The document is a comprehensive Room Data Matrix (RDM) for the Port St. Lucie, Florida Outpatient Clinic (OPC) project, detailing specifications for numerous rooms across multiple functional areas. The matrix provides extensive technical details for each room, including room codes, quantities, floor and wall finishes, mechanical and electrical requirements, door hardware, temperature and humidity specifications, and power/receptacle configurations.
The Room Data Matrix covers multiple functional areas including Community Based Outpatient Clinic (CBOC), Ambulatory Surgery Center (ASC), Sterile Processing Service (SPS), and various clinical and support spaces such as primary care, mental health, audiology, dental, eye clinic, imaging, laboratory, pharmacy, and staff support areas. Each room entry specifies precise requirements for construction materials, environmental conditions, air exchange rates, noise levels, and electrical infrastructure, providing a comprehensive blueprint for the facility's interior design and technical specifications.
View the file
Other files
Show all 36
On GovTribe
Work with this file
- Download the original file
- Contacts named in this file
- Similar government files
- Ask GovTribe AI about this file
Text version
NOTES
Department Number &
Name
Functional Area Number
& Name
Room
Code
Known
Legacy
Room
Code
Project Room Name
Quantity of This
Room
FGI Equivalent for ASHRAE 170
FGI Equivalent for Table 1-2-5
Minimum
Sound Isolation
F lo o r
F in is h
B a se
W a ll F in is h
W a ll F in is h A lt e rn a te
W a in sc o t
M a te ri a l
W a in sc o t
H e ig h t
S T
C
C e il in g H e ig h t
C e il in g F in is h
N o te s
S iz e
W id th
H e ig h t
T y p e
M a te ri a l
G la zi n g
R a ti n g
H a rd w a re
G ro u p
H a rd w a re
N o te s
In d o o r T e m p e ra tu re C o o li n g
F
In d o o r T e m p e ra tu re H e a ti n g
F
In d o o r R e la ti v e H u m id it y
R H
M a x
In d o o r R e la ti v e H u m id it y in
M in im u m T o ta l A
C H
M in im u m O u ts id e
A ir
C h a n g e te
M in im u m O
A A
C H
R o o m
A ir
R e tu rn
G e n E x h
G S p e c
E x h S
M in im u m N o is e L e v e l
N C
R o o m
A ir
B a la n ce
H V
A C
N o te s
D u p le x
R e ce p ta cl e s
Q u a d R e ce p ta cl e s
P o w e r
N o te s
F ix tu re
T y p e
C o n tr o ls
Li g h ti n g
S p e ci a l R e q u ir e m e n ts
Li g h ti n g
N o te s
SB101 CBOC Veteran Drop-off, Bldg Sprt 1 N/A N/A N/A N/A N/A N/A N/A N/A N/A N/A N/A N/A N/A N/A N/A N/A N/A N/A N/A N/A N/A N/A N/A N/A N/A N/A N/A N/A N/A N/A 1 weather proof cover Surface mount
Comply with
AHRAE/UFC 3-530-1
SB102 LOVP1
CBOC Valet Parking Station, Bldg
Sprt 1 N/A N/A N/A N/A N/A N/A N/A N/A N/A N/A N/A N/A N/A N/A N/A N/A N/A N/A N/A N/A N/A N/A N/A N/A N/A N/A N/A N/A N/A N/A 1 weather proof cover
Surface mount
Comply with
AHRAE/UFC 3-530-1
SB103 CBOC Bicycle Rack Area, Bldg Sprt 1 N/A N/A N/A N/A N/A N/A N/A N/A N/A N/A N/A N/A N/A N/A N/A N/A N/A N/A N/A N/A N/A N/A N/A N/A N/A N/A N/A N/A N/A N/A 1 weather proof cover Surface mount
Comply with
AHRAE/UFC 3-530-1
SB104
CBOC Service Dog Walk Area, Bldg
Sprt 1 N/A N/A N/A N/A N/A N/A N/A N/A N/A N/A N/A N/A N/A N/A N/A N/A N/A N/A N/A N/A N/A N/A N/A N/A N/A N/A N/A N/A N/A N/A 1 weather proof cover
Surface mount
Comply with
AHRAE/UFC 3-530-1
SB253
CBOC Gurney Corral / Parking, Clncl Sprt 1 N/A m:LVT m:RB h:4" m:GWB f:SC N/A N/A N/A N/A 9'-0" m: AT N/A N/A 7'-0" m: Open N/A N/A N/A 75 72 60 N/A N/A STD 62 STD 62 N/A N/A N/A N/A 4 2x4 D/I
Dimming-Comply with
AHRAE/UFC 3-530-1
SB262 SRLW1
CBOC Wheelchair Corral / Parking, Clncl Sprt 1 N/A m:LVT m:RB h:4" m:GWB f:SC N/A N/A N/A N/A 9'-0" m: AT N/A N/A 7'-0" m: Open N/A N/A N/A 75 72 60 N/A N/A STD 62 STD 62 N/A N/A N/A N/A 4 2x4 D/I
Dimming-Comply with
AHRAE/UFC 3-530-1
SC093 CSPL1
CBOC Mobile Lift Corral / Parking, Clncl Sprt 1 N/A m:LVT m:RB h:4" m:GWB f:SC N/A N/A N/A N/A 9'-0" m: AT N/A N/A 7'-0" m: Open N/A N/A N/A 75 72 60 N/A N/A STD 62 STD 62 N/A N/A N/A N/A 4 2x4 D/I
Dimming-Comply with
AHRAE/UFC 3-530-1
CWV02 LAC01 CBOC Lactation Room, Wm Vet Svc 1 N/A m:LVT m:RB h:4" m:GWB f:P N/A N/A N/A N/A 9'-0" m: AT 3'-0" 7'-0" 19 m: Wood N/A hw: 2G 75 72 60 N/A N/A STD 62 STD 62 N/A N/A N/A N/A 4 2x4 D/I
Dimming-Comply with
AHRAE/UFC 3-530-1
OCB16 SRS01 Travel /ROI Office 1 N/A m:LVT or m:CPT m:RB h:4" m:GWB f:P N/A N/A N/A 40 9'-0" m: AT 3'-0" 7'-0" 1 m: Wood T hw: 3E 75 72 60 N/A N/A STD 62 STD 62 N/A N/A N/A N/A 4 2x4 D/I
Dimming-Comply with
AHRAE/UFC 3-530-1
OCB18 SRS01
Veteran Information / Welcome
Area Storage Room, CBOC 1 N/A m:VT m: RB h:4" m:GWB f:SC N/A m:RWC h:4'-0" 35 9'-0" m: AT 3'-6" 7'-0" 11 m: Wood F hw: 5 75 72 60 N/A N/A STD 62 STD 62 N/A N/A N/A N/A 4 2x4 D/I
Dimming-Comply with
AHRAE/UFC 3-530-1
SB051 WTF01 Family Seating, Bldg Sprt 1 N/A m:CPT or m:LVT m:RB h:4" m:GWB f:P N/A m:RWC h:4'-0" 40 9'-0" m: AT N/A 7'-0" m: Open N/A N/A N/A 75 72 60 N/A N/A STD 62 STD 62 N/A N/A N/A N/A 4 2x4 D/I
Comply with
AHRAE/UFC 3-530-1
SB131 Information/Welcome Desk 1 N/A m:LVT m:RB h:4" m:GWB f:P N/A N/A N/A 40 9'-0" m: AT N/A 7'-0" m: Open N/A N/A N/A 75 72 60 N/A N/A STD 62 STD 62 N/A N/A N/A N/A 4 2x4 D/I
Dimming-Comply with
AHRAE/UFC 3-530-1
SB163 TPB01 Bariatric Patient Toilet, Bldg Sprt 1 N/A Aligns with FGI m:PT or m:RES m: PT or
RES H:4"
m:GWB f:SC N/A m:PT or
CT or S 4'-0" 45 9'-0" m: GWB f: SC 3'-6" 7'-0" 1 m: Wood N/A hw:2H 2 or 4U 75 72 60 N/A N/A STD 62 STD 62 N/A N/A N/A N/A 1 2x4 D/I
Dimming-Comply with
AHRAE/UFC 3-530-1
SC170 My HealtheVet Connect Station 2 N/A m:CPT or m:LVT m: RB h:
4" m:GWB f:P N/A N/A N/A 40 9'-0" m: AT 3'-0" 7'-0" 19 m: Wood S hw:2H 75 72 60 N/A N/A STD 62 STD 62 N/A N/A N/A N/A 4 2x4 D/I
Dimming-Comply with
AHRAE/UFC 3-530-1
CBOC Patient Advocate Office, Stff
Sprt 1 N/A m:LVT or m:CPT m:RB h:4" m:GWB f:P N/A N/A N/A 40 9'-0" m: AT 3'-0" 7'-0" 1 m: Wood T hw:2H 75 72 60 N/A N/A STD 62 STD 62 N/A N/A N/A N/A 5 1 2x4 D/I
Dimming-Comply with
AHRAE/UFC 3-530-1
CBOC Patient Enrollment Office, Stff Sprt 1 N/A m:CPT m:RB h:4" m:GWB f:P N/A N/A N/A 35 9'-0" m: AT 3'-0" 7'-0" 1 m: Wood T hw:2H 75 72 60 N/A N/A STD 62 STD 62 N/A N/A N/A N/A 5 1 2x4 D/I
Dimming-Comply with
AHRAE/UFC 3-530-1
SB207 CBOC Outdoor Seating, Bldg Sprt 1 N/A N/A N/A N/A N/A N/A N/A N/A N/A N/A N/A N/A N/A N/A N/A N/A N/A hw:2H N/A 75 72 60 N/A N/A STD 62 STD 62 N/A N/A N/A N/A 4 2x4 D/I Comply with
AHRAE/UFC 3-530-1
SV381 NCWD4
CBOC Refreshment Station, Bldg
Sprt 1 N/A m:LVT m:RB h:4" m:GWB f:P N/A N/A 40 9'-0" m: AT N/A 7'-0" m: Open N/A N/A N/A 75 72 60 N/A N/A STD 62 STD 62 N/A N/A N/A N/A 4 2x4 D/I
Comply with
AHRAE/UFC 3-530-1
SV626
CBOC Cafe / Bistro/Mini Mart, VC
Svc 1 N/A m:LVT m:RB h:4" m:GWB f:P N/A N/A 40 9'-0" m: AT N/A 7'-0" m: Open N/A N/A N/A 75 72 60 N/A N/A STD 62 STD 62 N/A N/A N/A N/A 4 2x4 D/I
Comply with
AHRAE/UFC 3-530-1
SV627 SRS01
CBOC Cafe / Bistro Storage Room, VC Svc 1 N/A m:VT m:RB h:4" m:GWB f:P m:RWC h:4'-0" 40 9'-0" m: AT 3'-8" 7'-0" 11 m: Wood F hw: 5 75 72 60 N/A N/A STD 62 STD 62 N/A N/A N/A N/A 4 2x4 D/I
Comply with
AHRAE/UFC 3-530-1
CBOC Cafe / Bistro Seating, VC Svc 1 N/A m:LVT m:RB h:4" m:GWB f:P N/A N/A 40 9'-0" m: AT N/A 7'-0" m: Open N/A N/A N/A 75 72 60 N/A N/A STD 62 STD 62 N/A N/A N/A N/A 4 2x4 D/I
