25-8408_Exhibit_M-1_-_Civil_Plans_S&S_10.3.pdf

PDF 23 MB Posted

Attached to
Central County Water Reclamation Facility Expansion
Solicitation number
25-8408
Issued by
Collier County, Florida

About this file

These are bid plans for the Central County Water Reclamation Facility project by Collier County Public Utilities, located in Collier County, Florida (Section 28, Township 49 South, Range 26 East). The project involves the design and construction of a water reclamation facility with multiple key components, including operations buildings, reclaimed water storage tanks, reject water storage tanks, a dewatering facility, blower building, generator building, and associated infrastructure. The site plan covers approximately 12.76 acres, with buildings, tanks, pavement, and open space strategically arranged. The facility will include provisions for future expansion, such as additional flow equalization tanks and membrane bioreactor (MBR) systems.

The bid documents indicate detailed specifications for site grading, drainage, utilities, and construction requirements. The project includes parking calculations (17 spaces for the operations building, including 2 handicap spaces), and adheres to local zoning regulations with building setbacks and height restrictions. Storm water management is carefully planned, with elevation considerations for flood protection (minimum parking elevation at 10.60 ft NAVD and finished floor elevations at 11.60 ft NAVD). The facility is designed with multiple storage and processing tanks, including reclaimed water storage, reject water storage, and provisions for future pump stations and infrastructure expansion. The overall design emphasizes functionality, future adaptability, and compliance with local engineering and environmental standards.

View the file

Other files

File Type Posted
Construction_Services_Agreement_2025_Template_ver_3_with_Exhibits.pdf PDF
PO_Terms_and_Conditions_Rev.3.pdf PDF
PO_Terms_and_Conditions_Rev.3.pdf PDF
25-8408_Exhibit_M-5_-_CCWRF_Bid_Alternate_Drawings.pdf PDF
25-8408_Exhibit_M-4_-_GGWWPT-SDPA-Site_(Dumpster_Enclosure)_S&S.pdf PDF
25-8408_Exhibit_I-1_-_Existing_Golden_Gate_WWTP_Drawings.pdf PDF
25-8408_Exhibit_N_-_EHS_Contractor_Requirements_Master_2021_rev.pdf PDF
25-8408_Exhibit_N_-_EHS_Contractor_Requirements_Master_2021_rev.pdf PDF
25-8408_Exhibit_M-2_–_Drawings_S&S_10.3.pdf PDF
25-8408_Exhibit_J_-_Technical_Specifications_S&S_10.3.pdf PDF
25-8408_Exhibit_I-1_-_Supplemental_Conditions_R1.pdf PDF
25-8408_Exhibit_M-2_–_Drawings_S&S_9.11.pdf PDF
25-8408_Exhibit_J_-_Technical_Specifications_S&S_9.26.pdf PDF
Exhibits_Combined.pdf PDF
Construction_Services_Agreement_2025_Template_ver_3.pdf PDF
Construction_Bid_Instructions_Version_1.pdf PDF
25-8408_Bid_Schedule_.xlsx XLSX spreadsheet
25-8408_Bid_Schedule_.xlsx XLSX spreadsheet
25-8408_Bid_Schedule_.xlsx XLSX spreadsheet
25-8408_Bid_Schedule_.xlsx XLSX spreadsheet
25-8408_Solicitation.pdf PDF
25-8408_-_Exhibit_M-3_-_Drawings_-_Drawing_Index.pdf PDF
25-8408_-_Exhibit_J-1_-_Technical_Specifications_-_Table_of_Contents.pdf PDF
25-8408_-_Pre-Bid_Sign-in_Sheets.pdf PDF
Construction_Bid_Instructions_Form_2025_Rev.2.pdf PDF
25-8408_Bid_Schedule_.xlsx XLSX spreadsheet
25-8408_-_Solicitation.pdf PDF
Construction_Services_Agreement_2025_ver._3.pdf PDF
PO_Terms_and_Conditions_Rev.3.pdf PDF
25-8408_-_Exhibit_N_-_EHS_Contractor_Requirements_Master_2021_rev.pdf PDF
25-8408_-_Exhibit_M-2_-_Drawings_S&S_5.23.2025.pdf PDF
25-8408_-_Exhibit_M-1_-_Plans_S&S_5.23.2025.pdf PDF
25-8408_-_Exhibit_J_-_Technical_Specifications_S&S_6.10.pdf PDF
25-8408_-_Exhibit_I-1_-_Supplemental_Conditions.pdf PDF
Show all 34

On GovTribe

Work with this file

  • Download the original file
  • Contacts named in this file
  • Similar government files
  • Ask GovTribe AI about this file

Text version

C ol lie r

B lv d.

CITY

PLANTATION

C ol lie r

B lv d.

S an ta B ar ba ra B lv d.

Interstate - 75

Golden Gate Pkwy

Radio Rd

Da vis

B lvd

E xt

BERKSHIRE

LAKES

Golden Gate Pkwy

Location Map

Plans Prepared For:

Prepared by:

Central County Water Reclamation Facility

Bid Plans Located in Collier County

Section 28, Township 49 South, Range 26 East

B

ID

G ol de n

G at e W as te w at er T re at m en t P la nt B id P la ns

Know what's below.

before you dig.Call

R

ZONING: RSF-3, PU-84-8C (RESOLUTION 84-148), CU-94-1 (RESOLUTION 94-533), &

CU-PL20210001657

GOVERNING SPECIFICATIONS:

Public Utilities Department Project Manager: Corinne Trtan, PMP 3339 Tamiami Trail E Suite 303 Naples, FL 34112 Tel: (239) 252-4233 Fax: (239) 252-3989

Property Owner: Collier County Water-Sewer District

Board of County Commisioners:

Rick Locastro District 1 Chris Hall District 2 Burt L. Sanders District 3 Dan Kowal District 4 William L, McDaniel, Jr. District 5

PROJECT

LOCATION

WWTP

Approved By:

Revisions

Collier County Public Utilities

LEGAL DESCRIPTION: USE/BUILDING CONSTRUCTION TYPE TOTAL AREA

BASE FIRE

FLOW

REQUIRED

SPRINKLERED REQUIRED

FIRE FLOW

NFPA IBC (SF) (GPM) (GPM)

