25106 - Portage Geo and Solar - Elec Bid Set 25-08-29.pdf

PDF 3 MB Posted

Attached to
Town of Portage Town hall renovation
Solicitation number
2130423
Issued by
Montgomery County, New York

About this file

This is an electrical bid set and project specification document for the Town of Portage Town Hall Renovation project located in Hunt, New York. The project, designed by Turner Engineering, PC and Hager Engineering Solutions, encompasses a comprehensive interior renovation with new utilities including electrical systems integrated with renewable energy and geothermal heating technologies. The electrical scope includes complete installation of lighting systems, power distribution, receptacles, occupancy sensors, emergency systems, panelboards, and associated controls throughout the facility. The project incorporates a 39.6 kW DC-rated solar photovoltaic system with three 11.4 kW inverters, 72 Longi bifacial solar modules rated at 550 watts each, and a combiner panel with fused disconnect as part of a net-zero energy design. Additional electrical work includes removal and relocation of existing equipment, installation of new branch circuits and panelboards (P1 at 200A and P2 at 225A), LED luminaires of various types (recessed panels, linear over-mirror, surface-mounted, and exit signs), motor starters for HVAC equipment, emergency lighting with battery backup, voice and data outlets, fire alarm systems, and all associated conduit, wiring, and controls. All work must comply with the 2017 National Electrical Code, New York State building codes, and OSHA requirements.

The specification documents establish that all electrical materials, labor, equipment, and services for complete installation are the contractor's responsibility, with stranded copper wire minimum #12 AWG, EMT interior conduit with set-screw fittings, and rigid steel conduit for exterior above-grade applications. Contractor-provided services include obtaining an Underwriters Certificate upon substantial completion, providing engraved laminate plastic nameplates on all major equipment, field-applied vinyl labels on receptacles and circuits, updated panelboard directories, and fire stopping for all floor and wall penetrations per ASTM E814. Equipment specifications mandate Square D or equal panelboards and disconnect switches, Hubbell or equal receptacles and wiring devices in light almond color, Lithonia or Isolite lighting fixtures with specified lumens and color temperatures, and Sensor Switch occupancy sensors with dimming and daylight harvesting capabilities. The project includes demolition notes requiring disconnection and removal of existing electrical equipment, raceways, and wiring unless specifically noted to remain, with field verification of existing conditions required. No incumbent information, pricing terms, set-asides, or contract award dates are specified in these technical documents, which serve as the bid set specifications for electrical contractors responding to the Town of Portage's request for proposals.

View the file

Other files

On GovTribe

Work with this file

  • Download the original file
  • Contacts named in this file
  • Similar government files
  • Ask GovTribe AI about this file

Text version

SYMBOL DESCRIPTION

POWER DISTRIBUTION

SURFACE/FLUSH MOUNTED BRANCH

CIRCUIT PANELBOARD. 208Y/120V OR

240/120V. REFER TO PANELBOARD

SCHEDULE

MANUAL MOTOR STARTER OR MOTOR

RATED SWITCH.

NON-FUSED DISCONNECT SWITCH.

ELECTRICAL

DESCRIPTION

DUPLEX RECEPTACLE,

SUBSCRIPTS AS FOLLOWS:

AFI

CR

EP

GFI

H

IG

SS

WP

TR

WR

USB

ARC FAULT INTERRUPTER

CORROSION RESISTANT

EXPLOSION PROOF

GROUND FAULT INTERRUPTER

HOSPITAL GRADE

ISOLATED GROUND

SURGE SUPPRESSION

WEATHER PROOF

TAMPER RESISTANT

WEATHER RESISTANT

UNIVERSAL SERIAL BUS

SYMBOL DESCRIPTION

LIGHTING

SINGLE POLE SWITCH

WALL MOUNTED OCCUPANCY

SENSOR SWITCH

CEILING MOUNTED OCCUPANCY

SENSOR. SUBSCRIPT INDICATES

TYPE

2'X4' RECESSED LUMINAIRE. DESIGNATION

REFERS TO LUMINAIRE SCHEDULE

EMERGENCY REMOTE BATTERY PACK.

DESIGNATION REFERS TO LUMINAIRE

SCHEDULE

SINGLE FACE UNIVERSAL MOUNTED EXIT

SIGN. DESIGNATION REFERS TO

LUMINAIRE SCHEDULE

LA

EM2

X1

LA

SYMBOL LIST

OS-A

THREE-WAY POLE SWITCH

SUBSCRIPT INDICATES QUANTITY OF

SWITCHES. REFER TO LUMINAIRES FOR

SWITCHING DESIGNATIONS

a,b

2'X2' RECESSED LUMINAIRE. DESIGNATION

REFERS TO LUMINAIRE SCHEDULE

LA

JUNCTION BOX

BELL OR BUZZER

DOORBELL OR PUSHBUTTON

E-3

SYMBOL DESCRIPTION

MISCELLANEOUS

REFERENCE TO DRAWING NOTE

REFERENCE TO EQUIPMENT OR

FEEDER NUMBER

DETAIL REFERENCE SYMBOL

SYMBOL DESCRIPTION

LINE STYLES

INDICATES UNDERGROUND TELEPHONE

SPECIAL PURPOSE RECEPTACLE

LIGHTING CONTROL PANEL

LCP

PHOTOCELL

MOTOR. DESIGNATION REFERS TO

ELECTRIC EQUIPMENT AND CONTROL

SCHEDULE

EMERGENCY DUPLEX RECEPTACLE

EMERGENCY BATTERY PACK.

DESIGNATION REFERS TO LUMINAIRE

SCHEDULE

EM1

DUAL FACE UNIVERSAL MOUNTED EXIT

SIGN. DESIGNATION REFERS TO

LUMINAIRE SCHEDULE

X2

LA DOWNLIGHT. DESIGNATION REFERS TO

LUMINAIRE SCHEDULE

INDICATES UNDERGROUND ELECTRIC

INDICATES NEW DEVICE OR EQUIPMENT

INDICATES UNDERGROUND CATV

E

T

CATV

LA POLE MOUNTED LUMINAIRE. DESIGNATION

REFERS TO LUMINAIRE SCHEDULE

SURFACE LUMINAIRE. DESIGNATION

REFERS TO LUMINAIRE SCHEDULE

M

MS

J

DOUBLE DUPLEX RECEPTACLE

EMERGENCY DOUBLE DUPLEX

RECEPTACLE

B

EMERGENCY POWER OFF PUSHBUTTONEPO

120 VOLT CONNECTION TO EQUIPMENT

PC

OS

EXTERIOR WALL MOUNTED LUMINAIRE.

DESIGNATION REFERS TO LUMINAIRE

SCHEDULE

REFERENCE TO DEMOLITION NOTE2

INDICATES EXISTING DEVICE OR EQUIPMENT

TO REMAIN

INDICATES DEVICE OR EQUIPMENT TO BE

REMOVED OR RELOCATED

DIMMING SWITCHD

WALL MOUNTED VACANCY

SENSOR SWITCH

VS

LA

INDICATES CABLE TRAY

SYMBOL

SYMBOL DESCRIPTION

COMMUNICATIONS

SECURITY

EXISTING VOICE/DATA OUTLET.

TV

VOICE/DATA OUTLET. PROVIDE 2-GANG

OUTLET BOX WITH SINGLE GANG MUD

RING AND 1" CONDUIT TO ACCESSIBLE

CEILING SPACE ABOVE.

CATV OUTLET. PROVIDE 2-GANG OUTLET

BOX WITH SINGLE GANG MUD RING AND 1"

CONDUIT TO ACCESSIBLE CEILING SPACE

ABOVE.

TELEPHONE ONLY OUTLET. PROVIDE 2-

GANG OUTLET BOX WITH SINGLE GANG

MUD RING AND 1" CONDUIT TO

ACCESSIBLE CEILING SPACE ABOVE.

