24019_MECHANICAL_BID.pdf
PDF 785 KB Posted
- Attached to
- Grayton Beach Community Center
- Solicitation number
- ITB 24-35
- Issued by
- Walton County, Florida
About this file
Summary of 24019_MECHANICAL_BID.pdf
This mechanical bid document is a comprehensive HVAC specification and design plan prepared by W3 Engineering Inc. for the Grayton Beach Community Center project in Walton County, Florida. The document establishes detailed technical requirements for the installation of a complete mechanical system including HVAC equipment, ductwork, piping, and related components in compliance with Florida Building Code 2020 (7th Edition), National Electrical Code (2014), NFPA 101 Life Safety Code (2015), and ADA 2010 standards. The mechanical system design includes multiple equipment units designated as ERV1, OAHU1, OACU1, DCU1, EDH1, DAC1, and associated distribution components serving restroom facilities and mechanical/storage spaces across two floor levels. The contract encompasses the fabrication and installation of supply, return, and exhaust air ductwork with specified pressure classifications, insulation requirements, and sealing standards; concrete equipment pads with 6-inch minimum thickness; condensate drain systems; thermostat and humidity sensor installations; and vibration-free equipment mounting with appropriate access panels and inspection doors. The design includes supply air diffusers and registers equivalent to Titus 272FL models and return/exhaust registers equivalent to Titus 350FL models, with flexible duct limited to maximum 5-foot runs using factory-preinsulated Thermoflex or equivalent materials.
The technical specifications detail medium-pressure ductwork upstream of terminal units with 4 inches water column static pressure and SMACNA Seal Class A, low-pressure ductwork downstream of terminal units with 2 inches water column static pressure, and return/exhaust air ductwork with respective pressure classifications. All exposed ductwork must be double-wall spiral insulated galvanized finish suitable for painting, with insulation terminating at fire dampers and flexible connections. The document mandates coordination of all duct and piping dimensions with manufacturer recommendations prior to fabrication, verification of equipment clearances, and fire-stopping of all wall penetrations with listed firestop systems. Additional requirements include installation of emergency air distribution shutdown switches in accessible locations, maintenance of minimum 10-foot clearance between air intake and exhaust openings to prevent recirculation, provision of wind-driven rain-resistant hurricane louvers (Ruskin HZ700 basis of design), and installation of refrigerant line conduit coordinated with indoor unit manufacturers. The specification emphasizes strict adherence to SMACNA HVAC duct construction standards for hanger and support sizing, with detailed tables provided for minimum hanger specifications based on duct diameter and perimeter measurements.
View the file
Other files
Show all 29
On GovTribe
Work with this file
- Download the original file
- Contacts named in this file
- Similar government files
- Ask GovTribe AI about this file
Text version
1. ALL WORK SHALL COMPLY WITH ALL LOCAL BUILDING CODES, LAWS, REGULATIONS, ORDINANCES, AND CODES AS FOLLOWS:
" ACCESIBILITY: FLORIDA BUILDING CODE − 2020 7TH EDITION
" ENERGY CONSERVATION: FLORIDA BUILDING CODE − 2020 7TH EDITION
" BUILDING: FLORIDA BUILDING CODE − 2020 7TH EDITION
" EXISTING BUILDING: FLORIDA BUILDING CODE − 2020 7TH EDITION
" FUEL GAS: FLORIDA BUILDING CODE − 2020 7TH EDITION
" MECHANICAL: FLORIDA BUILDING CODE − 2020 7TH EDITION
" PLUMBING: FLORIDA BUILDING CODE − 2020 7TH EDITION
" NATIONAL ELECTRICAL CODE − 2014 EDITION
" NATIONAL FIRE PROTECTION ASSOCIATION (NFPA) 101, 2015 LIFE SAFETY CODE FOR FLORIDA
" APPLICABLE CODE SECTIONS AS REQUIRED BY FLORIDA ADMINISTRATIVE CODE 69A−3.012
" AMERICANS WITH DISABILITY ACT 2010 (ADA 2010)
CODE REFERENCESHVAC LEGEND
DETAIL NUMBER
SHEET NUMBER
DETAIL NUMBER
SHEET NUMBER
REFERENCE SHEET
EQUIPMENT
ABBREVIATION
EQUIPMENT
MARK
INDICATES AIR FLOW
INDICATES SCHEDULED TYPE
PBD
OBD
SUPPLY AIR DUCT UP
SUPPLY AIR DUCT DOWN
RETURN AIR DUCT UP
RETURN AIR DUCT DOWN
EXHAUST AIR DUCT UP
EXHAUST AIR DUCT DOWN
ø ø ø
W xH ø
W xH
WxH
SUPPLY AIR DIFFUSER/GRILLE TAG
WxH
RECTANGULAR SLIP AND DRIVE GALVANIZED
DUCTWORK, SIZES SHOWN ARE INTERNAL CLEAR
DIMENSIONS. FIRST FIGURE IS SIDE SHOWN.
ROUND SPIRAL SEAM GALVANIZED DUCTWORK.
SIZE SHOWN IS SHEET METAL DIAMETER.
ROUND BRANCH DUCT TAKEOFF FROM ROUND
DUCT MAIN. BRANCH DUCT SHALL BE ROUND
SNAPLOCK GALVANIZED STEEL DUCTWORK.
ROUND DUCT TAP IN SHALL BE MADE WITH SPIN−
IN COLLAR WITH MANUAL VOLUME DAMPER.
ROUND BRANCH DUCT TAKEOFF FROM
RECTANGULAR DUCT MAIN. BRANCH DUCT SHALL
BE ROUND SNAPLOCK GALVANIZED STEEL
DUCTWORK. ROUND DUCT TAP IN SHALL BE MADE
WITH SPIN−IN COLLAR WITH MANUAL VOLUME
DAMPER.
RECTANGULAR BRANCH DUCT TAKEOFF FROM
RECTANGULAR DUCT MAIN. BRANCH DUCT SHALL
BE RECTANGULAR SLIP AND DRIVE GALVANIZED
STEEL DUCTWORK. RECTANGULAR DUCT TAP IN
SHALL BE MADE WITH 45° COLLAR WITH MANUAL
VOLUME DAMPER.
RECTANGULAR MITERED ELBOW WITH TURNING
VANES.
RECTANGULAR LONG RADIUS ELBOW.
DIVERGING DUCT TRANSITION, UNLESS
OTHERWISE NOTED.
CONVERGING DUCT TRANSITION, UNLESS
OTHERWISE NOTED.
MODULATING OPPOSED BLADE DAMPER. LOW
LEAKAGE DAMPERS SHALL HAVE A MAXIMUM
LEAKAGE RATE OF 3CFM/SQUARE FOOT WITH A
DIFFERENTIAL PRESSURE OF 1 IN. W.G. ACROSS
THE DAMPER.
SHUTOFF PARALLEL BLADE DAMPER. LOW
LEAKAGE DAMPERS SHALL HAVE A MAXIMUM
LEAKAGE RATE OF 3CFM/SQUARE FOOT WITH A
DIFFERENTIAL PRESSURE OF 1 IN. W.G. ACROSS
THE DAMPER.
MANUAL VOLUME DAMPER, PROVIDE WITH
LOCKING QUADRANT
SPACE THERMOSTAT SERVING UNIT #, MOUNT 48"
A.F.F.; PROVIDE LOCKING THERMOSTAT COVER
SPACE HUMIDITY SENSOR, MOUNT 48" A.F.F.;
PROVIDE LOCKING THERMOSTAT COVER
DOOR UNDERCUT.
.0
0°
.0 0°
T
(S#) SIDE WALL MOUNTED SUPPLY REGISTER, EQUAL TO
"TITUS 272FL".
(R#) SIDE WALL MOUNTED RETURN REGISTER, EQUAL TO
"TITUS 350FL".
(E#) SIDE WALL MOUNTED EXHAUST REGISTER, EQUAL TO
"TITUS 350FL".
SECTION NUMBER
SHEET NUMBER
SECTION NUMBER
SHEET NUMBER
REFERENCE SHEET
LIMIT OF DEMOLITION.
CONNECT TO EXISTING.
RETURN/EXHAUST AIR GRILLE TAG
INDICATES AIR FLOW
INDICATES SCHEDULED TYPE ?
EQUIPMENT TAG
1/2"UC
H
MVD
AHU−1
1. INSTALL A COMPLETE AND OPERABLE MECHANICAL SYSTEM AS INDICATED ON THE DRAWINGS, AS SPECIFIED AND AS REQUIRED BY CODE.
2. CONTRACT DOCUMENT DRAWINGS FOR HVAC AND PLUMBING WORK ARE DIAGRAMMATIC AND ARE INTENDED TO CONVEY SCOPE AND GENERAL ARRANGEMENT ONLY.
