These construction documents are for the Los Angeles National Cemetery Maintenance Facility project, prepared for the Department of Veterans Affairs National Cemetery Administration. The plans detail a comprehensive site redevelopment including demolition of existing structures, utilities, and landscaping, followed by construction of new facilities including an administration building, maintenance building, and covered vehicle storage area. The site plan indicates multiple key components: removal of existing asphalt, concrete, buildings, retaining walls, and vegetation; installation of new utility infrastructure including water lines, sanitary sewer, storm drainage, and electrical systems; and grading and paving for a new maintenance complex. The documents include detailed demolition, utility, grading, site, and drainage plans with specific technical specifications for excavation, concrete work, utility connections, and site restoration, with a project scale suggesting a significant infrastructure upgrade for the national cemetery's maintenance operations.
View the file
Other files
Show all 23
On GovTribe
Work with this file
- Download the original file
- Contacts named in this file
- Similar government files
- Ask GovTribe AI about this file
Text version
370.360
IE
373.820
IE
378.900
TG B
379.150
TG
379.020
TG
378.750
TG E
378.820
TG
379.080
TG 5.2 DIP
379.580
TC B
379.420
INLET B
379.520
INLET E
8" DIA CYPRESS
24" DIA EUCALYPTUS
24" DIA EUCALYPTUS
12" DIA EUCALYPTUS
18" DIA EUCALYPTUS
12" DIA EUCALYPTUS
6" DIA EUCALYPTUS
36" DIA EUCALYPTUS
12" DIA EUCALYPTUS
6" DIA PEPPER TREE
6" DIA EUCALYPTUS
8" DIA EUCALYPTUS
12" DIA SPINELESS YUCCA
12" MULTI TRUNK EUCALYPTUS
24" DIA EUCALYPTUS
36" DIA EUCALYPTUS
36" DIA EUCALYPTUS
48" DIA EUCALYPTUS
12" MULTI TRUNK EUCALYPTUS
36" DIA EUCALYPTUS
24" DIA EUCALYPTUS
12" DIA EUCALYPTUS
24" DIA EUCALYPTUS
36" DIA EUCALYPTUS
24" DIA EUCALYPTUS
36" DIA EUCALYPTUS
8" DIA CYPRESS 8" DIA CYPRESS
X
X
X
X
X
X
X
X
X
X
X
0 10 20
1 INCH = 10 FEET
1. SAW CUT AND REMOVE EXISTING ASPHALT PAVING.
2. REMOVE REINFORCED CONCRETE PAVING AND
MISCELLANEOUS FLATWORK.
3. REMOVE EXISTING GRAVEL PARKING AREA.
4. REMOVE EXISTING CONCRETE WASH BAY AND ALL
APPURTENANCES.
5. REMOVE FLAMMABLE STORAGE BUILDING.
6. REMOVE C.M.U. / STONE BUILDING.
7. DEMOLISH AND REMOVE EXISTING MAINTENANCE
BUILDING AND ASSOCIATED FOUNDATIONS.
8. NOT USED.
9. REMOVE C.M.U. STONE WALL.
10. REMOVE EXISTING RAILROAD TIE RETAINING WALL.
11. REMOVE EXISTING C.M.U. RETAINING WALLS.
12. REMOVE RAILROAD TIE PLANTER.
13. REMOVE BRUSH AND VEGETATION AS NEEDED FOR
EXCAVATION.
14. REMOVE EXISTING TREE, STUMP AND ASSOCIATED ROOT
MASS.
15. REMOVE EXISTING TREE. STUMP AND ROOT MASS TO
REMAIN, SEE GENERAL NOTES BELOW.
16. REMOVE EXISTING MOW CURB.
17. PRESERVE EXISTING STORAGE BUILDING PER
ARCHITECTURAL PLANS.
Project Number
Building Number
Drawing Number
Project Title
Location
Issue Date Checked Drawn
Drawing Title
Approved:
VA FORM 08 - 6231
A
BID DOCUMENT
SUBMITTAL
N/A
National Cemetery Administration
Design and Construction Service
U.S. Department of Veterans Affairs
B
C
D
E
F
A
B
C
D
E
F
21 4 5 6 7 8 9 10
PhaseARCHITECT/ENGINEER OF RECORD STAMPCONSULTANT
321 4 5 6 7 8 9 10
LOS ANGELES NATIONAL CEMETERY
CONSTRUCT MAINTENANCE FACILITY
Los Angeles, CA
898CM3034
N/A Project Director
5/24/2023Revisions: Date: Sheet of 95
VCI Project Management Construction Management Engineering Juan Kays
Department of Veterans Affairs, NCA
Phone: 202.632.5057 Email: juan.kays@va.gov
1331 17TH STREET SUITE 605
DENVER, COLORADO 80202
PHONE: (720) 439-4700
WEBSITE: www.dci-engineers.com
CIVIL / STRUCTURAL
JD Engineering, PC 371 Zimmerman Lane Hamilton, MT 59840 Phone: (406) 218 - 9980
720.491.7559; Sean Fitzpatrick
56 LOUIS PRIMA DRIVE, SUITE B, COVINGTON, LA 70433 SF JV
EXISTING STORAGE BUILDING
(SEE OTHER PLANS FOR
LIMITS OF DEMOLITION)
EXISTING MAINTENANCE BUILDING
(TO BE DEMOLISHED)
EXISTING VEHICLE
WASH AREA
(TO BE REMOVED)
AMIENS AVENUE
SOISSONS AVENUE
KEYED NOTES
DEMOLITION PLAN - SITE
CD101
GENERAL NOTES:
1. SEE ELECTRICAL, MECHANICAL, LANDSCAPE,
ARCHITECTURAL AND STRUCTURAL DEMOLITION PLANS
FOR ADDITIONAL DEMOLITION REQUIREMENTS.
