24-8284_-_Exhibit_M_-_CAXAMBAS_ELECTRICAL_Rev._1.pdf
PDF 698 KB Posted
- Solicitation number
- 24-8284
- Issued by
- Collier County, Miami City, Florida
About this file
This document is an electrical design specification set for the Caxambas Marina Fuel System Replacement project in Collier County, Florida, prepared by Jenkins Maag Associates, LLC. The electrical plans and specifications cover a comprehensive electrical replacement and upgrade for the marina's fuel system, including detailed electrical symbols, riser diagrams, wire and conduit schedules, and specific installation requirements. The document provides technical guidance for electrical contractors, outlining specific requirements for conduit installation, wiring devices, disconnects, grounding, and compliance with various electrical codes including the 2020 National Electrical Code, 2023 Florida Building Code, and NFPA standards.
The specifications include precise technical requirements for electrical components, such as using copper wire, specific conduit types (rigid galvanized steel, PVC schedule 40), GFCI receptacles, and emergency shutoff devices. The project involves replacing existing electrical systems for fuel dispensers, storage tanks, and associated equipment, with careful attention to safety protocols for fuel-related electrical installations. The electrical design incorporates specific requirements for classified locations, underground conduit installations, and compliance with hazardous area electrical standards, particularly those related to fuel handling and dispensing environments. The design ensures electrical safety and functionality for the marina's fuel system infrastructure, with detailed provisions for emergency power disconnection, equipment labeling, and proper electrical system integration.
View the file
Other files
Show all 14
On GovTribe
Work with this file
- Download the original file
- Contacts named in this file
- Similar government files
- Ask GovTribe AI about this file
Text version
C O
LL
IE
R C
O U
N T
Y C
A X A
M B A
S M
A R
IN
A
F U
EL
SY
ST
EM
R
EP
LA
C
EM
EN
T
C o ll ie r C t.
M ar co
I sl an d
FL
C O
RK
SC
RE
W
R D
SU
IT
E
ES
T
ER
O
FL
Fl o ri d a
C o A
Je ff re y
A Je n k in s, F
L
PE
P:
-2
-5
F:
-2
-5
JM
A
JE
N
K
IN
S M
A A
G A
SS
O C
IA
T
ES
LL
C
SYMBOL LEGEND,
ABBREVIATIONS AND
NOTES
E-1
ELECTRICAL SYMBOL LEGEND
SYMBOL DESCRIPTION
DUPLEX RECEPTACLE - 125V
PANEL AND CIRCUIT NUMBER INDICATED
WL = WET LOCATION COVER
FB-15
GFCI DUPLEX RECEPTACLE - 125V
TRANSFORMER - SINGLE PHASE
ELECTRICAL SHEET INDEX
SHEET ID SHEET TITLE SHEET SCALE
E-1 SYMBOL LEGEND, ABBREVIATIONS AND NOTES NO SCALE
E-2 SPECIFICATIONS NO SCALE
E-3 ELECTRICAL PLANS 1/8" = 1'-0"
E-4 RISER AND SCHEDULES NO SCALE
GENERAL ELECTRICAL NOTES
A. THE ELECTRICAL CONTRACTOR SHALL VERIFY THE EXACT
LOCATION OF FUEL STORAGE AND DISPENSING EQUIPMENT WITH
THE INSTALLING CONTRACTORS, AND MAKE FINAL CONNECTIONS
TO THE EQUIPMENT. EXACT ELECTRICAL REQUIREMENTS SHALL
BE VERIFIED IN THE FIELD WITH THE EQUIPMENT NAMEPLATE
DATA. THE ELECTRICAL CONTRACTOR SHALL MAKE
APPROPRIATE ADJUSTMENTS TO WIRE AND OVERCURRENT
PROTECTION DEVICE SIZES IN ACCORDANCE WITH THE
NAMEPLATE DATA.
B. ELECTRICAL EQUIPMENT ENCLOSURES, SUCH AS FOR
DISCONNECTS LOCATED OUTDOORS SHALL HAVE NEMA-4X RATED
ENCLOSURES, UON.
C. PROVIDE NAMEPLATES ON THE EXTERIOR OF ALL ELECTRICAL
EQUIPMENT, INCLUDING EXISTING PANELBOARDS LOCATED
WITHIN THE BUILDING AND NEW DISCONNECTS.
D. ARC FLASH WARNING LABELS SHALL BE PROVIDED FOR
ELECTRICAL EQUIPMENT, SUCH AS EXISTING PANELBOARDS
LOCATED WITHING THE BUILDING AND CONTROL PANELS, AS
REQUIRED BY NEC 110.16. THE WARNING LABELS SHALL BE
MINIMUM 2" X 3", PRE PRINTED TYPE BY A LABEL MANUFACTURER,
SUITABLE FOR THE ENVIRONMENT WHERE INSTALLED AND
MEETING NEC 110.21(B), NFPA AND OSHA REQUIREMENTS.
E. PROVIDE PROTECTION AGAINST DISSIMILAR METALS. ALL WIRING
TERMINATIONS SHALL BE MADE USING COMPONENTS LISTED FOR
THE APPLICATION AND MATERIALS USED.
F. ALL 120V, 15 AND 20 AMP BRANCH CIRCUITS SERVING OUTLETS
LOCATED BELOW THE FLOOD ELEVATION, AND ALL 120V, 15 AND
20 AMP BRANCH CIRCUITS WITH WIRING LOCATED BELOW THE
FLOOD ELEVATION SHALL BE PROTECTED BY GFCI CIRCUIT
BREAKERS.
G. SPARE CIRCUIT BREAKERS IN PANELBOARDS SHALL BE
IDENTIFIED AS SPARE ON THE PANEL DIRECTORY AND LEFT IN
THE OFF (OPEN) POSITION.
H. PROVIDE COMPLETE, UPDATED, TYPED CIRCUIT DIRECTORIES,
INCLUDING THE DATE THE DIRECTORIES WERE COMPLETED, FOR
EXISTING PANELBOARDS WITH NEW OR REVISED CIRCUITS. ALL
NEW CIRCUIT BREAKERS PROVIDED TO BE INSTALLED IN ANY
EXISTING PANEL SHALL MATCH THE EXISTING EQUIPMENT
MANUFACTURER, BE LISTED FOR USE IN THE EXISTING
EQUIPMENT AND HAVE A SHORT CIRCUIT RATING TO MEET OR
EXCEED THE RATING OF THE EXISTING EQUIPMENT.