B (OPERATIONS) II(000) IIB 3,787 1,500 YES 1,000

F-2 (ELECTRICAL) II(000) IIB 3,115 1,500 NO 1,500

F-2 (ELECTRICAL/BLOWER) II(000) IIB 2,720 1,500 NO 1,500

MINIMUM REDUCED FIRE FLOW FOR SPRINKLERED BUILDING IS 1,000 GPM

Index of Sheets

Sheet No. Sheet Description

1 COVER SHEET

2 GENERAL NOTES

3 AERIAL, CLEARING AND DEMOLITION PLAN

4 OVERALL SITE PLAN

5 OVERALL GRADING, PAVING AND DRAINAGE PLAN

6 GRADING, PAVING, and DRAINAGE PLAN (NORTHWEST)

7 GRADING, PAVING, and DRAINAGE PLAN (NORTHEAST)

8 GRADING, PAVING, and DRAINAGE PLAN (SOUTHWEST)

9 GRADING, PAVING, and DRAINAGE PLAN (SOUTHEAST)

10 CROSS SECTIONS AND STORMWATER DETAILS

11 UTILITY PLAN

12 STRIPING, SIGNAGE AND PAVING DETAILS

13 GENERAL UTILITY DETAILS

14 SANITARY SEWER DETAILS

15 WATER DETAILS

Collier County Project No.: 70243

C en tr al

C ou nt y

W at er R ec la m at io n

F ac ili ty

G ra dy M in or

P A P E -D A W S O N a c om pa ny

Civil Engineers ● Land Surveyors ● Planners ● Landscape Architects Cert. of Auth. EB 0005151 Cert. of Auth. LB 0005151 Business LC 26000266

Q. Grady Minor and Associates, LLC 3800 Via Del Rey

Bonita Springs, Florida 34134

Bonita Springs: 239.947.1144 ZZZ.GradyMinor.coP Fort Myers: 239.690.4380

Q. Grady Minor and Associates, LLC 3800 Via Del Rey

Bonita Springs, Florida 34134 GradyMinor PAPE-DAWSONa company

SERVICE PROVIDER UTILITY COMPANY TELEPHONE

ELECTRIC FLORIDA POWER & LIGHT (24 HOUR EMERGENCY) 239-353-6010

TELEPHONE CENTURY LINK 1-800-339-1811

CABLE T.V. COMCAST (239) 432-1850

UNDERGROUND FACILITY LOCATION SERVICES SUNSHINE ONE CALL 811 or 1-800-432-4770

WASTEWATER COLLIER COUNTY (239) 252-6886

WATER COLLIER COUNTY (239) 252-6245

GAS TECO ENERGY 1-877-832-6747

COMMUNICATIONS CROWN CASTLE FIBER 1-866-787-2637

COMMUNICATIONS SUMMIT BROADBAND (239) 444-0400

STORMWATER COLLIER COUNTY (239) 252-8192

GENERAL NOTES:

GENERAL NOTES (cont.)

STORMWATER NOTES:

Q. Grady Minor and Associates, LLC 3800 Via Del Rey

Q. Grady Minor and Associates, LLC 3800 Via Del Rey

Bonita Springs, Florida 34134 GradyMinor PAPE-DAWSONa company

QGM STANDARD ABBREVIATIONS

A.C. ASBESTOS CEMENT

BFW BUTT FUSION WELD

BL BASELINE

BLVD. BOULEVARD

BOC BACK OF CURB

BSP BACTERIAL SAMPLE POINT

CATV CABLE TELEVISION

CB CATCH BASIN

CL CENTERLINE

CMP CORRUGATED METAL PIPE

CO CLEAN OUT

CONC. CONCRETE

CUE COUNTY UTILITY EASEMENT

DBI DITCH BOTTOM INLET

DE DRAINAGE EASEMENT

DIP DUCTILE IRON PIPE

EL. OR ELEV. ELEVATION

EOP EDGE OF PAVEMENT

ERCP ELLIPTICAL REINFORCED CONCRETE PIPE

EXIST. or EX EXISTING

FDC FIRE DEPARTMENT CONNECTION

FDOT FLORIDA DEPARTMENT OF TRANSPORTATION

FE FLARED END

FEMA FEDERAL EMERGENCY MANAGEMENT AGENCY

FFE FINISHED FLOOR ELEVATION

F.H. FIRE HYDRANT

FLG FLANGED FITTING

FM FORCE MAIN

FPL OR FP&L FLORIDA POWER & LIGHT

GV GATE VALVE

HDPE HIGH DENSITY POLYETHYLENE

HORIZ. HORIZONTAL

HW HEADWALL

INC. INCORPORATED

INV. INVERT

IRR. IRRIGATION

JB JUNCTION BOX

LBR LANDSCAPE BUFFER EASEMENT

L.F. LINEAR FEET

LME LAKE MAINTENANCE EASEMENT

MES MITERED END SECTION

MH MANHOLE

M.J. MECHANICAL JOINT

MIN. MINIMUM

NGVD NATIONAL GEODETIC VERTICAL DATUM

NIC NOT IN CONTRACT

OFF. OFFSET

PBSP PERMANENT BACTERIAL SAMPLE POINT

PL PROPERTY LINE

POT. POTABLE

COD

E

DESCRIPTION

AC_ AIR CONDITIONING UNIT

ARL_ ARROW LEFT

ARR_ ARROW RIGHT

ARS_ ARROW STRAIGHT

ARV_ AIR RELEASE VALVE

_BM_ BENCHMARK (START w/BM or FOLLOWS MON. CODE)

BC_ BUILDING CORNER

BFP_ BACK FLOW PREVENTOR

BKR_ BIKE RACK

BOC_ BACK OF CURB_TYPE (A, D, E, F, VG)

BOL_ BOLLARD_TYPE

BPL_ BLUE PAINT LINE

BPR_ BRICK PAVER

BRA_ BRIDGE ABUTTMENT

BS_ BACK SITE_POINT #

BTS_ BOTTOM OF STEP

BUF BURIED UTILITY FLAG

BW_ BOTTOM OF WALL

CALC_ CALCULATED COORDINATE POINT

CB_ CATCH BASIN_PIPE SIZE_INVERT

CHW_ CONCRETE HEADWALL

CLH_ CENTERLINE HEDGE_WIDTH

CMP_ CORRUGATED METAL PIPE_SIZE

CNP_ CONCRETE PAD

CO_ CLEANOUT

CPP_ CORRUGATED PLASTIC PIPE_SIZE

CS_ CONTROL STRUCTURE

DCK_ DOCK OR DECK

DEAD_ DEAD TREE_SIZE_#(IF CLUSTER)

DKP_ DOCK OR DECK PILING OR POLE

DP_ DUMPSTER PAD

EB_ ELECTRIC BOX(IN GROUND)

