24-8284_-_Exhibit_M_-_CAXAMBAS_TANK_STRUCTURAL_Rev._1.pdf
PDF 507 KB Posted
- Solicitation number
- 24-8284
- Issued by
- Collier County, Miami City, Florida
About this file
The provided documents are structural engineering drawings for the Caxambas Marina Fuel System Replacement project in Collier County, Florida, prepared by Select Structural. The project involves replacing the fuel system at 909 Collier Ct. on Marco Island, with detailed foundation and slab design for fuel tanks and dispensers. The design is based on the 2023 Florida Building Code and considers specific environmental conditions, including a V-zone flood designation with wind speeds up to 170 MPH and exposure category D.
The structural drawings specify a foundation design using 14"x14" precast concrete piles driven to a safe bearing capacity of 35 tons and uplift capacity of 10 tons. The fuel tank slab is designed to support a maximum tank weight of 100 kips and account for a net buoyancy force of 82 kips when empty. The design includes provisions for flood-resistant materials, breakaway walls, and dry flood-proofing. An independent geotechnical consultant will be retained to monitor pile installation and verify load capacity, with an as-built survey required to document pile locations horizontally and vertically.
View the file
Other files
Show all 14
On GovTribe
Work with this file
- Download the original file
- Contacts named in this file
- Similar government files
- Ask GovTribe AI about this file
Text version
STANDARD ABBREVIATIONS
AB ANCHOR BOLT
ACI AMERICAN CONCRETE INSTITUTE
AFF ABOVE FINISH FLOOR
ALT ALTERNATE
ARCH ARCHITECT
ASCE AMERICAN SOCIETY OF CIVIL ENGINEERS
ASD ALLOWABLE STRESS DESIGN
ASTM AMERICAN SOCIETY FOR TESTING AND MATERIALS
AWS AMERICAN WELDING SOCIETY
@ AT
BLDG BUILDING
BLK BLOCKING
BOT BOTTOM
BP BASE PLATE
BRG BEARING
BTWN BETWEEN
CANT CANTILEVER
CG CENTER OF GRAVITY
CIP CAST IN PLACE
CJ CONTROL JOINT
CL CENTERLINE
CLR CLEAR, CLEARANCE
COL COLUMN
CONC CONCRETE
CONN CONNECTION
CONT CONTINUOUS
CTR CENTER
DEG DEGREES
DIA DIAMETER
DL DEAD LOAD
DN DOWN
DTL DETAIL
DWG DRAWING
DWL DOWEL
(E) EXISTING
EA EACH
EF EACH FACE
EJ EXPANSION JOINT
ELEV ELEVATOR
EQ EQUAL
EW EACH WAY
f’c CONCRETE STRENGTH
FBC FLORIDA BUILDING CODE
FIN FINISH
FND FOUNDATION
FTG FOOTING
Fy YIELD STRENGTH OF STEEL
GA GAUGE
GALV GALVANIZED
GC GENERAL CONTRACTOR
HORIZ HORIZONTAL
K KIPS
KLF KIPS PER LINEAR FOOT
KSF KIPS PER SQUARE FOOT
KSI KIPS PER SQUARE INCH
LL LIVE LOAD
LLH LONG LEG HORIZONTAL
LLV LONG LEG VERTICAL
LRFD LOAD AND RESISTANCE FACTOR DESIGN
Lr ROOF LIVE LOAD
LSH LONG SIDE HORIZONTAL
LSL LONG SLOTTED