2. CONTRACTOR SHALL PRESERVE AND PROTECT THE
EXISTING ENTRY GATE.
3. CONTRACTOR SHALL PRESERVE AND PROTECT ALL
EXISTING LANDSCAPING AND IRRIGATION.
4. CONTRACTOR SHALL REPAIR ALL DAMAGED TURF WITH
IMPORTED SOIL AND SOD PER TURF RENOVATION SPECIES
TO THE SATISFACTION OF THE COR AT NO ADDITIONAL
COST TO THE GOVERNMENT.
LEGEND AND SYMBOLS
EX. CONTOUR MAJOR
EX. CONTOUR MINOR
EX. CURB & GUTTER
EX. SIDEWALK
EX. TREE (TYP.)
EX. MANHOLE
EX. UTILITY BOX
EX. C.M.U. RETAINING WALL
GRAVEL PARKING REMOVAL
EX. CHAIN LINK FENCING
DEMO CHAIN LINK FENCING
SAW CUT ASPHALT
ASPHALT REMOVAL
CONCRETE REMOVAL
X
*SEE SURVEY SHEETS FOR EXISTING CONDITIONS LEGEND
EX. GATE
7 7
15 15
COBBLESTONE WALL
DEMO COBBLESTONE WALL
PRESERVE AND PROTECT
LIMITS OF DISTURBANCE
TREE AND STUMP REMOVAL
TREE REMOVAL
START WALL
REMOVAL
END WALL
REMOVAL
TREE REMOVAL NOTES:
1. ALL TREE STUMPS TO REMAIN SHALL BE CUT NO HIGHER
THAN 1' ABOVE GRADE.
2. FOR TREE STUMPS TO REMAIN, CONTRACTOR SHALL
INSTALL *GROW MORE STUMP REMOVER (OR APPROVED
EQUAL) PER MANUFACTURER'S PRINTED INSTRUCTIONS.
3. FOR TREE STUMPS TO BE REMOVED OUTSIDE OF THE
LIMITS OF DISTURBANCE, THE CONTRACTOR SHALL REPAIR
ALL DISTURBED AREAS TO MATCH THE ADJACENT
LANDSCAPING AT NO ADDITIONAL COST TO THE
GOVERNMENT.
4. CONTRACTOR SHALL REPAIR ALL DAMAGED VEGETATION
OUTSIDE OF THE LIMITS OF DISTURBANCE TO THE
SATISFACTION OF THE COR AT NO ADDITIONAL COST TO
THE GOVERNMENT.
No. 44593
PROFESSIONAL
REGISTERED
JORDAN D. VANDERMEE
RENG INEER
05/24/2023
370.360
IE
373.820
IE
378.900
TG B
379.150
TG
379.020
TG
378.750
TG E
378.820
TG
379.080
TG 5.2 DIP
379.580
TC B
379.420
INLET B
379.520
INLET E
8" DIA CYPRESS
24" DIA EUCALYPTUS
24" DIA EUCALYPTUS
12" DIA EUCALYPTUS
18" DIA EUCALYPTUS
12" DIA EUCALYPTUS
6" DIA EUCALYPTUS
36" DIA EUCALYPTUS
12" DIA EUCALYPTUS
6" DIA PEPPER TREE
6" DIA EUCALYPTUS
8" DIA EUCALYPTUS
12" DIA SPINELESS YUCCA
12" MULTI TRUNK EUCALYPTUS
24" DIA EUCALYPTUS
36" DIA EUCALYPTUS
36" DIA EUCALYPTUS
48" DIA EUCALYPTUS
12" MULTI TRUNK EUCALYPTUS
36" DIA EUCALYPTUS
24" DIA EUCALYPTUS
12" DIA EUCALYPTUS
24" DIA EUCALYPTUS
36" DIA EUCALYPTUS
24" DIA EUCALYPTUS
36" DIA EUCALYPTUS
8" DIA CYPRESS 8" DIA CYPRESS
X
X
X
X
X
X
X
X
X
X
X
0 10 20
1 INCH = 10 FEET
Project Number
Building Number
Drawing Number
Project Title
Location
Issue Date Checked Drawn
Drawing Title
Approved:
