This document contains a detailed sequence of operation and points list for an HVAC system upgrade project for the Columbia Schools in Michigan. The project involves upgrading the air handling unit (AHU-1) and variable air volume (VAV) terminal units. The scope includes providing all necessary controls points and sequences to integrate the equipment into the building automation system. Key details include control sequences for occupied, unoccupied, and optimal start/stop modes, economizer operation, demand control ventilation, and temperature setpoint reset strategies. The points lists outline the required analog and digital inputs, outputs, and software points for the AHU and VAV terminal units.
The pricing, funding sources, and other contractual terms are not included in this technical document. However, this HVAC upgrade project is part of a larger state and local contract opportunity focused on HVAC system improvements for Jackson County, Michigan. Interested contractors should review the full bid information, including any set-aside requirements, to understand the complete scope and terms of this contract opportunity.
View the file
Other files
Show all 11
On GovTribe
Work with this file
- Download the original file
- Contacts named in this file
- Similar government files
- Ask GovTribe AI about this file
Text version
1 AHU FLOW DIAGRAM
FLOW DIAGRAM: AHU-1
POINTS LIST: AHU-1
System Point Description POINTS ALARMS
NOTE: THE CONTROL POINTS FOR THE
ASSOCIATE EQUIPMENT INCLUDES, BUT IS NOT
LIMITED TO, THE FOLLOWING POINTS. THE
CONTROLS CONTRACTOR IS RESPONSIBLE
FOR PROVIDING ALL NECESSARY POINTS TO
CONTROL THE EQUIPMENT PER THE
SEQUENCE OF OPERATION.
GR
AP
HI
C
AN
AL
OG
H
AR
DW
AR
E
IN
PU
T (A
I)
BI
NA
RY
H
AR
DW
AR
E
IN
PU
T
(B I)
AN
AL
OG
H
AR
DW
AR
E
OU
TP
UT
(A
O)
BI
NA
RY
H
AR
DW
AR
E
OU
TP
UT
(B O)
SO
FT
W
AR
E
PO
IN
T
(S
FT
HA
RD
W
AR
E
IN
TE
RL
OC
K (H
DW
W
IR
EL
ES
S (W
LS
NE
TW
OR
K
(N
ET
HI
GH
A
NA
LO
G
LIM
IT
LO
W A
NA
LO
G
LIM
IT
BI
NA
RY
LA
TC
H
DI
AG
NO
ST
IC
SE
NS
OR
F
AI
L
CO
MM
UN
IC
AT
IO
N
FA
IL
CONDENSATE OVERFLOW DETECTION LOCAL
CND OVRFL
X X X X
COOLING COIL LEAVING TEMPERATURE
CC LAT
X X X X X
COOLING OUTPUT COMMAND
CLG
X X
DISCHARGE AIR TEMPERATURE
DAT
X X X X X
DISCHARGE AIR STATIC PRESSURE LOCAL
DA SP
X X X X X
FILTER STATUS
FIL
X X X
HEATING OUTPUT COMMAND
HTG
X X
HIGH STATIC ALARM
HSP ALM
X X X X
HIGH STATIC ALARM INTERLOCK
HSP INTLK
X
MIXED AIR DAMPER COMMAND
MAD
X X
MIXED AIR LOW TEMPERATURE CUTOUT ALARM
MA LLT
X X
MIXED AIR TEMPERATURE LOCAL
MAT
X X X X
OUTDOOR AIR DAMPER COMMAND
OAD
X X
OUTDOOR AIR FLOW
OA FLW
X X
OUTDOOR AIR RELATIVE HUMIDITY LOCAL
OAH
X X
OUTDOOR AIR TEMPERATURE LOCAL
OAT
X X
REHEAT LEAVING COIL TEMPERATURE LOCAL
RH LAT
X X X X X
REHEAT OUTPUT COMMAND
