238900_Louvers_and_Vents.pdf
PDF 68 KB Posted
- Solicitation number
- S124834-vCurrent
- Issued by
- Hampden County, Massachusetts
About this file
This document is a specification for the Louvers and Vents section of the Chicopee Armory Rehabilitation project in Chicopee, Massachusetts. The project involves the rehabilitation of the Chicopee Armory, including the installation of fixed, extruded-aluminum and formed-metal louvers. The louvers must meet specific performance requirements for structural integrity, wind loads, and water penetration, and be compliant with AMCA standards. The specification covers the required materials, fabrication, finishes, and installation procedures for the louvers and associated components such as screens and blank-off panels.
The state and local contract opportunity related to this document is for the overall Chicopee Armory Renovations General Contractor project. This project is being managed by the state of Massachusetts. The contract will involve general construction work to rehabilitate the Chicopee Armory facility. Bids for the general contractor role are being solicited, with a bid due date and award date not specified in the provided information.
View the file
Other files
Show 40 more
Latest 50 of 185 listed here. See the rest on GovTribe.
On GovTribe
Work with this file
- Download the original file
- Contacts named in this file
- Similar government files
- Ask GovTribe AI about this file
Text version
CHICOPEE ARMORY REHABILITATION MMD PROJECT NO. 985101
CHICOPEE, MASSACHUSETTS ISSUED FOR BID - 05/20/11
10090 LOUVERS AND VENTS 23 89 00-1
SECTION 238900
LOUVERS AND VENTS
PART 1 - GENERAL
1.1 RELATED DOCUMENTS
A. Drawings and general provisions of the Contract, including General and Supplementary
Conditions and Division 01 Specification Sections, apply to this Section.
1.2 SUMMARY
A. Section Includes:
1. Fixed, extruded-aluminum and formed-metal louvers.
B. Related Sections:
1. Section 042000 "Unit Masonry" for building wall vents (brick vents) into masonry.
2. Section 081113 "Hollow Metal Doors and Frames" for louvers in hollow-metal doors.
3. Section 099113 "Exterior Painting" for field painting louvers.
4. Section 230900 "Instrumentation and Control for HVAC" for electric, electronic, and pneumatic control of adjustable louvers.
1.3 DEFINITIONS
A. Louver Terminology: Definitions of terms for metal louvers contained in AMCA 501 apply to this Section unless otherwise defined in this Section or in referenced standards.
B. Horizontal Louver: Louver with horizontal blades; i.e., the axes of the blades are horizontal.
C. Vertical Louver: Louver with vertical blades; i.e., the axes of the blades are vertical.
D. Drainable-Blade Louver: Louver with blades having gutters that collect water and drain it to channels in jambs and mullions, which carry it to bottom of unit and away from opening.
E. Storm-Resistant Louver: Louver that provides specified wind-driven rain performance, as determined by testing according to AMCA 500-L.
1.4 PERFORMANCE REQUIREMENTS
A. Delegated Design: Design louvers, including comprehensive engineering analysis by a qualified professional engineer, using structural performance requirements and design criteria indicated.
10090 LOUVERS AND VENTS 23 89 00-2
B. Structural Performance: Louvers shall withstand the effects of gravity loads and the following loads and stresses within limits and under conditions indicated without permanent deformation of louver components, noise or metal fatigue caused by louver blade rattle or flutter, or permanent damage to fasteners and anchors. Wind pressures shall be considered to act normal to the face of the building.
1. Wind Loads: Determine loads based on a uniform pressure of 20 lbf/sq. ft., acting inward or outward.
C. Seismic Performance: Louvers, including attachments to other construction, shall withstand the effects of earthquake motions determined according to SEI/ASCE 7.
D. Louver Performance Ratings: Provide louvers complying with requirements specified, as demonstrated by testing manufacturer's stock units identical to those provided, except for length and width according to AMCA 500-L.
1.5 ACTION SUBMITTALS
A. Product Data: For each type of product indicated.
1. For louvers specified to bear AMCA seal, include printed catalog pages showing specified models with appropriate AMCA Certified Ratings Seals.
