24-8284_-_Exhibit_M_-_CAXAMBAS_ELECTRICAL_Rev._1.pdf

PDF 698 KB Posted

Attached to
Caxambas Hurricane Ian Permanent Fuel Tank Installation
Solicitation number
24-8284
Issued by
Collier County, Miami City, Florida

About this file

This document is an electrical design specification set for the Caxambas Marina Fuel System Replacement project in Collier County, Florida, prepared by Jenkins Maag Associates, LLC. The electrical plans and specifications cover a comprehensive electrical replacement and upgrade for the marina's fuel system, including detailed electrical symbols, riser diagrams, wire and conduit schedules, and specific installation requirements. The document provides technical guidance for electrical contractors, outlining specific requirements for conduit installation, wiring devices, disconnects, grounding, and compliance with various electrical codes including the 2020 National Electrical Code, 2023 Florida Building Code, and NFPA standards.

The specifications include precise technical requirements for electrical components, such as using copper wire, specific conduit types (rigid galvanized steel, PVC schedule 40), GFCI receptacles, and emergency shutoff devices. The project involves replacing existing electrical systems for fuel dispensers, storage tanks, and associated equipment, with careful attention to safety protocols for fuel-related electrical installations. The electrical design incorporates specific requirements for classified locations, underground conduit installations, and compliance with hazardous area electrical standards, particularly those related to fuel handling and dispensing environments. The design ensures electrical safety and functionality for the marina's fuel system infrastructure, with detailed provisions for emergency power disconnection, equipment labeling, and proper electrical system integration.

View the file

Other files

Show all 14

On GovTribe

Work with this file

  • Download the original file
  • Contacts named in this file
  • Similar government files
  • Ask GovTribe AI about this file

Text version

C O

LL

IE

R C

O U

N T

Y C

A X A

M B A

S M

A R

IN

A

F U

EL

SY

ST

EM

R

EP

LA

C

EM

EN

T

C o ll ie r C t.

M ar co

I sl an d

FL

C O

RK

SC

RE

W

R D

SU

IT

E

ES

T

ER

O

FL

Fl o ri d a

C o A

Je ff re y

A Je n k in s, F

L

PE

P:

-2

-5

F:

-2

-5

JM

A

JE

N

K

IN

S M

A A

G A

SS

O C

IA

T

ES

LL

C

SYMBOL LEGEND,

ABBREVIATIONS AND

NOTES

E-1

ELECTRICAL SYMBOL LEGEND

SYMBOL DESCRIPTION

DUPLEX RECEPTACLE - 125V

PANEL AND CIRCUIT NUMBER INDICATED

WL = WET LOCATION COVER

FB-15

GFCI DUPLEX RECEPTACLE - 125V

TRANSFORMER - SINGLE PHASE

ELECTRICAL SHEET INDEX

SHEET ID SHEET TITLE SHEET SCALE

E-1 SYMBOL LEGEND, ABBREVIATIONS AND NOTES NO SCALE

E-2 SPECIFICATIONS NO SCALE

E-3 ELECTRICAL PLANS 1/8" = 1'-0"

E-4 RISER AND SCHEDULES NO SCALE

GENERAL ELECTRICAL NOTES

A. THE ELECTRICAL CONTRACTOR SHALL VERIFY THE EXACT

LOCATION OF FUEL STORAGE AND DISPENSING EQUIPMENT WITH

THE INSTALLING CONTRACTORS, AND MAKE FINAL CONNECTIONS

TO THE EQUIPMENT. EXACT ELECTRICAL REQUIREMENTS SHALL

BE VERIFIED IN THE FIELD WITH THE EQUIPMENT NAMEPLATE

DATA. THE ELECTRICAL CONTRACTOR SHALL MAKE

APPROPRIATE ADJUSTMENTS TO WIRE AND OVERCURRENT

PROTECTION DEVICE SIZES IN ACCORDANCE WITH THE

NAMEPLATE DATA.

B. ELECTRICAL EQUIPMENT ENCLOSURES, SUCH AS FOR

DISCONNECTS LOCATED OUTDOORS SHALL HAVE NEMA-4X RATED

ENCLOSURES, UON.

C. PROVIDE NAMEPLATES ON THE EXTERIOR OF ALL ELECTRICAL

EQUIPMENT, INCLUDING EXISTING PANELBOARDS LOCATED

WITHIN THE BUILDING AND NEW DISCONNECTS.

D. ARC FLASH WARNING LABELS SHALL BE PROVIDED FOR

ELECTRICAL EQUIPMENT, SUCH AS EXISTING PANELBOARDS

LOCATED WITHING THE BUILDING AND CONTROL PANELS, AS

REQUIRED BY NEC 110.16. THE WARNING LABELS SHALL BE

MINIMUM 2" X 3", PRE PRINTED TYPE BY A LABEL MANUFACTURER,

SUITABLE FOR THE ENVIRONMENT WHERE INSTALLED AND

MEETING NEC 110.21(B), NFPA AND OSHA REQUIREMENTS.

E. PROVIDE PROTECTION AGAINST DISSIMILAR METALS. ALL WIRING

TERMINATIONS SHALL BE MADE USING COMPONENTS LISTED FOR

THE APPLICATION AND MATERIALS USED.

F. ALL 120V, 15 AND 20 AMP BRANCH CIRCUITS SERVING OUTLETS

LOCATED BELOW THE FLOOD ELEVATION, AND ALL 120V, 15 AND

20 AMP BRANCH CIRCUITS WITH WIRING LOCATED BELOW THE

FLOOD ELEVATION SHALL BE PROTECTED BY GFCI CIRCUIT

BREAKERS.

G. SPARE CIRCUIT BREAKERS IN PANELBOARDS SHALL BE

IDENTIFIED AS SPARE ON THE PANEL DIRECTORY AND LEFT IN

THE OFF (OPEN) POSITION.

H. PROVIDE COMPLETE, UPDATED, TYPED CIRCUIT DIRECTORIES,

INCLUDING THE DATE THE DIRECTORIES WERE COMPLETED, FOR

EXISTING PANELBOARDS WITH NEW OR REVISED CIRCUITS. ALL

NEW CIRCUIT BREAKERS PROVIDED TO BE INSTALLED IN ANY

EXISTING PANEL SHALL MATCH THE EXISTING EQUIPMENT

MANUFACTURER, BE LISTED FOR USE IN THE EXISTING

EQUIPMENT AND HAVE A SHORT CIRCUIT RATING TO MEET OR

EXCEED THE RATING OF THE EXISTING EQUIPMENT.

APPLICABLE CODES AND STANDARDS:

ALL ELECTRICAL WORK SHALL BE GOVERNED AND INSTALLED IN

COMPLIANCE WITH THE APPLICABLE PROVISIONS OF THE FOLLOWING

CODES AND STANDARDS:

- FLORIDA BUILDING CODE - 2023 8TH EDITION

- FLORIDA FIRE PREVENTION CODE - 8TH EDITION (2023)

- NFPA 30: FLAMMABLE AND COMBUSTIBLE LIQUIDS CODE - 2021

EDITION

- NFPA 30A: CODE FOR MOTOR FUEL DISPENSING FACILITIES AND

REPAIR GARAGES - 2021 EDITION

- NFPA-70: NATIONAL ELECTRICAL CODE - 2020 EDITION

CODES AND STANDARDS

ABBREVIATIONS

3W THREE WIRE

A AMPERE

AC ALTERNATING CURRENT

ADA AMERICANS WITH DISABILITIES ACT

AFF ABOVE FINISHED FLOOR (HEIGHT TO CENTER)