VA FORM 08 - 6231
A
BID DOCUMENT
SUBMITTAL
N/A
National Cemetery Administration
Design and Construction Service
U.S. Department of Veterans Affairs
B
C
D
E
F
A
B
C
D
E
F
21 4 5 6 7 8 9 10
PhaseARCHITECT/ENGINEER OF RECORD STAMPCONSULTANT
321 4 5 6 7 8 9 10
LOS ANGELES NATIONAL CEMETERY
CONSTRUCT MAINTENANCE FACILITY
Los Angeles, CA
898CM3034
N/A Project Director
5/24/2023Revisions: Date: Sheet of 95
VCI Project Management Construction Management Engineering Juan Kays
Department of Veterans Affairs, NCA
Phone: 202.632.5057 Email: juan.kays@va.gov
1331 17TH STREET SUITE 605
DENVER, COLORADO 80202
PHONE: (720) 439-4700
WEBSITE: www.dci-engineers.com
CIVIL / STRUCTURAL
JD Engineering, PC 371 Zimmerman Lane Hamilton, MT 59840 Phone: (406) 218 - 9980
720.491.7559; Sean Fitzpatrick
56 LOUIS PRIMA DRIVE, SUITE B, COVINGTON, LA 70433 SF JV
DEMOLITION PLAN - UTILITIES
CD102
SOISSONS AVENUE
1. REMOVE EXISTING WATER LINE.
2. REMOVE EXISTING SANITARY SEWER.
3. REMOVE EXISTING HOSE BIB.
4. REMOVE EXISTING WATER VALVE.
5. REMOVE EXISTING CLEANOUT.
6. REMOVE EXISTING DRAINAGE INLET AND ASSOCIATED
PIPING.
7. REMOVE ALL DRAINAGE/SEWER LINES ASSOCIATED WITH
THE EXISTING WASH BAY.
8. REMOVE EXISTING WATER STORAGE TANK AND ALL
ASSOCIATED PIPING.
9. RELOCATE 500 GALLON FUEL TANK.
10. REMOVE EXISTING FUEL TANK AND ALL ASSOCIATED
APPURTENANCES.
KEYED NOTES
GENERAL NOTES:
1. SEE ELECTRICAL, MECHANICAL, LANDSCAPE,
ARCHITECTURAL AND STRUCTURAL DEMOLITION
PLANS FOR ADDITIONAL DEMOLITION REQUIREMENTS.
2. CONTRACTOR SHALL REMOVE THE EXISTING POTABLE
WATER DISTRIBUTION LINE FROM THE EXISTING
MAINTENANCE YARD TO THE NEAREST VALVE AT NO
ADDITIONAL COST TO THE GOVERNMENT.
2.1. CONTRACTOR SHALL BID THE REMOVAL OF 125 L.F.
OF WATER DISTRIBUTION LINE.
2.2. CONTRACTOR SHALL FIELD VERIFY WATER LINE
CONNECTION POINT PRIOR TO CONSTRUCTION.
3. CONTRACTOR SHALL REPAIR ALL DAMAGED TURF WITH
IMPORTED SOIL AND SOD PER TURF RENOVATION
SPECIES TO THE SATISFACTION OF THE COR AT NO
ADDITIONAL COST TO THE GOVERNMENT AND MODIFY
ALL IMPACTED IRRIGATION HEADS AS DIRECTED BY
COR.
4. THE CONTRACTOR SHALL CONFIRM WITH CEMETERY
WHICH FUEL TANK IS TO BE REMOVED AND WHICH IS
TO BE RELOCATED.
LEGEND AND SYMBOLS
EX. CONTOUR MAJOR
EX. CONTOUR MINOR
EX. CURB & GUTTER
EX. SIDEWALK
EX. TREE (TYP.)
EX. MANHOLE
EX. UTILITY BOX
EX. C.M.U. RETAINING WALL
EX. CHAIN LINK FENCING
DEMO SEWER LINE
*SEE SURVEY SHEETS FOR EXISTING CONDITIONS LEGEND
EX. GATE
COBBLESTONE WALL
DEMO WATER LINE
RENOVATED BRICK STORAGE BUILDING DEMOLITION NOTES:
1. CONTRACTOR SHALL REMOVE ALL SANITARY SEWER
SERVICE LINES CONNECTED TO THE BUILDING UP TO THE
EXISTING FOUNDATION.
1.1. CONTRACTOR SHALL FILL WITH CONCRETE SLURRY
AND ABANDON IN PLACE ALL SANITARY SEWER
SERVICE LINES UNDERNEATH THE EXISTING
FOUNDATION.
2. CONTRACTOR SHALL REMOVE ALL WATER SERVICE LINES
CONNECTED TO THE BUILDING UP TO THE EXISTING
FOUNDATION.
2.1. CONTRACTOR SHALL ABANDON IN PLACE ALL WATER
SERVICE LINES UNDERNEATH THE EXISTING
FOUNDATION.
No. 44593
PROFESSIONAL
REGISTERED
JORDAN D. VANDERMEE
6.00'
8.00'
10.00'
10.00'
24.00'
24.00'
50.00'
8.00'
12.00'
9.57'
9.75'
9.75'
.5
7'
.0
0'
8.
.8 1'
.7
4'
.8
1'
.1
7' 22.00'
20.05'
.0
0'
9.14'
9.
3.50'
2.48'
5.
5.50'
X
X
X
X
X
X
X
X
RENOVATED BRICK
STORAGE BUILDING
MAINTENANCE VEHICLE
PARKING
EMPLOYEE PARKING
VEHICLE WASH AREA
AMIENS AVENUE
SOISSONS AVENUE
CO
CO
10.00'TYP.