B. Shop Drawings: For louvers and accessories. Include plans, elevations, sections, details, and attachments to other work. Show frame profiles and blade profiles, angles, and spacing.
1. Show weep paths, gaskets, flashing, sealant, and other means of preventing water intrusion.
2. Show mullion profiles and locations.
3. Wiring Diagrams: For power, signal, and control wiring for motorized adjustable louvers.
C. Samples for Initial Selection: For units with factory-applied color finishes.
D. Samples for Verification: For each type of metal finish required.
E. Delegated-Design Submittal: For louvers indicated to comply with structural[ and seismic] performance requirements and design criteria, including analysis data signed and sealed by the qualified professional engineer responsible for their preparation.
1.6 INFORMATIONAL SUBMITTALS
A. Product Test Reports: Based on evaluation of comprehensive tests performed according to
AMCA 500-L by a qualified testing agency or by manufacturer and witnessed by a qualified testing agency, for each type of louver and showing compliance with performance requirements specified.
10090 LOUVERS AND VENTS 23 89 00-3
1.7 QUALITY ASSURANCE
A. Source Limitations: Obtain louvers and vents from single source from a single manufacturer where indicated to be of same type, design, or factory-applied color finish.
B. SMACNA Standard: Comply with recommendations in SMACNA's "Architectural Sheet Metal
Manual" for fabrication, construction details, and installation procedures.
1.8 PROJECT CONDITIONS
A. Field Measurements: Verify actual dimensions of openings by field measurements before fabrication.
PART 2 - PRODUCTS
2.1 MATERIALS
A. Aluminum Extrusions: ASTM B 221, Alloy 6063-T5, T-52, or T6.
B. Aluminum Sheet: ASTM B 209, Alloy 3003 or 5005 with temper as required for forming, or as otherwise recommended by metal producer for required finish.
C. Aluminum Castings: ASTM B 26/B 26M, Alloy 319.
D. Galvanized-Steel Sheet: ASTM A 653/A 653M, G60 zinc coating, mill phosphatized.
E. Stainless-Steel Sheet: ASTM A 240/A 240M, Type 304, [No. 2B finish] [No. 2D finish] [No. 4 finish, with grain running parallel to length of blades and frame members] [No. 4 finish, with grain running perpendicular to length of blades and frame members] [No. 4 finish, with grain running perpendicular to length of blades and parallel to length of frame members] [No. 6 finish].
F. Fasteners: Use types and sizes to suit unit installation conditions.
1. Use hex-head or Phillips pan-head screws for exposed fasteners unless otherwise indicated.
2. For fastening aluminum, use aluminum or 300 series stainless-steel fasteners.
3. For fastening galvanized steel, use hot-dip-galvanized steel or 300 series stainless-steel fasteners.
4. For fastening stainless steel, use 300 series stainless-steel fasteners.
5. For color-finished louvers, use fasteners with heads that match color of louvers.
G. Postinstalled Fasteners for Concrete and Masonry: Torque-controlled expansion anchors, made from stainless-steel components, with capability to sustain, without failure, a load equal to 4 times the loads imposed, for concrete, or 6 times the load imposed, for masonry, as determined by testing per ASTM E 488, conducted by a qualified independent testing agency.
H. Bituminous Paint: Cold-applied asphalt emulsion complying with ASTM D 1187.
10090 LOUVERS AND VENTS 23 89 00-4
2.2 FABRICATION, GENERAL
A. Assemble louvers in factory to minimize field splicing and assembly. Disassemble units as necessary for shipping and handling limitations. Clearly mark units for reassembly and coordinated installation.
B. Maintain equal louver blade spacing, including separation between blades and frames at head and sill, to produce uniform appearance.
C. Fabricate frames, including integral sills, to fit in openings of sizes indicated, with allowances made for fabrication and installation tolerances, adjoining material tolerances, and perimeter sealant joints.
1. Frame Type: Channel unless otherwise indicated.
D. Include supports, anchorages, and accessories required for complete assembly.
E. Provide vertical mullions of type and at spacings indicated, but not more than recommended by manufacturer, or 72 inches o.c., whichever is less.
