The provided document is a comprehensive plumbing design set for the Grayton Beach Community Center project in Walton County, Florida, prepared by W3 Engineering Inc. The plumbing plans include detailed drawings for domestic water systems, sanitary sewer and vent systems, fixture schedules, and technical specifications across multiple building floors. The plans specify plumbing materials, pipe types, fixture details, and installation requirements, with a focus on bathroom facilities in men's and women's restrooms, mechanical/storage areas, and an elevator area.
The technical specifications outline precise requirements for pipe materials, including copper and PVC, with specific guidelines for underground and above-grade installations. The fixture schedule details equipment like water closets, lavatories, urinals, and a utility sink, with provisions for ADA-compliant fixtures. The design includes an electric water heater (EWH-1) with 50-gallon capacity, operating at 208V, and incorporates water hammer arrestors and thermal expansion tanks. The plumbing system is designed with attention to code compliance, including Florida Plumbing Code requirements, and includes detailed specifications for pipe supports, insulation, and installation techniques.
View the file
Other files
Show all 29
On GovTribe
Work with this file
- Download the original file
- Contacts named in this file
- Similar government files
- Ask GovTribe AI about this file
Text version
A FOUNDATION MAY BE REQUIRED IN VERY POOR SOIL CONDITIONS.
BEDDING IS REQUIRED PRIMARILY TO BRING THE TRENCH BOTTOM UP TO GRADE. BEDDING
MATERIALS SHALL PROVIDE A UNIFORM AND ADEQUATE LONGITUDINAL SUPPORT UNDER THE
PIPE. IN DRY SOIL CONDITIONS, CLASS II OR III MATERIAL SHALL BE HAND PLACED IN 4−6", LIGHTLY
COMPACTED UNIFORM AND NOT FINER THAN THE FOUNDATION MATERIAL. IN WET CONDITIONS,
CLASS I, II OR III MATERIAL SHALL BE HAND PLACED, 4−6", UNIFORM AND NOT FINER THAN THE FOUNDATION MATERIAL. WHEN UTILIZING CLASS I MATERIAL, SUFFICIENT AMOUNTS OF CLASS II OR III MATERIAL SHALL BE ADDED TO FILL ALL VOIDS CREATED BY THE USE OF CLASS I MATERIAL.
HAUNCHING MATERIAL SHALL BE HAND PLACED TO THE SPRINGLINE OF THE PIPE. CLASS II OR III MATERIAL SHALL BE CONSOLIDATED UNDER THE PIPE AND HAND TAMPED TO PROVIDE ADEQUATE
SIDE SUPPORT.
INITIAL BACKFILL MATERIAL SHALL BE CLASS II OR III. IT SHALL BE PLACED WITHIN 24−30" ABOVE
THE TOP OF THE PIPE AND TAMPED BY A PORTABLE VIBRATOR.
FINAL BACKFILL MATERIAL MAY BE MACHINE PLACED. THE MATERIAL SHALL BE CLASS II OR III
MATERIAL. CLASS IV MATERIAL MAY BE INSTALLED OUTSIDE OF ROADWAY. FINAL BACKFILL
UNDER ROADWAYS MAY REQUIRE SPECIAL COMPACTION AND DENSITY TESTS. A MINIMUM OF 30"
OF COVER OVER THE TOP OF THE PIPE SHALL BE PROVIDED BEFORE THE TRENCH IS WHEEL−
LOADED.
NOTE: ALL EMBEDMENT MATERIALS SHALL BE NO LESS THAN 95% OF MAXIMUM DENSITY.
LABORATORY TESTING OF THE SOIL WILL BE REQUIRED. THIS PROCEDURE SHALL BE REQUIRED
ON ALL INSTALLATIONS.
E M B E D M E N T M
A T E R
IA
L
INITIAL
BACKFILL
HAUNCHING
BEDDING
(MAX 6")
FOUNDATION
(MAY NOT BE
REQUIRED)
SPRING
LINE OF
PIPING
NOT TO SCALE
GENERAL DATA BACKFILLING REQ.
SPRING
LINE OF
PIPING
FOUNDATION (MAY
NOT BE REQUIRED)
HAUNCHING
INITIAL
BACKFILL
BEDDING (MAX 6")
E M B E D M E N T M
A T E R
IA
L
EMBEDMENT MATERIALS
CLASS I:
ANGULAR, 1/2" TO 1−1/2", GRADED STONE, INCLUDING A NUMBER OF FILL MATERIALS THAT HAVE REGIONAL
SIGNIFICANCE SUCH AS CORAL, SLAG, CINDERS, CRUSHED STONE AND CRUSHED SHELLS.
CLASS II:
COARSE SANDS AND GRAVELS WITH MAXIMUM PARTICLE SIZE OF 1i" INCLUDING VARIOUS GRADED SANDS AND GRAVELS CONTAINING SMALL PERCENTAGES OF FINES, GENERALLY GRANULAR AND NON−COHESIVE, EITHER WET OR DRY. SOIL TYPES GW, GP, SW, AND SP ARE INCLUDED IN THIS CLASS.
CLASS III:
FINE SAND AND CLAY GRAVELS, INCLUDING FINE SANDS, SAND−CLAY MIXTURES AND GRAVEL−CLAY
MIXTURES. SOIL TYPES GM, GC, SM, AND SC ARE INCLUDED IN THIS CLASS.
CLASS IV:
SILT, SILTY CLAYS, AND CLAYS, INCLUDING INORGANIC CLAYS AND SILT OF MEDIUM TO HIGH PLASTICITY AND LIQUID LIMITS. SOIL TYPES MH, ML, CH, AND CL ARE INCLUDED IN THIS CLASS. THESE MATERIALS ARE NOT
TO BE USED FOR BEDDING, HAUNCHING, OR INITIAL BACKFILL.
CLASS V:
THIS CLASS INCLUDES THE ORGANIC SOILS, AS WELL AS SOILS CONTAINING FROZEN EARTH, DEBRIS, ROCKS LARGER THAN 1−1/2" IN DIAMETER AND OTHER FOREIGN MATERIALS. THESE MATERIALS ARE NOT TO BE USED
FOR BEDDING, HAUNCHING, OR INITIAL BACKFILL.
NOT TO SCALE
GENERAL DATA SOIL CLASSIFICATION
A. PIPE AND FITTINGS
1. DOMESTIC HOT AND COLD WATER:
(A) UNDERGROUND − TYPE "K" HARD DRAWN COPPER WITH WROUGHT COPPER FITTINGS.
(B) ABOVE GRADE − TYPE "L" HARD DRAWN COPPER WITH WROUGHT COPPER FITTINGS.
2. SANITARY SOIL, WASTE AND VENT:
(A) UNDERGROUND − SERVICE WEIGHT CAST IRON BELL AND SPIGOT ENDS OR SCHEDULE 40 PVC.
(B) ABOVE GRADE − SERVICE WEIGHT CAST IRON NO−HUB OR SCHEDULE 40 PVC.
B. PIPE JOINTS
1. SWEAT SOLDER JOINTS IN COPPER PIPING SYSTEMS SHALL BE MADE WITH STAY−SAFE "BRIDGIT" LEAD FREE BEARING SOLDER WITH STAY−CLEAN LIQUID OR STAY−CLEAN PASTE FLUX BY J.W. HARRIS AND CO. INC.