LSV LONG SIDE VERTICAL
LW LIGHTWEIGHT
MAX MAXIMUM
MECH MECHANICAL
MEP MECHANICAL, ELECTRICAL AND PLUMBING
MEZZ MEZZANINE
MFR MANUFACTURER
MIN MINIMUM
MISC MISCELLANEOUS
NDS NATIONAL DESIGN SPECIFICATION FOR
WOOD
NOM NOMINAL
NTS NOT TO SCALE
OC ON CENTER
OPP OPPOSITE
OWJ OPEN WEB JOIST
PCF POUNDS PER CUBIC FOOT
PCI PRECAST CONCRETE INSTITUTE
PL PLATE
PLF POUNDS PER LINEAR FOOT
PSF POUNDS PER SQUARE FOOT
PSI POUNDS PER SQUARE INCH
PT PRESSURE TREATED, POST-TENSION
REF REFERENCE
REINF REINFORCEMENT
REQD REQUIRED
REV REVISION
SDI STEEL DECK INSTITUTE
SF SQUARE FOOT
SIM SIMILAR
SOG SLAB ON GRADE
SPEC SPECIFICATION
SS STAINLESS STEEL
SSL SHORT SLOTTED
STD STANDARD
T&B TOP AND BOTTOM
T/REFERENCE TOP OF REFERENCE
TYP TYPICAL
UNO UNLESS NOTED OTHERWISE
VERT VERTICAL
W/ WITH
W/O WITHOUT
WWF WELDED WIRE FABRIC
S E
LE
C
T
S
R
U C
T U
R A
L
S E
L E
C T
S T
R U
C T
U R
A L
N e w
B ri tt a n y B lv d
F o rt
M y e rs
F lo ri d a
P h o n e (2
-5 in fo s e le c ts tr u c tu ra l.
c o m
C e rt if ic a ti o n
A u th
JOB NO.:
SCALE: AS INDICATED
ENGINEERED BY:
DRAWN BY:
ISSUED DATE:
SEAL
SHEET TITLE:
SHEET NO.:
REVISIONS
02/26/2024
GENERAL
NOTES
S1.0
C O
L L
IE
R C
O U
N T
Y C
A X
A M
B A
S M
A R
IN
A
F U
E L S
Y S
T E
M R
E P
L A
C M
E N
T
C o lli e r
C t.
M a rc o I sl a n d F
L
SRA
JLS
24160
GENERAL STRUCTURAL NOTES
GENERAL: DETAILS AND SECTIONS SHOWN ON THE DRAWINGS ARE TYPICAL AND APPLY TO SIMILAR SITUATIONS ELSEWHERE, EXCEPT AS OTHERWISE INDICATED. ADAPT REQUIREMENTS OF DETAILS, SECTIONS, PLANS, AND NOTES AT LOCATIONS WHERE CONDITIONS ARE SIMILAR.
CENTER ALL FOOTINGS AND PIERS UNDER COLUMNS ABOVE UNLESS SPECIFICALLY DIMENSIONED OTHERWISE.
STRUCTURAL DRAWINGS SHALL BE USED IN CONJUNCTION WITH JOB SPECIFICATIONS AND ARCHITECTURAL, MECHANICAL, ELECTRICAL, PLUMBING, AND SITE DRAWINGS. CONSULT THESE DRAWINGS FOR SLEEVES, DEPRESSIONS, AND OTHER DETAILS NOT SHOWN ON STRUCTURAL
DRAWINGS.
CONTRACTOR SHALL LOCATE ALL BURIED UTILITIES PRIOR TO EXCAVATION FOR BUILDING FOUNDATIONS. THE STRUCTURAL ENGINEER SHALL
BE NOTIFIED OF POTENTIAL CONFLICTS BETWEEN FOUNDATIONS AND BURIED UTILITIES.
CODE REQUIREMENTS: THE BUILDING STRUCTURE IS DESIGNED IN ACCORDANCE WITH THE 2023 8th EDITION OF THE FLORIDA BUILDING CODE.
FOLLOW ALL APPLICABLE PROVISIONS FOR ALL PHASES OF CONSTRUCTION. ADDITIONS ARE IN COMPLIANCE WITH THE 2023 EDITION OF THE
FLORIDA EXISTING BUILDING CODE.
TEMPORARY CONDITIONS: THE STRUCTURAL INTEGRITY OF THE COMPLETED STRUCTURE DEPENDS ON INTERACTION OF VARIOUS CONNECTED COMPONENTS. PROVIDE ADEQUATE BRACING, SHORING, AND OTHER TEMPORARY SUPPORTS AS REQUIRED TO SAFELY COMPLETE THE WORK.