ELC_ ELECTRC LINE

ELR_ ELECTRIC RISER

EM_ ELECTRIC METER

EOC_ EDGE OF CONCRETE

EOG_ EDGE OF GRAVEL

EOP_ EDGE OF PAVEMENT

EOW_ EDGE OF WATER

ERCP_ ELLIPTICAL RCP_SIZE

ESW_ EDGE SIDEWALK

ETP_ ELECTRIC TRANSFORMER PAD

FCL_ FENCE CHAIN LINK

FCM_ FOUND CONCRETE MONUMENT_SIZE_LB# OR NOID

FCR_ FENCE CORNER

FDC_ FIRE DEPARTMENT CONTROL

FDH_ FOUND DRILL HOLE

FFE_ FINISHED FLOOR ELEVATION

FGE_ FINISHED GARAGE FLOOR

FGP_ FENCE GATE/GATE POST

FH_ FIRE HYDRANT

FIP_ FOUND IRON PIPE_SIZE_LB# OR NOID

COD

E

DESCRIPTION

FIR_ FOUND IRON ROD_SIZE_LB# OR NOID

FLGP_ FLAG POLE

FMN_ FOUND MAG NAIL_SIZE_LB# OR NOID

FNL_ FOUND NAIL_SIZE_LB# OR NOID

FOC_ FACE OF CURB_TYPE (A, D, E, F, VG)

FPK_ FOUND P/K NAIL_SIZE_LB# OR NOID

FPL_ FLORIDA POWER AND LIGHT

FRM_ FORCE MAIN_U(UNDERGROUND), A(ABOVE GROUNT)

FSE_ FINISH SECOND FLOOR ELEVATION

FWD_ FENCE WOOD

GA_ GUY ANCHOR

GB_ GRADE BREAK

GMM_ GAS MAIN MARKER

GP_ GENERATOR PAD

GR_ GUIDE RAIL

GSL_ UNDERGROUND GAS LINE

GSM_ GAS METER

GT_ GREASE TRAP

GUMB_ GUMBO TREE_SIZE_#(IF CLUSTER)

GV_ GAS VALVE

HH_ HAND HOLE

HPM_ HANDICAP MAN SYMBOL

IRR_ IRRIGATION METER

IRV_ IRRIGATION VALVE

LDA_ LANDSCAPE PLANTING AREA

LIT_ LITTORAL SHELF

LP_ LIGHT POLE_TYPE (WOOD, METAL, FIBERGLASS,

CONCRETE)

LA_ LANDSCAPE LIGHT

MAL_ MALILUKA TREE_SIZE_#(IF CLUSTER)

MB_ MAILBOX

MES_ MITERED END SECTION_PIPE SIZE (SHOT AT END OF

PIPE AT INVERT)

MHD_ DRAINAGE MANHOLE_DEPTH

MHE_ ELECTRIC MANHOLE

MHS_ SANITARY MANHOLE_DEPTH

MHT_ TELEPHONE MANHOLE

MHWL_ MEAN HIGH WATER LINE

MHWT_ MANHOLE WATER

MNGO MANGO TREE_SIZE_#(IF CLUSTER)

MPL MAPLE TREE_SIZE_#(IF CLUSTER)

NG_ NATURAL GRADE (DIRT, GRASS, ETC.)

OAK_ OAK TREE_SIZE_#(IF CLUSTER)

OHW_ OVERHEAD WIRES

PALM_ PALM TREE_SIZE_#(IF CLUSTER)

PBID_ PELICAN BAY IMPROVEMENT DEISTRICT

PINE_ PINE TREE_SIZE_#(IF CLUSTER)

POL_ POINT ON LINE

PPR_ PAPER TREE

RCP_ REINFORCED CONCRETE PIPE_SIZE

RMP_ HANDICAP RAMP

SB_ STOP BAR STRIPING

COD

E

DESCRIPTION

SCM_ SET CONCRETE MONUMENT

SDH_ SET DRILL HOLE

SFS_ FEATURE SIGN

SG_ SPOT GRADE (ON VARIOUS TYPES OF PAVEMENT)

SIGN_ SIGN_TYPE (DONOT ENTER, HANDICAP, STOP, #MPH,

1WAY, NO PARKING, TRAFFIC-GENERAL, ETC)

SHT_ SET HUB TACK

SIR_ SET IRON ROD_SIZE

SL_ SET LATHE_X (GRADE) OR C# (MARKED CUT) OR F#

(MARKED FILL)

SNL_ SET NAIL_SIZE

SPK_ SET PARKER KALON NAIL_SIZE

STL_ STEEL PIPE_SIZE

SV_ SEWER VALVE

SWB_ SEA WALL BOTTOM

SWL_ SWALE/FLOW LINE

SWT_ SEA WALL TOP

TBX_ TELEPHONE BOX (IN GROUND)

TCP_ TERRA COTTA PIPE_SIZE

TLC_ CONC. TRAFFIC POLE

TLM_ METAL TRAFFIC POLE

TLW_ WOOD TRAFFIC POLE

TOB_ TOP OF BANK

TOS_ TOE OF SLOPE

TOW_ TOP OF WALL

TP_ TRAVERSE POINT

TREE_ TREE_TYPE_SIZE_#(IF CLUSTER)

TRS_ TELEPHONE RISER

TST_ TOP OF STEP

TVB_ CABLE TELEVISION BOX (IN GROUND)

TVR_ CABLE TELEVISION RISER

UGTP_ UNDERGROUND TELEPHONE LINE

UGTV_ UNDERGROUND TELEVISION LINE

UMKR_ UNDERGROUND BURIED CABLE MARKER

UPC_ CONCRETE UTILITY POLE

UPM_ METAL UTILITY POLE

UPW_ WOOD UTILITY POLE

VGL_ VEGETATION LINE

WBSP_ WATER BACTERIAL SAMPLE POINT

WDL_ WOODS LINE

WELL_ WATER WELL

WLC_ WALL CONCRETE

WLN_ WATER LINE_U(UNDERGROUND), A(ABOVE GROUNT)

WLW_ WALL WOOD

WM_ WATER METER

WPL_ WHITE PAINTED LINE

WS_ WHEEL STOP

WTL_ WETLAND MARKER_DESIGNATION & NUMBER

WV_ WATER VALVE

YD_ YARD DRAIN

YPL_ YELLOW PAINTED LINE

SURVEY KEY DESCRIPTIONS

WATER and WASTEWATER NOTES: PROP. PROPOSED

PVC POLYVINYL CHLORIDE PIPE

PVI POINT OF VERTICAL INTERSECTION

PVMT. PAVEMENT

P.S. PUMP STATION

RED. REDUCER

RCP REINFORCED CONCRETE PIPE

R.O.W. RIGHT-OF-WAY

SAN. SANITARY

SB SOIL BORING

ST. STREET

STA. STATION

SWK. SIDEWALK

SWR. SEWER

TBSP TEMPORARY BACTERIAL SAMPLE POINT

TEMP. TEMPORARY

TOB TOP OF BANK

TOS TOE OF SLOPE

TYP. TYPICAL

UE UTILITY EASEMENT

VERT. VERTICAL

VG VALLEY GUTTER

W/ WITH

WCS WATER CONTROL STRUCTURE

WM WATER MAIN

YD YARD DRAIN

LEGEND:

EX. MITERED END SECTION EX. SANITARY SEWER

EX. CATCH BASIN EX. WATERMAIN

PROPOSED YARD DRAIN EX. STORM SEWER

PROPOSED CATCH BASIN PROPOSED SANITARY SEWER & MANHOLE

PROPOSED MITERED END SECTION PROPOSED WATERMAIN & GATE VALVES

PROPOSED WATER METER & SERVICE PROPOSED STORM SEWER

PROPOSED FIRE HYDRANT & TEE

PROPOSED SAN. SEWER LATERAL & C.O.

PROPOSED GRADE

2''W

EX

.FM

EX

.FM

EX

.FM

EX

.FM

EX

.FM

EX

.FM

EX

.FM

EX

.FM

EX

.FM

EX.F

M

EX

.FM

EX

.FM

EX

.FM

EX

.FM

EX.F

M

EX

.FM

EX

.FM

EX

.FM

EX

.FM

EX

.FM

EX

.FM

0 50' 100'25'

SCALE: 1" = 50'

Q. Grady Minor and Associates, LLC 3800 Via Del Rey

Q. Grady Minor and Associates, LLC 3800 Via Del Rey

Bonita Springs, Florida 34134 GradyMinor PAPE-DAWSONa company

TYPICAL SILT FENCE DETAIL

N.T.S.

FLOATING TURBIDITY BARRIERS

N.T.S.

GRAVEL OR PAVED CONSTRUCTION ENTRANCE DETAIL

(RUBBLE STRIP)

N.T.S.

32nd AVE. S.W.

TR

O

PI

C

AN

A

B

LV

D

31st PL. S.W.

31st AVE. S.W.

C

C C xx xx xx xx xxxxxxxx xxxxxx xx xx xx xx xx

2''W

2''W

EX

.FM

EX

.FM

EX

.FM

EX

.FM

EX

.FM

EX

.FM

EX

.FM

EX

.FM

EX

.FM

EX

.FM

EX

.FM

EX

.FM

EX

.FM

EX

.FM

EX

.FM

EX

.FM

EX

.FM

EX

.FM

EX

.FM

EX

.FM

EX

.FM

TROPICANA CANAL

PROPERTY

BOUNDARY

ODOR

CONTROL

SODIUM HYPOCHLORITE TANKS

FUTURE MBR

EXIST.

FILTERS

HATCHED AREA

DENOTES

EXISTING SITE

CONFIGURATION

TO REMAIN

WRF SITE ACCESS

(PHASE-2)

CENTRAL COUNTY WRF EXPANSION

Collier County Project No.: 70243

FOR PROP. GRADING AND STORM

DRAIN SYSTEM (REFER TO SHEET 5) FOR PROP. SITE GRAVITY

SANITARY SEWER SYSTEM

REFER TO SHEET 11

PROP. SITE LIGHTING (TYP.)

PROPOSED PHASE-2 PARKING

(REFER TO SHEET 12 FOR DETAILS)

FOR PROP. CONTROL STRUCTURE

DETAIL REFER TO SHEET 10

FLOW EQ

TANKS

FUTURE FLOW

EQ TANK

OPERATIONS

BUILDING

MBR

FUTURE MBR

RECLAIMED WATER

STORAGE TANK 1

DEWATERING

FACILITY

SLUDGE

HOLDING

TANK

RECLAIMED WATER

STORAGE TANK 2

REJECT WATER

STORAGE TANK 1

BLOWER

BUILDING

EXISTING

CLARIFIER #1

EXISTING

DIGESTER

EXISTING

HLD

EXIST.

FILTERS

EXISTING

CLARIFIER #2

EXIST.

WWTP

SITE

EFFLUENT

TRANSFER

STATION

FUEL

TANKS

ODOR

CONTROL

SKID UNIT

ODOR

CONTROL

SODIUM HYPOCHLORITE TANKS

ASPHALT

PAVEMENT

(TYP.)

GENERATOR

BUILDING

TROPICANA CANAL

HEADWORKS

STRUCTURE

REJECT WATER

STORAGE TANK 2

INJECTION WELL

FUTURE RECLAIMED

PUMP STATION

FLOW METER

FLOW EQ

TANKS

Q. Grady Minor and Associates, LLC 3800 Via Del Rey

Q. Grady Minor and Associates, LLC 3800 Via Del Rey

Bonita Springs, Florida 34134 GradyMinor PAPE-DAWSONa company

STORM WATER MANAGEMENT SUMMARY

10 YEAR , 1 DAY STORM STAGE (FT.-NAVD) = 9.88'

25 YEAR , 3 DAY STORM STAGE (FT.-NAVD) = 10.57'

100 YEAR , 3 DAY STORM STAGE (FT.-NAVD) = 11.59'

MINIMUM PARKING ELEVATION (FT.-NAVD) = 10.60'

MINIMUM FINISHED BERM ELEVATION (FT.-NAVD) = 11.60'

RECOMMENDED FINISHED FLOOR ELEVATION (FT.-NAVD) = 11.60'

PARKING AND LOADING ZONE CALCULATIONS

BUILDING CRITERIA CALCULATION REQUIRED PROVIDED

OPERATIONS BLDG. (4,470 SF) 1 SPACE PER 275 SQ FT (4,470 SF) x (1/275) = 16.25 17 17

TOTAL (INCL. H/C) 17 19

HANDICAPPED SPACES 1 HANDICAPPED SPACE FOR UP TO 25 1 2

PHASE -1 OFFICE TRAILER

PHASE-1 OFFICE TRAILER (1,440 SF) 1 SPACECE PER 300 SF (1,440 SF) x (1/300) = 4.8 5 5 (INC. 1 HC SPACE)

32nd AVE. S.W.

TR

O

PI

C

AN

A

B

LV

D

31st PL. S.W.

31st AVE. S.W.

LAND USE SUMMARY

DRY DETENTION (BOTTOM AREA) 1.59 Ac.

OPEN SPACE 5.27 Ac.

PAVEMENT/SIDEWALKS 2.67 Ac.

OPEN TANKS** 2.94 Ac.

BUILDINGS 0.30 Ac.