2. CAST IRON BELL AND SPIGOT − TYLER "TY−SEAL" NEOPRENE JOINTS.
3. CAST IRON NO−HUB NEOPRENE SLEEVE − STAINLESS STEEL TYPE 304 SHIELD AND CLAMP, 24 GUAGE WITH HI− TORQUE CLAMPS TIGHTENED TO 100−12 INCH−POUNDS. CLAMPS SHALL BE CLAMP−ALL CORPORATION, ANAHEIM
FOUNDRY CO. "HUSKY" OR MISSION.
4. SCHEDULE 40 PVC DWV PIPE FITTINGS − SOCKET GLUE OR THREADED.
C. VALVES
1. BALL VALVES SHALL HAVE CHROME PLATED BRASS BALL, VINYL COVERED STEEL HANDLE, TEFLON OR TFE SEATS, TWO−PIECE CONSTRUCTION. VALVES SHALL BE 150 LB. CLASS, MILWAUKEE BA−50, CRANE 9322 , OR WATTS B6001.
2. CHECK VALVES SHALL HAVE BRASS BODY WITH SCREW PATTERN; MILWAUKEE NO. 509, STOCKHAM OR HAMMOND.
3. PLUG VALVES (COCKS): IRON BODIES WITH SCREW PATTERN; A.Y. MCDONNEL #10686, NORDSTROM FIG. 114 OR
NORDSTROM FIG. 115.
D. PIPE INSULATION
1. FIBERGLASS, 1" THICK FOR DOMESTIC HOT WATER AND 1/2" THICK FOR DOMESTIC COLD WATER SYSTEMS; 1" THICK FOR STORM WATER (PRIMARY, SECONDARY PIPING IN ITS ENTIRETY) OWENS CORNING TYPE ASJ/SSL−11. ENDS OF FIBERGLASS PIPE INSULATION SHALL BE SEALED WITH FOSTER 30−35 COATING AT ALL FLANGES, VALVES, FITTINGS AND AT INTERVALS OF NOT MORE THAN 20’ OF CONTINUOUS RUNS OF PIPE. VALVE BODIES AND BONNETS SHALL BE
INSULATED. NO STAPLES SHALL BE PERMITTED FOR INSTALLATION OF INSULATION.
E. PIPE HANGERS AND SUPPORTS
1. HANGERS − ADJUSTABLE CARBON STEEL CLEVIS; GRINNEL NO. 260, CT−65.
2. VERTICAL SUPPORT − STEEL RISER CLAMP.
3. PROVIDE COPPER PLATED HANGERS AND SUPPORTS FOR COPPER PIPING.
4. SPACE SUPPORTS NO MORE THAN 8 FEET APART FOR 10−FOOT SECTION OF CAST IRON SOIL PIPE WITH A MINIMUM OF TWO SUPPORTS PER 10−FOOT SECTION. SUPPORT HORIZONTAL SOIL PIPE NEAR EACH HUB. SUPPORTS FOR COPPER
PIPE SHALL BE SPACED NO MORE THAN 5 FEET APART.
F. DRAIN PANS
1. ALL FLOOR DRAIN, EXCEPT FOR THOSE IN CONCRETE SLAB ABOVE EARTHFILL, SHALL BE PROVIDED WITH NON− PLASTICIZED CHLORINATED POLYETHYLENE, "CHLORALOY 240" BRAND CONCEALED WATERPROOFING MEMBRANE.
PLUMBING MATERIALS
1. THE FOLLOWING NOTES ARE GENERAL IN NATURE AND PERTAIN TO THE ENTIRE PROJECT. WHERE THERE ARE EXCEPTIONS, ADDITIONS, OR REVISIONS TO THESE NOTES SUCH EXCEPTIONS, ADDITIONS OR REVISIONS
ARE SO NOTED ON THE PARTICULAR DRAWING THEY OCCUR.
2. PIPING IS SHOWN IN SCHEMATIC FORM. ALL WORK SHALL BE COORDINATED WITH ALL TRADES INVOLVED.
3. REFER TO ARCHITECTURAL PLANS FOR LOCATION OF ALL EQUIPMENT.
4. ACCESS PANELS SHALL BE PROVIDED, WHERE REQUIRED, TO SERVICE VALVES AND OTHER MECHANICAL
EQUIPMENT.
5. ALL VALVES IN CORRIDORS SHALL BE LOCATED 1’− 0" AWAY FROM WALLS CLEAR OF SOFFITS UNLESS
NOTED OTHERWISE.
6. STORM AND SANITARY PIPING 3" AND LARGER SHALL BE SLOPED AT 1/8" PER FOOT UNLESS NOTED
OTHERWISE.
7. VERIFY ALL EQUIPMENT CONNECTIONS WITH MANUFACTURERS CERTIFIED DRAWINGS. FIELD VERIFY AND
COORDINATE ALL DIMENSIONS PRIOR TO FABRICATION.
8. FIELD VERIFY ALL EXISTING CONDITIONS DURING DEMOLITION AND REROUTE PIPING CONFIGURATIONS AS
NECESSARY.
9. UNLESS NOTED OR OBVIOUS OTHERWISE, PIPE RUNS SHOWN OCCUR IN THE CEILING SPACE OF THE LEVEL
INDICATED ON PLANS.
ADA REQUIREMENTS
PLUMBING LEGEND
DETAIL NUMBER
SHEET NUMBER
DETAIL NUMBER
SHEET NUMBER
REFERENCE SHEET
SECTION NUMBER
SHEET NUMBER
SECTION NUMBER
SHEET NUMBER
REFERENCE SHEET
PIPE UP
PIPE DN
ANGLE STOP VALVE
GATE VALVE (2"−12")
BALL VALVE (1/4"−48")
CHECK VALVE (1−1/2"−12")
2"ø DCW
1 1/2"ø DHW
1 1/2"ø DHWR
2"ø V
4"ø SS
LIMIT OF DEMOLITION
CONNECT TO EXISTING
1% SLOPE
2% SLOPE
1/8" / 12" SLOPE
1/4" / 12" SLOPE
NOTES: NOT ALL SYMBOLS SHOWN MAY BE REQUIRED FOR THIS PROJECT.
1. ALL WORK SHALL COMPLY WITH ALL LOCAL BUILDING CODES, LAWS, REGULATIONS,
ORDINANCES, AND CODES AS FOLLOWS:
" ACCESIBILITY: FLORIDA BUILDING CODE − 2020 7TH EDITION
" ENERGY CONSERVATION: FLORIDA BUILDING CODE − 2020 7TH EDITION
" BUILDING: FLORIDA BUILDING CODE − 2020 7TH EDITION
" EXISTING BUILDING: FLORIDA BUILDING CODE − 2020 7TH EDITION
" FUEL GAS: FLORIDA BUILDING CODE − 2020 7TH EDITION
" MECHANICAL: FLORIDA BUILDING CODE − 2020 7TH EDITION
" PLUMBING: FLORIDA BUILDING CODE − 2020 7TH EDITION
" NATIONAL ELECTRICAL CODE − 2014 EDITION
" NATIONAL FIRE PROTECTION ASSOCIATION (NFPA) 101, 2015 LIFE SAFETY CODE
FOR FLORIDA
" APPLICABLE CODE SECTIONS AS REQUIRED BY FLORIDA ADMINISTRATIVE CODE
69A−3.012
" AMERICANS WITH DISABILITY ACT 2010 (ADA 2010)
CODE REFERENCES
ADA REQUIREMENTS
THIS APPLIES TO HANDICAPPED ACCESSIBLE FIXTURES ONLY.