SYMBOL DESCRIPTION

2 POST TEL/DATA RACK

CARD READER

DOOR STRIKE

DOOR CONTACT

ACCESS CONTROL PANELACP

DS

DC

CR

FINISHED FLOOR

CEILING

AAB12

AAB13

4" MINIMUM

PROVIDE 3/4" CONDUIT

INSIDE NEW WALL

PROVIDE 4 11/16" SQUARE x 2 1/8"

DEEP BACKBOX WITH SINGLE GANG

MUD RING

PROVIDE 2-GANG BACKBOX

WITH DOUBLE DUPLEX

RECEPTACLE, FLUSH MOUNTED

PROVIDE 1" CONDUIT

WITH PULLSTRING TO

CEILING SPACE

NOTES:

IN LOCATIONS WHERE SIMILAR DEVICES ARE MOUNTED AT THE SAME HEIGHT, DEVICES SHALL BE PROPERLY "GANGED" AND SHALL HAVE A SINGLE

COVER PLATE.

IN LOCATIONS WHERE DIFFERENT DEVICES ARE MOUNTED AT DIFFERENT HEIGHTS WITHIN FOUR FEET OF ONE ANOTHER DEVICES SHALL BE MOUNTED SUCH THAT THEY HAVE A COMMON CENTERLINE. IF THERE ARE THREE OR MORE DEVICES, THE CONTRACTOR SHALL REQUEST A DETAIL FROM THE

ARCHITECT.

1.

2.

FT

P A N E L B

O A R

D

D

IS

C O

N N E C T

T H E R

M O

S T A T O

T

E M

P E R

A T U R

E S

E N S O

R

L

IG

H T S

W

IT

C H

C A R

D A

C C E S S

V O

IC

E /D

A T A O

U T L E T

D U P L E X R

E C E P T A C L E

6'-8" 6'-0" 5'-0"

4'-0" 4'-0" 4'-0" 4'-0" 4'-0"

1'-6" 1'-6" 1'-6"

4'-0"

7'-8"7'-6"

F

IR

E A

L A R

M A U D

IO

/V

IS

U A L

A N D

V

IS

U A L

D E V

IC

E

F

IR

E A

L A R

M P U L L S

T A T

IO

N

W A L L M

O U N T E D

T E L E P H O

N E

D U P L E X R

E C E P T A C L E

M E C H R

O O

M G

A R

A G

E S

C L O

C K

O U T L E T

D E S K T

O P T

E L E P H O

N E

C A T V

O U T L E T

FINISHED

FLOOR

D O

M E

L

IG

H T

4'-0"

A P A R

T M

E N T L

O A D

C E N T E R

4'-0"

M O

T O

R R

A T E D

S W

IT

C H

TURNER

E N G I N E E R I N G , P C

One Woodbury Boulevard Rochester, NY 14604

585.381.3360

IT IS A VIOLATION OF LAW FOR ANY PERSONS,

UNLESS ACTING UNDER THE DIRECTION OF A

LICENSED PROFESSIONAL ENGINEER, TO ALTER

ANY ITEM ON THIS DOCUMENT IN ANY WAY. ANY

LICENSEE WHO ALTERS THIS DOCUMENT IS

REQUIRED BY LAW TO AFFIX HIS OR HER SEAL

AND THE NOTATION "ALTERED BY", FOLLOWED

BY HIS OR HER SIGNATURE AND A SPECIFIC

DESCRIPTION OF THE ALTERATIONS.

Client

Project

Drawing

Issue Date:

Proj. No.

Sheet

Revisions

Proj. Status:

E-001

ELECTRICAL GENERAL

NOTES, SPECIFICATIONS,

AND SYMBOLS

Project No. 25106

TOWN OF PORTAGE GEO

AND SOLAR

TOWN OF PORTAGE

25106

08/29/2025

9907 CHURCH STREET

HUNT, NY 14846

BID DOCUMENTS

ELECTRICAL SPECIFICATIONS

1. PROVIDE ALL LABOR, MATERIALS, EQUIPMENT AND SERVICES TO PERFORM

ALL OPERATIONS REQUIRED FOR THE COMPLETE INSTALLATION AND

RELATED WORK AS SHOWN ON DRAWINGS AND SPECIFIED HEREIN. ELECTRIC

EQUIPMENT SHALL BE INSTALLED IN A NEAT AND WORKMAN LIKE MANNER.

PROVIDE ALL ELECTRICAL EQUIPMENT CONNECTIONS. PROVIDE ALL

REQUIRED SUPPORTS AND ACCESSORIES. INSTALL ALL WORK IN

COMPLIANCE WITH LATEST EDITION OF THE NATIONAL ELECTRICAL CODE,

NFPA-70, NEW YORK STATE UNIFORM FIRE PREVENTION AND BUILDING CODE,

NEW YORK STATE ENERGY CONSERVATION CONSTRUCTION CODE, OSHA

REQUIREMENTS, AND LOCAL ORDINANCES.

2. INSTALL ALL WIRING AND EQUIPMENT IN ACCORDANCE WITH THE 2017

NATIONAL ELECTRICAL CODE.

3. OBTAIN AN UNDERWRITERS CERTIFICATE UPON SUBSTANTIAL COMPLETION.

4. COORDINATE ALL WORK WITH OTHER TRADES.

5. PROVIDE EQUIPMENT IDENTIFICATION NAMEPLATES ON ALL SWITCHBOARDS,

PANELBOARDS, ELECTRICAL EQUIPMENT ENCLOSURES, TRANSFORMERS,

DISCONNECT SWITCHES, AND MOTOR STARTERS. NAMEPLATES SHALL BE

ENGRAVED LAMINATE PLASTIC INDICATING EQUIPMENT NAME, VOLTAGE,

PHASE, AND SOURCE OF POWER.

6. PROVIDE CIRCUIT LABELS ON ALL RECEPTACLES AND DEVICES. LABELS

SHALL BE FIELD-APPLIED VINYL PRINTED STICKERS INDICATING

PANELBOARD NAME AND CIRCUIT NUMBER. LABELS FOR RECEPTACLES

WITHIN OFFICE AREAS SHALL BE ON THE INSIDE OF COVERPLATES.

7. WIRE SHALL BE STRANDED COPPER WITH THHN/THWN INSULATION, MINIMUM

#12 AWG.

8. INTERIOR CONDUIT SHALL BE EMT WITH SET-SCREW FITTINGS.

9. EXTERIOR, ABOVE GRADE CONDUIT SHALL BE RIGID STEEL WITH THREADED

FITTINGS.

10. EXTERIOR, BELOW GRADE CONDUIT SHALL BE PVC, SCHEDULE 80, DIRECT

BURIED.

11. TYPE MC CABLE WITH A SEPARATE INSULATED GROUND IS PERMITTED. IN

INTERIOR, CONCEALED LOCATIONS. SUPPORT CABLE ON MINIMUM 4.5'

CENTERS.

12. ALL HOMERUNS TO PANELBOARDS SHALL BE INSTALLED IN EMT CONDUIT.

TYPE MC CABLE MAY BE USED FROM OUTLET BOXES IN THE CEILING TO

DEVICES AND LUMINAIRES, AND MAY BE RUN HORIZONTALLY IN THE METAL

STUD PARTITIONS.

13. PROVIDE UPDATED TYPE-WRITTEN DIRECTORIES FOR ALL PANELBOARDS

AFFECTED BY THIS PROJECT.

14. ALL EXPOSED WIRING SHALL BE INSTALLED IN CONDUIT OR SURFACE METAL

RACEWAY.

15. WHEREVER POSSIBLE, INSTALL ALL RACEWAYS CONCEALED AND DEVICES

FLUSH MOUNTED. WHERE REQUIRED DUE TO FIELD CONDITIONS, PROVIDE

SURFACE METAL RACEWAY. PAINT TO MATCH EXISTING SURFACES.