APPLICABLE CODES AND STANDARDS:
ALL ELECTRICAL WORK SHALL BE GOVERNED AND INSTALLED IN
COMPLIANCE WITH THE APPLICABLE PROVISIONS OF THE FOLLOWING
CODES AND STANDARDS:
- FLORIDA BUILDING CODE - 2023 8TH EDITION
- FLORIDA FIRE PREVENTION CODE - 8TH EDITION (2023)
- NFPA 30: FLAMMABLE AND COMBUSTIBLE LIQUIDS CODE - 2021
EDITION
- NFPA 30A: CODE FOR MOTOR FUEL DISPENSING FACILITIES AND
REPAIR GARAGES - 2021 EDITION
- NFPA-70: NATIONAL ELECTRICAL CODE - 2020 EDITION
CODES AND STANDARDS
ABBREVIATIONS
3W THREE WIRE
A AMPERE
AC ALTERNATING CURRENT
ADA AMERICANS WITH DISABILITIES ACT
AFF ABOVE FINISHED FLOOR (HEIGHT TO CENTER)
AFG ABOVE FINISHED GRADE
AHJ AUTHORITY HAVING JURISDICTION
AHU AIR HANDLING UNIT
AIC AMPERE INTERRUPTING CAPACITY
AL ALUMINUM
ANSI AMERICAN NATIONAL STANDARDS INSTITUTE
AWG AMERICAN WIRE GAUGE
C CELSIUS
CB CIRCUIT BREAKER
CCTV CLOSED CIRCUIT TELEVISION
CKT CIRCUIT
CLG CEILING
CT CURRENT TRANSFORMER
CU COPPER
DC DIRECT CURRENT
DEMO DEMOLITION
DL DAMP LOCATION
EA EACH
EC ELECTRICAL CONTRACTOR
EF EXHAUST FAN
EH ELECTRIC HEATER
EM EMERGENCY
EMT ELECTRICAL METALLIC TUBING
EPO EMERGENCY POWER OFF
ETR EXISTING TO REMAIN
EWC ELECTRIC WATER COOLER
EWH ELECTRIC WATER HEATER
F FAHRENHEIT
FLA FULL LOAD AMPS
G GROUND
GC GENERAL CONTRACTOR
GFCI GROUND FAULT CIRCUIT INTERRUPTER (PERSONNEL)
GF-E GROUND FAULT CIRCUIT INTERRUPTER (EQUIPMENT)
GFP GROUND FAULT PROTECTION
HP HORSEPOWER
HVAC HEATING, VENTILATING, AND AIR CONDITIONING
J-BOX JUNCTION BOX
K KELVIN
KCMIL KILO-CIRCULAR MILS
KVA KILOVOLT AMPERES
KW KILOWATTS
KWC KILOWATTS CONNECTED
KWD KILOWATTS DEMAND
L-OFF CIRCUIT BREAKER LOCK IN OPEN POSITION
L-ON CIRCUIT BREAKER LOCK IN CLOSED POSITION
LTG LIGHTING
MC MECHANICAL CONTRACTOR
MCB MAIN CIRCUIT BREAKER
MLO MAIN LUGS ONLY
MOD MOTOR OPERATED DAMPER
MTS MANUAL TRANSFER SWITCH
NEC NATIONAL ELECTRICAL CODE
NEMA NATIONAL ELECTRICAL MANUFACTURERS ASSOCIATION
NFPA NATIONAL FIRE PROTECTION ASSOCIATION
NIC NOT IN CONTRACT
NTS NOT TO SCALE
P POLE
PA PUBLIC ADDRESS
PH PHASE
PT POTENTIAL TRANSFORMER
QTY QUANTITY
REC RECEPTACLE
RMC RIGID METALLIC CONDUIT
RNC RIGID NON-METALLIC CONDUIT
RP RELAY PANEL
RR REMOVE AND RELOCATE
SCA SHORT CIRCUIT CURRENT AVAILABLE
SPD SURGE PROTECTION DEVICE
ST SHUNT TRIP
TTB TELEPHONE TERMINAL BOARD
TV TELEVISION
TYP TYPICAL
UL UNDERWRITERS LABORATORIES
UON UNLESS OTHERWISE NOTED
UPS UNINTERRUPTIBLE POWER SUPPLY
V VOLT
VA VOLT AMPERE
VAR VOLT AMPERE REACTIVE
W WATT
WAP WIRELESS ACCESS POINT
WL WET LOCATION
WP WEATHERPROOF
GENERAL DEMOLITION NOTES
A. ALL EXISTING DEVICES AND EQUIPMENT SHOWN ARE THE RESULT
OF FIELD INSPECTIONS AND ARE NOT INTENDED TO REPRESENT
EXACT FIELD CONDITIONS, BUT ARE INTENDED TO REPRESENT
THE EXTENT OF ELECTRICAL DEMOLITION. THE ELECTRICAL
CONTRACTOR SHALL FIELD VERIFY THE EXTENT OF DEMOLITION
PRIOR TO COMMENCEMENT OF WORK.
B. EXISTING CONDUIT AND WIRING TO REMAIN SHALL BE PROTECTED
DURING DEMOLITION. RELOCATE AND REROUTE WHERE
REQUIRED TO ALLOW FOR DEMOLITION.
C. MAINTAIN CONTINUITY OF BRANCH CIRCUITS TO ALL DEVICES AND
FIXTURES SHOWN TO REMAIN (ETR).
D. FOR ALL EQUIPMENT TO BE REMOVED (DEMO), REMOVE RELATED
WIRING COMPLETE TO SOURCE. RE-LABEL EXISTING CIRCUIT
BREAKERS AS "SPARE" WHEN LOAD IS COMPLETELY REMOVED OR
REVISE LABEL ON PANEL DIRECTORY ACCORDINGLY.
HOMERUN TO PANEL 'A', CIRCUIT NUMBER 1
A-1
THE SCOPE OF WORK INCLUDED WITHIN THE ELECTRICAL DRAWINGS
IS TO PROVIDE POWER FOR THE NEW FUEL SYSTEM EQUIPMENT
FROM THE EXISTING ELECTRICAL PANEL, INCLUDING PROVIDING NEW
CIRCUIT BREAKERS WITHIN THE EXISTING PANEL, AS WELL AS NEW
DISCONNECTS, CONDUIT AND WIRING REQUIRED FOR A COMPLETE
INSTALLATION.
SCOPE OF WORK
JUNCTION BOXJ
JUNCTION BOX - WALLJ
EMERGENCY POWER OFF PUSHBUTTON
E
CIRCUIT BREAKER DISCONNECT
MOTOR
PANELBOARD
METER
RISER SYMBOLS
GROUND
PANELBOARD - MAIN LUGS ONLY OR MAIN CIRCUIT
BREAKER
CIRCUIT BREAKER DISCONNECT
SIZE AS INDICATED
60A
METER
CT = CT TYPE METERM
SERVICE TRANSFORMER
CIRCUIT BREAKER
SIZE AS INDICATED
60A
DATA OUTLET - WALL
AutoCAD SHX Text
REVISION
AutoCAD SHX Text
DATE
AutoCAD SHX Text
NO.
AutoCAD SHX Text
ISSUE:
AutoCAD SHX Text
ISSUE DATE:
AutoCAD SHX Text
DRAWN BY:
AutoCAD SHX Text
CHECKED BY:
AutoCAD SHX Text
PROJECT NUMBER:
AutoCAD SHX Text
PERMIT SET
AutoCAD SHX Text 05.06.2024
AutoCAD SHX Text
CCO23002
AutoCAD SHX Text
PERMIT SET
AutoCAD SHX Text 05.06.2024
AutoCAD SHX Text
RMR
AutoCAD SHX Text
JAJ
LL
IE
R C
O U
N T
Y C
A X A
M B A
S M
A R
IN
A
F U
EL
SY
ST
EM
R
EP
LA
C
EM
EN
T
C o ll ie r C t.
M ar co
I sl an d
FL
C O
RK
SC
RE
W
R D
SU
IT
E
ES
T
ER
O
FL
Fl o ri d a
C o A
Je ff re y
A Je n k in s, F
L
PE
P:
-2
-5
F:
-2
-5
JM
A
JE
N
K
IN
S M
A A
G A
SS
O C
IA
T
ES
LL
C
SPECIFICATIONS
E-2
GENERAL PROVISIONS
1. PROVISIONS OF THIS SPECIFICATION APPLY TO ALL WORK OF THE
ELECTRICAL CONTRACTOR. GENERAL CONDITIONS,
SUPPLEMENTARY CONDITIONS, AND GENERAL REQUIREMENTS OF
THE ARCHITECTURAL SPECIFICATIONS APPLY TO ALL WORK OF
THE ELECTRICAL CONTRACTOR. FUEL SYSTEM EQUIPMENT,
ELECTRICAL, AND ALL OTHER DRAWINGS AS WELL AS THE
SPECIFICATIONS FOR ALL OTHER DIVISIONS SHALL BE DEFINED
AS THE CONTRACT DOCUMENTS. CONTRACTOR SHALL REVIEW
ENTIRE SET OF CONTRACT DOCUMENTS PRIOR TO BIDDING FOR
ADDITIONAL PROJECT REQUIREMENTS WHICH MAY AFFECT WORK
UNDER THIS DIVISION.
