25106 - Portage Geo and Solar - Elec Bid Set 25-08-29.pdf
PDF 3 MB Posted
- Attached to
- Town of Portage Town hall renovation
- Solicitation number
- 2130423
- Issued by
- Montgomery County, New York
About this file
This is an electrical bid set and project specification document for the Town of Portage Town Hall Renovation project located in Hunt, New York. The project, designed by Turner Engineering, PC and Hager Engineering Solutions, encompasses a comprehensive interior renovation with new utilities including electrical systems integrated with renewable energy and geothermal heating technologies. The electrical scope includes complete installation of lighting systems, power distribution, receptacles, occupancy sensors, emergency systems, panelboards, and associated controls throughout the facility. The project incorporates a 39.6 kW DC-rated solar photovoltaic system with three 11.4 kW inverters, 72 Longi bifacial solar modules rated at 550 watts each, and a combiner panel with fused disconnect as part of a net-zero energy design. Additional electrical work includes removal and relocation of existing equipment, installation of new branch circuits and panelboards (P1 at 200A and P2 at 225A), LED luminaires of various types (recessed panels, linear over-mirror, surface-mounted, and exit signs), motor starters for HVAC equipment, emergency lighting with battery backup, voice and data outlets, fire alarm systems, and all associated conduit, wiring, and controls. All work must comply with the 2017 National Electrical Code, New York State building codes, and OSHA requirements.
The specification documents establish that all electrical materials, labor, equipment, and services for complete installation are the contractor's responsibility, with stranded copper wire minimum #12 AWG, EMT interior conduit with set-screw fittings, and rigid steel conduit for exterior above-grade applications. Contractor-provided services include obtaining an Underwriters Certificate upon substantial completion, providing engraved laminate plastic nameplates on all major equipment, field-applied vinyl labels on receptacles and circuits, updated panelboard directories, and fire stopping for all floor and wall penetrations per ASTM E814. Equipment specifications mandate Square D or equal panelboards and disconnect switches, Hubbell or equal receptacles and wiring devices in light almond color, Lithonia or Isolite lighting fixtures with specified lumens and color temperatures, and Sensor Switch occupancy sensors with dimming and daylight harvesting capabilities. The project includes demolition notes requiring disconnection and removal of existing electrical equipment, raceways, and wiring unless specifically noted to remain, with field verification of existing conditions required. No incumbent information, pricing terms, set-asides, or contract award dates are specified in these technical documents, which serve as the bid set specifications for electrical contractors responding to the Town of Portage's request for proposals.
View the file
Other files
On GovTribe
Work with this file
- Download the original file
- Contacts named in this file
- Similar government files
- Ask GovTribe AI about this file
Text version
SYMBOL DESCRIPTION
POWER DISTRIBUTION
SURFACE/FLUSH MOUNTED BRANCH
CIRCUIT PANELBOARD. 208Y/120V OR
240/120V. REFER TO PANELBOARD
SCHEDULE
MANUAL MOTOR STARTER OR MOTOR
RATED SWITCH.
NON-FUSED DISCONNECT SWITCH.
ELECTRICAL
DESCRIPTION
DUPLEX RECEPTACLE,
SUBSCRIPTS AS FOLLOWS:
AFI
CR
EP
GFI
H
IG
SS
WP
TR
WR
USB
ARC FAULT INTERRUPTER
CORROSION RESISTANT
EXPLOSION PROOF
GROUND FAULT INTERRUPTER
HOSPITAL GRADE
ISOLATED GROUND
SURGE SUPPRESSION
WEATHER PROOF
TAMPER RESISTANT
WEATHER RESISTANT
UNIVERSAL SERIAL BUS
SYMBOL DESCRIPTION
LIGHTING
SINGLE POLE SWITCH
WALL MOUNTED OCCUPANCY
SENSOR SWITCH
CEILING MOUNTED OCCUPANCY
SENSOR. SUBSCRIPT INDICATES
TYPE
2'X4' RECESSED LUMINAIRE. DESIGNATION
REFERS TO LUMINAIRE SCHEDULE
EMERGENCY REMOTE BATTERY PACK.
DESIGNATION REFERS TO LUMINAIRE
SCHEDULE
SINGLE FACE UNIVERSAL MOUNTED EXIT
SIGN. DESIGNATION REFERS TO
LUMINAIRE SCHEDULE
LA
EM2
X1
LA
SYMBOL LIST
OS-A
THREE-WAY POLE SWITCH
SUBSCRIPT INDICATES QUANTITY OF
SWITCHES. REFER TO LUMINAIRES FOR
SWITCHING DESIGNATIONS
a,b
2'X2' RECESSED LUMINAIRE. DESIGNATION
REFERS TO LUMINAIRE SCHEDULE
LA
JUNCTION BOX
BELL OR BUZZER
DOORBELL OR PUSHBUTTON
E-3
SYMBOL DESCRIPTION
MISCELLANEOUS
REFERENCE TO DRAWING NOTE
REFERENCE TO EQUIPMENT OR
FEEDER NUMBER
DETAIL REFERENCE SYMBOL
SYMBOL DESCRIPTION
LINE STYLES
INDICATES UNDERGROUND TELEPHONE
SPECIAL PURPOSE RECEPTACLE
LIGHTING CONTROL PANEL
LCP
PHOTOCELL
MOTOR. DESIGNATION REFERS TO
ELECTRIC EQUIPMENT AND CONTROL
SCHEDULE
EMERGENCY DUPLEX RECEPTACLE
EMERGENCY BATTERY PACK.
DESIGNATION REFERS TO LUMINAIRE
SCHEDULE
EM1
DUAL FACE UNIVERSAL MOUNTED EXIT
SIGN. DESIGNATION REFERS TO
LUMINAIRE SCHEDULE
X2
LA DOWNLIGHT. DESIGNATION REFERS TO
LUMINAIRE SCHEDULE
INDICATES UNDERGROUND ELECTRIC
INDICATES NEW DEVICE OR EQUIPMENT
INDICATES UNDERGROUND CATV
E
T
CATV
LA POLE MOUNTED LUMINAIRE. DESIGNATION
REFERS TO LUMINAIRE SCHEDULE
SURFACE LUMINAIRE. DESIGNATION
REFERS TO LUMINAIRE SCHEDULE
M
MS
J
DOUBLE DUPLEX RECEPTACLE
EMERGENCY DOUBLE DUPLEX
RECEPTACLE
B
EMERGENCY POWER OFF PUSHBUTTONEPO
120 VOLT CONNECTION TO EQUIPMENT
PC
OS
EXTERIOR WALL MOUNTED LUMINAIRE.
DESIGNATION REFERS TO LUMINAIRE
SCHEDULE
REFERENCE TO DEMOLITION NOTE2
INDICATES EXISTING DEVICE OR EQUIPMENT
TO REMAIN
INDICATES DEVICE OR EQUIPMENT TO BE
REMOVED OR RELOCATED
DIMMING SWITCHD
WALL MOUNTED VACANCY
SENSOR SWITCH
VS
LA
INDICATES CABLE TRAY
SYMBOL
SYMBOL DESCRIPTION
COMMUNICATIONS
SECURITY
EXISTING VOICE/DATA OUTLET.
TV
VOICE/DATA OUTLET. PROVIDE 2-GANG
OUTLET BOX WITH SINGLE GANG MUD
RING AND 1" CONDUIT TO ACCESSIBLE
CEILING SPACE ABOVE.
CATV OUTLET. PROVIDE 2-GANG OUTLET
BOX WITH SINGLE GANG MUD RING AND 1"
CONDUIT TO ACCESSIBLE CEILING SPACE
ABOVE.
TELEPHONE ONLY OUTLET. PROVIDE 2-
GANG OUTLET BOX WITH SINGLE GANG
MUD RING AND 1" CONDUIT TO
ACCESSIBLE CEILING SPACE ABOVE.