1. Semirecessed Mullions: Where indicated, provide mullions partly recessed behind louver blades so louver blades appear continuous. Where length of louver exceeds fabrication and handling limitations, fabricate with interlocking split mullions and close-fitting blade splices designed to permit expansion and contraction.
2. Exposed Mullions: Where indicated, provide units with exposed mullions of same width and depth as louver frame. Where length of louver exceeds fabrication and handling limitations, provide interlocking split mullions designed to permit expansion and contraction.
3. Exterior Corners: Prefabricated corner units with mitered [and welded blades] blades with concealed close-fitting splices and with mullions at corners.
F. Provide subsills made of same material as louvers for recessed louvers.
G. Join frame members to each other and to fixed louver blades with fillet welds concealed from view unless otherwise indicated or size of louver assembly makes bolted connections between frame members necessary.
2.3 FIXED, EXTRUDED-ALUMINUM LOUVERS
A. Horizontal Storm-Resistant Louver:
1. Manufacturers: Subject to compliance with requirements, available manufacturers offering products that may be incorporated into the Work include, but are not limited to, the following:
a. Air Balance Inc.; a Mestek company.
b. Air Flow Company, Inc.
c. Airolite Company, LLC (The).
d. All-Lite Architectural Products.
e. American Warming and Ventilating, Inc.; a Mestek company.
f. Arrow United Industries; a division of Mestek, Inc.
http://www.specagent.com/LookUp/?uid=123456814583&mf=04&src=wd http://www.specagent.com/LookUp/?uid=123456791796&mf=04&src=wd http://www.specagent.com/LookUp/?uid=123456791798&mf=04&src=wd http://www.specagent.com/LookUp/?uid=123456791800&mf=04&src=wd http://www.specagent.com/LookUp/?uid=123456814584&mf=04&src=wd http://www.specagent.com/LookUp/?uid=123456814585&mf=04&src=wd
10090 LOUVERS AND VENTS 23 89 00-5
g. Construction Specialties, Inc.
h. Greenheck Fan Corporation.
i. Industrial Louvers, Inc.
j. NCA Manufacturing, Inc.
k. Nystrom Building Products.
l. Reliable Products, Inc.
m. Ruskin Company; Tomkins PLC.
n. United Enertech Corp.
o. .
2. Louver Depth: 4 inches.
3. Frame and Blade Nominal Thickness: Not less than 0.080 inch.
4. Louver Performance Ratings:
a. Air Performance: Not more than 0.10-inch wg static pressure drop at 600-fpm free-area velocity.
b. Wind-Driven Rain Performance: Not less than 99 percent effectiveness when subjected to a rainfall rate of 3 inches per hour and a wind speed of 29 mph at a core-area intake velocity of 500 fpm.
5. AMCA Seal: Mark units with AMCA Certified Ratings Seal.
B. Horizontal, Drainable-Blade Louver:
1. Manufacturers: Subject to compliance with requirements, available manufacturers offering products that may be incorporated into the Work include, but are not limited to, the following:
a. Air Balance Inc.; a Mestek company.
b. Air Flow Company, Inc.
c. Airolite Company, LLC (The)).
d. All-Lite Architectural Products.
e. American Warming and Ventilating, Inc.; a Mestek company.
f. Arrow United Industries; a division of Mestek, Inc.
g. Carnes Company, Inc.
h. Cesco Products; a division of Mestek, Inc.
i. Construction Specialties, Inc.
j. Dowco Products Group; Safe-Air of Illinois, Inc.
k. Greenheck Fan Corporation.
l. Industrial Louvers, Inc.
m. Louvers & Dampers, Inc.; a division of Mestek, Inc.
n. Metal Form Manufacturing Inc.
o. NCA Manufacturing, Inc.
p. Nystrom Building Products.
q. Reliable Products, Inc.
r. Ruskin Company; Tomkins PLC.
s. United Enertech Corp.
t. Vent Products Company, Inc.