PROJECT AREA TOTAL 12.76 Ac.

AREA OUTSIDE OF PROJECT BOUNDARY 3.20 Ac.

TOTAL PROPERTY AREA 15.96 Ac.

**OPEN TANKS EXCLUDED FROM DRAINAGE BASIN

BUILDING SETBACKS

BASE ZONING RSF-3 REQUIRED PROPOSED

MIN. DISTANCE BETWEEN BUILDINGS NONE NONE

FRONT YARD SETBACK 30' 30'

SIDEYARD / WATERFRONT SETBACK 10' 35

REAR YARD SETBACK 25' 80

MAX. BUILDING HEIGHT PER CU-PL20210001657 50' ABOVE GRADE 48.45 ABOVE GRADE

EX

.FM

EX

.FM

EX

.FM

EX

.FM

EX

.FM

EX

.FM

EX

.FM

EX

.FM

EX.FM

EX

.FM

EX

.FM

EX

.FM

EX

.FM

EX.FM

EX

.FM

EX

.FM

EX

.FM

EX

.FM

EX

.FM

EX

.FM

EX

.FM

C

C C

C C xx xx xx xx xxxxxxxx xxxxxx xx xx xx xx xx

EX. C.B.

TYPE: DBI

GRATE: 11.20'

INV (E): 3.50'

INV (SE): 3.50'

EX. C.B.

TYPE: DBI

GRATE EL: 9.00'

INV: 3.50' (NE)

EX. C.B.

TYPE: WCS

GRATE EL: 11.50'

INV: 5.00' (NE)

EX. 15" RCP

EX. 1

5" R

CP

EX. C.B.

TYPE: DBI

GRATE: 9.50'

INV (W): 3.50'

EX. M.E.S.

INV: 4.00'

EX. 15" N-12 ADS

C

D

E

A

B

FLOW EQ

TANKS

FUTURE FLOW

EQ TANK

OPERATIONS

BUILDING

MBR

FUTURE MBR

RECLAIMED WATER

STORAGE TANK 1

DEWATERING

FACILITY

SLUDGE

HOLDING

TANK

RECLAIMED WATER

STORAGE TANK 2

REJECT WATER

STORAGE TANK 1

BLOWER

BUILDING

EXISTING

CLARIFIER #1

EXISTING

DIGESTER

EXISTING

HLD

EXIST.

FILTERS

EXISTING

CLARIFIER #2

EXIST.

WWTP

SITE

F.F.E. =14.5

F.F.E. =12.5 F.F.E. =13.25

F.F.E. =13.0

F.F.E. =14.5

F.F.E. =14.5

F.F.E. =14.00

F.F.E. =14.5

F.F.E. =14.5

F.F.E. =14.0

F.F.E. =12.0

F.F.E. =14.00

F.F.E. =13.5

F.F.E. =11.5

F.F.E. =12.0

F.F.E. =12.0

F.F.E. =13.0

F.F.E. =14.5

F.F.E. =12.5 F.F.E. =13.25

F.F.E. =13.0

F.F.E. =14.5

F.F.E. =14.5

F.F.E. =14.00

F.F.E. =14.5

F.F.E. =14.5

F.F.E. =14.0

F.F.E. =12.0

F.F.E. =14.00

EFFLUENT

TRANSFER

STATION

DS-12

DBI Type C G.E.: 13.00

INV: 7.00 (W)

DS-11

DBI Type C G.E.: 12.30

INV: 6.50 (N)

INV: 6.50 (E)

DS-21

DBI Type C G.E.: 12.20

INV: 6.50 (E)

DS-17

DBI Type C G.E.: 12.20

INV: 6.00 (N)

DS-20

DBI Type C G.E.: 12.10

INV: 6.30 (S)

INV: 6.30 (W)

DS-9

DBI Type C G.E.: 12.00

INV: 5.50 (N)

INV: 5.50 (S)

DS-10

DBI Type C G.E.: 12.30

INV: 6.00 (N)

INV: 6.00 (S)

DS-15

DBI Type C G.E.: 8.50

INV: 5.80 (SW)

DS-24

DBI Type C G.E.: 11.80

INV: 6.50 (S)

INV: 6.50 (N)

DS-19

DBI Type C G.E.: 11.70

INV: 6.10 (N)

DS-23

DBI Type C G.E.: 12.50

INV: 6.50 (SE)

INV: 6.50 (N)

WCS

DBI Type C G.E.: 10.60

INV: 4.00 (N)

DS-22

DBI Type C G.E.: 8.50

INV: 5.80 (NW)

DS-4

DBI Type C G.E.: 8.50

INV: 5.30 (N)

DS-5

DBI Type C G.E.: 8.50

INV: 5.30 (S)

DS-7

DBI Type C G.E.: 8.50

INV: 5.30 (S)

DS-6

DBI Type C G.E.: 8.50

INV: 5.30 (N)

DS-14

DBI Type C G.E.: 8.50

INV: 5.80 (N)

DS-8

DBI Type C G.E.: 8.50

INV: 5.00 (S)DS-13

DBI Type C G.E.: 8.50

INV: 5.80 (S)

24" MES

INV: 4.00 (S)

DS-16

DBI Type C G.E.: 12.00

INV: 6.00 (S)

INV: 6.00 (NE)

INV: 6.00 (E)

99 LF 18"

126 LF 18"

LF

8"

65 LF 18"

84 LF 18"

111 LF 18"

74 LF 18"

35 LF 24"

95 LF 24"

83 LF 24"

65 LF 15"

110 LF 15"

63 LF 15"

110 LF 24"

FUEL

TANKS

ODOR

CONTROL

SKID UNIT

ODOR

CONTROL

SODIUM HYPOCHLORITE TANKS

ASPHALT

PAVEMENT

(TYP.)

GENERATOR

BUILDING

31st AVENUE S.W.

31st PLACE S.W.

32nd AVE S.W.

32nd AVE S.W.

TR

O

PI

C

A N

A B

LV

D

TROPICANA CANAL

HEADWORKS

STRUCTURE

SMH-5

SMH-4

SMH-6

SMH-7

SMH-8

SMH-9

SMH-10 SMH-11

SMH-12

SMH-3

SMH-2SMH-1

L.S.

C.O.