SYMBOL DESCRIPTION
2 POST TEL/DATA RACK
CARD READER
DOOR STRIKE
DOOR CONTACT
ACCESS CONTROL PANELACP
DS
DC
CR
FINISHED FLOOR
CEILING
AAB12
AAB13
4" MINIMUM
PROVIDE 3/4" CONDUIT
INSIDE NEW WALL
PROVIDE 4 11/16" SQUARE x 2 1/8"
DEEP BACKBOX WITH SINGLE GANG
MUD RING
PROVIDE 2-GANG BACKBOX
WITH DOUBLE DUPLEX
RECEPTACLE, FLUSH MOUNTED
PROVIDE 1" CONDUIT
WITH PULLSTRING TO
CEILING SPACE
NOTES:
IN LOCATIONS WHERE SIMILAR DEVICES ARE MOUNTED AT THE SAME HEIGHT, DEVICES SHALL BE PROPERLY "GANGED" AND SHALL HAVE A SINGLE
COVER PLATE.
IN LOCATIONS WHERE DIFFERENT DEVICES ARE MOUNTED AT DIFFERENT HEIGHTS WITHIN FOUR FEET OF ONE ANOTHER DEVICES SHALL BE MOUNTED SUCH THAT THEY HAVE A COMMON CENTERLINE. IF THERE ARE THREE OR MORE DEVICES, THE CONTRACTOR SHALL REQUEST A DETAIL FROM THE
ARCHITECT.
1.
2.
FT
P A N E L B
O A R
D
D
IS
C O
N N E C T
T H E R
M O
S T A T O
T
E M
P E R
A T U R
E S
E N S O
R
L
IG
H T S
W
IT
C H
C A R
D A
C C E S S
V O
IC
E /D
A T A O
U T L E T
D U P L E X R
E C E P T A C L E
6'-8" 6'-0" 5'-0"
4'-0" 4'-0" 4'-0" 4'-0" 4'-0"
1'-6" 1'-6" 1'-6"
4'-0"
7'-8"7'-6"
F
IR
E A
L A R
M A U D
IO
/V
IS
U A L
A N D
V
IS
U A L
D E V
IC
E
F
IR
E A
L A R
M P U L L S
T A T
IO
N
W A L L M
O U N T E D
T E L E P H O
N E
D U P L E X R
E C E P T A C L E
M E C H R
O O
M G
A R
A G
E S
C L O
C K
O U T L E T
D E S K T
O P T
E L E P H O
N E
C A T V
O U T L E T
FINISHED
FLOOR
D O
M E
L
IG
H T
4'-0"
A P A R
T M
E N T L
O A D
C E N T E R
4'-0"
M O
T O
R R
A T E D
S W
IT
C H
TURNER
E N G I N E E R I N G , P C
One Woodbury Boulevard Rochester, NY 14604
585.381.3360
IT IS A VIOLATION OF LAW FOR ANY PERSONS,
UNLESS ACTING UNDER THE DIRECTION OF A
LICENSED PROFESSIONAL ENGINEER, TO ALTER
ANY ITEM ON THIS DOCUMENT IN ANY WAY. ANY
LICENSEE WHO ALTERS THIS DOCUMENT IS
REQUIRED BY LAW TO AFFIX HIS OR HER SEAL
AND THE NOTATION "ALTERED BY", FOLLOWED
BY HIS OR HER SIGNATURE AND A SPECIFIC
DESCRIPTION OF THE ALTERATIONS.
Client
Project
Drawing
Issue Date:
Proj. No.
Sheet
Revisions
Proj. Status:
E-001
ELECTRICAL GENERAL
NOTES, SPECIFICATIONS,
AND SYMBOLS
Project No. 25106
TOWN OF PORTAGE GEO
AND SOLAR
TOWN OF PORTAGE
25106
08/29/2025
9907 CHURCH STREET
HUNT, NY 14846
BID DOCUMENTS
ELECTRICAL SPECIFICATIONS
1. PROVIDE ALL LABOR, MATERIALS, EQUIPMENT AND SERVICES TO PERFORM
ALL OPERATIONS REQUIRED FOR THE COMPLETE INSTALLATION AND
RELATED WORK AS SHOWN ON DRAWINGS AND SPECIFIED HEREIN. ELECTRIC
EQUIPMENT SHALL BE INSTALLED IN A NEAT AND WORKMAN LIKE MANNER.
PROVIDE ALL ELECTRICAL EQUIPMENT CONNECTIONS. PROVIDE ALL
REQUIRED SUPPORTS AND ACCESSORIES. INSTALL ALL WORK IN
COMPLIANCE WITH LATEST EDITION OF THE NATIONAL ELECTRICAL CODE,
NFPA-70, NEW YORK STATE UNIFORM FIRE PREVENTION AND BUILDING CODE,
NEW YORK STATE ENERGY CONSERVATION CONSTRUCTION CODE, OSHA
REQUIREMENTS, AND LOCAL ORDINANCES.
2. INSTALL ALL WIRING AND EQUIPMENT IN ACCORDANCE WITH THE 2017
NATIONAL ELECTRICAL CODE.
3. OBTAIN AN UNDERWRITERS CERTIFICATE UPON SUBSTANTIAL COMPLETION.
4. COORDINATE ALL WORK WITH OTHER TRADES.
5. PROVIDE EQUIPMENT IDENTIFICATION NAMEPLATES ON ALL SWITCHBOARDS,
PANELBOARDS, ELECTRICAL EQUIPMENT ENCLOSURES, TRANSFORMERS,
DISCONNECT SWITCHES, AND MOTOR STARTERS. NAMEPLATES SHALL BE
ENGRAVED LAMINATE PLASTIC INDICATING EQUIPMENT NAME, VOLTAGE,
PHASE, AND SOURCE OF POWER.
6. PROVIDE CIRCUIT LABELS ON ALL RECEPTACLES AND DEVICES. LABELS
SHALL BE FIELD-APPLIED VINYL PRINTED STICKERS INDICATING
PANELBOARD NAME AND CIRCUIT NUMBER. LABELS FOR RECEPTACLES
WITHIN OFFICE AREAS SHALL BE ON THE INSIDE OF COVERPLATES.
7. WIRE SHALL BE STRANDED COPPER WITH THHN/THWN INSULATION, MINIMUM
#12 AWG.
8. INTERIOR CONDUIT SHALL BE EMT WITH SET-SCREW FITTINGS.
9. EXTERIOR, ABOVE GRADE CONDUIT SHALL BE RIGID STEEL WITH THREADED
FITTINGS.
10. EXTERIOR, BELOW GRADE CONDUIT SHALL BE PVC, SCHEDULE 80, DIRECT
BURIED.
11. TYPE MC CABLE WITH A SEPARATE INSULATED GROUND IS PERMITTED. IN
INTERIOR, CONCEALED LOCATIONS. SUPPORT CABLE ON MINIMUM 4.5'
CENTERS.
12. ALL HOMERUNS TO PANELBOARDS SHALL BE INSTALLED IN EMT CONDUIT.
TYPE MC CABLE MAY BE USED FROM OUTLET BOXES IN THE CEILING TO
DEVICES AND LUMINAIRES, AND MAY BE RUN HORIZONTALLY IN THE METAL
STUD PARTITIONS.
13. PROVIDE UPDATED TYPE-WRITTEN DIRECTORIES FOR ALL PANELBOARDS
AFFECTED BY THIS PROJECT.
14. ALL EXPOSED WIRING SHALL BE INSTALLED IN CONDUIT OR SURFACE METAL
RACEWAY.
15. WHEREVER POSSIBLE, INSTALL ALL RACEWAYS CONCEALED AND DEVICES
FLUSH MOUNTED. WHERE REQUIRED DUE TO FIELD CONDITIONS, PROVIDE
SURFACE METAL RACEWAY. PAINT TO MATCH EXISTING SURFACES.