2. VISIT THE SITE NO LATER THAN TWO (2) WEEKS PRIOR TO BIDDING
FOR FAMILIARIZATION WITH LOCAL CONDITIONS. IMMEDIATELY
NOTIFY THE ARCHITECT/ENGINEER OF ANY DEVIATIONS BETWEEN
BID DOCUMENTS AND LOCAL CONDITIONS. FAILURE TO NOTIFY
ASSUMES THAT ANY COST FOR CORRECTING TO LOCAL
CONDITIONS IS INCLUDED IN THE BID.
3. DEFINITIONS AS APPLIED TO THIS SPECIFICATION ARE AS
FOLLOWS:
3.1. "FURNISH" SHALL MEAN TO SUPPLY AND DELIVER TO THE
PROJECT SITE, READY FOR UNLOADING, UNPACKING,
ASSEMBLY, INSTALLATION AND SIMILAR OPERATIONS.
3.2. "INSTALL" SHALL MEAN WORK WHICH INCLUDES THE ACTUAL
UNLOADING, UNPACKING, ASSEMBLY, ERECTING, PLACING,
ANCHORING, APPLYING, FINISHING, CURING, PROTECTING,
CLEANING AND SIMILAR OPERATIONS.
3.3. "PROVIDE SHALL MEAN TO FURNISH AND INSTALL, COMPLETE
AND READY FOR THE INTENDED USE.
3.4. "EQUAL" SHALL MEAN TO MEET OR EXCEED THE STANDARDS
OF THE SPECIFIED PRODUCT OR LISTED MANUFACTURER.
3.5. "TYPICAL" IS NOTED WHERE WORK APPLIES TO A PATTERN
OR TYPE OF EQUIPMENT OR MATERIAL WHICH SHALL BE
FOLLOWED UNDER SIMILAR CIRCUMSTANCES, USUALLY IN
THE SAME TYPE OF SPACE.
4. THE INTENT OF THE DRAWINGS AND SPECIFICATIONS IS TO
ESTABLISH TYPE AND QUALITY OF MATERIALS; SIZES AND
CAPACITIES OF COMPONENTS; AND A GENERAL LAYOUT OF
LOCATION OF COMPONENTS THAT COMPRISE THE ELECTRICAL
SYSTEMS. ANY DEVIATIONS FROM THE DRAWINGS AND
SPECIFICATIONS MUST BE THROUGH A DULY ISSUED ADDENDUM.
THE BASE BID MUST REFLECT SYSTEMS AS INDICATED OR
REQUIRED BY THE CONTRACT DOCUMENTS.
5. PLANS AND SPECIFICATIONS SUPPLEMENT EACH OTHER AND
REQUIRE THE CONTRACTOR PROVIDE IN THEIR BID: ALL LABOR,
TOOLS, MATERIALS, PAINT, TRANSPORTATION, TAXES, RELATED
ITEMS, ETC., ESSENTIAL FOR INSTALLATION OF WORK; ALL
SYSTEMS COMPLETE AND LEFT IN GOOD OPERATING CONDITION;
ANY APPARATUS, APPLIANCE, MATERIAL OR WORK NOT SHOWN
ON DRAWINGS BUT MENTIONED IN SPECIFICATIONS, OR VICE
VERSA; ANY ACCESSORIES, REASONABLY INFERABLE FROM
DRAWINGS AND SPECIFICATIONS, NECESSARY TO MAKE WORK
COMPLETE AND READY FOR OPERATION.
6. WORK SHALL BE INSTALLED IN ACCORDANCE WITH ALL
APPLICABLE PROVISIONS OF LOCAL AND STATE CODES, AS WELL
AS THE NATIONAL ELECTRICAL CODE (NEC), AS INTERPRETED BY
THE LOCAL AUTHORITY HAVING JURISDICTION.
7. ALL DISTRIBUTION EQUIPMENT, DEVICES, LIGHTING FIXTURES,
CONTROL DEVICES AND EQUIPMENT, AND ALL OTHER SPECIFIED
ELECTRICAL EQUIPMENT SHALL BE INSTALLED AS REQUIRED BY
THE MANUFACTURER'S INSTALLATION INSTRUCTIONS.
8. THE INSTALLATION SHALL BE MADE IN A NEAT AND WORKMANLIKE
MANNER BY PERSONNEL LICENSED AND SKILLED IN THE TRADE
AND SHALL BE DONE UNDER THE SUPERVISION OF A MASTER
ELECTRICIAN LICENSED TO DO WORK IN THE STATE OF FLORIDA.
9. THE DRAWINGS ARE ESSENTIALLY DIAGRAMMATIC AND ARE
INTENDED TO GENERALLY INDICATE SIZE, CAPACITY AND
LOCATION, HOWEVER, NOT EXACT DETAILS OR ARRANGEMENT OF
CONSTRUCTION. CONTRACT DOCUMENTS SHALL BE EXAMINED
SO THAT ALL DETAILS OF THE PROJECT ARE UNDERSTOOD AND
WORK PROCEDURES KNOWN BEFORE BID AND INSTALLATION.
EXACT LOCATIONS AND DETAILS SHALL BE OBTAINED FROM
DIMENSIONED ARCHITECTURAL AND STRUCTURAL DRAWINGS,
HOWEVER DIMENSIONS SHOWN ON DRAWINGS SHALL NOT TAKE
PRECEDENCE OVER FIELD LAYOUT DIMENSIONS.
10. MISCELLANEOUS EQUIPMENT (PULL BOXES, JUNCTION BOXES,
FITTINGS, EXPANSION JOINT COUPLINGS, ETC) NECESSARY TO
COMPLETE THE WORK SHALL BE FURNISHED AND INSTALLED
EVEN THOUGH NOT SPECIFICALLY SHOWN ON PLANS.
11. ALL MATERIALS AND LABOR SHALL BE UNCONDITIONALLY
WARRANTED FOR A PERIOD OF ONE (1) YEAR FROM DATE OF
SUBSTANTIAL COMPLETION. SPECIFIC MANUFACTURER'S
EQUIPMENT WARRANTIES IN EXCESS OF ONE (1) YEAR SHALL
TAKE PRECEDENCE. MANUFACTURER'S WARRANTIES SHALL BE
PROVIDED WHENEVER AVAILABLE AND POSSIBLE. ALL
EQUIPMENT AND MATERIALS SHALL BE NEW AND UNUSED FROM
THE FACTORY AND SHALL BE UL LISTED FOR THE APPLICATION.
MINOR ADJUSTMENTS OR ALIGNMENTS REQUIRED FOR PROPER
OPERATION ARE ACCEPTABLE.
12. PROVIDE PRODUCT DATA AND SHOP DRAWINGS FOR: WIRING
DEVICES, DISCONNECT SWITCHES, AND ALL OTHER SPECIFIED
SYSTEMS AND COMPONENTS.