Comply with
AHRAE/UFC 3-530-1
CBOC Refreshment Seating, VC Svc 1 N/A m:LVT m:RB h:4" m:GWB f:P N/A N/A 40 9'-0" m: AT N/A 7'-0" m: Open N/A N/A N/A 75 72 60 N/A N/A STD 62 STD 62 N/A N/A N/A N/A 4 2x4 D/I
Comply with
AHRAE/UFC 3-530-1
SV692 BX002
CBOC Vending Area, Blind Veteran
Vender/VCS 1 N/A m:LVT m:RB h:4" m:GWB f:P N/A N/A 40 9'-0" m: AT N/A 7'-0" m: Open N/A N/A N/A 75 72 60 N/A N/A STD 62 STD 62 N/A N/A N/A N/A 4 2x4 D/I
Comply with
AHRAE/UFC 3-530-1
OCB21 CFR02
Shared Group / Multifunction
Room, CBOC 1 N/A m:CPT or m:LVT m:RB h:4" m:GWB f:P N/A N/A 40 9'-0" m: GWB f: P or m: AT
3'-6" 7'-0" 19 m: Wood N/A hw: 4N 75 72 60 N/A N/A STD 62 STD 62 N/A N/A N/A N/A 4 2x4 D/I
Comply with
AHRAE/UFC 3-530-1
OCB24 SRS01
Shared Group / Multifunction
Storage Room, CBOC 1 N/A m:VT m:RB h:4" m:GWB f:P m:RWC h:4'-0" 40 9'-0" m: AT 3'-8" 7'-0" 11 m: Wood F hw: 5 75 72 60 N/A N/A STD 62 STD 62 N/A N/A N/A N/A 4 2x4 D/I
Comply with
AHRAE/UFC 3-530-1
SC276
CBOC Demonstration Kitchen, Clncl
Sprt 1 N/A m:PT or m:RES m: PT or
RES H:4"
m:GWB f:SC m:PT or
CT or S 4'-0" 40 9'-0" m: GWB f: SC 3'-6" 7'-0" 1 m: Wood N/A hw:2H 2 or 4U 75 72 60 N/A N/A STD 62 STD 62 G N/A N/A N/A 4 2x4 D/I
Comply with
AHRAE/UFC 3-530-1
CEY62 OPIM2
CBOC Tele Retinal Imaging Patient
Care Room 1 N/A Aligns with FGI m:WSF or m:LVT m:RB or m:WSF h:4" m:GWB f:P N/A N/A 55 9'-0" m: AT or GWB f: P
N/A 7'-0" m: Open N/A N/A N/A 75 72 60 N/A N/A STD 62 STD 62 N/A N/A N/A N/A 4 2x4 D/I
Dimming-Comply with
AHRAE/UFC 3-530-1
CT024 Multipurpose Group Room 1 N/A m:CPT or m:LVT m:RB h:4" m:GWB f:P N/A N/A 40 9'-0" m: GWB f: P or m: AT
3'-6" 7'-0" 19 m: Wood N/A hw: 4N 75 72 60 N/A N/A STD 62 STD 62 N/A N/A N/A N/A 4 2x4 D/I
Dimming-Comply with
AHRAE/UFC 3-530-1
CT025 Group Room Storage Room 1 N/A m:VT m:RB h:4" m:GWB f:P m:RWC h:4'-0" 40 9'-0" m: AT 3'-8" 7'-0" 11 m: Wood F hw: 5 75 72 60 N/A N/A STD 62 STD 62 N/A N/A N/A N/A 4 2x4 D/I
Comply with
AHRAE/UFC 3-530-1
CWV16 EXW01
Women Veteran Patient Care
Room 1 N/A m:LVT m: RB h:4" m:GWB f:P m:RWC h:4'-0" 35 9'-0" m: AT 3'-6" 7'-0" 19 m: Wood N/A hw: 1Q 75 72 60 N/A N/A STD 62 STD 62 N/A N/A N/A N/A 4 2x4 D/I
Dimming-Comply with
AHRAE/UFC 3-530-1
OCB31 EXRG3
General Patient Care
Room/Exam/Consult 19 N/A Aligns with FGI m:LVT m:RB h:4" m:GWB f:P m:RWC h:4'-0" 50 9'-0" m: AT 3'-6" 7'-0" 19 m: Wood N/A hw: 1L 75 72 60 N/A N/A STD 62 STD 62 N/A N/A N/A N/A 4 2x4 D/I
Dimming-Comply with
AHRAE/UFC 3-530-1
OCB37 EXEB1
Multi-Use / Bariatric Patient Care
Room/Procedure/Treatment/Fami ly Consult, CBOC
1 N/A Aligns with FGI m:WSF or m:RESIN m:WSF or m:RESIN h:4" m:GWB f:SC m:RWC h:4'-0" 50 9'-0" m: AT 4'-0" 7'-0" 19 m: Wood T hw: 13 75 72 60 N/A N/A STD 62 STD 62 N/A N/A N/A N/A 4 2x4 D/I
Dimming-Comply with
AHRAE/UFC 3-530-1
SB003 WRC01 General Waiting 1 N/A m:CPT or m:LVT m:RB h:4" m:GWB f:P m:RWC h:4'-0" 40 9'-0" m: AT N/A 7'-0" m: Open N/A N/A N/A 75 72 60 N/A N/A STD 62 STD 62 N/A N/A N/A N/A 4 2x4 D/I
Comply with
AHRAE/UFC 3-530-1
SB159 TLTF2
CBOC Women Veteran Patient
Toilet 1 N/A Aligns with FGI m:PT or m:RES m: PT or
RES H:4"
m:GWB f:SC m:PT or
CT or S 4'-0" 45 9'-0" m: GWB f: SC 3'-6" 7'-0" 1 m: Wood N/A hw:2H 2 or 4U 75 72 60 N/A N/A STD 62 STD 62 G N/A (-) N/A 0
DL/VANI
TY
Comply with
AHRAE/UFC 3-530-1
SB191 TNPG1 Universal Non-Patient/Staff Toilet 2 N/A Aligns with FGI m:PT or m:RES m: PT or
RES H:4"
m:GWB f:SC m:PT or
CT or S 4'-0" 45 9'-0" m: GWB f: SC 3'-6" 7'-0" 1 m: Wood N/A hw:2H 2 or 4U 75 72 60 N/A N/A STD 62 STD 62 G N/A (-) N/A 1
DL/VANI
TY
Comply with
AHRAE/UFC 3-530-1
SB201 TPG01 CBOC Patient Toilet 3 N/A Aligns with FGI m:PT or m:RES m: PT or
RES H:4"
m:GWB f:SC m:PT or
CT or S 4'-0" 45 9'-0" m: GWB f: SC 3'-6" 7'-0" 1 m: Wood N/A hw:2H 2 or 4U 75 72 60 N/A N/A STD 62 STD 62 G N/A (-) N/A 0
DL/VANI
TY
Comply with
AHRAE/UFC 3-530-1
SB721 STEQ1 Medical Equipment Storage Room 1 N/A m:VT m:RB h:4" m:GWB f:P m:RWC h:4'-0" 35 9'-0" m: AT 3'-8" 7'-0" 11 m: Wood F hw: 5 75 72 60 N/A N/A STD 62 STD 62 N/A N/A N/A N/A 4 2x4 D/I
Comply with
AHRAE/UFC 3-530-1
SB737 UCCL1 Clean Utility Room 1 N/A m:WSF m:WSF h:4" m:GWB f:SC m:RWC h:4'-0" 35 9'-0" m: AT f:SP 3'-8" 7'-0" 11 m: Wood F SH-3C ds:YES 75 72 60 N/A N/A STD 62 STD 62 N/A N/A (+) N/A 4 2x4 D/I
Comply with
AHRAE/UFC 3-530-1
SB743 USCL1 Soiled Holding Room 1 N/A m:WSF m:WSF h:4" m:GWB f:SC m:RWC h:4'-0" 35 9'-0" m: AT f:SP 3'-8" 7'-0" 11 m: Wood F SH-3C ds:YES 75 72 60 N/A N/A STD 62 STD 62 G N/A (-) N/A 4 2x4 D/I
Comply with
AHRAE/UFC 3-530-1
SC066 PEHW2
CBOC Accessible Patient Height &
Weight Station 2 N/A m:LVT m:RB h:4" m:GWB f:P N/A N/A 40 9'-0" m: AT N/A 7'-0" m: Open N/A N/A N/A 75 72 60 N/A N/A STD 62 STD 62 N/A N/A N/A N/A 1 DL
Comply with
AHRAE/UFC 3-530-1
SC083 CSMP1
Medication Alcove, Automated
Dispensing Unit 1 N/A m:VT m:RB h:4" m:GWB f:P m:RWC h:4'-0" 40 9'-0" m: AT 3'-8" 7'-0" 11 m: Wood F hw: 5 75 72 60 N/A N/A STD 62 STD 62 N/A N/A N/A N/A 1 Provide dedicated circuit for med dispenser machine DL
Comply with
AHRAE/UFC 3-530-1
SC183 RCP01 Reception 1 N/A m:LVT or m:CPT m: RB h:4" m:GWB f:P N/A N/A 40 9'-0" m: AT
3'-0" or
OPEN
7'-0" or
OPEN
1 OR
OPEN
m: Wood
3E or
OPEN
hw: 3E or N/A 75 72 60 N/A N/A STD 62 STD 62 N/A N/A N/A N/A 4 1 2x4 D/I
Comply with
AHRAE/UFC 3-530-1
SC243 PACT Team Room (2 workstations) 12 N/A m:CPT or m:LVT m:RB h:
4" m:GWB f:P N/A N/A 40 9'-0" m: AT N/A 7'-0" m: Open N/A N/A N/A 75 72 60 N/A N/A STD 62 STD 62 N/A N/A N/A N/A 4 2 2x4 D/I
Dimming-Comply with
AHRAE/UFC 3-530-1
SC281 CBOC Point of Use Supply Alcove 1 N/A m:CPT or m:LVT m:RB h:4" m:GWB f:P N/A N/A 35 9'-0" m: AT or GWB f: P
N/A 7'-0" m: Open N/A N/A N/A 75 72 60 N/A N/A STD 62 STD 62 N/A N/A N/A N/A 0 DL
Comply with
AHRAE/UFC 3-530-1
Office, HAS Supervisor Office 1 N/A m:LVT or m:CPT m:RB h:4" m:GWB f:P N/A N/A 40 9'-0" m: AT 3'-0" 7'-0" 1 m: Wood T hw: 3E 75 72 60 N/A N/A STD 62 STD 62 N/A N/A N/A N/A 5 1 2x4 D/I
Dimming-Comply with
AHRAE/UFC 3-530-1
Office, Nurse Manager, Primary
Care 1 N/A m:LVT or m:CPT m:RB h:4" m:GWB f:P N/A N/A 40 9'-0" m: AT 3'-0" 7'-0" 1 m: Wood T hw: 3E 75 72 60 N/A N/A STD 62 STD 62 N/A N/A N/A N/A 5 1 2x4 D/I
Dimming-Comply with
AHRAE/UFC 3-530-1
SS205 OFA09
01 - COMMUNITY BASED
OUTPATIENT CLINIC
(CBOC) (265)
05 - VETERAN
EDUCATION / GROUP
CARE AREA
01 - COMMUNITY BASED
OUTPATIENT CLINIC
(CBOC) (265)
06 - PATIENT CARE AREA:
PRIMARY CARE-PACT -
MODULE 1
01 - COMMUNITY BASED
OUTPATIENT CLINIC
(CBOC) (265)
01 - COMMUNITY BASED
OUTPATIENT CLINIC
(CBOC) (265)
01 - OUTDOOR PUBLIC
AREA
02 - INDOOR PUBLIC
AREA
01 - COMMUNITY BASED
OUTPATIENT CLINIC
(CBOC) (265)
03 - VETERAN WELCOME
AREA / MAIN STREET
01 - COMMUNITY BASED
OUTPATIENT CLINIC
(CBOC) (265)
SS203 OFA04
SV628 FSCD1
04 - CAFE /
REFRESHMENT AREA
ROOM DATA MATRIX INTERIOR CONSTRUCTION DOORS AND HARDWARE MECHANICAL ELECTRICAL
Note: Use parameters within FGI Guidelines for the noted FGI Equivalent category unless otherwise noted. FGI is required for
Ambulatory Surgical Center ASHRAE Standard 170 and the balance of other spaces outdoor ventilation and exhaust would fall under the requirments of ASHRAE Standard 62.