3. INSTALL ALL MECHANICAL EQUIPMENT IN ACCORDANCE WITH MANUFACTURERS’ RECOMMENDATIONS, CONTRACT DOCUMENTS, AND APPLICABLE CODES AND REGULATIONS.
4. THE APPROXIMATE LOCATIONS OF EXISTING UNDERGROUND UTILITIES ARE SHOWN. THE CONTRACTOR SHALL DETERMINE THE EXACT LOCATION OF ALL EXISTING UTILITIES AND
PROTECT BEFORE COMMENCING WORK.
5. COORDINATE EQUIPMENT CLEARANCES (AS RECOMMENDED BY MANUFACTURER) WITH ALL DISCIPLINES BEFORE INSTALLATION.
6. COORDINATE AND PROVIDE ALL DUCT AND PIPING TRANSITIONS REQUIRED FOR FINAL EQUIPMENT CONNECTIONS TO FURNISHED EQUIPMENT, VERIFY AND COORDINATE ALL DUCT AND
PIPING DIMENSIONS BEFORE FABRICATION.
7. CONCRETE HOUSEKEEPING PADS TO SUIT MECHANICAL EQUIPMENT, MINIMUM CONCRETE PAD THICKNESS SHALL BE 6 IN. PAD SHALL EXTEND BEYOND THE EQUIPMENT A MINIMUM OF
6 IN. ON ALL SIDES.
8. PROVIDE ACCESS PANELS FOR INSTALLATION IN WALLS AND CEILINGS, WHERE REQUIRED, TO SERVICE DAMPERS, VALVES, AND OTHER CONCEALED MECHANICAL EQUIPMENT.
9. PROVIDE ACCESS DOORS IN DUCTWORK TO PROVIDE ACCESS FOR ALL SMOKE DETECTORS, FIRE DAMPERS, VOLUME DAMPERS, HUMIDIFIERS, COILS, AND OTHER ITEMS LOCATED IN THE
DUCTWORK THAT REQUIRE SERVICE AND/OR INSPECTION.
10. ALL EQUIPMENT, PIPING, DUCTWORK, ETC., SHALL BE SUPPORTED AS DETAILED, SPECIFIED, AND REQUIRED TO PROVIDE A VIBRATION−FREE INSTALLATION.
11. LOCATIONS AND SIZES OF ALL FLOOR, WALL AND ROOF OPENINGS SHALL BE COORDINATED WITH ALL OTHER TRADES INVOLVED.
12. ALL OPENINGS IN FIRE WALLS DUE TO DUCTWORK, PIPING, CONDUIT, ETC., SHALL BE FIRE STOPPED WITH LISTED FIRESTOP SYSTEM.
13. ALL EQUIPMENT REQUIRING CONDENSATE DRAIN LINES SHALL BE PIPED FULL SIZE OF THE UNIT DRAIN OUTLET, TRAPPED PER MANUFACTURERS DETAILS FOR ACTUAL EQUIPMENT AND STATIC PRESSURE. CONDENSATE SHALL BE PIPED TO THE NEAREST MECHANICAL ROOM FLOOR DRAIN OR JANITOR’S CLOSET SERVICE SINK. PROVIDE CONDENSATE PUMPS AS
REQUIRED.
14. REFER TO TYPICAL DETAILS FOR DUCTWORK, PIPING, AND EQUIPMENT INSTALLATION.
15. T’STATS INDICATED ADJACENT TO DOORWAYS SHALL BE LOCATED WITHIN 18" OF JAMB. AT LOCATIONS WITH LIGHT SWITCHES, LOCATE T’STAT SUCH THAT LIGHT SWITCH IS BETWEEN T’STAT AND JAMB. T’STATS SHALL BE LOCATED 48" AFF. VERIFY T’STAT LOCATIONS WITH SYSTEMS FURNITURE LAYOUT PRIOR TO INSTALLING ANY T’STAT.
16. ALL DUCTWORK DIMENSIONS, AS SHOWN ON THE DRAWINGS, ARE INTERNAL CLEAR DIMENSIONS.
17. COORDINATE DIFFUSER, REGISTER, AND GRILLE LOCATIONS WITH ARCHITECTURAL REFLECTED CEILING PLANS, LIGHTING, AND OTHER CEILING MOUNTED EQUIPMENT AND MAKE MINOR
DUCT MODIFICATIONS TO SUIT.
18. LOUVER DIMENSIONS INDICATED DOES NOT INCLUDE FRAME OR FLANGES. APPROXIMATE ROUGH OPENING IN WALL ASSEMBLY IS INDICATED ON ARCHITECTURAL.
19. AIR INTAKES OPENING TO EXTERIOR SHALL HAVE A MIN 10’−0" CLEARANCE FROM ANY EXHAUST OPENING TO PREVENT RECIRCULATION.
HVAC GENERAL NOTES
1. ROUND FLEXIBLE DUCT SHALL BE FACTORY PREINSULATED THERMOFLEX OR EQUAL. MAXIMUM LENGTH OF ANY FLEXIBLE DUCT RUNOUT SHALL BE 5’−0". WHERE LENGTH REQUIRED EXCEEDS 5’−0", INSTALL EXTERNALLY INSULATED ROUND SNAPLOCK DUCT TO SPIN−IN TAP AT MAIN DUCT TRUNK.
2. SUPPLY AIR DUCTWORK UPSTREAM OF TERMINAL UNITS SHALL BE MEDIUM PRESSURE ROUND OR OVAL SPIRAL SEAM. DUCT SYSTEM STATIC PRESSURE 4" W.C., DUCT SMACNA SEAL CLASS A, OVAL/ROUND DUCT SMACNA LEAK CLASS 3, AND DUCT TEST PRESSURE 4" W.G. UNLESS INDICATED OTHERWISE, EXTERNALLY INSULATED WITH 2" − 3/4 LB. MINERAL FIBER BLANKET FOR CONCEALED DUCT, AND 2" − 3LB. MINERAL FIBER BOARD WITH FACTORY APPLIED ASJ FOR EXPOSED DUCT.
3. SUPPLY AIR DUCTWORK DOWNSTREAM OF AIR TERMINAL UNITS (EXCEPT TAKEOFFS TO SUPPLY AIR DIFFUSERS) SHALL BE LOW PRESSURE ROUND OR RECTANGULAR. DUCT SYSTEM STATIC PRESSURE 2" W.C., DUCT SMACNA SEAL CLASS A, ROUND DUCT SMACNA LEAK CLASS 6, RECTANGULAR DUCT SMACNA LEAK CLASS 12, AND DUCT TEST PRESSURE 2" W.G.
UNLESS INDICATED OTHERWISE, EXTERNALLY INSULATED WITH 2" − 3/4 LB. MINERAL FIBER BLANKET FOR CONCEALED DUCT, AND 2" − 3LB. MINERAL FIBER BOARD WITH FACTORY
APPLIED ASJ FOR EXPOSED DUCT.
4. RETURN AIR DUCTWORK SHALL BE LOW PRESSURE RECTANGULAR. DUCT SYSTEM STATIC PRESSURE 2" W.C., DUCT SMACNA SEAL CLASS A, RECTANGULAR DUCT SMACNA LEAK CLASS
12, AND DUCT TEST PRESSURE 2" W.G.
5. EXHAUST AIR DUCTWORK SHALL BE LOW PRESSURE RECTANGULAR. DUCT SYSTEM STATIC PRESSURE 1" W.C., DUCT SMACNA SEAL CLASS A, RECTANGULAR DUCT SMACNA LEAK
CLASS 24, AND DUCT TEST PRESSURE 1" W.G.
6. OUTSIDE AIR INTAKE DUCTWORK SHALL BE LOW PRESSURE RECTANGULAR. DUCT SYSTEM STATIC PRESSURE 2" W.C., DUCT SMACNA SEAL CLASS A, RECTANGULAR DUCT SMACNA LEAK CLASS 12, AND DUCT TEST PRESSURE 2" W.G. UNLESS INDICATED OTHERWISE, EXTERNALLY INSULATED WITH 2" − 3/4 LB. MINERAL FIBER BLANKET FOR CONCEALED DUCT, AND
2" − 3LB. MINERAL FIBER BOARD WITH FACTORY APPLIED ASJ FOR EXPOSED DUCT.
7. EMERGENCY AIR DISTRIBUTION SHUTDOWN SWITCHES SHALL BE EASILY ACCESSIBLE BY BUILDING OCCUPANTS AND LOCATED IN A CONDITIONS SPACE AND ADJACENT TO OR IN BUILDING MASS NOTIFICATION SYSTEM LOCAL OPERATING CONSOLES (LOC.) SHUTOFF SWITCHES SHALL BE WELL LABELED, AND OF A DIFFERENT COLOR THAN FIRE ALARM PULL
STATIONS.