AFG ABOVE FINISHED GRADE

AHJ AUTHORITY HAVING JURISDICTION

AHU AIR HANDLING UNIT

AIC AMPERE INTERRUPTING CAPACITY

AL ALUMINUM

ANSI AMERICAN NATIONAL STANDARDS INSTITUTE

AWG AMERICAN WIRE GAUGE

C CELSIUS

CB CIRCUIT BREAKER

CCTV CLOSED CIRCUIT TELEVISION

CKT CIRCUIT

CLG CEILING

CT CURRENT TRANSFORMER

CU COPPER

DC DIRECT CURRENT

DEMO DEMOLITION

DL DAMP LOCATION

EA EACH

EC ELECTRICAL CONTRACTOR

EF EXHAUST FAN

EH ELECTRIC HEATER

EM EMERGENCY

EMT ELECTRICAL METALLIC TUBING

EPO EMERGENCY POWER OFF

ETR EXISTING TO REMAIN

EWC ELECTRIC WATER COOLER

EWH ELECTRIC WATER HEATER

F FAHRENHEIT

FLA FULL LOAD AMPS

G GROUND

GC GENERAL CONTRACTOR

GFCI GROUND FAULT CIRCUIT INTERRUPTER (PERSONNEL)

GF-E GROUND FAULT CIRCUIT INTERRUPTER (EQUIPMENT)

GFP GROUND FAULT PROTECTION

HP HORSEPOWER

HVAC HEATING, VENTILATING, AND AIR CONDITIONING

J-BOX JUNCTION BOX

K KELVIN

KCMIL KILO-CIRCULAR MILS

KVA KILOVOLT AMPERES

KW KILOWATTS

KWC KILOWATTS CONNECTED

KWD KILOWATTS DEMAND

L-OFF CIRCUIT BREAKER LOCK IN OPEN POSITION

L-ON CIRCUIT BREAKER LOCK IN CLOSED POSITION

LTG LIGHTING

MC MECHANICAL CONTRACTOR

MCB MAIN CIRCUIT BREAKER

MLO MAIN LUGS ONLY

MOD MOTOR OPERATED DAMPER

MTS MANUAL TRANSFER SWITCH

NEC NATIONAL ELECTRICAL CODE

NEMA NATIONAL ELECTRICAL MANUFACTURERS ASSOCIATION

NFPA NATIONAL FIRE PROTECTION ASSOCIATION

NIC NOT IN CONTRACT

NTS NOT TO SCALE

P POLE

PA PUBLIC ADDRESS

PH PHASE

PT POTENTIAL TRANSFORMER

QTY QUANTITY

REC RECEPTACLE

RMC RIGID METALLIC CONDUIT

RNC RIGID NON-METALLIC CONDUIT

RP RELAY PANEL

RR REMOVE AND RELOCATE

SCA SHORT CIRCUIT CURRENT AVAILABLE

SPD SURGE PROTECTION DEVICE

ST SHUNT TRIP

TTB TELEPHONE TERMINAL BOARD

TV TELEVISION

TYP TYPICAL

UL UNDERWRITERS LABORATORIES

UON UNLESS OTHERWISE NOTED

UPS UNINTERRUPTIBLE POWER SUPPLY

V VOLT

VA VOLT AMPERE

VAR VOLT AMPERE REACTIVE

W WATT

WAP WIRELESS ACCESS POINT

WL WET LOCATION

WP WEATHERPROOF

GENERAL DEMOLITION NOTES

A. ALL EXISTING DEVICES AND EQUIPMENT SHOWN ARE THE RESULT

OF FIELD INSPECTIONS AND ARE NOT INTENDED TO REPRESENT

EXACT FIELD CONDITIONS, BUT ARE INTENDED TO REPRESENT

THE EXTENT OF ELECTRICAL DEMOLITION. THE ELECTRICAL

CONTRACTOR SHALL FIELD VERIFY THE EXTENT OF DEMOLITION

PRIOR TO COMMENCEMENT OF WORK.

B. EXISTING CONDUIT AND WIRING TO REMAIN SHALL BE PROTECTED

DURING DEMOLITION. RELOCATE AND REROUTE WHERE

REQUIRED TO ALLOW FOR DEMOLITION.

C. MAINTAIN CONTINUITY OF BRANCH CIRCUITS TO ALL DEVICES AND

FIXTURES SHOWN TO REMAIN (ETR).

D. FOR ALL EQUIPMENT TO BE REMOVED (DEMO), REMOVE RELATED

WIRING COMPLETE TO SOURCE. RE-LABEL EXISTING CIRCUIT

BREAKERS AS "SPARE" WHEN LOAD IS COMPLETELY REMOVED OR

REVISE LABEL ON PANEL DIRECTORY ACCORDINGLY.

HOMERUN TO PANEL 'A', CIRCUIT NUMBER 1

A-1

THE SCOPE OF WORK INCLUDED WITHIN THE ELECTRICAL DRAWINGS

IS TO PROVIDE POWER FOR THE NEW FUEL SYSTEM EQUIPMENT

FROM THE EXISTING ELECTRICAL PANEL, INCLUDING PROVIDING NEW

CIRCUIT BREAKERS WITHIN THE EXISTING PANEL, AS WELL AS NEW

DISCONNECTS, CONDUIT AND WIRING REQUIRED FOR A COMPLETE

INSTALLATION.

SCOPE OF WORK

JUNCTION BOXJ

JUNCTION BOX - WALLJ

EMERGENCY POWER OFF PUSHBUTTON

E

CIRCUIT BREAKER DISCONNECT

MOTOR

PANELBOARD

METER

RISER SYMBOLS

GROUND

PANELBOARD - MAIN LUGS ONLY OR MAIN CIRCUIT

BREAKER

CIRCUIT BREAKER DISCONNECT

SIZE AS INDICATED

60A

METER

CT = CT TYPE METERM

SERVICE TRANSFORMER

CIRCUIT BREAKER

SIZE AS INDICATED

60A

DATA OUTLET - WALL

AutoCAD SHX Text

REVISION

AutoCAD SHX Text

DATE

AutoCAD SHX Text

NO.

AutoCAD SHX Text

ISSUE:

AutoCAD SHX Text

ISSUE DATE:

AutoCAD SHX Text

DRAWN BY:

AutoCAD SHX Text

CHECKED BY:

AutoCAD SHX Text

PROJECT NUMBER:

AutoCAD SHX Text

PERMIT SET

AutoCAD SHX Text 05.06.2024

AutoCAD SHX Text

CCO23002

AutoCAD SHX Text

PERMIT SET

AutoCAD SHX Text 05.06.2024

AutoCAD SHX Text

RMR

AutoCAD SHX Text

JAJ

LL

IE

R C

O U

N T

Y C

A X A

M B A

S M

A R

IN

A

F U

EL

SY

ST

EM

R

EP

LA

C

EM

EN

T

C o ll ie r C t.

M ar co

I sl an d

FL

C O

RK

SC

RE

W

R D

SU

IT

E

ES

T

ER

O

FL

Fl o ri d a

C o A

Je ff re y

A Je n k in s, F

L

PE

P:

-2

-5

F:

-2

-5

JM

A

JE

N

K

IN

S M

A A

G A

SS

O C

IA

T

ES

LL

C

SPECIFICATIONS

E-2

GENERAL PROVISIONS

1. PROVISIONS OF THIS SPECIFICATION APPLY TO ALL WORK OF THE

ELECTRICAL CONTRACTOR. GENERAL CONDITIONS,

SUPPLEMENTARY CONDITIONS, AND GENERAL REQUIREMENTS OF

THE ARCHITECTURAL SPECIFICATIONS APPLY TO ALL WORK OF

THE ELECTRICAL CONTRACTOR. FUEL SYSTEM EQUIPMENT,

ELECTRICAL, AND ALL OTHER DRAWINGS AS WELL AS THE

SPECIFICATIONS FOR ALL OTHER DIVISIONS SHALL BE DEFINED

AS THE CONTRACT DOCUMENTS. CONTRACTOR SHALL REVIEW

ENTIRE SET OF CONTRACT DOCUMENTS PRIOR TO BIDDING FOR

ADDITIONAL PROJECT REQUIREMENTS WHICH MAY AFFECT WORK

UNDER THIS DIVISION.

