22521.00 - Columbia Schools HVAC Upgrades - Mechanical Set - 2 of 3.pdf
PDF 5 MB Posted
- Attached to
- HVAC Bid Information
- Solicitation number
- RFP - CSD - 240000000475
- Issued by
- Jackson County, Michigan
About this file
This document contains mechanical drawings and specifications for HVAC upgrades at Columbia Schools in Michigan. The project includes furnishing and installing new rooftop units, air handling units, and condensing units to replace previously demolished equipment at the Intermediate School and High School. The drawings provide key details on the layout of the new equipment, ductwork, piping, and other mechanical components. The sequence of operations describes how the HVAC systems will be controlled and integrated with the building automation system. This contract opportunity is being bid through Jackson County, Michigan.
The document does not provide pricing terms, set asides, incumbent information, funding sources, or other financial details. It focuses on the technical requirements and scope of work for the HVAC upgrades at the two school facilities.
View the file
Other files
Show all 11
On GovTribe
Work with this file
- Download the original file
- Contacts named in this file
- Similar government files
- Ask GovTribe AI about this file
Text version
X-RTU
X-EF
X-EF
X-RTU
X-G
X-G
X-G
X-G
X-G
X-G
RTU-113
RTU-110
RTU-111
RTU-1
RTU-107
RTU-108
RTU-112
MECHANICAL KEY NOTES
1 FURNISH AND INSTALL NEW ROOFTOP UNIT IN LOCATION OF
PREVIOUSLY DEMOLISHED UNIT. PROVIDE MANUFACTURERS
CURB ADAPTER FOR INSTALLATION ON EXISTING CURB.
MODIFY SA AND RA DUCTWORK AS NECESSARY TO CONNECT
TO NEW RTU. EXTEND GAS PIPING AS REQUIRED FOR A
COMPLETE CONNECTION.
N
INTERMEDIATE SCHOOL - ROOF PLAN - MECHANICAL NEW (ADD ALTERNATE #1)
SCALE: 1/16" = 1'-0"
10510 4020
M A
T R
I X
X-6''Ø EA
X-6''Ø EA
X-6''Ø EA
X-6''Ø EA
X-10''Ø EA
X-10''Ø EA
X-6''Ø EA
X-6''Ø EA
X-6''Ø EA X-6''Ø EA
X-6''Ø EA
X-10''Ø EA
X-8''Ø SA
X-14''Ø SA
X-8''Ø SA
X-12''Ø SA
X-8''Ø SA
X-8''Ø SA
X-FCU-501
X-FCU-502
X-14''Ø V
THRU ROOF
X-14''Ø V
THRU ROOF
X-EF X-EF
X-SD 330
X-SD 330
--- TYP.2 X-SD 330
--- TYP.2
330X-SD
X-EG 150
6''x6'' ---
X-EG 175
6''x6'' ---
175X-EG
---6''x6''
350X-EG
TYP.28''x8''
75X-EG
---6''x6''
75X-EG
---6''x6'' 100X-SD
---8''Ø
100X-SD
---8''Ø
X-10''x20''
OA DN
X-LOUVER
X-54''x20'' OA DN X-56''x20'' RA
UP
X-6''Ø EA (TYP. 3) X-12''Ø EA
X-48''x20'' SA UP
X-CC-502
X-SG
X-RG
X-AHU-502
X-4'' G
X-1'' HS & HR
X-2'' HS & HR
SL & LL
TO CU-502
SL & LL UP THRU
ROOF TO CU-2
SL & LL UP THRU
ROOF TO CU-3
3/4'' CD 3/4'' CD
MECHANICAL KEY NOTES
1 FURNISH AND INSTALL NEW DX COOLING COIL IN EXISTING FAN
COIL UNIT. ROUTE NEW REFRIGERANT PIPING THRU ROOF TO
NEW CONDENSING UNIT.
ROUTE NEW REFRIGERANT PIPING THRU WALL TO NEW
OUTDOOR CONDENSING UNIT.
M A
T R
I X
N
HIGH SCHOOL - PARTIAL FLOOR PLAN - UNIT 500 - MECHANICAL NEW (BASE BID)
SCALE: 1/8" = 1'-0"
0 1 5 10 20 N
HIGH SCHOOL - MEZZANINE PLAN - UNIT 500 - MECHANICAL NEW (BASE BID)
SCALE: 1/8" = 1'-0"
0 1 5 10 20
RTURTURTU
RTU
RTU RTU RTU
RTU
RTU
RTU
RTU
RTU
RTU
RTU
RTU RTU
RTU
RTU
RTU
RTU
RTU
RTU
CU
CU
CU
CU
CU
X-RTU
X-RTUX-RTU
X-RTU
X-RTU
X-RTUX-RTUX-RTU
X-RTU
X-RTU
X-RTU
X-RTU
X-RTU
X-RTU
X-RTU
X-RTU
X-RTU
X-RTU
X-RTU
X-EF X-EF
X-EF
X-1'' G
X-1'' G
X-2-1/2'' G
X-1'' G
X-4'' GX-2'' G
X-3'' G
TO X-CC-502
RTU-305
AHU-1
CU-1
CU-2
CU-3
RTU-304
X-DX
X-DX
CU-502
SL & LL DN THRU
ROOF TO X-FCU-501
SL & LL DN THRU
ROOF TO X-FCU-502
MECHANICAL KEY NOTES
1 FURNISH AND INSTALL NEW ROOFTOP UNIT IN LOCATION OF
PREVIOUSLY DEMOLISHED UNIT. PROVIDE MANUFACTURERS
CURB ADAPTER FOR INSTALLATION ON EXISTING CURB.
MODIFY SA AND RA DUCTWORK AS NECESSARY TO CONNECT
TO NEW RTU. EXTEND GAS PIPING AS REQUIRED FOR A
COMPLETE CONNECTION.
FURNISH AND INSTALL NEW AIR HANDLING UNIT IN LOCATION
OF PREVIOUSLY DEMOLISHED UNIT. PROVIDE
MANUFACTURERS CURB ADAPTER FOR INSTALLATION ON
EXISTING CURB. MODIFY SA AND RA DUCTWORK AS
NECESSARY TO CONNECT TO NEW AHU.
FURNISH AND INSTALL NEW CONDENSING UNIT IN LOCATION
SHOWN. ROUTE REFRIGERANT PIPING TO AHU-1.
FURNISH AND INSTALL NEW CONDENSING UNIT IN LOCATION
SHOWN. ROUTE REFRIGERANT PIPING TO ASSOCIATED INDOOR
EQUIPMENT.
N
HIGH SCHOOL - ROOF PLAN - MECHANICAL NEW (BASE BID)
SCALE: 1/32" = 1'-0"
0 51 10 25 80
M A
T R
UNIT 300
UNIT 200
UNIT 200
UNIT 300
UN
IT
UN
IT
UN
IT
UN
IT
X-UH
X-2-1/2'' HS & HR X-2'' HS & HR
X-4'' HS & HR
X-4'' HS & HR
X-3/4'' HS & HR
3'' HS & HR
PIPING KEY NOTES
INSTALL AND MODIFY NEW HEATING HOT WATER
SUPPLY AND RETURN PIPING AT LOCATION SHOWN.
