The provided files are electrical engineering design documents for the Grayton Beach Community Center project, prepared by Ruby Engineering, Inc. for Walton County, Florida. The electrical plans cover a two-story facility with detailed specifications for electrical installations, including power and lighting systems, electrical equipment connections, and control devices. The documents include comprehensive electrical design drawings for site plans, first and second floor power and lighting layouts, electrical legends, abbreviations, equipment connection schedules, and lighting control details. The design follows the 2023 Florida Building Code and 2020 National Electrical Code (NFPA 70), specifying copper wire usage, grounding requirements, raceway and box installations, and specific electrical equipment specifications.
Key technical specifications include a 400A main service with a 120/240V single-phase electrical system, utilizing a utility meter enclosure and main fused disconnect. The design incorporates various electrical components such as outdoor air conditioning units, heat pump units, energy recovery units, electric water heaters, and an elevator. Lighting systems include wall switches, occupancy sensors, dimmers, and exterior lighting controlled by a time clock. The electrical design emphasizes compliance with national and local electrical standards, with specific requirements for conductor sizing, grounding, conduit installation, and equipment identification. The project appears to be a comprehensive electrical infrastructure design for a new community center facility in Grayton Beach, Florida.
View the file
Other files
Show all 29
On GovTribe
Work with this file
- Download the original file
- Contacts named in this file
- Similar government files
- Ask GovTribe AI about this file
Text version
RUBY ENGINEERING, INC
3 W GARDEN ST, STE 414
PENSACOLA, FL 32502
PHONE: (850) 455-5540
FL AUTHORIZATION #31884
A
54321
B
C
D
E
APPROVED BY
CHECKED BY
SHEET NO.
TITLE
DRAWN BY
DATE
PROJECT NO.
SCALE
SEAL
REVISIONS
NO. DESCRIPTION DATE
877 CR 393 North Santa Rosa Beach, FL 32459 850.267.0759
SCALE:
G R
AY
TO
N B
EA
C
H
15 July, 2024
JLB
JJT
AS SHOWN
JAMES J TATONE FL PE - 57609
JJT
ISSUED FOR BID DATE
F
A - AMPERES
AC - ABOVE CEILING
AF - AMPERE FRAME
AFCI - ARC FAULT CIRCUIT INTERRUPTER
AFF - ABOVE FINISHED FLOOR
AIC - AMP INTERRUPTING CAPACITY
ALT - ALTERNATE
AT - AMPERE TRIP
AUTO - AUTOMATIC
AWG - AMERICAN WIRE GAUGE
BATT - BATTERY
BFC - BELOW FINISHED CEILING
BLDG - BUILDING
C - CONDUIT
CFCI - CONTRACTOR FURNISHED,
CONTRACTOR INSTALLED
CLG - CEILING
CT - CURRENT TRANSFORMER
DC - DIRECT CURRENT
DISC - DISCONNECT
EBJ - EQUIPMENT BONDING JUMPER
EMT - ELECTRICAL METALLIC TUBING
ETR - EXISTING TO REMAIN
FACP - FIRE ALARM CONTROL PANEL
FDR - FEEDER
FLA - FULL LOAD AMPERES
FVNR - FULL VOLTAGE NON-REVERSING
G - EQUIPMENT GROUND
GEC - GROUNDING ELECTRODE CONDUCTOR
GFCI - GROUND FAULT CIRCUIT INTERRUPTER
GFP - GROUND FAULT PROTECTION
GND - GROUND
HOA - HAND OFF AUTOMATIC
HP - HORSEPOWER
IMC - INTERMEDIATE METAL CONDUIT
JB - JUNCTION BOX
KV - KILOVOLT
KVA - KILOVOLT-AMPERES
KW - KILOWATTS
KWH - KILOWATT HOURS
LAN - LOCAL AREA NETWORK
LMNS - LUMENS
LOTO - LOCK-OUT / TAG-OUT
LTG - LIGHTING
LTS - LIGHTS
LV - LOW VOLTAGE
MCB - MAIN CIRCUIT BREAKER
MIN - MINIMUM
MLO - MAIN LUGS ONLY
MTG - MOUNTING
NA - NOT APPLICABLE
NAC - NOTIFICATION APPLICANCE CIRCUIT
NC - NORMALLY CLOSED
NO - NORMALLY OPEN
OFCI - OWNER FURNISHED CONTRACTOR INSTALLED
OFOI - OWNER FURNISHED OWNER INSTALLED
P - POLE
PC - PHOTOCELL
PF - POWER FACTOR
PH - PHASE
PT - POTENTIAL TRANSFORMER
RAC - RELEASING APPLIANCE CIRCUIT
REC - RECEPTACLE
RMC - RIGID METALLIC CONDUIT
SDCM - STANDARD DEVIATION COLOR MATCHING
SPD - SURGE PROTECTIVE DEVICE
SWBD - SWITCHBOARD
TR - TAMPER RESISTANT
TV - TELEVISION
TYP - TYPICAL
UC - UNDER COUNTER
UG - UNDERGROUND
UNO - UNLESS NOTED OTHERWISE
UPS - UNINTERRUPTED POWER SUPPLY
V - VOLTAGE
VFD - VARIABLE FREQUENCY DRIVE
W/ - WITH
WP - WEATHERPROOF
XFMR - TRANSFORMER
ELECTRICAL ABBREVIATIONS
NON-FUSED DISCONNECT
KEYED NOTE
FIXED EQUIPMENT CONNECTION
WIRING
FUSED DISCONNECT
ELECTRICAL LEGEND
M
GROUND ROD
SECTION 26 0511 - REQUIREMENTS FOR ELECTRICAL INSTALLATIONS
A. ALL ELECTRICAL WORK SHALL CONFORM WITH ALL STATE AND LOCAL CODES
AND STANDARDS INCLUDING, BUT NOT LIMITED TO, THE FOLLOWING:
1. FLORIDA BUILDING CODE (2023)
2. NFPA 70 NATIONAL ELECTRICAL CODE (2020)
B. WHEREVER CONFLICTS OCCUR, MORE STRINGENT CODES SHALL APPLY.
C. ALL MATERIALS AND EQUIPMENT SHALL BE LISTED, LABELED OR CERTIFIED
BY A NATIONALLY RECOGNIZED TESTING LABORATORY (NRTL) TO MEET
UNDERWRITERS LABORATORIES, INC. (UL), STANDARDS WHERE TEST
STANDARDS HAVE BEEN ESTABLISHED.
D. COORDINATE LOCATION OF EQUIPMENT AND CONDUIT WITH OTHER TRADES
AND EQUIPMENT VENDORS TO MINIMIZE INTERFERENCE.
E. ELECTRICAL IDENTIFICATION:
1. COLOR-CODED TAPE SHALL BE 3M COMPANY "SCOTCH 35" VINYL
PLASTIC ELECTRICAL TAPE.
2. IDENTIFY PHASE OF EACH CONDUCTOR AT EACH PULL BOX, JUNCTION
BOX AND AT EACH OUTLET WITH PERMANENTLY ATTACHED, WRAP
AROUND, ADHESIVE MARKERS. WITH AN APPROPRIATE NUMBER OR
LETTER THAT WILL EXPEDITE FUTURE TRACING AND TROUBLE
SHOOTING.
3. PROVIDE NAMEPLATE MOUNTED ON ALL ELECTRICAL EQUIPMENT (I.E.
PANELBOARDS, DISCONNECTS, ETC) INDICATING THE EQUIPMENT
DESIGNATION AS SHOWN ON DRAWINGS AND THE EQUIPMENT
DESIGNATION SERVING THE EQUIPMENT (I.E. SERVED FROM PANEL P).
4. IDENTIFICATION NAMEPLATES SHALL BE LAMINATED BLACK PHENOLIC
RESIN WITH A WHITE CORE WITH ENGRAVED LETTERIING. LETTERING
SHALL BE A MINIMUM OF 12 INCH HIGH.
H. WORKING CLEARANCES SHALL NOT BE LESS THAN SPECIFIED IN THE NEC.
SECTION 26 0519 - LOW-VOLTAGE ELECTRICAL POWER CONDUCTORS AND CABLES
A. CONDUCTOR SIZES (AND ASSOCIATED CONDUIT SIZES) IN THESE CONTRACT
DOCUMENTS ARE BASED ON THE USE OF COPPER WIRE APPLIED AT 75 DEG.
C RATING. ONLY COPPER WIRE SHALL BE USED.
B. BUILDING WIRE SHALL BE TYPE THHN/THWN SINGLE CONDUCTOR INSULATED
COPPER WIRE RATED FOR 600 VOLTS, RATED 90 DEGREES C DRY/75
DEGREES C WET. WIRE NO. 12 AND SMALLER MAY BE SOLID OR STRANDED
AND WIRE NO. 10 AND LARGER SHALL BE STRANDED ONLY. PROVIDE
STRANDED CONDUCTORS WHERE CONDUCTORS TERMINATE IN CRIMP TYPE
LUGS. WIRING CONNECTORS SHALL BE SPRING WIRE CONNECTORS: UL
486C; RATED FOR 600 VOLTS, 105 DEG. C.
C. LIMIT BRANCH CIRCUITS TO 3 CURRENT-CARRYING CONDUCTORS PER
CONDUIT IN ACCORDANCE WITH NEC 310-15(B)(2)(A). FOR 20A CIRCUITS OF
ALTERNATING PHASES, 4 CURRENT CARRYING CONDUCTORS MAY BE
PERMITTED IN A RACEWAY. MINIMUM CONDUCTOR SIZES SHALL BE NO. 12
FOR BRANCH CIRCUITS OF ANY KIND.
