:RES h:4" m:GWB f:SC m:PT or m:CT h:4'-0" 40 9'-0" m: AT 3'-0" 7'-0" 19 m: Wood N/A hw: 4U 75 72 60 N/A N/A STD 62 STD 62 N/A N/A N/A N/A 1 2x4 D/I

Comply with

AHRAE/UFC 3-530-1

SS291 CFR01 CBOC Huddle Space 1 N/A m:CPT or m:LVT m:RB h:

4" m:GWB f:P N/A N/A 40 9'-0" m: AT N/A 7'-0" m: Open N/A N/A N/A 75 72 60 N/A N/A STD 62 STD 62 N/A N/A N/A N/A 4 2x4 D/I

Comply with

AHRAE/UFC 3-530-1

CED66 Patient Storage Room 1 N/A m:VT m:RB h:4" m:GWB f:P m:RWC h:4'-0" 40 9'-0" m: AT 3'-8" 7'-0" 11 m: Wood F hw: 5 75 72 60 N/A N/A STD 62 STD 62 N/A N/A N/A N/A 4 2x4 D/I

Comply with

AHRAE/UFC 3-530-1

CT024

Multipurpose Group Room, MHC

Svc 3 N/A m:CPT or m:LVT m:RB h:4" m:GWB f:P N/A N/A 40 9'-0" m: GWB f: P or m: AT

3'-6" 7'-0" 19 m: Wood N/A hw: 4N 75 72 60 N/A N/A STD 62 STD 62 N/A N/A N/A N/A 4 2x4 D/I

Comply with

AHRAE/UFC 3-530-1

IMH17 Exam Room, MHC 3 N/A Aligns with FGI m:WSF m:WSF h:4" m:GWB f:P N/A N/A 40 9'-0" m: GWB f: P or m: AT

3'-6" 7'-0" 19 m: Wood N/A hw: 4N 75 72 60 N/A N/A STD 62 STD 62 N/A N/A N/A N/A 4 2x4 D/I

Dimming-Comply with

AHRAE/UFC 3-530-1

IMH17

Transcutaneous Magnetic

Stimulation (TMS) Room 1 N/A m:WSF m:WSF h:4" m:GWB f:P N/A N/A 40 9'-0" m: GWB f: P or m: AT

3'-6" 7'-0" 19 m: Wood N/A hw: 4N 75 72 60 N/A N/A STD 62 STD 62 N/A N/A N/A N/A 4 2x4 D/I

Dimming-Comply with

AHRAE/UFC 3-530-1

OCM05 OPMH3

CBOC Counseling Patient Care

Room 26 N/A m:LVT or m:CPT m:RB h:4" m:GWB f:P N/A N/A 40 9'-0" m: AT or GWB 3'-8" 7'-0" 19 m: Wood N/A hw: 4N 75 72 60 N/A N/A STD 62 STD 62 N/A N/A N/A N/A 4 2x4 D/I

Dimming-Comply with

AHRAE/UFC 3-530-1

SB003 WRC01 MHC Waiting, Bldg Sprt 1 N/A m:CPT or m:LVT m:RB h:4" m:GWB f:P m:RWC h:4'-0" 40 9'-0" m: AT N/A 7'-0" m: Open N/A N/A N/A 75 72 60 N/A N/A STD 62 STD 62 N/A N/A N/A N/A 4 2x4 D/I

Comply with

AHRAE/UFC 3-530-1

SB199 TSPG1

Universal Patient Toilet / Shower, Bldg Sprt 1 N/A Aligns with FGI m:PT or m:RES m: PT or

RES H:4"

m:GWB f:SC m:PT or

CT or S h:

4'-0"

4'-0" 45 9'-0" m: GWB f:SC 3'-6" m: Wood N/A hw:2H 75 72 60 N/A N/A STD 62 STD 62 N/A N/A N/A N/A 1

DL/VANI

TY

Comply with

AHRAE/UFC 3-530-1

SB201 TPG01 MHC Patient Toilet, Bldg Sprt 3 N/A Aligns with FGI m:PT or m:RES m: PT or