RH
X X
RELIEF AIR FAN AIR FLOW LOCAL
RLF FLW
X X
RELIEF AIR FAN SPEED OUTPUT COMMAND
RLF
X X
RELIEF AIR FAN START STOP
RLF
X X
RETURN AIR CO2 LOCAL
RA CO2
X X X
RETURN AIR DAMPER COMMAND
RAD
X X
RETURN AIR TEMPERATURE LOCAL
RAT
X X
RETURN FAN AIR FLOW LOCAL
RAF FLW
X X
RETURN SMOKE DETECTOR INPUT
RA SD
X
SPACE TEMPERATURE LOCAL
SPT
X X X X X
SPACE TEMPERATURE SETPOINT LOCAL
SPT SP
X X
SUPPLY FAN AIR FLOW LOCAL
SF FLW
X X
SUPPLY FAN SPEED COMMAND
SAF
X X
SUPPLY FAN START STOP COMMAND
SAF
X X
SUPPLY FAN STATUS
SAF
X X
SUPPLY SMOKE DETECTOR INPUT
SA SD
X
BAS COMMUNICATION STATE
BAS COM
X X
DISCHARGE AIR COOLING SETPOINT
DA CL SP
X
DISCHARGE AIR HEATING SETPOINT
DA HT SP
X
MAINTENANCE REQUIRED
MNT REQ
X X
MIXED AIR TEMPERATURE LOW LIMIT SETPOINT
MA LLT STPT
X
OCCUPIED COOLING SETPOINT
OCC CLG STPT
X X
OCCUPIED HEATING SETPOINT
OCC HTG STPT
X X
SUPPLY FAN FAILURE
SF FAIL
X X X
UNOCCUPIED COOLING SETPOINT
UNOCC CLG STPT
X X
UNOCCUPIED HEATING SETPOINT
UNOCC HTG STPT
X X
SEQUENCE OF OPERATION: AHU-1
BUILDING AUTOMATION SYSTEM INTERFACE:
THE BUILDING AUTOMATION SYSTEM (BAS) SHALL SEND THE CONTROLLER OCCUPIED BYPASS, MORNING WARM-UP/PRE-COOL, OCCUPIED/UNOCCUPIED AND HEAT/COOL MODES. IF A BAS IS NOT PRESENT, OR COMMUNICATION IS LOST WITH THE BAS THE CONTROLLER SHALL OPERATE USING DEFAULT MODES AND
SETPOINTS.
OCCUPIED:
DURING OCCUPIED PERIODS, THE SUPPLY FAN SHALL RUN CONTINUOUSLY AND THE MIXED AIR DAMPERS SHALL
OPEN TO MAINTAIN MINIMUM VENTILATION REQUIREMENTS.
THE DX COOLING AND THE HOT WATER VALVE SHALL CONTROL TO MAINTAIN THE DISCHARGE AIR TEMPERATURE SETPOINT. IF ECONOMIZING IS ENABLED, THE OUTDOOR AIR OR MIXED AIR DAMPERS SHALL MODULATE TO MAINTAIN THE DISCHARGE AIR TEMPERATURE SETPOINT AND THE RELIEF AIR DAMPER SHALL TRACK THE MIXED AIR DAMPERS. THE DISCHARGE AIR TEMPERATURE SETPOINT SHALL BE DYNAMICALLY RESET BASED ON THE DEVIATION OF ACTUAL SPACE TEMPERATURE FROM THE ACTIVE SPACE TEMPERATURE SETPOINT. IF THE DISCHARGE AIR TEMPERATURE SENSOR FAILS, THE DX COOLING AND THE HOT WATER VALVE SHALL CONTROL TO MAINTAIN THE ACTIVE SPACE TEMPERATURE SETPOINT AND AN ALARM SHALL ANNUNCIATE AT THE BAS. IF THE DISCHARGE AIR TEMPERATURE SENSOR AND THE SPACE TEMPERATURE SENSOR FAIL, THE DX COOLING SHALL BE DISABLED, THE HOT WATER VALVE SHALL CLOSE AND AN ALARM SHALL ANNUNCIATE AT THE BAS.
UNOCCUPIED:
WHEN THE SPACE TEMPERATURE IS BELOW THE UNOCCUPIED HEATING SETPOINT OF 60.0 DEG. F (ADJ.) THE SUPPLY FAN SHALL START, THE OUTSIDE AIR DAMPER SHALL REMAIN CLOSED AND THE HOT WATER VALVE SHALL OPEN. WHEN THE SPACE TEMPERATURE RISES ABOVE THE UNOCCUPIED HEATING SETPOINT OF 60.0 DEG. F (ADJ.) PLUS THE UNOCCUPIED DIFFERENTIAL OF 4.0 DEG. F (ADJ.) THE SUPPLY FAN SHALL STOP AND THE HOT
WATER VALVE SHALL CLOSE.