D. COLOR CODE POWER WIRING AS FOLLOWS:
1. 120/240V: PHASE A - BLACK, PHASE B - RED, NEUTRAL - WHITE, GROUND
CONDUCTOR - GREEN
F. SHARED NEUTRAL CONDUCTORS (MULTI-WIRE BRANCH CIRCUITS) ARE NOT
ALLOWED.
SECTION 26 0526 - GROUNDING AND BONDING FOR ELECTRICAL SYSTEMS
A. ALL CONDUIT AND CABLE SYSTEMS SHALL CONTAIN AN EQUIPMENT
GROUNDING CONDUCTOR.
B. BOND THE EQUIPMENT GROUNDING CONDUCTOR TO EACH PULLBOX,
JUNCTION BOX, OUTLET BOX, DEVICE BOX, CABINETS AND OTHER
ENCLOSURES THROUGH WHICH THE CONDUCTOR PASSES.
C. RECEPTACLES OF ANY AMPERAGE SHALL BE GROUNDING TYPE AND SHALL
HAVE SEPARATE GROUNDING CONTACT. INSTALL SEPARATE JUMPER
BETWEEN GROUNDING TERMINAL ON DEVICE AND METALLIC BOX.
D. MULTIPLE CONDUCTORS IN SINGLE LUG NOT PERMITTED. EACH GROUNDING
CONDUCTOR SHALL TERMINATE IN ITS OWN TERMINAL LUG.
E. PROVIDE SEPARATE GREEN WIRE GROUND CONDUCTOR FOR EACH BRANCH
CIRCUIT AND FEEDER CONDUIT. GROUND CONDUCTORS SHALL BE SIZE AS
INDICATED IN NEC, EXCEPT MINIMUM SIZE GROUND CONDUCTOR SHALL BE
NO. 12 AWG.
F. GROUNDING CONDUCTOR IS IN ADDITION TO NEUTRAL CONDUCTOR AND IN
NO CASE SHALL NEUTRAL CONDUCTOR SERVE AS GROUNDING MEANS.
SECTION 26 0533 - RACEWAY AND BOXES FOR ELECTRICAL SYSTEMS
A. CONDUIT BODIES SHALL BE MADE FROM COPPER-FREE ALUMINUM AND HAVE
OPENINGS COMPATIBLE WITH CONDUIT FITTINGS. PROVIDE BLANK COVERS
WITH NEOPRENE GASKETS HELD IN PLACE WITH TWO (2) STAINLESS STEEL
SCREWS. BODIES SHALL BE LB, C OR OTHER TYPE INDICATED.
B. ALL CONDUIT ROUTING WITHIN THE BUILDING INTERIOR SHALL BE EMT.
C. ALL EXTERIOR CONDUITS INSTALLED ABOVE GRADE SHALL BE RIGID
ALUMINUM CONDUIT (RAC). CONNECTIONS SHALL HAVE BUSHINGS WITH
INTEGRAL INSULATOR. PROVIDE BONDING BUSHINGS FOR ALL CONNECTIONS
THROUGH PRE-PUNCHED CONCENTRIC OR ECCENTRIC KNOCKOUTS.
D. CONDUITS INSTALLED BELOW GRADE SHALL BE SCHEDULE 40 PVC CONDUIT.
UNDERGROUND CONDUIT SHALL TRANSITION TO RIGID ALUMINUM CONDUIT
USING RIGID ALUMINUM CONDUIT 90° ELBOWS WITH ALL RIGID ALUMINUM
CONDUIT INSTALLED BELOW GRADE PAINTED WITH BITUMASTIC COATING OR
WRAPPED IN CORROSION PROTECTION TAPE.
E. PROVIDE ONE-PIECE, CAST ALUMINUM TYPE OUTLET BOXES TO
ACCOMMODATE DEVICES, IN CONFORMANCE WITH CODE REQUIREMENTS,
NUMBER AND SIZE OF CONDUCTORS AND SPLICES AND CONSISTENT WITH
TYPE OF CONSTRUCTION.
F. PROVIDE HEAVY DUTY SHEET STAINLESS STEEL STRAPS, OR CHANNEL
SYSTEM WITH APPROPRIATE COMPONENTS CONDUIT SUPPORTS FOR
HORIZONTAL OR VERTICAL SINGLE RUNS, SPRING TYPE PRESSURE CLAMPS
MAY BE USED WITH CONDUIT THROUGH 3/4".
G. REAM CONDUIT SMOOTH AT ENDS, CAP UPON INSTALLATION, RIGIDLY
ATTACH TO STRUCTURAL SUPPORTS AND SECURELY FASTEN TO OUTLET
BOXES, PANEL CABINETS, JUNCTION BOXES, PULL BOXES, SPLICING
CHAMBERS, SAFETY SWITCHES AND OTHER COMPONENTS OF THE RACEWAY
SYSTEM.
H. MINIMUM CONDUIT SIZE IS 3/4".ALL FEEDER CONDUCTORS SHALL BE
INSTALLED UNDERGROUND IN SCHEDULE 40 PVC CONDUIT AT A MINIMUM
BURIAL DEPTH OF 36" TO TOP OF CONDUIT.