BALANCE VALVE TO 34.5 GPM.
N INTERMEDIATE SCHOOL - PARTIAL FLOOR PLAN - UNIT 200 - PIPING NEW (ADD ALTERNATE #1)
M A
T R
I X
2'' HS & HR 1-1/2'' HS & HR 1-1/4'' HS & HR1-1/4'' HS & HR
1'' HS & HR
3/4'' HS & HR
3/4'' HS & HR3/4'' HS & HR
3/4'' HS & HR
UNIT 300
UNIT 200
UNIT 200
UNIT 300
X-UVX-UV
X-UV
X-1-1/4''
HS & HR
X-1-1/4''
HS & HR
X-2'' HS & HR
3/4'' HS & HR
VAV-1 VAV-2
VAV-4 VAV-6
VAV-5
VAV-3
3/4'' HS & HR 3/4'' HS & HR
PIPING KEY NOTES
MODIFY EXISTING HEATING HOT WATER SUPPLY AND
RETURN PIPING AT LOCATION SHOWN AS NEEDED TO
INSTALL NEW HEATING HOT WATER SUPPLY AND
RETURN PIPING.
N INTERMEDIATE SCHOOL - PARTIAL FLOOR PLAN - UNIT 100 - PIPING NEW (ADD ALTERNATE #1)
M A
T R
I X
ISOLATION
VALVES
FILTER DRYER
EXPANSION VALVE
(TYPICAL)
PITCH
EVAPORATOR COIL
L
CHARGING
VALVE
PITCH
CONDENSING UNIT
PITCH
S
SIGHT GLASS
NOTES:
1. PITCH ALL LINES MIN. 1/2" PER 10' IN
DIRECTION OF REFRIGERANT FLOW.
2. INSULATE SUCTION PIPING.
3. KEEP HORIZONTAL DISTANCE OF TRAPS TO
A MINIMUM.
4. PROVIDE TRAPS IF VERTICAL DISTANCE OF
PIPING EXCEEDS 8 FT.
EQUIPMENT MANUFACTURER TO PROVIDE
FACTORY APPROVED PIPING DETAIL VIA SHOP
DRAWINGS TO ENGINEER BEFORE CONSTRUCTION
BEGINS.
13 CONDENSING UNIT PIPING DIAGRAM
SCALE: NTS
TRAP
RECTANGULAR TRANSITIONS, OFFSETS,
AND ELBOWS
SCALE: NTS
RADIUS ELBOW
NOTE:
90° ELBOW SHOWN
SIMILAR RADIUS
CONSTRUCTION FOR
ALL ANGLES
R
R
OFFSET
ELBOW
FULL RADIUS
(R=W)
FLOW
AIR
TRANSITION - CONTRACTION FLOW
TRANSITION - DIVERGING FLOW
15°
FLOW
AIR
15°
W
W
W
R=1/ W
15°
15°
4 DUCT TRANSITION DETAIL
SCALE: NTS
L
W
SA FLOW
RA FLOW
MAIN AIR DUCT
BALANCING DAMPER IN ALL
SA AND RA BRANCHES TO
AIR OUTLETS
BRANCH AIR DUCT
(TYPICAL)
NOTE:
L=1/4 W (4" MIN.)
45°
TURNING VANES FOR
SQUARE ELBOW DETAIL
SCALE: NTS
FRAME
VANE ELBOW
LOCKING LUG
2-1/4"R
4-1/2"R
TURNING VANE
NOTES:
1. LOCKING LUGS INTEGRAL WITH VANE
2. MAXIMUM UNSUPPORTED VANE LENGTH 48"
3. FRAMES - BOLTED OR RIVETED TO ELBOW
4. VANES AND FRAMES - SAME GAUGE AS ELBOW
2 1 /4"
3 1 /2"
6 DUCT HANGER DETAIL
SCALE: NTSSCALE: NTSSCALE: NTS
HANGER STRAPS HANGER RODS
STRAP HANGER TRAPEZE HANGER
NO POP RIVETS ALLOWED, USE
SELF-TAPPING SHEET METAL SCREWS
ONLY (TYP)
5 DUCT TRANSITION DETAIL
SCALE: NTS
VD
NOTES:
1. "ALTERNATE" FITTINGS SHALL BE
ACCEPTABLE ONLY WHEN DUCT HEIGHT
DOES NOT PERMIT THE USE OF
"PERMITTED" FULL SIZE BELLMOUTH
CONNECTION
2. THIS DETAIL APPLIES TO SINGLE TAKEOFFS
TO DIFFUSER AS WELL AS BRANCH
TAKEOFFS. IT ALSO APPLIES TO TAKEOFFS
IN THE HORIZONTAL AS WELL AS THE
VERTICAL DIRECTION.
DUCT SIZE:
(SEE PLANS)
PREFERRED
TAKE-OFF DETAIL
STANDARD
45° RECTANGULAR
DUCT CONNECTION
(SUPPLY SHOWN,
RETURN/EXHAUST SIMILAR)
BELLMOUTH
CONNECTION
MANUAL VOLUME
DAMPER TYPICAL AT
ALL DUCT
TAKE-OFFS
MAIN DUCT
AIR FLOW
6" min.
2 SUPPLY AIR DIFFUSER DETAIL
SCALE: NTS
CONICAL TAKE-OFF WITH
VOLUME DAMPER (TYP)
SUPPLY AIR
BRANCH DUCT
FLEXIBLE DUCT
LAY-IN CLG TILE (TYP)
CEILING SUPPORT
TEE (TYP)
SUPPLY DIFFUSER
(SEE SCHEDULE FOR
TYPE)
COLLAR
HARD ELBOW
(AS REQ'D)
1 INSULATION DETAIL AT HANGER
SCALE: NTS
14 GAUGE ZINC COATED
SHEET STEEL SADDLE, AT
LEAST 12" LONG
PIPE
INSULATION
THERMAL HANGERS
SHIELD INSERTS (360-DEG)
9 ROOF TOP UNIT
SCALE: NTS
14" HIGH INSULATED
CURB W/ CANT STRIP
WEATHERTIGHT
FLASHING
INSULATION
UNION
GAS COCK
G
DIRT LEG
(TYP.2)
AD
RTU
FD
ROOF
PROVIDE AND INSTALL
CURB ADAPTER
(CONTRACTOR SHALL
FIELD VERIFY SIZE)
12 VAV TERMINAL UNIT DETAIL
SCALE: NTS
NOTES:
1. FLEXIBLE DUCTWORK SHALL NOT BE PERMITTED
UPSTREAM OF VAV BOXES.
2. DUCT TRANSITIONS SHALL BE A MINIMUM OF 3
DUCT DIAMETERS UPSTREAM OF ANY VAV BOX.
REDUCER OR INCREASER
IF REQUIRED
LINED SHEET METAL RUN-OUT
SIZE AS SHOWN ON PLAN 5 FT.