16. OUTLET BOXES AND COVERS SHALL BE GALVANIZED STEEL, NOT LESS THAN

1-1/2" DEEP, 4" SQUARE OR OCTAGONAL, WITH KNOCKOUTS. OUTLET BOXES

EXPOSED TO MOISTURE, EXTERIOR, WET OR DAMP LOCATIONS SHALL BE

CADMIUM CAST ALLOY COMPLETE WITH THREADED HUBS AND GASKETED

SCREW FASTENED COVERS. MINIMUM BOX SIZE SHALL BE AS INDICATED IN

ARTICLE 370 OF THE NATIONAL ELECTRIC CODE FOR THE CONDUCTORS AND

DEVICES INSTALLED. MAKE SHALL BE STEEL CITY OR EQUAL.

17. DUPLEX RECEPTACLES SHALL BE CONSTRUCTION GRADE. INTERIOR TYPE

SHALL BE DUPLEX, 20 AMPERE, TWO-POLE, THREE-WIRE, 125 VOLTS AC,

GROUNDING, WITH SIDE AND BACK TERMINAL CONNECTIONS AND SPLITWIRING

LINK, U.L. LISTED, WITH THERMOPLASTIC COVERPLATES. COLOR TO BE LIGHT

ALMOND. MAKE SHALL BE HUBBELL OR EQUAL.

ELECTRICAL SPECIFICATIONS

18. PROVIDE LABELS ON ALL RECEPTACLES INDICATING BRANCH CIRCUIT PANEL

AND CIRCUIT NUMBER.

19. WIRING DEVICES SHALL BE CONSTRUCTION GRADE, LIGHT ALMOND IN

COLOR, WITH THERMOPLASTIC COVERPLATES. MAKE SHALL BE HUBBELL OR

EQUAL.

20. WEATHER RESISTANT DEVICE COVERS SHALL BE UL LISTED WITH THE DEVICE

PLUGGED IN. MAKE SHALL BE HUBBELL OR EQUAL.

21. WALL MOUNTED ANALOG VACANCY SENSORS SHALL BE DUAL TECHNOLOGY

AND INSTALL IN A SINGLE GANG OUTLET BOX. DEVICE SHALL BE EQUIPPED

WITH A SET OF AUXILIARY CONTACTS TO CONTROL ADDITIONAL EQUIPMENT.

WHERE CALLED FOR ON THE PLANS, PROVIDE DUAL INTEGRAL SWITCHES TO

PROVIDE THREE-LEVEL LIGHTING. MAKE SHALL BE SENSOR SWITCH WSXA

PDT SERIES OR APPROVED EQUAL.

22. WALL MOUNTED ANALOG OCCUPANCY SENSOR WITH DIMMING AND ADAPTIVE

DAYLIGHT HARVESTING SHALL BE DUAL TECHNOLOGY AND INSTALL IN A

SINGLE GANG OUTLET BOX. DEVICE SHALL BE EQUIPPED WITH A SET OF

AUXILIARY CONTACTS TO CONTROL ADDITIONAL EQUIPMENT. MAKE SHALL

BE SENSOR SWITCH WSXA PDT D SERIES OR APPROVED EQUAL.

23. WALL MOUNTED DIGITAL VACANCY SENSORS SHALL BE DUAL TECHNOLOGY

AND INSTALL IN A SINGLE GANG OUTLET BOX. DEVICE SHALL BE EQUIPPED

WITH A SET OF AUXILIARY CONTACTS TO CONTROL ADDITIONAL EQUIPMENT.

WHERE CALLED FOR ON THE PLANS, PROVIDE DUAL INTEGRAL SWITCHES TO

PROVIDE THREE-LEVEL LIGHTING. MAKE SHALL BE SENSOR SWITCH nWSXA

PDT SERIES OR APPROVED EQUAL. PROVIDE CAT5 CABLE AS REQUIRED.

24. WALL MOUNTED DIGITAL OCCUPANCY SENSOR WITH DIMMING AND ADAPTIVE

DAYLIGHT HARVESTING SHALL BE DUAL TECHNOLOGY AND INSTALL IN A

SINGLE GANG OUTLET BOX. DEVICE SHALL BE EQUIPPED WITH A SET OF

AUXILIARY CONTACTS TO CONTROL ADDITIONAL EQUIPMENT. MAKE SHALL

BE SENSOR SWITCH nWSXA PDT D SERIES OR APPROVED EQUAL. PROVIDE

CAT5 CABLE AS REQUIRED.

25. OCCUPANCY SENSOR OS-A SHALL BE CEILING MOUNTED ULTRASONIC,

SUITABLE FOR SPACES UP TO 1000 SQUARE FEET. MAKE SHALL BE SENSOR

SWITCH nCM PDT 9 SERIES OR EQUAL.

26. PANELBOARDS SHALL HAVE ALUMINUM BUS WITH PLUG-ON CIRCUIT BREAKERS

AND HINGED TRIM. COORDINATE TRIM TYPE IN THE FIELD. MAKE SHALL BE

SQUARE D OR EQUAL.

27. DISCONNECT SWITCHES SHALL BE HEAVY DUTY WITH COPPER BUS. KNIVES

SHALL BE VISIBLE IN THE OPEN POSITION. MAKE SHALL BE SQUARE D OR

EQUAL.

28. MANUAL MOTOR STARTERS AND MOTOR RATED SWITCHES SHALL BE 277

VOLT, 30 AMPERE RATED, IN A NEMA 1 ENCLOSURE WITH A H-O-A SELECTOR

SWITCH AND A RELAY FOR REMOTE CONTROL OF THE EQUIPMENT IN THE

AUTO MODE. PROVIDE OVERLOADS AS REQUIRED. MAKE SHALL BE SQUARE

D CLASS 2510 OR EQUAL.

29. ALL LUMINAIRES SHALL BE CONNECTED WITH THREE #12 CONDUCTORS IN A

FLEXIBLE CABLE WHIP, 6'-0" MAXIMUM IN LENGTH. CABLE SHALL BE

INSTALLED SUCH THAT FIXTURES IN LAY-IN CEILING SYSTEM MAY BE

RELOCATED ONE-TILE IN ANY DIRECTION WITHOUT REWIRING. ALL LUMINAIRE

WHIPS SHALL BE CONNECTED TO A JUNCTION BOX. LUMINAIRES SHALL NOT

BE CONNECTED TOGETHER IN A DAISY CHAIN MANNER. SECURELY SUPPORT

ALL CONDUITS AND OUTLET BOXES FROM STRUCTURAL MEMBERS, OUTLET

BOXES SHALL NOT BE SUPPORTED BY CONDUIT, AND INDEPENDENTLY

SUPPORT LUMINAIRES FROM BUILDING STRUCTURE.

30. PROVIDE FIRE STOPPING FOR ALL PENETRATIONS THROUGH FLOORS, WALLS

AND ALL OTHER RELATED ASSEMBLIES. PROVIDE FIRE STOPPING SYSTEMS

IN ACCORDANCE WITH ASTM E814.

ELECTRICAL GENERAL DEMOLITION NOTES

A. NOTES APPLY TO ALL DEMOLITION ELECTRICAL DRAWINGS.

B. DISCONNECT AND REMOVE ALL EXISTING ELECTRICAL EQUIPMENT, WIRING, AND

RACEWAYS UNLESS NOTED TO REMAIN AND TO BE RELOCATED.

C. DISCONNECT AND REMOVE ALL EMPTY AND ABANDONED RACEWAYS UNLESS

NOTED OTHERWISE. CUT FLUSH WITH FLOOR WHERE APPLICABLE AND PLUG WITH

GROUT.

D. COORDINATE ALL REMOVAL WORK WITH OTHER TRADES. PROVIDE ALL WIRING

AND CONNECTIONS REQUIRED TO MAINTAIN BRANCH CIRCUIT OR SPECIAL

SYSTEMS CIRCUIT CONTINUITY TO DEVICES AND EQUIPMENT TO REMAIN, WHETHER

LOCATED WITHIN OR OUTSIDE OF THE PROJECT BOUNDARY.