Project Number
Building Number
Drawing Number
Project Title
Location
Issue Date Checked Drawn
Drawing Title
Approved:
VA FORM 08 - 6231
A
BID DOCUMENT
SUBMITTAL
N/A
National Cemetery Administration
Design and Construction Service
U.S. Department of Veterans Affairs
B
C
D
E
F
A
B
C
D
E
F
21 4 5 6 7 8 9 10
PhaseARCHITECT/ENGINEER OF RECORD STAMPCONSULTANT
321 4 5 6 7 8 9 10
LOS ANGELES NATIONAL CEMETERY
CONSTRUCT MAINTENANCE FACILITY
Los Angeles, CA
898CM3034
N/A Project Director
5/24/2023Revisions: Date: Sheet of 95
VCI Project Management Construction Management Engineering Juan Kays
Department of Veterans Affairs, NCA
Phone: 202.632.5057 Email: juan.kays@va.gov
1331 17TH STREET SUITE 605
DENVER, COLORADO 80202
PHONE: (720) 439-4700
WEBSITE: www.dci-engineers.com
CIVIL / STRUCTURAL
JD Engineering, PC 371 Zimmerman Lane Hamilton, MT 59840 Phone: (406) 218 - 9980
720.491.7559; Sean Fitzpatrick
56 LOUIS PRIMA DRIVE, SUITE B, COVINGTON, LA 70433 SF JV
1. 4' WIDE VALLEY GUTTER, SEE DETAIL F2/C-501.
2. ROLLED TYPE CURB AND GUTTER, TRANSITION FROM
VALLEY TYPE TO SPILL TYPE OVER 1', SEE DETAIL
D2/C-501.
3. STANDARD CURB AND GUTTER, SEE DETAIL B5/C-501.
4. 5" WIDE, WHITE PARKING LOT STRIPING, SEE
SPECIFICATIONS.
5. DRAINAGE STRUCTURE, SEE SHEET C-103.
6. SANITARY SEWER STRUCTURE AND OR SEPARATOR,
SEE SHEET C-102.
7. LANDSCAPE CURB, SEE DETAIL F5/C-501.
8. C.M.U. RETAINING WALL, SEE SHEET S-301.
9. ASPHALT PAVEMENT, SEE DETAIL A2/C-501.
10. CONCRETE PAVEMENT, SEE DETAIL F8/C-501.
11. RAILROAD TIE RETAINING WALL, SEE DETAIL F8/C-504 &
GENERAL NOTES BELOW.
12. FUEL TANK PAD, SEE DETAIL F5/C-504.
13. RELOCATED 500 GALLON ABOVE GROUND FUEL TANK.
14. REMOVABLE BOLLARD, SEE DETAIL D5/C-504.
NEW ADMINISTRATION
BUILDING
NE
W
M
AI
NT
EN
AN
CE
BU
IL
DI
NG
NEW COVERED VEHICLE
STORAGE
0 10 20
1 INCH = 10 FEET
Project Number
Building Number
Drawing Number
Project Title
Location
Issue Date Checked Drawn
Drawing Title
Approved:
VA FORM 08 - 6231
A
BID DOCUMENT
SUBMITTAL
N/A
National Cemetery Administration
Design and Construction Service
U.S. Department of Veterans Affairs
B
C
D
E
F
A
B
C
D
E
F
21 4 5 6 7 8 9 10
PhaseARCHITECT/ENGINEER OF RECORD STAMPCONSULTANT
321 4 5 6 7 8 9 10
LOS ANGELES NATIONAL CEMETERY
CONSTRUCT MAINTENANCE FACILITY
Los Angeles, CA
898CM3034
N/A Project Director
5/24/2023Revisions: Date: Sheet of 95
VCI Project Management Construction Management Engineering Juan Kays
Department of Veterans Affairs, NCA
Phone: 202.632.5057 Email: juan.kays@va.gov
1331 17TH STREET SUITE 605
DENVER, COLORADO 80202
PHONE: (720) 439-4700
WEBSITE: www.dci-engineers.com
CIVIL / STRUCTURAL
JD Engineering, PC 371 Zimmerman Lane Hamilton, MT 59840 Phone: (406) 218 - 9980
720.491.7559; Sean Fitzpatrick
56 LOUIS PRIMA DRIVE, SUITE B, COVINGTON, LA 70433 SF JV
SITE PLAN
C-101
KEYED NOTES
GENERAL NOTES:
1. CONTRACTOR SHALL PLACE A NON-DOWELED
EXPANSION JOINT AROUND THE PERIMETER OF THE
CONCRETE PAVING.
2. CONTRACTOR SHALL PLACE A DOWELED EXPANSION
JOINT AROUND THE PERIMETER OF THE VALLEY
GUTTER.
3. CONTRACTOR SHALL PROVIDE A JOINTING PLAN FOR
APPROVAL BY THE COR 60 DAYS PRIOR TO THE
PLACEMENT OF CONCRETE.
4. CONTRACTOR SHALL FOLD NEW RAILROAD TIES INTO
THE EXISTING RAILROAD TIE RETAINING WALL.
4.1. RAILROAD TIES SHALL HAVE AN OIL-BASED
CREOSOTE TREATMENT.
5. CONTRACTOR SHALL MATCH EXISTING GRADES ALONG
AMIENS AVE.