WHEN THE SPACE TEMPERATURE IS ABOVE THE UNOCCUPIED COOLING SETPOINT OF 85.0 DEG. F (ADJ.) THE SUPPLY FAN SHALL START, THE OUTSIDE AIR DAMPER SHALL OPEN IF ECONOMIZING IS ENABLED AND REMAIN CLOSED IF ECONOMIZING IS DISABLED AND THE DX COOLING SHALL BE ENABLED. WHEN THE SPACE TEMPERATURE FALLS BELOW THE UNOCCUPIED COOLING SETPOINT OF 85.0 DEG. F MINUS THE UNOCCUPIED DIFFERENTIAL OF 4.0 DEG. F (ADJ.) THE SUPPLY FAN SHALL STOP, THE DX COOLING SHALL BE DISABLED AND THE
OUTSIDE AIR DAMPER SHALL CLOSE.
OPTIMAL START:
THE BAS SHALL MONITOR THE SCHEDULED OCCUPIED TIME, OCCUPIED SPACE SETPOINTS AND SPACE
TEMPERATURE TO CALCULATE WHEN THE OPTIMAL START OCCURS.
OPTIMAL STOP:
THE BAS SHALL MONITOR THE SCHEDULED UNOCCUPIED TIME, OCCUPIED SETPOINTS AND SPACE TEMPERATURE TO CALCULATE WHEN THE OPTIMAL STOP OCCURS. WHEN THE OPTIMAL STOP MODE IS ACTIVE THE UNIT CONTROLLER SHALL MAINTAIN THE SPACE TEMPERATURE TO THE SPACE TEMPERATURE OFFSET SETPOINT.
OUTSIDE AIR DAMPER SHALL REMAIN ENABLED TO PROVIDE MINIMUM VENTILATION.
OCCUPIED BYPASS:
THE BAS SHALL MONITOR THE STATUS OF THE ON AND CANCEL BUTTONS OF THE SPACE TEMPERATURE SENSOR.
WHEN AN OCCUPIED BYPASS REQUEST IS RECEIVED FROM A SPACE SENSOR, THE UNIT SHALL TRANSITION FROM ITS CURRENT OCCUPANCY MODE TO OCCUPIED BYPASS MODE AND THE UNIT SHALL MAINTAIN THE SPACE
TEMPERATURE TO THE OCCUPIED SETPOINTS (ADJ.).
HEAT/COOL MODE:
WHEN THE SPACE TEMPERATURE RISES ABOVE THE OCCUPIED COOLING SETPOINT THE MODE SHALL TRANSITION TO COOLING. WHEN THE SPACE TEMPERATURE FALLS BELOW THE OCCUPIED HEATING SETPOINT THE MODE SHALL TRANSITION TO HEATING. WHEN THE SPACE TEMPERATURE IS ABOVE THE OCCUPIED COOLING SETPOINT OR BELOW THE OCCUPIED HEATING SETPOINT THE MODE SHALL REMAIN IN ITS LAST STATE. IF THE SPACE TEMPERATURE SENSOR FAILS THE MODE SHALL REMAIN IN ITS LAST STATE AND AN ALARM SHALL ANNUNCIATE AT THE BAS. IF THE LOCAL AND COMMUNICATED SETPOINTS FAIL THE CONTROLLER SHALL DISABLE THE SUPPLY FAN
AND AN ALARM SHALL ANNUNCIATE AT THE BAS.
MORNING WARM-UP MODE:
DURING OPTIMAL START, IF THE SPACE TEMPERATURE IS BELOW THE OCCUPIED HEATING SETPOINT A MORNING WARM-UP MODE SHALL BE ACTIVATED. WHEN MORNING WARM-UP IS INITIATED THE UNIT SHALL ENABLE THE HEATING AND FAN(S). THE OUTSIDE AIR DAMPER SHALL REMAIN CLOSED. WHEN THE SPACE TEMPERATURE REACHES THE OCCUPIED HEATING SETPOINT (ADJ.), THE UNIT SHALL TRANSITION TO THE OCCUPIED MODE.
DAYTIME WARM-UP CONTROL:
DURING OCCUPIED PERIODS, WHEN THE SPACE TEMPERATURE IS BELOW THE DAYTIME WARM-UP INITIATE SETPOINT, A DAYTIME WARM-UP SEQUENCE SHALL BE ACTIVATED. THE OUTSIDE AIR DAMPER SHALL MODULATE TO MAINTAIN MINIMUM VENTILATION REQUIREMENTS, AND THE HEATING SHALL ENABLE TO MAINTAIN THE DISCHARGE AIR TEMPERATURE HEATING SETPOINT. DAYTIME WARM-UP SHALL TERMINATE WHEN THE AVERAGE
SPACE TEMPERATURE REACHES THE OCCUPIED HEATING SETPOINT.