13. IDENTIFICATION OF ELECTRICAL SYSTEMS AND EQUIPMENT SHALL
BE AS FOLLOWS: PANELBOARDS, DISCONNECT SWITCHES, ETC.,
PROVIDE ENGRAVED LAMINATED PLASTIC PLATES WITH
LETTERING. CHARACTERS SHALL BE MINIMUM 1/2" AND THE
INSCRIPTION SHALL BE CENTERED ON THE PLATE, DOOR OR
SECTION. ATTACH PLATES WITH SELF-TAPPING SCREWS OR 3M
CP-5200 ADHESIVE. NAMEPLATES SHALL INCLUDE THE
EQUIPMENT DESIGNATION, VOLTAGE AND PHASE, THE SOURCE
PANELBOARD, AND THE LOAD SERVED (FOR DISCONNECT
SWITCHES. ALL PANELBOARDS SUPPLIED BY A FEEDER SHALL BE
MARKED TO INDICATE EACH DEVICE OR EQUIPMENT WHERE THE
POWER ORIGINATES AS REQUIRED BY NEC 408.4(B). NAMEPLATES
SHALL HAVE WHITE BACKGROUND WITH BLACK TEXT.
14. THE OUTSIDE OF COVERPLATES FOR JUNCTION BOXES (INSIDE OF
COVERPLATES FOR JUNCTION BOXES LOCATED IN FINISHED
AREAS) SHALL BE PERMANENTLY MARKED TO INDICATE THE
PANEL NAME AND CIRCUIT NUMBER, OR THE SYSTEM.
15. PROVIDE EXTERIOR SITE ELECTRICAL EQUIPMENT AND
MATERIALS AS DESCRIBED ON THE CONTRACT DOCUMENTS,
INCLUDING EXCAVATION, TRENCHING AND BACKFILL.
16. ANY EXISTING UTILITIES THAT ARE SHOWN ON THE DRAWINGS OR
THE LOCATION OF WHICH IS MADE KNOWN TO THE CONTRACTOR
PRIOR TO EXCAVATION SHALL BE PROTECTED FROM DAMAGE
DURING THE EXCAVATION AND BACKFILLING OF TRENCHES, AND
IF DAMAGED SHALL BE REPAIRED BY THE CONTRACTOR AT THEIR
EXPENSE.
17. THE CONTRACTOR SHALL BE RESPONSIBLE FOR ALL NECESSARY
CUTTING AND PATCHING REQUIRED IN CONNECTION WITH THIS
WORK. CUTTING OF STRUCTURAL MEMBERS AND FINISHED
SURFACES IS NOT PERMITTED WITHOUT PERMISSION FROM THE
ARCHITECT OR STRUCTURAL ENGINEER.
18. AFTER INSTALLATION, THE CONTRACTOR SHALL TEST FOR
GROUNDS, SHORT CIRCUITS AND PROPER OPERATION OF EACH
SYSTEM AND RELATED WIRING. INSULATION RESISTANCE TESTS
SHALL BE MADE ON THE ELECTRICAL SYSTEM WITH AN APPROVED
MEGOHMMETER. A GROUND CONTINUITY TEST SHALL BE MADE
ON THE ENTIRE GROUNDING SYSTEM FROM THE SERVICE TO
EVERY NEW OUTLET.
19. THE CONTRACTOR SHALL CLEAR AWAY ALL DEBRIS, SURPLUS
MATERIALS, ETC., RESULTING FROM THIS WORK AND
OPERATIONS, LEAVING THE JOB AND EQUIPMENT FURNISHED
UNDER THIS CONTRACT IN A CLEAN AND FIRST-CLASS CONDITION.
20. THE CONTRACTOR SHALL INSURE THAT PERSONNEL AS
DESIGNATED BY THE OWNER SHALL BE INSTRUCTED, TO THE
OWNER'S SATISFACTION, IN THE USE AND MAINTENANCE OF
ELECTRICAL EQUIPMENT AND SYSTEMS DESCRIBED IN THESE
DRAWINGS AND SPECIFICATIONS, BY AUTHORIZED
MANUFACTURER'S PERSONNEL.
21. FURNISH AS-BUILT DRAWINGS FOR ELECTRIC POWER SYSTEMS
WITHIN 30 DAYS OF SYSTEM ACCEPTANCE TO BUILDING OWNER.
FURNISH OPERATION AND MAINTENANCE INSTRUCTIONS FOR
ELECTRICAL SYSTEMS AND EQUIPMENT TO THE BUILDING OWNER
OR DESIGNATED REPRESENTATIVE.
WIRE AND CABLE
1. WIRE AND CABLE FOR BRANCH CIRCUITS AND FEEDERS SHALL BE
600 VOLT WITH MAXIMUM OPERATING TEMPERATURE OF 90°C,
TYPE THHN OR THWN-2. TYPE XHHW SHALL ALSO BE
ACCEPTABLE FOR FEEDERS. ALL CONDUCTORS SHALL BE
COPPER EXCEPT AS NOTED OTHERWISE ON THE DRAWINGS.
MINIMUM SIZE SHALL BE #12 AWG FOR POWER WIRING, AND #14
FOR CONTROL WIRING. ALL 600 VOLT CONDUCTORS SHALL BE
INSTALLED IN CONDUIT.
WIRE AND CABLE SHALL BE IDENTIFIED IN ACCORDANCE WITH THE
NATIONAL ELECTRICAL CODE. FEEDER CONDUCTORS SHALL
BE IDENTIFIED BY COLORED INSULATION OR COLORED TAPE
AT THE TERMINALS.
2. WHERE MORE THAN ONE NEUTRAL CONDUCTOR ASSOCIATED
WITH DIFFERENT CIRCUITS IS LOCATED IN AN ENCLOSURE,
NEUTRAL CONDUCTORS OF EACH CIRCUIT SHALL BE IDENTIFIED
OR GROUPED TO CORRESPOND WITH THE UNGROUNDED CIRCUIT
CONDUCTOR(S) BY WIRE MARKERS, CABLE TIES, OR SIMILAR
MEANS WITHIN THE ENCLOSURE AS REQUIRED BY NEC 200.4(B).
3. FEEDER AND BRANCH CIRCUIT CONDUCTORS SHALL BE COLOR
CODED AS FOLLOWS:
3.1. 240/120V, 1 PH, 3W SYSTEM:
PHASE A - BLACK
PHASE B - RED
NEUTRAL - WHITE
GROUNDING AND BONDING
1. INSTALL INSULATED EQUIPMENT GROUNDING CONDUCTORS WITH
ALL FEEDERS AND BRANCH CIRCUITS.
2. BOND ALL ELECTRICAL SYSTEM RACEWAYS, PANELS, METAL
BOXES, WIRING DEVICES, MOTORS, AND OTHER EXPOSED
NON-CURRENT CARRYING METAL PARTS OF ELECTRICAL
EQUIPMENT IN ACCORDANCE WITH NEC ARTICLE 250.
3. INSTALL BONDING JUMPERS ACROSS ALL CONDUIT EXPANSION
FITTINGS.
4. ROUTE GROUNDING CONDUCTORS ALONG THE SHORTEST AND
STRAIGHTEST PATHS POSSIBLE UNLESS OTHERWISE NOTED OR
REQUIRED BY NEC ARTICLE 250. AVOID OBSTRUCTING ACCESS
AND AVOID PLACING GROUNDING CONDUCTORS WHERE THEY
MAY BE SUBJECTED TO STRAIN, IMPACT, OR DAMAGE.
5. ALL GROUNDING SYSTEMS SHALL BE TESTED AND DOCUMENTED
IN FULL ACCORDANCE WITH IEEE STANDARD 81 "IEEE GUIDE FOR
MEASURING EARTH RESISTIVITY, GROUND IMPEDANCE AND
EARTH SURFACE POTENTIALS OF A GROUND SYSTEM" AND THE
NETA ATS-2021 SPECIFICATIONS.