THE STRUCTURE SHOWN ON THE DRAWINGS HAS BEEN DESIGNED FOR STABILITY UNDER FINAL CONFIGURATION ONLY.
RETAINING WALLS WHICH TIE TO UPPER SLABS SHALL NOT BE BACKFILLED UNTIL THE UPPER SLABS REACH FULL STRENGTH, UNLESS
ADEQUATE BRACING IS PROVIDED AT THE TOP OF THE WALL.
EXISTING CONDITIONS: ALL EXISTING CONDITIONS, DIMENSIONS AND ELEVATIONS SHALL BE FIELD VERIFIED. THE CONTRACTOR SHALL NOTIFY THE ENGINEER OF ANY SIGNIFICANT DISCREPANCIES FROM CONDITIONS SHOWN ON THE DRAWINGS.
DESIGN CRITERIA: DESIGN WAS BASED ON STRENGTH AND DEFLECTION CRITERIA OF THE 2023 FLORIDA BUILDING CODE. THE FOLLOWING
LOADS WERE USED FOR DESIGN, WITH LIVE LOADS REDUCED PER THE 2023 FBC.
WIND SPEED (ASCE 7-22) 170 MPH (132 MPH ALLOWABLE)
RISK CATEGORY II
EXPOSURE D
INTERNAL PRESSURE COEFF 0.0 OPEN BUILDING
FLOOD DESIGN: THE STRUCTURAL ELEMENTS BELOW FLOOD ELEVATION SHALL BE FLOOD DAMAGE-RESISTANT MATERIALS PER ASCE 24-14.
THE STRUCTURE IS LOCATED IN A V-ZONE, ALL WALLS AT GROUND LEVEL, NOT DESIGNATED AS SHEARWALLS, ARE BREAKAWAY WALLS AND SHALL HAVE FLOOD OPENINGS. THE GROUND FLOOR IS TO BE DRY FLOOD-PROOFED. THE STRUCTURAL COMPONENTS HAVE BEEN DESIGNED TO RESIST HYDROSTATIC AND HYDRODYNAMIC LOADS AND EFFECTS OF BOUYANCY IN ACCORDANCE WITH FEMA GUIDELINES AND ASCE 24-14.
PILE FOUNDATIONS: FOUNDATION DESIGN IS BASED ON THE GEOTECHNICAL RECOMMENDATIONS IN THE REPORT PREPARED BY: Wood E&I Solutions PROJECT NUMBER: 6788-18-3064.00010.01 DATED: July 16, 2018 FOR PRE-STRESSED SQUARE PILES. CONTRACTOR SHALL FOLLOW THE RECOMMENDATIONS SPECIFIED IN THE GEOTECHNICAL REPORT INCLUDING, BUT NOT LIMITED TO, SITE PREPARATION AND PILE INSTALLATION.
THE GEOTECHNICAL ENGINEER SHALL BE RETAINED FOR FOUNDATION INSTALLATION MONITORING.
PRECAST CONCRETE PILES: CONCRETE PILES SHALL BE 14”X14”. ALL PILING SHALL BE DRIVEN OR JETTED AND DRIVEN TO A SAFE BEARING CAPACITY OF 35 TONS AND UPLIFT CAPACITY OF 10 TONS USING AN APPROPRIATE DRIVING. PILES TO BE CUT OFF SQUARE AT PROPER ELEVATIONS. AN INDEPENDENT GEOTECHNICAL CONSULTANT SHALL BE RETAINED TO MONITOR PILE INSTALLATION AND VERIFY LOAD CAPACITY.
PILE SURVEY: AN AS-BUILT SURVEY OF PILE LOCATIONS SHALL BE PERFORMED BY A PROFESSIONAL REGISTERED LAND SURVEYOR. PILES SHALL BE LOCATED ON THE AS-BUILT DRAWINGS HORIZONTALLY AND VERTICALLY FROM THE THEORETICAL PILE LOCATION. SUBMIT THE
AS-BUILT DRAWINGS TO THE STRUCTURAL ENGINEER FOR APPROVAL.