PRE-COOL MODE:
DURING OPTIMAL START, IF THE SPACE TEMPERATURE IS ABOVE THE OCCUPIED COOLING SETPOINT, PRE-COOL MODE SHALL BE ACTIVATED. WHEN PRE-COOL IS INITIATED THE UNIT SHALL ENABLE THE FAN AND COOLING OR ECONOMIZER. THE OUTSIDE AIR DAMPER SHALL REMAIN CLOSED, UNLESS ECONOMIZING. WHEN THE SPACE TEMPERATURE REACHES OCCUPIED COOLING SETPOINT (ADJ.), THE UNIT SHALL TRANSITION TO THE OCCUPIED
MODE.
ECONOMIZER MODE:
ENABLE: OUTSIDE AIR (OA) ENTHALPY SHALL BE COMPARED WITH THE REFERENCE ENTHALPY CONTROL SETPOINT. THE ECONOMIZER SHALL ENABLE WHEN OA ENTHALPY IS 2.0 BTU/LB LESS THAN ENTHALPY CONTROL SETPOINT. THE ECONOMIZER SHALL DISABLE WHEN OA ENTHALPY IS GREATER THAN ENTHALPY CONTROL
SETPOINT.
OPERATION: WHEN ECONOMIZING IS ENABLED AND THE UNIT IS OPERATING IN THE COOLING MODE, THE ECONOMIZER DAMPER SHALL BE MODULATED BETWEEN ITS MINIMUM POSITION AND 100% TO MAINTAIN THE SPACE TEMPERATURE SETPOINT. THE ECONOMIZER DAMPER SHALL MODULATE TOWARD MINIMUM POSITION IN THE EVENT THE MIXED AIR TEMPERATURE FALLS BELOW THE LOW TEMPERATURE LIMIT SETTING.
DEMAND CONTROL VENTILATION:
USING A RETURN CO2 INPUT (LOCAL SENSOR OR NETWORK COMMUNICATED VALUE), THE CONTROLLER SHALL MONITOR AND COMPARE THE MEASURED RETURN CO2 TO THE RETURN CO2 CONCENTRATION SETPOINT (ADJ.).
WHEN THE MEASURED RETURN CO2 CONCENTRATION REACHES THE SETPOINT (ADJ.), THE OUTSIDE AIR DAMPER SHALL MODULATE OPEN INCREMENTALLY UNTIL THE RETURN AIR CO2 LEVEL IS SATISFIED OR THE OUTSIDE AIR DAMPER REACHES THE FULL OPEN POSITION. IF THE MEASURED CO2 CONCENTRATION FALLS, THE OUTSIDE AIR DAMPER SHALL MODULATE TOWARD NORMAL ECONOMIZER OPERATION. IF THE MIXED AIR TEMPERATURE DROPS BELOW THE MIXED AIR LOW LIMIT SETPOINT THE CO2 SENSOR INPUT IS OVERRIDDEN AND THE OUTSIDE AIR DAMPER WILL BE MODULATED CLOSED TO MAINTAIN THE MIXED AIR TEMPERATURE LOW LIMIT SETPOINT. WHEN THE MIXED AIR TEMPERATURE RISES ABOVE THE MIXED AIR LOW LIMIT SETPOINT, CO2 OPERATION IS RESTORED.
DISCHARGE AIR TEMPERATURE RESET CONTROL:
ON A RISE IN SPACE TEMPERATURE (+2.0 DEG. F ADJ. OR GREATER) ABOVE THE SPACE COOLING SETPOINT (74.0 DEG. F ADJ.); THE SUPPLY FAN SPEED SHALL MODULATE FROM MINIMUM (50% ADJ.) TO MAXIMUM (OR DESIGN) AIR FLOW TO MAINTAIN SPACE COOLING TEMPERATURE SETPOINT WHILE KEEPING THE DISCHARGE AIR
TEMPERATURE SETPOINT AT MINIMUM (55.0 DEG. F ADJ.).
AS SPACE TEMPERATURE DECREASES BELOW 76.0 DEG. F (SPACE COOLING SETPOINT 74.0 DEG. F + 2.0 DEG. F);
THE FAN SPEED SHALL BE LOCKED AT MINIMUM AIR FLOW AND THE DISCHARGE AIR TEMPERATURE SETPOINT
REMAINS AT MINIMUM.