RACEWAYS AND FITTINGS
1. ALL CONDUITS AND FITTINGS SHALL BE CONCEALED
THROUGHOUT THE BUILDING, EXCEPT UNFINISHED AREAS. ALL
CONDUIT RUNS SHALL BE PARALLEL OR PERPENDICULAR TO
BUILDING GRID LINES AND SHALL GENERALLY FOLLOW THE
DIRECTION OF MAJOR FRAMING JOISTS OR FURRING. ALL
CONDUITS AND RACEWAYS SHALL BE SECURELY SUPPORTED BY
GALVANIZED STEEL SUPPORTS. CONDUIT SHALL BE CAPPED OR
PLUGGED DURING CONSTRUCTION TO KEEP OUT FOREIGN
MATERIALS AND MOISTURE.
2. RIGID GALVANIZED STEEL CONDUIT OR INTERMEDIATE METALLIC
CONDUIT SHALL BE PROVIDED IN DAMP OR WET LOCATIONS, OR
WHERE SUBJECT TO PHYSICAL ABUSE. PVC SCHEDULE 40
CONDUIT SHALL BE PROVIDED IN OR BELOW SLABS ON GRADE, IN
ALL EXTERIOR UNDERGROUND APPLICATIONS, WHERE NOT
SUBJECT TO PHYSICAL ABUSE. ALL OTHER INTERIOR CONDUITS
SHALL BE ELECTRICAL METALLIC TUBING (EMT), UON.
3. ALL UNDERGROUND CONDUIT INSTALLED BETWEEN THE
BUILDING, ABOVE GROUND FUEL STORAGE TANK, AND FUEL
DISPENSERS SHALL BE THREADED RMC CONDUIT AS REQUIRED
BY NEC 514.8. PROVIDE LISTED SEAL OFF FITTINGS AT FUEL
DISPENSERS, THE ABOVE GROUND FUEL STORAGE TANK AND AT
BOUNDARIES OF CLASSIFIED LOCATIONS. THE SEAL OFF FITTINGS
SHALL BE THE FIRST FITTINGS AFTER THE CONDUIT EMERGES
FROM THE EARTH OR CONCRETE AS REQUIRED BY NEC 514.9.
4. ALL CONDUITS AND FITTINGS SHALL BE UL LISTED FOR THE
APPLICATION AND SHALL BE 3/4" TRADE SIZE, MINIMUM, UNLESS
OTHERWISE NOTED ON THE DRAWINGS. PROVIDE STEEL SET
SCREW FITTINGS FOR ALL EMT CONDUIT.
5. COORDINATE EXACT ROUTING AND ELEVATION OF
UNDERGROUND CONDUIT WITH ALL OTHER TRADES PRIOR TO
EXCAVATION AND INSTALLATION.
6. PROVIDE LISTED EXPANSION/DEFLECTION FITTINGS AT ALL
LOCATIONS WHERE A RACEWAY CROSSES A STRUCTURAL JOINT
INTENDED FOR EXPANSION, CONTRACTION OR DEFLECTION AS
REQUIRED BY NEC 300.4(H), OR WHERE NECESSARY TO
COMPENSATE FOR THERMAL EXPANSION, DEFLECTION AND
CONTRACTION AS REQUIRED BY NEC 300.7(B).
7. CONDUITS PASSING FROM THE EXTERIOR TO THE INTERIOR OF A
BUILDING SHALL BE FILLED WITH AN APPROVED MATERIAL TO
PREVENT THE CIRCULATION OF WARM AIR TO A COLDER SECTION
OF THE RACEWAY IN ACCORDANCE WITH NEC 300.7(A).
8. CONDUITS SHALL BE CONTINUOUS AND SECURED TO ALL BOXES
IN SUCH A MANNER THAT EACH CONDUIT SYSTEM IS
ELECTRICALLY CONTINUOUS FROM THE POINT OF SERVICE TO
ALL DEVICE BOXES. THE ACTUAL ROUTING OF CONDUIT SHALL BE
INSTALLED TO SUIT THE FIELD CONDITIONS.
ELECTRICAL BOXES
1. OUTLET AND JUNCTION BOXES FOR INTERIOR USE SHALL BE UL
LISTED GALVANIZED PRESSED STEEL TYPE, 4"X4"X2" DEEP
MINIMUM, AND SHALL BE PROVIDED WITH COVERPLATES
SUITABLE FOR THE APPLICATION. ALL OUTLET BOXES SHALL BE
CONCEALED WHEREVER POSSIBLE THROUGHOUT THE BUILDING,
UON. 4" SQUARE AND 4-11/16" SQUARE BOXES SHALL BE FITTED
WITH GALVANIZED STEEL PLASTER COVERS OR RINGS DESIGNED
FOR FLUSH INSTALLATION.
2. OUTLET BOXES FOR EXTERIOR USE SHALL BE CAST OR
MALLEABLE IRON TYPE WITH THREADED HUBS AND
WEATHERPROOF COVERS AND FITTINGS. CAST BOXES SHALL BE
TYPE FS.
3. ALL BOXES SHALL BE RIGIDLY SUPPORTED FROM THE BUILDING
STRUCTURE INDEPENDENT OF THE CONDUIT SYSTEM. BOX
STABILIZERS SHALL BE PROVIDED TO PROPERLY SUPPORT BOXES
IN METAL STUD CONSTRUCTION.
WIRING DEVICES
1. ALL DEVICES AND COVERPLATES SHALL BE PRODUCTS OF ONE
MANUFACTURER WHEREVER POSSIBLE. WIRING DEVICES SHALL
BE STANDARD TYPE MANUFACTURED BY LEVITON, OR
EQUIVALENT BY HUBBELL, COOPER, OR PASS AND SEYMOUR.
2. DUPLEX RECEPTACLES SHALL BE 20 AMPERES, 125 VOLTS AC,
NEMA 5-20R - LEVITON INDUSTRIAL SPECIFICATION GRADE 5362
SERIES. PROVIDE GROUND FAULT CIRCUIT INTERRUPTING (GFCI)
TYPE WHERE INDICATED ON THE DRAWINGS.
3. PROVIDE COVERPLATES FOR ALL WIRING DEVICES.
COVERPLATES FOR FLUSH MOUNTED INDOOR DEVICES SHALL BE
SMOOTH HIGH IMPACT THERMOPLASTIC NYLON WITH COLOR TO
MATCH DEVICES. COVERPLATES FOR SURFACE MOUNTED
INDOOR DEVICES IN UNFINISHED AREAS SHALL BE RAISED
GALVANIZED STEEL INDUSTRIAL TYPE WITH COVER-MOUNTED
DEVICES.
4. ALL RECEPTACLES SHALL BE WHITE, VERIFY COLOR WITH THE
OWNER PRIOR TO PROCUREMENT OF THE DEVICES.
5. ALL DEVICES SHALL BE SECURED WITH MORE THAN A SINGLE
SCREW.
DISCONNECTS
1. SAFETY SWITCHES SHALL BE HEAVY-DUTY FUSIBLE OR
NON-FUSIBLE TYPE AS SHOWN ON THE DRAWINGS.
2. ENCLOSED CIRCUIT BREAKERS SHALL BE MOLDED CASE CIRCUIT
BREAKERS MOUNTED IN INDIVIDUAL ENCLOSURES. CIRCUIT
BREAKERS SHALL BE THERMAL-MAGNETIC TYPE, WITH TRIP
RATINGS AS SHOWN ON THE DRAWINGS. THE SHORT CIRCUIT
RATING SHALL NOT BE LESS THAN THE REQUIRED RATING SHOWN
ON THE DRAWINGS.
3. SAFETY SWITCHES AND ENCLOSED CIRCUIT BREAKERS SHALL BE
CAPABLE OF BEING LOCKED IN THE OPEN POSITION.
4. SAFETY SWITCHES AND ENCLOSED CIRCUIT BREAKERS SHALL BE
MANUFACTURED BY SQUARE D, SIEMENS, ABB OR EATON CUTLER
HAMMER.