SUBMITTALS: SHOP DRAWINGS SHALL BE SUBMITTED TO THE ARCHITECT PRIOR TO FABRICATION AND CONSTRUCTION REGARDING ALL
STRUCTURAL ITEMS INCLUDING THE FOLLOWING:
CONCRETE MIX DESIGNS,
CONCRETE REINFORCING.
SHOP DRAWINGS SHALL BE REVIEWED BY THE CONTRACTOR PRIOR TO SUBMITTAL TO THE ARCHITECT/ENGINEER. DRAWINGS SUBMITTED
WITHOUT REVIEW WILL BE RETURNED UNCHECKED.
IF THE SHOP DRAWINGS DIFFER FROM OR ADD TO THE DESIGN OF THE STRUCTURAL DRAWINGS, THEY SHALL BEAR THE SEAL AND SIGNATURE OF A STRUCTURAL ENGINEER REGISTERED IN THE STATE OF THE PROJECT LOCATION. ANY CHANGES TO THE STRUCTURAL DRAWINGS SHALL BE SUBMITTED TO THE ARCHITECT AND ARE SUBJECT TO THE REVIEW AND ACCEPTANCE OF THE ENGINEER.
DESIGN DRAWINGS, SHOP DRAWINGS, AND CALCULATIONS FOR THE DESIGN AND FABRICATION OF ITEMS THAT ARE DESIGNED BY OTHERS, INCLUDING:
PRECAST CONCRETE MEMBERS
SHALL BEAR THE SEAL AND SIGNATURE OF A STRUCTURAL ENGINEER REGISTERED IN THE STATE OF THE PROJECT LOCATION AND SHALL BE SUBMITTED TO THE ARCHITECT PRIOR TO FABRICATION. CALCULATIONS SHALL BE INCLUDED FOR ALL CONNECTIONS TO THE STRUCTURE, CONSIDERING LOCALIZED EFFECTS ON THE STRUCTURAL ELEMENTS INDUCED BY THE CONNECTION LOADS. DESIGN SHALL BE BASED ON THE
REQUIREMENTS OF THE 2023 FBC.
SHOP DRAWINGS WILL BE REVIEWED FOR GENERAL COMPLIANCE WITH THE DESIGN INTENT OF THE CONTRACT DOCUMENTS ONLY. IT SHALL BE THE RESPONSIBILITY OF THE CONTRACTOR TO VERIFY COMPLIANCE WITH THE CONTRACT DOCUMENTS AS TO QUANTITY, LENGTH, ELEVATIONS, DIMENSIONS, ETC. CONTRACTOR SHALL NOT BE RELIEVED FROM RESPONSIBILITY FOR ERRORS OR OMISSIONS IN SHOP DRAWINGS OR MIX
DESIGNS BY THE ENGINEER’S REVIEW.
DEFERRED SUBMITTALS: IN ACCORDANCE WITH FBC 107.3.4.1, THE FOLLOWING SPECIALITY ITEMS FOR PORTIONS OF THE BUILDING WILL NOT BE SUBMITTED AT THE TIME OF BUILDING PERMIT APPLICATION BUT WILL BE DEFERRED UNTIL AFTER THE PERMIT HAS BEEN ISSUED.
PRECAST CONCRETE MEMBERS
THESE ELEMENTS ARE PERFORMANCE-BASED DESIGN. THE CONTRACTOR SHALL CONTRACT FOR THE DESIGN AND CONSTRUCTION OF THESE ELEMENTS DURING THE CONSTRUCTION PHASE. THE SHOP DRAWINGS AND CALCULATIONS SHALL BE PREPARED AND SIGNED BY A STRUCTURAL ENGINEER REGISTERED IN THE STATE OF THE PROJECT LOCATION. THEY SHALL BE SUBMITTED FOR REVIEW AND APPROVAL
PRIOR TO FABRICATION.