Minimum receptacle quantities provided in this matrix. Equipment layouts must be assessed for each room to provide the correct receptacle and hardwire connection quantity. Where required by ASHRAE 90.1 and UFC 3-520-01, all workstations and work areas must have controlled and non-controlled outlets. All office, staff-support spaces, and other workstation locations require a minimum of two duplex receptacles, one double duplex, or one quadraplex receptacle for each workstation. Provide GFCI receptacles as required by NFPA 70. Receptacle layout and quantities must meet UFC 3-520-01 requirements.
POWER
Lighting fixture quantity and type provided are an estimate to meet minimum requirements.
Ceiling material selection will affect fixture type and size. Provide computer-generated photometric plans for each space to verify proposed lighting design meets the required performance criteria using the applicable light loss factor (LLF). All interior and exterior lighting design shall meet all UFC 3-530-1 and ASHRAE requirements. Egress lighting and controls shall comply with NFPA 101 and UFC 3-530-1. LIGHTING
ROOM IDENTIFICATION FACILITY GUIDELINES INSTITUTE FLOOR WALLS CEILING
Lessor: ________ VA:________
Name
Functional Area Number
& Name
Room
Code
Known
Legacy
Room
Code
Project Room Name
Quantity of This
Room
FGI Equivalent for ASHRAE 170
FGI Equivalent for Table 1-2-5
Minimum
Sound Isolation
F lo o r
F in is h
B a se
W a ll F in is h
W a ll F in is h A lt e rn a te
W a in sc o t
M a te ri a l
W a in sc o t
H e ig h t
S T
C
C e il in g H e ig h t
C e il in g F in is h
N o te s
S iz e
W id th
H e ig h t
T y p e
M a te ri a l
G la zi n g
R a ti n g
H a rd w a re
G ro u p
H a rd w a re
N o te s
In d o o r T e m p e ra tu re C o o li n g
F
In d o o r T e m p e ra tu re H e a ti n g
F
In d o o r R e la ti v e H u m id it y x
In d o o r R e la ti v e H u m id it y
M in im u m T o ta l A
C H
M in im u m O u ts id e
A ir
C h a n te
M in im u m O
A A
C H
R o o m
A ir
R e tu rn
G e n E x h
G S p e c
E x h S
M in im u m N o is e L e v e l
N C
R o o m
A ir
B a la n ce
H V
A C
N o te s
D u p le x
R e ce p ta cl e s
Q u a d R e ce p ta cl e s
P o w e r
N o te s
F ix tu re
T y p e
C o n tr o ls
Li g h ti n g
S p e ci a l R e q u ir e m e n ts
Li g h ti n g
N o te s
ROOM DATA MATRIX INTERIOR CONSTRUCTION DOORS AND HARDWARE MECHANICAL ELECTRICAL
Note: Use parameters within FGI Guidelines for the noted FGI Equivalent category unless otherwise noted. FGI is required for
Ambulatory Surgical Center ASHRAE Standard 170 and the balance of other spaces outdoor ventilation and exhaust would fall under the requirments of ASHRAE Standard 62.
Minimum receptacle quantities provided in this matrix. Equipment layouts must be assessed for each room to provide the correct receptacle and hardwire connection quantity. Where required by ASHRAE 90.1 and UFC 3-520-01, all workstations and work areas must have controlled and non-controlled outlets. All office, staff-support spaces, and other workstation locations require a minimum of two duplex receptacles, one double duplex, or one quadraplex receptacle for each workstation. Provide GFCI receptacles as required by NFPA 70. Receptacle layout and quantities must meet UFC 3-520-01 requirements.
POWER
Lighting fixture quantity and type provided are an estimate to meet minimum requirements.
Ceiling material selection will affect fixture type and size. Provide computer-generated photometric plans for each space to verify proposed lighting design meets the required performance criteria using the applicable light loss factor (LLF). All interior and exterior lighting design shall meet all UFC 3-530-1 and ASHRAE requirements. Egress lighting and controls shall comply with NFPA 101 and UFC 3-530-1. LIGHTING
ROOM IDENTIFICATION FACILITY GUIDELINES INSTITUTE FLOOR WALLS CEILING
SS217 OFA07 CBOC Hoteling Workstation 2 N/A m:CPT or m:LVT m:RB h:
4" m:GWB f:P N/A N/A 40 9'-0" m: AT N/A 7'-0" m: Open N/A N/A N/A 75 72 60 N/A N/A STD 62 STD 62 N/A N/A N/A N/A 4 1 2x4 D/I
Dimming-Comply with
AHRAE/UFC 3-530-1
SS268 RPR03 CBOC Team Copy / Supply Alcove 1 N/A m:CPT or m:LVT m:RB h:4" m:GWB f:P N/A N/A 40 9'-0" m: AT or GWB f: P
N/A 7'-0" m: Open N/A N/A N/A 75 72 60 N/A N/A STD 62 STD 62 N/A N/A N/A N/A 0 1 provide dedicated circuit for copy machine DL
Comply with
AHRAE/UFC 3-530-1
SS282 LR001 Universal Locker Room 1 N/A m:PT or m:RES m:PT or m:RES h:4" m:GWB f:SC m:PT or m:CT h:4'-0" 40 9'-0" m: AT 3'-0" 7'-0" 19 m: Wood N/A hw: 4U 75 72 60 N/A N/A STD 62 STD 62 N/A N/A N/A N/A 1 2x4 D/I
Comply with
AHRAE/UFC 3-530-1
SS291 CFR01 CBOC Huddle Space 1 N/A m:CPT m:RB h:4" m:GWB f:P N/A N/A 36 9'-0" m: AT 3'-8" 7'-0" 19 m: Wood T hw: 3G 75 72 60 N/A N/A STD 62 STD 62 N/A N/A N/A N/A 4 2x4 D/I
Comply with
AHRAE/UFC 3-530-1
CT024 Multipurpose Group Room 1 N/A m:CPT or m:LVT m:RB h:4" m:GWB f:P N/A N/A 40 9'-0" m: GWB f: P or m: AT
3'-6" 7'-0" 19 m: Wood N/A hw: 4N 75 72 60 N/A N/A STD 62 STD 62 N/A N/A N/A N/A 4 2x4 D/I
Comply with
AHRAE/UFC 3-530-1
CT025 Group Room Storage Room 1 N/A m:VT m:RB h:4" m:GWB f:P m:RWC h:4'-0" 40 9'-0" m: AT 3'-8" 7'-0" 11 m: Wood F hw: 5 75 72 60 N/A N/A STD 62 STD 62 N/A N/A N/A N/A 4 2x4 D/I
Comply with
AHRAE/UFC 3-530-1
CWV16 EXW01
Women Veteran Patient Care
Room 1 N/A m:LVT m: RB h:4" m:GWB f:P m:RWC h:4'-0" 35 9'-0" m: AT 3'-6" 7'-0" 19 m: Wood N/A hw: 1Q 75 72 60 N/A N/A STD 62 STD 62 N/A N/A N/A N/A 4 2x4 D/I
Dimming-Comply with
AHRAE/UFC 3-530-1
OCB31 EXRG3
General Patient Care
Room/Exam/Consult 19 N/A Aligns with FGI m: LVT m:RB h:4" m:GWB f:P N/A N/A 50 9'-0" m: GWB f: P or m: AT
4'-0" 7'-0" 19 m: Wood N/A hw: 1L 4N 75 72 60 N/A N/A STD 62 STD 62 N/A N/A N/A N/A 4 2x4 D/I
Dimming-Comply with
AHRAE/UFC 3-530-1
OCB37 EXEB1
Multi-Use / Bariatric Patient Care
Room/Procedure/Treatment/Fami ly Consult, CBOC
1 N/A Aligns with FGI m:WSF m:WSF h:4" m:GWB f:P N/A N/A 50 9'-0" m: GWB f: P or m: AT
3'-6" 7'-0" 19 m: Wood N/A hw: 4N 75 72 60 N/A N/A STD 62 STD 62 N/A N/A N/A N/A 4 2x4 D/I
Dimming-Comply with
AHRAE/UFC 3-530-1
SB003 WRC01 General Waiting 1 N/A m:CPT or m:LVT m:RB h:4" m:GWB f:P m:RWC h:4'-0" 40 9'-0" m: AT N/A 7'-0" m: Open N/A N/A N/A 75 72 60 N/A N/A STD 62 STD 62 N/A N/A N/A N/A 4 2x4 D/I