WATER CLOSETS: THE HEIGHT OF WATER CLOSETS SHALL BE 17" TO 19" MEASURED TO
THE TOP OF THE TOILET SET. SEATS SHALL NOT BE SPRUNG TO RETURN TO A
LIFTED POSITION. THE WATER CLOSET SHALL BE LOCATED 18" FROM THE SIDE WALL
TO THE CENTER LINE OF THE BOWL. HAND OPERATED FLUSH CONTROLS SHALL BE
MOUNTED ON THE WIDE SIDE OF TOILET AREAS NO MORE THAN 29" ABOVE THE
FINISH FLOOR. SEE ARCHITECTURAL DRAWINGS FOR GRAB BAR LOCATIONS.
URINALS: THE URINALS SHALL BE WALL HUNG WITH AN ELONGATED RIM AT A
MAXIMUM OF 17" ABOVE THE FINISH FLOOR. HAND OPERATED FLUSH CONTROLS SHALL
BE MOUNTED NO MORE THAN 44" ABOVE FINISH FLOOR.
LAVATORIES: LAVATORIES SHALL BE MOUNTED WITH THE RIM OR COUNTER SURFACE
NO HIGHER 34" ABOVE THE FINISH FLOOR. PROVIDE A CLEARANCE OF AT LEAST 29"
ABOVE THE FINISH FLOOR TO THE BOTTOM OF THE APRON. KNEE SPACE SHALL BE 8"
FROM BOTTOM EDGE OF APRON TO THE LEADING EDGE OF THE BOTTOM OF THE
BOWL. THE BOTTOM OF THE BOWL SHALL BE A MINIMUM OF 27" ABOVE THE FINISH
FLOOR. ALL WATER AND DRAIN PIPING UNDER LAVATORIES SHALL BE INSULATED
WITH A FOAM INSERT COVERED WITH A 1/8" VINYL OUTER SHELL. ANGLE STOPS SHALL
HAVE A FLIP TOP ACCESS.
FAUCETS: CONTROLS SHALL BE LEVER HANDLES OPERABLE WITH ONE HAND AND
SHALL NOT REQUIRE TIGHT GRASPING, PINCHING, OR TWISTING OF THE WRIST. THE
FORCE REQUIRED TO ACTIVATE CONTROLS SHALL BE NO GREATER THAN 5 LBF.
SINKS: SINKS SHALL BE MOUNTED WITH THE RIM OR COUNTER SURFACE NO HIGHER
34" ABOVE THE FINISH FLOOR. PROVIDE A KNEE CLEARANCE OF AT LEAST 27" HIGH,
30" WIDE, AND 19" DEEP. SINKS SHALL BE A MAXIMUM OF 6 1/2" DEEP. ALL WATER AND
DRAIN PIPING UNDER LAVATORIES SHALL BE INSULATED WITH A FOAM INSERT
COVERED WITH A 1/8" VINYL OUTER SHELL. ANGLE STOPS SHALL HAVE A FLIP TOP
ACCESS.
SCALE:
877 CR 393 North Santa Rosa Beach, FL 32459 850.267.0759
A
54321
B
C
D
E
APPROVED BY
CHECKED BY
SHEET NO.
TITLE
DRAWN BY
DATE
PROJECT NO.
SCALE
SEAL
REVISIONS
NO. DESCRIPTION DATE
W3 Engineering Inc.
110 E. WRIGHT ST.
PENSACOLA, FL 32501
T: (850)629-8270
F: (888)478-4898
FL P.E. #: 70595
FL AUTHORIZATION #: 31078
James E. Wells III
P.E. Number: 70595
As indicated
/2
/2
:2
:0
A
M
P-001
PLUMBING
LEGEND, ABBREV.
& NOTES
-G
R A
Y T
O N
B E
A C
H
E n te r a d d re s s h e re
7/15/24
BEJ
JEW3
JEW3
ISSUED FOR BID
MENS RESTROOM
MECHANICAL /
STORAGE
WOMENS
RESTROOM
ELEV.
P−2
P−2
P−3A P−3 P−1
P−2A P−1A
P−5
P−2A P−1A
P−1P−1P−1P−1P−1
P−2
P−2
P-301P-111
4"FCO
2−WAY
4"GCO
2" D
C W
S S
BUILDING DRAIN
HORIZONTAL
BRANCH DRAIN
HORIZONTAL
BRANCH DRAIN
P-301P-111
P-301P-111
P-301P-111
A
2" SS
S S
4"FCO
FD/SI
FD/SI
FD/SI
4"FCO
2" V
2" V
2" V
2" S
S
2" S
S
2" S
S
S S
2" S
S
4" SS
4" SS
4" S
S
3" SS
4" SS
2" S
S
S S
S S
S S
S S
S S
4" SS
SCALE:
877 CR 393 North Santa Rosa Beach, FL 32459 850.267.0759
A
54321
B
C
D
E
APPROVED BY
CHECKED BY
SHEET NO.
TITLE
DRAWN BY
DATE
PROJECT NO.
SCALE
SEAL
REVISIONS
NO. DESCRIPTION DATE
W3 Engineering Inc.
110 E. WRIGHT ST.
PENSACOLA, FL 32501
T: (850)629-8270
F: (888)478-4898
FL P.E. #: 70595
FL AUTHORIZATION #: 31078
James E. Wells III
P.E. Number: 70595
1/4" = 1'-0"
/2
/2
:2
:0
A
M
P-111
PLUMBING
OVERALL BELOW
FIRST FLOOR PLAN
-G
R A
Y T
O N
B E
A C
H
E n te r a d d re s s h e re
7/15/24
BEJ
JEW3
JEW3
ISSUED FOR BID
SCALE:
0 4’ 8’
1/4" = 1’ − 0"
4’ 8’
1/4" = 1'-0"P-111
PLUMBING OVERALL BELOW FIRST FLOOR
PLAN
P-301P-111
P-301P-111
P-301P-111
P-301P-111
MENS RESTROOM
MECHANICAL /
STORAGE
WOMENS
RESTROOM
ELEV.
ET−1
P−2
P−2 P−3A P−3
P−1 P−2A
P−1A
P−5
P−2A
P−1AP−1P−1P−1P−1P−1
P−2
P−2
4"FCO
2−WAY
4"GCO
A
2 1/2" V P-401
P-402
P-401
P-402
24"FCO
TMV
FD/SI
HB/VB
WH/VB
FD/SI
4"FCO
WH/VB
FD/SI
4"FCO
SCALE:
877 CR 393 North Santa Rosa Beach, FL 32459 850.267.0759
A
54321
B
C
D
E
APPROVED BY
CHECKED BY
SHEET NO.
TITLE
DRAWN BY
DATE
PROJECT NO.
SCALE
SEAL
REVISIONS
NO. DESCRIPTION DATE
W3 Engineering Inc.