I. OUTLET, JUNCTION AND PULL BOXES SHALL BE UL-50 AND UL-514A LISTED.
J. REAM CONDUIT SMOOTH AT ENDS, CAP UPON INSTALLATION, RIGIDLY
ATTACH TO STRUCTURAL PARTS OF BUILDING AND SECURELY FASTEN TO
OUTLET BOXES, PANEL CABINETS, JUNCTION BOXES, PULL BOXES, SPLICING
CHAMBERS, SAFETY SWITCHES AND OTHER COMPONENTS OF THE RACEWAY
SYSTEM.
SECTION 26 0923 - LIGHTING CONTROL DEVICES
A. WALL SWITCHES SHALL BE 20A, 120V, HEAVY DUTY COMMERCIAL GRADE,
QUIET TYPE, WHITE COLOR WITH COVERPLATE TO MATCH.
B. DIMMERS SHALL BE COORDINATED WITH LUMINAIRE DIMMING DRIVER.
COORDINATE DIMMER WITH EACH LUMINAIRE SUBMITTAL TO ENSURE
COMPATIBILITY. DIMMERS SHALL HAVE PRE-SET SLIDE TYPE DIMMING
CONTROL WITH ON/OFF ROCKER SWITCH.
C. CEILING MOUNTED LOW VOLTAGE OCCUPANCY SENSORS SHALL BE DUAL
TECHNOLOGY WITH 360° SMALL MOTION COVERAGE TYPE, SENSORSWITCH
CM PDT SERIES OR EQUAL.
D. WALL MOUNTED LOW VOLTAGE OCCUPANCY SENSORS SHALL BE DUAL
TECHNOLOGY, SENSOR SWITCH WV16 SERIES OR EQUAL.
E. PROVIDE POWER PACK FOR THE LOW VOLTAGE TYPE OCCUPANCY SENSORS
AS SHOWN ON DRAWINGS, SENSORSWITCH PP20 SERIES OR EQUAL.
G. PROVIDE POWER PACK FOR THE LOW VOLTAGE TYPE OCCUPANCY SENSORS
AS SHOWN ON DRAWINGS, SENSORSWITCH PP20 SERIES OR EQUAL.
H. TIME CLOCK SHALL BE 7-DAY DUSK/DAWN ASTRONOMIC, FOUR CIRCUIT TIME
SWITCH, INTERMATIC MODEL ET2845C OR EQUAL WITH FOUR SINGLE POLE,
SINGLE THROW 30A RATED SWITCHES FOR 120V OPERATION IN NEMA 1,
STEEL ENCLOSURE.
I. MOUNTING HEIGHTS INDICATED ARE TO CENTER OF DEVICE UNLESS NOTED
OTHERWISE.
J. INSTALL PRODUCTS IN ACCORDANCE WITH MANUFACTURER'S INSTRUCTIONS.
SECTION 26 2116 - METERING EQUIPMENT
A. METER IS SPECIFIED FOR A UTILITY SERVICE FED FROM A 120/240 VAC,
SINGLE PHASE, THREE WIRE SYSTEM.
B. METER ENCLOSURE SHALL BE 320 AMP, 4 TERMINAL, SINGLE POSITION,
SINGLE PHASE, THREE WIRE WITH LEVER BYPASS IN ALUMINUM HOUSING.
C. METER ENCLOSURE SHALL BE PROVIDED TO MEET THE LOCAL UTILITY
COMPANY REQUIREMENTS. REFER TO THE LOCAL UTILITY COMPANY
ELECTRIC SERVICE STANDARDS FOR APPROVED METER ENCLOSURES.
D. MOUNT METER SOCKET SUCH THAT THE CENTER OF THE METER IS 60" ABOVE
THE FINISHED FLOOR.
SECTION 26 2416 - PANELBOARDS
A. BASIS OF DESIGN: LIGHTING AND APPLIANCE PANELBOARDS - SQUARE D NQ
B. PANELBOARDS SHALL BE UL 50 AND UL 67 LISTED.
C. CIRCUIT BREAKERS SHALL BE UL 489 LISTED.
D. PANELBOARDS SHALL BE COMPLETELY FACTORY ASSEMBLED WITH MOLDED
CASE CIRCUIT BREAKERS AND INTEGRAL ACCESSORIES AS SHOWN IN THE
PANEL SCHEDULES.
E. PROVIDE PRINTED SCHEDULE OF CIRCUITS IN EACH PANELBOARD.
SCHEDULES SHALL REFLECT FINAL LOAD DESCRIPTIONS AND ROOM
NUMBERS CONNECTED TO EACH CIRCUIT BREAKER. SCHEDULES SHALL BE
PRINTED ON THE PANELBOARD DIRECTORY CARDS AND BE INSTALLED IN THE
APPROPRIATE PANELBOARD.