E. PARTIAL BRANCH CIRCUIT WIRING DENOTING EXISTING CIRCUITING OR CONTROL

IS SHOWN FOR REFERENCE ONLY, AND IS NOT INTENDED TO ILLUSTRATE

COMPLETE WIRING SYSTEM. FIELD VERIFY EXISTING WIRING AND CONNECTIONS.

F. "ETR" ADJACENT TO A DEVICE, FIXTURE, OR PIECE OF EQUIPMENT INDICATES

ITEM SHALL REMAIN. MAINTAIN EXISTING ELECTRICAL CONNECTIONS UNLESS

OTHERWISE NOTED.

G. "ERL" ADJACENT TO A DEVICE, FIXTURE, OR PIECE OF EQUIPMENT INDICATES

EXISTING ITEM SHALL BE RELOCATED. DISCONNECT AND REMOVE, REINSTALL

AT NEW LOCATION AND RECONNECT ITEM AS REQUIRED.

ELECTRICAL GENERAL NOTES

A. GENERAL NOTES APPLY TO ALL ELECTRICAL DRAWINGS.

B. PROVIDE UPDATED TYPE WRITTEN PANELBOARD SCHEDULES FOR ALL PANELS

USED IN THIS PROJECT.

C. INSTALL ALL DEVICES FLUSH IN WALL CONSTRUCTION.

D. PROVIDE BLANK COVERPLATES ON ALL EXISTING AND NEW UNUSED OUTLET

BOXES.

E. COORDINATE ALL CONDUIT RUNS WITH OTHER TRADES PRIOR TO ROUGH-IN.

RELOCATE ANY CONDUITS AS NECESSARY TO PERMIT INSTALLATION OF

DUCTWORK, PIPING OR ANY SUPPORTS.

F. PROVIDE CUTTING, PATCHING TO MATCH, AND FIRE SEAL AS REQUIRED WHERE

EXISTING COMMUNICATION OR ELECTRICAL WORK HAS BEEN REMOVED AND

WHERE NEW WORK IS INSTALLED. COORDINATE WITH GENERAL CONTRACTOR.

G. REMOVE AND REINSTALL EXISTING CEILING TILES AS REQUIRED FOR

INSTALLATION OF BRANCH CIRCUIT WIRING AND CONDUIT. REPLACE ALL

DAMAGED TILES WITH MATCHING TILES.

H. RUN ALL WIRING CONCEALED IN WALL. CUT AND PATCH TO MATCH DRYWALL AS

REQUIRED. MINIMIZE USE OF SURFACE METAL RACEWAY.

I. COORDINATE MOUNTING HEIGHTS OF DEVICES WITH ARCHITECTURAL ELEVATIONS

AND OWNER PRIOR TO ROUGH-IN.

J. ALL DATA WIRING BY SPECTRUM. COORDINATE DEVICE LOCATION AND

QUANTITIES IN FIELD WITH OWNER PRIOR TO ROUGHING IN CONDUITS AND BOXES.

NO SCALE

FLUSH VOICE/DATA OUTLET INSTALLATION DETAIL

NO SCALE

TYPICAL DEVICE MOUNTING ELEVATIONS

TOWN CLERK

TO REMAIN

VAULT

TO REMAIN

HALL

BATH ROOM

KITCHEN

JUDGE'S

OFFICE

MEETING

ROOM

HW REF SINK

ST

PT

M

JJ

T

T

M

M S

S

48" 48"

60"

48"

48"

48"

44"

TO PANEL

SE CABLE

PULLBOX

LC

44"

44"

48"

EBB

(E)

EBB

1 11

6 6

(E) MDP

TURNER

E N G I N E E R I N G , P C

One Woodbury Boulevard Rochester, NY 14604

585.381.3360

IT IS A VIOLATION OF LAW FOR ANY PERSONS,

UNLESS ACTING UNDER THE DIRECTION OF A

LICENSED PROFESSIONAL ENGINEER, TO ALTER

ANY ITEM ON THIS DOCUMENT IN ANY WAY. ANY

LICENSEE WHO ALTERS THIS DOCUMENT IS

REQUIRED BY LAW TO AFFIX HIS OR HER SEAL

AND THE NOTATION "ALTERED BY", FOLLOWED

BY HIS OR HER SIGNATURE AND A SPECIFIC

DESCRIPTION OF THE ALTERATIONS.

Client

Project

Drawing

Issue Date:

Proj. No.

Sheet

Revisions

Proj. Status:

E-100

FLOOR PLAN -

ELECTRICAL DEMOLITION

Project No. 25106

TOWN OF PORTAGE GEO

AND SOLAR

TOWN OF PORTAGE

25106

08/29/2025

9907 CHURCH STREET

HUNT, NY 14846

BID DOCUMENTS

1/4" = 1'-0"

FIRST FLOOR WEST DEMOLITION PLAN - ELECTRICAL

N O

R T

H

ELECTRICAL DEMOLITION NOTES

1 DISCONNECT AND REMOVE LUMINAIRES IN THIS AREA. EXISTING WIRING

TO REMAIN AND BE REUSED.

2 DISCONNECT AND REMOVE LUMINAIRE. REMOVE WIRING BACK TO

NEAREST ACTIVE LUMINAIRE TO REMAIN. MAINTAIN CONTINUITY OF

CIRCUIT.

3 DISCONNECT AND REMOVE SWITCH. REMOVE WIRING BACK TO

LUMINAIRE.

4 DISCONNECT AND REMOVE FAN. REMOVE CONTROL. REMOVE WIRING

BACK TO SOURCE.

5 DISCONNECT MECHANICAL EQUIPMENT BEING REMOVED BY OTHERS.

REMOVE WIRING BACK TO SOURCE.

6 DISCONNECT AND REMOVE RECEPTACLE. REMOVE WIRING BACK TO

NEAREST ACTIVE DEVICE TO REMAIN. MAINTAIN CONTINUITY OF CIRCUIT.

7 DISCONNECT AND REMOVE OVERHEAD DOOR MOTOR AND ALL

ASSOCIATED DEVICES. REMOVE WIRING BACK TO SOURCE.

8 DISCONNECT AND REMOVE SWITCH. REMOVE SURFACE MOUNTED

OUTLET BOX AND RACEWAY. EXISTING WIRING TO REMAIN AND BE

REUSED.

9 DISCONNECT AND REMOVE PANEL. REMOVE ALL BRANCH WIRING TO

OFFICE AREA. SOME GARAGE CIRCUITS MAY BE EXISTING TO REMAIN.

TAG ALL REMAINING CIRCUITS FOR REUSE. REMOVE PANEL FEEDER

BACK TO SOURCE.

10 DISCONENCT AND REMOVE PANELBOARD. TAG ALL BRANCH CIRCUIT

WIRING FOR REUSE.

1/4" = 1'-0"

FIRST FLOOR EAST DEMOLITION PLAN - ELECTRICAL

REF

V S D

V S D

V S D

OS OS

VS

OS-B

OS-A

OS-A

OS-A

OS-A

D

OS-A

D

JUDGE

HALL

TLT.TLT.MECH

KITCHEN

HIGHWAY

SUPERINTENDENT

HALL

VAULT

TOWN

CLERK

MEETING

ROOM

CODE

INSPECTOR

TOWN

SUPERVISOR

(ETR)

LD

LA1

LA1

LA2LA2

LA2

LA2

LA1

LA2

LA1

LA2

LA2

LA2

LA2

LA2

LA2 LA2

LA2

LA2

LA2

LC LC

EM1

EM1

EM1

EM1

EM1

EM1

EM1

EM1

X1

X1 1

X1

1X1

LA2

LA2

LA2

LA2

P2

RELOCATE, EXTEND

CIRCUITS, RECONNECT

LA1 LA1

P2/2

P2/2

TURNER

E N G I N E E R I N G , P C

One Woodbury Boulevard Rochester, NY 14604

585.381.3360

IT IS A VIOLATION OF LAW FOR ANY PERSONS,

UNLESS ACTING UNDER THE DIRECTION OF A

LICENSED PROFESSIONAL ENGINEER, TO ALTER

ANY ITEM ON THIS DOCUMENT IN ANY WAY. ANY

LICENSEE WHO ALTERS THIS DOCUMENT IS

REQUIRED BY LAW TO AFFIX HIS OR HER SEAL

AND THE NOTATION "ALTERED BY", FOLLOWED

BY HIS OR HER SIGNATURE AND A SPECIFIC

DESCRIPTION OF THE ALTERATIONS.