110 E. WRIGHT ST.
PENSACOLA, FL 32501
T: (850)629-8270
F: (888)478-4898
FL P.E. #: 70595
FL AUTHORIZATION #: 31078
James E. Wells III
P.E. Number: 70595
1/4" = 1'-0"
/2
/2
:2
:0
A
M
P-112
PLUMBING
OVERALL ABOVE
FIRST FLOOR PLAN
-G
R A
Y T
O N
B E
A C
H
E n te r a d d re s s h e re
7/15/24
BEJ
JEW3
JEW3
ISSUED FOR BID
SCALE:
0 4’ 8’
1/4" = 1’ − 0"
4’ 8’
1/4" = 1'-0"P-112
PLUMBING OVERALL ABOVE FIRST FLOOR
PLAN
LOCAL
INFORMATION
ELEV.
A
2 1/2" V
SCALE:
877 CR 393 North Santa Rosa Beach, FL 32459 850.267.0759
A
54321
B
C
D
E
APPROVED BY
CHECKED BY
SHEET NO.
TITLE
DRAWN BY
DATE
PROJECT NO.
SCALE
SEAL
REVISIONS
NO. DESCRIPTION DATE
W3 Engineering Inc.
110 E. WRIGHT ST.
PENSACOLA, FL 32501
T: (850)629-8270
F: (888)478-4898
FL P.E. #: 70595
FL AUTHORIZATION #: 31078
James E. Wells III
P.E. Number: 70595
1/4" = 1'-0"
/2
/2
:2
:0
A
M
P-113
PLUMBING
OVERALL SECOND
FLOOR PLAN
-G
R A
Y T
O N
B E
A C
H
E n te r a d d re s s h e re
7/15/24
BEJ
JEW3
JEW3
ISSUED FOR BID
SCALE:
0 4’ 8’
1/4" = 1’ − 0"
4’ 8’
1/4" = 1'-0"P-113
1 PLUMBING OVERALL SECOND FLOOR PLAN
LEVEL 1
5' - 6"
LEVEL 2
20' - 0"
P−5
ET−1
P−1A 4"FCO
P−1A
2−WAY
4"GCO
4" SS
2" DCW
MENS RESTROOM
WOMENS
RESTROOM
FIRST FLOOR
LEVEL
5' - 6"
4" SS2
/8
EWH−1
/2
REFER TO CIVIL FOR
CONTINUATION.
2 1/2" V
1/ 2"
V
2" V
2" V
2" V
1 1/2" DHW
2" DCW
LEVEL 1
5' - 6"
LEVEL 2
20' - 0"
MENS RESTROOM
FIRST FLOOR
LEVEL
5' - 6"
P−2
FD/SI
2" V
4" SS
4"FCO
2" V
LEVEL 1
5' - 6"
LEVEL 2
20' - 0"
P−2 P−1 P−1 P−1 P−1 P−1
P−2A
4"FCO
P−1A
FIRST FLOOR
LEVEL
5' - 6"
4"FCOFD/SI
4" SS
2" V
2" V
2" DCW1 1/2" DCW
2" V
2" V
2" V
2" V
2" V
2" V
2" V
2" V
1 1/2" DHW3/4" DHW
2 1/2" V
LEVEL 1
5' - 6"
LEVEL 2
20' - 0"
ROOF
30' - 0"
2" DCW
P−5
ET−1
2 1/2" V
1/ 2"
V
4" SS 3" SS
LOCAL
INFORMATION
FIRST FLOOR
LEVEL
5' - 6"
4"FCO
2" V
FD/SI
HB/VB
WH/VB
4" SS
EWH−1
TMV
2" V
2" V
2" V
2" V
2" V
2" V
2" V
2" V
2" V
2" DCW
1 1/2" DHW
3/4" DHW
1 1/2" DCW
SCALE:
877 CR 393 North Santa Rosa Beach, FL 32459 850.267.0759
A
54321
B
C
D
E
APPROVED BY
CHECKED BY
SHEET NO.
TITLE
DRAWN BY
DATE
PROJECT NO.
SCALE
SEAL
REVISIONS
NO. DESCRIPTION DATE
W3 Engineering Inc.
110 E. WRIGHT ST.
PENSACOLA, FL 32501
T: (850)629-8270
F: (888)478-4898
FL P.E. #: 70595
FL AUTHORIZATION #: 31078
James E. Wells III
P.E. Number: 70595
1/4" = 1'-0"
/2
/2
:2
:1
A
M
P-301
PLUMBING
SECTION/INVERT
PLAN
-G
R A
Y T
O N
B E
A C
H
E n te r a d d re s s h e re
7/15/24
BEJ
JEW3
JEW3
ISSUED FOR BID
SCALE:
0 2’ 4’
1/2" = 1’ − 0"
2’ 4’
1/4" = 1'-0"P-301
1 SECTION / INVERT-1
1/4" = 1'-0"P-301
2 SECTION / INVERT-2
1/4" = 1'-0"P-301
3 SECTION / INVERT-3
1/4" = 1'-0"P-301
4 SECTION / INVERT-4
MENS RESTROOM
MECHANICAL /
STORAGE
2" D
C W
2−WAY
4"GCO
P−2
P−2
P−3A P−3
P−1
P−2A
P−1A
ET−1
P−5
EWH−1
FD/SI
4"FCO
WH/VB
HB/VB
FD/SI
TMV
2" DCW
3/4" DHW 1 1/2" DHW
1 1/2" DCW1/2" DCW
4"FCO
MENS RESTROOM
MECHANICAL /
STORAGE
2−WAY
4"GCO
FD/SI
2" V 2" V 2" V 2" V 2" V
2" V
2" V
4" SS
S S
4" S
S
2" S
S
2" S
S
2" S
S
S S
2" S
S
4" S
S
S S
S S
P−2
P−2
2" V
2" V
1/ 2"
VET−1
EWH−1
P−5
3" SS
2 1/2" V
FD/SI
4"FCO
4"FCO
SCALE:
877 CR 393 North Santa Rosa Beach, FL 32459 850.267.0759
A
54321
B
C
D
E
APPROVED BY
CHECKED BY
SHEET NO.
TITLE
DRAWN BY
DATE
PROJECT NO.
SCALE
SEAL
REVISIONS
NO. DESCRIPTION DATE
W3 Engineering Inc.
110 E. WRIGHT ST.
PENSACOLA, FL 32501
T: (850)629-8270
F: (888)478-4898
FL P.E. #: 70595
FL AUTHORIZATION #: 31078
James E. Wells III
P.E. Number: 70595
1/2" = 1'-0"
/2
/2
:2
:1
A
M
P-401
PLUMBING
ENLARGED FLOOR
PLAN SET-1
-G
R A
Y T
O N
B E
A C
H
E n te r a d d re s s h e re
7/15/24
BEJ
JEW3
JEW3
ISSUED FOR BID
SCALE:
0 2’ 4’
1/2" = 1’ − 0"
2’ 4’
1/2" = 1'-0"P-401
ENLARGED MENS RESTROOM FLOOR PLAN -
DOMESTIC WATER
1/2" = 1'-0"P-401
ENLARGED MENS RESTROOM FLOOR PLAN -
SANITARY SEWER
WOMENS
RESTROOM
FD/SI
4"FCO
P−2
P−2
1 1/2" DHW3/4" DHW
1/2" DHW
1 1/2" DCW 2" DCW
2" D
C W
1/ 2"
D H W
P−1 P−1 P−1 P−1 P−1
P−2A
P−1A
4"FCO
WH/VB
WOMENS
RESTROOM
FD/SI
4"FCO
P−2
P−2
2" SS
4" SS
4" SS
4" SS
4" SS
4" SS
4" SS
2" SS
4" SS
S S
4"FCO
S S
4" SS2" V 2" V 2" V 2" V 2" V 2" V 2" V
2" V
2" V 2" V
1/ 2"
V
S S
4" SS
P−1 P−1 P−1 P−1 P−1
P−2A
P−1A
2" V
SCALE:
877 CR 393 North Santa Rosa Beach, FL 32459 850.267.0759
A
54321
B
C
D
E
APPROVED BY
CHECKED BY
SHEET NO.