2. Louver Depth: 4 inches.
3. Frame and Blade Nominal Thickness: Not less than 0.080 inch.
4. Mullion Type: Exposed.
http://www.specagent.com/LookUp/?uid=123456791804&mf=04&src=wd http://www.specagent.com/LookUp/?uid=123456791807&mf=04&src=wd http://www.specagent.com/LookUp/?uid=123456791808&mf=04&src=wd http://www.specagent.com/LookUp/?uid=123456791810&mf=04&src=wd http://www.specagent.com/LookUp/?uid=123456791812&mf=04&src=wd http://www.specagent.com/LookUp/?uid=123456791814&mf=04&src=wd http://www.specagent.com/LookUp/?uid=123456814586&mf=04&src=wd http://www.specagent.com/LookUp/?uid=123456791818&mf=04&src=wd http://www.specagent.com/LookUp/?uid=123456814593&mf=04&src=wd http://www.specagent.com/LookUp/?uid=123456791847&mf=04&src=wd http://www.specagent.com/LookUp/?uid=123456791853&mf=04&src=wd http://www.specagent.com/LookUp/?uid=123456791851&mf=04&src=wd http://www.specagent.com/LookUp/?uid=123456814594&mf=04&src=wd http://www.specagent.com/LookUp/?uid=123456814595&mf=04&src=wd http://www.specagent.com/LookUp/?uid=123456791854&mf=04&src=wd http://www.specagent.com/LookUp/?uid=123456814596&mf=04&src=wd http://www.specagent.com/LookUp/?uid=123456791857&mf=04&src=wd http://www.specagent.com/LookUp/?uid=123456814597&mf=04&src=wd http://www.specagent.com/LookUp/?uid=123456791859&mf=04&src=wd http://www.specagent.com/LookUp/?uid=123456791860&mf=04&src=wd http://www.specagent.com/LookUp/?uid=123456814598&mf=04&src=wd http://www.specagent.com/LookUp/?uid=123456791865&mf=04&src=wd http://www.specagent.com/LookUp/?uid=123456791866&mf=04&src=wd http://www.specagent.com/LookUp/?uid=123456791870&mf=04&src=wd http://www.specagent.com/LookUp/?uid=123456791871&mf=04&src=wd http://www.specagent.com/LookUp/?uid=123456814599&mf=04&src=wd http://www.specagent.com/LookUp/?uid=123456791875&mf=04&src=wd http://www.specagent.com/LookUp/?uid=123456791878&mf=04&src=wd
10090 LOUVERS AND VENTS 23 89 00-6
5. Louver Performance Ratings:
a. Point of Beginning Water Penetration: Not less than 900 fpm.
b. Air Performance: Not more than 0.10-inch wg static pressure drop at 700-fpm free-area intake velocity.
6. AMCA Seal: Mark units with AMCA Certified Ratings Seal.
2.4 FIXED, FORMED-METAL LOUVERS
A. Horizontal, Drainable-Blade Louver:
1. Manufacturers: Subject to compliance with requirements, available manufacturers offering products that may be incorporated into the Work include, but are not limited to, the following:
a. Air Balance Inc.; a Mestek company.
b. Air Flow Company, Inc.
c. Airolite Company, LLC (The).
d. American Warming and Ventilating, Inc.; a Mestek company.
e. Arrow United Industries; a division of Mestek, Inc.
f. Cesco Products; a division of Mestek, Inc.
g. Construction Specialties, Inc.
h. Dowco Products Group; Safe-Air of Illinois, Inc.
i. Greenheck Fan Corporation.
j. Industrial Louvers, Inc.
k. Metal Form Manufacturing Inc.
l. NCA Manufacturing, Inc.
m. Ruskin Company; Tomkins PLC.
n. United Enertech Corp.
o. Vent Products Company, Inc.
2. Louver Depth: 4 inches.
3. Frame and Blade Material and Nominal Thickness: Galvanized-steel sheet, not less than
0.052 inch for frames and 0.040 inch for blades.
4. Mullion Type: Exposed.
5. Louver Performance Ratings:
a. Point of Beginning Water Penetration: Not less than [900 fpm].
b. Air Performance: Not more than 0.10-inch wg static pressure drop at 700-fpm free-area intake velocity.