WHEN SPACE TEMPERATURE DECREASES TO 75.0 DEG. F (COOLING SETPOINT OF 74.0 DEG. F ADJ. + 1.0 DEG. F) OR BELOW FOR A PERIOD OF TIME (DEFAULT 1 MIN. ADJ.); THE FAN SPEED SHALL REMAIN AT MINIMUM, THE DISCHARGE AIR TEMPERATURE SETPOINT REMAINS AT MINIMUM, AND CONTROL ENTERS INTO DISCHARGE AIR
TEMPERATURE SETPOINT RESET MODE.
AS SPACE TEMPERATURE CONTINUES TO DROP BELOW 75.0 DEG. F (SPACE TEMPERATURE COOLING SETPOINT +
1.0 DEG. F); THE FAN SPEED SHALL REMAIN AT MINIMUM AND THE DISCHARGE AIR TEMPERATURE SETPOINT SHALL BE RESET FROM MINIMUM (55.0 DEG. F ADJ.) TO MAXIMUM (65.0 DEG. F ADJ.) AS SPACE TEMPERATURE DROPS FROM 75.0 DEG. F TO 74.0 DEG. F TO MAINTAIN THE SPACE COOLING TEMPERATURE SETPOINT.
ON A CONTINUED DROP OF SPACE TEMPERATURE BELOW THE SPACE COOLING TEMPERATURE SETPOINT (74.0 DEG. F ADJ.) THROUGH (71.0 DEG. F ADJ.) THE SPACE TEMPERATURE CONTROL SHALL BE WITHIN ITS DEADBAND;
THE FAN SPEED REMAINS AT MINIMUM AND DISCHARGE AIR SETPOINT OF (65.0 DEG. F ADJ.) FOR COOLING.
AS SPACE TEMPERATURE DECREASES TOWARDS THE HEATING SETPOINT (71.0 DEG. F ADJ.) THE CONTROL SHALL SWITCH TO THE HEATING DISCHARGE AIR TEMPERATURE RESET. IN THE HEATING MODE, THE HEAT SHALL BE ENABLED; THE SUPPLY FAN SHALL REMAIN AT MINIMUM AIR FLOW AND THE DISCHARGE AIR TEMPERATURE SETPOINT SHALL BE RESET FROM 70.0 DEG. F TO 90.0 DEG. F AS THE SPACE TEMPERATURE DROPS FROM 71.0
DEG. F TO 70.0 DEG. F.
AS SPACE TEMPERATURE CONTINUES TO DECREASE TOWARDS THE HEATING SETPOINT (71.0 DEG. F ADJ.) - 1.0 DEG. F; THE DISCHARGE AIR TEMPERATURE SETPOINT SHALL REMAIN AT MAXIMUM (90.0 DEG. F ADJ.), THE FAN SHALL BE MODULATED FROM MINIMUM TO MAXIMUM AIR FLOW TO MAINTAIN THE SPACE TEMPERATURE HEATING
SETPOINT.
WHEN THE SPACE TEMPERATURE INCREASES THE REVERSE CONTROL SHALL BE IMPLEMENTED.
SUPPLY FAN:
THE UNIT CONTROLLER SHALL VARY THE SUPPLY FAN SPEED TO OPTIMIZE MINIMUM FAN SPEED IN ALL COOLING
AND HEATING MODES.
BUILDING PRESSURE CONTROL (RELIEF AIR):
AFTER THE FAN STARTUP DELAY EXPIRES, BUILDING STATIC PRESSURE SHALL BE CONTROLLED BY MODULATING THE OUTSIDE AIR DAMPER. AS BUILDING PRESSURE INCREASES OVER THE BUILDING PRESSURE SETPOINT (ADJ.), THE DAMPER SHALL MODULATE CLOSED. IF THE BUILDING PRESSURE FALLS BELOW THE SETPOINT, THE DAMPER
SHALL MODULATE OPEN.
MIXED AIR LOW LIMIT:
THE INITIAL DAMPER OPENING RATE SHALL BE LIMITED TO 2% PER MINUTE (ADJ.) UNTIL THE DAMPER HAS REACHED ITS MINIMUM VENTILATION POSITION. THE OUTSIDE AIR DAMPER SHALL MODULATE TO A POSITION LESS THAN THE MINIMUM DAMPER POSITION IF THE MIXED AIR TEMPERATURE DROPS BELOW 50.0 DEG. F (ADJ.). IF THE MIXED AIR TEMPERATURE SENSOR FAILS AN ALARM SHALL ANNUNCIATE AT THE BAS AND THE OUTSIDE AIR
DAMPER SHALL RETURN TO THE MINIMUM POSITION.