2. VISIT THE SITE NO LATER THAN TWO (2) WEEKS PRIOR TO BIDDING

FOR FAMILIARIZATION WITH LOCAL CONDITIONS. IMMEDIATELY

NOTIFY THE ARCHITECT/ENGINEER OF ANY DEVIATIONS BETWEEN

BID DOCUMENTS AND LOCAL CONDITIONS. FAILURE TO NOTIFY

ASSUMES THAT ANY COST FOR CORRECTING TO LOCAL

CONDITIONS IS INCLUDED IN THE BID.

3. DEFINITIONS AS APPLIED TO THIS SPECIFICATION ARE AS

FOLLOWS:

3.1. "FURNISH" SHALL MEAN TO SUPPLY AND DELIVER TO THE

PROJECT SITE, READY FOR UNLOADING, UNPACKING,

ASSEMBLY, INSTALLATION AND SIMILAR OPERATIONS.

3.2. "INSTALL" SHALL MEAN WORK WHICH INCLUDES THE ACTUAL

UNLOADING, UNPACKING, ASSEMBLY, ERECTING, PLACING,

ANCHORING, APPLYING, FINISHING, CURING, PROTECTING,

CLEANING AND SIMILAR OPERATIONS.

3.3. "PROVIDE SHALL MEAN TO FURNISH AND INSTALL, COMPLETE

AND READY FOR THE INTENDED USE.

3.4. "EQUAL" SHALL MEAN TO MEET OR EXCEED THE STANDARDS

OF THE SPECIFIED PRODUCT OR LISTED MANUFACTURER.

3.5. "TYPICAL" IS NOTED WHERE WORK APPLIES TO A PATTERN

OR TYPE OF EQUIPMENT OR MATERIAL WHICH SHALL BE

FOLLOWED UNDER SIMILAR CIRCUMSTANCES, USUALLY IN

THE SAME TYPE OF SPACE.

4. THE INTENT OF THE DRAWINGS AND SPECIFICATIONS IS TO

ESTABLISH TYPE AND QUALITY OF MATERIALS; SIZES AND

CAPACITIES OF COMPONENTS; AND A GENERAL LAYOUT OF

LOCATION OF COMPONENTS THAT COMPRISE THE ELECTRICAL

SYSTEMS. ANY DEVIATIONS FROM THE DRAWINGS AND

SPECIFICATIONS MUST BE THROUGH A DULY ISSUED ADDENDUM.

THE BASE BID MUST REFLECT SYSTEMS AS INDICATED OR

REQUIRED BY THE CONTRACT DOCUMENTS.

5. PLANS AND SPECIFICATIONS SUPPLEMENT EACH OTHER AND

REQUIRE THE CONTRACTOR PROVIDE IN THEIR BID: ALL LABOR,

TOOLS, MATERIALS, PAINT, TRANSPORTATION, TAXES, RELATED

ITEMS, ETC., ESSENTIAL FOR INSTALLATION OF WORK; ALL

SYSTEMS COMPLETE AND LEFT IN GOOD OPERATING CONDITION;

ANY APPARATUS, APPLIANCE, MATERIAL OR WORK NOT SHOWN

ON DRAWINGS BUT MENTIONED IN SPECIFICATIONS, OR VICE

VERSA; ANY ACCESSORIES, REASONABLY INFERABLE FROM

DRAWINGS AND SPECIFICATIONS, NECESSARY TO MAKE WORK

COMPLETE AND READY FOR OPERATION.

6. WORK SHALL BE INSTALLED IN ACCORDANCE WITH ALL

APPLICABLE PROVISIONS OF LOCAL AND STATE CODES, AS WELL

AS THE NATIONAL ELECTRICAL CODE (NEC), AS INTERPRETED BY

THE LOCAL AUTHORITY HAVING JURISDICTION.

7. ALL DISTRIBUTION EQUIPMENT, DEVICES, LIGHTING FIXTURES,

CONTROL DEVICES AND EQUIPMENT, AND ALL OTHER SPECIFIED

ELECTRICAL EQUIPMENT SHALL BE INSTALLED AS REQUIRED BY

THE MANUFACTURER'S INSTALLATION INSTRUCTIONS.

8. THE INSTALLATION SHALL BE MADE IN A NEAT AND WORKMANLIKE

MANNER BY PERSONNEL LICENSED AND SKILLED IN THE TRADE

AND SHALL BE DONE UNDER THE SUPERVISION OF A MASTER

ELECTRICIAN LICENSED TO DO WORK IN THE STATE OF FLORIDA.

9. THE DRAWINGS ARE ESSENTIALLY DIAGRAMMATIC AND ARE

INTENDED TO GENERALLY INDICATE SIZE, CAPACITY AND

LOCATION, HOWEVER, NOT EXACT DETAILS OR ARRANGEMENT OF

CONSTRUCTION. CONTRACT DOCUMENTS SHALL BE EXAMINED

SO THAT ALL DETAILS OF THE PROJECT ARE UNDERSTOOD AND

WORK PROCEDURES KNOWN BEFORE BID AND INSTALLATION.

EXACT LOCATIONS AND DETAILS SHALL BE OBTAINED FROM

DIMENSIONED ARCHITECTURAL AND STRUCTURAL DRAWINGS,

HOWEVER DIMENSIONS SHOWN ON DRAWINGS SHALL NOT TAKE

PRECEDENCE OVER FIELD LAYOUT DIMENSIONS.

10. MISCELLANEOUS EQUIPMENT (PULL BOXES, JUNCTION BOXES,

FITTINGS, EXPANSION JOINT COUPLINGS, ETC) NECESSARY TO

COMPLETE THE WORK SHALL BE FURNISHED AND INSTALLED

EVEN THOUGH NOT SPECIFICALLY SHOWN ON PLANS.

11. ALL MATERIALS AND LABOR SHALL BE UNCONDITIONALLY

WARRANTED FOR A PERIOD OF ONE (1) YEAR FROM DATE OF

SUBSTANTIAL COMPLETION. SPECIFIC MANUFACTURER'S

EQUIPMENT WARRANTIES IN EXCESS OF ONE (1) YEAR SHALL

TAKE PRECEDENCE. MANUFACTURER'S WARRANTIES SHALL BE

PROVIDED WHENEVER AVAILABLE AND POSSIBLE. ALL

EQUIPMENT AND MATERIALS SHALL BE NEW AND UNUSED FROM

THE FACTORY AND SHALL BE UL LISTED FOR THE APPLICATION.

MINOR ADJUSTMENTS OR ALIGNMENTS REQUIRED FOR PROPER

OPERATION ARE ACCEPTABLE.

12. PROVIDE PRODUCT DATA AND SHOP DRAWINGS FOR: WIRING

DEVICES, DISCONNECT SWITCHES, AND ALL OTHER SPECIFIED

SYSTEMS AND COMPONENTS.