F. MOUNT PANELBOARDS SUCH THAT THE MAXIMUM HEIGHT OF THE TOP
CIRCUIT BREAKER ABOVE THE FINISHED FLOOR SHALL NOT EXCEED 78
INCHES.
G. PROVIDE BLANK COVER FOR EACH UNUSED CIRCUIT BREAKER MOUNTING
SPACE.
SECTION 26 2726 - WIRING DEVICES
A. RECEPTACLES SHALL BE NEMA 5-20R, RATED 20 AMPS, 125 VOLTS AC, BACK
AND SIDE WIRED CAPABLE. GRAY COLORED. PUSH-IN TYPE CONNECTIONS
ARE NOT PERMITTED.
B. ALL RECEPTACLES SHALL BE TAMPER RESISTANT TYPE.
C. INTERIOR DEVICE COVER PLATES SHALL BE 316L STAINLESS STEEL.
D. WEATHERPROOF RECEPTACLE COVERPLATES SHALL BE WEATHERPROOF
CAST ALUMINUM, "WHILE IN USE" TYPE. COORDINATE COLOR SELECTION
WITH OWNER/ARCHITECT.
E. INSTALL PRODUCTS IN ACCORDANCE WITH MANUFACTURER'S INSTRUCTIONS.
INDICATED MOUNTING HEIGHTS ARE TO CENTER LINE OF DEVICES UNLESS
NOTED OTHERWISE. RECEPTACLES SHALL BE MOUNTED AT 18" AFF UNLESS
NOTED OTHERWISE. WALL SWITCHES SHALL BE MOUNTED AT 42" AFF
UNLESS NOTED OTHERWISE.
F. TEST EACH RECEPTACLE DEVICE FOR PROPER POLARITY. ADJUST DEVICES
AND WALL PLATES TO BE FLUSH AND LEVEL.
SECTION 26 5000 - LUMINAIRES
A. PROVIDE LUMINAIRES AS SPECIFIED UNDER THE LUMINAIRE SCHEDULE ON
SHEET E2.1.
B. LUMINAIRES SHALL BE CERTIFIED BY THE FLORIDA FISH AND WILDLIFE
CONSERVATION COMMISSION THROUGH THE WILDLIFE LIGHTING
CERTIFICATION PROGRAM.
C. SUBMIT MANUFACTURER'S CUT SHEET INCLUDING THE SPECTRAL
DISTRIBUTION GRAPHS OR LM-79 REPORTS FOR ALL LUMINAIRE SELECTIONS
WITH ALL OPTIONS FOR EACH LUMINAIRE IDENTIFIED FOR FINAL APPROVAL.
ELECTRICAL SPECIFICATIONS
TS TIME SWITCH
DUPLEX RECEPTACLE (NEMA 5-20R)
MOUNTING HEIGHT: 18" AFF UNO
SURGE PROTECTIVE DEVICESPD
S CEILING MOUNTED, DUAL
TECHNOLOGY OCCUPANCY SENSOR
METER ENCLOSURE
SUSPENDED LINEAR
S
WALL MOUNTED, DUAL TECHNOLOGY
OCCUPANCY SENSOR
MOUNTING HEIGHT: 6" BFC
E0.1
LEGEND AND
SPECIFICATIONS
LINEAR LED
PP POWER PACK FOR OCCUPANCY SENSOR
PANEL BOARD - SURFACE MOUNTED
EQ
# REVISION NUMBER DESIGNATION
EQUIPMENT DESIGNATION
TOP DESIGNATES EQUIPMENT
ABBREVIATION, BOTTOM DESIGNATES
EQUIPMENT NUMBER
FIRE ALARM SMOKE DETECTOR
MOUNTING LOCATION: CEILING
FIRE ALARM HEAT DETECTOR
MOUNTING LOCATION: CEILING
S
H
QUAD RECEPTACLE (TWO NEMA 5-20R)
MOUNTING HEIGHT: 18" AFF UNO
DUPLEX RECEPTACLE (NEMA
5-20R) - ABOVE CASEWORK
ELI EMERGENCY LIGHTING INVERTER
AutoCAD SHX Text
AutoCAD SHX Text
WALL MOUNTED LUMINAIRE
AutoCAD SHX Text
WALL SCONCE TYPE LUMINAIRE
AutoCAD SHX Text
WALL RECESSED TYPE LUMINAIRE
AutoCAD SHX Text F
AutoCAD SHX Text F
D
EF
U N
IA
K
ST
R
EE
T
(5 0'
R /W
P1 P1
P1
P1
P1
P1
P1
P1
P1 P1P1
P1
P1
P1
P1
P1
P1
P1
P1 P1 P1
P1
P1
P1
P1
P1 P1
P1 P1 P1
P1
P1
P1
P1
P1
P1
P1
P1
P1
P1
P1
P1
P1
M
E
UTILITY
METER
ENCLOSURE
UTILITY ELECTRIC
SERVICE PEDESTAL
UNDERGROUND
ELECTRICAL SERVICE
FEEDER. REFER TO
THE POWER AND
GROUNDING RISER
DIAGRAM ON SHEET E3.1
RUBY ENGINEERING, INC
3 W GARDEN ST, STE 414
PENSACOLA, FL 32502
PHONE: (850) 455-5540
FL AUTHORIZATION #31884
A
54321
B
C
D
E
APPROVED BY
CHECKED BY
SHEET NO.