Client

Project

Drawing

Issue Date:

Proj. No.

Sheet

Revisions

Proj. Status:

E-101

FLOOR PLAN - LIGHTING

Project No. 25106

TOWN OF PORTAGE GEO

AND SOLAR

TOWN OF PORTAGE

25106

08/29/2025

9907 CHURCH STREET

HUNT, NY 14846

BID DOCUMENTS

1/4" = 1'-0"

FIRST FLOOR PLAN - LIGHTING

N O

R T

H

LIGHTING DRAWING NOTES

1 PROVIDE EXIT SIGN. CONNECT TO A 20A/1P CIRCUIT

BREAKER IN PANEL **, CIRCUIT ** USING 2-#12, 1-#12EG IN

½"C. LOCK CIRCUIT BREAKER IN THE "ON" POSITION.

2 PROVIDE EMERGENCY BATTERY BACK-UP LUMINAIRE.

CONNECT TO AREA LIGHTING BRANCH CIRCUIT AHEAD OF

ALL SWITCHING.

3 PROVIDE OLD WORK BOX IN EXISTING WALL. FISH WALL

FROM ABOVE ACCESSIBLE CEILING SPACE WITH ¾"

FLEXIBLE METAL CONDUIT AND PROVIDE EMERGENCY

BATTERY BACK-UP LUMINAIRE. CONNECT TO AREA

LIGHTING BRANCH CIRCUIT AHEAD OF ALL SWITCHING.

4 PROVIDE EXTERIOR LUMINAIRE TO MATCH EXISTING

BUILDING WALL MOUNTED LUMINAIRES. CONNECT TO

EXISTING EXTERIOR LIGHTING BRANCH CIRCUIT AND

CONTROL.

#LIGHT FIXTURE SCHEDULE

TYPE DESCRIPTION LUMENS CCT/CRI WATTAGE (VA) VOLTAGE

DESIGN MAKE ACCEPTABLE

MANUFACTURERMANUFACTURER MODEL NO.

EM1 WALL MOUNTED, TWO-HEAD LED EMERGENCY BATTERY PACK WITH WHITE FINISH AND SELF

DIAGNOSTICS AND TESTING

250 - 4 VA 120 ISOLITE LIGHTING RL2LED-4-WH-MBC-SD APPROVED EQUAL

LA1 2'X2' FLAT PANEL LED LUMINAIRE WITH SWITCHABLE LUMENS SET AT LOW, SWITCHABLE COLOR

TEMPERATURE SET AT 3500K, PRISTMATIC ACRYLIC LENS AND WHITE HOUSING.

2489 3500K/80CRI 21 VA 120 LITHONIA LIGHTING CPX 2X2 AL07 80CRI SWW7 A12 APPROVED EQUAL

LA2 2'X2' FLAT PANEL LED LUMINAIRE WITH SWITCHABLE LUMENS SET AT MEDIUM, SWITCHABLE

COLOR TEMPERATURE SET AT 3500K, PRISTMATIC ACRYLIC LENS AND WHITE HOUSING.

3302 3500K/80CRI 28 VA 120 LITHONIA LIGHTING CPX 2X2 AL07 80CRI SWW7 A12 APPROVED EQUAL

LC 25" LINEAR LED OVER MIRROR LUMINAIRE WITH MATTE WHITE ACRYLIC LENS AND SATIN NICKEL

FINISH.

1300 3500K/90CRI 18 VA 120 LITHONIA LIGHTING FMVCSL 24IN MVOLT 30K 90CRI BN

M6

APPROVED EQUAL

LD 4' SURFACE MOUNTED LED LUMINAIRE WITH SELECTABLE LUMENS SET AT 4000 LUMENS,

SELECTABLE COLOR TEMPERATURE SET AT 3500K, ACRYLIC LENS, AND WHITE HOUSING.

4732 3500K, 80CRI 36 VA 120 LITHONIA LIGHTING CSS L48 AL03 MVOLT SWW3 80CRI APPROVED EQUAL

X1 SINGLE FACED UNIVERSAL MOUNT LED EXIT SIGN WITH WHITE THERMOPLASTIC HOUSING, RED

LETTERS, REMOVABLE CHEVRONS, AND BATTERY BACK UP, AND SELF DIAGNOSTICS AND

TESTING.

0 - 4 VA 120 ISOLITE LIGHTING RL-EM-R-U-WH-MTEB-SD APPROVED EQUAL

REF

T

S

MS

M S

MS

MS

M S

MS

JUDGE

HALL

TLT.

MECH

KITCHEN

HIGHWAY

SUPERINTENDENT

HALL

VAULT

TOWN

CLERK

MEETING

ROOMCODE

INSPECTOR

TOWN

SUPERVISOR

(ETR)

48"

46"

GFI

46"

GFI

46"

GFI

46"

48"

GFI

GFI

WP

P2/1

P2/3

P2/5

P2/17

P2/19

HP-2

ERV-2

ERV-1

HP-1

HP-3

HW-1

HWRP

M

M

M

M M

M M

P2

P1 P2/7

P2/15

P2/9

P2/11

P2/21

48"

GFI

48"

GFI

P2/13

GFI

WP

M

M

P-1 P-2

7 10

INVERTER

TYP. OF (3)

PV COMBINER PANEL

(E) METER

PV DISCONNECT

(E) ATS

(4) MOTOR RATED SWITCHES

MOTOR RATED SWITCH

MANUAL MOTOR STARTER

MANUAL MOTOR STARTER WITH RELAY

MAGNETIC STARTER

COMBINATION MAGNETIC STARTER

VARIABLE FREQUENCY DRIVE

COMBINATION TWO SPEED MAGNETIC STARTER

COMBINATION REDUCED VOLTAGE MAGNETIC STARTER

DUPLEX CONTROLLER WITH ALTERNATION CIRCUIT

PACKAGED CONTROL UNIT

H-O-A SELECTOR SWITCH IN COVER

PILOT LIGHT IN COVER

REMOTE START-STOP PUSHBUTTONS

FIRE ALARM FAN SHUTDOWN

LINE-VOLTAGE THERMOSTAT

MOTOR STARTER/CONTROLLER NOTES:

1.

2.

3.

4.

5.

6.

7.

8.

9.

10.

11.

12.

13.

14.

15.

EXTEND 120 VOLT CIRCUIT FROM HWRP-1 AND CONNECT

AQUASTAT AND TIME SWITCH.

NOTES:

1.

G

M

POLE MOUNT XFMR

240/120V SECONDARY

(E) NYSEG?