16. OUTLET BOXES AND COVERS SHALL BE GALVANIZED STEEL, NOT LESS THAN
1-1/2" DEEP, 4" SQUARE OR OCTAGONAL, WITH KNOCKOUTS. OUTLET BOXES
EXPOSED TO MOISTURE, EXTERIOR, WET OR DAMP LOCATIONS SHALL BE
CADMIUM CAST ALLOY COMPLETE WITH THREADED HUBS AND GASKETED
SCREW FASTENED COVERS. MINIMUM BOX SIZE SHALL BE AS INDICATED IN
ARTICLE 370 OF THE NATIONAL ELECTRIC CODE FOR THE CONDUCTORS AND
DEVICES INSTALLED. MAKE SHALL BE STEEL CITY OR EQUAL.
17. DUPLEX RECEPTACLES SHALL BE CONSTRUCTION GRADE. INTERIOR TYPE
SHALL BE DUPLEX, 20 AMPERE, TWO-POLE, THREE-WIRE, 125 VOLTS AC,
GROUNDING, WITH SIDE AND BACK TERMINAL CONNECTIONS AND SPLITWIRING
LINK, U.L. LISTED, WITH THERMOPLASTIC COVERPLATES. COLOR TO BE LIGHT
ALMOND. MAKE SHALL BE HUBBELL OR EQUAL.
ELECTRICAL SPECIFICATIONS
18. PROVIDE LABELS ON ALL RECEPTACLES INDICATING BRANCH CIRCUIT PANEL
AND CIRCUIT NUMBER.
19. WIRING DEVICES SHALL BE CONSTRUCTION GRADE, LIGHT ALMOND IN
COLOR, WITH THERMOPLASTIC COVERPLATES. MAKE SHALL BE HUBBELL OR
EQUAL.
20. WEATHER RESISTANT DEVICE COVERS SHALL BE UL LISTED WITH THE DEVICE
PLUGGED IN. MAKE SHALL BE HUBBELL OR EQUAL.
21. WALL MOUNTED ANALOG VACANCY SENSORS SHALL BE DUAL TECHNOLOGY
AND INSTALL IN A SINGLE GANG OUTLET BOX. DEVICE SHALL BE EQUIPPED
WITH A SET OF AUXILIARY CONTACTS TO CONTROL ADDITIONAL EQUIPMENT.
WHERE CALLED FOR ON THE PLANS, PROVIDE DUAL INTEGRAL SWITCHES TO
PROVIDE THREE-LEVEL LIGHTING. MAKE SHALL BE SENSOR SWITCH WSXA
PDT SERIES OR APPROVED EQUAL.
22. WALL MOUNTED ANALOG OCCUPANCY SENSOR WITH DIMMING AND ADAPTIVE
DAYLIGHT HARVESTING SHALL BE DUAL TECHNOLOGY AND INSTALL IN A
SINGLE GANG OUTLET BOX. DEVICE SHALL BE EQUIPPED WITH A SET OF
AUXILIARY CONTACTS TO CONTROL ADDITIONAL EQUIPMENT. MAKE SHALL
BE SENSOR SWITCH WSXA PDT D SERIES OR APPROVED EQUAL.
23. WALL MOUNTED DIGITAL VACANCY SENSORS SHALL BE DUAL TECHNOLOGY
AND INSTALL IN A SINGLE GANG OUTLET BOX. DEVICE SHALL BE EQUIPPED
WITH A SET OF AUXILIARY CONTACTS TO CONTROL ADDITIONAL EQUIPMENT.
WHERE CALLED FOR ON THE PLANS, PROVIDE DUAL INTEGRAL SWITCHES TO
PROVIDE THREE-LEVEL LIGHTING. MAKE SHALL BE SENSOR SWITCH nWSXA
PDT SERIES OR APPROVED EQUAL. PROVIDE CAT5 CABLE AS REQUIRED.
24. WALL MOUNTED DIGITAL OCCUPANCY SENSOR WITH DIMMING AND ADAPTIVE
DAYLIGHT HARVESTING SHALL BE DUAL TECHNOLOGY AND INSTALL IN A
SINGLE GANG OUTLET BOX. DEVICE SHALL BE EQUIPPED WITH A SET OF
AUXILIARY CONTACTS TO CONTROL ADDITIONAL EQUIPMENT. MAKE SHALL
BE SENSOR SWITCH nWSXA PDT D SERIES OR APPROVED EQUAL. PROVIDE
CAT5 CABLE AS REQUIRED.
25. OCCUPANCY SENSOR OS-A SHALL BE CEILING MOUNTED ULTRASONIC,
SUITABLE FOR SPACES UP TO 1000 SQUARE FEET. MAKE SHALL BE SENSOR
SWITCH nCM PDT 9 SERIES OR EQUAL.
26. PANELBOARDS SHALL HAVE ALUMINUM BUS WITH PLUG-ON CIRCUIT BREAKERS
AND HINGED TRIM. COORDINATE TRIM TYPE IN THE FIELD. MAKE SHALL BE
SQUARE D OR EQUAL.
27. DISCONNECT SWITCHES SHALL BE HEAVY DUTY WITH COPPER BUS. KNIVES
SHALL BE VISIBLE IN THE OPEN POSITION. MAKE SHALL BE SQUARE D OR
EQUAL.
28. MANUAL MOTOR STARTERS AND MOTOR RATED SWITCHES SHALL BE 277
VOLT, 30 AMPERE RATED, IN A NEMA 1 ENCLOSURE WITH A H-O-A SELECTOR
SWITCH AND A RELAY FOR REMOTE CONTROL OF THE EQUIPMENT IN THE
AUTO MODE. PROVIDE OVERLOADS AS REQUIRED. MAKE SHALL BE SQUARE
D CLASS 2510 OR EQUAL.
29. ALL LUMINAIRES SHALL BE CONNECTED WITH THREE #12 CONDUCTORS IN A
FLEXIBLE CABLE WHIP, 6'-0" MAXIMUM IN LENGTH. CABLE SHALL BE
INSTALLED SUCH THAT FIXTURES IN LAY-IN CEILING SYSTEM MAY BE
RELOCATED ONE-TILE IN ANY DIRECTION WITHOUT REWIRING. ALL LUMINAIRE
WHIPS SHALL BE CONNECTED TO A JUNCTION BOX. LUMINAIRES SHALL NOT
BE CONNECTED TOGETHER IN A DAISY CHAIN MANNER. SECURELY SUPPORT
ALL CONDUITS AND OUTLET BOXES FROM STRUCTURAL MEMBERS, OUTLET
BOXES SHALL NOT BE SUPPORTED BY CONDUIT, AND INDEPENDENTLY
SUPPORT LUMINAIRES FROM BUILDING STRUCTURE.
30. PROVIDE FIRE STOPPING FOR ALL PENETRATIONS THROUGH FLOORS, WALLS
AND ALL OTHER RELATED ASSEMBLIES. PROVIDE FIRE STOPPING SYSTEMS
IN ACCORDANCE WITH ASTM E814.
ELECTRICAL GENERAL DEMOLITION NOTES
A. NOTES APPLY TO ALL DEMOLITION ELECTRICAL DRAWINGS.
B. DISCONNECT AND REMOVE ALL EXISTING ELECTRICAL EQUIPMENT, WIRING, AND
RACEWAYS UNLESS NOTED TO REMAIN AND TO BE RELOCATED.
C. DISCONNECT AND REMOVE ALL EMPTY AND ABANDONED RACEWAYS UNLESS
NOTED OTHERWISE. CUT FLUSH WITH FLOOR WHERE APPLICABLE AND PLUG WITH
GROUT.
D. COORDINATE ALL REMOVAL WORK WITH OTHER TRADES. PROVIDE ALL WIRING
AND CONNECTIONS REQUIRED TO MAINTAIN BRANCH CIRCUIT OR SPECIAL
SYSTEMS CIRCUIT CONTINUITY TO DEVICES AND EQUIPMENT TO REMAIN, WHETHER
LOCATED WITHIN OR OUTSIDE OF THE PROJECT BOUNDARY.