RES H:4"

m:GWB f:SC m:PT or m:CT 4'-0" 45 9'-0" 3'-0" 7'-0" 19 m: Wood N/A hw: 2G or 4B

75 72 60 N/A N/A STD 62 STD 62 G N/A (-) N/A 0

DL/VANI

TY

Comply with

AHRAE/UFC 3-530-1

SC183 RCP01 MHC Reception, Clncl Sprt 1 N/A m:LVT or m:CPT m: RB h:4" m:GWB f:P N/A N/A 40 9'-0" m: AT

3'-0" or

OPEN

7'-0" or

OPEN

1 OR

OPEN

m: Wood

3E or

OPEN

hw: 3E or N/A 75 72 60 N/A N/A STD 62 STD 62 N/A N/A N/A N/A 4 1 2x4 D/I

Comply with

AHRAE/UFC 3-530-1

E-Range Team Room (2 workstations) 2 N/A m:CPT or m:LVT m:RB h:

4" m:GWB f:P N/A N/A 40 9'-0" m: AT N/A 7'-0" m: Open N/A N/A N/A 75 72 60 N/A N/A STD 62 STD 62 N/A N/A N/A N/A 4 2 2x4 D/I

Dimming-Comply with

AHRAE/UFC 3-530-1

Social Worker Team Room (2 workstations) 2 N/A m:CPT or m:LVT m:RB h:

4" m:GWB f:P N/A N/A 40 9'-0" m: AT N/A 7'-0" m: Open N/A N/A N/A 75 72 60 N/A N/A STD 62 STD 62 N/A N/A N/A N/A 4 2 2x4 D/I

Dimming-Comply with

AHRAE/UFC 3-530-1

SC249 WRTM3

CBOC Telehealth Patient Care

Room, Clncl Sprt 2 N/A Aligns with FGI m:CPT or m:LVT m: RB h:

4" m:GWB f:P N/A N/A 55 9'-0" m: AT 3'-0" 7'-0" 19 m: Wood S hw: 3E 75 72 60 N/A N/A STD 62 STD 62 N/A N/A N/A N/A 4 2x4 D/I

Dimming-Comply with

AHRAE/UFC 3-530-1

SS258 Printer Station, Stff Sprt 1 N/A m:CPT or m:LVT m:RB h:

4" m:GWB f:P N/A N/A 40 9'-0" m: AT N/A 7'-0" m: Open N/A N/A N/A 75 72 60 N/A N/A STD 62 STD 62 N/A N/A N/A N/A 2 1 2x4 D/I

Comply with

AHRAE/UFC 3-530-1

SV007 OFDC2 Family Consult Room 1 N/A Aligns with FGI m:CPT m:RB h:4" m:GWB f:P N/A N/A 50 9'-0" m: AT 3'-8" 7'-0" 19 m: Wood T hw: 3G 75 72 60 N/A N/A STD 62 STD 62 N/A N/A N/A N/A 4 Provide dedicated circuit for med dispenser machine 2x4 D/I

Comply with

AHRAE/UFC 3-530-1

CAS01 AURH2

Audiology Counseling Room, ASLP

Svc 5 N/A m:CPT m:RB h:4" m:GWB f:P N/A N/A 40 9'-0" m: AT 3'-8" 7'-0" 19 m: Wood N/A hw: 3F 75 72 60 N/A N/A STD 62 STD 62 N/A N/A N/A N/A 4 2x4 D/I

Dimming-Comply with

AHRAE/UFC 3-530-1

CAS11 AUDE2

Audiometric Booth Patient Care

Room, ASLP Svc 3 N/A PREFAB PREFAB PREFAB PREFAB PREFAB PREFAB PREFAB PREFAB PREFAB PREFAB PREFAB PREFAB PREFAB PREFAB PREFAB PREFAB PREFAB PREFAB 75 72 60 N/A N/A STD 62 STD 62 N/A N/A N/A N/A 4 provide dedicated circuit for audio booth 2x4 D/I

Dimming-Comply with

AHRAE/UFC 3-530-1

CAS31 AUD04

Audiology Treatment Room, ASLP

Svc 1 N/A Aligns with FGI m:LVT m: RB h:

4" m:GWB f:P N/A N/A 50 9'-0" m: AT 3'-6" 7'-0" 19 m: Wood N/A hw: 4N 75 72 60 N/A N/A STD 62 STD 62 N/A N/A N/A N/A 6 2x4 D/I