THE DEFERRED SUBMITTAL ITEMS SHALL NOT BE INSTALLED UNTIL THE DEFERRED SUBMITTAL DOCUMENTS HAVE BEEN APPROVED BY THE
BUILDING OFFICIAL.
CONCRETE: REINFORCED CONCRETE CONSTRUCTION SHALL CONFORM TO THE FBC AND ACI 318 "BUILDING CODE REQUIREMENTS FOR REINFORCED CONCRETE". CONCRETE STRENGTHS SHALL BE VERIFIED BY STANDARD 28-DAY CYLINDER TESTS PER ASTM C39, AND SHALL BE AS
FOLLOWS:
f’c USE
4000 PSI ALL USES, U.N.O.
CEMENT SHALL CONFORM TO ASTM C150, TYPE 1. FLY ASH CONFORMING TO ASTM C618, TYPE F OR TYPE C, MAY BE USED TO REPLACE UP TO 20% OF THE CEMENT CONTENT, PROVIDED THAT THE MIX STRENGTH IS SUBSTANTIATED BY TEST DATA. COARSE AGGREGATE SHALL CONFORM TO ASTM C33 WITH A MAXIMUM SIZE OF 3/4". FINE AGGREGATE SHALL BE CLEAN, DURABLE, NATURAL SAND CONFORMING TO ASTM C33.
A WATER-REDUCING ADMIXTURE, IF USED, SHALL CONFORM TO ASTM C494 AND USED IN STRICT ACCORDANCE WITH THE MANUFACTURER’S RECOMMENDATIONS, SHALL BE INCORPORATED IN CONCRETE DESIGN MIXES. A HIGH-RANGE WATER-REDUCING ADMIXTURE CONFORMING TO ASTM C494, TYPE F OR G, MAY BE USED IN CONCRETE MIXES, PROVIDING THAT THE SLUMP DOES NOT EXCEED 8”.
SLEEVES, OPENINGS, CONDUIT, AND OTHER EMBEDDED ITEMS NOT SHOWN ON THE STRUCTURAL DRAWINGS SHALL BE APPROVED BY THE STRUCTURAL ENGINEER BEFORE POURING. NO SLEEVE, OPENING, OR INSERT MAY BE PLACED IN BEAMS, JOISTS, OR COLUMNS UNLESS APPROVED BY THE ENGINEER. CONDUITS EMBEDDED IN SLABS SHALL NOT BE LARGER IN OUTSIDE DIMENSION THAN ONE THIRD OF THE THICKNESS OF THE SLAB AND SHALL NOT BE SPACED CLOSER THAN THREE DIAMETERS ON CENTER.
PROVIDE 3/4” CHAMFERS ON ALL EXPOSED CONCRETE EDGES, UNLESS NOTED OTHERWISE. WHERE INDICATED OR REQUIRED, SLOPE
CONCRETE SLABS TO DRAINS SHOWN ON PLUMBING AND/OR ARCHITECTURAL DRAWINGS.
ALL CONCRETE SHALL BE CURED IMMEDIATELY AFTER FINISHING OPERATIONS.
REINFORCING STEEL: REINFORCING STEEL SHALL CONFORM TO ASTM A615, GRADE 60, FOR DEFORMED BAR AND ASTM A1064 FOR SMOOTH WELDED WIRE FABRIC (WWF), UNLESS OTHERWISE NOTED. REINFORCING STEEL TO BE WELDED SHALL CONFORM TO ASTM A706.
REINFORCING STEEL SHALL BE SECURELY TIED IN PLACE WITH #16 ANNEALED IRON WIRE.
ALL DETAILING AND ACCESSORIES SHALL CONFORM TO ACI DETAILING MANUAL SP-66. PROVIDE CHAIRS, SPACERS, BOLSTERS, AND ITEMS IN CONTACT WITH FORMS WITH HOT-DIP GALVANIZED LEGS OR PLASTIC LEGS. ACCURATELY POSITION, SUPPORT, AND SECURE REINFORCEMENT AGAINST DISPLACEMENT BY FORMWORK CONSTRUCTION OR CONCRETE PLACEMENT OPERATIONS. "WET-STICKING" OF REINFORCING IS
PROHIBITED.