MIN. BEFORE TAKE OFF
SUPPLY DIFFUSER (SEE
SCHED. FOR TYPE)
COLLAR
FLEX ELBOW
DIFFUSER
NECK SIZE
FLEXIBLE DUCT
PROVIDE HANGER
CEILING
SHEET METAL RUN-OUT
SIZE AS SHOWN ON PLAN
BALANCE DAMPER
FLOW RING
TERMINAL UNIT
SUPPLY AIR
DUCT
CONICAL TAP.
RUNOUT SIZE
PER PLAN
TRANSITION AS
REQUIRED
3 DUCT
DIA. MIN.
5 DUCT DIA. MIN.
6'-0" MAX.
REHEAT COIL
TYPICAL VAV TERMINAL UNIT HYDRONIC
PIPING DIAGRAM (2-WAY CONTROL VALVE)
SCALE: NTS
COIL
HS
HR
3/4" HOSE END
DRAIN VALVE
2-WAY MODULATING
CONTROL VALVE
SHUTOFF VALVE (TYP.)
CIRCUIT SETTER
UNION (TYP)MANUAL AIR VENT
P/T TAP (TYP.)
STRAINER
HOSE END DRAIN VALVE
HS
HR
COIL
MANUAL AIR VENT
2-WAY MODULATING
CONTROL VALVE
BALANCE (TYP.)
CIRCUIT SETTER
SHUT-OFF VALVE
THERMOMETER (TYP.)
UNION (TYP.)
P/T TAP (TYP.)
STRAINER(TYP.)
11 AHU-1 HEATING COIL DETAIL
SCALE: NTS
PATE PIPE CURB (SEE DETAIL)
MIRO 6-HD STAND. SECURE TO ROOF
PER MAUFACTERER RECOMMENDATIONS
ROOF
FASTENING
SCREW
GRADUATED
STEP BOOT(S)
SATINLESS
STEEL CLAMPS
PIPE/CONDUIT
ACRYLIC CLAD
THERMOPLASTIC
COVER
2x2 NAILER
3# INSULATION
HEAVY GAGE GALV.
STEEL ROOF CURB
FLASH TO ROOF
WEATHERTIGHT
NOTE:
SEE PLANS FOR ROOF PENETRATIONS. PROVIDE CONDUIT AS REQUIRED TO ACCOMMODATE
ELECTRICAL AND TEMPERATURE CONTROL REQUIREMENTS OF MECHANICAL EQUIPMENT
3 PIPE CURB DETAIL
SCALE: NTS
M A
T R
SEQUENCE OF OPERATION: RTU -1, 101, 102, 103, 104, 107, 108, 110, 113, 304, 308
BUILDING AUTOMATION SYSTEM INTERFACE:
THE BUILDING AUTOMATION SYSTEM (BAS) SHALL SEND THE CONTROLLER OCCUPIED BYPASS, MORNING WARM-UP/PRE-COOL, OCCUPIED/UNOCCUPIED AND HEAT/COOL MODES. IF A BAS IS NOT PRESENT, OR COMMUNICATION IS LOST WITH THE BAS THE CONTROLLER SHALL OPERATE USING DEFAULT MODES AND
SETPOINTS.
OCCUPIED:
DURING OCCUPIED PERIODS, THE SUPPLY FAN SHALL RUN CONTINUOUSLY AND THE MIXED AIR DAMPERS SHALL OPEN TO MAINTAIN MINIMUM VENTILATION REQUIREMENTS. UPON A CALL FOR DX COOLING, THE UNIT CONTROLLER SHALL ENABLE THE FIRST FIXED SPEED COMPRESSOR. IF THE FIXED SPEED COMPRESSOR CANNOT SATISFY THE LOAD CONDITIONS, THE UNIT CONTROLLER SHALL START THE NEXT FIXED SPEED COMPRESSOR IN SEQUENCE TO ADD TO THE TOTAL UNIT COOLING LOAD PERCENTAGE. THIS PROCESS SHALL REPEAT UNTIL ALL OF THE FIXED SPEED COMPRESSORS HAVE BEEN STARTED OR UNTIL THE ACTIVE SPACE TEMPERATURE SETPOINT IS SATISFIED. IF ECONOMIZING IS ENABLED, THE OUTDOOR AIR OR MIXED AIR DAMPERS SHALL MODULATE TO MAINTAIN THE DISCHARGE AIR TEMPERATURE SETPOINT AND THE RELIEF AIR DAMPER SHALL TRACK THE MIXED AIR DAMPERS. THE DISCHARGE AIR TEMPERATURE SETPOINT SHALL BE DYNAMICALLY RESET BASED ON THE DEVIATION OF ACTUAL SPACE TEMPERATURE FROM THE ACTIVE SPACE TEMPERATURE SETPOINT.
IF THE DISCHARGE AIR TEMPERATURE SENSOR FAILS, THE DX COOLING AND THE GAS HEAT SHALL CONTROL TO MAINTAIN THE ACTIVE SPACE TEMPERATURE SETPOINT AND AN ALARM SHALL ANNUNCIATE AT THE BAS. IF THE DISCHARGE AIR TEMPERATURE SENSOR AND THE SPACE TEMPERATURE SENSOR FAIL, THE DX COOLING SHALL BE DISABLED, THE GAS HEAT SHALL BE DISABLED, AND AN ALARM SHALL ANNUNCIATE AT THE BAS.
UNOCCUPIED:
WHEN THE SPACE TEMPERATURE IS BELOW THE UNOCCUPIED HEATING SETPOINT OF 60.0 DEG. F (ADJ.) THE SUPPLY FAN SHALL BE COMMANDED ON, THE OUTSIDE AIR DAMPER SHALL REMAIN CLOSED AND THE GAS HEAT SHALL BE ENABLED. WHEN THE SPACE TEMPERATURE RISES ABOVE THE UNOCCUPIED HEATING SETPOINT OF
60.0 DEG. F (ADJ.) PLUS THE UNOCCUPIED DIFFERENTIAL OF 4.0 DEG. F (ADJ.) THE SUPPLY FAN SHALL STOP AND THE GAS HEAT SHALL BE DISABLED. WHEN THE SPACE TEMPERATURE IS ABOVE THE UNOCCUPIED COOLING SETPOINT OF 85.0 DEG. F (ADJ.) THE SUPPLY FAN SHALL BE COMMANDED ON, THE OUTSIDE AIR DAMPER SHALL OPEN IF ECONOMIZING IS ENABLED AND REMAIN CLOSED IF ECONOMIZING IS DISABLED AND THE DX COOLING SHALL BE ENABLED. WHEN THE SPACE TEMPERATURE FALLS BELOW THE UNOCCUPIED COOLING SETPOINT OF
85.0 DEG. F MINUS THE UNOCCUPIED DIFFERENTIAL OF 4.0 DEG. F (ADJ.) THE SUPPLY FAN SHALL STOP, THE DX
COOLING SHALL BE DISABLED AND THE OUTSIDE AIR DAMPER SHALL CLOSE.