Comply with

AHRAE/UFC 3-530-1

CAS51

Speech-Language Pathology

Exam/consult, ASLP Svc 1 N/A Aligns with FGI m:LVT m:RB h:4" m:GWB f:P N/A N/A 50 9'-0" m: AT 3'-0" 7'-0" 19 m: Wood N/A hw:1Q 4N 75 72 60 N/A N/A STD 62 STD 62 N/A N/A N/A N/A 4 2x4 D/I

Dimming-Comply with

AHRAE/UFC 3-530-1

CAS67 AUDS1

Audiology Hearing Aid Lab, ASLP

Svc 1 N/A m:WSF m:WSF h:4" m:GWB f:P N/A N/A 40 9'-0" m: AT 3'-6" 7'-0" 19 m: Wood N/A hw: 4N 75 72 60 N/A N/A STD 62 STD 62 N/A N/A N/A N/A 4 2x4 D/I

Dimming-Comply with

AHRAE/UFC 3-530-1

CAS76 SRSP1

Audiology Supply Storage Room, ASLP Svc 1 N/A m:VT m:RB h:4" m:GWB f:P m:RWC h:4'-0" 40 9'-0" m: AT 3'-8" 7'-0" 11 m: Wood F hw: 5 75 72 60 N/A N/A STD 62 STD 62 N/A N/A N/A N/A 4 2x4 D/I

Comply with

AHRAE/UFC 3-530-1

CAS94 HAFR1

Hearing Aid Fitting Patient Care

Room, ASLP Svc 2 N/A m:CPT m:RB h:4" m:GWB f:P N/A N/A 40 9'-0" m: AT 3'-8" 7'-0" 19 m: Wood N/A hw: 3F 75 72 60 N/A N/A STD 62 STD 62 N/A N/A N/A N/A 4 2x4 D/I

Dimming-Comply with

AHRAE/UFC 3-530-1

SB003 WRC01 Audiology Waiting, Bldg Sprt 1 N/A m:CPT or m:LVT m:RB h:4" m:GWB f:P m:RWC h:4'-0" 40 9'-0" m: AT N/A 7'-0" m: Open N/A N/A N/A 75 72 60 N/A N/A STD 62 STD 62 N/A N/A N/A N/A 4 2x4 D/I

Comply with

AHRAE/UFC 3-530-1

SB201 TPG01 Patient Toilet, Bldg Sprt 1 N/A Aligns with FGI m:PT or m:RES m: PT or

RES H:4"

m:GWB f:SC m:PT or

CT or S 4'-0" 45 9'-0" m: GWB f: SC 3'-6" 7'-0" 1 m: Wood N/A hw:2H 2 or 4U 75 72 60 N/A N/A STD 62 STD 62 G N/A (-) N/A 0

DL/VANI

TY

Comply with

AHRAE/UFC 3-530-1

SC183 RCP01 Audiology Reception, Clncl Sprt 1 N/A m:LVT or m:CPT m: RB h:4" m:GWB f:P N/A N/A 40 9'-0" m: AT

3'-0" or

OPEN

7'-0" or

OPEN

1 OR

OPEN

m: Wood

3E or

OPEN

hw: 3E or N/A 75 72 60 N/A N/A STD 62 STD 62 N/A N/A N/A N/A 4 1 2x4 D/I

Comply with

AHRAE/UFC 3-530-1

SS258 Printer Station, Stff Sprt 1 N/A m:CPT m:RB h:4" m:GWB f:P N/A N/A 35 9'-0" m: AT 3'-0" 7'-0" 19 m: Wood S hw: 1L 75 72 60 N/A N/A STD 62 STD 62 N/A N/A N/A N/A 2 1 2x4 D/I

Comply with

AHRAE/UFC 3-530-1

CDS03 DNXS1

Panoramic / Cephalometric X-Ray

Room 1 N/A m:LVT m:RB h:4" m:GWB f:P N/A N/A N/A 40 9'-0" m: AT 4'-0" 7'-0" 15 m: Wood N/A hw: 4Q 75 72 60 N/A N/A STD 62 STD 62 N/A N/A N/A N/A 4 2x4 D/I