Comply with
AHRAE/UFC 3-530-1
SB159 TLTF2
CBOC Women Veteran Patient
Toilet 1 N/A Aligns with FGI m:PT or m:RES m: PT or
RES H:4"
m:GWB f:SC m:PT or m:CT 4'-0" 45 9'-0" 3'-0" 7'-0" 19 m: Wood N/A hw: 2G or 4B
75 72 60 N/A N/A STD 62 STD 62 G N/A (-) N/A 0
DL/VANI
TY
Comply with
AHRAE/UFC 3-530-1
SB191 TNPG1 Universal Non-Patient/Staff Toilet 2 N/A Aligns with FGI m:PT or m:RES m: PT or
RES H:4"
m:GWB f:SC m:PT or m:CT 4'-0" 45 9'-0" 3'-0" 7'-0" 19 m: Wood N/A hw: 2G or 4B
75 72 60 N/A N/A STD 62 STD 62 G N/A (-) N/A 1
DL/VANI
TY
Comply with
AHRAE/UFC 3-530-1
SB201 TPG01 CBOC Patient Toilet 2 N/A Aligns with FGI m:PT or m:RES m: PT or
RES H:4"
m:GWB f:SC m:PT or m:CT 4'-0" 45 9'-0" 3'-0" 7'-0" 19 m: Wood N/A hw: 2G or 4B
75 72 60 N/A N/A STD 62 STD 62 G N/A (-) N/A 0
DL/VANI
TY
Comply with
AHRAE/UFC 3-530-1
SB721 STEQ1 Medical Equipment Storage Room 1 N/A m:VT m:RB h:4" m:GWB f:P m:RWC h:4'-0" 40 9'-0" m: AT 3'-8" 7'-0" 11 m: Wood F hw: 5 75 72 60 N/A N/A STD 62 STD 62 G N/A (-) N/A 4 2x4 D/I
Comply with
AHRAE/UFC 3-530-1
SB737 UCCL1 Clean Utility Room 1 N/A m:WSF m:WSF h:4" m:GWB f:SC m:RWC h:4'-0" 35 9'-0" m: AT f:SP 3'-8" 7'-0" 11 m: Wood F SH-3C ds:YES 75 72 60 N/A N/A STD 62 STD 62 N/A N/A (+) N/A 4 2x4 D/I
Comply with
AHRAE/UFC 3-530-1
SB743 USCL1 Soiled Utility Room 1 N/A m:WSF m:WSF h:4" m:GWB f:SC m:RWC h:4'-0" 35 9'-0" m: AT f:SP 3'-8" 7'-0" 11 m: Wood F SH-3C ds:YES 75 72 60 N/A N/A STD 62 STD 62 G N/A (-) N/A 4 2x4 D/I
Comply with
AHRAE/UFC 3-530-1
SC066 PEHW2
CBOC Accessible Patient Height &
Weight Station 1 N/A m:WSF or m:LVT m:RB or m:WSF h:4" m:GWB f:P N/A N/A 40 9'-0" m: AT or GWB f: P
N/A 7'-0" m: Open N/A N/A N/A 75 72 60 N/A N/A STD 62 STD 62 N/A N/A N/A N/A 1 2x4 D/I
Comply with
AHRAE/UFC 3-530-1
SC079 CSME1
CBOC Point of Use Equipment
Alcove 1 N/A m:WSF or m:LVT m:RB or m:WSF h:4" m:GWB f:P N/A N/A 40 9'-0" m: AT or GWB f: P
N/A 7'-0" m: Open N/A N/A N/A 75 72 60 N/A N/A STD 62 STD 62 N/A N/A N/A N/A 0 DL
Comply with
AHRAE/UFC 3-530-1
SC083 CSMP1
Medication Alcove, Automated
Dispensing Unit 1 N/A m:WSF or m:LVT m:RB or m:WSF h:4" m:GWB f:P N/A N/A 40 9'-0" m: AT or GWB f: P
N/A 7'-0" m: Open N/A N/A N/A 75 72 60 N/A N/A STD 62 STD 62 N/A N/A N/A N/A 1 Provide dedicated circuit for med dispenser machine DL
Comply with
AHRAE/UFC 3-530-1
SC183 RCP01 Reception 1 N/A m:LVT or m:CPT m: RB h:4" m:GWB f:P N/A N/A 40 9'-0" m: AT
3'-0" or
OPEN
7'-0" or
OPEN
1 OR
OPEN
m: Wood
3E or
OPEN
hw: 3E or N/A 75 72 60 N/A N/A STD 62 STD 62 N/A N/A N/A N/A 4 1 2x4 D/I
Comply with
AHRAE/UFC 3-530-1
SC243 PACT Team Room (2 workstations) 12 N/A m:CPT or m:LVT m:RB h:
4" m:GWB f:P N/A N/A 40 9'-0" m: AT N/A 7'-0" m: Open N/A N/A N/A 75 72 60 N/A N/A STD 62 STD 62 N/A N/A N/A N/A 4 2 2x4 D/I
Dimming-Comply with
AHRAE/UFC 3-530-1
SC281 CBOC Point of Use Supply Alcove 1 N/A m:WSF or m:LVT m:RB or m:WSF h:4" m:GWB f:P N/A N/A 40 9'-0" m: AT or GWB f: P
N/A 7'-0" m: Open N/A N/A N/A 75 72 60 N/A N/A STD 62 STD 62 N/A N/A N/A N/A 0 DL
Comply with
AHRAE/UFC 3-530-1
SS217 OFA07 CBOC Hoteling Workstation 2 N/A m:CPT or m:LVT m:RB h:
4" m:GWB f:P N/A N/A 40 9'-0" m: AT N/A 7'-0" m: Open N/A N/A N/A 75 72 60 N/A N/A STD 62 STD 62 N/A N/A N/A N/A 4 1 2x4 D/I
Dimming-Comply with
AHRAE/UFC 3-530-1
SS268 RPR03 CBOC Team Copy / Supply Alcove 1 N/A m:CPT or m:LVT m:RB h:4" m:GWB f:P N/A 40 9'-0" m: AT or GWB f: P
N/A 7'-0" m: Open N/A N/A N/A 75 72 60 N/A N/A STD 62 STD 62 N/A N/A N/A N/A 0 1 provide dedicated circuit for copy machine DL
Comply with
AHRAE/UFC 3-530-1
SS282 LR001 Universal Locker Room 1 N/A m:PT or m:RES m:PT or m:RES h:4" m:GWB f:SC m:PT or m:CT h:4'-0" 40 9'-0" m: AT 3'-0" 7'-0" 19 m: Wood N/A hw: 4U 75 72 60 N/A N/A STD 62 STD 62 N/A N/A N/A N/A 1 2x4 D/I
Comply with
AHRAE/UFC 3-530-1
SS291 CFR01 CBOC Huddle Space 1 N/A m:CPT or m:LVT m:RB h:4" m:GWB f:P N/A N/A 40 9'-0" m: AT or GWB f: P
N/A 7'-0" m: Open N/A N/A N/A 75 72 60 N/A N/A STD 62 STD 62 N/A N/A N/A N/A 4 2x4 D/I
Comply with
AHRAE/UFC 3-530-1
CCD31 OPTM1 Stress Testing Treadmill Room 1 N/A m:LVT m:RB h:4" m:GWB f:P N/A N/A 40 9'-0" m: AT 4'-0" 7'-0" 19 m:Wood T hw: 4J 75 72 60 N/A N/A STD 62 STD 62 N/A N/A N/A N/A 4 provide dedicated circuit for treadmill 2x4 D/I
Comply with
AHRAE/UFC 3-530-1
CPL42 SRS01 Oxygen Cylinder Storage Room 1 N/A m:CPT or m:LVT m:RB h:4" m:GWB f:P N/A N/A 40 9'-0" m: AT or GWB w/ P
N/A 7'-0" m: Open N/A N/A N/A 75 72 60 N/A N/A STD 62 STD 62 N/A N/A N/A N/A 4 2x4 D/I
Comply with
AHRAE/UFC 3-530-1
CT024 Multipurpose Group Room 1 N/A m:CPT m:RB h:4" m:GWB f:P N/A N/A 40 9'-0" m: GWB 3'-6" 7'-0" 19 m: Wood N/A hw: 4N 75 72 60 N/A N/A STD 62 STD 62 N/A N/A N/A N/A 4 2x4 D/I
Comply with
AHRAE/UFC 3-530-1
CT025 Group Room Storage Room 1 N/A m:CPT or m:LVT m:RB h:4" m:GWB f:P N/A N/A 40 9'-0" m: AT or GWB w/ P
N/A 7'-0" m: Open N/A N/A N/A 75 72 60 N/A N/A STD 62 STD 62 N/A N/A N/A N/A 4 2x4 D/I
Comply with
AHRAE/UFC 3-530-1
CWV16 EXW01
Women Veteran Patient Care
Room 1 N/A m:LVT m: RB h:4" m:GWB f:P m:RWC h:4'-0" 35 9'-0" m: AT 3'-6" 7'-0" 19 m: Wood hw: 1Q 75 72 60 N/A N/A STD 62 STD 62 N/A N/A N/A N/A 4 2x4 D/I
Dimming-Comply with
AHRAE/UFC 3-530-1
OCB31 EXRG3
General Patient Care
Room/Exam/Consult - PACT &
Multi-specialty
18 N/A Aligns with FGI m: LVT m:RB h:4" m:GWB f:P N/A N/A 50 9'-0" m: GWB f: P or m: AT
3'-6" 7'-0" 19 m: Wood N/A hw: 4N 75 72 60 N/A N/A STD 62 STD 62 N/A N/A N/A N/A 4 2x4 D/I
Dimming-Comply with
AHRAE/UFC 3-530-1
OCB37 EXEB1
Multi-Use / Bariatric Patient Care
Room/Procedure/Treatment/Fami ly Consult, CBOC
2 N/A Aligns with FGI m:WSF m:WSF h:4" m:GWB f:P N/A N/A 50 9'-0" m: GWB f: P or m: AT
3'-6" 7'-0" 19 m: Wood N/A hw: 4N 75 72 60 N/A N/A STD 62 STD 62 N/A N/A N/A N/A 4 2x4 D/I
Dimming-Comply with
AHRAE/UFC 3-530-1
OCB37 EXEB1
Dermatology
Procedure/Treatment 1 N/A Aligns with FGI m:WSF m:WSF h:4" m:GWB f:P N/A N/A 50 9'-0" m: GWB f: P or m: AT
3'-6" 7'-0" 19 m: Wood N/A hw: 4N 75 72 60 N/A N/A STD 62 STD 62 N/A N/A N/A N/A 4 2x4 D/I
Dimming-Comply with
AHRAE/UFC 3-530-1
OCB41 EXP01 Podiatry Patient Care Room 3 N/A m:LVT m:RB h:4" m:GWB f:P N/A N/A 40 9'-0" m: GWB f: P or m: AT