13. IDENTIFICATION OF ELECTRICAL SYSTEMS AND EQUIPMENT SHALL

BE AS FOLLOWS: PANELBOARDS, DISCONNECT SWITCHES, ETC.,

PROVIDE ENGRAVED LAMINATED PLASTIC PLATES WITH

LETTERING. CHARACTERS SHALL BE MINIMUM 1/2" AND THE

INSCRIPTION SHALL BE CENTERED ON THE PLATE, DOOR OR

SECTION. ATTACH PLATES WITH SELF-TAPPING SCREWS OR 3M

CP-5200 ADHESIVE. NAMEPLATES SHALL INCLUDE THE

EQUIPMENT DESIGNATION, VOLTAGE AND PHASE, THE SOURCE

PANELBOARD, AND THE LOAD SERVED (FOR DISCONNECT

SWITCHES. ALL PANELBOARDS SUPPLIED BY A FEEDER SHALL BE

MARKED TO INDICATE EACH DEVICE OR EQUIPMENT WHERE THE

POWER ORIGINATES AS REQUIRED BY NEC 408.4(B). NAMEPLATES

SHALL HAVE WHITE BACKGROUND WITH BLACK TEXT.

14. THE OUTSIDE OF COVERPLATES FOR JUNCTION BOXES (INSIDE OF

COVERPLATES FOR JUNCTION BOXES LOCATED IN FINISHED

AREAS) SHALL BE PERMANENTLY MARKED TO INDICATE THE

PANEL NAME AND CIRCUIT NUMBER, OR THE SYSTEM.

15. PROVIDE EXTERIOR SITE ELECTRICAL EQUIPMENT AND

MATERIALS AS DESCRIBED ON THE CONTRACT DOCUMENTS,

INCLUDING EXCAVATION, TRENCHING AND BACKFILL.

16. ANY EXISTING UTILITIES THAT ARE SHOWN ON THE DRAWINGS OR

THE LOCATION OF WHICH IS MADE KNOWN TO THE CONTRACTOR

PRIOR TO EXCAVATION SHALL BE PROTECTED FROM DAMAGE

DURING THE EXCAVATION AND BACKFILLING OF TRENCHES, AND

IF DAMAGED SHALL BE REPAIRED BY THE CONTRACTOR AT THEIR

EXPENSE.

17. THE CONTRACTOR SHALL BE RESPONSIBLE FOR ALL NECESSARY

CUTTING AND PATCHING REQUIRED IN CONNECTION WITH THIS

WORK. CUTTING OF STRUCTURAL MEMBERS AND FINISHED

SURFACES IS NOT PERMITTED WITHOUT PERMISSION FROM THE

ARCHITECT OR STRUCTURAL ENGINEER.

18. AFTER INSTALLATION, THE CONTRACTOR SHALL TEST FOR

GROUNDS, SHORT CIRCUITS AND PROPER OPERATION OF EACH

SYSTEM AND RELATED WIRING. INSULATION RESISTANCE TESTS

SHALL BE MADE ON THE ELECTRICAL SYSTEM WITH AN APPROVED

MEGOHMMETER. A GROUND CONTINUITY TEST SHALL BE MADE

ON THE ENTIRE GROUNDING SYSTEM FROM THE SERVICE TO

EVERY NEW OUTLET.

19. THE CONTRACTOR SHALL CLEAR AWAY ALL DEBRIS, SURPLUS

MATERIALS, ETC., RESULTING FROM THIS WORK AND

OPERATIONS, LEAVING THE JOB AND EQUIPMENT FURNISHED

UNDER THIS CONTRACT IN A CLEAN AND FIRST-CLASS CONDITION.

20. THE CONTRACTOR SHALL INSURE THAT PERSONNEL AS

DESIGNATED BY THE OWNER SHALL BE INSTRUCTED, TO THE

OWNER'S SATISFACTION, IN THE USE AND MAINTENANCE OF

ELECTRICAL EQUIPMENT AND SYSTEMS DESCRIBED IN THESE

DRAWINGS AND SPECIFICATIONS, BY AUTHORIZED

MANUFACTURER'S PERSONNEL.

21. FURNISH AS-BUILT DRAWINGS FOR ELECTRIC POWER SYSTEMS

WITHIN 30 DAYS OF SYSTEM ACCEPTANCE TO BUILDING OWNER.

FURNISH OPERATION AND MAINTENANCE INSTRUCTIONS FOR

ELECTRICAL SYSTEMS AND EQUIPMENT TO THE BUILDING OWNER

OR DESIGNATED REPRESENTATIVE.

WIRE AND CABLE

1. WIRE AND CABLE FOR BRANCH CIRCUITS AND FEEDERS SHALL BE

600 VOLT WITH MAXIMUM OPERATING TEMPERATURE OF 90°C,

TYPE THHN OR THWN-2. TYPE XHHW SHALL ALSO BE

ACCEPTABLE FOR FEEDERS. ALL CONDUCTORS SHALL BE

COPPER EXCEPT AS NOTED OTHERWISE ON THE DRAWINGS.

MINIMUM SIZE SHALL BE #12 AWG FOR POWER WIRING, AND #14

FOR CONTROL WIRING. ALL 600 VOLT CONDUCTORS SHALL BE

INSTALLED IN CONDUIT.

WIRE AND CABLE SHALL BE IDENTIFIED IN ACCORDANCE WITH THE

NATIONAL ELECTRICAL CODE. FEEDER CONDUCTORS SHALL

BE IDENTIFIED BY COLORED INSULATION OR COLORED TAPE

AT THE TERMINALS.

2. WHERE MORE THAN ONE NEUTRAL CONDUCTOR ASSOCIATED

WITH DIFFERENT CIRCUITS IS LOCATED IN AN ENCLOSURE,

NEUTRAL CONDUCTORS OF EACH CIRCUIT SHALL BE IDENTIFIED

OR GROUPED TO CORRESPOND WITH THE UNGROUNDED CIRCUIT

CONDUCTOR(S) BY WIRE MARKERS, CABLE TIES, OR SIMILAR

MEANS WITHIN THE ENCLOSURE AS REQUIRED BY NEC 200.4(B).

3. FEEDER AND BRANCH CIRCUIT CONDUCTORS SHALL BE COLOR

CODED AS FOLLOWS:

3.1. 240/120V, 1 PH, 3W SYSTEM:

PHASE A - BLACK

PHASE B - RED

NEUTRAL - WHITE

GROUNDING AND BONDING

1. INSTALL INSULATED EQUIPMENT GROUNDING CONDUCTORS WITH

ALL FEEDERS AND BRANCH CIRCUITS.

2. BOND ALL ELECTRICAL SYSTEM RACEWAYS, PANELS, METAL

BOXES, WIRING DEVICES, MOTORS, AND OTHER EXPOSED

NON-CURRENT CARRYING METAL PARTS OF ELECTRICAL

EQUIPMENT IN ACCORDANCE WITH NEC ARTICLE 250.

3. INSTALL BONDING JUMPERS ACROSS ALL CONDUIT EXPANSION

FITTINGS.

4. ROUTE GROUNDING CONDUCTORS ALONG THE SHORTEST AND

STRAIGHTEST PATHS POSSIBLE UNLESS OTHERWISE NOTED OR

REQUIRED BY NEC ARTICLE 250. AVOID OBSTRUCTING ACCESS

AND AVOID PLACING GROUNDING CONDUCTORS WHERE THEY

MAY BE SUBJECTED TO STRAIN, IMPACT, OR DAMAGE.

5. ALL GROUNDING SYSTEMS SHALL BE TESTED AND DOCUMENTED

IN FULL ACCORDANCE WITH IEEE STANDARD 81 "IEEE GUIDE FOR

MEASURING EARTH RESISTIVITY, GROUND IMPEDANCE AND

EARTH SURFACE POTENTIALS OF A GROUND SYSTEM" AND THE

NETA ATS-2021 SPECIFICATIONS.