Dimming-Comply with

AHRAE/UFC 3-530-1

CDS11 DNTG1

Multifunctional Dental Treatment

Patient Care Room 10 N/A Aligns with FGI m:LVT m:RB h:4" m:GWB f:P m:RWC h:4'-0" 50 9'-0" m: AT 3'-6" 7'-0" 19 m: Wood N/A hw: 1L 75 72 60 N/A N/A STD 62 STD 62 N/A N/A N/A N/A 4 2x4 D/I

Dimming-Comply with

AHRAE/UFC 3-530-1

CDS13 DNTG5

Special Needs Dental Treatment

Room (DTR) 1 N/A Aligns with FGI m:RF m:RF h:4" m:GWB f:SC N/A N/A 50 9'-0" m:AT 3'-0" 7'-0" 19 m: Wood N/A hw: 1L 75 72 60 N/A N/A STD 62 STD 62 N/A N/A N/A N/A 4 2x4 D/I

Dimming-Comply with

AHRAE/UFC 3-530-1

CDS21 UCCL1 Clean Supply Room 1 N/A m:WSF m:WSF h:4" m:GWB f:SC m:RWC h:4'-0" 35 9'-0" m: AT f:SP 3'-8" 7'-0" 11 m: Wood F SH-3C ds:YES 75 72 60 N/A N/A STD 62 STD 62 N/A N/A (+) N/A 4 2x4 D/I

Comply with

AHRAE/UFC 3-530-1

CDS26 SRS01 Supply Storage Room 1 N/A m:VT m:RB h:4" m:GWB f:P m:RWC h:4'-0" 40 9'-0" m: AT 3'-8" 7'-0" 11 m: Wood F hw: 5 75 72 60 N/A N/A STD 62 STD 62 N/A N/A N/A N/A 4 2x4 D/I

Comply with

AHRAE/UFC 3-530-1

CDS47 DNTS1 Surgery Operating Room (OR) 3 N/A Aligns with FGI m:WSF m:WSF h:4" m:GWB f:SC m:RWC h:4'-0" 50 9'-0" m: AT f:SP 3'-8" 7'-0" 11 m: Wood F SH-3C ds:YES 75 72 60 N/A 20 4 4 N/A N/A (+) N/A

Each operating room shall be provided with a minimum of 36 receptacles divided between at least two branch circuits. At least 12 receptacles, but no more than 24, shall be connected to either.

CDS51 DNPL1 General Purpose Laboratory 1 N/A m:WSF or m:RES m: RES h:

4" m:GWB f:SC N/A N/A 40 9'-0" m: GWB f: SC SC 3'-0" 7'-0" 1 m: Wood T hw:4G 4K 75 72 60 N/A N/A STD 62 STD 62 N/A N/A N/A N/A 4 2x4 D/I

Comply with

AHRAE/UFC 3-530-1

CDS95 MECH1

Dental Equipment Mechanical

Room 1 N/A m:VT m:RB h:4" m:GWB f:P m:RWC h:4'-0" 40 9'-0" m: AT 3'-8" 7'-0" 11 m: Wood F hw: 5 75 72 60 N/A N/A STD 62 STD 62 N/A N/A N/A N/A 4 1x4 IF

Comply with

AHRAE/UFC 3-530-1

SB003 WRC01 Dental Waiting 4 N/A m:CPT or m:LVT m:RB h:4" m:GWB f:P m:RWC h:4'-0" 40 9'-0" m: AT N/A 7'-0" m: Open N/A N/A N/A 75 72 60 N/A N/A STD 62 STD 62 N/A N/A N/A N/A 4 2x4 D/I

Comply with

AHRAE/UFC 3-530-1

SB191 TNPG1

Dental Universal Non-Patient

Toilet 1 N/A Aligns with FGI m:PT or m:RES m: PT or

RES H:4"

m:GWB f:SC m:PT or

CT or S 4'-0" 45 9'-0" m: GWB f: SC 3'-6" 7'-0" 1 m: Wood N/A hw:2H 2 or 4U 75 72 60 N/A N/A STD 62 STD 62 G N/A (-) N/A 1

DL/VANI

TY

Comply with

AHRAE/UFC 3-530-1

SC243

01 - COMMUNITY BASED

OUTPATIENT CLINIC

(CBOC) (265)