TITLE
DRAWN BY
DATE
PROJECT NO.
SCALE
SEAL
REVISIONS
NO. DESCRIPTION DATE
877 CR 393 North Santa Rosa Beach, FL 32459 850.267.0759
SCALE:
G R
AY
TO
N B
EA
C
H
15 July, 2024
JLB
JJT
AS SHOWN
JAMES J TATONE FL PE - 57609
JJT
ISSUED FOR BID DATE
SCALE:
SITE PLAN1 1/8" = 1'-0"
E1.1
SITE PLAN
MEN'S
RESTROOM
ELEV
MECHANICAL/
STORAGE
WOMEN'S
RESTROOM
W4E
W4 W4E W4 W4 W4 W4EW4W4
W4E
W4 W4 W4 W4W4E
F4E F4 F4
F4E F4
F4 F4
S1
S1
S1
S S
S
S
S
S
S
S
1 1
S 2
F4E
F4E
S WP
PP
PP
PP
TSD
PP
POWER PACK
AND DIMMER FOR
2ND FLOOR TDC
SPACE
P-7
ELI
ELEV
TDC
SPACE
S1S1
S1
S1
S1S1
S1
S1
L22
L22 L22 L22
SS
SS
3 3
GENERAL NOTES
1. ALL EXTERIOR LIGHTING SHALL BE CONTROLLED
VIA TIME CLOCK. REFER TO THE EXTERIOR
LIGHTING CONTROL SCHEMATIC, DETAIL 4 ON
SHEET E4.1.
KEYED NOTES
1 REFER TO THE RESTROOM OCCUPANCY SENSOR
CONTROL SCHEMATIC, DETAIL 1 ON SHEET E4.1.
2 REFER TO THE MECHANICAL/STORAGE
OCCUPANCY SENSOR CONTROL SCHEMATIC,
DETAIL 2 ON SHEET E4.1.
3 REFER TO THE TDC SPACE OCCUPANCY SENSOR
CONTROL SCHEMATIC, DETAIL 3 ON SHEET E4.1.
4 EMERGENCY LIGHTING INVERTER AND TIME
SWITCH FOR EXTERIOR LIGHTING. REFER TO THE
EXTERIOR LIGHTING CONTROL SCHEMATIC,
DETAIL 4 ON SHEET E4.1.
RUBY ENGINEERING, INC
3 W GARDEN ST, STE 414
PENSACOLA, FL 32502
PHONE: (850) 455-5540
FL AUTHORIZATION #31884
A
54321
B
C
D
E
APPROVED BY
CHECKED BY
SHEET NO.
TITLE
DRAWN BY
DATE
PROJECT NO.
SCALE
SEAL
REVISIONS
NO. DESCRIPTION DATE
877 CR 393 North Santa Rosa Beach, FL 32459 850.267.0759
SCALE:
G R
AY
TO
N B
EA
C
H
15 July, 2024
JLB
JJT
AS SHOWN
JAMES J TATONE FL PE - 57609
JJT
ISSUED FOR BID DATE
SCALE:
FIRST FLOOR LIGHTING PLAN1 1/4" = 1'-0"SCALE:
SECOND FLOOR LIGHTING PLAN2 1/4" = 1'-0"
E2.1
LIGHTING
PLANS
MEN'S
RESTROOM
ELEV
MECHANICAL/
STORAGE
WOMEN'S
RESTROOM
ELEV
M
GFI/WP
ERV
OAHU
EWH
DCU
OACU
P-21,23 (2)#10, #10G, 3/4"C
P-24,26
(2)#8, #10G, 3/4"CP-32,34
P-29,31
P-33,35
F
UTILITY
METER
ENCLOSURE
MAIN FUSED
DISCONNECT
GFI/WP
GFI
GFI
GFI/WP
GFI
GFI
PANEL
P
F
P-37 P-39,41 (2)#3, #8G, 1"C
ELEVATOR
MAIN POWER
DISCONNECTELEVATOR
CONTROLLER
ELEVATOR CAB
LIGHTS/RECEPTACLE
DISCONNECT
OAHU
P-36,38
OACU
P-28,30 (2)#8, #10G, 3/4"C
P-8
P-2
GFI/WP
P-11
P-9
GFI
GFI
GFI
P-5
P-3
F H
ELEV
TDC
SPACE
DAC
P- 25,27
P- 14
P- 10
P- 12
F S
S
GENERAL NOTES
1. REFER TO EQUIPMENT CONNECTION SCHEDULE
ON SHEET E5.1.