RACEWAYS AND FITTINGS

1. ALL CONDUITS AND FITTINGS SHALL BE CONCEALED

THROUGHOUT THE BUILDING, EXCEPT UNFINISHED AREAS. ALL

CONDUIT RUNS SHALL BE PARALLEL OR PERPENDICULAR TO

BUILDING GRID LINES AND SHALL GENERALLY FOLLOW THE

DIRECTION OF MAJOR FRAMING JOISTS OR FURRING. ALL

CONDUITS AND RACEWAYS SHALL BE SECURELY SUPPORTED BY

GALVANIZED STEEL SUPPORTS. CONDUIT SHALL BE CAPPED OR

PLUGGED DURING CONSTRUCTION TO KEEP OUT FOREIGN

MATERIALS AND MOISTURE.

2. RIGID GALVANIZED STEEL CONDUIT OR INTERMEDIATE METALLIC

CONDUIT SHALL BE PROVIDED IN DAMP OR WET LOCATIONS, OR

WHERE SUBJECT TO PHYSICAL ABUSE. PVC SCHEDULE 40

CONDUIT SHALL BE PROVIDED IN OR BELOW SLABS ON GRADE, IN

ALL EXTERIOR UNDERGROUND APPLICATIONS, WHERE NOT

SUBJECT TO PHYSICAL ABUSE. ALL OTHER INTERIOR CONDUITS

SHALL BE ELECTRICAL METALLIC TUBING (EMT), UON.

3. ALL UNDERGROUND CONDUIT INSTALLED BETWEEN THE

BUILDING, ABOVE GROUND FUEL STORAGE TANK, AND FUEL

DISPENSERS SHALL BE THREADED RMC CONDUIT AS REQUIRED

BY NEC 514.8. PROVIDE LISTED SEAL OFF FITTINGS AT FUEL

DISPENSERS, THE ABOVE GROUND FUEL STORAGE TANK AND AT

BOUNDARIES OF CLASSIFIED LOCATIONS. THE SEAL OFF FITTINGS

SHALL BE THE FIRST FITTINGS AFTER THE CONDUIT EMERGES

FROM THE EARTH OR CONCRETE AS REQUIRED BY NEC 514.9.

4. ALL CONDUITS AND FITTINGS SHALL BE UL LISTED FOR THE

APPLICATION AND SHALL BE 3/4" TRADE SIZE, MINIMUM, UNLESS

OTHERWISE NOTED ON THE DRAWINGS. PROVIDE STEEL SET

SCREW FITTINGS FOR ALL EMT CONDUIT.

5. COORDINATE EXACT ROUTING AND ELEVATION OF

UNDERGROUND CONDUIT WITH ALL OTHER TRADES PRIOR TO

EXCAVATION AND INSTALLATION.

6. PROVIDE LISTED EXPANSION/DEFLECTION FITTINGS AT ALL

LOCATIONS WHERE A RACEWAY CROSSES A STRUCTURAL JOINT

INTENDED FOR EXPANSION, CONTRACTION OR DEFLECTION AS

REQUIRED BY NEC 300.4(H), OR WHERE NECESSARY TO

COMPENSATE FOR THERMAL EXPANSION, DEFLECTION AND

CONTRACTION AS REQUIRED BY NEC 300.7(B).

7. CONDUITS PASSING FROM THE EXTERIOR TO THE INTERIOR OF A

BUILDING SHALL BE FILLED WITH AN APPROVED MATERIAL TO

PREVENT THE CIRCULATION OF WARM AIR TO A COLDER SECTION

OF THE RACEWAY IN ACCORDANCE WITH NEC 300.7(A).

8. CONDUITS SHALL BE CONTINUOUS AND SECURED TO ALL BOXES

IN SUCH A MANNER THAT EACH CONDUIT SYSTEM IS

ELECTRICALLY CONTINUOUS FROM THE POINT OF SERVICE TO

ALL DEVICE BOXES. THE ACTUAL ROUTING OF CONDUIT SHALL BE

INSTALLED TO SUIT THE FIELD CONDITIONS.

ELECTRICAL BOXES

1. OUTLET AND JUNCTION BOXES FOR INTERIOR USE SHALL BE UL

LISTED GALVANIZED PRESSED STEEL TYPE, 4"X4"X2" DEEP

MINIMUM, AND SHALL BE PROVIDED WITH COVERPLATES

SUITABLE FOR THE APPLICATION. ALL OUTLET BOXES SHALL BE

CONCEALED WHEREVER POSSIBLE THROUGHOUT THE BUILDING,

UON. 4" SQUARE AND 4-11/16" SQUARE BOXES SHALL BE FITTED

WITH GALVANIZED STEEL PLASTER COVERS OR RINGS DESIGNED

FOR FLUSH INSTALLATION.

2. OUTLET BOXES FOR EXTERIOR USE SHALL BE CAST OR

MALLEABLE IRON TYPE WITH THREADED HUBS AND

WEATHERPROOF COVERS AND FITTINGS. CAST BOXES SHALL BE

TYPE FS.

3. ALL BOXES SHALL BE RIGIDLY SUPPORTED FROM THE BUILDING

STRUCTURE INDEPENDENT OF THE CONDUIT SYSTEM. BOX

STABILIZERS SHALL BE PROVIDED TO PROPERLY SUPPORT BOXES

IN METAL STUD CONSTRUCTION.

WIRING DEVICES

1. ALL DEVICES AND COVERPLATES SHALL BE PRODUCTS OF ONE

MANUFACTURER WHEREVER POSSIBLE. WIRING DEVICES SHALL

BE STANDARD TYPE MANUFACTURED BY LEVITON, OR

EQUIVALENT BY HUBBELL, COOPER, OR PASS AND SEYMOUR.

2. DUPLEX RECEPTACLES SHALL BE 20 AMPERES, 125 VOLTS AC,

NEMA 5-20R - LEVITON INDUSTRIAL SPECIFICATION GRADE 5362

SERIES. PROVIDE GROUND FAULT CIRCUIT INTERRUPTING (GFCI)

TYPE WHERE INDICATED ON THE DRAWINGS.

3. PROVIDE COVERPLATES FOR ALL WIRING DEVICES.

COVERPLATES FOR FLUSH MOUNTED INDOOR DEVICES SHALL BE

SMOOTH HIGH IMPACT THERMOPLASTIC NYLON WITH COLOR TO

MATCH DEVICES. COVERPLATES FOR SURFACE MOUNTED

INDOOR DEVICES IN UNFINISHED AREAS SHALL BE RAISED

GALVANIZED STEEL INDUSTRIAL TYPE WITH COVER-MOUNTED

DEVICES.

4. ALL RECEPTACLES SHALL BE WHITE, VERIFY COLOR WITH THE

OWNER PRIOR TO PROCUREMENT OF THE DEVICES.

5. ALL DEVICES SHALL BE SECURED WITH MORE THAN A SINGLE

SCREW.

DISCONNECTS

1. SAFETY SWITCHES SHALL BE HEAVY-DUTY FUSIBLE OR

NON-FUSIBLE TYPE AS SHOWN ON THE DRAWINGS.

2. ENCLOSED CIRCUIT BREAKERS SHALL BE MOLDED CASE CIRCUIT

BREAKERS MOUNTED IN INDIVIDUAL ENCLOSURES. CIRCUIT

BREAKERS SHALL BE THERMAL-MAGNETIC TYPE, WITH TRIP

RATINGS AS SHOWN ON THE DRAWINGS. THE SHORT CIRCUIT

RATING SHALL NOT BE LESS THAN THE REQUIRED RATING SHOWN

ON THE DRAWINGS.

3. SAFETY SWITCHES AND ENCLOSED CIRCUIT BREAKERS SHALL BE

CAPABLE OF BEING LOCKED IN THE OPEN POSITION.

4. SAFETY SWITCHES AND ENCLOSED CIRCUIT BREAKERS SHALL BE

MANUFACTURED BY SQUARE D, SIEMENS, ABB OR EATON CUTLER

HAMMER.