REQUIRED CONCRETE COVER FOR REINFORCING STEEL (UNLESS NOTED OTHERWISE):
SLABS 4" BOTTOM, 1 1/2" TOP AND SIDES
LAP SPLICE CONTINUOUS VERTICAL OR HORIZONTAL BARS IN CONCRETE MEMBERS IN ACCORDANCE WITH ACI 318-19, FOR CLASS "B" TENSION LAP SPLICES. DO NOT SPLICE CONTINUOUS TOP BARS IN BEAMS AT ENDS OF CLEAR SPANS. DO NOT SPLICE CONTINUOUS BOTTOM BARS IN BEAMS IN CLEAR SPANS BETWEEN SUPPORTS. SHOW ALL SPLICES ON SHOP DRAWINGS. SPLICE LOCATIONS AND METHODS SUBJECT TO
APPROVAL OF STRUCTURAL ENGINEER.
AT SLAB RE-ENTRANT CORNERS, PROVIDE (2) #5 X 4’-0” DIAGONAL BARS. AT SLAB AND WALL OPENINGS PROVIDE A MINIMUM OF (2) #5 BARS ALL FOUR SIDES AND DIAGONALLY; EXTEND THESE BARS A LAP DISTANCE OR A MINIMUM OF 24” PAST THE OPENING OR HOOK BARS IF
DISCONTINUOUS.
DOWEL ALL WALLS AND COLUMNS TO FOOTINGS WITH BAR SIZE AND SPACING TO MATCH VERTICAL REINFORCING UNLESS OTHERWISE SHOWN.
WHERE NEW CONCRETE IS PLACED AGAINST EXISTING CONCRETE, THE EXISTING CONCRETE SURFACE SHOULD BE CLEANED AND ROUGHENED
TO A MINIMUM 1/4” AMPLITUDE.
CONCRETE ACCESSORIES:
PERMANENTLY EXPOSED STEEL CONNECTIONS SHALL BE HOT-DIPPED GALVANIZED AFTER FABRICATION.
ADHESIVE ANCHORS: ADHESIVE ANCHORS (EPOXY STYLE) SHALL HAVE THE ICC ES EVALUATION REPORT INDICATING CONFORMANCE WITH
CURRENT APPLICABLE ICC ES ACCEPTANCE CRITERIA.
INSTALLATION SHALL BE IN CONFORMANCE WITH MANUFACTURER'S PRINTED INSTALLATION INSTRUCTIONS. EMBEDMENT SHALL BE AS
INDICATED ON THE STRUCTURAL DRAWINGS.
IDENTIFY POSITION OF REINFORCING STEEL AND OTHER EMBEDDED ITEMS PRIOR TO DRILLING HOLES FOR ANCHORS. EXERCISE CARE IN CORING OR DRILLING TO AVOID DAMAGING EXISTING REINFORCING OR EMBEDDED ITEMS. NOTIFY THE ENGINEER IF REINFORCING STEEL OR
OTHER EMBEDDED ITEMS ARE ENCOUNTERED DURING DRILLING.
NO. DATE DESCRIPTION
07/16/2024
16/07/2024
THIS ITEM HAS BEEN ELECTRONICALLY SIGNED AND
SEALED USING A DIGITAL SIGNATURE.
PRINTED COPIES OF THIS DOCUMENT ARE NOT
CONSIDERED SIGNED AND SEALED AND THE
SIGNATURE MUST BE VERIFIED ON ANY ELECTRONIC
COPIES.
S2.0
31' - 9"
CONCRETE
SLAB_20" W/ #5
@ 10" OC EW
T&B
3' - 0" 8' - 1" 9' - 7" 9' - 7" 1' - 6"
THICKNESS = 1'-8"
BOLLARD BY OTHERS, TYP.
T/SLAB
1'-8"
FINISH GRADE
0'-0"
DRILL AND EPOXY (4) #6 HOOKED BARS
W/ HILTI HIT-RE 500 V3 EPOXY. 12" EMBED MIN.