8. EXPOSED DUCTWORK SHALL BE DOUBLE−WALL SPIRAL INSULATED (MIN. R=4.2) GALVANIZED FINISH SUITABLE FOR PAINTING. PRIME AND PAINT WITH DRIP PROOF PAINT WITH COLOR
SELECTED BY ARCHITECT.
9. PROVIDE DUCT INSULATION IN ACCORDANCE WITH SPECIFICATION SECTION 23 07 00 THERMAL INSULATION FOR MECHANICAL SYSTEMS. INSULATION SHALL BE CONTINUOUS THROUGH SLEEVES AND PREPARED OPENINGS EXCEPT FIREWALL PENETRATIONS. TERMINATE DUCT INSULATION AT FIRE DAMPERS AND FLEXIBLE CONNECTIONS. FOR DUCT HANDLING AIR AT OR BELOW 60 DEGREES F, PROVIDE INSULATION CONTINUOUS OVER THE DAMPER COLLAR AND RETAINING ANGLE OF FIRE DAMPERS, WHICH ARE EXPOSED TO UNCONDITIONED AIR.
10. ALL DUCTWORK DIMENSIONS, AS SHOWN ON THE DRAWINGS, ARE INTERNAL CLEAR DIMENSIONS.
11. PROVIDE ALL 90−DEGREE SQUARE ELBOWS WITH TURNING VANES.
12. AVOID ROUTING DUCTWORK AND MECHANICAL EQUIPMENT OVER LIGHTS WHEREVER POSSIBLE. MAINTAIN MINIMUM 5" CLEARANCE BETWEEN MECHANICAL EQUIPMENT AND DUCT INSULATION TO TOP OF LIGHTS. PROVIDE CLEARANCE AND ACCESS ALL AROUND AND BELOW MECHANICAL EQUIPMENT AS REQUIRED FOR ROUTINE MAINTENANCE.
13. SEAL ALL DUCT PENETRATIONS OF WALLS AIRTIGHT, REGARDLESS OF WHETHER WALLS ARE FIRE RATED OR NOT.
14. MOUNT DUCTWORK AS HIGH AS POSSIBLE WHERE EXPOSED, UNLESS OTHERWISE NOTED.
TYPICAL DUCTWORK & INSULATION NOTES
SCALE:
877 CR 393 North Santa Rosa Beach, FL 32459 850.267.0759
A
54321
B
C
D
E
APPROVED BY
CHECKED BY
SHEET NO.
TITLE
DRAWN BY
DATE
PROJECT NO.
SCALE
SEAL
REVISIONS
NO. DESCRIPTION DATE
W3 Engineering Inc.
110 E. WRIGHT ST.
PENSACOLA, FL 32501
T: (850)629-8270
F: (888)478-4898
FL P.E. #: 70595
FL AUTHORIZATION #: 31078
James E. Wells III
P.E. Number: 70595
As indicated
/2
/2
:2
:5
A
M
M-001
LEGEND &
GENERAL NOTES
-G
R A
Y T
O N
B E
A C
H
E n te r a d d re s s h e re
7/15/24
BEJ
JEW3
JEW3
ISSUED FOR BID
MENS RESTROOM
MECHANICAL /
STORAGE
ELEV.
WOMENS
RESTROOM
M-301M-111
M-301M-111
ERV−1
OAHU−1
OACU−1
DCU−1
LVR−2
LVR−1
16" x 16" OA
DESIGNER NOTES:
4*70=280 4*50=250
6*70=420 6*50=300
290 sf * 1 cfm/sf = 290 cfm new ttl exhaust 760+290= 1050 cfm
E2
E1
S1
12" x 24" EA
14" x 14" OA x O A x E A
6" x 6" OA
S1
OBD
x
O A x
O A
T H
EDH−1
OAHU−1
E1
S2 x
E A
18" x 12" EA
SCALE:
877 CR 393 North Santa Rosa Beach, FL 32459 850.267.0759
A
54321
B
C
D
E
APPROVED BY
CHECKED BY
SHEET NO.
TITLE
DRAWN BY
DATE
PROJECT NO.
SCALE
SEAL
REVISIONS
NO. DESCRIPTION DATE
W3 Engineering Inc.
110 E. WRIGHT ST.
PENSACOLA, FL 32501
T: (850)629-8270
F: (888)478-4898
FL P.E. #: 70595
FL AUTHORIZATION #: 31078
James E. Wells III
P.E. Number: 70595
As indicated
/2
/2
:2
:5
A
M
M-111
HVAC OVERALL
FIRST FLOOR PLAN
-G
R A
Y T
O N
B E
A C
H
E n te r a d d re s s h e re
7/15/24
BEJ
JEW3
JEW3
ISSUED FOR BID
SCALE:
0 4’ 8’
1/4" = 1’ − 0"
4’ 8’
1/4" = 1’−0"
HVAC OVERALL FIRST FLOOR PLAN
SHEET NOTES
KEY # KEYNOTE TEXT
PROVIDE WIND−DRIVEN, RAIN RESISTANT, STATIONARY HURRICANE
LOUVER. COORDINATE FINAL COLOR AND ELEVATION W/ ARCHITECT
PRIOR TO ORDERING. BASIS OF DESIGN: RUSKIN HZ700
PROVIDE WIND−DRIVEN, RAIN RESISTANT, STATIONARY HURRICANE
LOUVER. COORDINATE FINAL COLOR AND ELEVATION W/ ARCHITECT
PRIOR TO ORDERING. BASIS OF DESIGN: RUSKIN HZ700
COORDINATE EXACT LOCATION AND ELEVATION OF EQUIPMENT PAD WITH
ARCHITECTURAL AND CIVIL.
ROUTE REFRIGERANT LINES IN CONDUIT TO ASSOCIATED INDOOR UNITS.
COORDINATE WITH THE MANUFACTURER FOR REFRIGERANT LINE SIZES
AND QUATITY. THE SIZE OF THE CONDUIT SHALL BE OF SUFFICIENT
DIAMETER TO ACCOMADATE THE REFRIGERNAT LINES.
LOCAL
INFORMATION
ELEV.
M-301M-111
M-301M-111
DAC−1
A
S3
T
DAC−1
SCALE:
877 CR 393 North Santa Rosa Beach, FL 32459 850.267.0759
A
54321
B
C
D
E
APPROVED BY
CHECKED BY
SHEET NO.
TITLE
DRAWN BY
DATE
PROJECT NO.
SCALE
SEAL
REVISIONS
NO. DESCRIPTION DATE
W3 Engineering Inc.
110 E. WRIGHT ST.
PENSACOLA, FL 32501
T: (850)629-8270
F: (888)478-4898
FL P.E. #: 70595
FL AUTHORIZATION #: 31078
James E. Wells III
P.E. Number: 70595
As indicated
/2
/2
:2
:5
A
M
M-112
HVAC OVERALL
SECOND FLOOR
PLAN
-G
R A
Y T
O N
B E
A C
H
E n te r a d d re s s h e re
7/15/24
BEJ
JEW3
JEW3
ISSUED FOR BID
SCALE:
0 4’ 8’
1/4" = 1’ − 0"
4’ 8’
1/4" = 1’−0"
HVAC OVERALL SECOND FLOOR PLAN
MECHANICAL /
STORAGE
LOCAL
INFORMATION
DAC−1
ERV−1
OAHU−1
OACU−1
DCU−1
LVR−1
LVR−2
S3
TH
/8
10' - 3 11/32"
"EDH−1
11' - 3 17/32"
/3
17' - 3 31/32"
OBD
E1
S1
260 MECHANICAL /
STORAGE
WOMENS
RESTROOM
MENS RESTROOM
OAHU−1
ERV−1
DAC−1
LVR−2
S1
S3
E1
S1
E2
S2
E1
12" x 12" OA
12" x 8" OA
12" x 6" OA
12" x 12" EA
SCALE:
877 CR 393 North Santa Rosa Beach, FL 32459 850.267.0759
A
54321
B
C
D
E
APPROVED BY
CHECKED BY
SHEET NO.
TITLE
DRAWN BY
DATE
PROJECT NO.
SCALE
SEAL
REVISIONS
NO. DESCRIPTION DATE
W3 Engineering Inc.
110 E. WRIGHT ST.
PENSACOLA, FL 32501
T: (850)629-8270
F: (888)478-4898
FL P.E. #: 70595
FL AUTHORIZATION #: 31078
James E. Wells III
P.E. Number: 70595
1/4" = 1'-0"
/2
/2
:2
:0
A
M
M-301
HVAC SECTIONS
-G
R A
Y T
O N
B E
A C
H
E n te r a d d re s s h e re
7/15/24
BEJ
JEW3
JEW3
ISSUED FOR BID
1/4" = 1’−0"
SECTION−1
1/4" = 1’−0"
SECTION−2
SCALE:
0 4’ 8’
1/4" = 1’ − 0"
4’ 8’
TYP.