REJECT WATER

STORAGE TANK 2

F.F.E. =13.5

F.F.E. =11.5

F.F.E. =12.0

F.F.E. =12.0

INJECTION WELL

FUTURE RECLAIMED

PUMP STATION

FLOW METER

DS-16 (1)

DBI Type C G.E.: 11.20

INV: 6.00 (W)

DS-24 (1)

DBI Type C G.E.: 12.50

INV: 6.50 (S)

56 LF 12"

17 LF 12"

Q. Grady Minor and Associates, LLC 3800 Via Del Rey

Q. Grady Minor and Associates, LLC 3800 Via Del Rey

Bonita Springs, Florida 34134 GradyMinor PAPE-DAWSONa company

SHEET 9

SHEET 7

SHEET 8

SHEET 6

PROP. INLINE

BOOSTER P.S.

PROP. TEMP. CONSTR. TRAILER

OFFICE

TRAILER

LEGEND:

PROPOSED SURFACE WATER FLOW DIRECTION

PROPOSED FINISH GRADE

EXISTING GROUND ELEVATION

NOTES:

1. MINIMUM FINISHED GRADES OF 11.6 FT NAVD, AS SHOWN FOR

THE PHASE-1 OFFICE AND CONSTRUCTION TRAILERS, REFER TO

LIMEROCK BASE PAD WITHIN THE FOOTPRINT OF THE TRAILER -

ACTUAL OFFICE TRAILER FLOOR ELEVATION SHALL BE AT

ELEVATION 13.3 FT NAVD.

2. ALL CATCH BASINS WITHIN PAVED ROADWAYS AND AREAS

ACCESSIBLE FOR VEHICULAR TRAFFIC SHALL BE EQUIPPED WITH

HEAVY DUTY TRAFFIC GRATES.

E

A

FLOW EQ

TANKS

FUTURE FLOW

EQ TANK

MBR

FUTURE MBR

F.F.E. =12.5 F.F.E. =13.25

F.F.E. =13.0

F.F.E. =14.5

F.F.E. =14.00

F.F.E. =13.5

F.F.E. =11.5

F.F.E. =12.5 F.F.E. =13.25

F.F.E. =13.0

F.F.E. =14.5

F.F.E. =14.00

DS-11

DBI Type C G.E.: 12.30

INV: 6.50 (N)

INV: 6.50 (E)

DS-17

DBI Type C G.E.: 12.20

INV: 6.00 (N)

DS-9

DBI Type C G.E.: 12.00

INV: 5.50 (N)

INV: 5.50 (S)

DS-10

DBI Type C G.E.: 12.30

INV: 6.00 (N)

INV: 6.00 (S)

DS-15

DBI Type C G.E.: 8.50

INV: 5.80 (SW)

DS-14

DBI Type C G.E.: 8.50

INV: 5.80 (N)

DS-8

DBI Type C G.E.: 8.50

INV: 5.00 (S)

DS-13

DBI Type C G.E.: 8.50

INV: 5.80 (S)

DS-16

DBI Type C G.E.: 12.00

INV: 6.00 (S)

INV: 6.00 (NE)

INV: 6.00 (E)

99 LF 18"

126 LF 18"

84 LF 18"

111 LF 18"

74 LF 18"

63 LF 15"

110 LF 24"

FUEL

TANKS

ODOR

CONTROL

SKID UNIT

ODOR

CONTROL

GENERATOR

BUILDING

TROPICANA CANAL

HEADWORKS

STRUCTURE

SMH-5

SMH-4

SMH-6

SMH-7

SMH-8

F.F.E. =13.5

F.F.E. =11.5

DS-16 (1)

DBI Type C G.E.: 11.20

INV: 6.00 (W)17 LF 12"

0 30' 60'15'

SCALE: 1" = 30'

Q. Grady Minor and Associates, LLC 3800 Via Del Rey

Q. Grady Minor and Associates, LLC 3800 Via Del Rey

Bonita Springs, Florida 34134 GradyMinor PAPE-DAWSONa company

MATCHLINE - SEE SHEET 8

M

AT

C H

LI

N

E

- S

EE

S

H

EE

T

LEGEND:

PROPOSED SURFACE WATER FLOW DIRECTION

PROPOSED FINISH GRADE

EXISTING GROUND ELEVATION

xx xx xx xx xx xx xx xxxxxxxxxx xx xx xx xx xx xx xx xx xx

C

B

OPERATIONS

BUILDING

RECLAIMED WATER

STORAGE TANK 1

RECLAIMED WATER

STORAGE TANK 2

REJECT WATER

STORAGE TANK 1

BLOWER

BUILDING

F.F.E. =14.5

F.F.E. =14.5

F.F.E. =14.00

F.F.E. =14.5

F.F.E. =12.0

F.F.E. =13.0

F.F.E. =14.5

F.F.E. =14.5

F.F.E. =14.00

F.F.E. =14.5

DS-12

DBI Type C G.E.: 13.00

INV: 7.00 (W)

DS-24

DBI Type C G.E.: 11.80

INV: 6.50 (S)

INV: 6.50 (N)

WCS

DBI Type C G.E.: 10.60

INV: 4.00 (N)

DS-5

DBI Type C G.E.: 8.50

INV: 5.30 (S)

DS-7

DBI Type C G.E.: 8.50

INV: 5.30 (S)

DS-6

DBI Type C G.E.: 8.50

INV: 5.30 (N)

24" MES

INV: 4.00 (S)

35 LF 24"

95 LF 24"

FUEL

TANKS

GENERATOR

BUILDING

31st AVENUE S.W.

31st PLACE S.W.

SMH-4

SMH-9

SMH-11

REJECT WATER

STORAGE TANK 2

F.F.E. =12.0

FUTURE RECLAIMED

PUMP STATION

FLOW METER

DS-24 (1)

DBI Type C G.E.: 12.50

INV: 6.50 (S)

56 LF 12"

Q. Grady Minor and Associates, LLC 3800 Via Del Rey

Q. Grady Minor and Associates, LLC 3800 Via Del Rey

Bonita Springs, Florida 34134 GradyMinor PAPE-DAWSONa company

MATCHLINE - SEE SHEET 9

M

AT

C H

LI

N

E

- S

EE

S

H

EE

T

LEGEND:

PROPOSED SURFACE WATER FLOW DIRECTION

2''W

2''W

C C

C C

EX. C.B.

TYPE: DBI

GRATE: 11.20'

INV (E): 3.50'

INV (SE): 3.50'

EX. C.B.

TYPE: DBI

GRATE EL: 9.00'

INV: 3.50' (NE)

EX. C.B.

TYPE: WCS

GRATE EL: 11.50'

INV: 5.00' (NE)

EX. 15" RCP

EX. 1

5" R

CP

EX. C.B.

TYPE: DBI

GRATE: 9.50'

INV (W): 3.50'

EX. M.E.S.

INV: 4.00'

EX. 15" N-12 ADS

FLOW EQ

TANKS EQ TANK

EXISTING

CLARIFIER #1

EXISTING

DIGESTER

EXISTING

HLD

EXIST.