AutoCAD SHX Text
REVISION
AutoCAD SHX Text
DATE
AutoCAD SHX Text
NO.
AutoCAD SHX Text
ISSUE:
AutoCAD SHX Text
ISSUE DATE:
AutoCAD SHX Text
DRAWN BY:
AutoCAD SHX Text
CHECKED BY:
AutoCAD SHX Text
PROJECT NUMBER:
AutoCAD SHX Text
PERMIT SET
AutoCAD SHX Text 05.06.2024
AutoCAD SHX Text
CCO23002
AutoCAD SHX Text
PERMIT SET
AutoCAD SHX Text 05.06.2024
AutoCAD SHX Text
RMR
EE
DEMO
E
FB-14,16
E-3
RESTROOMS
ELECTRICAL
ROOM
FB-20
PADMOUNT SERVICE
TRANSFORMER (ETR)
LIFT STATION SERVICE
PANEL AND METER (ETR)
BOAT LIFT SERVICE
DISCONNECT AND
METER (ETR)
BUILDING SERVICE
DISCONNECT AND
METER (ETR)
J
FB-15 J
FB-18
FB-9
PANEL F (ETR)
PANEL FB (ETR)
FB-11
ELECTRICAL
ROOM
C O
LL
IE
R C
O U
N T
Y C
A X A
M B A
S M
A R
IN
A
F U
EL
SY
ST
EM
R
EP
LA
C
EM
EN
T
C o ll ie r C t.
M ar co
I sl an d
FL
C O
RK
SC
RE
W
R D
SU
IT
E
ES
T
ER
O
FL
Fl o ri d a
C o A
Je ff re y
A Je n k in s, F
L
PE
P:
-2
-5
F:
-2
-5
JM
A
JE
N
K
IN
S M
A A
G A
SS
O C
IA
T
ES
LL
C
ELECTRICAL PLANS
E-3
SCALE: 1/8" = 1'-0" 0 8' 16'4'
NORTH
SITE ELECTRICAL PLAN
A. PROVIDE A CLEARLY IDENTIFIED EMERGENCY SHUTOFF DEVICE
OR DISCONNECT BETWEEN 20FT AND 100FT FROM THE
DISPENSING DEVICE SERVED. PROVIDE LABEL AT DEVICE,
"EMERGENCY FUEL SHUTOFF". ELECTRICAL SHUTOFF DEVICES
SHALL BE INSTALLED AND CAPABLE OF MEETING ALL
REQUIREMENTS OF NFPA 30A SECTION 6.7.
B. REFER TO NFPA 30A FIGURE 8.3.3 AND TABLE 8.3.3 FOR AVAILABLE
INSTALL LOCATIONS OF ELECTRICAL WIRING AND EQUIPMENT.
ELECTRICAL WIRING/CONDUITS TO BE CLASS 1, DIVISION 1 OR
CLASS 1, DIVISION 2, PER THIS TABLE.
C. ALL ELECTRICAL WIRING FOR POWER SHALL BE PROTECTED
FROM A RELEASE FROM THE FUEL PIPING SYSTEM.
D. ALL UNDERGROUND CONDUIT INSTALLED BETWEEN THE
BUILDING, THE ABOVE GROUND FUEL STORAGE TANK, AND FUEL
DISPENSERS SHALL BE THREADED RMC CONDUIT AS REQUIRED
BY NEC 514.8. PROVIDE LISTED SEAL OFF FITTINGS AT FUEL
DISPENSERS, THE ABOVE GROUND FUEL STORAGE TANK AND AT
BOUNDARIES OF CLASSIFIED LOCATIONS. THE SEAL OFF FITTINGS
SHALL BE THE FIRST FITTINGS AFTER THE CONDUIT EMERGES
FROM THE EARTH OR CONCRETE AS REQUIRED BY NEC 514.9.
SHEET KEYNOTES
1. EXISTING EMERGENCY SHUT OFF SHALL BE REMOVED. REMOVE
WIRING COMPLETE TO SOURCE SHUNT TRIP CIRCUIT BREAKER IN
PANEL F.
2. EXISTING PULLBOX WITH CONDUIT FROM PANEL FB AND OUT TO
EXISTING PUMPS, DISPENSERS AND CONTROLS.
3. EXISTING UNDERGROUND FUEL TANK LOCATION. EC SHALL
DISCONNECT AND REMOVE ELECTRICAL CONNECTIONS TO PUMPS
AND CONTROLS, AND REMOVE WIRING COMPLETE TO SOURCE
PANEL FB.
4. SUBMERSIBLE PUMP AT ABOVE GROUND FUEL TANK - 230V, 1 PH, 2
HP. COORDINATE WITH EQUIPMENT INSTALLER.
5. SUBMERSIBLE PUMP CONTROL PANEL- 120V. COORDINATE WITH
EQUIPMENT INSTALLER.
6. NEW EMERGENCY SHUT OFF PUSHBUTTON - REFER TO THE RISER
DIAGRAM ON SHEET E-4.
7. DEVICES SHALL BE INSTALLED AT ATTENDED DESK, COORDINATE
EXACT LOCATION WITH COUNTY.
8. FUEL DISPENSER - 120V. COORDINATE WITH EQUIPMENT
INSTALLER.
9. 3/4" CONDUIT UNDERGROUND WITH PULL STRING TO ELECTRICAL
ROOM FOR LOW VOLTAGE DATA/COMMUNICATION CABLING FOR
FUEL DISPENSER.
10. NOT USED.
11. NOT USED.
12. OVERFILL ALARM/LEAK DETECTION CONTROL PANEL - 120V.
COORDINATE WITH EQUIPMENT INSTALLER.
13. EXISTING FUEL SYSTEM AND FUEL STORAGE TANK CONTROLS
THIS ROOM TO BE REMOVED, EC SHALL DISCONNECT EQUIPMENT
AND REMOVE WIRING COMPLETE TO SOURCE PANEL FB. FIELD
VERIFY EXISTING CONDITIONS AND COORDINATE WITH FUEL
SYSTEM EQUIPMENT INSTALLER.
14. HIGHLINK MONITORING SYSTEM - 120V. COORDINATE WITH
EQUIPMENT INSTALLER.
15. ROUTE 1" CONDUIT WITH PULL STRING UNDERGROUND FROM
DISPENSER TO FUEL STORAGE TANK CONTROLS/SOLENOID
VALVE. COORDINATE EXACT REQUIREMENTS WITH FUEL
STORAGE TANK/CONTROLS INSTALLER.
GENERAL SHEET NOTES
SCALE: 1/4" = 1'-0" 0 4' 8'2'
NORTH
ENLARGED
ELECTRICAL ROOM
A1
A1
AutoCAD SHX Text S
AutoCAD SHX Text S
AutoCAD SHX Text
DESTROYED CONCRETE AREA (COVERED IN SHELL)
AutoCAD SHX Text
BOAT RAMP
AutoCAD SHX Text
EXIST. BUILDING
AutoCAD SHX Text
EXIST. SHED
AutoCAD SHX Text
SEAWALL
AutoCAD SHX Text
SEAWALL
AutoCAD SHX Text
FUEL DOCK
AutoCAD SHX Text
DOCK
AutoCAD SHX Text
REVISION
AutoCAD SHX Text
DATE
AutoCAD SHX Text
NO.
AutoCAD SHX Text
ISSUE:
AutoCAD SHX Text
ISSUE DATE:
AutoCAD SHX Text
DRAWN BY:
AutoCAD SHX Text
CHECKED BY:
AutoCAD SHX Text
PROJECT NUMBER:
AutoCAD SHX Text
PERMIT SET
AutoCAD SHX Text 05.06.2024
AutoCAD SHX Text
CCO23002
AutoCAD SHX Text
PERMIT SET
AutoCAD SHX Text 05.06.2024
AutoCAD SHX Text
RMR
AutoCAD SHX Text
JAJ
AutoCAD SHX Text
ADDENDUM #1
AutoCAD SHX Text 07.16.2024
A1
LL
IE
R C
O U
N T
Y C
A X A
M B A
S M
A R
IN
A
F U
EL
SY
ST
EM
R
EP
LA
C
EM
EN
T
C o ll ie r C t.