3'-6" 7'-0" 19 m: Wood N/A hw: 4N 75 72 60 N/A N/A STD 62 STD 62 N/A N/A N/A N/A 4 2x4 D/I
Dimming-Comply with
AHRAE/UFC 3-530-1
SB003 WRC01 General Waiting 1 N/A m:CPT or m:LVT m:RB h:4" m:GWB f:P m:RWC h:4'-0" 40 9'-0" m: AT N/A 7'-0" m: Open N/A N/A N/A 75 72 60 N/A N/A STD 62 STD 62 N/A N/A N/A N/A 4 2x4 D/I
Comply with
AHRAE/UFC 3-530-1
SB159 TLTF2
CBOC Women Veteran Patient
Toilet 1 N/A Aligns with FGI m:PT or m:RES m: PT or
RES H:4"
m:GWB f:SC m:PT or m:CT 4'-0" 45 9'-0" 3'-0" 7'-0" 19 m: Wood N/A hw: 2G or 4B
75 72 60 N/A N/A STD 62 STD 62 N/A N/A N/A N/A 0
DL/VANI
TY
Comply with
AHRAE/UFC 3-530-1
SB191 TNPG1 Universal Non-Patient/Staff Toilet 2 N/A Aligns with FGI m:PT or m:RES m: PT or
RES H:4"
m:GWB f:SC m:PT or m:CT 4'-0" 45 9'-0" 3'-0" 7'-0" 19 m: Wood N/A hw: 2G or 4B
75 72 60 N/A N/A STD 62 STD 62 N/A N/A N/A N/A 1
DL/VANI
TY
Comply with
AHRAE/UFC 3-530-1
SB201 TPG01 CBOC Patient Toilet 3 N/A Aligns with FGI m:PT or m:RES m: PT or
RES H:4"
m:GWB f:SC m:PT or m:CT 4'-0" 45 9'-0" 3'-0" 7'-0" 19 m: Wood N/A hw: 2G or 4B
75 72 60 N/A N/A STD 62 STD 62 G N/A (-) N/A 0
DL/VANI
TY
Comply with
AHRAE/UFC 3-530-1
SB721 STEQ1 Medical Equipment Storage 2 N/A m:VT m:RB h:4" m:GWB f:P m:RWC h:4'-0" 40 9'-0" m: AT 3'-8" 7'-0" 11 m: Wood F hw: 5 75 72 60 N/A N/A STD 62 STD 62 N/A N/A N/A N/A 4 2x4 D/I
Comply with
AHRAE/UFC 3-530-1
SB737 UCCL1 Clean Utility Room 1 N/A m:WSF m:WSF h:4" m:GWB f:SC m:RWC h:4'-0" 35 9'-0" m: AT f:SP 3'-8" 7'-0" 11 m: Wood F SH-3C ds:YES 75 72 60 N/A N/A STD 62 STD 62 N/A N/A (+) N/A 4 2x4 D/I
Comply with
AHRAE/UFC 3-530-1
SB743 USCL1 Soiled Utility Room 1 N/A m:WSF m:WSF h:4" m:GWB f:SC m:RWC h:4'-0" 35 9'-0" m: AT f:SP 3'-8" 7'-0" 11 m: Wood F SH-3C ds:YES 75 72 60 N/A N/A STD 62 STD 62 G N/A (-) N/A 4 2x4 D/I
Comply with
AHRAE/UFC 3-530-1
SC066 PEHW2
CBOC Accessible Patient Height &
Weight Station 1 N/A m:LVT m:RB h:4" m:GWB f:P m:RWC h:4'-0" 40 9'-0" m: AT 3'-6" 7'-0" 19 m: Wood N/A hw: 3E 75 72 60 N/A N/A STD 62 STD 62 N/A N/A N/A N/A 1 2x4 D/I
Comply with
AHRAE/UFC 3-530-1
SC079 CSME1
CBOC Point of Use Equipment
Alcove 1 N/A m:CPT or m:LVT m:RB h:4" m:GWB f:P N/A N/A 40 9'-0" m: AT or GWB f: P
N/A 7'-0" m: Open N/A N/A N/A 75 72 60 N/A N/A STD 62 STD 62 N/A N/A N/A N/A 0 DL
Comply with
AHRAE/UFC 3-530-1
SC083 CSMP1 Medication Room 1 N/A m:VT m:RB h:4" m:GWB f:P N/A N/A 40 9'-0" m: AT 3'-0" 7'-0" 1 m: Wood T SH-3C ds:YES 75 72 60 N/A N/A STD 62 STD 62 N/A N/A N/A N/A 4 Provide dedicated circuit for med dispenser machine 2x4 D/I
Comply with
AHRAE/UFC 3-530-1
01 - COMMUNITY BASED
OUTPATIENT CLINIC
(CBOC) (265)
08 - PATIENT CARE AREA:
MULTI-SPECIALTY AND
ONE PACT TEAMLET
01 - COMMUNITY BASED
OUTPATIENT CLINIC
(CBOC) (265)
07 - PATIENT CARE AREA:
PRIMARY CARE-PACT -
MODULE 2
Name
Functional Area Number
& Name
Room
Code
Known
Legacy
Room
Code
Project Room Name
Quantity of This
Room
FGI Equivalent for ASHRAE 170
FGI Equivalent for Table 1-2-5
Minimum
Sound Isolation
F lo o r
F in is h
B a se
W a ll F in is h
W a ll F in is h A lt e rn a te
W a in sc o t
M a te ri a l
W a in sc o t
H e ig h t
S T
C
C e il in g H e ig h t
C e il in g F in is h
N o te s
S iz e
W id th
H e ig h t
T y p e
M a te ri a l
G la zi n g
R a ti n g
H a rd w a re
G ro u p
H a rd w a re
N o te s
In d o o r T e m p e ra tu re C o o li n g
F
In d o o r T e m p e ra tu re H e a ti n g
F
In d o o r R e la ti v e H u m id it y x
In d o o r R e la ti v e H u m id it y
M in im u m T o ta l A
C H
M in im u m O u ts id e
A ir
C h a n te
M in im u m O
A A
C H
R o o m
A ir
R e tu rn
G e n E x h
G S p e c
E x h S
M in im u m N o is e L e v e l
N C
R o o m
A ir
B a la n ce
H V
A C
N o te s
D u p le x
R e ce p ta cl e s
Q u a d R e ce p ta cl e s
P o w e r
N o te s
F ix tu re
T y p e
C o n tr o ls
Li g h ti n g
S p e ci a l R e q u ir e m e n ts
Li g h ti n g
N o te s
ROOM DATA MATRIX INTERIOR CONSTRUCTION DOORS AND HARDWARE MECHANICAL ELECTRICAL
Note: Use parameters within FGI Guidelines for the noted FGI Equivalent category unless otherwise noted. FGI is required for
Ambulatory Surgical Center ASHRAE Standard 170 and the balance of other spaces outdoor ventilation and exhaust would fall under the requirments of ASHRAE Standard 62.
Minimum receptacle quantities provided in this matrix. Equipment layouts must be assessed for each room to provide the correct receptacle and hardwire connection quantity. Where required by ASHRAE 90.1 and UFC 3-520-01, all workstations and work areas must have controlled and non-controlled outlets. All office, staff-support spaces, and other workstation locations require a minimum of two duplex receptacles, one double duplex, or one quadraplex receptacle for each workstation. Provide GFCI receptacles as required by NFPA 70. Receptacle layout and quantities must meet UFC 3-520-01 requirements.
POWER
Lighting fixture quantity and type provided are an estimate to meet minimum requirements.
Ceiling material selection will affect fixture type and size. Provide computer-generated photometric plans for each space to verify proposed lighting design meets the required performance criteria using the applicable light loss factor (LLF). All interior and exterior lighting design shall meet all UFC 3-530-1 and ASHRAE requirements. Egress lighting and controls shall comply with NFPA 101 and UFC 3-530-1. LIGHTING
ROOM IDENTIFICATION FACILITY GUIDELINES INSTITUTE FLOOR WALLS CEILING
SC183 RCP01 Reception 2 N/A m:LVT or m:CPT m: RB h:4" m:GWB f:P N/A N/A 40 9'-0" m: AT
3'-0" or
OPEN
7'-0" or
OPEN
1 OR
OPEN
m: Wood
3E or
OPEN
hw: 3E or N/A 75 72 60 N/A N/A STD 62 STD 62 N/A N/A N/A N/A 4 1 2x4 D/I
Comply with
AHRAE/UFC 3-530-1
SC243 PACT Team Room (2 workstations) 12 N/A m:CPT or m:LVT m:RB h:
4" m:GWB f:P N/A N/A 40 9'-0" m: AT N/A 7'-0" m: Open N/A N/A N/A 75 72 60 N/A N/A STD 62 STD 62 N/A N/A N/A N/A 4 2 2x4 D/I
Dimming-Comply with
AHRAE/UFC 3-530-1
SC281 CBOC Point of Use Supply Alcove 1 N/A m:CPT or m:LVT m:RB h:4" m:GWB f:P N/A N/A 40 9'-0" m: AT or GWB f: P
N/A 7'-0" m: Open N/A N/A N/A 75 72 60 N/A N/A STD 62 STD 62 N/A N/A N/A N/A 0 DL
Comply with
AHRAE/UFC 3-530-1
SS205 OFA09
Office, Nurse Manager, Specialty