OVHD SERVICE LATERAL

200A

200A/2P

(E) GENERAC SE ATS

UTILITY METER

RG&E TO REPLACE WITH INTERVAL

METER FOR VDER CREDITING

240/120V

200A/2P

P1

SQ D NQ

200A MCB

240/120V

70A/2P

(E) GENERATOR

15kW

PROPANE

GENERAC

200A PV SYSTEM DISCONNECT

200A FUSES

240/120V 1Ø, 3W

NEMA 3R

BEHIND-THE-METER CONNECTION

AHEAD OF SE DISCONNECT

PROVIDE JUNCTION BOX

3-#3/0, 1-#6EG, 2"C

3-#3/0, 1-#6EG, 2"C

3-#3/0, 1-#6EG, 2"C

3-#3/0, 1-#6EG, 2"C

TO SOLAR COMBINER PANEL

REFER TO DETAIL ON E103

3-#3/0, 1-#6EG, 2"C

P2

SQ D NQ

225A MLO

240/120V

FEED-THRU LUGS

TURNER

E N G I N E E R I N G , P C

One Woodbury Boulevard Rochester, NY 14604

585.381.3360

IT IS A VIOLATION OF LAW FOR ANY PERSONS,

UNLESS ACTING UNDER THE DIRECTION OF A

LICENSED PROFESSIONAL ENGINEER, TO ALTER

ANY ITEM ON THIS DOCUMENT IN ANY WAY. ANY

LICENSEE WHO ALTERS THIS DOCUMENT IS

REQUIRED BY LAW TO AFFIX HIS OR HER SEAL

AND THE NOTATION "ALTERED BY", FOLLOWED

BY HIS OR HER SIGNATURE AND A SPECIFIC

DESCRIPTION OF THE ALTERATIONS.

Client

Project

Drawing

Issue Date:

Proj. No.

Sheet

Revisions

Proj. Status:

E-102

FLOOR PLAN - POWER &

SYSTEMS

Project No. 25106

TOWN OF PORTAGE GEO

AND SOLAR

TOWN OF PORTAGE

25106

08/29/2025

9907 CHURCH STREET

HUNT, NY 14846

BID DOCUMENTS

1/8" = 1'-0"

FIRST FLOOR PLAN - POWER & SYSTEMS

N O

R T

H

ELECTRICAL DRAWING NOTES

1 PROVIDE NEW PANELBOARD. EXTEND ANY IN-USE EXISTING

CIRCUITS AND RECONNECT TO PANEL. COORDINATE

LOCATION IN FIELD WITH OWNER.

2 PROVIDE OLD WORK BOX IN EXISTING WALL. CUT AND

PATCH AS REQUIRED.

ELECTRIC EQUIPMENT SCHEDULE

ITEM

NO. NAME

ROOM

LOCATION HP KW PH VOLTS PANEL

CIRCUIT

NUMBER

CIRCUIT

BREAKER

WIRING FROM PANEL

TO CONTROL UNIT

WIRING FROM CONTROL

UNIT TO EQUIPMENT

DISCONNECT SWITCH DISCONNECT SWITCH MOTOR STARTER/

CONTROLLER NOTES

CONTROLLER

LOCATION

NEMA

RATING NOTESSWITCH AMPS FUSE SIZE

1 ERV-1 HALL 0.1 1 120 P2 28 20A-1P 2-#12, 1-#12EG, 1/2"C 2-#12, 1-#12EG, 1/2"C 1 AU 1

2 ERV-2 MEETING 0.4 1 120 P2 30 20A-1P 2-#12, 1-#12EG, 1/2"C 2-#12, 1-#12EG, 1/2"C 1 AU 1

3 HP-1 HALL 0.9 1 240 P2 36,38 20A-2P 2-#12, 1-#12EG, 1/2"C 2-#12, 1-#12EG, 1/2"C 1 AU 1

4 HP-2 KITCHEN 1.1 1 240 P2 36,38 20A-2P 2-#12, 1-#12EG, 1/2"C 2-#12, 1-#12EG, 1/2"C 1 AU 1

5 HP-3 MEETING 2.3 1 240 P2 40,42 20A-2P 2-#12, 1-#12EG, 1/2"C 2-#12, 1-#12EG, 1/2"C 1 AU 1

6 P-1 MECH 1/2 1 240 P2 32,34 20A-2P 2-#12, 1-#12EG, 1/2"C 2-#12, 1-#12EG, 1/2"C 1 AU 1

7 P-2 MECH 1/2 1 240 P2 32,34 20A-2P 2-#12, 1-#12EG, 1/2"C 2-#12, 1-#12EG, 1/2"C 1 AU 1

10 HW-1 MECH 1.65 1 120 P2 26 20A-1P 2-#12, 1-#12EG, 1/2"C 2-#12, 1-#12EG, 1/2"C 1 AU 1

11 HWRP MECH FRAC 1 120 P2 24 20A-1P 2-#12, 1-#12EG, 1/2"C 2-#12, 1-#12EG, 1/2"C 1 AU 1 1

Receptacle 9020 VA 100.00% 9020 VA

Other 4410 VA 100.00% 4410 VA TOTAL EST. DEMAND: 66 A

Motor 85 VA 75.00% 64 VA TOTAL CONN.: 68 A

Lighting 726 VA 90.00% 653 VA TOTAL EST. DEMAND: 15744 VA

Heating 1650 VA 65.00% 1073 VA TOTAL CONN. LOAD: 16416 VA

HVAC 525 VA 100.00% 525 VA

LOAD CLASSIFICATION CONNECTED LOAD DEMAND FACTOR ESTIMATED DEMAND PANEL TOTALS

TOTAL AMPS: 84 A 53 A

TOTAL LOAD: 10111 VA 6305 VA

41 SPACE -- 1 -- -- 1 -- SPACE 42

39 0.00 0.00 40

ILLEGIBLE - EXISTING 20 A 2

0.00 0.00 2 30 A

AIR COMPRESSOR -

EXISTING

35 0.00 0.00 1 15 A CEILING FANS - EXISTING 36

ILLEGIBLE - EXISTING 20 A 2

0.00 -- 1 -- SPACE 34

31 0.00 -- 1 -- SPACE 32

ILLEGIBLE - EXISTING 50 A 2

0.00 -- 1 -- SPACE 30

27 0.00 0.00 1 20 A OUTLET TRUCK AREA - EXISTING 28

ILLEGIBLE - EXISTING 30 A 2

0.00 0.00 1 20 A OUTLET SHOP NORTH - EXISTING 26

23 SPACE -- 1 -- -- 1 -- SPACE 24

21 ILLEGIBLE - EXISTING 20 A 1 0.00 -- 1 -- SPACE 22

19 ILLEGIBLE - EXISTING 20 A 1 0.00 -- 1 -- SPACE 20

17 #5 BAY DOOR - EXISTING 20 A 1 0.00 -- 1 -- SPACE 18

15 #4 BAY DOOR - EXISTING 20 A 1 0.00 -- 1 -- SPACE 16

13 #3 BAY DOOR - EXISTING 20 A 1 0.00 0.00 1 15 A PUMP LIGHT - EXISTING 14

11 SHOP DOOR OPENER - EXISTING 20 A 1 0.00 0.00 1 20 A PUMPS - ?? - EXISTING 12

9 ILLEGIBLE - EXISTING 15 A 1 0.00 0.00 1 20 A OUTLETS - EXISTING 10

7 LIGHTS - EXISTING 15 A 1 0.00 0.00 1 20 A HEATERS - GARAGE 8

5 HEATER - EAST - EXISTING 20 A 1 0.00 0.00 1 15 A LIGHTS - EXISTING 6

3 GFI OFFICE DOOR - EXISTING 15 A 1 0.00 -- 1 -- SPACE 4

1 SPACE -- 1 -- -- 1 -- SPACE 2

CKT CIRCUIT DESCRIPTION TRIP POLES A (kVA) B (kVA) POLES TRIP CIRCUIT DESCRIPTION CKT

NOTES:

P1 200 A 1Ø, 3W 120/240... Surface 10 NQ Type 1

MCB MLO

NAME LOCATION SOURCE

RATING (AMPS)

PHASE/WIRE VOLTAGE MOUNTING KAIC DESIGN MAKE NEMA TYPE

HINGED TRIM X 200% NEUTRAL SUB-FEED LUGS SPD SIZE:PANELBOARD SCHEDULE SE RATED SUB-FEED BREAKER FEED-THRU LUGS X INTEGRAL SPD