AutoCAD SHX Text

REVISION

AutoCAD SHX Text

DATE

AutoCAD SHX Text

NO.

AutoCAD SHX Text

ISSUE:

AutoCAD SHX Text

ISSUE DATE:

AutoCAD SHX Text

DRAWN BY:

AutoCAD SHX Text

CHECKED BY:

AutoCAD SHX Text

PROJECT NUMBER:

AutoCAD SHX Text

PERMIT SET

AutoCAD SHX Text 05.06.2024

AutoCAD SHX Text

CCO23002

AutoCAD SHX Text

PERMIT SET

AutoCAD SHX Text 05.06.2024

AutoCAD SHX Text

RMR

EE

DEMO

E

FB-14,16

E-3

RESTROOMS

ELECTRICAL

ROOM

FB-20

PADMOUNT SERVICE

TRANSFORMER (ETR)

LIFT STATION SERVICE

PANEL AND METER (ETR)

BOAT LIFT SERVICE

DISCONNECT AND

METER (ETR)

BUILDING SERVICE

DISCONNECT AND

METER (ETR)

J

FB-15 J

FB-18

FB-9

PANEL F (ETR)

PANEL FB (ETR)

FB-11

ELECTRICAL

ROOM

C O

LL

IE

R C

O U

N T

Y C

A X A

M B A

S M

A R

IN

A

F U

EL

SY

ST

EM

R

EP

LA

C

EM

EN

T

C o ll ie r C t.

M ar co

I sl an d

FL

C O

RK

SC

RE

W

R D

SU

IT

E

ES

T

ER

O

FL

Fl o ri d a

C o A

Je ff re y

A Je n k in s, F

L

PE

P:

-2

-5

F:

-2

-5

JM

A

JE

N

K

IN

S M

A A

G A

SS

O C

IA

T

ES

LL

C

ELECTRICAL PLANS

E-3

SCALE: 1/8" = 1'-0" 0 8' 16'4'

NORTH

SITE ELECTRICAL PLAN

A. PROVIDE A CLEARLY IDENTIFIED EMERGENCY SHUTOFF DEVICE

OR DISCONNECT BETWEEN 20FT AND 100FT FROM THE

DISPENSING DEVICE SERVED. PROVIDE LABEL AT DEVICE,

"EMERGENCY FUEL SHUTOFF". ELECTRICAL SHUTOFF DEVICES

SHALL BE INSTALLED AND CAPABLE OF MEETING ALL

REQUIREMENTS OF NFPA 30A SECTION 6.7.

B. REFER TO NFPA 30A FIGURE 8.3.3 AND TABLE 8.3.3 FOR AVAILABLE

INSTALL LOCATIONS OF ELECTRICAL WIRING AND EQUIPMENT.

ELECTRICAL WIRING/CONDUITS TO BE CLASS 1, DIVISION 1 OR

CLASS 1, DIVISION 2, PER THIS TABLE.

C. ALL ELECTRICAL WIRING FOR POWER SHALL BE PROTECTED

FROM A RELEASE FROM THE FUEL PIPING SYSTEM.

D. ALL UNDERGROUND CONDUIT INSTALLED BETWEEN THE

BUILDING, THE ABOVE GROUND FUEL STORAGE TANK, AND FUEL

DISPENSERS SHALL BE THREADED RMC CONDUIT AS REQUIRED

BY NEC 514.8. PROVIDE LISTED SEAL OFF FITTINGS AT FUEL

DISPENSERS, THE ABOVE GROUND FUEL STORAGE TANK AND AT

BOUNDARIES OF CLASSIFIED LOCATIONS. THE SEAL OFF FITTINGS

SHALL BE THE FIRST FITTINGS AFTER THE CONDUIT EMERGES

FROM THE EARTH OR CONCRETE AS REQUIRED BY NEC 514.9.

SHEET KEYNOTES

1. EXISTING EMERGENCY SHUT OFF SHALL BE REMOVED. REMOVE

WIRING COMPLETE TO SOURCE SHUNT TRIP CIRCUIT BREAKER IN

PANEL F.

2. EXISTING PULLBOX WITH CONDUIT FROM PANEL FB AND OUT TO

EXISTING PUMPS, DISPENSERS AND CONTROLS.

3. EXISTING UNDERGROUND FUEL TANK LOCATION. EC SHALL

DISCONNECT AND REMOVE ELECTRICAL CONNECTIONS TO PUMPS

AND CONTROLS, AND REMOVE WIRING COMPLETE TO SOURCE

PANEL FB.

4. SUBMERSIBLE PUMP AT ABOVE GROUND FUEL TANK - 230V, 1 PH, 2

HP. COORDINATE WITH EQUIPMENT INSTALLER.

5. SUBMERSIBLE PUMP CONTROL PANEL- 120V. COORDINATE WITH

EQUIPMENT INSTALLER.

6. NEW EMERGENCY SHUT OFF PUSHBUTTON - REFER TO THE RISER

DIAGRAM ON SHEET E-4.

7. DEVICES SHALL BE INSTALLED AT ATTENDED DESK, COORDINATE

EXACT LOCATION WITH COUNTY.

8. FUEL DISPENSER - 120V. COORDINATE WITH EQUIPMENT

INSTALLER.

9. 3/4" CONDUIT UNDERGROUND WITH PULL STRING TO ELECTRICAL

ROOM FOR LOW VOLTAGE DATA/COMMUNICATION CABLING FOR

FUEL DISPENSER.

10. NOT USED.

11. NOT USED.

12. OVERFILL ALARM/LEAK DETECTION CONTROL PANEL - 120V.

COORDINATE WITH EQUIPMENT INSTALLER.

13. EXISTING FUEL SYSTEM AND FUEL STORAGE TANK CONTROLS

THIS ROOM TO BE REMOVED, EC SHALL DISCONNECT EQUIPMENT

AND REMOVE WIRING COMPLETE TO SOURCE PANEL FB. FIELD

VERIFY EXISTING CONDITIONS AND COORDINATE WITH FUEL

SYSTEM EQUIPMENT INSTALLER.

14. HIGHLINK MONITORING SYSTEM - 120V. COORDINATE WITH

EQUIPMENT INSTALLER.

15. ROUTE 1" CONDUIT WITH PULL STRING UNDERGROUND FROM

DISPENSER TO FUEL STORAGE TANK CONTROLS/SOLENOID

VALVE. COORDINATE EXACT REQUIREMENTS WITH FUEL

STORAGE TANK/CONTROLS INSTALLER.

GENERAL SHEET NOTES

SCALE: 1/4" = 1'-0" 0 4' 8'2'

NORTH

ENLARGED

ELECTRICAL ROOM

A1

A1

AutoCAD SHX Text S

AutoCAD SHX Text S

AutoCAD SHX Text

DESTROYED CONCRETE AREA (COVERED IN SHELL)

AutoCAD SHX Text

BOAT RAMP

AutoCAD SHX Text

EXIST. BUILDING

AutoCAD SHX Text

EXIST. SHED

AutoCAD SHX Text

SEAWALL

AutoCAD SHX Text

SEAWALL

AutoCAD SHX Text

FUEL DOCK

AutoCAD SHX Text

DOCK

AutoCAD SHX Text

REVISION

AutoCAD SHX Text

DATE

AutoCAD SHX Text

NO.