OPTIMAL START:
THE BAS SHALL MONITOR THE SCHEDULED OCCUPIED TIME, OCCUPIED SPACE SETPOINTS AND SPACE
TEMPERATURE TO CALCULATE WHEN THE OPTIMAL START OCCURS.
OPTIMAL STOP:
THE BAS SHALL MONITOR THE SCHEDULED UNOCCUPIED TIME, OCCUPIED SETPOINTS AND SPACE TEMPERATURE TO CALCULATE WHEN THE OPTIMAL STOP OCCURS. WHEN THE OPTIMAL STOP MODE IS ACTIVE THE UNIT CONTROLLER SHALL MAINTAIN THE SPACE TEMPERATURE TO THE SPACE TEMPERATURE OFFSET SETPOINT.
OUTSIDE AIR DAMPER SHALL REMAIN ENABLED TO PROVIDE MINIMUM VENTILATION.
MORNING WARM-UP MODE:
DURING OPTIMAL START, IF THE SPACE TEMPERATURE IS BELOW THE OCCUPIED HEATING SETPOINT A MORNING WARM-UP MODE SHALL BE ACTIVATED. WHEN MORNING WARM-UP IS INITIATED THE UNIT SHALL ENABLE THE HEATING AND FAN(S). THE OUTSIDE AIR DAMPER SHALL REMAIN CLOSED. WHEN THE SPACE TEMPERATURE REACHES THE OCCUPIED HEATING SETPOINT (ADJ.), THE UNIT SHALL TRANSITION TO THE OCCUPIED MODE.
PRE-COOL MODE:
DURING OPTIMAL START, IF THE SPACE TEMPERATURE IS ABOVE THE OCCUPIED COOLING SETPOINT, PRE-COOL MODE SHALL BE ACTIVATED. WHEN PRE-COOL IS INITIATED THE UNIT SHALL ENABLE THE FAN AND COOLING OR ECONOMIZER. THE OUTSIDE AIR DAMPER SHALL REMAIN CLOSED, UNLESS ECONOMIZING. WHEN THE SPACE TEMPERATURE REACHES OCCUPIED COOLING SETPOINT (ADJ.), THE UNIT SHALL TRANSITION TO THE OCCUPIED
MODE.
OCCUPIED BYPASS:
THE BAS SHALL MONITOR THE STATUS OF THE ON AND CANCEL BUTTONS OF THE SPACE TEMPERATURE SENSOR.
WHEN AN OCCUPIED BYPASS REQUEST IS RECEIVED FROM A SPACE SENSOR, THE UNIT SHALL TRANSITION FROM ITS CURRENT OCCUPANCY MODE TO OCCUPIED BYPASS MODE AND THE UNIT SHALL MAINTAIN THE SPACE
TEMPERATURE TO THE OCCUPIED SETPOINTS (ADJ.).
HEAT/COOL MODE:
WHEN THE SPACE TEMPERATURE RISES ABOVE THE OCCUPIED COOLING SETPOINT THE MODE SHALL TRANSITION TO COOLING. WHEN THE SPACE TEMPERATURE FALLS BELOW THE OCCUPIED HEATING SETPOINT THE MODE SHALL TRANSITION TO HEATING. WHEN THE SPACE TEMPERATURE IS ABOVE THE OCCUPIED COOLING SETPOINT OR BELOW THE OCCUPIED HEATING SETPOINT THE MODE SHALL REMAIN IN ITS LAST STATE. IF THE SPACE TEMPERATURE SENSOR FAILS THE MODE SHALL REMAIN IN ITS LAST STATE AND AN ALARM SHALL ANNUNCIATE AT THE BAS. IF THE LOCAL AND COMMUNICATED SETPOINTS FAIL THE CONTROLLER SHALL DISABLE THE SUPPLY FAN
AND AN ALARM SHALL ANNUNCIATE AT THE BAS.
DEHUMIDIFICATION:
THE UNIT SHALL BE IN DEHUMIDIFICATION MODE IF THE RETURN HUMIDITY IS ABOVE THE DEHUMIDIFICATION SETPOINT. IN THE DEHUMIDIFICATION MODE, THE SUPPLY AIR FAN SHALL BE ENABLED, THE OUTSIDE AIR DAMPER SHALL BE COMMANDED TO MINIMUM POSITION, AND THE UNIT CONTROLLER SHALL ENERGIZE MECHANICAL
COOLING AND THE HOT GAS REHEAT SOLENOID.
MULTI-CIRCUIT UNITS: DURING DEHUMIDIFICATION MODE THE OUTSIDE AIR TEMPERATURE SHALL BE MONITORED.
IF THIS TEMPERATURE RISES ABOVE THE REHEAT CAPACITY LIMIT SETPOINT OR FALLS BELOW THE REHEAT CAPACITY LIMIT SETPOINT – 3.0 DEG. F (ADJ.), THE UNIT SHALL STAGE DOWN OR STAGE UP THE COMPRESSORS RESPECTIVELY TO MEET FULL OR PART LOAD CAPACITY REQUIREMENTS BASED ON AMBIENT TEMPERATURE.
FACTORY INSTALLED HOT GAS REHEAT SHALL ALLOW APPLICATION OF DEHUMIDIFICATION. DEHUMIDIFICATION SHALL BE ALLOWED ONLY WHEN THE OUTSIDE AIR TEMPERATURE IS ABOVE 40.0 DEG. F AND BELOW 100.0 DEG. F.
THE ECONOMIZER OUTSIDE AIR DAMPER SHALL DRIVE TO MINIMUM POSITION DURING DEHUMIDIFICATION.
MULTI-CIRCUIT UNITS: ON A CALL FOR DEHUMIDIFICATION, THE HOT GAS REHEAT VALVE IN CIRCUIT 1 SHALL ENERGIZE AND THE COMPRESSOR(S) SHALL ENABLE. WHEN THE HUMIDITY CONTROL SETPOINT IS SATISFIES, THE VALVE SHALL BE DE-ENERGIZED AND THE COMPRESSOR(S) IN CIRCUIT 1 SHALL BE DISABLED. IF THERE IS A CALL FOR 1ST STAGE COOLING WHILE IN THE DEHUMIDIFICATION MODE, NO ACTION SHALL TAKE PLACE. IF THERE IS A CALL FOR 2ND STAGE COOLING, THE HOT GAS REHEAT VALVE SHALL BE DE-ENERGIZED, AND THE UNIT SHALL REVERT TO THE COOLING MODE. IF 2ND STAGE COOLING IS SATISFIED AND THERE IS STILL A CALL FOR
DEHUMIDIFICATION, THE HOT GAS REHEAT VALVE SHALL ONCE AGAIN BE ENERGIZED.
ECONOMIZER:
ENABLE (COMPARATIVE ENTHALPY): OUTSIDE AIR (OA) ENTHALPY SHALL BE COMPARED WITH RETURN AIR (RA) ENTHALPY POINT. THE ECONOMIZER SHALL ENABLE WHEN OA ENTHALPY IS LESS THAN RA ENTHALPY - 2.0 BTU/LB.