FREEZE PROTECTION:
A HARDWIRED, LOW LIMIT TEMPERATURE SWITCH SHALL BE ELECTRICALLY INTERLOCKED WITH THE VARIABLE SPEED DRIVE. IF THE LOW LIMIT TEMPERATURE SWITCH IS TRIPPED 38.0 DEG. F (ADJ.), THE FAN SHALL BE COMMANDED OFF AND THE OUTSIDE AIR DAMPER SHALL CLOSE. ALL VALVES SHALL BE COMMANDED OPEN TO 100% (ADJUST PER CLIMATE). THE DX COOLING SHALL BE DISABLED. AN ALARM SHALL ANNUNCIATE AT THE BAS AND MANUAL RESET OF THE LOW LIMIT TEMPERATURE SWITCH SHALL BE REQUIRED TO RESTART THE FAN.
CONDENSATE OVERFLOW MONITORING:
IF THE CONDENSATE LEVEL REACHES THE TRIP POINT, A CONDENSATE OVERFLOW DIAGNOSTIC SHALL ANNUNCIATE AT THE BAS. TO PREVENT THE CONDENSATE DRAIN PAN FROM OVERFLOWING AND CAUSING WATER DAMAGE TO THE BUILDING THE FAN SHALL BE DISABLED AND THE DX COOLING SHALL BE DISABLED.
FILTER STATUS:
A DIFFERENTIAL PRESSURE SWITCH SHALL MONITOR THE DIFFERENTIAL PRESSURE ACROSS THE FILTER(S) WHEN THE FAN IS RUNNING. IF THE SWITCH CLOSES DURING NORMAL OPERATION A DIRTY FILTER ALARM SHALL
ANNUNCIATE AT THE BAS.
SMOKE DETECTOR SHUTDOWN:
THE UNIT SHALL SHUT DOWN IN RESPONSE TO A SIGNAL FROM THE SMOKE DETECTOR INDICATING THE PRESENCE OF SMOKE. THE SMOKE DETECTOR SHALL BE INTERLOCKED TO THE UNIT THROUGH THE DRY CONTACTS OF THE SMOKE DETECTOR. A MANUAL RESET OF THE SMOKE DETECTOR SHALL BE REQUIRED TO
RESTART THE UNIT.
M A
T R
I X
1 VAV FLOW DIAGRAM
SEQUENCE OF OPERATION: VAV TERMINAL UNIT
BUILDING AUTOMATION SYSTEM INTERFACE:
THE BUILDING AUTOMATION SYSTEM (BAS) SHALL SEND THE CONTROLLER OCCUPIED, AND UNOCCUPIED COMMANDS. THE BAS MAY ALSO SEND A HEAT/COOL MODE, PRIORITY SHUTDOWN COMMANDS, SPACE TEMPERATURE AND/OR SPACE TEMPERATURE SETPOINT. IF COMMUNICATION IS LOST WITH THE BAS, THE
CONTROLLER SHALL OPERATE USING ITS LOCAL SETPOINTS.
OCCUPIED:
NORMAL OPERATING MODE FOR OCCUPIED SPACES OR DAYTIME OPERATION. WHEN THE UNIT IS IN THE OCCUPIED MODE THE VAV SHALL MAINTAIN THE SPACE TEMPERATURE AT THE ACTIVE OCCUPIED HEATING OR COOLING SETPOINT. APPLICABLE VENTILATION AND AIRFLOW SETPOINTS SHALL BE ENFORCED. THE OCCUPIED
MODE SHALL BE THE DEFAULT MODE OF THE VAV.
UNOCCUPIED:
NORMAL OPERATING MODE FOR UNOCCUPIED SPACES OR NIGHTTIME OPERATION. WHEN THE UNIT IS IN UNOCCUPIED MODE THE VAV CONTROLLER SHALL MAINTAIN THE SPACE TEMPERATURE AT THE STORED UNOCCUPIED HEATING OR COOLING SETPOINT REGARDLESS OF THE PRESENCE OF A HARDWIRED OR COMMUNICATED SETPOINT. WHEN THE SPACE TEMPERATURE EXCEEDS THE ACTIVE UNOCCUPIED SETPOINT THE
VAV SHALL MODULATE FULLY CLOSED.