11 - PATIENT CARE AREA:

DENTAL

01 - COMMUNITY BASED

OUTPATIENT CLINIC

(CBOC) (265)

09 - PATIENT CARE AREA:

MENTAL HEALTH

01 - COMMUNITY BASED

OUTPATIENT CLINIC

(CBOC) (265)

10 - PATIENT CARE AREA:

AUDIOLOGY

Name

Functional Area Number

& Name

Room

Code

Known

Legacy

Room

Code

Project Room Name

Quantity of This

Room

FGI Equivalent for ASHRAE 170

FGI Equivalent for Table 1-2-5

Minimum

Sound Isolation

F lo o r

F in is h

B a se

W a ll F in is h

W a ll F in is h A lt e rn a te

W a in sc o t

M a te ri a l

W a in sc o t

H e ig h t

S T

C

C e il in g H e ig h t

C e il in g F in is h

N o te s

S iz e

W id th

H e ig h t

T y p e

M a te ri a l

G la zi n g

R a ti n g

H a rd w a re

G ro u p

H a rd w a re

N o te s

In d o o r T e m p e ra tu re C o o li n g

F

In d o o r T e m p e ra tu re H e a ti n g

F

In d o o r R e la ti v e H u m id it y x

In d o o r R e la ti v e H u m id it y

M in im u m T o ta l A

C H

M in im u m O u ts id e

A ir

C h a n te

M in im u m O

A A

C H

R o o m

A ir

R e tu rn

G e n E x h

G S p e c

E x h S

M in im u m N o is e L e v e l

N C

R o o m

A ir

B a la n ce

H V

A C

N o te s

D u p le x

R e ce p ta cl e s

Q u a d R e ce p ta cl e s

P o w e r

N o te s

F ix tu re

T y p e

C o n tr o ls

Li g h ti n g

S p e ci a l R e q u ir e m e n ts

Li g h ti n g

N o te s

ROOM DATA MATRIX INTERIOR CONSTRUCTION DOORS AND HARDWARE MECHANICAL ELECTRICAL

Note: Use parameters within FGI Guidelines for the noted FGI Equivalent category unless otherwise noted. FGI is required for

Ambulatory Surgical Center ASHRAE Standard 170 and the balance of other spaces outdoor ventilation and exhaust would fall under the requirments of ASHRAE Standard 62.

Minimum receptacle quantities provided in this matrix. Equipment layouts must be assessed for each room to provide the correct receptacle and hardwire connection quantity. Where required by ASHRAE 90.1 and UFC 3-520-01, all workstations and work areas must have controlled and non-controlled outlets. All office, staff-support spaces, and other workstation locations require a minimum of two duplex receptacles, one double duplex, or one quadraplex receptacle for each workstation. Provide GFCI receptacles as required by NFPA 70. Receptacle layout and quantities must meet UFC 3-520-01 requirements.

POWER

Lighting fixture quantity and type provided are an estimate to meet minimum requirements.

Ceiling material selection will affect fixture type and size. Provide computer-generated photometric plans for each space to verify proposed lighting design meets the required performance criteria using the applicable light loss factor (LLF). All interior and exterior lighting design shall meet all UFC 3-530-1 and ASHRAE requirements. Egress lighting and controls shall comply with NFPA 101 and UFC 3-530-1. LIGHTING

ROOM IDENTIFICATION FACILITY GUIDELINES INSTITUTE FLOOR WALLS CEILING

SB201 TPG01 Dental Patient Toilet 1 N/A Aligns with FGI m:PT or m:RES m: PT or

RES H:4"

m:GWB f:SC m:PT or

CT or S 4'-0" 45 9'-0" m: GWB f: SC 3'-6" 7'-0" 1 m: Wood N/A hw:2H 2 or 4U 75 72 60 N/A N/A STD 62 STD 62 G N/A (-) N/A 0

DL/VANI

TY

Comply with

AHRAE/UFC 3-530-1

SB743 USCL1 Soiled Holding Room 1 N/A m:WSF m:WSF h:4" m:GWB f:SC m:RWC h:4'-0" 35 9'-0" m: AT f:SP 3'-8" 7'-0" 11 m: Wood F SH-3C ds:YES 75 72 60 N/A N/A STD 62 STD 62 G N/A (-) N/A 4 2x4 D/I