E. PARTIAL BRANCH CIRCUIT WIRING DENOTING EXISTING CIRCUITING OR CONTROL
IS SHOWN FOR REFERENCE ONLY, AND IS NOT INTENDED TO ILLUSTRATE
COMPLETE WIRING SYSTEM. FIELD VERIFY EXISTING WIRING AND CONNECTIONS.
F. "ETR" ADJACENT TO A DEVICE, FIXTURE, OR PIECE OF EQUIPMENT INDICATES
ITEM SHALL REMAIN. MAINTAIN EXISTING ELECTRICAL CONNECTIONS UNLESS
OTHERWISE NOTED.
G. "ERL" ADJACENT TO A DEVICE, FIXTURE, OR PIECE OF EQUIPMENT INDICATES
EXISTING ITEM SHALL BE RELOCATED. DISCONNECT AND REMOVE, REINSTALL
AT NEW LOCATION AND RECONNECT ITEM AS REQUIRED.
ELECTRICAL GENERAL NOTES
A. GENERAL NOTES APPLY TO ALL ELECTRICAL DRAWINGS.
B. PROVIDE UPDATED TYPE WRITTEN PANELBOARD SCHEDULES FOR ALL PANELS
USED IN THIS PROJECT.
C. INSTALL ALL DEVICES FLUSH IN WALL CONSTRUCTION.
D. PROVIDE BLANK COVERPLATES ON ALL EXISTING AND NEW UNUSED OUTLET
BOXES.
E. COORDINATE ALL CONDUIT RUNS WITH OTHER TRADES PRIOR TO ROUGH-IN.
RELOCATE ANY CONDUITS AS NECESSARY TO PERMIT INSTALLATION OF
DUCTWORK, PIPING OR ANY SUPPORTS.
F. PROVIDE CUTTING, PATCHING TO MATCH, AND FIRE SEAL AS REQUIRED WHERE
EXISTING COMMUNICATION OR ELECTRICAL WORK HAS BEEN REMOVED AND
WHERE NEW WORK IS INSTALLED. COORDINATE WITH GENERAL CONTRACTOR.
G. REMOVE AND REINSTALL EXISTING CEILING TILES AS REQUIRED FOR
INSTALLATION OF BRANCH CIRCUIT WIRING AND CONDUIT. REPLACE ALL
DAMAGED TILES WITH MATCHING TILES.
H. RUN ALL WIRING CONCEALED IN WALL. CUT AND PATCH TO MATCH DRYWALL AS
REQUIRED. MINIMIZE USE OF SURFACE METAL RACEWAY.
I. COORDINATE MOUNTING HEIGHTS OF DEVICES WITH ARCHITECTURAL ELEVATIONS
AND OWNER PRIOR TO ROUGH-IN.
J. ALL DATA WIRING BY SPECTRUM. COORDINATE DEVICE LOCATION AND
QUANTITIES IN FIELD WITH OWNER PRIOR TO ROUGHING IN CONDUITS AND BOXES.
NO SCALE
FLUSH VOICE/DATA OUTLET INSTALLATION DETAIL
NO SCALE
TYPICAL DEVICE MOUNTING ELEVATIONS
TOWN CLERK
TO REMAIN
VAULT
TO REMAIN
HALL
BATH ROOM
KITCHEN
JUDGE'S
OFFICE
MEETING
ROOM
HW REF SINK
ST
PT
M
JJ
T
T
M
M S
S
48" 48"
60"
48"
48"
48"
44"
TO PANEL
SE CABLE
PULLBOX
LC
44"
44"
48"
EBB
(E)
EBB
1 11
6 6
(E) MDP
TURNER
E N G I N E E R I N G , P C
One Woodbury Boulevard Rochester, NY 14604
585.381.3360
IT IS A VIOLATION OF LAW FOR ANY PERSONS,
UNLESS ACTING UNDER THE DIRECTION OF A
LICENSED PROFESSIONAL ENGINEER, TO ALTER
ANY ITEM ON THIS DOCUMENT IN ANY WAY. ANY
LICENSEE WHO ALTERS THIS DOCUMENT IS
REQUIRED BY LAW TO AFFIX HIS OR HER SEAL
AND THE NOTATION "ALTERED BY", FOLLOWED
BY HIS OR HER SIGNATURE AND A SPECIFIC
DESCRIPTION OF THE ALTERATIONS.
Client
Project
Drawing
Issue Date:
Proj. No.
Sheet
Revisions
Proj. Status:
E-100
FLOOR PLAN -
ELECTRICAL DEMOLITION
Project No. 25106
TOWN OF PORTAGE GEO
AND SOLAR
TOWN OF PORTAGE
25106
08/29/2025
9907 CHURCH STREET
HUNT, NY 14846
BID DOCUMENTS
1/4" = 1'-0"
FIRST FLOOR WEST DEMOLITION PLAN - ELECTRICAL
N O
R T
H
ELECTRICAL DEMOLITION NOTES
1 DISCONNECT AND REMOVE LUMINAIRES IN THIS AREA. EXISTING WIRING
TO REMAIN AND BE REUSED.
2 DISCONNECT AND REMOVE LUMINAIRE. REMOVE WIRING BACK TO
NEAREST ACTIVE LUMINAIRE TO REMAIN. MAINTAIN CONTINUITY OF
CIRCUIT.
3 DISCONNECT AND REMOVE SWITCH. REMOVE WIRING BACK TO
LUMINAIRE.
4 DISCONNECT AND REMOVE FAN. REMOVE CONTROL. REMOVE WIRING
BACK TO SOURCE.
5 DISCONNECT MECHANICAL EQUIPMENT BEING REMOVED BY OTHERS.
REMOVE WIRING BACK TO SOURCE.
6 DISCONNECT AND REMOVE RECEPTACLE. REMOVE WIRING BACK TO
NEAREST ACTIVE DEVICE TO REMAIN. MAINTAIN CONTINUITY OF CIRCUIT.
7 DISCONNECT AND REMOVE OVERHEAD DOOR MOTOR AND ALL
ASSOCIATED DEVICES. REMOVE WIRING BACK TO SOURCE.
8 DISCONNECT AND REMOVE SWITCH. REMOVE SURFACE MOUNTED
OUTLET BOX AND RACEWAY. EXISTING WIRING TO REMAIN AND BE
REUSED.
9 DISCONNECT AND REMOVE PANEL. REMOVE ALL BRANCH WIRING TO
OFFICE AREA. SOME GARAGE CIRCUITS MAY BE EXISTING TO REMAIN.
TAG ALL REMAINING CIRCUITS FOR REUSE. REMOVE PANEL FEEDER
BACK TO SOURCE.
10 DISCONENCT AND REMOVE PANELBOARD. TAG ALL BRANCH CIRCUIT
WIRING FOR REUSE.
1/4" = 1'-0"
FIRST FLOOR EAST DEMOLITION PLAN - ELECTRICAL
REF
V S D
V S D
V S D
OS OS
VS
OS-B
OS-A
OS-A
OS-A
OS-A
D
OS-A
D
JUDGE
HALL
TLT.TLT.MECH
KITCHEN
HIGHWAY
SUPERINTENDENT
HALL
VAULT
TOWN
CLERK
MEETING
ROOM
CODE
INSPECTOR
TOWN
SUPERVISOR
(ETR)
LD
LA1
LA1
LA2LA2
LA2
LA2
LA1
LA2
LA1
LA2
LA2
LA2
LA2
LA2
LA2 LA2
LA2
LA2
LA2
LC LC
EM1
EM1
EM1
EM1
EM1
EM1
EM1
EM1
X1
X1 1
X1
1X1
LA2
LA2
LA2
LA2
P2
RELOCATE, EXTEND
CIRCUITS, RECONNECT
LA1 LA1
P2/2
P2/2
TURNER
E N G I N E E R I N G , P C
One Woodbury Boulevard Rochester, NY 14604
585.381.3360
IT IS A VIOLATION OF LAW FOR ANY PERSONS,
UNLESS ACTING UNDER THE DIRECTION OF A
LICENSED PROFESSIONAL ENGINEER, TO ALTER
ANY ITEM ON THIS DOCUMENT IN ANY WAY. ANY
LICENSEE WHO ALTERS THIS DOCUMENT IS
REQUIRED BY LAW TO AFFIX HIS OR HER SEAL
AND THE NOTATION "ALTERED BY", FOLLOWED
BY HIS OR HER SIGNATURE AND A SPECIFIC
DESCRIPTION OF THE ALTERATIONS.