TITLE
DRAWN BY
DATE
PROJECT NO.
SCALE
SEAL
REVISIONS
NO. DESCRIPTION DATE
W3 Engineering Inc.
110 E. WRIGHT ST.
PENSACOLA, FL 32501
T: (850)629-8270
F: (888)478-4898
FL P.E. #: 70595
FL AUTHORIZATION #: 31078
James E. Wells III
P.E. Number: 70595
1/2" = 1'-0"
/2
/2
:2
:1
A
M
P-402
PLUMBING
ENLARGED FLOOR
PLAN SET-2
-G
R A
Y T
O N
B E
A C
H
E n te r a d d re s s h e re
7/15/24
BEJ
JEW3
JEW3
ISSUED FOR BID
SCALE:
0 2’ 4’
1/2" = 1’ − 0"
2’ 4’
1/2" = 1'-0"P-402
ENLARGED WOMENS RESTROOM FLOOR PLAN
- DOMESTIC WATER
1/2" = 1'-0"P-402
ENLARGED WOMENS RESTROOM FLOOR PLAN
- SANITARY SEWER
ADJUSTABLE HOUSING
WITH LEVELING SCREWS
PIPE EXTENSION
WITH CLEANOUT
PLUG
FINISH FLOOR
FURNISH FLANGE AND
CLAMPING RING FOR
WATERPROOFING
MEMBRANE
NOTE: PROVIDE NICKEL BRONZE
ADJUSTABLE CARPET FRAME
COVER IN AREAS WHERE FINAL
FLOOR FINISH CONSISTS OF
CARPETING. COORDINATE WITH
ARCHITECTURAL DWGS FOR
FINAL FLOOR FINISH.
SECURED RIM SCORIATED
COVER WITH VANDAL
RESISTANT SCREWS, COVER
WITH "C.O." NICKEL−BRONZE
NOTE:
" SLOPE FLOOR TO FLOOR DRAIN COORDINATE WITH ARCHITECTURAL PLANS.
" EACH PLUMBING FIXTURE SHALL BE SEPARATELY TRAPPED BY A LIQUID−
SEAL TRAP.
" THE VERTICAL DISTANCE FROM THE FIXTURE OUTLET TO THE TRAP WEIR
SHALL NOT EXCEED 24", AND THE HORIZONTAL DISTANCE SHALL NOT
EXCEED 30" MEASURED FROM THE CENTERLINE OF THE FIXTURE OUTLET
TO THE CENTERLINE OF THE INLET OF THE TRAP.
" VERTICAL RISE OF VENT TO A POINT NOT LESS THAN 6" ABOVE THE
FLOOD LEVEL RIM OF THE HIGHEST TRAP OR TRAPPED FIXTURE BEING
VENTED.
" MAXIMUM DISTANCE OF 1 1/4" FIXTURE TRAP FROM VENT SHALL BE 5 FT.
" MAXIMUM DISTANCE OF 1 1/2" FIXTURE TRAP FROM VENT SHALL BE 6 FT.
" MAXIMUM DISTANCE OF 2" FIXTURE TRAP FROM VENT SHALL BE8 FT.
" MAXIMUM DISTANCE OF 3" FIXTURE TRAP FROM VENT SHALL BE 12 FT.
" MAXIMUM DISTANCE OF 4" FIXTURE TRAP FROM VENT SHALL BE 16 FT.
FINISHED FLOOR
DRAIN STRAINER FLUSH WITH
FINISHED FLOOR WTIH
ADJUSTABLE DRAIN HEAD.
1/2" TRAP PRIMER
CONNECTION
NON−SHRINK
GROUTE
DEEP SEAL "P" TRAP
CAST IRON
DRAIN BODY
WATERPROOFING
MEMBRANE
INVERTED COLLAR
SANITARY
TEE
FIXTURE
VENT
COUNTERSUNK
BRASS CLEANOUT
PLUG.
24"x24"x4" SEWER
CLEANOUT PAD.
REINFORCED WITH
DOUBLE (2) WIRES.
2−WAY CLEANOUT
FITTING
2’ − 0"
GRADE
CW SUPPLY
ISOLATION VALVE
ROUTE TO FLOOR DRAIN
TRAP PRIMER
ANCHOR TO SURFACE WITH
UNISTRUT AND PIPE CLAMPS
MIN 1/2" COPPER
CW LINE
EXPOSED
INTENDED FOR
MECHANICAL/EQUIPMENT
APPLICATION ONLY.
MIN. 1/2" COPPER LINE
TO FLOOR DRAIN DRAP
SLEEVE PIPE BELOW FLOOR
W/ 27 MIL. FLEX PIPE
PROTECTOR
HEAVY DUTY CHROME
PLATED BRONZE
HEAD CASTING.
HEAVY DUTY BRASS
CASING TUBE.
/4
"ø D C W
VANDAL RESISTANT INTEGRAL
VACUUM BREAKER AND 3/4"
MALE HOSE CONNECTION.
HINGED LOCKING COVER
RECOMMENDED WALL
OPENING 4−1/4" x 6−1/4".
DUAL O−RING
PISTON
1/2" WATER HAMMER
ARRESTOR SHALL BE
PDI RATED AND
APPROVED.
1"ø DCW
1" ø
D C W
CHECK VALVE
ISOLATION VALVE
CHECK VALVE
THERMOMETER
THERMOSTATIC
MIXING VALVE
ROUTE TO FLOOR DRAIN
SAFETY PAN. ROUTE 1" PAN DRAIN TO FD WITH AIR GAP.
HOSE BIBB WITH VACUUM BREAKER
ELECTRIC WATER HEATER
CW SUPPLY
TEMP. AND PRESSURE
RELIEF VALVE
VACUUM RELIEF VALVE
EXPANSION TANK
110°F HW TO FIXTURES
BALL VALVE OR LUG
BUTTERFLY VALVE
HEAT TRAP
SCALE:
877 CR 393 North Santa Rosa Beach, FL 32459 850.267.0759
A
54321
B
C
D
E
APPROVED BY
CHECKED BY
SHEET NO.
TITLE
DRAWN BY
DATE
PROJECT NO.
SCALE
SEAL
REVISIONS
NO. DESCRIPTION DATE
W3 Engineering Inc.