OR
50" DIA. MAX.
> 50" DIA.
OR
MAXIMUM SPACINGDIA.
TABLE 4−2 MINIMUM HANGER SIZES FOR ROUND DUCT
12’−0"
WIRE DIA.
ONE 12 GA.
ROD
1/4"
STRAP
1"x22 GA.
NOTES:
" REFERENCE TO THE SMACNA HVAC DUCT CONSTRUCTION STANDARDS CHAPTER 4 HANGERS AND
SUPPORTS.
" STRAPS ARE GALVANIZED STEEL; RODS ARE UNCOATED OR GALVANIZED STEEL; WIRE IS BLACK
ANNEALED, BRIGHT BASIC, OR GALVANIZED STEEL. ALL ARE ALTERNATIVES.
" TABLE ALLOWS FOR CONVENTIONAL WALL THICKNESS, AND JOINT SYSTEMS PLUS ONE LB/SF INSULATION
WEIGHT. IF HEAVIER DUCTS ARE TO BE INSTALLED ADJUST HANGER SIZE TO BE WITHIN THEIR LOAD
LIMITS.
" FOR INDUSTRIAL GRADE SUPPORTS SEE SMACNA’S ROUND INSDUSTRIAL DUCT CONSTRUCTION STANDARDS.
" ALL EQUIPMENT MOUNTINGS ARE TO RESIST FORCES OF 0.5 TIMES THE EQUIPMENT WEIGHT IN ANY
HORIZONTAL DIRECTION AND 1.5 TIMES IN THE DOWNWARD DIRECTION.
5 5
1 2
31 2
3 4
10" DIA. MAX.
LOWER HANGER ATTACHEMENT NOTES
HANGER STRAP
HANGER ROD
METAL ANGLE
SCREW
LOCKNUT
LOAD RATED FASTENERS
SECURE WIRE
SCREWS MAY BE OMITTED IF HANGER LOOPS.
P/2 = 30" 1"x22 GA.
10FT SPACINGPERIMETER/2
TABLE 5−1 MINIMUM HANGER SIZES FOR
RECTANGULAR DUCT
P/2 = 72"
P/2 = 96"
P/2 = 120"
P/2 = 168"
P/2 = 192"
P/2 > 193"
STRAP WIRE/ROD
0.135"
1"x18 GA. 3/8"
1"x16 GA. 3/8"
1.5"x16 GA. 1/2"
1.5"x16 GA. 1/2"
− 1/2"
1"x22 GA.
8FT SPACING
STRAP WIRE/ROD
0.135"
1"x20 GA. 1/4"
1"x18 GA. 3/8"
1"x16 GA. 3/8"
1.5"x16 GA. 1/2"
1/2"
1"x22 GA.
5FT SPACING
STRAP WIRE/ROD
0.135"
1"x22 GA.
1"x20 GA.
1"x18 GA.
1"x16 GA.
4FT SPACING
STRAP WIRE/ROD
1.5"x16 GA. 1"x16 GA.
1/4"
3/8"
3/8"
3/8"
3/8"
1"x22 GA. 0.135"
1"x22 GA.
1"x22 GA.
1"x20 GA.
1"x18 GA.
1"x16 GA.
1/4"
1/4"
1/4"
3/8"
3/8"
SPECIAL ANALYSIS REQUIRED
NOTES:
" REFERENCE TO THE SMACNA HVAC DUCT CONSTRUCTION STANDARDS CHAPTER 4 HANGERS
AND SUPPORTS.
" ALL EQUIPMENT MOUNTINGS ARE TO RESIST FORCES OF 0.5 TIMES THE EQUIPMENT WEIGHT
IN ANY HORIZONTAL DIRECTION AND 1.5 TIMES IN THE DOWNWARD DIRECTION.
WHEN STRAPS ARE LAP JOINED USE
THESE MINIMUM FASTENERS:
1"x18, 20, 22 GA. − TWO #10 OR ONE 1/4" BOLT 1"x16 GA. − TWO 1/4" DIA.
1−1/2"x16 GA. − TWO 3/8" DIA
PLACE FASTENERS IN SERIES, NOT SIDE BY SIDE.
SINGLE HANGER MAXIMUM ALLOWABLE LOAD
STRAP WIRE OR ROD (DIA.)
1"x22 GA. − 260 LBS.
1"x20 GA. − 320 LBS.
1"x18 GA. − 420 LBS.
1"x16 GA. − 700 LBS.
1−1/2"x16 GA. − 1100 LBS.
0.106" − 80 LBS.
0.135" − 80 LBS.
0.162" − 80 LBS.
1/4" − 80 LBS.
3/8" − 80 LBS.
1/2" − 80 LBS.
5/8" − 80 LBS.
3/4" − 80 LBS.
<10"
12’−0" TWO 12 GA. OR ONE 8 GA.1/4" 1"x22 GA.11−18"
12’−0" TWO 10 GA. 1/4" 1"x22 GA.19−24"
12’−0" 3/8" 1"x20 GA.25−36"
12’−0" TWO 3/8" TWO 1"x20 GA.37−50"
12’−0" TWO 1"x18 GA.51−60"
12’−0" TWO 1"x16 GA.61−84"
TWO 8 GA.
TWO 3/8"
TWO 3/8"
RECTANGULAR SUPPLY DUCTWORK ONLY.
RETURN OR EXHAUST AIRFLOW IS REVERSED.
F L O W
45° COLLAR TAKE−OFF WITH ADJUSTABLE VOLUME
DAMPER WITH POSITIONING LEVER, EXTENSION
SECTION (INSULATED DUCT ONLY) AND LOCKING
WING NUT. VOLUME DAMPER SHALL BE SINGLE
BLADE OR MULTI−BLADE DEPENDING ON DUCT SIZE,
SEE SPECIFICATIONS. LOCATE DAMPER AT LEAST
12" DOWNSTREAM OF TAKEOFF.
WIDTH/4", 4" MIN.
1" OR 2" INSULATION WITH MINIMUM
1−1/2 POUND DENSITY COATED
FIBROUS GLASS MATERIAL HAVE A
THERMAL CONDUCTIVITY NOT
GREATER THAN 0.23 BTU/HR−SF−F.
ADJUSTABLE ROLLER HANGER
WELD SADDLE
TO PIPE.
HANGER ROD
ADJUSTABLE CLEVIS HANGER
SIDE VIEW
BAND
NOTE:
" REFER TO STANDARD PRACTIC MSS SP−58 MAXIMUM HORIZONTAL PIPE AND
SUPPORT SPACING.
" FOR TRAPEZE HANGER TAKE SPACING OF SMALLEST SIZE ON TRAPEZE.
" ALL EQUIPMENT MOUNTINGS ARE TO RESIST FORCES OF 0.5 TIMES THE
EQUIPMENT WEIGHT IN ANY HORIZONTAL DIRECTION AND 1.5 TIMES IN THE
DOWNWARD DIRECTION.
INSULATION SHEILD
AT HANGER.
PROVIDE HIGH
COMPRESSIVE
STRENGTH INSULATION
INSERT BLOCKS UNDER
INSULATION SHIELD.
INSULATION (VAPOR
BARRIER TYPE IS
REQUIRED FOR LOW
TEMPERATURE PIPE).
HANGER
ROD
INSULATION (VAPOR
BARRIER TYPE IS
REQUIRED FOR LOW
TEMPERATURE PIPE).
i" DIA. HANGER RODS WITH
36" MAX SPACING ON EACH
CHENNEL.
PROVIDE INSULATION
SHIELD AND INSERT FOR
ALL PIPING MAX 8".
12 GAGE
CHANNEL OR 2"
X 2" X r" ANGLE.
CARRIER
PIPE.