Comply with

AHRAE/UFC 3-530-1

SB763 SRS04 Sterile Supplies Room 1 N/A m:WSF m:WSF h:4" m:GWB f:SC N/A N/A 35 9'-0" m: AT 3'-6" 7'-0" 19 m: Wood hw: 5B 75 72 60 N/A N/A STD 62 STD 62 N/A N/A (+) N/A 4 2x4 D/I

Comply with

AHRAE/UFC 3-530-1

SC083 CSMP1 Dental Medication Room 1 N/A m:VT m:RB h:4" m:GWB f:P N/A N/A 40 9'-0" m: AT 3'-0" 7'-0" 1 m: Wood T SH-3C ds:YES 75 72 60 N/A N/A STD 62 STD 62 N/A N/A N/A N/A 4 2x4 D/I

Comply with

AHRAE/UFC 3-530-1

SC183 RCP01 Dental Reception 1 N/A m:LVT or m:CPT m: RB h:4" m:GWB f:P N/A N/A 40 9'-0" m: AT

3'-0" or

OPEN

7'-0" or

OPEN

1 OR

OPEN

m: Wood

3E or

OPEN

hw: 3E or N/A 75 72 60 N/A N/A STD 62 STD 62 N/A N/A N/A N/A 4 1 2x4 D/I

Comply with

AHRAE/UFC 3-530-1

SC243 Dental Team Room 1 N/A m:CPT or m:LVT m:RB h:4 m:GWB f:P N/A N/A 40 9'-0" m: AT 3'-0" 7'-0" 19 m: Wood T hw: 3G 75 72 60 N/A N/A STD 62 STD 62 N/A N/A N/A N/A 4 2x4 D/I

Comply with

AHRAE/UFC 3-530-1

SS204 OFA09 Office, Chief 1 N/A m:LVT or m:CPT m:RB h:4" m:GWB f:P N/A N/A 40 9'-0" m: AT 3'-0" 7'-0" 1 m: Wood T hw: 3E 75 72 60 N/A N/A STD 62 STD 62 N/A N/A N/A N/A 5 1 2x4 D/I

Dimming-Comply with

AHRAE/UFC 3-530-1

SS209 OFD02 Admin Team Room 1 N/A m:CPT or m:LVT m:RB h:4 m:GWB f:P N/A N/A 40 9'-0" m: AT 3'-0" 7'-0" 19 m: Wood T hw: 3G 75 72 60 N/A N/A STD 62 STD 62 N/A N/A N/A N/A 4 2x4 D/I

Comply with

AHRAE/UFC 3-530-1

SS258 Printer Station 1 N/A m:LVT m:RB h:4" m:GWB f:P m:RWC h:4'-0" 40 9'-0" m: AT N/A 7'-0" m: Open N/A N/A N/A 75 72 60 N/A N/A STD 62 STD 62 N/A N/A N/A N/A 2 1 2x4 D/I

Comply with

AHRAE/UFC 3-530-1

CEY12 OPVF1 Visual Fields Room 1 N/A m:LVT m:RB h:4" m:GWB f:P N/A N/A 40 9'-0" m: AT 3'-0" 7'-0" 19 m: Wood N/A hw: 1L 75 72 60 N/A N/A STD 62 STD 62 N/A N/A N/A N/A 4 2x4 D/I

Comply with

AHRAE/UFC 3-530-1

CEY13 EYVF1 Photography Room 1 N/A m: LVT m: RB h:4" m: GWB f:P N/A N/A 40 9'-0" m: AT 3'-0" 7'-0" 19 m: Wood N/A hw: 1L 75 72 60 N/A N/A STD 62 STD 62 N/A N/A N/A N/A 4 2x4 D/I

Comply with

AHRAE/UFC 3-530-1

CEY16 OPIM1 Imaging Room 1 N/A m: WSF m: WSF h:

4" m: GWB f: SC N/A N/A 40 9'-0" m: AT 3'-6" 7'-0" 19 m: Wood N/A hw: 1Q 75 72 60 N/A N/A STD 62 STD 62 N/A N/A N/A N/A 4 2x4 D/I