FILTERS

EXISTING

CLARIFIER #2

EXIST.

WWTP

SITE

F.F.E. =12.5 F.F.E. =13.25

F.F.E. =12.0

F.F.E. =13.5

F.F.E. =12.0

F.F.E. =12.5 F.F.E. =13.25

F.F.E. =12.0

EFFLUENT

TRANSFER

STATION

DS-21

DBI Type C G.E.: 12.20

INV: 6.50 (E)

32nd AVE S.W.

STRUCTURE

SMH-10

SMH-3

SMH-2

SMH-1

L.S.

C.O.

F.F.E. =13.5

F.F.E. =12.0

Q. Grady Minor and Associates, LLC 3800 Via Del Rey

Q. Grady Minor and Associates, LLC 3800 Via Del Rey

Bonita Springs, Florida 34134 GradyMinor PAPE-DAWSONa company

MATCHLINE - SEE SHEET 6

M

AT

C H

LI

N

E

- S

EE

S

H

EE

T

PROP. INLINE

BOOSTER P.S.

PROP. TEMP. CONSTR. TRAILER

OFFICE

TRAILER

LEGEND:

PROPOSED SURFACE WATER FLOW DIRECTION

EX

.FM

EX

.FM

EX

.FM

EX

.FM

EX

.FM

EX

.FM

EX

.FM

EX.FM

EX

.FM

EX

.FM

EX

.FM

EX

.FM

EX

.FM

EX

.FM

EX

.FM

EX

.FM

EX

.FM

EX

.FM

EX

.FM

EX

.FM

EX.FM

EX

.FM

EX

.FM

EX

.FM

EX

.FM

EX.FM

EX

.FM

EX

.FM

EX

.FM

EX

.FM

EX

.FM

EX

.FM

EX

.FM

EX

.FM

EX

.FM

C

C xx xx xx xx xx xx xx xx xxxxxxxxxxxx

D

DEWATERING

FACILITY

SLUDGE

HOLDING

TANK

F.F.E. =14.5

F.F.E. =14.5

F.F.E. =14.5

F.F.E. =14.0

F.F.E. =12.0

F.F.E. =14.00

F.F.E. =13.0

F.F.E. =14.5

F.F.E. =14.5

F.F.E. =14.5

F.F.E. =14.0

F.F.E. =12.0

F.F.E. =14.00

EFFLUENT

TRANSFER

STATION

DS-20

DBI Type C G.E.: 12.10

INV: 6.30 (S)

INV: 6.30 (W)

INV: 6.50 (N)

DS-19

DBI Type C G.E.: 11.70

INV: 6.10 (N)

DS-23

DBI Type C G.E.: 12.50

INV: 6.50 (SE)

INV: 6.50 (N)

DS-22

DBI Type C G.E.: 8.50

INV: 5.80 (NW)

DS-4

DBI Type C G.E.: 8.50

INV: 5.30 (N)

LF

8"

65 LF 18"

83 LF 24"

65 LF 15"

110 LF 15"

SODIUM HYPOCHLORITE TANKS

ASPHALT

PAVEMENT

(TYP.)

31st PLACE S.W.

32nd AVE S.W.

TR

O

PI

C

A N

A B

LV

D

SMH-11

SMH-12

SMH-3

INJECTION WELL

FUTURE RECLAIMED

PUMP STATION

FLOW METER

56 LF 12"

Q. Grady Minor and Associates, LLC 3800 Via Del Rey

Q. Grady Minor and Associates, LLC 3800 Via Del Rey

Bonita Springs, Florida 34134 GradyMinor PAPE-DAWSONa company

MATCHLINE - SEE SHEET 7

M

AT

C H

LI

N

E

- S

EE

S

H

EE

T

PROPOSED SURFACE WATER FLOW DIRECTION

PROPOSED FINISH GRADE

LEGEND:

Q. Grady Minor and Associates, LLC 3800 Via Del Rey

Q. Grady Minor and Associates, LLC 3800 Via Del Rey

Bonita Springs, Florida 34134 GradyMinor PAPE-DAWSONa company

NOTES:

CATCH BASIN DETAIL

N.T.S.

SECTION

TYPE C CAST IRON GRATE PLAN VIEW

BASIN DIMENSIONS

TYPE

C-I-P PRECAST

HL W L W

C 4'-5" 3'-4" 4'-1" 3'-0" VARIES

D 4'-5" 5'-5" 4'-1" 5'-1" VARIES

E 5'-10" 4'-4" 5'-6" 4'-0" VARIES

WATER CONTROL STRUCTURE

DETAIL (WC-1)

N.T.S.

JUNCTION BOX DETAIL

N.T.S.

SECTION A

N.T.S.

SECTION B

N.T.S.

SECTION C

N.T.S.

SECTION E

N.T.S.

SECTION D

N.T.S.

MITERED END SECTION DETAIL

N.T.S.

DBDBDBDB

C C

C C xx xx xx xx xxxxxxxx xxxxxx xx xx xx xx xx

D B

D B

DB

DB

D B

DB DB DB DB DB DB DB

D B

D B

D B

D B

D B

D B

DBDBDBDBDBDBDBDBDB

DB DB

DB

D B

D B

D B

D B

DB DB DB DB DB

DB DB DB DB

DB DB DB DB

D B

DB

DB DB DB

D B

D B

D B

DB

D B

D B

D B

D B

D B

DBDBDBDBDBDBDBDBDBDBDBDB

D B

D B

D B

D B

DB

DB

DB

D B

D B

D B

D B

D B

DB

DB

DB

D B

D B

D B

D B

D B

D B

D B

D B

D B

DB

DB

DB

DB

DB

DB

DB DB DB DB DB DB

D B

D B

D B

DB

DB

DB

DB

DB

D B

D B

DB DB DB

DB DB DB DB DB DB DB DB DB DB DB

D B

D B

D B

D B

D B

D B

D B

D B

D B

D B

D B

D B

D B

DB

DB

DB

DB

DB

DB DB DB

D B

D B

DBDBDBDBDBDBDB

DB

DB

DB

DB

DBDB

D B

D B

D B

D B

DB

DB

DB

DB

DB

DB

DB

DB

DB

DB

DB

D B

D B

DB

DB

DB DB DB DB DB DB DB DB DB

DB

DB

DB

DBDBDB

DB

DB

D B

D B

D B

D B

DB

DB

DB

D B

D B

DB

DB

DB

DB

D B

DB DB

D B

D B

DB

DB

DB

DB

D B

FLOW EQ

TANKS

FUTURE FLOW

EQ TANK

OPERATIONS

BUILDING

MBR

FUTURE MBR

RECLAIMED WATER

STORAGE TANK 1

DEWATERING

FACILITY

SLUDGE

HOLDING

TANK

RECLAIMED WATER

STORAGE TANK 2

REJECT WATER

STORAGE TANK 1

BLOWER

BUILDING

EXISTING

CLARIFIER #1

EXISTING

DIGESTER

EXISTING

HLD

EXIST.