6. AMCA Seal: Mark units with AMCA Certified Ratings Seal.
2.5 LOUVER SCREENS
A. General: Provide screen at [each exterior louver] [louvers indicated].
1. Screen Location for Fixed Louvers: Interior face.
2. Screening Type: Bird screening.
http://www.specagent.com/LookUp/?uid=123456814621&mf=04&src=wd http://www.specagent.com/LookUp/?uid=123456791972&mf=04&src=wd http://www.specagent.com/LookUp/?uid=123456791974&mf=04&src=wd http://www.specagent.com/LookUp/?uid=123456814622&mf=04&src=wd http://www.specagent.com/LookUp/?uid=123456814623&mf=04&src=wd http://www.specagent.com/LookUp/?uid=123456814624&mf=04&src=wd http://www.specagent.com/LookUp/?uid=123456791976&mf=04&src=wd http://www.specagent.com/LookUp/?uid=123456814625&mf=04&src=wd http://www.specagent.com/LookUp/?uid=123456791977&mf=04&src=wd http://www.specagent.com/LookUp/?uid=123456791978&mf=04&src=wd http://www.specagent.com/LookUp/?uid=123456791980&mf=04&src=wd http://www.specagent.com/LookUp/?uid=123456791981&mf=04&src=wd http://www.specagent.com/LookUp/?uid=123456814626&mf=04&src=wd http://www.specagent.com/LookUp/?uid=123456791990&mf=04&src=wd http://www.specagent.com/LookUp/?uid=123456791993&mf=04&src=wd
10090 LOUVERS AND VENTS 23 89 00-7
B. Secure screen frames to louver frames with machine screws with heads finished to match louver, spaced a maximum of 6 inches from each corner and at 12 inches o.c.
C. Louver Screen Frames: Fabricate with mitered corners to louver sizes indicated.
1. Metal: Same kind and form of metal as indicated for louver to which screens are attached. Reinforce extruded-aluminum screen frames at corners with clips.
2. Finish: Same finish as louver frames to which louver screens are attached.
D. Louver Screening for Aluminum Louvers:
1. Bird Screening: Aluminum, 1/2-inch- square mesh, 0.063-inch wire.
2. Bird Screening: Flattened, expanded aluminum, 3/4 by 0.050 inch thick.
E. Louver Screening for Galvanized-Steel Louvers:
1. Bird Screening: Galvanized steel, 1/2-inch- square mesh, 0.041-inch wire.
2.6 BLANK-OFF PANELS
A. Insulated, Blank-Off Panels: Laminated panels consisting of insulating core surfaced on back and front with metal sheets and attached to back of louver.
1. Thickness: 1 inch.
2. Metal Facing Sheets: Aluminum sheet, not less than 0.032-inch nominal thickness.
3. Metal Facing Sheets: Galvanized-steel sheet, not less than 0.028-inch nominal thickness.
4. Metal Facing Sheets: Stainless-steel sheet, not less than 0.031-inch nominal thickness.
5. Insulating Core: Rigid, glass-fiber-board insulation or extruded-polystyrene foam.
6. Edge Treatment: Trim perimeter edges of blank-off panels with louver manufacturer's standard extruded-aluminum-channel frames, not less than 0.080-inch nominal thickness, with corners mitered and with same finish as panels.
7. Seal perimeter joints between panel faces and louver frames with gaskets or sealant.
8. Panel Finish: Same type of finish applied to louvers, but black color.
9. Attach blank-off panels with sheet metal screws.
2.7 FINISHES, GENERAL
A. Comply with NAAMM's "Metal Finishes Manual for Architectural and Metal Products" for recommendations for applying and designating finishes.
2.8 ALUMINUM FINISHES
A. Finish louvers after assembly.
B. Color Anodic Finish: AAMA 611, [AA-M12C22A42/A44, Class I, 0.018 mm] [AA-
M12C22A32/A34, Class II, 0.010 mm] or thicker.
1. Color: As selected by Architect from full range of industry colors and color densities.
10090 LOUVERS AND VENTS 23 89 00-8
C. Conversion-Coated Finish: AA-C12C42 (Chemical Finish: cleaned with inhibited chemicals;
Chemical Finish: acid-chromate-fluoride-phosphate conversion coating).