Care 1 N/A m:LVT or m:CPT m:RB h:4" m:GWB f:P N/A N/A 40 9'-0" m: AT 3'-0" 7'-0" 1 m: Wood T hw: 3E 75 72 60 N/A N/A STD 62 STD 62 N/A N/A N/A N/A 5 1 2x4 D/I
Dimming-Comply with
AHRAE/UFC 3-530-1
SS217 OFA07 CBOC Hoteling Workstation 2 N/A m:CPT or m:LVT m:RB h:
4" m:GWB f:P N/A N/A 40 9'-0" m: AT N/A 7'-0" m: Open N/A N/A N/A 75 72 60 N/A N/A STD 62 STD 62 N/A N/A N/A N/A 4 1 2x4 D/I
Dimming-Comply with
AHRAE/UFC 3-530-1
SS268 RPR03 CBOC Team Copy / Supply Alcove 1 N/A m:CPT or m:LVT m:RB h:4" m:GWB f:P N/A N/A 40 9'-0" m: AT or GWB f: P
N/A 7'-0" m: Open N/A N/A N/A 75 72 60 N/A N/A STD 62 STD 62 N/A N/A N/A N/A 0 1 provide dedicated circuit for copy machine DL
Comply with
AHRAE/UFC 3-530-1
SS282 LR001 Universal Locker Room 1 N/A m:PT or m:RES m:PT or m:RES h:4" m:GWB f:SC m:PT or m:CT h:4'-0" 40 9'-0" m: AT 3'-0" 7'-0" 19 m: Wood N/A hw: 4U 75 72 60 N/A N/A STD 62 STD 62 N/A N/A N/A N/A 1 2x4 D/I
Comply with
AHRAE/UFC 3-530-1
SS291 CFR01 CBOC Huddle Space 1 N/A m:CPT or m:LVT m:RB h:
4" m:GWB f:P N/A N/A 40 9'-0" m: AT N/A 7'-0" m: Open N/A N/A N/A 75 72 60 N/A N/A STD 62 STD 62 N/A N/A N/A N/A 4 2x4 D/I
Comply with
AHRAE/UFC 3-530-1
CED66 Patient Storage Room 1 N/A m:VT m:RB h:4" m:GWB f:P m:RWC h:4'-0" 40 9'-0" m: AT 3'-8" 7'-0" 11 m: Wood F hw: 5 75 72 60 N/A N/A STD 62 STD 62 N/A N/A N/A N/A 4 2x4 D/I
Comply with
AHRAE/UFC 3-530-1
CT024
Multipurpose Group Room, MHC
Svc 3 N/A m:CPT or m:LVT m:RB h:4" m:GWB f:P N/A N/A 40 9'-0" m: GWB f: P or m: AT
3'-6" 7'-0" 19 m: Wood N/A hw: 4N 75 72 60 N/A N/A STD 62 STD 62 N/A N/A N/A N/A 4 2x4 D/I
Comply with
AHRAE/UFC 3-530-1
IMH17 Exam Room, MHC 3 N/A Aligns with FGI m:WSF m:WSF h:4" m:GWB f:P N/A N/A 40 9'-0" m: GWB f: P or m: AT
3'-6" 7'-0" 19 m: Wood N/A hw: 4N 75 72 60 N/A N/A STD 62 STD 62 N/A N/A N/A N/A 4 2x4 D/I
Dimming-Comply with
AHRAE/UFC 3-530-1
IMH17
Transcutaneous Magnetic
Stimulation (TMS) Room 1 N/A m:WSF m:WSF h:4" m:GWB f:P N/A N/A 40 9'-0" m: GWB f: P or m: AT
3'-6" 7'-0" 19 m: Wood N/A hw: 4N 75 72 60 N/A N/A STD 62 STD 62 N/A N/A N/A N/A 4 2x4 D/I
Dimming-Comply with
AHRAE/UFC 3-530-1
OCM05 OPMH3
CBOC Counseling Patient Care
Room 26 N/A m:LVT or m:CPT m:RB h:4" m:GWB f:P N/A N/A 40 9'-0" m: AT or GWB 3'-8" 7'-0" 19 m: Wood N/A hw: 4N 75 72 60 N/A N/A STD 62 STD 62 N/A N/A N/A N/A 4 2x4 D/I
Dimming-Comply with
AHRAE/UFC 3-530-1
SB003 WRC01 MHC Waiting, Bldg Sprt 1 N/A m:CPT or m:LVT m:RB h:4" m:GWB f:P m:RWC h:4'-0" 40 9'-0" m: AT N/A 7'-0" m: Open N/A N/A N/A 75 72 60 N/A N/A STD 62 STD 62 N/A N/A N/A N/A 4 2x4 D/I
Comply with
AHRAE/UFC 3-530-1
SB199 TSPG1
Universal Patient Toilet / Shower, Bldg Sprt 1 N/A Aligns with FGI m:PT or m:RES m: PT or
RES H:4"
m:GWB f:SC m:PT or
CT or S h:
4'-0"
4'-0" 45 9'-0" m: GWB f:SC 3'-6" m: Wood N/A hw:2H 75 72 60 N/A N/A STD 62 STD 62 N/A N/A N/A N/A 1
DL/VANI
TY
Comply with
AHRAE/UFC 3-530-1
SB201 TPG01 MHC Patient Toilet, Bldg Sprt 3 N/A Aligns with FGI m:PT or m:RES m: PT or
RES H:4"
m:GWB f:SC m:PT or m:CT 4'-0" 45 9'-0" 3'-0" 7'-0" 19 m: Wood N/A hw: 2G or 4B
75 72 60 N/A N/A STD 62 STD 62 G N/A (-) N/A 0
DL/VANI
TY
Comply with
AHRAE/UFC 3-530-1
SC183 RCP01 MHC Reception, Clncl Sprt 1 N/A m:LVT or m:CPT m: RB h:4" m:GWB f:P N/A N/A 40 9'-0" m: AT
3'-0" or
OPEN
7'-0" or
OPEN
1 OR
OPEN
m: Wood
3E or
OPEN
hw: 3E or N/A 75 72 60 N/A N/A STD 62 STD 62 N/A N/A N/A N/A 4 1 2x4 D/I
Comply with
AHRAE/UFC 3-530-1
E-Range Team Room (2 workstations) 2 N/A m:CPT or m:LVT m:RB h:
4" m:GWB f:P N/A N/A 40 9'-0" m: AT N/A 7'-0" m: Open N/A N/A N/A 75 72 60 N/A N/A STD 62 STD 62 N/A N/A N/A N/A 4 2 2x4 D/I
Dimming-Comply with
AHRAE/UFC 3-530-1
Social Worker Team Room (2 workstations) 2 N/A m:CPT or m:LVT m:RB h:
4" m:GWB f:P N/A N/A 40 9'-0" m: AT N/A 7'-0" m: Open N/A N/A N/A 75 72 60 N/A N/A STD 62 STD 62 N/A N/A N/A N/A 4 2 2x4 D/I
Dimming-Comply with
AHRAE/UFC 3-530-1
SC249 WRTM3
CBOC Telehealth Patient Care
Room, Clncl Sprt 2 N/A Aligns with FGI m:CPT or m:LVT m: RB h:
4" m:GWB f:P N/A N/A 55 9'-0" m: AT 3'-0" 7'-0" 19 m: Wood S hw: 3E 75 72 60 N/A N/A STD 62 STD 62 N/A N/A N/A N/A 4 2x4 D/I
Dimming-Comply with
AHRAE/UFC 3-530-1
SS258 Printer Station, Stff Sprt 1 N/A m:CPT or m:LVT m:RB h:
4" m:GWB f:P N/A N/A 40 9'-0" m: AT N/A 7'-0" m: Open N/A N/A N/A 75 72 60 N/A N/A STD 62 STD 62 N/A N/A N/A N/A 2 1 2x4 D/I
Comply with
AHRAE/UFC 3-530-1
SV007 OFDC2 Family Consult Room 1 N/A Aligns with FGI m:CPT m:RB h:4" m:GWB f:P N/A N/A 50 9'-0" m: AT 3'-8" 7'-0" 19 m: Wood T hw: 3G 75 72 60 N/A N/A STD 62 STD 62 N/A N/A N/A N/A 4 Provide dedicated circuit for med dispenser machine 2x4 D/I
Comply with
AHRAE/UFC 3-530-1
CAS01 AURH2
Audiology Counseling Room, ASLP
Svc 5 N/A m:CPT m:RB h:4" m:GWB f:P N/A N/A 40 9'-0" m: AT 3'-8" 7'-0" 19 m: Wood N/A hw: 3F 75 72 60 N/A N/A STD 62 STD 62 N/A N/A N/A N/A 4 2x4 D/I
Dimming-Comply with
AHRAE/UFC 3-530-1
CAS11 AUDE2
Audiometric Booth Patient Care
Room, ASLP Svc 3 N/A PREFAB PREFAB PREFAB PREFAB PREFAB PREFAB PREFAB PREFAB PREFAB PREFAB PREFAB PREFAB PREFAB PREFAB PREFAB PREFAB PREFAB PREFAB 75 72 60 N/A N/A STD 62 STD 62 N/A N/A N/A N/A 4 provide dedicated circuit for audio booth 2x4 D/I
Dimming-Comply with
AHRAE/UFC 3-530-1
CAS31 AUD04
Audiology Treatment Room, ASLP
Svc 1 N/A Aligns with FGI m:LVT m: RB h:
4" m:GWB f:P N/A N/A 50 9'-0" m: AT 3'-6" 7'-0" 19 m: Wood N/A hw: 4N 75 72 60 N/A N/A STD 62 STD 62 N/A N/A N/A N/A 6 2x4 D/I
Comply with
AHRAE/UFC 3-530-1
CAS51
Speech-Language Pathology
Exam/consult, ASLP Svc 1 N/A Aligns with FGI m:LVT m:RB h:4" m:GWB f:P N/A N/A 50 9'-0" m: AT 3'-0" 7'-0" 19 m: Wood N/A hw:1Q 4N 75 72 60 N/A N/A STD 62 STD 62 N/A N/A N/A N/A 4 2x4 D/I
Dimming-Comply with
AHRAE/UFC 3-530-1
CAS67 AUDS1
Audiology Hearing Aid Lab, ASLP
Svc 1 N/A m:WSF m:WSF h:4" m:GWB f:P N/A N/A 40 9'-0" m: AT 3'-6" 7'-0" 19 m: Wood N/A hw: 4N 75 72 60 N/A N/A STD 62 STD 62 N/A N/A N/A N/A 4 2x4 D/I
Dimming-Comply with
AHRAE/UFC 3-530-1
CAS76 SRSP1
Audiology Supply Storage Room, ASLP Svc 1 N/A m:VT m:RB h:4" m:GWB f:P m:RWC h:4'-0" 40 9'-0" m: AT 3'-8" 7'-0" 11 m: Wood F hw: 5 75 72 60 N/A N/A STD 62 STD 62 N/A N/A N/A N/A 4 2x4 D/I
Comply with
AHRAE/UFC 3-530-1
CAS94 HAFR1