THE ECONOMIZER SHALL DISABLE WHEN OA ENTHALPY IS GREATER THAN RA ENTHALPY.
OPERATION: THE SUPPLY AIR SENSOR SHALL MEASURE THE DRY BULB TEMPERATURE OF THE AIR LEAVING THE EVAPORATOR COIL WHILE ECONOMIZING. WHEN ECONOMIZING IS ENABLED AND THE UNIT IS OPERATING IN THE COOLING MODE, THE ECONOMIZER DAMPER SHALL MODULATE BETWEEN ITS MINIMUM POSITION AND 100% TO MAINTAIN THE SPACE TEMPERATURE SETPOINT. MINIMUM POSITION SHALL BE CALCULATED BASED ON SUPPLY FAN SPEED. IF THE SUPPLY AIR TEMPERATURE STARTS TO FALL BELOW SUPPLY AIR TEMPERATURE SETPOINT, THE OUTDOOR DAMPER SHALL BE AT MINIMUM POSITION. COMPRESSORS SHALL BE DELAYED FROM OPERATING
UNTIL THE ECONOMIZER HAS OPENED TO 100% FOR 5 MINUTES.
DEMAND CONTROL VENTILATION (DCV):
IF THE RETURN AIR CO2 LEVEL IS GREATER THAN OR EQUAL TO THE DESIGN MINIMUM CO2 SETPOINT, THE OUTDOOR AIR DAMPER SHALL OPEN TO THE DESIGN MINIMUM OUTDOOR AIR DAMPER SETPOINT. IF THERE IS A CALL FOR ECONOMIZER COOLING, THE DAMPER MAY BE OPENED FURTHER TO SATISFY THE COOLING REQUEST.
IF THE RETURN AIR CO2 LEVEL IS LESS THAN OR EQUAL TO THE DCV MINIMUM CO2 SETPOINT, THE OUTDOOR AIR DAMPER SHALL CLOSE TO THE DCV MINIMUM OUTDOOR AIR DAMPER SETPOINT. IF THERE IS A CALL FOR ECONOMIZER COOLING, THE DAMPER MAY BE OPENED FURTHER TO SATISFY THE COOLING REQUEST.
IF THE RETURN AIR CO2 LEVEL IS GREATER THAN THE DCV MINIMUM CO2 SETPOINT AND LESS THAN THE DESIGN MINIMUM CO2 SETPOINT, THE OUTDOOR AIR DAMPER POSITION SHALL BE MODULATED PROPORTIONALLY TO THE SPACE CO2 LEVEL RELATIVE TO A TARGET POSITION BETWEEN THE DCV MINIMUM CO2 SETPOINT AND THE DESIGN MINIMUM CO2 SETPOINT. IF THERE IS A CALL FOR ECONOMIZER COOLING, THE DAMPER MAY BE OPENED FURTHER
TO SATISFY THE COOLING REQUEST.
SUPPLY FAN:
THE UNIT CONTROLLER SHALL VARY THE SUPPLY FAN SPEED TO OPTIMIZE MINIMUM FAN SPEED IN ALL COOLING
AND HEATING MODES.
SUPPLY DUCT STATIC PRESSURE CONTROL:
THE UNIT CONTROLLER SHALL MODULATE THE SUPPLY FAN OUTPUT AS REQUIRED TO MAINTAIN THE SUPPLY DUCT STATIC PRESSURE SETPOINT. IF THE SUPPLY DUCT STATIC PRESSURE FALLS BELOW THE SUPPLY AIR STATIC SETPOINT + DEADBAND, THE UNIT CONTROLLER SHALL INCREASE THE OUTPUT TO THE SUPPLY FAN TO MAINTAIN SETPOINT. IF THE SUPPLY DUCT STATIC PRESSURE RISES ABOVE THE SUPPLY AIR STATIC SETPOINT + DEADBAND, THE UNIT CONTROLLER SHALL DECREASE THE OUTPUT TO THE SUPPLY FAN TO MAINTAIN SETPOINT.
RELIEF AIR AND BUILDING PRESSURE CONTROL:
THE RELIEF AIR FAN SHALL ENABLE WHEN THE ECONOMIZER DAMPER POSITION IS EQUAL TO OR GREATER THAN
THE RELIEF AIR FAN SETPOINT.
A DIFFERENTIAL PRESSURE SWITCH SHALL MONITOR THE DIFFERENTIAL PRESSURE ACROSS THE RELIEF AIR FAN.
IF THE SWITCH IS DETECTED TO BE OPEN FOR 40 CONSECUTIVE SECONDS AFTER A REQUEST FOR RELIEF FAN OPERATION A FAN FAILURE ALARM SHALL ANNUNCIATE AT THE BAS AND THE RELIEF FAN SHALL STOP. A MANUAL
RESET SHALL BE REQUIRED.
FILTER STATUS:
A DIFFERENTIAL PRESSURE SWITCH SHALL MONITOR THE DIFFERENTIAL PRESSURE ACROSS THE FILTER(S) WHEN THE FAN IS RUNNING. IF THE SWITCH CLOSES DURING NORMAL OPERATION A DIRTY FILTER ALARM SHALL
ANNUNCIATE AT THE BAS.
SMOKE DETECTOR SHUTDOWN:
THE UNIT SHALL SHUT DOWN IN RESPONSE TO A SIGNAL FROM THE SMOKE DETECTOR INDICATING THE PRESENCE OF SMOKE. THE SMOKE DETECTOR SHALL BE INTERLOCKED TO THE UNIT THROUGH THE DRY CONTACTS OF THE SMOKE DETECTOR. A MANUAL RESET OF THE SMOKE DETECTOR SHALL BE REQUIRED TO
RESTART THE UNIT.
CONDENSATE OVERFLOW SHUTDOWN:
THE UNIT SHALL SHUT DOWN IN RESPONSE TO A SIGNAL FROM THE CONDENSATE OVERFLOW SENSOR. THE SENSOR SHALL BE INTERLOCKED TO THE UNIT COOLING CONTROLLER FOR IMMEDIATE SHUTDOWN OF COOLING.
POINTS LIST: RTU -1, 101, 102, 103, 104, 107, 108, 110, 113, 304, 308
SYSTEM POINT DESCRIPTION POINTS ALARMS
NOTE: THE CONTROL POINTS FOR THE
ASSOCIATE EQUIPMENT INCLUDES, BUT IS NOT
LIMITED TO, THE FOLLOWING POINTS. THE
CONTROLS CONTRACTOR IS RESPONSIBLE FOR
PROVIDING ALL NECESSARY POINTS TO CONTROL
THE EQUIPMENT PER THE SEQUENCE OF
OPERATION.