KEYED NOTES
1 PROVIDE WEATHERPROOF 135 DEGREE CELSIUS
RISE HEAT DETECTOR FOR ELEVATOR RECALL
SERVICE.
2 PROVIDE PHOTOELECTRIC TYPE SMOKE DETECTOR
FOR ELEVATOR RECALL SERVICE.
RUBY ENGINEERING, INC
3 W GARDEN ST, STE 414
PENSACOLA, FL 32502
PHONE: (850) 455-5540
FL AUTHORIZATION #31884
A
54321
B
C
D
E
APPROVED BY
CHECKED BY
SHEET NO.
TITLE
DRAWN BY
DATE
PROJECT NO.
SCALE
SEAL
REVISIONS
NO. DESCRIPTION DATE
877 CR 393 North Santa Rosa Beach, FL 32459 850.267.0759
SCALE:
G R
AY
TO
N B
EA
C
H
15 July, 2024
JLB
JJT
AS SHOWN
JAMES J TATONE FL PE - 57609
JJT
ISSUED FOR BID DATE
SCALE:
FIRST FLOOR POWER PLAN1 1/4" = 1'-0"SCALE:
SECOND FLOOR POWER PLAN2 1/4" = 1'-0"
E3.1
POWER
PLANS
DISC-MAIN
400A/2P
MAIN SERVICE
FUSED
DISCONNECT
WITH 300A
CLASS RK1
FUSES IN
NEMA 3R
ENCLOSURE
M
(3) 350 KCM, 3"C
PANEL P
400A MLO
120/240V 1Ø, 3W
REFER TO
PANEL
SCHEDULE ON
THIS SHEET
UTILITY
METER
ENCLOSURE
(3) 350 KCM, #4G, 3"C
INTERIOR EXTERIOR
UTILITY
ELECTRIC SERVICE
PEDESTAL
120/240V, 1Ø
MIN 6'
TYP
3/4" DIA X 20'L COPPER
GROUND ROD WITH EXOTHERMIC
WELD TYPE TERMINATIONS IN
GROUND TEST WELL.
GROUND ROD
TYPICAL OF 3
PROVIDE UL LISTED
GROUNDING ELECTRODE
CONNECTION TO
CONCRETE ENCASED
ELECTRODE PER NEC
ARTICLE 250.52(A)(3)
#4 AWG SOLID,
BARE COPPER
MECHANICAL/
STORAGE ROOM
(3) 350 KCM, 3"C
SPD
PROVIDE NIPPLE-MOUNTED,
NEMA 4X RATED SURGE
PROTECTION DEVICE WITH
25 KA SHORT CIRCUIT
CURRENT RATING AND 80 KA
PEAK SURGE CURRENT
RATING PER PHASE. LOCATE
ADJACENT TO BREAKER
SERVING THE SPD.
AutoCAD SHX Text
NOT TO SCALE
AutoCAD SHX Text
POWER AND GROUNDING RISER DIAGRAM
PENSACOLA, FL 32502
PHONE: (850) 455-5540
FL AUTHORIZATION #31884
A
54321
B
C
D
E
APPROVED BY
CHECKED BY
SHEET NO.
TITLE
DRAWN BY
DATE
PROJECT NO.
SCALE
SEAL
REVISIONS
NO. DESCRIPTION DATE
877 CR 393 North Santa Rosa Beach, FL 32459 850.267.0759
SCALE:
G R
AY
TO
N B
EA
C
H
15 July, 2024
JLB
JJT
AS SHOWN
JAMES J TATONE FL PE - 57609
JJT
ISSUED FOR BID DATE
E4.1
LIGHTING
CONTROL
DETAILS2
3TDC SPACE OCCUPANCY SENSOR SCHEMATIC
SCALE: NONE
1MECHANICAL/STORAGE OCCUPANCY SENSOR SCHEMATIC
4EXTERIOR LIGHTING CONTROL SCHEMATIC
RESTROOM OCCUPANCY SENSOR SCHEMATIC
POWER
PACK
CEILING
MOUNTED
OCCUPANCY
SENSOR
MANUAL ON
LOW VOLTAGE
SWITCH STATION
CEILING
MOUNTED
OCCUPANCY
SENSOR
POWER
PACK
WALL
MOUNTED
OCCUPANCY
SENSOR
WALL
MOUNTED
OCCUPANCY
SENSOR
WALL
MOUNTED
OCCUPANCY
SENSOR
POWER
PACK
WALL
MOUNTED
OCCUPANCY
SENSOR
CEILING
MOUNTED
OCCUPANCY
SENSOR
WALL
MOUNTED
OCCUPANCY
SENSOR
CEILING
MOUNTED
OCCUPANCY
SENSOR
SCALE: NONESCALE: NONE
SCALE: NONE
AutoCAD SHX Text C
AutoCAD SHX Text
7-DAY CALENDAR DIAL TIME SWITCH 120 VAC TIMING MOTOR IN NEMA 3R STEEL ENCLOSURE
AutoCAD SHX Text P-5