Client
Project
Drawing
Issue Date:
Proj. No.
Sheet
Revisions
Proj. Status:
E-101
FLOOR PLAN - LIGHTING
Project No. 25106
TOWN OF PORTAGE GEO
AND SOLAR
TOWN OF PORTAGE
25106
08/29/2025
9907 CHURCH STREET
HUNT, NY 14846
BID DOCUMENTS
1/4" = 1'-0"
FIRST FLOOR PLAN - LIGHTING
N O
R T
H
LIGHTING DRAWING NOTES
1 PROVIDE EXIT SIGN. CONNECT TO A 20A/1P CIRCUIT
BREAKER IN PANEL **, CIRCUIT ** USING 2-#12, 1-#12EG IN
½"C. LOCK CIRCUIT BREAKER IN THE "ON" POSITION.
2 PROVIDE EMERGENCY BATTERY BACK-UP LUMINAIRE.
CONNECT TO AREA LIGHTING BRANCH CIRCUIT AHEAD OF
ALL SWITCHING.
3 PROVIDE OLD WORK BOX IN EXISTING WALL. FISH WALL
FROM ABOVE ACCESSIBLE CEILING SPACE WITH ¾"
FLEXIBLE METAL CONDUIT AND PROVIDE EMERGENCY
BATTERY BACK-UP LUMINAIRE. CONNECT TO AREA
LIGHTING BRANCH CIRCUIT AHEAD OF ALL SWITCHING.
4 PROVIDE EXTERIOR LUMINAIRE TO MATCH EXISTING
BUILDING WALL MOUNTED LUMINAIRES. CONNECT TO
EXISTING EXTERIOR LIGHTING BRANCH CIRCUIT AND
CONTROL.
#LIGHT FIXTURE SCHEDULE
TYPE DESCRIPTION LUMENS CCT/CRI WATTAGE (VA) VOLTAGE
DESIGN MAKE ACCEPTABLE
MANUFACTURERMANUFACTURER MODEL NO.
EM1 WALL MOUNTED, TWO-HEAD LED EMERGENCY BATTERY PACK WITH WHITE FINISH AND SELF
DIAGNOSTICS AND TESTING
250 - 4 VA 120 ISOLITE LIGHTING RL2LED-4-WH-MBC-SD APPROVED EQUAL
LA1 2'X2' FLAT PANEL LED LUMINAIRE WITH SWITCHABLE LUMENS SET AT LOW, SWITCHABLE COLOR
TEMPERATURE SET AT 3500K, PRISTMATIC ACRYLIC LENS AND WHITE HOUSING.
2489 3500K/80CRI 21 VA 120 LITHONIA LIGHTING CPX 2X2 AL07 80CRI SWW7 A12 APPROVED EQUAL
LA2 2'X2' FLAT PANEL LED LUMINAIRE WITH SWITCHABLE LUMENS SET AT MEDIUM, SWITCHABLE
COLOR TEMPERATURE SET AT 3500K, PRISTMATIC ACRYLIC LENS AND WHITE HOUSING.
3302 3500K/80CRI 28 VA 120 LITHONIA LIGHTING CPX 2X2 AL07 80CRI SWW7 A12 APPROVED EQUAL
LC 25" LINEAR LED OVER MIRROR LUMINAIRE WITH MATTE WHITE ACRYLIC LENS AND SATIN NICKEL
FINISH.
1300 3500K/90CRI 18 VA 120 LITHONIA LIGHTING FMVCSL 24IN MVOLT 30K 90CRI BN
M6
APPROVED EQUAL
LD 4' SURFACE MOUNTED LED LUMINAIRE WITH SELECTABLE LUMENS SET AT 4000 LUMENS,
SELECTABLE COLOR TEMPERATURE SET AT 3500K, ACRYLIC LENS, AND WHITE HOUSING.
4732 3500K, 80CRI 36 VA 120 LITHONIA LIGHTING CSS L48 AL03 MVOLT SWW3 80CRI APPROVED EQUAL
X1 SINGLE FACED UNIVERSAL MOUNT LED EXIT SIGN WITH WHITE THERMOPLASTIC HOUSING, RED
LETTERS, REMOVABLE CHEVRONS, AND BATTERY BACK UP, AND SELF DIAGNOSTICS AND
TESTING.
0 - 4 VA 120 ISOLITE LIGHTING RL-EM-R-U-WH-MTEB-SD APPROVED EQUAL
REF
T
S
MS
M S
MS
MS
M S
MS
JUDGE
HALL
TLT.
MECH
KITCHEN
HIGHWAY
SUPERINTENDENT
HALL
VAULT
TOWN
CLERK
MEETING
ROOMCODE
INSPECTOR
TOWN
SUPERVISOR
(ETR)
48"
46"
GFI
46"
GFI
46"
GFI
46"
48"
GFI
GFI
WP
P2/1
P2/3
P2/5
P2/17
P2/19
HP-2
ERV-2
ERV-1
HP-1
HP-3
HW-1
HWRP
M
M
M
M M
M M
P2
P1 P2/7
P2/15
P2/9
P2/11
P2/21
48"
GFI
48"
GFI
P2/13
GFI
WP
M
M
P-1 P-2
7 10
INVERTER
TYP. OF (3)
PV COMBINER PANEL
(E) METER
PV DISCONNECT
(E) ATS
(4) MOTOR RATED SWITCHES
MOTOR RATED SWITCH
MANUAL MOTOR STARTER
MANUAL MOTOR STARTER WITH RELAY
MAGNETIC STARTER
COMBINATION MAGNETIC STARTER
VARIABLE FREQUENCY DRIVE
COMBINATION TWO SPEED MAGNETIC STARTER
COMBINATION REDUCED VOLTAGE MAGNETIC STARTER
DUPLEX CONTROLLER WITH ALTERNATION CIRCUIT
PACKAGED CONTROL UNIT
H-O-A SELECTOR SWITCH IN COVER
PILOT LIGHT IN COVER
REMOTE START-STOP PUSHBUTTONS
FIRE ALARM FAN SHUTDOWN
LINE-VOLTAGE THERMOSTAT
MOTOR STARTER/CONTROLLER NOTES:
1.
2.
3.
4.
5.
6.
7.
8.
9.
10.
11.
12.
13.
14.
15.
EXTEND 120 VOLT CIRCUIT FROM HWRP-1 AND CONNECT
AQUASTAT AND TIME SWITCH.
NOTES:
1.
G
M
POLE MOUNT XFMR
240/120V SECONDARY
(E) NYSEG?