6. CONTRACTOR SHALL TERMINATE LANDSCAPE CURB AT
ALL UTILITY BOXES.
LEGEND AND SYMBOLS
EX. CONTOUR MAJOR
EX. CONTOUR MINOR
EX. CURB & GUTTER
EX. SIDEWALK
EX. TREE (TYP.)
EX. MANHOLE
EX. UTILITY BOX
EX. C.M.U. RETAINING WALL
EX. CHAIN LINK FENCING
*SEE SURVEY SHEETS FOR EXISTING CONDITIONS LEGEND
EX. GATE
ASPHALT PAVING
CONCRETE PAVING
.0
0'
5.00' TYP.
4.00'
TYP.
1.00'
TYP.
1.00'
TYP.
4.00'
No. 44593
PROFESSIONAL
REGISTERED
JORDAN D. VANDERMEE
X
X
X
X
X
X
X
CO
STA:3+64
STA:0+00
STA:1+00
ST
A:
2+
ST
A:
3+
STA:0+33
CO
STA:0+00
STA:1+00
ST
A:
2+
ST
A:
3+
ST
A:
3+
1.5 W
1.5 W
1.5 W
1.5 W
1.5 W
1.5 W
STRM DOG HOUSE
EX SSMH
STRM JB
SS AD #6 (TYPE 1)
SSMH #2
SSMH #1
320 GALLON INTERCEPTOR
SS CO #2
SS CO #1
STRM AD #5 (TYPE 1)
STRM GI #2 (TYPE 2)
STRM GI #3 (TYPE 1)
STRM AD #4 (TYPE 2)
1,500 GALLON INTERCEPTOR
STRM GI #1 (TYPE 1)
387 388 389
STA:0+49
STA:0+00
STRM AD #5 (TYPE 2)
0 10 20
1 INCH = 10 FEET
1. 1" WATER LINE.
2. 1.5" WATER LINE MANIFOLD.
3. 1" GATE VALVE, SEE DETAIL B6/C-503.
4. WALL MOUNTED 34" HOSE BIB, F5/C-503.
5. 4" SANITARY SEWER.
6. 6" SANITARY SEWER.
7. 8" SANITARY SEWER.
8. SANITARY SEWER CLEANOUT, SEE DETAIL D9/C-503.
9. SANITARY SEWER MANHOLE, SEE DETAIL E9/C-502.
10. 1,500 GALLON SAND-OIL INTERCEPTOR, SEE DETAIL
E7/C-202.
11. 8" PVC STORM DRAIN.
12. 12" PVC STORM DRAIN.
13. 18" PVC STORM DRAIN.
14. STORM DRAIN GRATED INLET, SEE DETAIL B2/C-502.
15. STORM DRAIN AREA DRAIN WITH 4' CONCRETE COLLAR,
SEE DETAIL E2 & E5/C-502.
16. STORM DRAIN JUNCTION BOX, SEE DETAIL B6/C-502.
17. 4" PERFORATED PVC, SEE DETAIL B2/C-503.
18. 320 GALLON SAND-OIL INTERCEPTOR, SEE DETAIL
E7/C-202.
19. WALL MOUNTED ELECTRIC PRESSURE WASHER, SEE
NOTES BELOW.
KEYED NOTES
GENERAL NOTES:
1. HORIZONTAL AND VERTICAL LOCATIONS OF EXISTING
SANITARY SEWER AND STORM DRAIN LINES ARE
APPROXIMATED BASED ON AVAILABLE RECORD DATA
AND FIELD OBSERVATIONS. PROPOSED SANITARY
SEWER LINE LOCATIONS AND INVERTS ARE BASED ON
THE AVAILABLE DATA. THE CONTRACTOR IS TO VERIFY
THE LOCATIONS OF ALL EXISTING UTILITIES, INCLUDING
SANITARY SEWER, AND IS TO NOTIFY THE ENGINEER
OF ANY DISCREPANCIES BETWEEN AVAILABLE DATA
AND AS-BUILT CONDITIONS.
2. CONTRACTOR SHALL BID AN ADDITIONAL 125 L.F. OF
1.5 INCH WATER DISTRIBUTION LINE TO CONNECT TO
THE NEW 1.5 INCH WATER MANIFOLD AS DESCRIBED IN
THE DEMOLITION PLANS.
2.1. THE INSTALLATION OF 125 L.F. OF WATER LINE
INCLUDES ALL NECESSARY CONSTRUCTION
ACTIVITIES AND MATERIALS REQUIRED FOR
INSTALLATION.
3. CONTRACTOR SHALL COORDINATE UTIILTY
CONNECTIONS TO BUILDINGS WITH MECHANICAL
PLANS.