PROVIDE 4" CLR DISTANCE FROM EDGE OF
PILE TO CENTER OF REBAR.
CONCRETE SLAB PER PLAN
24"
12"
FOUNDATION PLAN NOTES:
1. REFER TO ARCHITECTURAL DRAWINGS FOR VAPOR BARRIER REQUIREMENTS, SLOPES, STEPS, AND DRAIN LOCATIONS IN FLOOR SLABS.
2. REFER TO GEOTECHNICAL RECOMMENDATIONS FOR SUBGRADE COMPACTION AND DRAINAGE REQUIREMENTS.
3. DO NOT SCALE DRAWINGS. VERIFY/COORDINATE ALL DIMENSIONS AND ELEVATIONS WITH ARCHITECTURAL DRAWINGS BEFORE COMMENCING CONSTRUCTION. NOTIFY THE STRUCTURAL ENGINEER AND ARCHITECT OF RECORD OF ANY DISCREPANCIES BEFORE PROCEEDING WITH CONSTRUCTION.
4. CONTRACTOR TO VERIFY ALL EXISTING CONDITIONS, DIMENSIONS AND ELEVATIONS PRIOR TO COMMENCING CONSTRUCTION. NOTIFY THE ENGINEER OF
RECORD OF ANY DISCREPANCIES.
5. VERIFY/COORDINATE THE LOCATION OF ALL UNDERGROUND PIPING WITH THE FOUNDATION.
6. FOUNDATION DESIGN IS PRELIMINARY BASED ON PROVIDED TANK DIMENSIONS. DESIGN IS SUBJECT TO CHANGE PENDING FINAL TANK DIMENSIONS.
(2) #5 CONT
SLAB ON GRADE
PER PLAN
FINISH GRADE
8"
S2.0
4'
6"
13' - 6"
COORDINATE DIMENSIONS OF
OPENING IN PAD WITH DISPENSER
SUMP OPENING DIMENSIONS
5" CONCRETE
SLAB ON GRADE
W/ 6X6
W2.1XW2.1 WWF
S E
LE
C
S
R
U C
T U
R A
L
S E
L E
C T
S T
R U
C T
U R
A L
N e w
B ri tt a n y B lv d
F o rt
M y e rs
F lo ri d a
P h o n e (2
-5 in fo s e le c ts tr u c tu ra l.
c o m
C e rt if ic a ti o n
A u th
JOB NO.:
SCALE: AS INDICATED
ENGINEERED BY:
DRAWN BY:
ISSUED DATE:
SEAL
SHEET TITLE:
SHEET NO.:
REVISIONS
02/26/2024
FOUNDATION
PLAN
S2.0
C O
L L
IE
R C
O U
N T
Y C
A X
A M
B A
S M
A R
IN
A
F U
E L S
Y S
T E
M R
E P
L A
C M
E N
T
C o lli e r
C t.
M a rc o I sl a n d F
L
SRA
JLS
24160
SCALE: 3/8" = 1'-0"
FUEL TANK SLAB/PILE CAP
SCALE: 3/8" = 1'-0"
SLAB SECTION
FUEL TANK AND SADDLE
CONNECTIONS TO SLAB PER MANUFACTURER
SCALE: 3/4" = 1'-0"
THICKENED SLAB EDGE
NOTE: FOUNDATION DESIGN IS FOR TANK WITH THE FOLLOWING LOAD CONDITIONS
MAXIMUM WEIGHT OF FULL TANK = 100 kips NET BUOYANCY FORCE OF EMPTY TANK = 82 kips.
NO. DATE DESCRIPTION
A1 07.16.2024 ADDENDUM #1
SCALE: 3/8" = 1'-0"
FUEL DISPENSER SLAB
A1
07/16/2024
| Sheets |
| S1.0 - GENERAL NOTES |
| S2.0 - FOUNDATION PLAN |
| 2024-07-16T16:19:43-0400 | |
| Esra Persellin |
File details come from the government source that posted it. Updated .