Receptacle 9020 VA 100.00% 9020 VA

Other 4410 VA 100.00% 4410 VA TOTAL EST. DEMAND: 66 A

Motor 85 VA 75.00% 64 VA TOTAL CONN.: 68 A

Lighting 726 VA 90.00% 653 VA TOTAL EST. DEMAND: 15744 VA

Heating 1650 VA 65.00% 1073 VA TOTAL CONN. LOAD: 16416 VA

HVAC 525 VA 100.00% 525 VA

LOAD CLASSIFICATION CONNECTED LOAD DEMAND FACTOR ESTIMATED DEMAND PANEL TOTALS

TOTAL AMPS: 84 A 53 A

TOTAL LOAD: 10111 VA 6305 VA

41 SPACE -- 1 -- 1.15 42

39 SPACE -- 1 -- 1.15

2 20 A HP-3

37 SPACE -- 1 -- 1.00 38

35 SPACE -- 1 -- 1.00

2 20 A HP-1, HP-2

33 SPACE -- 1 -- 0.09 34

31 SPACE -- 1 -- 0.09

2 20 A P-1, P-2

29 SPACE -- 1 -- 0.44 1 20 A ERV-2 30

27 SPACE -- 1 -- 0.11 1 20 A ERV-1 28

25 SPACE -- 1 -- 1.65 1 20 A HW-1 26

23 SPACE -- 1 -- 0.00 1 20 A HWRP 24

21 HIGHWAY SUPER REC 20 A 1 0.90 -- 1 -- SPACE 22

19 TOWN SUPER REC 20 A 1 1.08 -- 1 -- SPACE 20

17 HALL, MECH, KIT REC 20 A 1 0.72 -- 1 -- SPACE 18

15 MEETING REC 20 A 1 0.72 -- 1 -- SPACE 16

13 TOILET REC 20 A 1 0.36 0.00 1 20 A SPARE 14

11 CODE INSPEC REC 20 A 1 1.08 0.00 1 20 A SPARE 12

9 TOWN CLERK REC 20 A 1 1.08 0.00 1 20 A SPARE 10

7 JUDGE REC 20 A 1 0.72 0.00 1 20 A SPARE 8

5 REF REC 20 A 1 1.00 0.00 1 20 A SPARE 6

3 KITCHEN REC 20 A 1 0.36 0.00 1 20 A SPARE 4

1 MICROWAVE 20 A 1 1.00 0.73 1 20 A OFFICE LIGHTS 2

CKT CIRCUIT DESCRIPTION TRIP POLES A (kVA) B (kVA) POLES TRIP CIRCUIT DESCRIPTION CKT

NOTES:

P2 Space 1 P1 225 A 1Ø, 3W 120/240... Surface 10 NQ Type 1

MCB MLO

NAME LOCATION SOURCE

RATING (AMPS)

PHASE/WIRE VOLTAGE MOUNTING KAIC DESIGN MAKE NEMA TYPE

HINGED TRIM X 200% NEUTRAL SUB-FEED LUGS SPD SIZE:PANELBOARD SCHEDULE SE RATED SUB-FEED BREAKER FEED-THRU LUGS INTEGRAL SPD

NO SCALE

ONE-LINE DIAGRAM - ELECTRICAL

GARAGE OFFICE P1

GARAGE EAST SE ATS

PV MODULE (TYP.)

PV AC SERVICE

DISCONNECT

GAS METER

FIBER/DATA SERVICE ENTRANCE

OVERHEAD

P1

INVERTER

TYP. (3)

(E) ATS, METER

PV COMBINER PANEL

11'

11'

90'

CONDUCTOR SCHEDULE

MIN CONDUCTOR SIZES

2 - #10 PV WIRE

2 - #4 THWN-2

TO BE SIZED FOR LOADS ON CIRCUIT

CAT 5

3-#3/0 THWN-2

CIRCUIT

PV SOURCE CIRCUIT

INVERTER OUTPUT

LOAD CIRCUIT

INVERTER SUBPANEL FEEDER

COMMUNICATION

EQUIPMENT GROUND

BOND RACKING WITH #6 AWG

BARE COPPER WHERE NECESSARY

1 - #8 AWG THWN-2

1 - #6 AWG THWN-2

CONDUIT

FREE AIR, WIRE

MANAGEMENT

(1) 2" EMT

(1) 2-1/2" EMT

(1) 1" EMT

ID

EQUIPMENT SCHEDULE

QTY

SQ D

DESCRIPTION

PV MODULE

INVERTER W/ DC DISCONNECT

INVERTER COMBINER PANEL

PV FUSED DISCONNECT

OPTIMIZERS

MANUFACTURER

LONGI

DESCRIPTION

550 WATT BIFACIAL SOLAR MODULE. SEE MODULE

SPECIFICATIONS FOR DETAILS

SEE INVERTER SPECIFICATIONS

SQ D

SOLAREDGE

225A, 240/120V, 1-PHASE, 3 WIRE SERVICE PANEL.

(3) 60A-2P BREAKERS

NEMA 3R PV SYSTEM DISCONNECT FUSED

1EXISTING METER

SAFETY

SWITCH

MODEL

LR5-72HBD-550M

NQ

SE11400H-US

A

B

C

D

E

F

ID

SOLAREDGE 1100W, 2 PV MODULES IN SERIES PER

OPTIMIZER

SOLAREDGE P1100

UTILITY METER. RG&E TO REPLACE WITH

VDER CAPABLE METER.

INVERTER ELECTRICAL SPECIFICATIONS

MANUFACTURER

MODEL

NOMINAL APPARENT POWER AC

FREQUENCY

ENVIRONMENT RATING

MAX INPUT DC VOLTAGE

MPPT INPUT DC VOLTAGE RANGE: MIN

RATED OUTPUT POWER

MAX DC ARRAY STC WATTS

MPPT INPUT DC VOLTAGE RANGE: MAX

SOLAREDGE

SE11400H-US

11.4 kVA, P.F.=1, ADJUSTABLE

11.4 kWAC

NEMA 4X

480 VDC

400 VDC

480 VDC

60 HZ

240/120 VAC

17.65 KW

AC OUTPUT VOLTAGE

NOMINAL AC OUTPUT CURRENT

DC FUSE CONFIGURATION

47.5 A

(3) 30 AMP DC INPUT FUSES

PV MODULE ELECTRICAL SPECIFICATIONS

MANUFACTURER

MODEL

DC POWER NOMINAL

NOMINAL POWER VOLTAGE - VMPP

OPEN CIRCUIT VOLTAGE - VOC

SHORT CIRCUIT CURRENT - ISC

MAXIMUM SYSTEM VOLTAGE

TEMPERATURE COEFFICIENT OF VOC

NOMINAL POWER CURRENT - IMPP

MAX SERIES FUSE

TEMPERATURE COEFFICIENT OF PMAX

LONGI

LR5-72HBD-550M

550 W

41.95 V

49.8 V

13.99 A

1500 VDC

-0.265 %/0C

13.12 A

30 A

-0.34 %/0C

DC PV CIRCUITS

AC CIRCUITS

GROUNDING ELECTRODE CONDUCTOR

CAT 5

LINE TYPE LEGEND

72 MODULES X 550 W = 39.6 KW (DC)

RATED DC SYSTEM SIZE:

11.4 KW RATED INVERTERS X 3 INVERTERS = 34.2 KW (AC)

RATED AC SYSTEM SIZE:

1.

2.

3.

4.

GENERAL NOTES:

ALL EQUIPMENT SHALL BE UL LISTED FOR USE IN SYSTEM

CONFIGURATION.

INSTALLATION SHALL COMPLY WITH NEC 2017 STANDARDS.

LOWEST EXPECTED AMBIENT TEMPERATURE BASED ON ASHRAE

MINIMUM MEAN EXTREME DRY BULB TEMPERATURE IS USED FOR

DC MAXIMUM SYSTEM VOLTAGE CALCULATIONS.

SYSTEM COMPONENTS TO BE LABELED PER NEC STANDARDS.

G

M

POLE MOUNT XFMR

240/120V SECONDARY

(E) NYSEG?