Hearing Aid Fitting Patient Care
Room, ASLP Svc 2 N/A m:CPT m:RB h:4" m:GWB f:P N/A N/A 40 9'-0" m: AT 3'-8" 7'-0" 19 m: Wood N/A hw: 3F 75 72 60 N/A N/A STD 62 STD 62 N/A N/A N/A N/A 4 2x4 D/I
Dimming-Comply with
AHRAE/UFC 3-530-1
SB003 WRC01 Audiology Waiting, Bldg Sprt 1 N/A m:CPT or m:LVT m:RB h:4" m:GWB f:P m:RWC h:4'-0" 40 9'-0" m: AT N/A 7'-0" m: Open N/A N/A N/A 75 72 60 N/A N/A STD 62 STD 62 N/A N/A N/A N/A 4 2x4 D/I
Comply with
AHRAE/UFC 3-530-1
SB201 TPG01 Patient Toilet, Bldg Sprt 1 N/A Aligns with FGI m:PT or m:RES m: PT or
RES H:4"
m:GWB f:SC m:PT or
CT or S 4'-0" 45 9'-0" m: GWB f: SC 3'-6" 7'-0" 1 m: Wood N/A hw:2H 2 or 4U 75 72 60 N/A N/A STD 62 STD 62 G N/A (-) N/A 0
DL/VANI
TY
Comply with
AHRAE/UFC 3-530-1
SC183 RCP01 Audiology Reception, Clncl Sprt 1 N/A m:LVT or m:CPT m: RB h:4" m:GWB f:P N/A N/A 40 9'-0" m: AT
3'-0" or
OPEN
7'-0" or
OPEN
1 OR
OPEN
m: Wood
3E or
OPEN
hw: 3E or N/A 75 72 60 N/A N/A STD 62 STD 62 N/A N/A N/A N/A 4 1 2x4 D/I
Comply with
AHRAE/UFC 3-530-1
SS258 Printer Station, Stff Sprt 1 N/A m:CPT m:RB h:4" m:GWB f:P N/A N/A 35 9'-0" m: AT 3'-0" 7'-0" 19 m: Wood S hw: 1L 75 72 60 N/A N/A STD 62 STD 62 N/A N/A N/A N/A 2 1 2x4 D/I
Comply with
AHRAE/UFC 3-530-1
CDS03 DNXS1
Panoramic / Cephalometric X-Ray
Room 1 N/A m:LVT m:RB h:4" m:GWB f:P N/A N/A N/A 40 9'-0" m: AT 4'-0" 7'-0" 15 m: Wood N/A hw: 4Q 75 72 60 N/A N/A STD 62 STD 62 N/A N/A N/A N/A 4 2x4 D/I
Dimming-Comply with
AHRAE/UFC 3-530-1
CDS11 DNTG1
Multifunctional Dental Treatment
Patient Care Room 10 N/A Aligns with FGI m:LVT m:RB h:4" m:GWB f:P m:RWC h:4'-0" 50 9'-0" m: AT 3'-6" 7'-0" 19 m: Wood N/A hw: 1L 75 72 60 N/A N/A STD 62 STD 62 N/A N/A N/A N/A 4 2x4 D/I
Dimming-Comply with
AHRAE/UFC 3-530-1
CDS13 DNTG5
Special Needs Dental Treatment
Room (DTR) 1 N/A Aligns with FGI m:RF m:RF h:4" m:GWB f:SC N/A N/A 50 9'-0" m:AT 3'-0" 7'-0" 19 m: Wood N/A hw: 1L 75 72 60 N/A N/A STD 62 STD 62 N/A N/A N/A N/A 4 2x4 D/I
Dimming-Comply with
AHRAE/UFC 3-530-1
CDS21 UCCL1 Clean Supply Room 1 N/A m:WSF m:WSF h:4" m:GWB f:SC m:RWC h:4'-0" 35 9'-0" m: AT f:SP 3'-8" 7'-0" 11 m: Wood F SH-3C ds:YES 75 72 60 N/A N/A STD 62 STD 62 N/A N/A (+) N/A 4 2x4 D/I
Comply with
AHRAE/UFC 3-530-1
CDS26 SRS01 Supply Storage Room 1 N/A m:VT m:RB h:4" m:GWB f:P m:RWC h:4'-0" 40 9'-0" m: AT 3'-8" 7'-0" 11 m: Wood F hw: 5 75 72 60 N/A N/A STD 62 STD 62 N/A N/A N/A N/A 4 2x4 D/I
Comply with
AHRAE/UFC 3-530-1
CDS47 DNTS1 Surgery Operating Room (OR) 3 N/A Aligns with FGI m:WSF m:WSF h:4" m:GWB f:SC m:RWC h:4'-0" 50 9'-0" m: AT f:SP 3'-8" 7'-0" 11 m: Wood F SH-3C ds:YES 75 72 60 N/A 20 4 4 N/A N/A (+) N/A
Each operating room shall be provided with a minimum of 36 receptacles divided between at least two branch circuits. At least 12 receptacles, but no more than 24, shall be connected to either.
CDS51 DNPL1 General Purpose Laboratory 1 N/A m:WSF or m:RES m: RES h:
4" m:GWB f:SC N/A N/A 40 9'-0" m: GWB f: SC SC 3'-0" 7'-0" 1 m: Wood T hw:4G 4K 75 72 60 N/A N/A STD 62 STD 62 N/A N/A N/A N/A 4 2x4 D/I
Comply with
AHRAE/UFC 3-530-1
CDS95 MECH1
Dental Equipment Mechanical
Room 1 N/A m:VT m:RB h:4" m:GWB f:P m:RWC h:4'-0" 40 9'-0" m: AT 3'-8" 7'-0" 11 m: Wood F hw: 5 75 72 60 N/A N/A STD 62 STD 62 N/A N/A N/A N/A 4 1x4 IF
Comply with
AHRAE/UFC 3-530-1
SB003 WRC01 Dental Waiting 4 N/A m:CPT or m:LVT m:RB h:4" m:GWB f:P m:RWC h:4'-0" 40 9'-0" m: AT N/A 7'-0" m: Open N/A N/A N/A 75 72 60 N/A N/A STD 62 STD 62 N/A N/A N/A N/A 4 2x4 D/I
Comply with
AHRAE/UFC 3-530-1
SB191 TNPG1
Dental Universal Non-Patient
Toilet 1 N/A Aligns with FGI m:PT or m:RES m: PT or
RES H:4"
m:GWB f:SC m:PT or
CT or S 4'-0" 45 9'-0" m: GWB f: SC 3'-6" 7'-0" 1 m: Wood N/A hw:2H 2 or 4U 75 72 60 N/A N/A STD 62 STD 62 G N/A (-) N/A 1
DL/VANI
TY
Comply with
AHRAE/UFC 3-530-1
SC243
01 - COMMUNITY BASED
OUTPATIENT CLINIC
(CBOC) (265)
11 - PATIENT CARE AREA:
DENTAL
01 - COMMUNITY BASED
OUTPATIENT CLINIC
(CBOC) (265)
09 - PATIENT CARE AREA:
MENTAL HEALTH
01 - COMMUNITY BASED
OUTPATIENT CLINIC
(CBOC) (265)
10 - PATIENT CARE AREA:
AUDIOLOGY
Name
Functional Area Number
& Name
Room
Code
Known
Legacy
Room
Code
Project Room Name
Quantity of This
Room
FGI Equivalent for ASHRAE 170
FGI Equivalent for Table 1-2-5
Minimum
Sound Isolation
F lo o r
F in is h
B a se
W a ll F in is h
W a ll F in is h A lt e rn a te
W a in sc o t
M a te ri a l
W a in sc o t
H e ig h t
S T
C
C e il in g H e ig h t
C e il in g F in is h
N o te s
S iz e
W id th
H e ig h t
T y p e
M a te ri a l
G la zi n g
R a ti n g
H a rd w a re
G ro u p
H a rd w a re
N o te s
In d o o r T e m p e ra tu re C o o li n g
F
In d o o r T e m p e ra tu re H e a ti n g
F
In d o o r R e la ti v e H u m id it y x
In d o o r R e la ti v e H u m id it y
M in im u m T o ta l A
C H
M in im u m O u ts id e
A ir
C h a n te
M in im u m O
A A
C H
R o o m
A ir
R e tu rn
G e n E x h
G S p e c
E x h S
M in im u m N o is e L e v e l
N C
R o o m
A ir
B a la n ce
H V
A C
N o te s
D u p le x
R e ce p ta cl e s
Q u a d R e ce p ta cl e s
P o w e r
N o te s
F ix tu re
T y p e
C o n tr o ls
Li g h ti n g
S p e ci a l R e q u ir e m e n ts
Li g h ti n g
N o te s
ROOM DATA MATRIX INTERIOR CONSTRUCTION DOORS AND HARDWARE MECHANICAL ELECTRICAL
Note: Use parameters within FGI Guidelines for the noted FGI Equivalent category unless otherwise noted. FGI is required for
Ambulatory Surgical Center ASHRAE Standard 170 and the balance of other spaces outdoor ventilation and exhaust would fall under the requirments of ASHRAE Standard 62.
Minimum receptacle quantities provided in this matrix. Equipment layouts must be assessed for each room to provide the correct receptacle and hardwire connection quantity. Where required by ASHRAE 90.1 and UFC 3-520-01, all workstations and work areas must have controlled and non-controlled outlets. All office, staff-support spaces, and other workstation locations require a minimum of two duplex receptacles, one double duplex, or one quadraplex receptacle for each workstation. Provide GFCI receptacles as required by NFPA 70. Receptacle layout and quantities must meet UFC 3-520-01 requirements.
POWER
Lighting fixture quantity and type provided are an estimate to meet minimum requirements.