FILTERS

EXISTING

CLARIFIER #2

EFFLUENT

TRANSFER

STATION

FUEL

TANKS

ODOR

CONTROL

SKID UNIT

ODOR

CONTROL

SODIUM HYPOCHLORITE TANKS

ASPHALT

PAVEMENT

(TYP.)

GENERATOR

BUILDING

TROPICANA CANAL

HEADWORKS

STRUCTURE

REJECT WATER

STORAGE TANK 2

INJECTION WELL

FUTURE RECLAIMED

PUMP STATION

FLOW METER

2''W

2''W

EX

.FM

EX

.FM

EX

.FM

EX

.FM

EX

.FM

EX

.FM

EX

.FM

EX

.FM

EX

.FM

EX

.FM

EX

.FM

EX.F

M

EX

.FM

EX

.FM

EX

.FM

EX

.FM

EX.F

M

EX

.FM

EX

.FM

EX

.FM

EX

.FM

TROPICANA CANAL

EXISTING

CLARIFIER #1

EXISTING

DIGESTER

EXISTING

HLD

EXIST.

FILTERS

EXISTING

CLARIFIER #2

EXIST.

WWTP

SITE

TR

O

PI

C

A N

A B

LV

D

32nd AVENUE S.W.

31st PL S.W.

31st AVE. S.W.

C.O.

RIM: 11.50

INV OUT: 0.76 (S)

SMH-5

RIM: 12.10

INV IN: 3.40 (E)

SMH-7

RIM: 11.00

INV OUT: 3.85 (E)

SMH-3

RIM: 11.80

INV OUT: 1.48 (N)

L.S.

RIM: 12.00

INV IN: 0.50 (N)

SMH-12

RIM: 13.20

INV OUT: 2.96 (N)

SMH-1

RIM: 13.00

INV IN: 0.67 (E)

INV IN: 0.67 (N)

INV OUT: 0.57 (S)

SMH-2

RIM: 13.40

INV IN: 1.15 (N)

INV IN: 1.15 (S)

INV OUT: 1.05 (W)

SMH-10

RIM: 13.30

INV IN: 1.39 (N)

INV OUT: 1.39 (E)

INV OUT: 1.29 (S)

SMH-4

RIM: 13.50

INV IN: 1.89 (N)

INV OUT: 1.79 (S)

INV OUT: 1.89 (W)

SMH-6

RIM: 13.70

INV IN: 2.57 (N)

INV IN: 2.57 (W)

INV OUT: 2.47 (S)

SMH-8

RIM: 12.40

INV IN: 3.18 (E)

INV OUT: 3.08 (S)

SMH-9

RIM: 11.60

INV OUT: 4.36 (W)

22 LF of 10" PVC SAN. SEWER @ 0.40%

LF

o f 8 " P

VC

S

AN

. S

EW

ER

.4 0%

82 LF of 8" PVC SAN. SEWER @ 0.40%

17 LF of 8" PVC SAN. SEWER @ 0.40%

95 LF of 8" PVC SAN. SEWER @ 0.40%

36 LF of 8" PVC SAN. SEWER @ 0.39%

LF

o f 8 " P

VC

S

AN

. S

EW

ER

.4 0%

LF

o f 8 " P

VC

S

AN

. S

EW

ER

.4 0%

LF

o f 8 " P

VC

S

AN

. S

EW

ER

.4 0%

295 LF of 8" PVC SAN. SEWER @ 0.40%

321 LF of 8" PVC SAN. SEWER @ 0.40%

SMH-11

RIM: 14.20

INV IN: 2.24 (W)

INV IN: 2.34 (S)

DS-14

DS-13

DS-15

DS-16

DS-17

DS-10

WCS

24" MES

DS-7

DS-6

DS-4

DS-5

DS-22

DS-23

DS-24

DS-19

DS-20DS-21

DS-12

DS-11

DS-9

DS-8

Q. Grady Minor and Associates, LLC 3800 Via Del Rey

Q. Grady Minor and Associates, LLC 3800 Via Del Rey

Bonita Springs, Florida 34134 GradyMinor PAPE-DAWSONa company

GENERATOR ROOM

OPERATIONS

BUILDING

FIRE CONNECTION DETAIL

Q. Grady Minor and Associates, LLC 3800 Via Del Rey

Q. Grady Minor and Associates, LLC 3800 Via Del Rey

Bonita Springs, Florida 34134 GradyMinor PAPE-DAWSONa company

TYPICAL SIDEWALK SECTION

NOT TO SCALE

TYPICAL ASPHALT SECTION

N.T.S.

SITE SIGN BASE DETAILS

N.T.S.

PLAN VIEW

BREAK AWAY CHANNEL POST

PARTIAL ELEVATION

TYPICAL PARKING SPACES DETAIL

N.T.S.

HANDICAPPEDSTANDARD

NOTES:

CONCRETE BUMPER GUARD

N.T.S.

ACCESSIBLE SIGN DETAILS

R7-8-FL & R7-8-250

N.T.S.

FTP-21-06

(R7-8-FL)

FTP-22-06

(R7-8-250)

NOTES:

SIDEWALK DETAIL

NOT TO SCALE

Q. Grady Minor and Associates, LLC 3800 Via Del Rey

Q. Grady Minor and Associates, LLC 3800 Via Del Rey

Bonita Springs, Florida 34134

Q. Grady Minor and Associates, LLC 3800 Via Del Rey

Q. Grady Minor and Associates, LLC 3800 Via Del Rey

Bonita Springs, Florida 34134

Q. Grady Minor and Associates, LLC 3800 Via Del Rey

Q. Grady Minor and Associates, LLC 3800 Via Del Rey

Bonita Springs, Florida 34134

1 Cover Sheet
2 General Notes
3 Aerial
4 Overall Site Plan
5 Overall Grading Paving and Drainage Plan
6 GPD-NW
7 GPD-NE
8 GPD-SW
9 GPD-SE
10 SECT-DTL
11 Utility Plan
12 Dtls-Gen
13 Dtls-Gen Util
14 Dtls-San
15 Dtls-Wtr
2025-10-03T17:58:27-0400
Alexander P. Dunko, P.E.

File details come from the government source that posted it. Updated .