GR
AP
HI
C
AN
AL
OG
H
AR
DW
AR
E
IN
PU
T (A
I)
BI
NA
RY
H
AR
DW
AR
E
IN
PU
T
(B I)
AN
AL
OG
H
AR
DW
AR
E
OU
TP
UT
(A
O)
BI
NA
RY
H
AR
DW
AR
E
OU
TP
UT
(B O)
SO
FT
W
AR
E
PO
IN
T
(S
FT
HA
RD
W
AR
E
IN
TE
RL
OC
K (H
DW
W
IR
EL
ES
S (W
LS
NE
TW
OR
K
(N
ET
HI
GH
A
NA
LO
G
LIM
IT
LO
W A
NA
LO
G
LIM
IT
BI
NA
RY
LA
TC
H
DI
AG
NO
ST
IC
SE
NS
OR
F
AI
L
CO
MM
UN
IC
AT
IO
N
FA
IL
COMPRESSOR 1 MODULATION COMMAND
CMP1
X X
COMPRESSOR 2 COMMAND
CMP2
X X
COMPRESSOR 3 COMMAND
CMP3
X X
CONDENSATE OVERFLOW DETECTION LOCAL
CND OVRFL
X X X
COOLING OUTPUT COMMAND
CLG
X X
DISCHARGE AIR TEMPERATURE
DAT
X X X
DX COIL FROST STAT
FROSTAT
X X X
HEATING OUTPUT COMMAND
HTG
X X
HOT GAS REHEAT VALVE COMMAND
HGRH
X X
MIXED AIR DAMPER
MAD
X X
OUTSIDE AIR DAMPER COMMAND
OAD
X X
OUTSIDE AIR HUMIDITY LOCAL
OAH
X X X
OUTSIDE AIR TEMPERATURE LOCAL
OAT
X X X
PRIMARY FILTER STATUS LOCAL
FIL
X X X
RELIEF AIR FAN START/STOP
RLF
X X
RELIEF AIR FAN STATUS LOCAL
RLF
X X
RETURN AIR CO2 LOCAL
RA CO2
X X X
RETURN AIR HUMIDITY LOCAL
RAH
X X X
RETURN AIR SMOKE DETECTION LOCAL
RA SD
X
RETURN AIR TEMPERATURE LOCAL
RAT
X X X
SPACE TEMPERATURE LOCAL (WIRED)
SPT
X X X X
SPACE TEMPERATURE SETPOINT LOCAL (WIRED)
SPT SP
X X
SUPPLY AIR SMOKE DETECTION LOCAL
SA SD
X
SUPPLY FAN SPEED
SAF
X
SUPPLY FAN START/STOP
SAF
X X
SUPPLY FAN STATUS LOCAL
SAF
X X
APPLICATION MODE
APP MODE
X
BAS COMMUNICATION STATE
BAS COM
X X
COMPRESSOR ENABLE
CMP ENA
X X
COMPRESSOR LOCKOUT STATUS
CMP LCK
X
COOL OUTPUT
CLG
X
DISCHARGE AIR STATIC PRESSURE SETPOINT
DA SP SPT
X X
ECONOMIZER ENABLE
ECON ENA
X
ECONOMIZER MINIMUM POSITION SETPOINT
ECON MIN POS SP
X X
FAN MODE COMMAND
FAN MODE
X
FILTER TIMER HOURS
FIL HRS
X
HEAT / COOL MODE REQUEST
H/C REQ
X X
HEAT OUTPUT
HTG
X
OCCUPANCY
OCC
X X
OCCUPIED COOLING SETPOINT
OCC CLG SP
X X
SPACE CO2 HIGH LIMIT
SP CO2 HL
X
SPACE TEMPERATURE SETPOINT ACTIVE
SPT SP ACT
X X
TIMED OVERRIDE STATUS
TOV
X
UNOCCUPIED COOLING SETPOINT
UNOCC CLG SP
X X
UNOCCUPIED HEATING SETPOINT
UNOCC HTG SP
X X
1 SZ VAV RTU FLOW DIAGRAM
RAT (AI)
SAF (BI)
RAH (AI)
SAF (AO)
SAF (BO)
RA SD (HDW)
CMP1 (BO)
CMP2 (BO)
CMP3 (BO)
CND OVRFL (BI)OAT (AI)
MAD (AO)
SA SD (HDW)
RLF (BI)
HTG (AO)HGRH (BO)
OAH (AI)
FIL (BI)
SPT (AI)
SPT SP (AI)
FROSTAT (BI)
RA CO2 (AI)RLF (BO)
DAT (AI)
T
DPT
RA
H
VSD
SD
D
T
ACT
RLF
SD
DPT
H
DPT
DA
T
LLT
D
D
CO2
MS
OA
T
M A
T R
SEQUENCE OF OPERATION: RTU-111 & RTU-112
BUILDING AUTOMATION SYSTEM INTERFACE:
THE BUILDING AUTOMATION SYSTEM (BAS) SHALL SEND THE CONTROLLER OCCUPIED BYPASS, MORNING WARM-UP/PRE-COOL, OCCUPIED/UNOCCUPIED AND HEAT/COOL MODES. THE BAS SHALL ALSO SEND THE DISCHARGE AIR TEMPERATURE SETPOINT AND THE DUCT STATIC PRESSURE SETPOINT. IF A BAS IS NOT PRESENT, OR COMMUNICATION IS LOST WITH THE BAS THE CONTROLLER SHALL OPERATE USING DEFAULT MODES AND
SETPOINTS.
OCCUPIED:
DURING OCCUPIED PERIODS, THE SUPPLY FAN SHALL RUN CONTINUOUSLY AND THE MIXED AIR DAMPERS SHALL OPEN TO MAINTAIN MINIMUM VENTILATION REQUIREMENTS. THE UNIT CONTROLLER SHALL CONTROL THE SUPPLY FAN SPEED TO MAINTAIN THE CURRENT SUPPLY DUCT STATIC PRESSURE SETPOINT (ADJ.). UPON A CALL FOR DX COOLING, THE UNIT CONTROLLER SHALL ENABLE THE FIRST FIXED SPEED COMPRESSOR. IF THE FIXED SPEED COMPRESSOR CANNOT SATISFY THE LOAD CONDITIONS, THE UNIT CONTROLLER SHALL START THE NEXT FIXED SPEED COMPRESSOR IN SEQUENCE TO ADD TO THE TOTAL UNIT COOLING LOAD PERCENTAGE. THIS PROCESS SHALL REPEAT UNTIL ALL OF THE FIXED SPEED COMPRESSORS HAVE BEEN STARTED OR UNTIL THE ACTIVE SPACE TEMPERATURE SETPOINT IS SATISFIED. IF ECONOMIZING IS ENABLED, THE OUTDOOR AIR OR MIXED AIR DAMPERS SHALL MODULATE TO MAINTAIN THE DISCHARGE AIR TEMPERATURE SETPOINT AND THE RELIEF AIR DAMPER SHALL TRACK THE MIXED AIR DAMPERS. IF THE DISCHARGE AIR TEMPERATURE SENSOR FAILS, THE DX COOLING SHALL BE DISABLED, THE GAS HEAT SHALL BE DISABLED, AND AN ALARM SHALL ANNUNCIATE AT THE
BAS.