AutoCAD SHX Text

ISSUE:

AutoCAD SHX Text

ISSUE DATE:

AutoCAD SHX Text

DRAWN BY:

AutoCAD SHX Text

CHECKED BY:

AutoCAD SHX Text

PROJECT NUMBER:

AutoCAD SHX Text

PERMIT SET

AutoCAD SHX Text 05.06.2024

AutoCAD SHX Text

CCO23002

AutoCAD SHX Text

PERMIT SET

AutoCAD SHX Text 05.06.2024

AutoCAD SHX Text

RMR

AutoCAD SHX Text

JAJ

AutoCAD SHX Text

ADDENDUM #1

AutoCAD SHX Text 07.16.2024

A1

LL

IE

R C

O U

N T

Y C

A X A

M B A

S M

A R

IN

A

F U

EL

SY

ST

EM

R

EP

LA

C

EM

EN

T

C o ll ie r C t.

M ar co

I sl an d

FL

C O

RK

SC

RE

W

R D

SU

IT

E

ES

T

ER

O

FL

Fl o ri d a

C o A

Je ff re y

A Je n k in s, F

L

PE

P:

-2

-5

F:

-2

-5

JM

A

JE

N

K

IN

S M

A A

G A

SS

O C

IA

T

ES

LL

C

RISER AND SCHEDULES

E-4

COPPER WIRE AND CONDUIT SCHEDULE

DESIGNATION PARALLEL

RUNS

CONDUCTORS

(AWG/kcmil)

GROUND

(AWG/kcmil) CONDUIT

C2-20 1 2 # 12 1 # 12 3/4" C2-20v1 1 2 # 10 1 # 10 3/4" C2-30 1 2 # 10 1 # 10 3/4" C3-30 1 3 # 10 1 # 10 3/4" C3-60 1 3 # 6 1 # 10 1"

NOTES

1. ALL CONDUCTORS INDICATED IN SCHEDULE SHALL BE

COPPER.

NOTES:

1. CONTRACTOR SHALL LOCATE UNDERGROUND CONDUIT A

MINIMUM OF 10'-0" FROM NEAREST TREE, OR IF NOT PRACTICAL,

AS DIRECTED IN FIELD BY THE LANDSCAPE ARCHITECT.

2. ALL UNDERGROUND ELECTRIC CONDUIT SHALL HAVE A

DETECTABLE WARNING TAPE INSTALLED DIRECTLY ABOVE THE

CONDUIT. WARNING TAPE SHALL BE REEF INDUSTRIES, INC.

TERRA TAPE, 3" WIDE, LABELED WITH "CAUTION ELECTRIC LINE

BURIED BELOW".

CLEAN FILL

SELECTED

BACKFILL

CONDUIT

DETECTABLE

UNDERGROUND

WARNING TAPE

GRADE OR

PAVEMENT

18" MINIMUM

" M

IN

6" 12 " M

IN

PANEL: FB PANELBOARD SCHEDULE

CIRCUIT BREAKERS WIRE AND Ø WIRE AND CIRCUIT BREAKERS

# DESCRIPTION Trip (A) Poles Options CONDUIT LOAD (VA) LOAD (VA) CONDUIT Options Poles Trip (A) DESCRIPTION #

1 SPARE 20 2 - A - 2 20 SPARE 2

3 - B - 4

5 SPARE 20 2 - A - 2 20 SPARE 6

7 - B - 8 b 9 DISPENSER 20 1 C2-20v1 1,200 A - ETR 2 20 TEST RECEPTACLE 10 b 11 HIGHLINK CONTROLS 20 1 C2-20 200 B - 12

13 RECEPTACLE 30 1 ETR 2,500 A 1,380 C3-30 2 25 SUBMERSIBLE PUMP 14 a a 15 FUEL TANK ALARM SYSTEM 20 1 C2-20 200 B 1,380 16

17 SPACE - A 100 C2-20 1 20 PUMP CONTROLS 18 a 19 SPACE - B 180 C2-20 1 20 FUEL SYSTEM DISPLAY 20 a

21 SPACE - A - SPACE 22

23 SPACE - B - SPACE 24

Connected Demand Demand Feeder Size Connected Load (VA) Panel Requirements Load Description Load (VA) Factor Load (VA) Load (VA) Phase A: 5,180 Voltage: 120/240V, 1Ø, 3W Lighting: - 1.00 - 125% - Phase B: 1,960 Mains: 60 A MLO Receptacles - First 10 kVA: 180 1.00 180 100% 180 Rating: 10 kAIC Receptacles - Over 10 kVA: - 0.50 - 100% - Motors: - 1.00 - 100% - Mounting: Surface Largest Motor: 2,760 1.00 2,760 125% 3,450 Panel Service Enclosure Type: NEMA 1 Air Conditioning: - - - 100% - Fed From: Panel F Isolated Ground: No Heat Pumps: - 1.00 - 100% - Feeder: ETR Sub-feed Lugs: No Electric Space Heating: - 1.00 - 100% - Feed-thru Lugs: No Kitchen: - 1.00 - 100% - Elevators: - 1.00 - 100% - Continuous Loads: - 1.00 - 125% - Notes:

Non-continuous Loads: 4,200 1.00 4,200 100% 4,200 Square D QO Loadcenter Totals (VA): 7,140 7,140 7,830 Total (A): 30 A 33 A See Wire and Conduit Schedule for wire and conduit sizes.

a WIRE NEW CIRCUIT TO EXISTING SPARE CIRCUIT BREAKER OR CIRCUIT BREAKER MADE SPARE DURING DEMOLITION b REPLACE EXISTING SPARE CIRCUIT BREAKER OR CIRCUIT BREAKER MADE SPARE DURING DEMOLITION WITH NEW CIRCUIT BREAKER SHOWN

A. METER SOCKETS SHALL BE PERMANENTLY MARKED TO SHOW

PLAINLY THE LOCATION SERVED AND THE CHARACTER OF THE

SERVICE AS REQUIRED BY THE ELECTRIC UTILITY COMPANY. THE

MARKING SHALL CORRESPOND TO THE MARKING ON THE

ASSOCIATED SERVICE DISCONNECT(S).

B. ALL PANELBOARDS SUPPLIED BY A FEEDER SHALL BE

PERMANENTLY MARKED TO INDICATE EACH DEVICE OR

EQUIPMENT WHERE THE POWER ORIGINATES AS REQUIRED BY

NEC 408.4(B).

C. AN ATTEMPT HAS BEEN MADE TO INDICATE THE EXISTING POWER

DISTRIBUTION SYSTEM CONDITIONS. THE CONTRACTOR SHALL

VERIFY ALL EQUIPMENT, PANELS, FEEDERS, ETC. AND NOTIFY THE

ENGINEER OF ANY DISCREPANCIES.

D. THE EXISTING SERVICE SHALL REMAIN. COORDINATE ALL

SHUTDOWNS REQUIRED TO COMPLETE THIS WORK WITH THE

OWNER.

E. ALL NEW CIRCUIT BREAKERS PROVIDED TO BE INSTALLED IN ANY

EXISTING PANEL SHALL MATCH THE EXISTING EQUIPMENT

MANUFACTURER, BE LISTED FOR USE IN THE EXISTING

EQUIPMENT AND HAVE A SHORT CIRCUIT RATING TO MEET OR

EXCEED THE RATING OF THE EXISTING EQUIPMENT.

F. FAULT CURRENT CALCULATIONS BASED ON ESTIMATED SERVICE

TRANSFORMER SIZE.

GENERAL RISER DIAGRAM NOTES

1. CONTACTOR SHALL BE SQUARE D CLASS 8903 TYPE S

ELECTRICALLY HELD CONTACTOR OR EQUAL - 60A, 3-POLE,

MINIMUM 10 KAIC RATED, NORMALLY OPEN WITH 120V COIL.