110 E. WRIGHT ST.
PENSACOLA, FL 32501
T: (850)629-8270
F: (888)478-4898
FL P.E. #: 70595
FL AUTHORIZATION #: 31078
James E. Wells III
P.E. Number: 70595
As indicated
/2
/2
:2
:1
A
M
P-501
PLUMBING DETAIL
SET-1
-G
R A
Y T
O N
B E
A C
H
E n te r a d d re s s h e re
7/15/24
BEJ
JEW3
JEW3
ISSUED FOR BID
FLOOR CLEANOUT DETAIL EDITED
FLOOR DRAIN DETAIL EDITED
TWO−WAY GRADE CLEANOUT DETAIL
TRAP PRIMER DETAIL EDITED
WALL HYDRANT DETAIL
WATER HAMMER ARRESTOR DETAIL
WATER HEATER W/ MIXING VALVE EDITED
ADJUSTABLE ROLLER HANGER
WELD SADDLE
TO PIPE.
HANGER ROD
ADJUSTABLE CLEVIS HANGER
SIDE VIEW
BAND
NOTE:
" REFER TO STANDARD PRACTIC MSS SP−58 MAXIMUM HORIZONTAL PIPE AND
SUPPORT SPACING.
" FOR TRAPEZE HANGER TAKE SPACING OF SMALLEST SIZE ON TRAPEZE.
" ALL EQUIPMENT MOUNTINGS ARE TO RESIST FORCES OF 0.5 TIMES THE
EQUIPMENT WEIGHT IN ANY HORIZONTAL DIRECTION AND 1.5 TIMES IN THE
DOWNWARD DIRECTION.
INSULATION SHEILD
AT HANGER.
PROVIDE HIGH
COMPRESSIVE
STRENGTH INSULATION
INSERT BLOCKS UNDER
INSULATION SHIELD.
INSULATION (VAPOR
BARRIER TYPE IS
REQUIRED FOR LOW
TEMPERATURE PIPE).
HANGER
ROD
INSULATION (VAPOR
BARRIER TYPE IS
REQUIRED FOR LOW
TEMPERATURE PIPE).
i" DIA. HANGER RODS WITH
36" MAX SPACING ON EACH
CHENNEL.
PROVIDE INSULATION
SHIELD AND INSERT FOR
ALL PIPING MAX 8".
12 GAGE
CHANNEL OR 2"
X 2" X r" ANGLE.
CARRIER
PIPE.
STANDARD PRACTICE MSS SP−58 TABLE 4 MAXIMUM
HORIZONTAL PIPE HANGER AND SUPPORT SPACING
NOMINAL PIPE
OR TUBE SIZE
STD WEIGHT STEEL PIPE COPPER TUBE FIRE
PROTECTION
DUCTILE IRON
PIPE
CAST IRON
SOIL
GLASS PLASTIC
FIBERGLASS
REINFORCEDWATER SERVICE VAPOR SERVICE WATER SERVICE VAPOR SERVICE
NPS−IN FT FT FT FT
F O L L O W
R E Q U
IR
E M E N T S O
F T
H E N
A T
IO
N A L F
IR
E P
R O T E C T
IO
N
A S S O C
IA
T
IO
N S E E
S E C T
IO
N
.4
F T M
A X S
P A C
IN
G M
IN
O F O
N E 1) H
A N G E R P
E R P
IP
E S
E C T
C L O S E T
O J
O
IN
T O
N T H E B
A R R E L A L S O A
T C
H A N G E O
F D
IR
E C T
IO
N A
N D B
R A N
H
O N N E C T
IO
N S S E E
S E C T
IO
N
.3 .4
F
T M
A X S
P A C
IN
G M
IN
O F O
N E 1) H
A N G E R P
E R P
IP
E S
E C T
O S E T
O J
O
IN
T O
N T H E B
A R R E L A L S O A
T C
H A N G E O
F D
IR
E C T
IO
N A
N D B
R A N
H
O N N E C T
IO
N S S E E
S E C T
IO
N
.3 .4
F
T M
A X S
P A C
IN
G F O L L O W
P
IP
E M
A N U F A C T U R E R ’S
R E C O M M E N D A T
IO
N S S
E E S
E C T
IO
N .3
.5
F O L L O W
P
IP
E M
A N U F A C T U R E R ’S
R E C O M M E N D A T
IO
N S F
O R M
A T E R
IA
D S
E R V
IC
E C O N D
IT
IO
N S E E S
E C T
IO
N
.3 .6
F O L L O W
P
IP
E M
A N U F A C T U R E R ’S
R E C O M M E N D A T
IO
N S F
O R M
A T E R
IA
D S
E R V
IC
E C O N D
IT
IO
N S E E S
E C T
IO
N
.3 .7
1/4 − − 5 5
3/8 7 8 5 6
1/2 7 8 5 6
3/4 7 9 5 7
1 7 9 6 8
1 1/4 7 9 7 9
1 1/2 9 12 8 10
2 10 13 8 11
2 1/2 11 14 9 13
3 12 15 10 14
3 1/2 13 16 11 15
4 14 17 12 16
5 16 19 13 18
6 17 21 14 20
8 19 24 16 23
10 22 26 18 25
12 23 30 19 28
14 25 32 − −
16 27 35 − −
18 28 37 − −
20 30 39 − −
24 32 42 − −
30 33 44 − −
NOTE:
(A) FOR SPACING SUPPORTS INCORPORATING TYPE 40 SHEILDS, SEE TABLE A3.
(B) THIS TABLE DOES NOT APPLY WHERE SPAN CALCULATIONS ARE MADE OR WHERE THERE ARE CONCENTRATED LOADS BETWEEN SUPPORTS SUCH AS FLANGES, VALVES, SPECIALTIES, ETC., OR CHANGES IN DIRECTION REQUIRING ADDITIONAL SUPPORTS.
(C) UNBALANCED FORCES OF HYDROSTATIC OR HYDRODYNAMIC ORIGIN (THRUST FORCES) UNLESS RETRAINED EXTERNALLY CAN RESULT IN PIPE
MOVEMENT AND SEPARATION OF JOINTS IF THE JOINTS OF THE SYSTEM ARE
NOT OF A RESTRAINED JOINT DESIGN. SEE SECTION 7.5.3.
NOTE:
" UNLESS OTHERWISE APPROVED ALLOWABLE LOAD ON UPPER ATTACHEMENTS IS 1/4 OF FAILURE LOAD.
" UPPER ATTACHMENTS MAY BE TO WOOD STRUCTURES ALSO.
" WIRE USE IS NOT PRECULDED BY THESE ILLUSTRATIONS.
" NOT ALL ATTACHMENT DEVICES SHOWN, REFER TO SMACNA DUCT CONSTRUCTION STANDARDS.
FLAT BAR CONCRETE INSERT
#1 #4 #5*
#3b*
WASHER
WASHER
STRAP
NUT
#7* #8 #9*
WASHER
EXPANSION SHIELDS EXPANSION NAIL
CONCRETE ANCHORS
RETAINING CLIP
HANGER ROD
#6a C−CLAMP WITH RETAINING CLIP OR #6b C−CLAMP WITH LOCK NUT
(OPTIONAL)
A HANGER STRAP MAY ALSO BE C
CLAMPED TO THE STRUCTURAL FLANGE.