M ar co
I sl an d
FL
C O
RK
SC
RE
W
R D
SU
IT
E
ES
T
ER
O
FL
Fl o ri d a
C o A
Je ff re y
A Je n k in s, F
L
PE
P:
-2
-5
F:
-2
-5
JM
A
JE
N
K
IN
S M
A A
G A
SS
O C
IA
T
ES
LL
C
RISER AND SCHEDULES
E-4
COPPER WIRE AND CONDUIT SCHEDULE
DESIGNATION PARALLEL
RUNS
CONDUCTORS
(AWG/kcmil)
GROUND
(AWG/kcmil) CONDUIT
C2-20 1 2 # 12 1 # 12 3/4" C2-20v1 1 2 # 10 1 # 10 3/4" C2-30 1 2 # 10 1 # 10 3/4" C3-30 1 3 # 10 1 # 10 3/4" C3-60 1 3 # 6 1 # 10 1"
NOTES
1. ALL CONDUCTORS INDICATED IN SCHEDULE SHALL BE
COPPER.
NOTES:
1. CONTRACTOR SHALL LOCATE UNDERGROUND CONDUIT A
MINIMUM OF 10'-0" FROM NEAREST TREE, OR IF NOT PRACTICAL,
AS DIRECTED IN FIELD BY THE LANDSCAPE ARCHITECT.
2. ALL UNDERGROUND ELECTRIC CONDUIT SHALL HAVE A
DETECTABLE WARNING TAPE INSTALLED DIRECTLY ABOVE THE
CONDUIT. WARNING TAPE SHALL BE REEF INDUSTRIES, INC.
TERRA TAPE, 3" WIDE, LABELED WITH "CAUTION ELECTRIC LINE
BURIED BELOW".
CLEAN FILL
SELECTED
BACKFILL
CONDUIT
DETECTABLE
UNDERGROUND
WARNING TAPE
GRADE OR
PAVEMENT
18" MINIMUM
" M
IN
6" 12 " M
IN
PANEL: FB PANELBOARD SCHEDULE
CIRCUIT BREAKERS WIRE AND Ø WIRE AND CIRCUIT BREAKERS
# DESCRIPTION Trip (A) Poles Options CONDUIT LOAD (VA) LOAD (VA) CONDUIT Options Poles Trip (A) DESCRIPTION #
1 SPARE 20 2 - A - 2 20 SPARE 2
3 - B - 4
5 SPARE 20 2 - A - 2 20 SPARE 6
7 - B - 8 b 9 DISPENSER 20 1 C2-20v1 1,200 A - ETR 2 20 TEST RECEPTACLE 10 b 11 HIGHLINK CONTROLS 20 1 C2-20 200 B - 12
13 RECEPTACLE 30 1 ETR 2,500 A 1,380 C3-30 2 25 SUBMERSIBLE PUMP 14 a a 15 FUEL TANK ALARM SYSTEM 20 1 C2-20 200 B 1,380 16
17 SPACE - A 100 C2-20 1 20 PUMP CONTROLS 18 a 19 SPACE - B 180 C2-20 1 20 FUEL SYSTEM DISPLAY 20 a
21 SPACE - A - SPACE 22
23 SPACE - B - SPACE 24
Connected Demand Demand Feeder Size Connected Load (VA) Panel Requirements Load Description Load (VA) Factor Load (VA) Load (VA) Phase A: 5,180 Voltage: 120/240V, 1Ø, 3W Lighting: - 1.00 - 125% - Phase B: 1,960 Mains: 60 A MLO Receptacles - First 10 kVA: 180 1.00 180 100% 180 Rating: 10 kAIC Receptacles - Over 10 kVA: - 0.50 - 100% - Motors: - 1.00 - 100% - Mounting: Surface Largest Motor: 2,760 1.00 2,760 125% 3,450 Panel Service Enclosure Type: NEMA 1 Air Conditioning: - - - 100% - Fed From: Panel F Isolated Ground: No Heat Pumps: - 1.00 - 100% - Feeder: ETR Sub-feed Lugs: No Electric Space Heating: - 1.00 - 100% - Feed-thru Lugs: No Kitchen: - 1.00 - 100% - Elevators: - 1.00 - 100% - Continuous Loads: - 1.00 - 125% - Notes:
Non-continuous Loads: 4,200 1.00 4,200 100% 4,200 Square D QO Loadcenter Totals (VA): 7,140 7,140 7,830 Total (A): 30 A 33 A See Wire and Conduit Schedule for wire and conduit sizes.
a WIRE NEW CIRCUIT TO EXISTING SPARE CIRCUIT BREAKER OR CIRCUIT BREAKER MADE SPARE DURING DEMOLITION b REPLACE EXISTING SPARE CIRCUIT BREAKER OR CIRCUIT BREAKER MADE SPARE DURING DEMOLITION WITH NEW CIRCUIT BREAKER SHOWN
A. METER SOCKETS SHALL BE PERMANENTLY MARKED TO SHOW
PLAINLY THE LOCATION SERVED AND THE CHARACTER OF THE
SERVICE AS REQUIRED BY THE ELECTRIC UTILITY COMPANY. THE
MARKING SHALL CORRESPOND TO THE MARKING ON THE
ASSOCIATED SERVICE DISCONNECT(S).
B. ALL PANELBOARDS SUPPLIED BY A FEEDER SHALL BE
PERMANENTLY MARKED TO INDICATE EACH DEVICE OR
EQUIPMENT WHERE THE POWER ORIGINATES AS REQUIRED BY
NEC 408.4(B).
C. AN ATTEMPT HAS BEEN MADE TO INDICATE THE EXISTING POWER
DISTRIBUTION SYSTEM CONDITIONS. THE CONTRACTOR SHALL
VERIFY ALL EQUIPMENT, PANELS, FEEDERS, ETC. AND NOTIFY THE
ENGINEER OF ANY DISCREPANCIES.
D. THE EXISTING SERVICE SHALL REMAIN. COORDINATE ALL
SHUTDOWNS REQUIRED TO COMPLETE THIS WORK WITH THE
OWNER.
E. ALL NEW CIRCUIT BREAKERS PROVIDED TO BE INSTALLED IN ANY
EXISTING PANEL SHALL MATCH THE EXISTING EQUIPMENT
MANUFACTURER, BE LISTED FOR USE IN THE EXISTING
EQUIPMENT AND HAVE A SHORT CIRCUIT RATING TO MEET OR
EXCEED THE RATING OF THE EXISTING EQUIPMENT.
F. FAULT CURRENT CALCULATIONS BASED ON ESTIMATED SERVICE
TRANSFORMER SIZE.
GENERAL RISER DIAGRAM NOTES
1. CONTACTOR SHALL BE SQUARE D CLASS 8903 TYPE S
ELECTRICALLY HELD CONTACTOR OR EQUAL - 60A, 3-POLE,
MINIMUM 10 KAIC RATED, NORMALLY OPEN WITH 120V COIL.