Ceiling material selection will affect fixture type and size. Provide computer-generated photometric plans for each space to verify proposed lighting design meets the required performance criteria using the applicable light loss factor (LLF). All interior and exterior lighting design shall meet all UFC 3-530-1 and ASHRAE requirements. Egress lighting and controls shall comply with NFPA 101 and UFC 3-530-1. LIGHTING
ROOM IDENTIFICATION FACILITY GUIDELINES INSTITUTE FLOOR WALLS CEILING
SB201 TPG01 Dental Patient Toilet 1 N/A Aligns with FGI m:PT or m:RES m: PT or
RES H:4"
m:GWB f:SC m:PT or
CT or S 4'-0" 45 9'-0" m: GWB f: SC 3'-6" 7'-0" 1 m: Wood N/A hw:2H 2 or 4U 75 72 60 N/A N/A STD 62 STD 62 G N/A (-) N/A 0
DL/VANI
TY
Comply with
AHRAE/UFC 3-530-1
SB743 USCL1 Soiled Holding Room 1 N/A m:WSF m:WSF h:4" m:GWB f:SC m:RWC h:4'-0" 35 9'-0" m: AT f:SP 3'-8" 7'-0" 11 m: Wood F SH-3C ds:YES 75 72 60 N/A N/A STD 62 STD 62 G N/A (-) N/A 4 2x4 D/I
Comply with
AHRAE/UFC 3-530-1
SB763 SRS04 Sterile Supplies Room 1 N/A m:WSF m:WSF h:4" m:GWB f:SC N/A N/A 35 9'-0" m: AT 3'-6" 7'-0" 19 m: Wood hw: 5B 75 72 60 N/A N/A STD 62 STD 62 N/A N/A (+) N/A 4 2x4 D/I
Comply with
AHRAE/UFC 3-530-1
SC083 CSMP1 Dental Medication Room 1 N/A m:VT m:RB h:4" m:GWB f:P N/A N/A 40 9'-0" m: AT 3'-0" 7'-0" 1 m: Wood T SH-3C ds:YES 75 72 60 N/A N/A STD 62 STD 62 N/A N/A N/A N/A 4 2x4 D/I
Comply with
AHRAE/UFC 3-530-1
SC183 RCP01 Dental Reception 1 N/A m:LVT or m:CPT m: RB h:4" m:GWB f:P N/A N/A 40 9'-0" m: AT
3'-0" or
OPEN
7'-0" or
OPEN
1 OR
OPEN
m: Wood
3E or
OPEN
hw: 3E or N/A 75 72 60 N/A N/A STD 62 STD 62 N/A N/A N/A N/A 4 1 2x4 D/I
Comply with
AHRAE/UFC 3-530-1
SC243 Dental Team Room 1 N/A m:CPT or m:LVT m:RB h:4 m:GWB f:P N/A N/A 40 9'-0" m: AT 3'-0" 7'-0" 19 m: Wood T hw: 3G 75 72 60 N/A N/A STD 62 STD 62 N/A N/A N/A N/A 4 2x4 D/I
Comply with
AHRAE/UFC 3-530-1
SS204 OFA09 Office, Chief 1 N/A m:LVT or m:CPT m:RB h:4" m:GWB f:P N/A N/A 40 9'-0" m: AT 3'-0" 7'-0" 1 m: Wood T hw: 3E 75 72 60 N/A N/A STD 62 STD 62 N/A N/A N/A N/A 5 1 2x4 D/I
Dimming-Comply with
AHRAE/UFC 3-530-1
SS209 OFD02 Admin Team Room 1 N/A m:CPT or m:LVT m:RB h:4 m:GWB f:P N/A N/A 40 9'-0" m: AT 3'-0" 7'-0" 19 m: Wood T hw: 3G 75 72 60 N/A N/A STD 62 STD 62 N/A N/A N/A N/A 4 2x4 D/I
Comply with
AHRAE/UFC 3-530-1
SS258 Printer Station 1 N/A m:LVT m:RB h:4" m:GWB f:P m:RWC h:4'-0" 40 9'-0" m: AT N/A 7'-0" m: Open N/A N/A N/A 75 72 60 N/A N/A STD 62 STD 62 N/A N/A N/A N/A 2 1 2x4 D/I
Comply with
AHRAE/UFC 3-530-1
CEY12 OPVF1 Visual Fields Room 1 N/A m:LVT m:RB h:4" m:GWB f:P N/A N/A 40 9'-0" m: AT 3'-0" 7'-0" 19 m: Wood N/A hw: 1L 75 72 60 N/A N/A STD 62 STD 62 N/A N/A N/A N/A 4 2x4 D/I
Comply with
AHRAE/UFC 3-530-1
CEY13 EYVF1 Photography Room 1 N/A m: LVT m: RB h:4" m: GWB f:P N/A N/A 40 9'-0" m: AT 3'-0" 7'-0" 19 m: Wood N/A hw: 1L 75 72 60 N/A N/A STD 62 STD 62 N/A N/A N/A N/A 4 2x4 D/I
Comply with
AHRAE/UFC 3-530-1
CEY16 OPIM1 Imaging Room 1 N/A m: WSF m: WSF h:
4" m: GWB f: SC N/A N/A 40 9'-0" m: AT 3'-6" 7'-0" 19 m: Wood N/A hw: 1Q 75 72 60 N/A N/A STD 62 STD 62 N/A N/A N/A N/A 4 2x4 D/I
Comply with
AHRAE/UFC 3-530-1
CEY34 STEQ1 Equipment Storage Room 1 N/A m:VT m:RB h:4" m:GWB f:P m:RWC h:4'-0" 40 9'-0" m: AT 3'-8" 7'-0" 11 m: Wood F hw: 4Q 75 72 60 N/A N/A STD 62 STD 62 N/A N/A N/A N/A 4 2x4 D/I
Comply with
AHRAE/UFC 3-530-1
CEY41 SRS01 Supply Storage Room 1 N/A m:VT m:RB h:4" m:GWB f:P m:RWC h:4'-0" 40 9'-0" m: AT 3'-8" 7'-0" 11 m: Wood F hw: 3G 75 72 60 N/A N/A STD 62 STD 62 N/A N/A N/A N/A 4 2x4 D/I
Comply with
AHRAE/UFC 3-530-1
CEY52 OPPT2 Testing Patient Care Room 2 N/A m:LVT m:RB h:4" m:GWB f:P N/A N/A 40 9'-0" m: AT 3'-0" 7'-0" 19 m: Wood N/A hw: 5B 75 72 60 N/A N/A STD 62 STD 62 N/A N/A N/A N/A 4 2x4 D/I
Comply with
AHRAE/UFC 3-530-1
CEY53 OPET2 Patient Care Room 12 N/A m:LVT m:RB h:4" m:GWB f:P N/A N/A 40 9'-0" m: AT 3'-0" 7'-0" 19 m: Wood N/A hw: 1Q 75 72 60 N/A N/A STD 62 STD 62 N/A N/A N/A N/A 4 2x4 D/I
Comply with
AHRAE/UFC 3-530-1
CEY91 EYFD1
Eyeglass Fitting & Dispensing
Patient Care Room 1 N/A m:LVT m:RB h:4" m:GWB f:P N/A N/A 40 9'-0" m: AT 3'-0" 7'-0" 19 m: Wood N/A hw: 4F 75 72 60 N/A N/A STD 62 STD 62 N/A N/A N/A N/A 4 2x4 D/I
Comply with
AHRAE/UFC 3-530-1
SB001 Dilation Seating Alcove 2 N/A m:CPT or m:LVT m:RB h:4" m:GWB f:P m:RWC h:4'-0" 40 9'-0" m: AT N/A 7'-0" m: Open N/A N/A N/A 75 72 60 N/A N/A STD 62 STD 62 N/A N/A N/A N/A 1 DL
Comply with
AHRAE/UFC 3-530-1
SB003 WRC01 Eye Clinic Waiting 1 N/A m:CPT or m:LVT m:RB h:4" m:GWB f:P m:RWC h:4'-0" 40 9'-0" m: AT N/A 7'-0" m: Open N/A N/A N/A 75 72 60 N/A N/A STD 62 STD 62 N/A N/A N/A N/A 4 2x4 D/I
Comply with
AHRAE/UFC 3-530-1
SB201 TPG01 Patient Toilet 2 N/A Aligns with FGI m:PT or m:RES m: PT or
RES H:4"
m:GWB f:SC m:PT or
CT or S 4'-0" 45 9'-0" m: GWB f: SC 3'-6" 7'-0" 1 m: Wood N/A hw:2H 2 or 4U 75 72 60 N/A N/A STD 62 STD 62 G N/A (-) N/A 0
DL/VANI
TY
Comply with
AHRAE/UFC 3-530-1
SB743 USCL1 Soiled Utility Room 1 N/A m:WSF m:WSF h:4" m:GWB f:SC m:RWC h:4'-0" 35 9'-0" m: AT f:SP 3'-8" 7'-0" 11 m: Wood F SH-3C ds:YES 75 72 60 N/A N/A STD 62 STD 62 G N/A (-) N/A 4 2x4 D/I
Comply with
AHRAE/UFC 3-530-1
SC183 RCP01 Eye Clinic Reception 1 N/A m:LVT or m:CPT m: RB h:4" m:GWB f:P N/A N/A 40 9'-0" m: AT
3'-0" or
OPEN
7'-0" or
OPEN
1 OR
OPEN
m: Wood
3E or
OPEN
hw: 3E or N/A 75 72 60 N/A N/A STD 62 STD 62 N/A N/A N/A N/A 4 1 2x4 D/I
Comply with
AHRAE/UFC 3-530-1
SC243 Team Room (2 workstations) 2 N/A m:CPT or m:LVT m:RB h:
4" m:GWB f:P N/A N/A 40 9'-0" m: AT N/A 7'-0" m: Open N/A N/A N/A 75 72 60 N/A N/A STD 62 STD 62 N/A N/A N/A N/A 4 2 2x4 D/I
Dimming-Comply with
AHRAE/UFC 3-530-1
SS204 OFA09 Supervisor Office 1 N/A m:LVT or m:CPT m:RB h:4" m:GWB f:P N/A N/A 40 9'-0" m: AT 3'-0" 7'-0" 1 m: Wood T hw: 3E 75 72 60 N/A N/A STD 62 STD 62 N/A N/A N/A N/A 5 1 2x4 D/I
Dimming-Comply with
AHRAE/UFC 3-530-1
SS258 Printer Station 1 N/A m:CPT orm:LVT m:RB h:4" m:GWB f:P N/A N/A 40 9'-0" m: AT or GWB f: P
N/A 7'-0" m: Open N/A N/A N/A 75 72 60 N/A N/A STD 62 STD 62 N/A N/A N/A N/A 2 1 2x4 D/I
Comply with
AHRAE/UFC 3-530-1
Infusion Bay 8 N/A m:VT m:RB h:4" m:GWB f:P m:RWC m:4'-0" 35 9'-0" m: AT 3'-8" 7'-0" 11 m: Wood N/A SH-3F 75 72 60 N/A N/A STD 62 STD 62 N/A N/A N/A N/A 4 2x4 D/I
Comply with
AHRAE/UFC 3-530-1
Infusion Room 2 N/A m:VT m:RB h:4" m:GWB f:P m:RWC m:4'-0" 35 9'-0" m: AT 3'-8" 7'-0" 11 m: Wood N/A SH-3F 75 72 60 N/A N/A STD 62 STD 62 N/A N/A N/A N/A 4 2x4 D/I
Comply with
AHRAE/UFC 3-530-1
SB003 WRC01 General Waiting 1 N/A m:CPT or m:LVT m:RB h:4" m:GWB f:P m:RWC h:4'-0" 40 9'-0" m: AT N/A 7'-0" m: Open N/A N/A N/A 75 72 60 N/A N/A STD 62 STD 62 N/A N/A N/A N/A 4 2x4 D/I
Comply with
AHRAE/UFC 3-530-1
SB201 TPG01 Patient Toilet 2 N/A Aligns with FGI m:PT or m:RES m: PT or
RES H:4"
m:GWB f:SC m:PT or
CT or S 4'-0" 45 9'-0" m: GWB f: SC 3'-6" 7'-0" 1 m: Wood N/A hw:2H 2 or 4U 75 72 60 N/A N/A STD 62 STD 62 G N/A (-) N/A 0
DL/VANI
TY
Comply with
AHRAE/UFC 3-530-1
SB721 STEQ1 Medical Equipment Storage Room 2 N/A m:VT m:RB h:4" m:GWB f:P m:RWC h:4'-0" 40 9'-0" m: AT 3'-8" 7'-0" 11 m: Wood F hw: 5 75 72 60 N/A N/A STD 62 STD 62 N/A N/A N/A N/A 4 2x4 D/I
Comply with
AHRAE/UFC 3-530-1
SB735 UCCL1 Clean Utility Room 1 N/A m:WSF m:WSF h:4" m:GWB f:SC m:RWC h:4'-0" 35 9'-0" m: AT f:SP 3'-8" 7'-0" 11 m: Wood F SH-3C ds:YES 75 72 60 N/A N/A STD 62 STD 62 N/A N/A (+) N/A 4 2x4 D/I
Comply with
AHRAE/UFC 3-530-1
SB741 USCL1 Soiled Utility Holding Room 1 N/A m:WSF m:WSF h:4" m:GWB f:SC m:RWC h:4'-0" 35 9'-0" m: AT…