Comply with

AHRAE/UFC 3-530-1

CEY34 STEQ1 Equipment Storage Room 1 N/A m:VT m:RB h:4" m:GWB f:P m:RWC h:4'-0" 40 9'-0" m: AT 3'-8" 7'-0" 11 m: Wood F hw: 4Q 75 72 60 N/A N/A STD 62 STD 62 N/A N/A N/A N/A 4 2x4 D/I

Comply with

AHRAE/UFC 3-530-1

CEY41 SRS01 Supply Storage Room 1 N/A m:VT m:RB h:4" m:GWB f:P m:RWC h:4'-0" 40 9'-0" m: AT 3'-8" 7'-0" 11 m: Wood F hw: 3G 75 72 60 N/A N/A STD 62 STD 62 N/A N/A N/A N/A 4 2x4 D/I

Comply with

AHRAE/UFC 3-530-1

CEY52 OPPT2 Testing Patient Care Room 2 N/A m:LVT m:RB h:4" m:GWB f:P N/A N/A 40 9'-0" m: AT 3'-0" 7'-0" 19 m: Wood N/A hw: 5B 75 72 60 N/A N/A STD 62 STD 62 N/A N/A N/A N/A 4 2x4 D/I

Comply with

AHRAE/UFC 3-530-1

CEY53 OPET2 Patient Care Room 12 N/A m:LVT m:RB h:4" m:GWB f:P N/A N/A 40 9'-0" m: AT 3'-0" 7'-0" 19 m: Wood N/A hw: 1Q 75 72 60 N/A N/A STD 62 STD 62 N/A N/A N/A N/A 4 2x4 D/I

Comply with

AHRAE/UFC 3-530-1

CEY91 EYFD1

Eyeglass Fitting & Dispensing

Patient Care Room 1 N/A m:LVT m:RB h:4" m:GWB f:P N/A N/A 40 9'-0" m: AT 3'-0" 7'-0" 19 m: Wood N/A hw: 4F 75 72 60 N/A N/A STD 62 STD 62 N/A N/A N/A N/A 4 2x4 D/I

Comply with

AHRAE/UFC 3-530-1

SB001 Dilation Seating Alcove 2 N/A m:CPT or m:LVT m:RB h:4" m:GWB f:P m:RWC h:4'-0" 40 9'-0" m: AT N/A 7'-0" m: Open N/A N/A N/A 75 72 60 N/A N/A STD 62 STD 62 N/A N/A N/A N/A 1 DL

Comply with

AHRAE/UFC 3-530-1

SB003 WRC01 Eye Clinic Waiting 1 N/A m:CPT or m:LVT m:RB h:4" m:GWB f:P m:RWC h:4'-0" 40 9'-0" m: AT N/A 7'-0" m: Open N/A N/A N/A 75 72 60 N/A N/A STD 62 STD 62 N/A N/A N/A N/A 4 2x4 D/I

Comply with

AHRAE/UFC 3-530-1

SB201 TPG01 Patient Toilet 2 N/A Aligns with FGI m:PT or m:RES m: PT or

RES H:4"

m:GWB f:SC m:PT or

CT or S 4'-0" 45 9'-0" m: GWB f: SC 3'-6" 7'-0" 1 m: Wood N/A hw:2H 2 or 4U 75 72 60 N/A N/A STD 62 STD 62 G N/A (-) N/A 0

DL/VANI

TY

Comply with

AHRAE/UFC 3-530-1

SB743 USCL1 Soiled Utility Room 1 N/A m:WSF m:WSF h:4" m:GWB f:SC m:RWC h:4'-0" 35 9'-0" m: AT f:SP 3'-8" 7'-0" 11 m: Wood F SH-3C ds:YES 75 72 60 N/A N/A STD 62 STD 62 G N/A (-) N/A 4 2x4 D/I

Comply with

AHRAE/UFC 3-530-1

SC183 RCP01 Eye Clinic Reception 1 N/A m:LVT or m:CPT m: RB h:4" m:GWB f:P N/A N/A 40 9'-0" m: AT