STANDARD PRACTICE MSS SP−58 TABLE 4 MAXIMUM
HORIZONTAL PIPE HANGER AND SUPPORT SPACING
NOMINAL PIPE
OR TUBE SIZE
STD WEIGHT STEEL PIPE COPPER TUBE FIRE
PROTECTION
DUCTILE IRON
PIPE
CAST IRON
SOIL
GLASS PLASTIC
FIBERGLASS
REINFORCEDWATER SERVICE VAPOR SERVICE WATER SERVICE VAPOR SERVICE
NPS−IN FT FT FT FT
F O L L O W
R E Q U
IR
E M E N T S O
F T
H E N
A T
IO
N A L F
IR
E P
R O T E C T
IO
N
A S S O C
IA
T
IO
N S E E
S E C T
IO
N
.4
F T M
A X S
P A C
IN
G M
IN
O F O
N E 1) H
A N G E R P
E R P
IP
E S
E C T
C L O S E T
O J
O
IN
T O
N T H E B
A R R E L A L S O A
T C
H A N G E O
F D
IR
E C T
IO
N A
N D B
R A N
H
O N N E C T
IO
N S S E E
S E C T
IO
N
.3 .4
F
T M
A X S
P A C
IN
G M
IN
O F O
N E 1) H
A N G E R P
E R P
IP
E S
E C T
O S E T
O J
O
IN
T O
N T H E B
A R R E L A L S O A
T C
H A N G E O
F D
IR
E C T
IO
N A
N D B
R A N
H
O N N E C T
IO
N S S E E
S E C T
IO
N
.3 .4
F
T M
A X S
P A C
IN
G F O L L O W
P
IP
E M
A N U F A C T U R E R ’S
R E C O M M E N D A T
IO
N S S
E E S
E C T
IO
N .3
.5
F O L L O W
P
IP
E M
A N U F A C T U R E R ’S
R E C O M M E N D A T
IO
N S F
O R M
A T E R
IA
D S
E R V
IC
E C O N D
IT
IO
N S E E S
E C T
IO
N
.3 .6
F O L L O W
P
IP
E M
A N U F A C T U R E R ’S
R E C O M M E N D A T
IO
N S F
O R M
A T E R
IA
D S
E R V
IC
E C O N D
IT
IO
N S E E S
E C T
IO
N
.3 .7
1/4 − − 5 5
3/8 7 8 5 6
1/2 7 8 5 6
3/4 7 9 5 7
1 7 9 6 8
1 1/4 7 9 7 9
1 1/2 9 12 8 10
2 10 13 8 11
2 1/2 11 14 9 13
3 12 15 10 14
3 1/2 13 16 11 15
4 14 17 12 16
5 16 19 13 18
6 17 21 14 20
8 19 24 16 23
10 22 26 18 25
12 23 30 19 28
14 25 32 − −
16 27 35 − −
18 28 37 − −
20 30 39 − −
24 32 42 − −
30 33 44 − −
NOTE:
(A) FOR SPACING SUPPORTS INCORPORATING TYPE 40 SHEILDS, SEE TABLE A3.
(B) THIS TABLE DOES NOT APPLY WHERE SPAN CALCULATIONS ARE MADE OR WHERE THERE ARE CONCENTRATED LOADS BETWEEN SUPPORTS SUCH AS FLANGES, VALVES, SPECIALTIES, ETC., OR CHANGES IN DIRECTION REQUIRING ADDITIONAL SUPPORTS.
(C) UNBALANCED FORCES OF HYDROSTATIC OR HYDRODYNAMIC ORIGIN (THRUST FORCES) UNLESS RETRAINED EXTERNALLY CAN RESULT IN PIPE
MOVEMENT AND SEPARATION OF JOINTS IF THE JOINTS OF THE SYSTEM ARE
NOT OF A RESTRAINED JOINT DESIGN. SEE SECTION 7.5.3.
SCALE:
877 CR 393 North Santa Rosa Beach, FL 32459 850.267.0759
A
54321
B
C
D
E
APPROVED BY
CHECKED BY
SHEET NO.
TITLE
DRAWN BY
DATE
PROJECT NO.
SCALE
SEAL
REVISIONS
NO. DESCRIPTION DATE
W3 Engineering Inc.
110 E. WRIGHT ST.
PENSACOLA, FL 32501
T: (850)629-8270
F: (888)478-4898
FL P.E. #: 70595
FL AUTHORIZATION #: 31078
James E. Wells III
P.E. Number: 70595
NOT TO SCALE
/2
/2
:2
:0
A
M
M-501
HVAC DETAIL SET-1
-G
R A
Y T
O N
B E
A C
H
E n te r a d d re s s h e re
7/15/24
BEJ
JEW3
JEW3
ISSUED FOR BID
Not to Scale
DUCT HANGER DETAIL
Not to Scale
DUCT RECTANGULAR BRANCH TAKEOFF DETAIL
Not to Scale
PIPE HANGER DETAIL
w r
NOTES:
" THE INTERIOR SURFACE OF ALL RADIUS ELBOWS SHALL BE MADE ROUND.
" ALL STANDARD RADIUS ELBOWS SHOWN ON FLOOR PLANS MAY BE MADE
SHORT RADIUS ELBOWS. ALL SHORT RADIUS ELBOWS SHALL HAVE VANES.
VANES SHALL BE CONSTRUCTED, SUPPORTED AND FASTENED AS
RECOMMENDED BY SMACNA.
r SHALL EQUAL
OR BE GREATER
THAN w r SHALL EQUAL
OR BE GREATER
THAN 1/3 w r SHALL EQUAL
OR BE GREATER
THAN 1/8 w
STANDARD
RADIUS
ELBOW
STANDARD
RADIUS
ELBOW
STANDARD
RADIUS
ELBOW
r
2/3w
1/3w 1/3w
1/3w r
1/6w w w
VANE VANE
NOTES:
" ALL VANED ELBOWS SHALL BE CONSTRUCTED AND INSTALLED AS DETAILED BY SMACNA.
" WHEN W1 DOES NOT EQUAL W2, VANE SHALL BE SINGLE VANE TYPE REGARDLESS OF W
DIMENSTION.
" ALL SINGLE VANES SHALL HAVE A 2" RADIUS, 1−1/2" MAXIMUM SPACE BETWEEN VANES AND
A 3/4" TRAILING EDGE.
" WHEN W EQUALS W2 AND W1 IS GREATER THAN 20" VANES SHALL BE DOUBLE VANE TYPE.
W1
W2
REFER TO
NOTES
BELOW. CONVERGING DUCT TRANSITION
30 DEGREE MAXIMUM
DIVERGING DUCT TRANSITION
30 DEGREE MAXIMUM
20 DEGREE MAXIMUM
20 DEGREE MAXIMUM
NOTES:
" UNLESS NOTED OTHERWISE ON PLANS,
ANGLES SHOWN SHALL APPLY.
4" MIN FINISHED
FLOOR
PIPE SLEEVE
OR CONDUIT
C A R R
IE
R P
IP
E
NOTES:
" FOR CATHODIC PROTECTION, PIPE SLEEVE
SHALL BE NON−METALLIC OR NON−
METALLIC LINK SEAL TYPE FITTING TO
ENSURE NO CONTACT WITH REBAR.
1" CLEARANCE AROUND PIPE, SEAL
BOTH SIDES OF PENETRATION WITH
APPROVED SEALANT AND FINISHED
TO TOP OF SLEEVE.
CARRIER PIPE
NOTES:
" FOR SECURITY WALLS REFER TO SECURITY
BOUNDARY PIPE PENETRATION DETAILS.
ESCUTCHEON PLATE
FOR PIPING EXPOSED
TO VIEW.
PROVIDE PLASTIC PIPE SLEEVE IN
NONBEARING WALLS. PROVIDE
SCHEDULE 40 STEEL PIPE SLEEVE IN
BEARING WALLS AND CONNECT GROUND
WIRE TO BUILDING GROUND. SLEEVE
SHALL BE FLUSH WITH FINISH WALL.
INTERIOR WALL.
1" CLEARANCE AROUND PIPE, SEAL
BOTH SIDES OF PENETRATION WITH
APPROVED UL−LISTED ELASTOMERIC
SEALANT AND FINISHED TO MATCH
WALL.
PIPE INSULATION AS REQUIRED.
INSULATION SHALL BE PROVIDED
WITH THE SAME PERFORMANCE AS
THE FIRESTOPPING MATERIAL.
NOTE:
" UNLESS OTHERWISE APPROVED ALLOWABLE LOAD ON UPPER ATTACHEMENTS IS 1/4 OF FAILURE LOAD.
" UPPER ATTACHMENTS MAY BE TO WOOD STRUCTURES ALSO.
" WIRE USE IS NOT PRECULDED BY THESE ILLUSTRATIONS.
" NOT ALL ATTACHMENT DEVICES SHOWN, REFER TO SMACNA DUCT CONSTRUCTION STANDARDS.
FLAT BAR CONCRETE INSERT
#1 #4 #5*
#3b*
WASHER
WASHER
STRAP
NUT
#7* #8 #9*
WASHER
EXPANSION SHIELDS EXPANSION NAIL
CONCRETE ANCHORS
RETAINING CLIP
HANGER ROD
#6a C−CLAMP WITH RETAINING CLIP OR #6b C−CLAMP WITH LOCK NUT
(OPTIONAL)
A HANGER STRAP MAY ALSO BE C
CLAMPED TO THE STRUCTURAL FLANGE.
#10 #11 #12 #13*
HANGER
STRAP
COUPLING
HANGER ROD
HANGER
STRAP
NUT & BOLT
FRICTION CLAMPSWELDED STUDSPOWER ACTUATED
STUDS INTO STEEL
(STRUCTURE OR DECK)
NUT
ALTERNATE
#14
WASHER MAY BE OMITTED
WITH 100 LB MAX LOAD ON
22 GA STRAP WHEN
FOLDED.