OCCUPIED BYPASS:
MODE USED TO TEMPORARILY PLACE THE UNIT INTO THE OCCUPIED OPERATION. TENANTS SHALL BE ABLE TO OVERRIDE THE UNOCCUPIED MODE FROM THE SPACE SENSOR. THE OVERRIDE SHALL LAST FOR A MAXIMUM OF 4 HOURS (ADJ.). THE TENANTS SHALL BE ABLE TO CANCEL THE OVERRIDE FROM THE SPACE SENSOR AT ANY TIME.
DURING THE OVERRIDE THE UNIT SHALL OPERATE IN OCCUPIED MODE.
HEAT/COOL MODE:
THE HEAT/COOL MODE SHALL BE SET BY A COMMUNICATED VALUE OR AUTOMATICALLY BY THE VAV. IN STANDALONE OR AUTO MODE THE VAV SHALL COMPARE THE PRIMARY AIR TEMPERATURE WITH THE CONFIGURED AUTO CHANGEOVER SETPOINT TO DETERMINE IF THE AIR IS "HOT"" OR ""COLD"". HEATING MODE IMPLIES THE PRIMARY AIR TEMPERATURE IS HOT. COOLING MODE IMPLIES THE PRIMARY AIR TEMPERATURE IS COLD."
HEAT/COOL SETPOINT:
THE SPACE TEMPERATURE SETPOINT SHALL BE DETERMINED EITHER BY A LOCAL (E.G., THUMBWHEEL) SETPOINT, THE VAV DEFAULT SETPOINT OR A COMMUNICATED VALUE. THE VAV SHALL USE THE LOCALLY STORED DEFAULT SETPOINTS WHEN NEITHER A LOCAL SETPOINT NOR COMMUNICATED SETPOINT IS PRESENT. IF BOTH A LOCAL SETPOINT AND COMMUNICATED SETPOINT EXIST, THE VAV SHALL USE THE COMMUNICATED VALUE.
COOLING MODE:
WHEN THE UNIT IS IN COOLING MODE, THE VAV CONTROLLER SHALL MAINTAIN THE SPACE TEMPERATURE AT THE ACTIVE COOLING SETPOINT BY MODULATING THE AIRFLOW BETWEEN THE ACTIVE COOLING MINIMUM AIRFLOW SETPOINT TO THE MAXIMUM COOLING AIRFLOW SETPOINT. THE VAV SHALL USE THE MEASURED SPACE TEMPERATURE AND THE ACTIVE COOLING SETPOINT TO DETERMINE THE REQUESTED COOLING CAPACITY OF THE UNIT. THE OUTPUTS WILL BE CONTROLLED BASED ON THE UNIT CONFIGURATION AND THE REQUESTED COOLING CAPACITY. WHEN IN THE OCCUPIED MODE, THE CONTROLLER SHALL USE THE MEASURED SPACE TEMPERATURE AND THE ACTIVE COOLING SETPOINT TO DETERMINE THE REQUESTED COOLING CAPACITY OF THE UNIT. THE OUTPUTS SHALL BE CONTROLLED BASED ON THE UNIT CONFIGURATION AND THE REQUESTED COOLING
CAPACITY.
HEATING MODE:
WHEN THE UNIT IS IN HEATING MODE, THE VAV CONTROLLER SHALL MAINTAIN THE SPACE TEMPERATURE AT THE ACTIVE HEATING SETPOINT BY MODULATING THE AIRFLOW BETWEEN THE ACTIVE HEATING MINIMUM AIRFLOW SETPOINT TO THE MAXIMUM HEATING AIRFLOW SETPOINT. THE VAV CONTROLLER SHALL USE THE MEASURED SPACE TEMPERATURE AND THE ACTIVE HEATING SETPOINT TO DETERMINE THE REQUESTED HEATING CAPACITY OF THE UNIT. THE OUTPUTS WILL BE CONTROLLED BASED ON THE UNIT CONFIGURATION AND THE REQUESTED
HEATING CAPACITY.
PROPORTIONAL HOT WATER REHEAT:
IF THE SPACE TEMPERATURE IS BELOW THE HEATING SETPOINT THE HOT WATER REHEAT VALVE SHALL CONTROL
AS REQUIRED TO MAINTAIN THE ACTIVE HEATING SETPOINT.
DEMAND CONTROL VENTILATION:
WHEN THE UNIT IS IN UNOCCUPIED MODE, THE VENTILATION AIRFLOW SETPOINT WILL BE ZERO. WHEN THE UNIT IS IN OCCUPIED MODE, THE VENTILATION AIRFLOW SETPOINT SHALL EQUAL THE DESIGN OUTDOOR AIRFLOW (SEE
VAV SCHEDULE).