#10 #11 #12 #13*
HANGER
STRAP
COUPLING
HANGER ROD
HANGER
STRAP
NUT & BOLT
FRICTION CLAMPSWELDED STUDSPOWER ACTUATED
STUDS INTO STEEL
(STRUCTURE OR DECK)
NUT
ALTERNATE
#14
WASHER MAY BE OMITTED
WITH 100 LB MAX LOAD ON
22 GA STRAP WHEN
FOLDED.
SCALE:
877 CR 393 North Santa Rosa Beach, FL 32459 850.267.0759
A
54321
B
C
D
E
APPROVED BY
CHECKED BY
SHEET NO.
TITLE
DRAWN BY
DATE
PROJECT NO.
SCALE
SEAL
REVISIONS
NO. DESCRIPTION DATE
W3 Engineering Inc.
110 E. WRIGHT ST.
PENSACOLA, FL 32501
T: (850)629-8270
F: (888)478-4898
FL P.E. #: 70595
FL AUTHORIZATION #: 31078
James E. Wells III
P.E. Number: 70595
NOT TO SCALE
/2
/2
:2
:1
A
M
P-502
PLUMBING DETAIL
SET-2
-G
R A
Y T
O N
B E
A C
H
E n te r a d d re s s h e re
7/15/24
BEJ
JEW3
JEW3
ISSUED FOR BID
PIPE HANGER DETAIL
UPPER ATTACHMENT DEVICE DETAILS
WATER HAMMER ARRESTOR SCHEDULE
P.D.I. UNITS A B C D E F
FIXTURE UNITS 1−11 12−32 33−60 61−113 114−154 155−330
CLASSIFICATIONS ESTABLISHED BY THE PLUMBING AND DRAINAGE INSTITUTE "STANDARD P.D.I.−WH201".
APPROVED MANUFACTURERS:
1. ZURN, WADE, J.R. SMITH, JOSAM, MIFAB
SCALE:
877 CR 393 North Santa Rosa Beach, FL 32459 850.267.0759
A
54321
B
C
D
E
APPROVED BY
CHECKED BY
SHEET NO.
TITLE
DRAWN BY
DATE
PROJECT NO.
SCALE
SEAL
REVISIONS
NO. DESCRIPTION DATE
W3 Engineering Inc.
110 E. WRIGHT ST.
PENSACOLA, FL 32501
T: (850)629-8270
F: (888)478-4898
FL P.E. #: 70595
FL AUTHORIZATION #: 31078
James E. Wells III
P.E. Number: 70595
/2
/2
:2
:2
A
M
P-601
PLUMBING
SCHEDULES
-G
R A
Y T
O N
B E
A C
H
E n te r a d d re s s h e re
7/15/24
BEJ
JEW3
JEW3
ISSUED FOR BID
ELEC WATER HEATER SCHEDULE
MARK
CAPACITY
GAL
INLET
TEMP
OUTLET
TEMP
RECOVERY
GAL/HR
1ST HUR
DELIVERY
GAL/HR
ELECTRICAL DATA
DESCRIPTION
KW VOLTAGE PHASE Hz
EWH−1 50 40 140 50 90 12 208 V 1 60 Hz AO SMITH DRE−52−12
PLUMBING FIXTURE SCHEDULE
LABEL DESCRIPTION CW HW SAN COMMENTS
FD/SI FLOOR DRAIN WITH
SAND INTERCEPTOR
57 GALLON SAND INTERCEPTOR, GRATED COVER, POLYETHYLENE CATCH BASIN WITH H20 RATED CAST IRON GRATE AND BCB−7 SEDIMENT BASKET, STRIEM
CB−50−G
P−1 WATER CLOSET 1" − 3" FLOOR−MOUNTED, REAR OUTLET, VITREOUS CHINA, ELONGATED BOWL, TOP SPUD FLUSHOMETER BOWL, KOHLER ANGLESEY K−4352; TOILET MANUAL
FLUSHOMETER VALVE, 1.6 GPF, KOHLER PRIMME
P−1A WATER CLOSET ADA 1" − 3" FLOOR−MOUNTED, REAR OUTLET, VITREOUS CHINA, ELONGATED BOWL, TOP SPUD FLUSHOMETER BOWL, KOHLER ANGLESEY K−4352; TOILET MANUAL
FLUSHOMETER VALVE, 1.6 GPF, KOHLER PRIMME
P−2 LAVATORY 1/2" 1/2" 1 1/2" SINGLE FAUCET HOLE, DROP−IN OVAL LAVATORY, VITREOUS CHINA, KOHLER BRYANT K−2699−1; POLISHED CHROME−PLATED SINGLE LAVATORY, 0.5 GPM, SLOW−CLOSING METERING FAUCET, AND VANDAL−RESISTANT, ADA COMPLIANT HANDLE, ZURN Z86100−XL
P−2A LAVATORY ADA 1/2" 1/2" 1 1/2" SINGLE FAUCET HOLE, WALL−MOUNT LAVATORY, VITREOUS CHINA, KOHLER BRENHAM K−1997−SS1; POLISHED CHROME−PLATED SINGLE LAVATORY, 0.5 GPM, SLOW−CLOSING METERING FAUCET, AND VANDAL−RESISTANT, ADA COMPLIANT HANDLE, ZURN Z86100−XL
P−3 URINAL 3/4" − 2" WALL−MOUNTED HIGH−EFFICIENCY WASHOUT URINAL, TOP SPUD FLUSHOMETER, KOHLER BARDON K−4991−ET; URINAL MANUAL FLUSHOMETER VALVE, 0.125 GPF, KOHLER PRIMME
P−3A URINAL ADA 3/4" − 2" WALL−MOUNTED HIGH−EFFICIENCY WASHOUT URINAL, TOP SPUD FLUSHOMETER, KOHLER BARDON K−4991−ET; URINAL MANUAL FLUSHOMETER VALVE, 0.125 GPF, KOHLER PRIMME
P−5 UTILITY SINK 1/2" 1/2" 3" FREE STANDING UTILITY SINK, 14"DX20"LX24"W BASIN, MUSTEE 19CFT W/ MUSTEE 93.600 FAUCET
FIXTURE UNIT SCHEDULE
DESCRIPTION QUANTITY WSFU − CW WSFU − HW WSFU − TOTAL DFU
FLOOR DRAIN WITH SAND INTERCEPTOR 3 0 0 0 9
LAVATORY 4 6 6 8 4
LAVATORY ADA 2 3 3 4 2
URINAL 1 5 0 5 4
URINAL ADA 1 5 0 5 4
UTILITY SINK 1 3 3 4 4
WATER CLOSET 6 30 0 30 24
WATER CLOSET ADA 2 10 0 10 8
20 62 12 66 59
NOTES:
" COORDINATE FLOOR DRAIN TYPES WITH FLOOR TYPE ON ARCHITECTURAL PLAN. FLOOR DRAINS IN AREAS W/ EPOXY FLOORING SHALL BE PROVIDED WITH MEMBRANE CLAMP AND ADJUSTABLE COLLAR.
" PROVIDE DEEP SEAL TRAP OR TRAP PRIMER FROM NEAREST FIXTURE TO FLOOR DRAINS IN ACCORDANCE W/ FLORIDA PLUMBING CODE.
" PROVIDE RH OR LH TRIP LEVER FOR ABA/ADA WATER CLOSETS AS REQUIRED FOR GRAB BAR CONFIGURATION.
