262913_Motor_Controllers.pdf

PDF 60 KB Posted

Attached to
Chicopee Armory Renovations General Contractor Bids
Solicitation number
S124834-vCurrent
Issued by
Hampden County, Massachusetts

About this file

This document is a technical specification for motor controllers to be used in the Chicopee Armory Rehabilitation project in Chicopee, Massachusetts. The work includes providing locally installed, enclosed combination magnetic motor starters and manual motor starters. The products shall comply with NEMA and UL standards. The submittal requirements include manufacturer's product data sheets, dimensioned outline drawings, and control wiring diagrams. The specification lists the approved manufacturers as Allen-Bradley, Cutler-Hammer, Furnas Electric, General Electric, Siemens, and Square D.

The specification details the requirements for the magnetic motor starters, including NEMA ratings, disconnecting means, overload relays, control power transformers, and pilot devices. It also covers the requirements for manual motor starters. The work shall be installed in accordance with the project's electrical installation requirements.

View the file

Other files

File Type Posted
AE121-10090.pdf PDF
ED101-10090.pdf PDF
Sub_Bid_Result_Chicopee_2011.xls XLS spreadsheet
AE102-10090.pdf PDF
Business_Reference_Form_GC_Chicopee2011.doc DOC document
230719_hvac_pipe_ins.pdf PDF
EP651-10090.pdf PDF
Ch_149_FORM_FOR_SUB_BID_MIL_Chicopee2011_Electrical.doc DOC document
Ch_149_FORM_FOR_SUB_BID_MIL_Chicopee2011_Metal_Windows.doc DOC document
013200_FL-CONSTRUCTION_PROGRESS_DOCUMENTATION.pdf PDF
014000_FL-QUALITY_REQUIREMENTS.pdf PDF
236313_air_cooled_condensers.pdf PDF
AE311-10090.pdf PDF
020800_Asbestos_Technical_Specifications.pdf PDF
E-601-10090.pdf PDF
230001-HVAC_FSB.pdf PDF
Ch_149_FORM_FOR_SUB_BID_MIL_Chicopee2011_Resilient_Floors.doc DOC document
017900_FL-DEMONSTRATION_AND_TRAINING.pdf PDF
Ch_149_FORM_FOR_SUB_BID_MIL_Chicopee2011_Masonry.doc DOC document
AE401-10090.pdf PDF
SF502-10090.pdf PDF
070002-ROOFING_AND_FLASHING_FSB.pdf PDF
265100_Lighting_Fixtures.pdf PDF
030130_FL-MAINTENANCE_OF_CAST-IN-PLACE_CONCRETE.pdf PDF
220001-PLUMBING-FSB.pdf PDF
013100_FL-PROJECT_MANAGEMENT_AND_COORDINATION.pdf PDF
238900_Louvers_and_Vents.pdf PDF
SF101-10090.pdf PDF
016000_FL-PRODUCT_REQUIREMENTS.pdf PDF
M-651-10090.pdf PDF
GI001-10090.pdf PDF
Ch_149_FORM_FOR_GENERAL_BID_MIL_Chicopee2011.doc DOC document
093000_FL-TILING_v1.pdf PDF
088000_FL-GLAZING_v1.pdf PDF
081113_FL-HOLLOW_METAL_DOORS_AND_FRAMES_v1.pdf PDF
231123_fuel_gas_piping.pdf PDF
PL101-10090.pdf PDF
230900_hvac_instrumentation_controls.pdf PDF
224000_plumbing_fixtures_JPB.pdf PDF
061600_FL-SHEATHING_v1.pdf PDF
220100_plumbing_requirements_JPB.pdf PDF
232113_hydronic_piping.pdf PDF
EL101-10090.pdf PDF
232300_refrigerant_piping.pdf PDF
General_Bid_Tabulation_Chicopee_2011.xls XLS spreadsheet
220500_plumbing_materials_JPB.pdf PDF
262413_Switchboards.pdf PDF
092216_FL-NON-STRUCTURAL_META_FRAMING_v1.pdf PDF
X-100_SURVEY_CONTROL_PLAN.pdf PDF
AE611-10090.pdf PDF
Show 40 more

Latest 50 of 185 listed here. See the rest on GovTribe.