OVHD SERVICE LATERAL
200A
200A/2P
(E) GENERAC SE ATS
UTILITY METER
RG&E TO REPLACE WITH INTERVAL
METER FOR VDER CREDITING
240/120V
200A/2P
P1
SQ D NQ
200A MCB
240/120V
70A/2P
(E) GENERATOR
15kW
PROPANE
GENERAC
200A PV SYSTEM DISCONNECT
200A FUSES
240/120V 1Ø, 3W
NEMA 3R
BEHIND-THE-METER CONNECTION
AHEAD OF SE DISCONNECT
PROVIDE JUNCTION BOX
3-#3/0, 1-#6EG, 2"C
3-#3/0, 1-#6EG, 2"C
3-#3/0, 1-#6EG, 2"C
3-#3/0, 1-#6EG, 2"C
TO SOLAR COMBINER PANEL
REFER TO DETAIL ON E103
3-#3/0, 1-#6EG, 2"C
P2
SQ D NQ
225A MLO
240/120V
FEED-THRU LUGS
TURNER
E N G I N E E R I N G , P C
One Woodbury Boulevard Rochester, NY 14604
585.381.3360
IT IS A VIOLATION OF LAW FOR ANY PERSONS,
UNLESS ACTING UNDER THE DIRECTION OF A
LICENSED PROFESSIONAL ENGINEER, TO ALTER
ANY ITEM ON THIS DOCUMENT IN ANY WAY. ANY
LICENSEE WHO ALTERS THIS DOCUMENT IS
REQUIRED BY LAW TO AFFIX HIS OR HER SEAL
AND THE NOTATION "ALTERED BY", FOLLOWED
BY HIS OR HER SIGNATURE AND A SPECIFIC
DESCRIPTION OF THE ALTERATIONS.
Client
Project
Drawing
Issue Date:
Proj. No.
Sheet
Revisions
Proj. Status:
E-102
FLOOR PLAN - POWER &
SYSTEMS
Project No. 25106
TOWN OF PORTAGE GEO
AND SOLAR
TOWN OF PORTAGE
25106
08/29/2025
9907 CHURCH STREET
HUNT, NY 14846
BID DOCUMENTS
1/8" = 1'-0"
FIRST FLOOR PLAN - POWER & SYSTEMS
N O
R T
H
ELECTRICAL DRAWING NOTES
1 PROVIDE NEW PANELBOARD. EXTEND ANY IN-USE EXISTING
CIRCUITS AND RECONNECT TO PANEL. COORDINATE
LOCATION IN FIELD WITH OWNER.
2 PROVIDE OLD WORK BOX IN EXISTING WALL. CUT AND
PATCH AS REQUIRED.
ELECTRIC EQUIPMENT SCHEDULE
ITEM
NO. NAME
ROOM
LOCATION HP KW PH VOLTS PANEL
CIRCUIT
NUMBER
CIRCUIT
BREAKER
WIRING FROM PANEL
TO CONTROL UNIT
WIRING FROM CONTROL
UNIT TO EQUIPMENT
DISCONNECT SWITCH DISCONNECT SWITCH MOTOR STARTER/
CONTROLLER NOTES
CONTROLLER
LOCATION
NEMA
RATING NOTESSWITCH AMPS FUSE SIZE
1 ERV-1 HALL 0.1 1 120 P2 28 20A-1P 2-#12, 1-#12EG, 1/2"C 2-#12, 1-#12EG, 1/2"C 1 AU 1
2 ERV-2 MEETING 0.4 1 120 P2 30 20A-1P 2-#12, 1-#12EG, 1/2"C 2-#12, 1-#12EG, 1/2"C 1 AU 1
3 HP-1 HALL 0.9 1 240 P2 36,38 20A-2P 2-#12, 1-#12EG, 1/2"C 2-#12, 1-#12EG, 1/2"C 1 AU 1
4 HP-2 KITCHEN 1.1 1 240 P2 36,38 20A-2P 2-#12, 1-#12EG, 1/2"C 2-#12, 1-#12EG, 1/2"C 1 AU 1
5 HP-3 MEETING 2.3 1 240 P2 40,42 20A-2P 2-#12, 1-#12EG, 1/2"C 2-#12, 1-#12EG, 1/2"C 1 AU 1
6 P-1 MECH 1/2 1 240 P2 32,34 20A-2P 2-#12, 1-#12EG, 1/2"C 2-#12, 1-#12EG, 1/2"C 1 AU 1
7 P-2 MECH 1/2 1 240 P2 32,34 20A-2P 2-#12, 1-#12EG, 1/2"C 2-#12, 1-#12EG, 1/2"C 1 AU 1
10 HW-1 MECH 1.65 1 120 P2 26 20A-1P 2-#12, 1-#12EG, 1/2"C 2-#12, 1-#12EG, 1/2"C 1 AU 1
11 HWRP MECH FRAC 1 120 P2 24 20A-1P 2-#12, 1-#12EG, 1/2"C 2-#12, 1-#12EG, 1/2"C 1 AU 1 1
Receptacle 9020 VA 100.00% 9020 VA
Other 4410 VA 100.00% 4410 VA TOTAL EST. DEMAND: 66 A
Motor 85 VA 75.00% 64 VA TOTAL CONN.: 68 A
Lighting 726 VA 90.00% 653 VA TOTAL EST. DEMAND: 15744 VA
Heating 1650 VA 65.00% 1073 VA TOTAL CONN. LOAD: 16416 VA
HVAC 525 VA 100.00% 525 VA
LOAD CLASSIFICATION CONNECTED LOAD DEMAND FACTOR ESTIMATED DEMAND PANEL TOTALS
TOTAL AMPS: 84 A 53 A
TOTAL LOAD: 10111 VA 6305 VA
41 SPACE -- 1 -- -- 1 -- SPACE 42
39 0.00 0.00 40
ILLEGIBLE - EXISTING 20 A 2
0.00 0.00 2 30 A
AIR COMPRESSOR -
EXISTING
35 0.00 0.00 1 15 A CEILING FANS - EXISTING 36
ILLEGIBLE - EXISTING 20 A 2
0.00 -- 1 -- SPACE 34
31 0.00 -- 1 -- SPACE 32
ILLEGIBLE - EXISTING 50 A 2
0.00 -- 1 -- SPACE 30
27 0.00 0.00 1 20 A OUTLET TRUCK AREA - EXISTING 28
ILLEGIBLE - EXISTING 30 A 2
0.00 0.00 1 20 A OUTLET SHOP NORTH - EXISTING 26
23 SPACE -- 1 -- -- 1 -- SPACE 24
21 ILLEGIBLE - EXISTING 20 A 1 0.00 -- 1 -- SPACE 22
19 ILLEGIBLE - EXISTING 20 A 1 0.00 -- 1 -- SPACE 20
17 #5 BAY DOOR - EXISTING 20 A 1 0.00 -- 1 -- SPACE 18
15 #4 BAY DOOR - EXISTING 20 A 1 0.00 -- 1 -- SPACE 16
13 #3 BAY DOOR - EXISTING 20 A 1 0.00 0.00 1 15 A PUMP LIGHT - EXISTING 14
11 SHOP DOOR OPENER - EXISTING 20 A 1 0.00 0.00 1 20 A PUMPS - ?? - EXISTING 12
9 ILLEGIBLE - EXISTING 15 A 1 0.00 0.00 1 20 A OUTLETS - EXISTING 10
7 LIGHTS - EXISTING 15 A 1 0.00 0.00 1 20 A HEATERS - GARAGE 8
5 HEATER - EAST - EXISTING 20 A 1 0.00 0.00 1 15 A LIGHTS - EXISTING 6
3 GFI OFFICE DOOR - EXISTING 15 A 1 0.00 -- 1 -- SPACE 4
1 SPACE -- 1 -- -- 1 -- SPACE 2
CKT CIRCUIT DESCRIPTION TRIP POLES A (kVA) B (kVA) POLES TRIP CIRCUIT DESCRIPTION CKT
NOTES:
P1 200 A 1Ø, 3W 120/240... Surface 10 NQ Type 1
MCB MLO
NAME LOCATION SOURCE
RATING (AMPS)
PHASE/WIRE VOLTAGE MOUNTING KAIC DESIGN MAKE NEMA TYPE