SCALE:
877 CR 393 North Santa Rosa Beach, FL 32459 850.267.0759
A
54321
B
C
D
E
APPROVED BY
CHECKED BY
SHEET NO.
TITLE
DRAWN BY
DATE
PROJECT NO.
SCALE
SEAL
REVISIONS
NO. DESCRIPTION DATE
W3 Engineering Inc.
110 E. WRIGHT ST.
PENSACOLA, FL 32501
T: (850)629-8270
F: (888)478-4898
FL P.E. #: 70595
FL AUTHORIZATION #: 31078
James E. Wells III
P.E. Number: 70595
As indicated
/2
/2
:2
:0
A
M
M-502
HVAC DETAIL SET-2
-G
R A
Y T
O N
B E
A C
H
E n te r a d d re s s h e re
7/15/24
BEJ
JEW3
JEW3
ISSUED FOR BID
Not to Scale
DUCT FITTING RADIUS ELBOWS
Not to Scale
DUCT FITTING SQUARE VANED ELBOW
Not to Scale
DUCT FITTING TRANSITION DETAIL
Not to Scale
PIPE PENETRATION THROUGH MECHANICAL ROOM
FLOOR DETAIL
Not to Scale
PIPE PENETRATION THROUGH NONSECURE
INTERIOR WALL DETAIL
Not to Scale
UPPER ATTACHMENT DEVICE DETAILS
FCU
TYPICAL 5/16" THREADED ROD W/DOUBLE LOCK NUTS
ANGLE CROSS BRACING. USE RUBBER GROMMETS ON
RODS FOR ISOLATION. LOCATE RODS SO THAT THEY
DO NOT INTERFERE WITH ACCESS PANEL REMOVAL.
ANGLED 1"x1"x1/8" OR UNISTRUTNOTE:
" MOUNT UNITS HIGH ENOUGH TO HAVE 1/4"
PER FOOT SLOPE ON ALL DRAIN LINES
" SHUT DOWN UNIT IN THE EVENT OF A
CONDENSATE OVERFLOW.
FLEX CONNECTION
RETURN AIR SUPPLY AIR
NOTE:
" SECURE UNIT TO PAD. SIZE
CONCRETE PAD 6" LARGER THAN
UNIT ON ALL SIDES.
6" REINFORCE CONCRETE PAD
WITH 6x6x10x10 WELDED WIRE
MESH PANEL.
STRAP UNIT TO CONCRETE PAD
WITH ALUMINUM ANGLE STRAPS AND
STAINLESS STEEL FASTENERS.
PROVIDE (2) STAPS ON ALL SIDES.
INSULATED REFRIGERANT PIPE
SIZE PER MANUFACTURER.
IN PVC CONDUIT, SEAL
CONDUIT WATERTIGHT.
OUTDOOR CONDENSING UNIT
TO AIR HANDLER DEPTH SHALL VARY AS REQUIRED TO
PREVENT CONFLICT WITH OTHER
TRADES.
SIZE CONDUIT PER
MANUFACTURER’S
RECOMMENDATION, (MIN. 6")
FACTORY RUBBER−IN−
SHEAR ISOLATORS.
4" MIN.
2" MIN.
HURRICANE LOUVER WITH BIRD
SCREEN. REFER TO LOUVER
SCHEDULE FOR SIZE.
SEALANT & BACKER ROD.
SEALANT & BACKER ROD.
SPACER BY OTHER
FASTENERS
2" INSULATED BLANK OFF
PANEL.
LOUVER SUPPORT AS
REQUIRED.
AIR FOIL, CLASS 1A LEAKAGE,
LOW LEAKAGE DAMPER.
FRAME
TAB
DUCT
FRAME &
DOOR SEAL
DOOR HINGE
DOOR INSULATION
DOOR PANEL
ACCESS DOOR.
SCALE:
877 CR 393 North Santa Rosa Beach, FL 32459 850.267.0759
A
54321
B
C
D
E
APPROVED BY
CHECKED BY
SHEET NO.
TITLE
DRAWN BY
DATE
PROJECT NO.
SCALE
SEAL
REVISIONS
NO. DESCRIPTION DATE
W3 Engineering Inc.
110 E. WRIGHT ST.
PENSACOLA, FL 32501
T: (850)629-8270
F: (888)478-4898
FL P.E. #: 70595
FL AUTHORIZATION #: 31078
James E. Wells III
P.E. Number: 70595
As indicated
/2
/2
:2
:0
A
M
M-503
HVAC DETAIL SET-3
-G
R A
Y T
O N
B E
A C
H
E n te r a d d re s s h e re
7/15/24
BEJ
JEW3
JEW3
ISSUED FOR BID
Not to Scale
FAN COIL UNIT HORIZONTAL MOUNTING DETAIL
Not to Scale
HEAT PUMP UNIT PIPING AND MOUNTING DETAIL
Not to Scale
LOUVER ASSEMBLY DETAIL
SCALE:
877 CR 393 North Santa Rosa Beach, FL 32459 850.267.0759
A
54321
B
C
D
E
APPROVED BY
CHECKED BY
SHEET NO.
TITLE
DRAWN BY
DATE
PROJECT NO.
SCALE
SEAL
REVISIONS
NO. DESCRIPTION DATE
W3 Engineering Inc.
110 E. WRIGHT ST.
PENSACOLA, FL 32501
T: (850)629-8270
F: (888)478-4898
FL P.E. #: 70595
FL AUTHORIZATION #: 31078
James E. Wells III
P.E. Number: 70595
/2
/2
:2
:0
A
M
M-601
HVAC SCHEDULES
-G
R A
Y T
O N
B E
A C
H
E n te r a d d re s s h e re
7/15/24
BEJ
JEW3
JEW3
ISSUED FOR BID
OUTDOOR AIR HANDLING UNIT SCHEDULE
MARK
AIR DATA COOLING DATA HEATING DATA
EVAPORATOR FAN
DATA
ELECTRICAL DATA
DESCRIPTION
MIN. AIR
FLOW
E.S.P
TOTAL COOLING
CAPACITY
SENSIBLE COOLING
CAPACITY
AMBIENT
AIR TEMP.
COIL ENT.
(DB/WB)
HEATING
CAPACITY
AMBIENT
AIR TEMP.
COIL ENT.
(DB)
# FLA VOLTAGE PHASE HZ MCA MOCP
OAHU−1 950 0.60 in−wg 68500.0 Btu/h 26300.0 Btu/h 95 °F 91 / 82 32800.0 Btu/h 47 °F 41 / 36 2 3.8 / 3.5 208 / 230 1 60 4.8 / 4.3 15 BASIS OF DESIGN: MITSUBISHI PEFY−P72NMHU−OA
OUTDOOR AIR CONDENSING UNIT SCHEDULE
MARK
REFRIGERANT
TYPE
COOLING DATA HEATING DATA CONDENSER FAN DATA COMPRESSOR DATA ELECTRICAL DATA
DESCRIPTION
TOTAL COOLING CAPACITY AMBIENT AIR TEMP. HEATING CAPACITY AMBIENT AIR TEMP. # KW # KW VOLTAGE PHASE HZ MCA MOCP
OACU−1 R−410A 72000.0 Btu/h 95 °F 80000.0 Btu/h 47 °F 1 0.92 1 5.4 208 / 230 3 60 25 / 24 30 BASIS OF DESIGN: MITSUBISHI PUHY−P72TJMU−A−BS
NOTES:
" UNIT CAPACITIES RATED AT ARI CONDITIONS @ NONIMAL AIRFLOW.
" PROVIDE FACTORY SUPPLIED WIRED WALL−MOUNTED PROGRAMMABLE THERMOSTAT. LOCATE AS INDICATED.
" PROVIDE BLUE DIAMOND PUMPS MICROBLUE CONDENSATE PUMP FOR EACH AHU.
" PROVIDE VIBRATION ISOLATION.
" AIR FILTER FIELD SUPPLY.
" UNIT FEATURES: BUILT−IN CONDENSATE LIFT.
" CONTRACTOR SHALL ALLOW 0.2 INCHES EXTRA STATIC DROP FOR DIRTY FILTERS.
NOTES:
" UNIT CAPACITIES RATED AT ARI CONDITIONS @ NONIMAL AIRFLOW.
" UNIT FEATURES: MAX. REFRIGERANT LINE LENGTH 541 FT, AND SEACOAST PROTECTION RATED FOR 2,000 HOURS IN ACCORDANCE WITH ASTM B117 TESTING.