LOCATE IN A NEMA 1 ENCLOSURE ADJACENT PANEL FB. PANEL FB
SERVES ALL LINE VOLTAGE CIRCUITS TO THE FUEL PUMP
DISPENSERS, FUEL STORAGE TANK PUMP AND ALARMS, AND LOW
VOLTAGE EQUIPMENT THAT SERVES DATA AND MONITORING TO
THE FUEL PUMP DISPENSERS AND STORAGE TANK. THE
CONTACTOR SHALL BE WIRED TO THE EMERGENCY STOP
SWITCHES, SUCH THAT WHEN ANY SWITCH IS ACTIVATED, ALL
PHASE AND NEUTRAL CONDUCTORS IN FEEDER TO PANEL FB ARE
DISCONNECTED AS REQUIRED BY NEC 514.11.
2. REPLACE EXISTING 60A, 2-POLE SHUNT TRIP CIRCUIT BREAKER
WITH NEW 60A, 2-POLE CIRCUIT BREAKER.
RISER KEYNOTES
M
F FB
PADMOUNT SERVICE
TRANSFORMER
120/240V, 1 PH, 3W
(ETR)
E
PROVIDE EMERGENCY STOP PUSHBUTTONS THAT
REQUIRE MANUAL RESET, AS REQUIRED BY NEC
514.11, WIRED TO SIMULTANEOUSLY DISCONNECT
EACH CIRCUIT LEADING TO THE FUEL STORAGE
AND DISPENSING EQUIPMENT - 120V, NORMALLY
CLOSED. SEE SHEET E-3 FOR LOCATIONS.
PUSHBUTTON SHALL BE LABELED WITH AN
APPROVED SIGN STATING "EMERGENCY FUEL
SHUTOFF" AS REQUIRED BY NFPA 30A SECTION 6.7.
MA
IN
0A
E
1 (ETR)
(ETR)BUILDING SERVICE
DISCONNECT
200A
NEMA-3R
(ETR)
ETRETR
ETR ETR
ETR
METER
(ETR)
C3-60
SCALE: NONE1
RISER DIAGRAM
C2-20 F-35
SCA=
8,474A
SCA=
18,961A
SCA=
6,563A
PANEL: F PANELBOARD SCHEDULE
CIRCUIT BREAKERS WIRE AND Ø WIRE AND CIRCUIT BREAKERS
# DESCRIPTION Trip (A) Poles Options CONDUIT LOAD (VA) LOAD (VA) CONDUIT Options Poles Trip (A) DESCRIPTION # 1 AHU 45 2 ETR 3,936 A 5,180 See Riser 2 60 PANEL FB 2 b 3 3,936 B 1,960 4
5 CU 30 2 ETR 1,610 A - SPACE 6
7 1,610 B 1,380 ETR 2 30 PUMP OUT SYSTEM 8
9 LIGHTING 20 1 ETR 800 A 1,380 10
11 LIGHTING 20 1 ETR 800 B - SPACE 12
13 LIGHTING 20 1 ETR 800 A 360 ETR 1 20 REC - FILE ROOM 14
15 LIGHTING 20 1 ETR 800 B 360 ETR 1 20 REC - FILE ROOM 16
17 LIGHTING - EXTERIOR 20 1 ETR 800 A 360 ETR 1 20 REC - WEST WALL 18
19 REC - SHOW ROOM 20 1 ETR 360 B 360 ETR 1 20 REC - REGISTER 20
21 REC - SHOW ROOM 20 1 ETR 360 A 200 ETR 1 20 LIVE BAIT TANK 22
23 FREEZER 20 1 ETR 400 B 360 ETR 1 20 REC - SHOW ROOM 24
25 FREEZER 20 1 ETR 400 A 1,500 ETR 1 20 HOT WATER HEATER 26
27 SHOW WINDOW 20 1 ETR 1,200 B - ETR 1 20 FRONT CUBE RECEPTACLE 28
29 SHOW WINDOW 20 1 ETR 1,200 A 500 ETR 2 20 LIVE BAIT TANK 30
31 SIGN 20 1 ETR 1,200 B 500 32
33 FUEL TANK MONITOR 20 1 ETR 100 A 1,800 ETR 1 20 HAND DRYER 34
a 35 SHUNT TRIP 20 1 ETR - B 1,800 ETR 1 20 HAND DRYER 36
37 LIFT STATION 50 2 ETR - A 1,800 ETR 1 20 HAND DRYER 38
39 - B 1,800 ETR 1 20 HAND DRYER 40
41 SPACE - A - SPACE 42
Connected Demand Demand Feeder Size Connected Load (VA) Panel Requirements Load Description Load (VA) Factor Load (VA) Load (VA) Phase A: 23,086 Voltage: 120/240V, 1Ø, 3W Lighting: 4,000 1.00 4,000 125% 5,000 Phase B: 18,826 Mains: 200 A MCB Receptacles - First 10 kVA: 2,700 1.00 2,700 100% 2,700 Rating: 10 kAIC Receptacles - Over 10 kVA: - 0.50 - 100% - Motors: 3,432 1.00 3,432 100% 3,432 Mounting: Flush Largest Motor: 2,760 1.00 2,760 125% 3,450 Panel Service Enclosure Type: NEMA 1 Air Conditioning: 3,220 - - 100% - Fed From: SERVICE Isolated Ground: No Heat Pumps: - 1.00 - 100% - Feeder: ETR Sub-feed Lugs: No Electric Space Heating: 7,200 1.00 7,200 100% 7,200 Feed-thru Lugs: No Kitchen: - 1.00 - 100% - Elevators: - 1.00 - 100% - Continuous Loads: 5,100 1.00 5,100 125% 6,375 Notes:
Non-continuous Loads: 13,500 1.00 13,500 100% 13,500 Square D NQOD Panelboard Totals (VA): 41,912 38,692 41,657 The loads indicated as existing are estimated.
Total (A): 161 A 174 A See Wire and Conduit Schedule for wire and conduit sizes.
a WIRE NEW CIRCUIT TO EXISTING SPARE CIRCUIT BREAKER OR CIRCUIT BREAKER MADE SPARE DURING DEMOLITION b REPLACE EXISTING SPARE CIRCUIT BREAKER(S) WITH NEW CIRCUIT BREAKER SHOWN
CEILING
FLOOR
STUB CONDUITS 6" INTO SPACE
ABOVE ACCESSIBLE CEILING IN
THE NEAREST CORRIDOR OR
OPEN AREA. TERMINATE WITH
INSULATED BUSHING (TYPICAL).
1" CONDUIT WITH PULLWIRE
(TYPICAL).
NOTES:
1. DATA OUTLET FOR FUEL SYSTEM/DISPENSER SYSTEM
MONITORING/DISPLAY, COORDINATE EXACT LOCATION AND
REQUIREMENTS WITH SYSTEM INSTALLER.
SCALE: NONE2
LOW VOLTAGE ROUGH-IN
OUTLET BOX DETAIL
SCALE: NONE3
UNDERGROUND CONDUIT
INSTALLATION DETAIL
AutoCAD SHX Text
REVISION
AutoCAD SHX Text
DATE
AutoCAD SHX Text
NO.
AutoCAD SHX Text
ISSUE:
AutoCAD SHX Text
ISSUE DATE:
AutoCAD SHX Text
DRAWN BY:
AutoCAD SHX Text
CHECKED BY:
AutoCAD SHX Text
PROJECT NUMBER:
AutoCAD SHX Text
PERMIT SET
AutoCAD SHX Text 05.06.2024
AutoCAD SHX Text
CCO23002
AutoCAD SHX Text
PERMIT SET
AutoCAD SHX Text 05.06.2024
AutoCAD SHX Text
RMR
| Sheets and Views |
| E-1 - LEGEND |
| E-2 - SPECIFICATIONS |
| E-3 - SITE ELECTRICAL |
| E-4 - SCHEDULES |
| FL PE 65169, STATE OF FLORIDA | |
| 2024-07-18T23:55:15-0400 | |
| Jeffrey A Jenkins | |
| I am the author of this document |
File details come from the government source that posted it. Updated .