LOCATE IN A NEMA 1 ENCLOSURE ADJACENT PANEL FB. PANEL FB

SERVES ALL LINE VOLTAGE CIRCUITS TO THE FUEL PUMP

DISPENSERS, FUEL STORAGE TANK PUMP AND ALARMS, AND LOW

VOLTAGE EQUIPMENT THAT SERVES DATA AND MONITORING TO

THE FUEL PUMP DISPENSERS AND STORAGE TANK. THE

CONTACTOR SHALL BE WIRED TO THE EMERGENCY STOP

SWITCHES, SUCH THAT WHEN ANY SWITCH IS ACTIVATED, ALL

PHASE AND NEUTRAL CONDUCTORS IN FEEDER TO PANEL FB ARE

DISCONNECTED AS REQUIRED BY NEC 514.11.

2. REPLACE EXISTING 60A, 2-POLE SHUNT TRIP CIRCUIT BREAKER

WITH NEW 60A, 2-POLE CIRCUIT BREAKER.

RISER KEYNOTES

M

F FB

PADMOUNT SERVICE

TRANSFORMER

120/240V, 1 PH, 3W

(ETR)

E

PROVIDE EMERGENCY STOP PUSHBUTTONS THAT

REQUIRE MANUAL RESET, AS REQUIRED BY NEC

514.11, WIRED TO SIMULTANEOUSLY DISCONNECT

EACH CIRCUIT LEADING TO THE FUEL STORAGE

AND DISPENSING EQUIPMENT - 120V, NORMALLY

CLOSED. SEE SHEET E-3 FOR LOCATIONS.

PUSHBUTTON SHALL BE LABELED WITH AN

APPROVED SIGN STATING "EMERGENCY FUEL

SHUTOFF" AS REQUIRED BY NFPA 30A SECTION 6.7.

MA

IN

0A

E

1 (ETR)

(ETR)BUILDING SERVICE

DISCONNECT

200A

NEMA-3R

(ETR)

ETRETR

ETR ETR

ETR

METER

(ETR)

C3-60

SCALE: NONE1

RISER DIAGRAM

C2-20 F-35

SCA=

8,474A

SCA=

18,961A

SCA=

6,563A

PANEL: F PANELBOARD SCHEDULE

CIRCUIT BREAKERS WIRE AND Ø WIRE AND CIRCUIT BREAKERS

# DESCRIPTION Trip (A) Poles Options CONDUIT LOAD (VA) LOAD (VA) CONDUIT Options Poles Trip (A) DESCRIPTION # 1 AHU 45 2 ETR 3,936 A 5,180 See Riser 2 60 PANEL FB 2 b 3 3,936 B 1,960 4

5 CU 30 2 ETR 1,610 A - SPACE 6

7 1,610 B 1,380 ETR 2 30 PUMP OUT SYSTEM 8

9 LIGHTING 20 1 ETR 800 A 1,380 10

11 LIGHTING 20 1 ETR 800 B - SPACE 12

13 LIGHTING 20 1 ETR 800 A 360 ETR 1 20 REC - FILE ROOM 14

15 LIGHTING 20 1 ETR 800 B 360 ETR 1 20 REC - FILE ROOM 16

17 LIGHTING - EXTERIOR 20 1 ETR 800 A 360 ETR 1 20 REC - WEST WALL 18

19 REC - SHOW ROOM 20 1 ETR 360 B 360 ETR 1 20 REC - REGISTER 20

21 REC - SHOW ROOM 20 1 ETR 360 A 200 ETR 1 20 LIVE BAIT TANK 22

23 FREEZER 20 1 ETR 400 B 360 ETR 1 20 REC - SHOW ROOM 24

25 FREEZER 20 1 ETR 400 A 1,500 ETR 1 20 HOT WATER HEATER 26

27 SHOW WINDOW 20 1 ETR 1,200 B - ETR 1 20 FRONT CUBE RECEPTACLE 28

29 SHOW WINDOW 20 1 ETR 1,200 A 500 ETR 2 20 LIVE BAIT TANK 30

31 SIGN 20 1 ETR 1,200 B 500 32

33 FUEL TANK MONITOR 20 1 ETR 100 A 1,800 ETR 1 20 HAND DRYER 34

a 35 SHUNT TRIP 20 1 ETR - B 1,800 ETR 1 20 HAND DRYER 36

37 LIFT STATION 50 2 ETR - A 1,800 ETR 1 20 HAND DRYER 38

39 - B 1,800 ETR 1 20 HAND DRYER 40

41 SPACE - A - SPACE 42

Connected Demand Demand Feeder Size Connected Load (VA) Panel Requirements Load Description Load (VA) Factor Load (VA) Load (VA) Phase A: 23,086 Voltage: 120/240V, 1Ø, 3W Lighting: 4,000 1.00 4,000 125% 5,000 Phase B: 18,826 Mains: 200 A MCB Receptacles - First 10 kVA: 2,700 1.00 2,700 100% 2,700 Rating: 10 kAIC Receptacles - Over 10 kVA: - 0.50 - 100% - Motors: 3,432 1.00 3,432 100% 3,432 Mounting: Flush Largest Motor: 2,760 1.00 2,760 125% 3,450 Panel Service Enclosure Type: NEMA 1 Air Conditioning: 3,220 - - 100% - Fed From: SERVICE Isolated Ground: No Heat Pumps: - 1.00 - 100% - Feeder: ETR Sub-feed Lugs: No Electric Space Heating: 7,200 1.00 7,200 100% 7,200 Feed-thru Lugs: No Kitchen: - 1.00 - 100% - Elevators: - 1.00 - 100% - Continuous Loads: 5,100 1.00 5,100 125% 6,375 Notes:

Non-continuous Loads: 13,500 1.00 13,500 100% 13,500 Square D NQOD Panelboard Totals (VA): 41,912 38,692 41,657 The loads indicated as existing are estimated.

Total (A): 161 A 174 A See Wire and Conduit Schedule for wire and conduit sizes.

a WIRE NEW CIRCUIT TO EXISTING SPARE CIRCUIT BREAKER OR CIRCUIT BREAKER MADE SPARE DURING DEMOLITION b REPLACE EXISTING SPARE CIRCUIT BREAKER(S) WITH NEW CIRCUIT BREAKER SHOWN

CEILING

FLOOR

STUB CONDUITS 6" INTO SPACE

ABOVE ACCESSIBLE CEILING IN

THE NEAREST CORRIDOR OR

OPEN AREA. TERMINATE WITH

INSULATED BUSHING (TYPICAL).

1" CONDUIT WITH PULLWIRE

(TYPICAL).

NOTES:

1. DATA OUTLET FOR FUEL SYSTEM/DISPENSER SYSTEM

MONITORING/DISPLAY, COORDINATE EXACT LOCATION AND

REQUIREMENTS WITH SYSTEM INSTALLER.

SCALE: NONE2

LOW VOLTAGE ROUGH-IN

OUTLET BOX DETAIL

SCALE: NONE3

UNDERGROUND CONDUIT

INSTALLATION DETAIL

AutoCAD SHX Text

REVISION

AutoCAD SHX Text

DATE

AutoCAD SHX Text

NO.

AutoCAD SHX Text

ISSUE:

AutoCAD SHX Text

ISSUE DATE:

AutoCAD SHX Text

DRAWN BY:

AutoCAD SHX Text

CHECKED BY:

AutoCAD SHX Text

PROJECT NUMBER:

AutoCAD SHX Text

PERMIT SET

AutoCAD SHX Text 05.06.2024

AutoCAD SHX Text

CCO23002

AutoCAD SHX Text

PERMIT SET

AutoCAD SHX Text 05.06.2024

AutoCAD SHX Text

RMR

Sheets and Views
E-1 - LEGEND
E-2 - SPECIFICATIONS
E-3 - SITE ELECTRICAL
E-4 - SCHEDULES
FL PE 65169, STATE OF FLORIDA
2024-07-18T23:55:15-0400
Jeffrey A Jenkins
I am the author of this document

File details come from the government source that posted it. Updated .