EX CURB & GUTTER
CURB & GUTTER
STORM DRAIN CATCH BASIN /
AREA DRAIN PER PLAN
Project Number
Building Number
Drawing Number
Project Title
Location
Issue Date Checked Drawn
Drawing Title
Approved:
VA FORM 08 - 6231
A
BID DOCUMENT
SUBMITTAL
N/A
National Cemetery Administration
Design and Construction Service
U.S. Department of Veterans Affairs
B
C
D
E
F
A
B
C
D
E
F
21 4 5 6 7 8 9 10
PhaseARCHITECT/ENGINEER OF RECORD STAMPCONSULTANT
321 4 5 6 7 8 9 10
LOS ANGELES NATIONAL CEMETERY
CONSTRUCT MAINTENANCE FACILITY
Los Angeles, CA
898CM3034
N/A Project Director
5/24/2023Revisions: Date: Sheet of 95
VCI Project Management Construction Management Engineering Juan Kays
Department of Veterans Affairs, NCA
Phone: 202.632.5057 Email: juan.kays@va.gov
1331 17TH STREET SUITE 605
DENVER, COLORADO 80202
PHONE: (720) 439-4700
WEBSITE: www.dci-engineers.com
CIVIL / STRUCTURAL
JD Engineering, PC 371 Zimmerman Lane Hamilton, MT 59840 Phone: (406) 218 - 9980
720.491.7559; Sean Fitzpatrick
56 LOUIS PRIMA DRIVE, SUITE B, COVINGTON, LA 70433 SF JV
STORM DRAIN LINE
WATER LINE
6" SANITARY SEWER LINE
STORM DRAIN MANHOLE
EXISTING CONTOUR MINOR
EXISTING CONTOUR MAJOR
WATER VALVE
HOSE BIB
EX CURB INLET
EX TREE
UTILITY PLAN
C-102
STORM DRAINAGE RUN #1
STORM DRAINAGE RUN #2
SANITARY SEWER RUN #1
SANITARY SEWER RUN #2
NEW ADMINISTRATION
BUILDING
NE
W
M
AI
NT
EN
AN
CE
BU
IL
DI
NG
NEW COVERED VEHICLE
STORAGE
LEGEND AND SYMBOLS
OVERHEAD PARKING
8" SANITARY SEWER LINE
PRESSURE WASHER NOTES:
1. PRESSURE WASHER SHALL BE Mi-T-M, ELECTRIC, WALL
MOUNTED PRESSURE WASHER (CAW-3004-0ME1), OR
APPROVED EQUAL.
2. CONTRACTOR SHALL CONFIRM INSTALLATION
LOCATION WITH CEMETERY STAFF PRIOR TO
INSTALLATION.
3. UNIT SHALL HAVE, OR BE CAPABLE OF THE
FOLLOWING:
· WORKING PRESSURE - 3,000 PSI
· FLOW - 3.9 GPM
· HORESPOWER - 8.0
· REMOTE CONTROL BOX TO CONTROL ON/OFF
· AUTO START/STOP WHEN TRIGGER IS PULLED
· QUICK CONNECT LOW PRESSURE DETERGENT
INJECTOR
· THERMAL RELIEF VALVE
· TIME DELAY SUTDOWN
· 50-FOOT 38" HOSE
· 36-INCH ADJUSTABLE DUAL LANCE WITH INSULATED
TRIGGER GUN.
STORM DRAINAGE RUN #3
No. 44593
PROFESSIONAL
REGISTERED
JORDAN D. VANDERMEE
RENG INE ER
X
X
X
X
X
X
CO
CO
387 388 389
FG:382.21
FG:382.00
FG:382.45
FG:383.00
FG:383.00
FG:383.00
FG:383.00
FG:382.60
FG:382.40
FG:382.29
FG:382.07
FG:381.89
FG:381.06
FG:381.19
FG:380.85
FG:380.34
FG:380.07
FG:381.49
FG:381.56
FG:381.15
FG:381.20
FG:381.40
FG:381.08
FG:380.20
FG:380.61
FG:380.60
FG:380.61
FG:380.60
FG:380.40
FG:380.25
FG:380.25
FG:380.75
FG:380.75
FG:380.75 FG:380.89
FG:381.14
FG:380.62
FG:380.52
FG:380.41
FG:380.62
FG:380.62
FG:380.59FL:380.50
FG:380.88
FG:380.55
FG:380.10
FG:380.10
FG:380.60
FG:379.00
FG:379.00
FG:379.25
FG:379.25
FG:379.00
FG:379.00
FG:379.48
FG:379.48
FG:380.45
FG:380.15
FG:380.45
FG:380.50
FG:380.57
FG:380.57
FG:380.57
FG:380.60
FG:380.50
FG:380.07
FL:380.10
FL:379.81
FG:380.06
FG:380.06
FL:380.07
FG:380.03
FL:379.78
FG:380.03
FG:379.04
FG:379.15
FG:379.84
FG:379.53
FG:378.62
FG:378.62
FL:378.37
FG:378.32
FG:378.32
FL:378.32
FG:378.32
FG:378.32
FL:378.32
FG:378.59
FG:378.59
FL:378.34
TC:381.41
TC:381.38
TC:381.02
TC:MATCH EX
TC:MATCH EX
FG:385.50
FG:385.50
FG:383.22
FG:379.83
FG:379.15
FG:379.53
FG:379.04
FG:380.13
FG:380.13
TC:381.25TC:381.25
TC:381.29
TC:381.29
FG:380.50
FG:380.50
FG:380.53
FG:380.53
FG:382.00
FG:382.50
FG:382.50
TW:389.00
TW:387.00
TW:385.50
FG:379.80
0 10 20
1 INCH = 10 FEET
1. MATCH EXISTING ASPHALT PAVING AT SAWCUT LINE
2. APPROXIMATE LIMITS OF EXCAVATION FOR WALL
CONSTRUCTION AND PAD FILL, SEE GENERAL NOTES
BELOW.