THE CURRENT VENTILATION AIRFLOW SETPOINT SHALL BE COMMUNICATED TO THE BAS FOR CONTROL OF THE
SYSTEM OUTDOOR-AIR INTAKE.
SPACE SENSOR FAILURE:
IF THERE IS A FAULT WITH THE OPERATION OF THE ZONE SENSOR AN ALARM SHALL BE ANNUNCIATED AT THE BAS.
SPACE SENSOR FAILURE SHALL CAUSE THE VAV TO DRIVE THE DAMPER TO MINIMUM AIR FLOW IF THE VAV IS IN
THE OCCUPIED MODE, OR DRIVE IT CLOSED IF THE VAV IS IN THE UNOCCUPIED MODE.
HW VLV (AO)
SPT (AI)
SPT SP (AI)
DA FLW (AI)
AIR VLV (AO)
DAT (AI)
DAD
T
AFS
ACT
T
SA
POINTS LIST: VAV TERMINAL UNIT
SYSTEM POINT DESCRIPTION POINTS ALARMS
NOTE: THE CONTROL POINTS FOR THE
ASSOCIATE EQUIPMENT INCLUDES, BUT IS NOT
LIMITED TO, THE FOLLOWING POINTS. THE
CONTROLS CONTRACTOR IS RESPONSIBLE
FOR PROVIDING ALL NECESSARY POINTS TO
CONTROL THE EQUIPMENT PER THE
SEQUENCE OF OPERATION.
GR
AP
HI
C
AN
AL
OG
H
AR
DW
AR
E
IN
PU
T (A
I)
BI
NA
RY
H
AR
DW
AR
E
IN
PU
T
(B I)
AN
AL
OG
H
AR
DW
AR
E
OU
TP
UT
(A
O)
BI
NA
RY
H
AR
DW
AR
E
OU
TP
UT
(B O)
SO
FT
W
AR
E
PO
IN
T
(S
FT
HA
RD
W
AR
E
IN
TE
RL
OC
K (H
DW
W
IR
EL
ES
S (W
LS
NE
TW
OR
K
(N
ET
HI
GH
A
NA
LO
G
LIM
IT
LO
W A
NA
LO
G
LIM
IT
BI
NA
RY
LA
TC
H
DI
AG
NO
ST
IC
SE
NS
OR
F
AI
L
CO
MM
UN
IC
AT
IO
N
FA
IL
AIR VALVE MODULATION COMMAND
AIR VLV
X X
DISCHARGE AIR TEMPERATURE
DAT
X X X X X
LOCAL HEAT VALVE COMMAND
HW VLV
X X
SPACE TEMPERATURE LOCAL
SPT
X X
SPACE TEMPERATURE SETPOINT LOCAL
SPT SP
X X
SUPPLY AIRFLOW
DA FLW
X X X X
BAS COMMUNICATION STATE
BAS COM
X X
DESIGN HEAT DISCHARGE AIR TEMP SETPOINT
DSNG HT DAT SP
X
MAXIMUM COOLING AIRFLOW SETPOINT
MAX CLG FLW SP
X
MINIMUM COOLING AIRFLOW SETPOINT
MIN CLG FLW SP
X
MAXIMUM HEATING AIRFLOW SETPOINT
MAX HTG FLW SP
X
MINIMUM HEATING AIRFLOW SETPOINT
MIN HTG FLW SP
X
OCCUPIED BYPASS TIMER
OCC TMR
X X
OCCUPIED COOLING SETPOINT
OCC CLG SP
X X
OCCUPIED HEATING SETPOINT
OCC HTG SP
X X
UNOCCUPIED COOLING SETPOINT
UNOCC CLG SP
X X
SPACE OCCUPANCY
OCC SP
X X
UNOCCUPIED HEATING SETPOINT
UNOCC HTG SP
X X
SUPPLY FAN COMMAND
SF CMD
X X
M A
T R
M A
T R
| A000-2252100 |
| M100-2252100 |
| M300-2252100 |
| M301-2252100 |
| M302-2252100 |
| M303-2252100 |
| M304-2252100 |
| M305-2252100 |
| M400-2252100 |
| M401-2252100 |
| M402-2252100 |
| M403-2252100 |
| M404-2252100 |
| M600-2252100 |
| M601-2252100 |
| M800-2252100 |
| M801-2252100 |
| M802-2252100 |
| M803-2252100 |
| M804-2252100 |
| M900-2252100 |
File details come from the government source that posted it. Updated .