HINGED TRIM X 200% NEUTRAL SUB-FEED LUGS SPD SIZE:PANELBOARD SCHEDULE SE RATED SUB-FEED BREAKER FEED-THRU LUGS X INTEGRAL SPD
Receptacle 9020 VA 100.00% 9020 VA
Other 4410 VA 100.00% 4410 VA TOTAL EST. DEMAND: 66 A
Motor 85 VA 75.00% 64 VA TOTAL CONN.: 68 A
Lighting 726 VA 90.00% 653 VA TOTAL EST. DEMAND: 15744 VA
Heating 1650 VA 65.00% 1073 VA TOTAL CONN. LOAD: 16416 VA
HVAC 525 VA 100.00% 525 VA
LOAD CLASSIFICATION CONNECTED LOAD DEMAND FACTOR ESTIMATED DEMAND PANEL TOTALS
TOTAL AMPS: 84 A 53 A
TOTAL LOAD: 10111 VA 6305 VA
41 SPACE -- 1 -- 1.15 42
39 SPACE -- 1 -- 1.15
2 20 A HP-3
37 SPACE -- 1 -- 1.00 38
35 SPACE -- 1 -- 1.00
2 20 A HP-1, HP-2
33 SPACE -- 1 -- 0.09 34
31 SPACE -- 1 -- 0.09
2 20 A P-1, P-2
29 SPACE -- 1 -- 0.44 1 20 A ERV-2 30
27 SPACE -- 1 -- 0.11 1 20 A ERV-1 28
25 SPACE -- 1 -- 1.65 1 20 A HW-1 26
23 SPACE -- 1 -- 0.00 1 20 A HWRP 24
21 HIGHWAY SUPER REC 20 A 1 0.90 -- 1 -- SPACE 22
19 TOWN SUPER REC 20 A 1 1.08 -- 1 -- SPACE 20
17 HALL, MECH, KIT REC 20 A 1 0.72 -- 1 -- SPACE 18
15 MEETING REC 20 A 1 0.72 -- 1 -- SPACE 16
13 TOILET REC 20 A 1 0.36 0.00 1 20 A SPARE 14
11 CODE INSPEC REC 20 A 1 1.08 0.00 1 20 A SPARE 12
9 TOWN CLERK REC 20 A 1 1.08 0.00 1 20 A SPARE 10
7 JUDGE REC 20 A 1 0.72 0.00 1 20 A SPARE 8
5 REF REC 20 A 1 1.00 0.00 1 20 A SPARE 6
3 KITCHEN REC 20 A 1 0.36 0.00 1 20 A SPARE 4
1 MICROWAVE 20 A 1 1.00 0.73 1 20 A OFFICE LIGHTS 2
CKT CIRCUIT DESCRIPTION TRIP POLES A (kVA) B (kVA) POLES TRIP CIRCUIT DESCRIPTION CKT
NOTES:
P2 Space 1 P1 225 A 1Ø, 3W 120/240... Surface 10 NQ Type 1
MCB MLO
NAME LOCATION SOURCE
RATING (AMPS)
PHASE/WIRE VOLTAGE MOUNTING KAIC DESIGN MAKE NEMA TYPE
HINGED TRIM X 200% NEUTRAL SUB-FEED LUGS SPD SIZE:PANELBOARD SCHEDULE SE RATED SUB-FEED BREAKER FEED-THRU LUGS INTEGRAL SPD
NO SCALE
ONE-LINE DIAGRAM - ELECTRICAL
GARAGE OFFICE P1
GARAGE EAST SE ATS
PV MODULE (TYP.)
PV AC SERVICE
DISCONNECT
GAS METER
FIBER/DATA SERVICE ENTRANCE
OVERHEAD
P1
INVERTER
TYP. (3)
(E) ATS, METER
PV COMBINER PANEL
11'
11'
90'
CONDUCTOR SCHEDULE
MIN CONDUCTOR SIZES
2 - #10 PV WIRE
2 - #4 THWN-2
TO BE SIZED FOR LOADS ON CIRCUIT
CAT 5
3-#3/0 THWN-2
CIRCUIT
PV SOURCE CIRCUIT
INVERTER OUTPUT
LOAD CIRCUIT
INVERTER SUBPANEL FEEDER
COMMUNICATION
EQUIPMENT GROUND
BOND RACKING WITH #6 AWG
BARE COPPER WHERE NECESSARY
1 - #8 AWG THWN-2
1 - #6 AWG THWN-2
CONDUIT
FREE AIR, WIRE
MANAGEMENT
(1) 2" EMT
(1) 2-1/2" EMT
(1) 1" EMT
ID
EQUIPMENT SCHEDULE
QTY
SQ D
DESCRIPTION
PV MODULE
INVERTER W/ DC DISCONNECT
INVERTER COMBINER PANEL
PV FUSED DISCONNECT
OPTIMIZERS
MANUFACTURER
LONGI
DESCRIPTION
550 WATT BIFACIAL SOLAR MODULE. SEE MODULE
SPECIFICATIONS FOR DETAILS
SEE INVERTER SPECIFICATIONS
SQ D
SOLAREDGE
225A, 240/120V, 1-PHASE, 3 WIRE SERVICE PANEL.
(3) 60A-2P BREAKERS
NEMA 3R PV SYSTEM DISCONNECT FUSED
1EXISTING METER
SAFETY
SWITCH
MODEL
LR5-72HBD-550M
NQ
SE11400H-US
A
B
C
D
E
F
ID
SOLAREDGE 1100W, 2 PV MODULES IN SERIES PER
OPTIMIZER
SOLAREDGE P1100
UTILITY METER. RG&E TO REPLACE WITH
VDER CAPABLE METER.
INVERTER ELECTRICAL SPECIFICATIONS
MANUFACTURER
MODEL
NOMINAL APPARENT POWER AC
FREQUENCY
ENVIRONMENT RATING
MAX INPUT DC VOLTAGE
MPPT INPUT DC VOLTAGE RANGE: MIN
RATED OUTPUT POWER
MAX DC ARRAY STC WATTS
MPPT INPUT DC VOLTAGE RANGE: MAX
SOLAREDGE
SE11400H-US
11.4 kVA, P.F.=1, ADJUSTABLE
11.4 kWAC
NEMA 4X
480 VDC
400 VDC
480 VDC
60 HZ
240/120 VAC
17.65 KW
AC OUTPUT VOLTAGE
NOMINAL AC OUTPUT CURRENT
DC FUSE CONFIGURATION
47.5 A
(3) 30 AMP DC INPUT FUSES
PV MODULE ELECTRICAL SPECIFICATIONS
MANUFACTURER
MODEL
DC POWER NOMINAL
NOMINAL POWER VOLTAGE - VMPP
OPEN CIRCUIT VOLTAGE - VOC
SHORT CIRCUIT CURRENT - ISC
MAXIMUM SYSTEM VOLTAGE
TEMPERATURE COEFFICIENT OF VOC
NOMINAL POWER CURRENT - IMPP
MAX SERIES FUSE
TEMPERATURE COEFFICIENT OF PMAX
LONGI
LR5-72HBD-550M
550 W
41.95 V
49.8 V
13.99 A
1500 VDC
-0.265 %/0C
13.12 A
30 A
-0.34 %/0C
DC PV CIRCUITS
AC CIRCUITS
GROUNDING ELECTRODE CONDUCTOR
CAT 5
LINE TYPE LEGEND
72 MODULES X 550 W = 39.6 KW (DC)
RATED DC SYSTEM SIZE:
11.4 KW RATED INVERTERS X 3 INVERTERS = 34.2 KW (AC)
RATED AC SYSTEM SIZE:
1.
2.
3.
4.
GENERAL NOTES:
ALL EQUIPMENT SHALL BE UL LISTED FOR USE IN SYSTEM
CONFIGURATION.
INSTALLATION SHALL COMPLY WITH NEC 2017 STANDARDS.
LOWEST EXPECTED AMBIENT TEMPERATURE BASED ON ASHRAE
MINIMUM MEAN EXTREME DRY BULB TEMPERATURE IS USED FOR
DC MAXIMUM SYSTEM VOLTAGE CALCULATIONS.
SYSTEM COMPONENTS TO BE LABELED PER NEC STANDARDS.
G
M
POLE MOUNT XFMR
240/120V SECONDARY
(E) NYSEG?