OVHD SERVICE LATERAL

200A

200A/2P

(E) GENERAC SE ATS

(E) UTILITY METER

240/120V

70A/2P

(E) GENERATOR

15kW

PROPANE

GENERAC

60A/2P 60A/2P

(3) 11.4kW INVERTERS

60A/2P

200A PV SYSTEM DISCONNECT

200A FUSES

240/120V 1Ø, 3W

NEMA 3R

PV COMBINER PANEL

SQ D NQ

225A MLO

240/120V 1Ø, 3W

12 MODULES PER STRING

2 MODULES PER OPTIMIZER

2 STRINGS PER INVERTER

1 2

3 4

TYP.TYP. TYP.

LONGI SOLAR MODULE

LR5-72HBD-550M

SOLAREDGE OPTIMIZER

P1100

#10 STRING WIRES (TYP.)

2-#4, 1-#8EG, 2"C

BEHIND-THE-METER CONNECTION

AHEAD OF SE DISCONNECT

PROVIDE JUNCTION BOX

3-#3/0, 1-#6EG, 2-1/2"C

3-#3/0, 1-#6EG, 2-1/2"C

3-#3/0, 1-#6EG, 2-1/2"C

3-#3/0, 1-#6EG, 2-1/2"C

TO NEW P1

REFER TO E-102

TURNER

E N G I N E E R I N G , P C

One Woodbury Boulevard Rochester, NY 14604

585.381.3360

IT IS A VIOLATION OF LAW FOR ANY PERSONS,

UNLESS ACTING UNDER THE DIRECTION OF A

LICENSED PROFESSIONAL ENGINEER, TO ALTER

ANY ITEM ON THIS DOCUMENT IN ANY WAY. ANY

LICENSEE WHO ALTERS THIS DOCUMENT IS

REQUIRED BY LAW TO AFFIX HIS OR HER SEAL

AND THE NOTATION "ALTERED BY", FOLLOWED

BY HIS OR HER SIGNATURE AND A SPECIFIC

DESCRIPTION OF THE ALTERATIONS.

Client

Project

Drawing

Issue Date:

Proj. No.

Sheet

Revisions

Proj. Status:

E-201

SITE PLAN - SOLAR

Project No. 25106

TOWN OF PORTAGE GEO

AND SOLAR

TOWN OF PORTAGE

25106

08/29/2025

9907 CHURCH STREET

HUNT, NY 14846

BID DOCUMENTS

1" = 20'-0"

SITE PLAN - SOLAR

N O

R T

H

NO SCALE

PARTIAL ONE-LINE DIAGRAM - SOLAR

PROJECT LOCATION

42.54, -77.99

TILT ANGLE: 35.4°

MAGNETIC DECLINATION: 10.79°W

ALIGN PANELS TRUE SOUTH

ELEVATE PANELS TO 3FT ABOVE GRADE TO BOTTOM OF PANEL

ROW SPACING NOTE:

ROWS ARE SHOWN AS SPACED 11' ON CENTER. NORTH TWO

ROWS OF PANELS WILL NOT BE SHADED IN SUMMER BUT 40%

SHADED IN WINTER. CONSIDER INCREASING ROW SPACING TO 17'

ON CENTER FOR FULL YEAR-ROUND SUN EXPOSURE.

PHOTOVOLTAIC INVERTER

INVERTER DC INPUT RATINGS

RATED MAX POWER-POINT CURRENT (IMP)

RATED MAX POWER-POINT VOLTAGE (VMP)

MAX SYSTEM VOLTAGE (VOC)

MAX CIRCUIT CURRENT (ISC)

30.5 A

480 V 480 V 45 A

INVERTER AC OUTPUT RATINGS

RATED AC OUTPUT CURRENT

AC VOLTAGE

47.5 A

240/120 VAC

PHOTOVOLTAIC SYSTEM AC

DISCONNECT

AC INPUT RATINGS

RATED AC OUTPUT CURRENT

AC VOLTAGE

PHOTOVOLTAIC POWER SOURCE

200 A

240/120 VAC

PHOTOVOLTAIC SYSTEM EQUIPPED

WITH RAPID SHUTDOWN DEVICE

WARNING

ELECTRIC SHOCK HAZARD

THE DC CONDUCTORS OF THIS PHOTOVOLTAIC

SYSTEM ARE UNGROUNDED AND MAY BE

ENERGIZED

WARNING

ELECTRICAL SHOCK HAZARD DO NOT TOUCH

TERMINALS. TERMINALS ON BOTH THE LINE AND

LOAD SIDES MAY BE ENERGIZED IN THE OPEN

POSITION.

LABEL AND MARKING LEGEND

1 PROVIDE ON EACH INVERTER. (3) TOTAL

PROVIDE ON RACEWAYS AND JUNCTION BOXES ACCORDING

TO NEC 690.31.

PROVIDE ON EACH INVERTER. (3) TOTAL

PROVIDE ON EACH INVERTER. (3) TOTAL

PV SOURCE CIRCUIT "HOME RUNS" SHALL BE LABELED ON

BOTH ENDS AT THE ARRAY AND INVERTER INPUT.

PROVIDE ON INVERTER SUBPANEL AND AT MAIN SERVICE

DISCONNECTING MEANS.

PROVIDE ON INVERTER SUBPANEL.

NOT USED.

PROVIDE ON MAIN SERVICE PANEL.

1-01

WARNING

PV SYSTEM OUTPUT CONNECTION.

DO NOT RELOCATE THIS OVERCURRENT

PROTECTION DEVICE

PER INVERTER TOTAL

47.5 A

240/120 VAC

WARNING

ELECTRIC SHOCK HAZARD

POWER TO THIS SERVICE IS ALSO SUPPLIED BY A

PHOTOVOLTAIC (PV) SYSTEM. PV DISCONNECT IS

LOCATED NEXT TO SERVICE METER AND

DISCONNECT ON EAST EXTERIOR WALL.

TURNER

E N G I N E E R I N G , P C

One Woodbury Boulevard Rochester, NY 14604

585.381.3360

IT IS A VIOLATION OF LAW FOR ANY PERSONS,

UNLESS ACTING UNDER THE DIRECTION OF A

LICENSED PROFESSIONAL ENGINEER, TO ALTER

ANY ITEM ON THIS DOCUMENT IN ANY WAY. ANY

LICENSEE WHO ALTERS THIS DOCUMENT IS

REQUIRED BY LAW TO AFFIX HIS OR HER SEAL

AND THE NOTATION "ALTERED BY", FOLLOWED

BY HIS OR HER SIGNATURE AND A SPECIFIC

DESCRIPTION OF THE ALTERATIONS.

Client

Project

Drawing

Issue Date:

Proj. No.

Sheet

Revisions

Proj. Status:

E-202

SOLAR DETAILS

Project No. 25106

TOWN OF PORTAGE GEO

AND SOLAR

TOWN OF PORTAGE

25106

08/29/2025

9907 CHURCH STREET

HUNT, NY 14846

BID DOCUMENTS

NO SCALE

SOLAR COMMERCIAL SYSTEM EQUIPMENT LABELS

LOAD INFORMATION:

931 MAIN ESTIMATE YEARLY CONSUMPTION: 9787 kWh 966 MAIN ESTIMATE YEARLY CONSUMPTION: 765 kWh OAKLAND RD ESTIMATE YEARLY CONSUMPTION: 890 kWh

TOTAL PRODUCTION: 50.8MWh

% UTILIZATION: 543%

ESTIMATE ANNUAL EXPORT: 47MWh

Sheets
E-001 - ELECTRICAL GENERAL NOTES, SPECIFICATIONS, AND SYMBOLS
E-100 - FLOOR PLAN - ELECTRICAL DEMOLITION
E-101 - FLOOR PLAN - LIGHTING
E-102 - FLOOR PLAN - POWER & SYSTEMS
E-201 - SITE PLAN - SOLAR
E-202 - SOLAR DETAILS

File details come from the government source that posted it. Updated .