AutoCAD SHX Text
TS
AutoCAD SHX Text P-1
AutoCAD SHX Text
NEUTRAL
AutoCAD SHX Text
CONTROL OUTPUT
AutoCAD SHX Text
COMMON
AutoCAD SHX Text
+24VDC
AutoCAD SHX Text
CONTROL OUTPUT
AutoCAD SHX Text
COMMON
AutoCAD SHX Text
+24VDC
AutoCAD SHX Text
CONTROL OUTPUT
AutoCAD SHX Text
COMMON
AutoCAD SHX Text
+24VDC
AutoCAD SHX Text
PEDESTRIAN WALKWAY LUMINAIRES TYPE P1
AutoCAD SHX Text
WALL SCONCE LUMINAIRES TYPE S1
AutoCAD SHX Text P-3
AutoCAD SHX Text
NEUTRAL
AutoCAD SHX Text
CONTROL OUTPUT
AutoCAD SHX Text
COMMON
AutoCAD SHX Text
+24VDC
AutoCAD SHX Text
CONTROL OUTPUT
AutoCAD SHX Text
COMMON
AutoCAD SHX Text
+24VDC
AutoCAD SHX Text
CONTROL OUTPUT
AutoCAD SHX Text
COMMON
AutoCAD SHX Text
+24VDC
AutoCAD SHX Text
COMMON
AutoCAD SHX Text
+24VDC
AutoCAD SHX Text
POWER PACK LOCATED IN FIRST FLOOR MECHANICAL/STORAGE ROOM
AutoCAD SHX Text
TYPE L22 WALL MOUNTED LINEAR W/ EMERGENCY BATTERY
AutoCAD SHX Text D
AutoCAD SHX Text
DIMMER LOCATED IN FIRST FLOOR MECHANICAL/STORAGE ROOM
AutoCAD SHX Text P-1
AutoCAD SHX Text
NEUTRAL
AutoCAD SHX Text
CONTROL OUTPUT
AutoCAD SHX Text
COMMON
AutoCAD SHX Text
+24VDC
AutoCAD SHX Text
CONTROL OUTPUT
AutoCAD SHX Text
COMMON
AutoCAD SHX Text
+24VDC
AutoCAD SHX Text
CONTROL OUTPUT
AutoCAD SHX Text
COMMON
AutoCAD SHX Text
+24VDC
AutoCAD SHX Text
POWER PACK LOCATED IN FIRST FLOOR MECHANICAL/STORAGE ROOM
AutoCAD SHX Text
TYPE W4 LUMINAIRES
AutoCAD SHX Text
TYPE W4E LUMINAIRES
AutoCAD SHX Text
TYPE F4 LUMINAIRES
AutoCAD SHX Text
TYPE F4E LUMINAIRES
AutoCAD SHX Text
SPARE
AutoCAD SHX Text
SPARE
AutoCAD SHX Text
SPARE
AutoCAD SHX Text EMERGENCY LIGHTING INVERTER 500 WATT INPUT 350 WATT OUTPUT 120/277 VAC, 60 HZ UL 924 LISTED IOTA MODEL IIS 375 LED OR EQUAL
AutoCAD SHX Text
UNSWITCHED 120V INVERTER INPUT
AutoCAD SHX Text
NORMAL POWER 120V INPUT
AutoCAD SHX Text
NEUTRAL
AutoCAD SHX Text
ELI
AutoCAD SHX Text
PP
AutoCAD SHX Text
PP
PP
PENSACOLA, FL 32502
PHONE: (850) 455-5540
FL AUTHORIZATION #31884
A
54321
B
C
D
E
APPROVED BY
CHECKED BY
SHEET NO.
TITLE
DRAWN BY
DATE
PROJECT NO.
SCALE
SEAL
REVISIONS
NO. DESCRIPTION DATE
877 CR 393 North Santa Rosa Beach, FL 32459 850.267.0759
SCALE:
G R
AY
TO
N B
EA
C
H
15 July, 2024
JLB
JJT
AS SHOWN
JAMES J TATONE FL PE - 57609
JJT
ISSUED FOR BID DATE
E5.1
EQUIPMENT
CONNECTION
SCHEDULE
OACU
OAHU
DCU
DAC
ERV
EWH
ELEV
| E0.1 LEGEND-E0.1 |
| Sheets and Views |
| E0.1 |
| E1.1 SITE PLAN-E1.1 |
| Sheets and Views |
| E1.1 |
| E2.1 LIGHTING PLAN-E2.1 |
| Sheets and Views |
| E2.1 |
| E3.1 POWER PLAN-E3.1 |
| Sheets and Views |
| E3.1 |
| E4.1 LIGHTING CONTROL DETAILS-E4.1 |
| Sheets and Views |
| E4.1 |
| E5.1 EQUIP SCHEDLE-E5.1 |
| Sheets and Views |
| E5.1 |