D. Conversion-Coated and Factory-Primed Finish: AA-C12C42R1x (Chemical Finish: cleaned with inhibited chemicals; Chemical Finish: acid-chromate-fluoride-phosphate conversion coating; Organic Coating: as specified below).
1. Organic Coating: Air-dried primer of not less than 2-mil dry film thickness.
E. Baked-Enamel or Powder-Coat Finish: AAMA 2603 except with a minimum dry film thickness of 1.5 mils. Comply with coating manufacturer's written instructions for cleaning, conversion coating, and applying and baking finish.
1. Color and Gloss: As selected by Architect from manufacturer's full range.
2.9 GALVANIZED-STEEL SHEET FINISHES
A. Finish louvers after assembly.
B. Surface Preparation: Clean surfaces with nonpetroleum solvent so surfaces are free of oil and other contaminants. After cleaning, apply a conversion coating suited to the organic coating to be applied over it. Clean welds, mechanical connections, and abraded areas and repair according to ASTM A 780.
C. Baked-Enamel or Powder-Coat Finish: Immediately after cleaning and pretreating, apply manufacturer's standard 2-coat, baked-on finish consisting of prime coat and thermosetting topcoat, with a minimum dry film thickness of 1 mil for topcoat. Comply with coating manufacturer's written instructions for applying and baking to achieve a minimum dry film thickness of 2 mils.
1. Color and Gloss: As selected by Architect from manufacturer's full range.
2.10 STAINLESS-STEEL SHEET FINISHES
A. Repair sheet finish by grinding and polishing irregularities, weld spatter, scratches, and forming marks to match surrounding finish.
PART 3 - EXECUTION
3.1 EXAMINATION
A. Examine substrates and openings, with Installer present, for compliance with requirements for installation tolerances and other conditions affecting performance.
B. Proceed with installation only after unsatisfactory conditions have been corrected.
10090 LOUVERS AND VENTS 23 89 00-9
3.2 PREPARATION
A. Coordinate setting drawings, diagrams, templates, instructions, and directions for installation of anchorages that are to be embedded in concrete or masonry construction. Coordinate delivery of such items to Project site.
3.3 INSTALLATION
A. Locate and place louvers and vents level, plumb, and at indicated alignment with adjacent work.
B. Use concealed anchorages where possible. Provide brass or lead washers fitted to screws where required to protect metal surfaces and to make a weathertight connection.
C. Form closely fitted joints with exposed connections accurately located and secured.
D. Provide perimeter reveals and openings of uniform width for sealants and joint fillers, as indicated.
E. Repair finishes damaged by cutting, welding, soldering, and grinding. Restore finishes so no evidence remains of corrective work. Return items that cannot be refinished in the field to the factory, make required alterations, and refinish entire unit or provide new units.
F. Protect unpainted galvanized and nonferrous-metal surfaces that will be in contact with concrete, masonry, or dissimilar metals from corrosion and galvanic action by applying a heavy coating of bituminous paint or by separating surfaces with waterproof gaskets or nonmetallic flashing.
G. Install concealed gaskets, flashings, joint fillers, and insulation as louver installation progresses, where weathertight louver joints are required. Comply with Section 079200 "Joint Sealants" for sealants applied during louver installation.
3.4 ADJUSTING AND CLEANING
A. Test operation of adjustable louvers and adjust as needed to produce fully functioning units that comply with requirements.
B. Clean exposed surfaces of louvers and vents that are not protected by temporary covering, to remove fingerprints and soil during construction period. Do not let soil accumulate during construction period.
C. Before final inspection, clean exposed surfaces with water and a mild soap or detergent not harmful to finishes. Thoroughly rinse surfaces and dry.
D. Restore louvers and vents damaged during installation and construction so no evidence remains of corrective work. If results of restoration are unsuccessful, as determined by Architect, remove damaged units and replace with new units.
1. Touch up minor abrasions in finishes with air-dried coating that matches color and gloss of, and is compatible with, factory-applied finish coating.
10090 LOUVERS AND VENTS 23 89 00-10
END OF SECTION 089000