3. MATCH EXISTING GRADE WITH CURB.
KEYED NOTES
GENERAL NOTES:
1. THE LIMITS OF DISTURBANCE ALONG THE HILLSIDE
ARE SHOWN AS A CONVENIENCE TO THE
CONTRACTOR. ACTUAL LIMITS WILL DEPEND ON
MEANS AND METHODS UTILIZED BY THE CONTRACTOR
FOR EXCAVATION. CONTRACTOR IS TO APPLY
APPROPRIATE MEASURES TO LIMIT EXCAVATION SO AS
NOT TO DISTURB EXISTING BURIALS. AREAS OF
EXCAVATION AND FILL ARE TO BE PROPERLY
BACKFILLED, COMPACTED, AND LANDSCAPED PER THE
LANDSCAPE PLANS.
LEGEND AND SYMBOLS
EX CURB & GUTTER
CURB & GUTTER
CONTOUR MINOR
CONTOUR MAJOR370
STORM WATER CATCH BASIN
Project Number
Building Number
Drawing Number
Project Title
Location
Issue Date Checked Drawn
Drawing Title
Approved:
VA FORM 08 - 6231
A
BID DOCUMENT
SUBMITTAL
N/A
National Cemetery Administration
Design and Construction Service
U.S. Department of Veterans Affairs
B
C
D
E
F
A
B
C
D
E
F
21 4 5 6 7 8 9 10
PhaseARCHITECT/ENGINEER OF RECORD STAMPCONSULTANT
321 4 5 6 7 8 9 10
LOS ANGELES NATIONAL CEMETERY
CONSTRUCT MAINTENANCE FACILITY
Los Angeles, CA
898CM3034
N/A Project Director
5/24/2023Revisions: Date: Sheet of 95
VCI Project Management Construction Management Engineering Juan Kays
Department of Veterans Affairs, NCA
Phone: 202.632.5057 Email: juan.kays@va.gov
1331 17TH STREET SUITE 605
DENVER, COLORADO 80202
PHONE: (720) 439-4700
WEBSITE: www.dci-engineers.com
CIVIL / STRUCTURAL
JD Engineering, PC 371 Zimmerman Lane Hamilton, MT 59840 Phone: (406) 218 - 9980
720.491.7559; Sean Fitzpatrick
56 LOUIS PRIMA DRIVE, SUITE B, COVINGTON, LA 70433 SF JV
FINISHED GRADE
EXISTING CONTOUR MINOR
EXISTING CONTOUR MAJOR
EX CURB INLET
EX TREE
GRADING PLAN
C-103
NEW ADMINISTRATION BUILDING
FINISHED FLOOR = 380.60
TOP OF FOOTER = 378.60
NE
W
M
AI
NT
EN
AN
CE
B
UI
LD
IN
G
FI
NI
SH
ED
F
LO
OR
0.
(G
RA
DE
A
T 0.
5% T
OW
AR
D
FL
OOR
DR
AI
NS
TO
P
OF
FO
OTE
R
8.
NEW COVERED VEHICLE STORAGE
FINISHED FLOOR = VARIES
TOP OF FOOTER = 378.62
FG:100.00
TOP OF CURBTC:100.00
FLOW LINEFL:100.00
No. 44593
PROFESSIONAL
REGISTERED
JORDAN D. VANDERMEE
X
X
X
X
X
X
RENOVATED BRICK
STORAGE BUILDING
EMPLOYEE PARKING
VEHICLE WASH AREA
AMIENS AVENUE
SOISSONS AVENUE
CO
CO
Project Number
Building Number
Drawing Number
Project Title
Location
Issue Date Checked Drawn
Drawing Title
Approved:
VA FORM 08 - 6231
A
BID DOCUMENT
SUBMITTAL
N/A
National Cemetery Administration
Design and Construction Service
U.S. Department of Veterans Affairs
B
C
D
E
F
A
B
C
D
E
F
21 4 5 6 7 8 9 10
PhaseARCHITECT/ENGINEER OF RECORD STAMPCONSULTANT
321 4 5 6 7 8 9 10
LOS ANGELES NATIONAL CEMETERY
CONSTRUCT MAINTENANCE FACILITY
Los Angeles, CA
898CM3034
N/A Project Director
5/24/2023Revisions: Date: Sheet of 95
VCI Project Management Construction Management Engineering Juan Kays
Department of Veterans Affairs, NCA
Phone: 202.632.5057 Email: juan.kays@va.gov
1331 17TH STREET SUITE 605
DENVER, COLORADO 80202
PHONE: (720) 439-4700
WEBSITE: www.dci-engineers.com
CIVIL / STRUCTURAL
JD Engineering, PC 371 Zimmerman Lane Hamilton, MT 59840 Phone: (406) 218 - 9980
720.491.7559; Sean Fitzpatrick
56 LOUIS PRIMA DRIVE, SUITE B, COVINGTON, LA 70433 SF JV
1. EXPANSION JOINT, SEE DETAIL C8/C-501.
2. CONTRACTION JOINT, SEE DETAIL C5/C-501.
0 10 20
1 INCH = 10 FEET
Project Number
Building Number
Drawing Number
Project Title
Location
Issue Date Checked Drawn
Drawing Title
Approved:
VA FORM 08 - 6231
A
BID DOCUMENT
SUBMITTAL
N/A
National Cemetery Administration
Design and Construction Service
U.S. Department of Veterans Affairs
B
C
D
E
F
A
B
C
D
E
F
21 4 5 6 7 8 9 10
PhaseARCHITECT/ENGINEER OF RECORD STAMPCONSULTANT
321 4 5 6 7 8 9 10
LOS ANGELES NATIONAL CEMETERY
CONSTRUCT MAINTENANCE FACILITY
Los Angeles, CA
898CM3034
N/A Project Director
5/24/2023Revisions: Date: Sheet of 95
VCI Project Management Construction Management Engineering Juan Kays
Department of Veterans Affairs, NCA
Phone: 202.632.5057 Email: juan.kays@va.gov
1331 17TH STREET SUITE 605
DENVER, COLORADO 80202
PHONE: (720) 439-4700
WEBSITE: www.dci-engineers.com
CIVIL / STRUCTURAL
JD Engineering, PC 371 Zimmerman Lane Hamilton, MT 59840 Phone: (406) 218 - 9980
720.491.7559; Sean Fitzpatrick
56 LOUIS PRIMA DRIVE, SUITE B, COVINGTON, LA 70433 SF JV
JOINTING PLAN
C-104
KEYED NOTES
GENERAL NOTES:
1. CONTRACTOR SHALL PLACE A NON-DOWELED
EXPANSION JOINT AROUND THE PERIMETER OF THE
CONCRETE PAVING.
2. CONTRACTOR SHALL PLACE A DOWELED EXPANSION
JOINT AROUND THE PERIMETER OF THE VALLEY
GUTTER.
LEGEND AND SYMBOLS
EX. CONTOUR MAJOR
EX. CONTOUR MINOR
EX. CURB & GUTTER
EX. SIDEWALK
EX. TREE (TYP.)
EX. MANHOLE
EX. UTILITY BOX
EX. C.M.U. RETAINING WALL
EX. CHAIN LINK FENCING
*SEE SURVEY SHEETS FOR EXISTING CONDITIONS LEGEND
EX. GATE
NEW ADMINISTRATION BUILDING
NE
W
M
AI
NT
EN
AN
CE
B
UI
LD
IN
G
NEW COVERED VEHICLE STORAGE
EXPANSION JOINT
CONTROL JOINT
2 TYP.
2 TYP.
2 TYP.
1 TYP.
1 TYP.
TYP.
No. 44593
PROFESSIONAL
REGISTERED
JORDAN D. VANDERMEE
RENG INEER
05/24/2023
1 TYP.
1 TYP.
STORM DRAINAGE RUN 1 PROFILE
VERT. SCALE: 1"=1'
HORIZ SCALE: 1"=10'
0+00 1+00 2+00 3+00
154 LF 15" PVC @ 0.25%
27 LF 15" PVC @ 0.25%
75 LF 15" PVC @ 0.25%
59 LF 12" PVC @ 0.25%
49 LF 8" PVC @ 1.00%
STORM DRAINAGE RUN 2 PROFILE
VERT. SCALE: 1"=1'
HORIZ SCALE: 1"=10'
33 LF 8" PVC @ 1.00%
6" PVC
D
EP
TH
=1
.9 1'
STORM DRAINAGE RUN 3 PROFILE
VERT. SCALE: 1"=1'
HORIZ SCALE: 1"=10'
0+00
49 LF 8" PVC @ 1.00%
0 10 20
1 INCH = 10 FEET
Project Number
Building Number
Drawing Number
Project Title
Location
Issue Date Checked Drawn
Drawing Title
Approved:
VA FORM 08 - 6231
A
BID DOCUMENT
SUBMITTAL
N/A
National Cemetery Administration
Design and Construction Service
U.S. Department of Veterans Affairs
B
C
D
E
F
A
B
C
D
E
F
21 4 5 6 7 8 9 10
PhaseARCHITECT/ENGINEER OF RECORD STAMPCONSULTANT
321 4 5 6 7 8 9 10
LOS ANGELES NATIONAL CEMETERY
CONSTRUCT MAINTENANCE FACILITY
Los Angeles, CA
898CM3034
N/A Project Director
5/24/2023Revisions: Date: Sheet of 95
VCI Project Management Construction Management Engineering Juan Kays
Department of Veterans Affairs, NCA
Phone: 202.632.5057 Email: juan.kays@va.gov
1331 17TH STREET SUITE 605
DENVER, COLORADO 80202
PHONE: (720) 439-4700
WEBSITE: www.dci-engineers.com
CIVIL / STRUCTURAL
JD Engineering, PC 371 Zimmerman Lane Hamilton, MT 59840 Phone: (406) 218 - 9980
720.491.7559; Sean Fitzpatrick
56 LOUIS PRIMA DRIVE, SUITE B, COVINGTON, LA 70433 SF JV
STORM DRAINAGE PROFILES
C-201
No. 44593
PROFESSIONAL
REGISTERED
JORDAN D. VANDERMEE