UNOCCUPIED:
WHEN THE SPACE TEMPERATURE IS BELOW THE UNOCCUPIED HEATING SETPOINT OF 60.0 DEG. F (ADJ.) THE SUPPLY FAN SHALL BE COMMANDED ON, THE OUTSIDE AIR DAMPER SHALL REMAIN CLOSED AND THE GAS HEAT SHALL BE ENABLED. WHEN THE SPACE TEMPERATURE RISES ABOVE THE UNOCCUPIED HEATING SETPOINT OF
60.0 DEG. F (ADJ.) PLUS THE UNOCCUPIED DIFFERENTIAL OF 4.0 DEG. F (ADJ.) THE SUPPLY FAN SHALL STOP AND THE GAS HEAT SHALL BE DISABLED. WHEN THE SPACE TEMPERATURE IS ABOVE THE UNOCCUPIED COOLING SETPOINT OF 85.0 DEG. F (ADJ.) THE SUPPLY FAN SHALL BE COMMANDED ON, THE OUTSIDE AIR DAMPER SHALL OPEN IF ECONOMIZING IS ENABLED AND REMAIN CLOSED IF ECONOMIZING IS DISABLED AND THE DX COOLING SHALL BE ENABLED. WHEN THE SPACE TEMPERATURE FALLS BELOW THE UNOCCUPIED COOLING SETPOINT OF
85.0 DEG. F MINUS THE UNOCCUPIED DIFFERENTIAL OF 4.0 DEG. F (ADJ.) THE SUPPLY FAN SHALL STOP, THE DX
COOLING SHALL BE DISABLED AND THE OUTSIDE AIR DAMPER SHALL CLOSE.
OPTIMAL START:
THE BAS SHALL MONITOR THE SCHEDULED OCCUPIED TIME, OCCUPIED SPACE SETPOINTS AND SPACE
TEMPERATURE TO CALCULATE WHEN THE OPTIMAL START OCCURS.
OPTIMAL STOP:
THE BAS SHALL MONITOR THE SCHEDULED UNOCCUPIED TIME, OCCUPIED SETPOINTS AND SPACE TEMPERATURE TO CALCULATE WHEN THE OPTIMAL STOP OCCURS. WHEN THE OPTIMAL STOP MODE IS ACTIVE THE UNIT CONTROLLER SHALL MAINTAIN THE SPACE TEMPERATURE TO THE SPACE TEMPERATURE OFFSET SETPOINT.
OUTSIDE AIR DAMPER SHALL REMAIN ENABLED TO PROVIDE MINIMUM VENTILATION.
MORNING WARM-UP MODE:
DURING OPTIMAL START, IF THE AVERAGE SPACE TEMPERATURE IS BELOW THE OCCUPIED HEATING SETPOINT A MORNING WARM-UP MODE SHALL BE ACTIVATED. WHEN MORNING WARM-UP IS INITIATED THE UNIT SHALL ENABLE THE HEATING AND FAN(S). THE OUTSIDE AIR DAMPER SHALL REMAIN CLOSED. WHEN THE SPACE TEMPERATURE REACHES THE OCCUPIED HEATING SETPOINT (ADJ.), THE UNIT SHALL TRANSITION TO THE OCCUPIED MODE.
PRE-COOL MODE:
DURING OPTIMAL START, IF THE AVERAGE SPACE TEMPERATURE IS ABOVE THE OCCUPIED COOLING SETPOINT, PRE-COOL MODE SHALL BE ACTIVATED. WHEN PRE-COOL IS INITIATED THE UNIT SHALL ENABLE THE FAN AND COOLING OR ECONOMIZER. THE OUTSIDE AIR DAMPER SHALL REMAIN CLOSED, UNLESS ECONOMIZING. WHEN THE SPACE TEMPERATURE REACHES OCCUPIED COOLING SETPOINT (ADJ.), THE UNIT SHALL TRANSITION TO THE
OCCUPIED MODE.
OCCUPIED BYPASS:
THE BAS SHALL MONITOR THE STATUS OF THE ON AND CANCEL BUTTONS OF THE SPACE TEMPERATURE SENSORS. WHEN AN OCCUPIED BYPASS REQUEST IS RECEIVED FROM A SPACE SENSOR, THE UNIT SHALL TRANSITION FROM ITS CURRENT OCCUPANCY MODE TO OCCUPIED BYPASS MODE AND THE UNIT SHALL MAINTAIN
THE SPACE TEMPERATURE TO THE OCCUPIED SETPOINTS (ADJ.).
HEAT/COOL MODE:
COOLING: THE UNIT CONTROLLER SHALL USE THE DISCHARGE AIR TEMPERATURE SENSOR AND DISCHARGE AIR TEMPERATURE COOLING SETPOINT TO DETERMINE WHEN TO INITIATE REQUESTS FOR COOLING. DISCHARGE AIR
SETPOINT SHALL BE MAINTAINED BY CONTROLLING THE COOLING AS REQUIRED.
HEATING: THE UNIT CONTROLLER SHALL USE THE DISCHARGE AIR TEMPERATURE SENSOR AND DISCHARGE AIR TEMPERATURE HEATING SETPOINT TO DETERMINE WHEN TO INITIATE REQUESTS FOR HEATING. DISCHARGE AIR SETPOINT SHALL BE MAINTAINED BY CONTROLLING THE HEATING AS REQUIRED. DURING UNOCCUPIED HEATING OR MORNING WARM-UP MODE, THE UNIT HEAT REQUEST SHALL BE COMMUNICATED TO THE SYSTEM VAVS PRIOR TO COMMENCING HEATING OPERATION TO ALLOW VAV UNITS TO OPEN. THE VARIABLE SPEED DRIVE SHALL BE COMMANDED TO 100% AND THE HEAT SHALL BE STAGED ON AND OFF TO SATISFY THE ZONE TEMPERATURE
SETPOINT.
DISCHARGE AIR TEMPERATURE RESET CONTROL:
THE DISCHARGE AIR TEMPERATURE SETPOINT SHALL BE RESET TO THE OPTIMAL SETPOINT COMMUNICATED BY THE BAS. THE BAS SHALL RESET THE DISCHARGE AIR TEMPERATURE SETPOINT BASED ON THE CURRENT OUTSIDE AIR TEMPERATURE, BUT SHALL OVERRIDE THIS RESET FUNCTION AND RETURN THE DISCHARGE AIR TEMPERATURE SETPOINT TO 55.0 DEG. F (ADJ.) IF MORE THAN TWO (ADJ.) ZONES BEGIN TO OVERHEAT. ALSO, THE BAS SHALL OVERRIDE THIS RESET FUNCTION WHENEVER OUTDOOR DEW POINT IS HIGHER THAN 60.0 DEG. F (ADJ.)
OR INDOOR HUMIDITY IS HIGHER THAN 60% RH (ADJ.). IF THE DISCHARGE AIR TEMPERATURE DROPS BELOW THE MINIMUM LIMIT, A LOW TEMPERATURE ALARM SHALL ANNUNCIATE AND THE UNIT SHALL SHUT DOWN. IF THE DISCHARGE AIR TEMPERATURE RISES ABOVE THE MAXIMUM LIMIT, A HIGH TEMPERATURE ALARM SHALL
ANNUNCIATE.