ENERGY RECOVERY UNIT SCHEDULE
MARK
OUTSIDE AIR FAN DATA EXHAUST FAN DATA ENERGY RECOVERY PERFORMACE ELECTRICAL DATA
DESCRIPTION
OA FLOW OA E.S.P EA FLOW EA E.S.P. SUMMER ENTHALPY % WINTER ENTHALPY % VOLTAGE PHASE HZ MCA MOCP
ERV−1 950 0.60 in−wg 1050 0.60 in−wg 52 57 208 / 230 1 60 10.1 15 BASIS OF DESIGN: MITSUBISHI LGH−F940RVX2−E
NOTES:
" ALL EXHAUST FANS SHALL BE INSTALLED WITH FLEXIBLE DUCT CONNECTION, VIBRATION ISOLATORS, AND FLEXIBLE CONDUIT, FAN SHALL NOT BE IN
CONTACT WITH ANY OTHER DUCT, PIPING, CONDUIT, OR STRUCTURAL MEMBERS.
" FANS SHALL BE PROVIDED WITH BACKDRAFT DAMPERS.
" ALL DIRECT DRIVE FANS WITH MOTORS LESS THAN 1/2 HP SHALL BE PROVIDED WITH AN ADJUSTABLE ELECTRONIC SPEED CONTROLLER.
DUCTLESS SPLIT AIR HANDLING UNIT SCHEDULE
MARK
AIR DATA COOLING DATA HEATING DATA ELECTRICAL DATA
DESCRIPTION
AIR FLOW (L/M/H)
MAX.
E.S.P
TOTAL COOLING
CAPACITY
SENSIBLE COOLING
CAPACITY
AMBIENT
AIR TEMP.
COIL ENT.
(DB/WB)
HEATING
CAPACITY
AMBIENT
AIR TEMP.
COIL ENT.
(DB)
VOLTAGE PHASE HZ
SYSTEM
MCA
DAC−1 740 / 1,060 / 1,200 0.50 in−wg 42000.0 Btu/h 33180.0 Btu/h 95 °F 80/67 45000.0 Btu/h 47 °F 70/60 208 / 230 1 60 2 BASIS OF DESIGN: MITSUBISHI PLA−A42EA7
DUCTLESS SPLIT HEAT PUMP UNIT SCHEDULE
MARK
REFRIGERANT
TYPE
COOLING DATA HEATING DATA ENERGY PERFORMANCE
CONDENSER FAN
DATA
COMPRESSOR DATA ELECTRICAL DATA
DESCRIPTION
TOTAL COOLING
CAPACITY
AMBIENT
AIR TEMP.
HEATING
CAPACITY
AMBIENT
AIR TEMP.
EER / SEER HSPF / COP # FLA # RLA VOLTAGE PHASE HZ
SYSTEM
MCA
SYSTEM
MOCP
DCU−1 R−410A 42000.0 Btu/h 95 °F 45000.0 Btu/h 43 °F 11.6 / 21 9.3 / 4 2 0.5 + 0.5 1 8 208 / 230 1 60 25 31 BASIS OF DESIGN: MITSUBISHI PUZ−A42NKA7−BS
NOTES:
" UNIT CAPACITIES RATED AT ARI CONDITIONS @ NONIMAL AIRFLOW.
" UNIT FEATURES: POWER RECEIVER PRE−CHARGED WITH REFRIGERANT VOLUME FOR PIPING LENGTH UP TO 100 FT, LOW AMBIENT COOLING DOWN TO 0°F PROVIDING 100% CAPACITY, AND
SEACOAST PROTECTION RATED FOR 2,000 HOURS IN ACCORDANCE WITH ASTM B117 TESTING.
" CONTRACTOR SHALL VERIFY THAT THE INDOOR UNIT IS POWERED BY THE OUTDOOR UNIT.
NOTES:
" UNIT CAPACITIES RATED AT ARI CONDITIONS @ NONIMAL AIRFLOW.
" UNIT FEATURES: FILTER INDICATOR SIGNAL, WASHABLE FILTER, BUILT−IN CONDENSATE LIFT MECHANISM, AND WIRED OR WIRELESS CONTROLLERS.
" CONTRACTOR SHALL VERIFY THAT THE INDOOR UNIT IS POWERED BY THE OUTDOOR UNIT.
DIFFUSER AND REGISTER SCHEDULE
MARK MIN. FLOW MAX. FLOW DUCT CONNECTION SIZE DESCRIPTION
E1 240 290 12" x 6" ALUMINUM LOUVERED RETURN GRILLE, 3/4" BLADE SPACING, 35 DEGREE DEFLECTION, LONG BLADES;
BASIS OF DESIGN: TITUS 350FL
E2 420 600 12" x 12" ALUMINUM LOUVERED RETURN GRILLE, 3/4" BLADE SPACING, 35 DEGREE DEFLECTION, LONG BLADES;
BASIS OF DESIGN: TITUS 350FL
S1 240 320 12" x 6" ALUMINUM AEROBLADE DOUBLE DEFLECTION SUPPLY GRILLE, 3/4" BLADE SPACING, FRONT BLADES
PARALLEL TO LONG DIMENSION; BASIS OF DESIGN: TITUS 272FL
S2 340 440 12" x 8" ALUMINUM AEROBLADE DOUBLE DEFLECTION SUPPLY GRILLE, 3/4" BLADE SPACING, FRONT BLADES
PARALLEL TO LONG DIMENSION; BASIS OF DESIGN: TITUS 272FL
S3 60 190 16" x 8" LINEAR BAR DIFFUSER FOR UNDERFLOOR APPLICATIONS; BASIS OF DESIGN: TITUS CT−TAF−480
LOUVER SCHEDULE
MARK SYSTEM FLOW CFM SIZE
PRESSURE
DROP
FREE AREA
VELOCITY
FPM
FREE
AREA
FT^2
DESCRIPTION
LVR−1 INTAKE 950 36"x24" 0.03 in−wg 342 FPM 2.78 BASIS OF DESIGN: RUSKIN HZ700MD
LVR−2 EXHAUST 1050 36"x24 0.04 in−wg 377 FPM 2.78 BASIS OF DESIGN: RUSKIN HZ700MD
NOTES:
" PROVIDE AIR DEVICE WITH DUCT CONNECTION SHOWN ON SCHEDULE UNLESS OTHERWISE NOTED ON PLANS.
" MAXIMUM NC FOR DEVICES IS 20.
" PROVIDE REGISTERS WITH BALANCING DAMPERS.
" CONTRACTOR SHALL PROVIDE ADDITIONAL BALANCING DAMPERS EACH BRANCH OF RETURN/EXHAUST DUCT AS REQUIRED FOR BALANCING SYSTEM.
NOTES:
" PRODUCT FEATURES AMCA 550 LISTED AND AMCA 540 LISTED.
ROOM SETPOINT SCHEDULE
INSIDE − GENERAL
SPACE COOLING SETPOINT HEATING SETPOINT HUMIDITY SETPOINT
NIGHT SETBACK
COOLING SETPOINT
74 DEG F 68 DEG F 50% RH 85 DEG F
NIGHT SETBACK
HEATING SETPOINT
55 DEG F
NIGHT SETBACK
HUMIDITY SETPOINT
65% RH
DEADBAND
3 DEG F
ELECTRIC DUCT HEATER SCHEDULE
MARK DUCT CONNECTION SIZE
VELOCITY
FPM
WATTS/FT
^2 KW VOLTAGE PHASE HZ DESCRIPTION
EDH−1 14"x14" 772 FPM 13,500 10 120 1 60 GREENHECK IDHB
FAN
M
MS
HSYK
STATUS
OK/ALARM
DX COILFILTERCU
YK
STATUS
OK/ALARM
T
TT
SEQUENCE OF OPERATION DUCTLESS SPLIT SYSTEM
START/STOP:
1. THE FAN SHALL BE ENABLED/DISABLED THROUGH "HAND−OFF−AUTO" (HOA) CONTROLS ACCORDING TO
ITS’ OCCUPIED/UNOCCUPIED SCHEDULE. IN THE ’AUTO’ MODE, THE UNIT SHALL BE STARTED
AUTOMATICALLY BASED ON THE ROOM TEMPERATURE SENSOR, SUBJECT TO FIRE ALARM RELAYS AND
SAFETIES.
TEMPERATURE CONTROL:
1. WHEN ROOM/SPACE TEMPERATURE RISES ABOVE COOLING SETPOINT THE LCM SHALL ACTIVATE THE
OUTDOOR UNIT REVERSING VALVE AND CYLE COMPRESSOR COOLING AS NEEDED TO SATISFY ROOM
TEMPERATURE SET POINT.
2. WHEN ROOM/SPACE TEMPERATURE FALLS BELOW HEATING SETPOINT THE LCM SHALL DEACTIVATE THE OUTDOOR UNIT REVERSING VALVE AND CYCLE COMPRESSOR HEAT AS NEEDED TO SATISFY ROOM
TEMPERATURE SET POINT.
CONDENSATE STATUS:
1. THE LCM SHALL MONITOR CONDENSATE OVERFLOW AND SHUT DOWN THE UNIT WHEN ACTIVATED.
RA SA
TK
THERMOSTAT
ROOM/SPACE
7 DAY PROGRAMMABLE
H.O.A.