On GovTribe

Work with this file

  • Download the original file
  • Contacts named in this file
  • Similar government files
  • Ask GovTribe AI about this file

Text version

CHICOPEE ARMORY REHABILITATION MMD PROJECT NO. 985010

CHICOPEE, MASSACHUSETTS ISSUED FOR BID – 05/20/11

10090 MOTOR CONTROLLERS 262913-1

SECTION 262913

MOTOR CONTROLLERS

PART 1 - GENERAL

1.1 GENERAL

A. The provisions of Section 260500, General Requirements for Electrical Work, apply to the work of this Section.

B. The work of this section includes locally installed, enclosed combination magnetic motor starters and manual motor starters.

1.2 CODES AND STANDARDS

A. Products shall comply with the following codes and standards and shall be UL listed and labeled.

NEMA ICS-2 Industrial Control Devices, Controllers and Assemblies.

UL 508 Industrial Control Equipment.

1.3 SUBMITTALS

A. Manufacturer’s Product Data Sheets

B. Dimensioned Outline Drawings.

C. Control wiring diagrams.

1.4 MANUFACTURERS

Subject to compliance with the requirements of this Section:

Allen-Bradley

Cutler-Hammer

Furnas Electric

General Electric

Siemens

Square D

PART 2 - PRODUCTS

2.1 MAGNETIC MOTOR STARTERS

A. Unless otherwise noted, magnetic motor starters shall be NEMA rated full voltage type.

The disconnecting means shall be circuit breaker type, non-fused or fused switch as shown on the drawings. Minimum starter size shall be NEMA 1.

B. All components including the disconnecting means shall be installed in a single enclosure rated NEMA 1 for indoor locations and NEMA 3R for wet, damp and outdoor locations.

10090 MOTOR CONTROLLERS 262913-2

C. The disconnecting means shall be provided with an external operating handle which is interlocked to prevent opening the door when the handle is in the ON position and prevent closing the disconnect when the door is opened. The interlock shall be de-featable. The handle shall be pad-lockable in the OFF position.

D. Circuit breakers shall be adjustable magnetic trip, motor circuit protector type.

E. The short circuit rating of the assembly shall have a rating equal to the branch circuit breaker rating feeding the assembly.

F. Each motor starter shall be provided with a control power transformer to provide 120 VAC control power. The transformer shall be provided with two primary fuses and one secondary fuse. The transformer shall be extra capacity with a minimum rating of 100 VA.

G. Overload relays shall be three pole, trip free, manually reset Class 20, solid state with an external reset mechanism.

H. Contactor coils shall be provided with surge suppressors.

I. Sufficient auxiliary contacts shall be provided for all interlocks. A minimum of one normally opened and one normally closed spare contacts shall be provided.

J. Door mounted pilot devices shall be heavy duty oil tight. Pilot lights shall be transformer type. A HAND-OFF-AUTO maintained contact selector switch, red RUN and green

READY pilot lights shall be provided on each enclosure.

K. All control wiring shall be brought to terminal blocks for connection of field cabling.

Minimum wire size shall be #14 AWG.

L. Connections for motor leads shall be suitable for copper conductors applied at their 75° C rating.

2.2 MANUAL MOTOR STARTERS

A. Single phase fractional HP manual motor starters shall be toggle operated, enclosed, one or two pole switches as required by the installation.

B. Unless otherwise noted, the enclosure shall be NEMA 1 for indoor locations and NEMA

3R for outdoor, wet and damp locations. A handle guard shall be provided to allow the toggle operator to be padlocked in the OFF position.

C. Starters shall be provided with trip free melting alloy overloads where required.

PART 3 - EXECUTION

3.1 Equipment shall be installed in accordance with Section 260550, Installation of Electrical

Equipment.

3.2 The Contractor shall verify motor nameplate amperes and motor service factors and shall set all solid state relays for magnetic motor starters and provide all overload heater elements for manual

10090 MOTOR CONTROLLERS 262913-3

motor starters. Overload heater elements shall be sized in accordance with motor nameplate amperes.

END OF SECTION 262913