" PIPE SIZE CONNECTION INDICATED SHALL BE FULL SIZE TO EACH FIXTURE ROUGH IN.
" PROVIDE APPROPRIATE SUPPORT CARRIER FOR WALL MOUNTED FIXTURES.
NOTES:
" FURNISH WATER HEATER WITH T&P RELIEF VALVE, ANODE ROD, DIP TUBE, DRAIN VALVE, DIELECTRIC CONNECTIONS OR UNIONS.
" PROVIDE WATER HEATER STAND WITH DRAIN PAN AND ROUTE DRAIN TO NEAREST FLOOR DRAIN.
" WATER HEATER SHALL MEET OR EXCEED THE THERMAL EFFICIENCY AND/OR STANDBY LOSS REQUIREMENTS OF THE U.S. DEPARTMENT OF ENERGY AND
CURRENT EDITION OF ASHRAE 90.1.
" PROVIDE ASSE 1070 TEMPERATURE REDUCING MIXING VALVE.
DOMESTIC WATER THERMAL EXPANSION TANK SCHEDULE
MARK
CAPACITY
GAL
MAX
ACCEPTABL
E VOLUME
GAL
MAX
WORKING
PRESSURE
PSI
WEIGHT
LBS
DESCRIPTION
ET−1 2.1 1.27 150 5 BASIS OF DESIGN: AO SMITH PMC−2
NOTES:
" BUTYL RUBBER PARABOLIC DIAPHRAGM TYPE.
" FIELD ADJUSTABLE PRE−CHARGED WITH A 38 PSI AIR CHARGE.
P−2
1 DFU P−2
1 DFU
P−3A
4 DFU
P−3
4 DFU
P−1
4 DFU
P−2A
1 DFU
P−1A
4 DFU
P−5
4 DFU
P−2
1 DFU
P−2
1 DFU
P−1
4 DFU
P−1
4 DFU
P−1
4 DFU
P−1
4 DFU
P−1A
4 DFU
4"FCO
P−2A
1 DFU
2−WAY
4"GCO
4"FCO
2" V
FD/SI
3 DFU
2" V
2" V
2" SS
2" V P−1
4 DFU
4" SS
4" SS
4" SS
4" SS
4" SS
2" SS
4"
SS
4"
SS
FD/SI
3 DFU
FD/SI
3 DFU
4"
SS
2" S
S
2" S
S
S S
2" S
S
4"FCO
4" SS
4"
SS
4" SS
4" SS
4" SS
3" SS
S S
S S
2" V
2" V
2" V
2" V
2" V
2" V
2" V
2" V
2 1/2" V
2" V
2" V
2" V
2" V
2" V
2" V
2" V
2" V
2" V
2 1 /2"
V
1/ 2"
V
2" V
4"FCO
4" SS
REFER TO CIVIL FOR
CONTINUATION.
16' - 6 29/32"
1' - 4"
13' - 4 1/2"
/3
23' - 8 13/16"
/3
SCALE:
877 CR 393 North Santa Rosa Beach, FL 32459 850.267.0759
A
54321
B
C
D
E
APPROVED BY
CHECKED BY
SHEET NO.
TITLE
DRAWN BY
DATE
PROJECT NO.
SCALE
SEAL
REVISIONS
NO. DESCRIPTION DATE
W3 Engineering Inc.
110 E. WRIGHT ST.
PENSACOLA, FL 32501
T: (850)629-8270
F: (888)478-4898
FL P.E. #: 70595
FL AUTHORIZATION #: 31078
James E. Wells III
P.E. Number: 70595
/2
/2
:2
:2
A
M
P-901
PLUMBING
SANITARY SEWER
& VENT RISER
PLAN
-G
R A
Y T
O N
B E
A C
H
E n te r a d d re s s h e re
7/15/24
BEJ
JEW3
JEW3
ISSUED FOR BID
SANITARY SEWER & VENT RISER PLAN
P−2
1.5 CWFU
1.5 HWFU
P−2
1.5 CWFU
1.5 HWFU
P−1
5 CWFU
0 HWFU
P−1
5 CWFU
0 HWFU
P−1
5 CWFU
0 HWFU
P−1
5 CWFU
0 HWFU
P−2A
1.5 CWFU
1.5 HWFU
P−1A
5 CWFU
0 HWFU
P−5
3 CWFU
3 HWFU
ET−1
P−1A
5 CWFU
0 HWFU
P−2A
1.5 CWFU
1.5 HWFU
P−1
5 CWFU
0 HWFU
P−3
5 CWFU
0 HWFU
P−3A
5 CWFU
0 HWFU
P−2
1.5 CWFU
1.5 HWFU
P−2
1.5 CWFU
1.5 HWFU WH/VB
HB/VB
TMV
EWH−1
P−1
5 CWFU
0 HWFU
WH/VB
2" DCW
16' - 1 3/16"
22' - 8 1/8"
/1
2' - 10 3/4"
11' - 11 3/4"
2" D
C W
18' - 8 31/32"
1 1/ 2"
DC
W
1 1/ 2"
DC
W
3/ D H W
1/ 2"
D C W
2"
DC
W
1/ 2"
D C W
3/ D H W
1/ 2"
D H W
2"
DC
W
1/2 " D
HW
1/ 2"
D C W
1/2 " D
HW
1/ 2"
D H W
1/ 2"
D C W
1 1/ 2"
DH
W
1 1/ 2"
DH
W
1 1/ 2"
DH
W
REFER TO CIVIL FOR
CONTINUATION.
SCALE:
877 CR 393 North Santa Rosa Beach, FL 32459 850.267.0759
A
54321
B
C
D
E
APPROVED BY
CHECKED BY
SHEET NO.
TITLE
DRAWN BY
DATE
PROJECT NO.
SCALE
SEAL
REVISIONS
NO. DESCRIPTION DATE
W3 Engineering Inc.
110 E. WRIGHT ST.
PENSACOLA, FL 32501
T: (850)629-8270
F: (888)478-4898
FL P.E. #: 70595
FL AUTHORIZATION #: 31078
James E. Wells III
P.E. Number: 70595
/2
/2
:2
:2
A
M
P-902
PLUMBING
DOMESTIC WATER
RISER PLAN
-G
R A
Y T
O N
B E
A C
H
E n te r a d d re s s h e re
7/15/24
BEJ
JEW3
JEW3
ISSUED FOR BID
DOMESTIC WATER RISER PLAN
| Sheets |
| P-001 - PLUMBING LEGEND, ABBREV. & NOTES |
| P-111 - PLUMBING OVERALL BELOW FIRST FLOOR PLAN |
| P-112 - PLUMBING OVERALL ABOVE FIRST FLOOR PLAN |
| P-113 - PLUMBING OVERALL SECOND FLOOR PLAN |
| P-301 - PLUMBING SECTION/INVERT PLAN |
| P-401 - PLUMBING ENLARGED FLOOR PLAN SET-1 |
| P-402 - PLUMBING ENLARGED FLOOR PLAN SET-2 |
| P-501 - PLUMBING DETAIL SET-1 |
| P-502 - PLUMBING DETAIL SET-2 |
| P-601 - PLUMBING SCHEDULES |
| P-901 - PLUMBING SANITARY SEWER & VENT RISER PLAN |
| P-902 - PLUMBING DOMESTIC WATER RISER PLAN |