ERV SUPPLY FAN
SEQUENCE OF OPERATION OUTSIDE AIR UNIT & ERV
START/STOP:
1. THE FAN SHALL BE ENABLED/DISABLED THROUGH "HAND−OFF−AUTO" (HOA) CONTROLS ACCORDING TO ITS’ OCCUPIED/UNOCCUPIED SCHEDULE. IN THE ’AUTO’ MODE, THE UNIT
SHALL BE STARTED AUTOMATICALLY BASED ON THE ROOM TEMPERATURE SENSOR, SUBJECT TO FIRE ALARM RELAYS AND SAFETIES.
2. THE LCM SHALL MONITOR THE ROOM/SPACE TEMPERATURE AND RELATIVE HUMIDITY.
INTERLOCKS:
1. WHEN OAHU SUPPLY FAN IS ENERGIZED, ENERGIZE ERV SUPPLY FANS, AND EXHAUST FANS.
OAHU TEMPERATURE & HUMIDITY CONTROL:
1. WHEN THE FAN STARTS THE CONTROL SYSTEM SHALL BE ACTIVATED.
2. WHEN THE ROOM/SPACE TEMPERATURE RISES ABOVE COOLING SETPOINT THE LCM SHALL ACTIVATE THE OUTDOOR UNIT AND CYCLE COMPRESSOR DX COOLING AND STAGED
ON AS NEEDED TO SATISFY ROOM TEMPERATURE SET POINT.
3. WHEN ROOM/SPACE TEMPERATURE FALLS BELOW HEATING SETPOINT THE LCM SHALL STAGE ON THE ELECTRIC HEAT AS NEEDED TO SATISFY ROOM TEMPERATURE
SETPOINT.
4. WHEN THE ROOM/SPACE RELATIVE HUMIDITY RISES ABOVE SETPOINT OF 60% (ADJ) THE LCM SHALL MODULATE THE HOT GAS RE−HEAT VALVE TO SATISIFY ROOM HUMIDITY
SETPOINT AND STAGE ON THE ELECTRIC HEAT AS THE 2ND STAGE OF RE−HEAT.
CONDENSATE STATUS:
1. THE LCM SHALL MONITOR CONDENSATE OVERFLOW AND AN ALARM SHALL BE POSTED TO THE LCM.
ERV HEAT
EXCHANGER
ERV EXHAUST FAN
S
M
M
OAHU DX
COIL
FILTER
TT
TT
OAHU SUPPLY FAN
TT
M
MS
MS
TK
OAHU TEMP SENSOR
COIL INLET
TEMP °F
TK
OAHU TEMP SENSOR
COIL OUTLET
TEMP °F
TK
OAHU TEMP SENSOR
UNIT LEAVING
TEMP °F
MS
HS
H.O.A.
YK
OAHU
STATUS
OK/ALARM
OAHU
HGRH COIL
TT
TK
OAHU TEMP SENSOR
COIL OUTLET
TEMP °F
OA
EA
EA
SA
T
TT
TEMPERATURE SENSOR
OUTDOOR
TEMP °F
TT
N.O.
H
MT
HUMIDITY SENSOR
SPACE/ROOM
TEMP °F
MT
T
TT
TEMPERATURE SENSOR
SPACE/ROOM
TEMP °F
TT
OAHU ELEC
HEAT COIL
SA SA
HS
H.O.A.
YK
ERV
STATUS
OK/ALARM
SENSOR TYPE SEE "CONTROLS
IDENTIFICATION LETERS"
SENSOR
LOCATION
FLOOR QUANTITY
DESCRIPTION
POINT TYPE
MEASUREMENT
TYPE
MEASUREMENT
LOCATION
SENSOR
NUMBER
EQUIP. TAG
SENSORS AND INDICATORS DDC (GCM) OR PLC (LCM) CONTROL POINTS
INSTRUMENTATION TAG DESCRIPTION
ES
X
TAG
AI
TT
AHU−01
SUPPLY AIR
TEMP
AHU−01
SUPPLY AIR
TEMP
ELECTRIC CONTROL SIGNAL
LINE TYPE DESCRIPTION
TABLE 5.3.2 − LINE SYMBOLS
DESCRIPTIONSYMBOL
DESCRIPTIONSYMBOL
ROTARY MOTOR OPERATED ACTUATOR.
ELECTRIC, PNEUMATIC, OR HYDRAULIC.
LINEAR OR ROTARY ACTION.
MODULATING SOLENOID ACTUATOR.
SOLENOID ACTUATOR FOR PROCESS ON−OFF VALVES.
TABLE 5.4.1 − FINAL CONTROL ELEMENT SYMBOLS
TABLE 5.4.2 − FINAL CONTROL ELEMENT
ACTUATOR SYMBOLS
ESS
N.O./N.C.
M
DESCRIPTIONSYMBOL
FAN
COOLING COIL, HEATING COIL, DEHUMIDIFIER, ELECTRIC
HEATING COIL
FILTER
EQUIPMENT SYMBOLS
GENERIC OPPOSED BLADE DAMPER OR LOUVER.
EQUIPMENT
3,500PSI CONCRETE PAD WITH CHAMFER EDGES.
MS MOTOR STARTER
DESCRIPTIONSYMBOL
TABLE 5.2.1 − MEASUREMENT SYMBOLS:
PRIMARY ELEMENTS AND TRANSMITTERS
" TRANSMITTER WITH CLOSE−COUPLED PRIMARY
ELEMENT INSERTED IN OR ON PROCESS FLOW LINE,
VESSEL, OR EQUIPMENT, BUBBLE / GRAPHIC FORMAT.
" INSERT PRIMARY ELEMENT SYMBOL FROM TABLE
5.2.3 AT #.
" CONNECT TO OTHER INSTRUMENTS BY SYMBOLS
FROM TABLE 5.3.2.
?T
PLC CONTROL
FUNCTION
DDC CONTROL
FUNCTION
EXTERNALLY
POWERED SENSOR
OR INDICATOR
LOCATION NORMALLY
ACCESSIBLE BY USER
LOCATION
TABLE 5.1.1 − INSTRUMENTATION DEVICE AND
FUNCTION SYMBOLS
XXXXX
XXXX
XXXXX
XXXX X
XXXXX
NOTES:
" INSTRUMENTATION IDENTIFICATION TAGS SHOWN ON THE ENCLOSED CONTROL DRAWINGS
ARE INTENDED TO BE SPECIFIC FOR EACH SEQUENCE. NO ATTEMPT HAS BEEN MADE TO
COORDINATE ALL NUMBERS IN ALL SEQUENCES AS THIS EFFORT WOULD NOT AID IN THE
UNDERSTANDING OF THE DESIGN INTENT. THEREFORE THERE ARE INSTRUMENTS ON THE
CONTROL DRAWINGS WHICH APPEAR TO HAVE THE SAME IDENTIFICATION NUMBER.
" THE CONTRACTOR SHALL PROVIE AND COORDINATE A COMPLETE LIST OF
INSTRUMENTATION, THE ASSOCIATED IDENTIFICATION TAGS AND A CROSS REFERENCE TO
BE USED IN THE EMCS (ENERGY MANAGEMENT AND CONTROL SYSTEM) PROGRAM CODE.
NOTES:
" TABLE REFERENCES ANSI/ISA−S5.1 INSTRUMENTATION SYMBOLS AND IDENTIFICATION.
SCALE:
877 CR 393 North Santa Rosa Beach, FL 32459 850.267.0759
A
54321
B
C
D
E
APPROVED BY
CHECKED BY
SHEET NO.
TITLE
DRAWN BY
DATE
PROJECT NO.
SCALE
SEAL
REVISIONS
NO. DESCRIPTION DATE
W3 Engineering Inc.
110 E. WRIGHT ST.
PENSACOLA, FL 32501
T: (850)629-8270
F: (888)478-4898
FL P.E. #: 70595
FL AUTHORIZATION #: 31078
James E. Wells III
P.E. Number: 70595
As indicated
/2
/2
:2
:0
A
M
M-701
SEQUENCE OF
OPERATION
-G
R A
Y T
O N
B E
A C
H
E n te r a d d re s s h e re
7/15/24
BEJ
JEW3
JEW3
ISSUED FOR BID
| Sheets |
| M-001 - LEGEND & GENERAL NOTES |
| M-111 - HVAC OVERALL FIRST FLOOR PLAN |
| M-112 - HVAC OVERALL SECOND FLOOR PLAN |
| M-301 - HVAC SECTIONS |
| M-501 - HVAC DETAIL SET-1 |
| M-502 - HVAC DETAIL SET-2 |
| M-503 - HVAC DETAIL SET-3 |
| M-601 - HVAC SCHEDULES |
| M-701 - SEQUENCE OF OPERATION |