OVHD SERVICE LATERAL
200A
200A/2P
(E) GENERAC SE ATS
(E) UTILITY METER
240/120V
70A/2P
(E) GENERATOR
15kW
PROPANE
GENERAC
60A/2P 60A/2P
(3) 11.4kW INVERTERS
60A/2P
200A PV SYSTEM DISCONNECT
200A FUSES
240/120V 1Ø, 3W
NEMA 3R
PV COMBINER PANEL
SQ D NQ
225A MLO
240/120V 1Ø, 3W
12 MODULES PER STRING
2 MODULES PER OPTIMIZER
2 STRINGS PER INVERTER
1 2
3 4
TYP.TYP. TYP.
LONGI SOLAR MODULE
LR5-72HBD-550M
SOLAREDGE OPTIMIZER
P1100
#10 STRING WIRES (TYP.)
2-#4, 1-#8EG, 2"C
BEHIND-THE-METER CONNECTION
AHEAD OF SE DISCONNECT
PROVIDE JUNCTION BOX
3-#3/0, 1-#6EG, 2-1/2"C
3-#3/0, 1-#6EG, 2-1/2"C
3-#3/0, 1-#6EG, 2-1/2"C
3-#3/0, 1-#6EG, 2-1/2"C
TO NEW P1
REFER TO E-102
TURNER
E N G I N E E R I N G , P C
One Woodbury Boulevard Rochester, NY 14604
585.381.3360
IT IS A VIOLATION OF LAW FOR ANY PERSONS,
UNLESS ACTING UNDER THE DIRECTION OF A
LICENSED PROFESSIONAL ENGINEER, TO ALTER
ANY ITEM ON THIS DOCUMENT IN ANY WAY. ANY
LICENSEE WHO ALTERS THIS DOCUMENT IS
REQUIRED BY LAW TO AFFIX HIS OR HER SEAL
AND THE NOTATION "ALTERED BY", FOLLOWED
BY HIS OR HER SIGNATURE AND A SPECIFIC
DESCRIPTION OF THE ALTERATIONS.
Client
Project
Drawing
Issue Date:
Proj. No.
Sheet
Revisions
Proj. Status:
E-201
SITE PLAN - SOLAR
Project No. 25106
TOWN OF PORTAGE GEO
AND SOLAR
TOWN OF PORTAGE
25106
08/29/2025
9907 CHURCH STREET
HUNT, NY 14846
BID DOCUMENTS
1" = 20'-0"
SITE PLAN - SOLAR
N O
R T
H
NO SCALE
PARTIAL ONE-LINE DIAGRAM - SOLAR
PROJECT LOCATION
42.54, -77.99
TILT ANGLE: 35.4°
MAGNETIC DECLINATION: 10.79°W
ALIGN PANELS TRUE SOUTH
ELEVATE PANELS TO 3FT ABOVE GRADE TO BOTTOM OF PANEL
ROW SPACING NOTE:
ROWS ARE SHOWN AS SPACED 11' ON CENTER. NORTH TWO
ROWS OF PANELS WILL NOT BE SHADED IN SUMMER BUT 40%
SHADED IN WINTER. CONSIDER INCREASING ROW SPACING TO 17'
ON CENTER FOR FULL YEAR-ROUND SUN EXPOSURE.
PHOTOVOLTAIC INVERTER
INVERTER DC INPUT RATINGS
RATED MAX POWER-POINT CURRENT (IMP)
RATED MAX POWER-POINT VOLTAGE (VMP)
MAX SYSTEM VOLTAGE (VOC)
MAX CIRCUIT CURRENT (ISC)
30.5 A
480 V 480 V 45 A
INVERTER AC OUTPUT RATINGS
RATED AC OUTPUT CURRENT
AC VOLTAGE
47.5 A
240/120 VAC
PHOTOVOLTAIC SYSTEM AC
DISCONNECT
AC INPUT RATINGS
RATED AC OUTPUT CURRENT
AC VOLTAGE
PHOTOVOLTAIC POWER SOURCE
200 A
240/120 VAC
PHOTOVOLTAIC SYSTEM EQUIPPED
WITH RAPID SHUTDOWN DEVICE
WARNING
ELECTRIC SHOCK HAZARD
THE DC CONDUCTORS OF THIS PHOTOVOLTAIC
SYSTEM ARE UNGROUNDED AND MAY BE
ENERGIZED
WARNING
ELECTRICAL SHOCK HAZARD DO NOT TOUCH
TERMINALS. TERMINALS ON BOTH THE LINE AND
LOAD SIDES MAY BE ENERGIZED IN THE OPEN
POSITION.
LABEL AND MARKING LEGEND
1 PROVIDE ON EACH INVERTER. (3) TOTAL
PROVIDE ON RACEWAYS AND JUNCTION BOXES ACCORDING
TO NEC 690.31.
PROVIDE ON EACH INVERTER. (3) TOTAL
PROVIDE ON EACH INVERTER. (3) TOTAL
PV SOURCE CIRCUIT "HOME RUNS" SHALL BE LABELED ON
BOTH ENDS AT THE ARRAY AND INVERTER INPUT.
PROVIDE ON INVERTER SUBPANEL AND AT MAIN SERVICE
DISCONNECTING MEANS.
PROVIDE ON INVERTER SUBPANEL.
NOT USED.
PROVIDE ON MAIN SERVICE PANEL.
1-01
WARNING
PV SYSTEM OUTPUT CONNECTION.
DO NOT RELOCATE THIS OVERCURRENT
PROTECTION DEVICE
PER INVERTER TOTAL
47.5 A
240/120 VAC
WARNING
ELECTRIC SHOCK HAZARD
POWER TO THIS SERVICE IS ALSO SUPPLIED BY A
PHOTOVOLTAIC (PV) SYSTEM. PV DISCONNECT IS
LOCATED NEXT TO SERVICE METER AND
DISCONNECT ON EAST EXTERIOR WALL.
TURNER
E N G I N E E R I N G , P C
One Woodbury Boulevard Rochester, NY 14604
585.381.3360
IT IS A VIOLATION OF LAW FOR ANY PERSONS,
UNLESS ACTING UNDER THE DIRECTION OF A
LICENSED PROFESSIONAL ENGINEER, TO ALTER
ANY ITEM ON THIS DOCUMENT IN ANY WAY. ANY
LICENSEE WHO ALTERS THIS DOCUMENT IS
REQUIRED BY LAW TO AFFIX HIS OR HER SEAL
AND THE NOTATION "ALTERED BY", FOLLOWED
BY HIS OR HER SIGNATURE AND A SPECIFIC
DESCRIPTION OF THE ALTERATIONS.
Client
Project
Drawing
Issue Date:
Proj. No.
Sheet
Revisions
Proj. Status:
E-202
SOLAR DETAILS
Project No. 25106
TOWN OF PORTAGE GEO
AND SOLAR
TOWN OF PORTAGE
25106
08/29/2025
9907 CHURCH STREET
HUNT, NY 14846
BID DOCUMENTS
NO SCALE
SOLAR COMMERCIAL SYSTEM EQUIPMENT LABELS
LOAD INFORMATION:
931 MAIN ESTIMATE YEARLY CONSUMPTION: 9787 kWh 966 MAIN ESTIMATE YEARLY CONSUMPTION: 765 kWh OAKLAND RD ESTIMATE YEARLY CONSUMPTION: 890 kWh
TOTAL PRODUCTION: 50.8MWh
% UTILIZATION: 543%
ESTIMATE ANNUAL EXPORT: 47MWh
| Sheets |
| E-001 - ELECTRICAL GENERAL NOTES, SPECIFICATIONS, AND SYMBOLS |
| E-100 - FLOOR PLAN - ELECTRICAL DEMOLITION |
| E-101 - FLOOR PLAN - LIGHTING |
| E-102 - FLOOR PLAN - POWER & SYSTEMS |
| E-201 - SITE PLAN - SOLAR |
| E-202 - SOLAR DETAILS |
File details come from the government source that posted it. Updated .