3'-0" or

OPEN

7'-0" or

OPEN

1 OR

OPEN

m: Wood

3E or

OPEN

hw: 3E or N/A 75 72 60 N/A N/A STD 62 STD 62 N/A N/A N/A N/A 4 1 2x4 D/I

Comply with

AHRAE/UFC 3-530-1

SC243 Team Room (2 workstations) 2 N/A m:CPT or m:LVT m:RB h:

4" m:GWB f:P N/A N/A 40 9'-0" m: AT N/A 7'-0" m: Open N/A N/A N/A 75 72 60 N/A N/A STD 62 STD 62 N/A N/A N/A N/A 4 2 2x4 D/I

Dimming-Comply with

AHRAE/UFC 3-530-1

SS204 OFA09 Supervisor Office 1 N/A m:LVT or m:CPT m:RB h:4" m:GWB f:P N/A N/A 40 9'-0" m: AT 3'-0" 7'-0" 1 m: Wood T hw: 3E 75 72 60 N/A N/A STD 62 STD 62 N/A N/A N/A N/A 5 1 2x4 D/I

Dimming-Comply with

AHRAE/UFC 3-530-1

SS258 Printer Station 1 N/A m:CPT orm:LVT m:RB h:4" m:GWB f:P N/A N/A 40 9'-0" m: AT or GWB f: P

N/A 7'-0" m: Open N/A N/A N/A 75 72 60 N/A N/A STD 62 STD 62 N/A N/A N/A N/A 2 1 2x4 D/I

Comply with

AHRAE/UFC 3-530-1

Infusion Bay 8 N/A m:VT m:RB h:4" m:GWB f:P m:RWC m:4'-0" 35 9'-0" m: AT 3'-8" 7'-0" 11 m: Wood N/A SH-3F 75 72 60 N/A N/A STD 62 STD 62 N/A N/A N/A N/A 4 2x4 D/I

Comply with

AHRAE/UFC 3-530-1

Infusion Room 2 N/A m:VT m:RB h:4" m:GWB f:P m:RWC m:4'-0" 35 9'-0" m: AT 3'-8" 7'-0" 11 m: Wood N/A SH-3F 75 72 60 N/A N/A STD 62 STD 62 N/A N/A N/A N/A 4 2x4 D/I

Comply with

AHRAE/UFC 3-530-1

SB003 WRC01 General Waiting 1 N/A m:CPT or m:LVT m:RB h:4" m:GWB f:P m:RWC h:4'-0" 40 9'-0" m: AT N/A 7'-0" m: Open N/A N/A N/A 75 72 60 N/A N/A STD 62 STD 62 N/A N/A N/A N/A 4 2x4 D/I

Comply with

AHRAE/UFC 3-530-1

SB201 TPG01 Patient Toilet 2 N/A Aligns with FGI m:PT or m:RES m: PT or

RES H:4"

m:GWB f:SC m:PT or

CT or S 4'-0" 45 9'-0" m: GWB f: SC 3'-6" 7'-0" 1 m: Wood N/A hw:2H 2 or 4U 75 72 60 N/A N/A STD 62 STD 62 G N/A (-) N/A 0

DL/VANI

TY

Comply with

AHRAE/UFC 3-530-1

SB721 STEQ1 Medical Equipment Storage Room 2 N/A m:VT m:RB h:4" m:GWB f:P m:RWC h:4'-0" 40 9'-0" m: AT 3'-8" 7'-0" 11 m: Wood F hw: 5 75 72 60 N/A N/A STD 62 STD 62 N/A N/A N/A N/A 4 2x4 D/I

Comply with

AHRAE/UFC 3-530-1

SB735 UCCL1 Clean Utility Room 1 N/A m:WSF m:WSF h:4" m:GWB f:SC m:RWC h:4'-0" 35 9'-0" m: AT f:SP 3'-8" 7'-0" 11 m: Wood F SH-3C ds:YES 75 72 60 N/A N/A STD 62 STD 62 N/A N/A (+) N/A 4 2x4 D/I

Comply with

AHRAE/UFC 3-530-1

SB741 USCL1 Soiled Utility Holding Room 1 N/A m:WSF m:WSF h:4" m:GWB f:SC m:RWC h:4'-0" 35 9'-0" m: AT…

This is the start of the file's text. The full file is on GovTribe.