DEHUMIDIFICATION:
THE UNIT SHALL BE IN DEHUMIDIFICATION MODE IF THE RETURN HUMIDITY IS ABOVE THE DEHUMIDIFICATION SETPOINT. IN THE DEHUMIDIFICATION MODE, THE SUPPLY AIR FAN SHALL BE ENABLED, THE OUTSIDE AIR DAMPER SHALL BE COMMANDED TO MINIMUM POSITION, AND THE UNIT CONTROLLER SHALL ENERGIZE MECHANICAL
COOLING AND THE HOT GAS REHEAT SOLENOID.
MULTI-CIRCUIT UNITS: DURING DEHUMIDIFICATION MODE THE OUTSIDE AIR TEMPERATURE SHALL BE MONITORED.
IF THIS TEMPERATURE RISES ABOVE THE REHEAT CAPACITY LIMIT SETPOINT OR FALLS BELOW THE REHEAT CAPACITY LIMIT SETPOINT – 3.0 DEG. F (ADJ.), THE UNIT SHALL STAGE DOWN OR STAGE UP THE COMPRESSORS RESPECTIVELY TO MEET FULL OR PART LOAD CAPACITY REQUIREMENTS BASED ON AMBIENT TEMPERATURE.
FACTORY INSTALLED HOT GAS REHEAT SHALL ALLOW APPLICATION OF DEHUMIDIFICATION. DEHUMIDIFICATION SHALL BE ALLOWED ONLY WHEN THE OUTSIDE AIR TEMPERATURE IS ABOVE 40.0 DEG. F AND BELOW 100.0 DEG. F.
THE ECONOMIZER OUTSIDE AIR DAMPER SHALL DRIVE TO MINIMUM POSITION DURING DEHUMIDIFICATION.
MULTI-CIRCUIT UNITS: ON A CALL FOR DEHUMIDIFICATION, THE HOT GAS REHEAT VALVE IN CIRCUIT 1 SHALL ENERGIZE AND THE COMPRESSOR(S) SHALL ENABLE. WHEN THE HUMIDITY CONTROL SETPOINT IS SATISFIES, THE VALVE SHALL BE DE-ENERGIZED AND THE COMPRESSOR(S) IN CIRCUIT 1 SHALL BE DISABLED. IF THERE IS A CALL FOR 1ST STAGE COOLING WHILE IN THE DEHUMIDIFICATION MODE, NO ACTION SHALL TAKE PLACE. IF THERE IS A CALL FOR 2ND STAGE COOLING, THE HOT GAS REHEAT VALVE SHALL BE DE-ENERGIZED, AND THE UNIT SHALL REVERT TO THE COOLING MODE. IF 2ND STAGE COOLING IS SATISFIED AND THERE IS STILL A CALL FOR
DEHUMIDIFICATION, THE HOT GAS REHEAT VALVE SHALL ONCE AGAIN BE ENERGIZED.
ECONOMIZER:
ENABLE (COMPARATIVE ENTHALPY): OUTSIDE AIR (OA) ENTHALPY SHALL BE COMPARED WITH RETURN AIR (RA) ENTHALPY POINT. THE ECONOMIZER SHALL ENABLE WHEN OA ENTHALPY IS LESS THAN RA ENTHALPY - 2.0 BTU/LB.
THE ECONOMIZER SHALL DISABLE WHEN OA ENTHALPY IS GREATER THAN RA ENTHALPY.
OPERATION: THE SUPPLY AIR SENSOR SHALL MEASURE THE DRY BULB TEMPERATURE OF THE AIR LEAVING THE EVAPORATOR COIL WHILE ECONOMIZING. WHEN ECONOMIZING IS ENABLED AND THE UNIT IS OPERATING IN THE COOLING MODE, THE ECONOMIZER DAMPER SHALL BE MODULATED BETWEEN ITS MINIMUM POSITION AND 100% TO MAINTAIN THE DISCHARGE AIR TEMPERATURE SETPOINT. THE ECONOMIZER DAMPER SHALL MODULATE TOWARD MINIMUM POSITION IN THE EVENT THE DISCHARGE AIR TEMPERATURE FALLS BELOW THE DISCHARGE LOW LIMIT TEMPERATURE SETPOINT. COMPRESSORS SHALL BE DELAYED FROM OPERATING UNTIL THE
ECONOMIZER HAS OPENED TO 100%.
DEMAND CONTROL VENTILATION (DCV):
IF THE RETURN AIR CO2 LEVEL IS GREATER THAN OR EQUAL TO THE DESIGN MINIMUM CO2 SETPOINT, THE OUTDOOR AIR DAMPER SHALL OPEN TO THE DESIGN MINIMUM OUTDOOR AIR DAMPER SETPOINT. IF THERE IS A CALL FOR ECONOMIZER COOLING, THE DAMPER MAY BE OPENED FURTHER TO SATISFY THE COOLING REQUEST.
IF THE RETURN AIR CO2 LEVEL IS LESS THAN OR EQUAL TO THE DCV MINIMUM CO2 SETPOINT, THE OUTDOOR AIR
DAMPER SHALL CLOSE TO THE DCV MINIMUM OUTDOOR AIR DAMPER SETPOINT. IF THERE IS A CALL FOR ECONOMIZER COOLING, THE DAMPER MAY BE OPENED FURTHER TO SATISFY THE COOLING REQUEST.
IF THE RETURN AIR CO2 LEVEL IS GREATER THAN THE DCV MINIMUM CO2 SETPOINT AND LESS THAN THE DESIGN MINIMUM CO2 SETPOINT, THE OUTDOOR AIR DAMPER POSITION SHALL BE MODULATED PROPORTIONALLY TO THE SPACE CO2 LEVEL RELATIVE TO A TARGET POSITION BETWEEN THE DCV MINIMUM CO2 SETPOINT AND THE DESIGN MINIMUM CO2 SETPOINT. IF THERE IS A CALL FOR ECONOMIZER COOLING, THE DAMPER MAY BE OPENED FURTHER
TO SATISFY THE COOLING REQUEST.
SUPPLY FAN:
THE SUPPLY FAN SHALL BE ENABLED WHILE IN THE OCCUPIED MODE AND CYCLED ON DURING THE UNOCCUPIED
MODE.
SUPPLY DUCT STATIC PRESSURE CONTROL:
DURING THE OCCUPIED MODE THE UNIT CONTROLLER SHALL MODULATE THE OUTPUT TO THE VARIABLE SPEED DRIVE AS REQUIRED TO MAINTAIN THE SUPPLY DUCT STATIC PRESSURE SETPOINT OF 1.5 INCHES OF W.C. (ADJ.).
IF THE SUPPLY DUCT STATIC PRESSURE FALLS BELOW 1.3 INCHES OF W.C. (ADJ.) THE UNIT CONTROLLER SHALL INCREASE THE OUTPUT TO THE VARIABLE SPEED DRIVE TO MAINTAIN SETPOINT. IF THE SUPPLY DUCT STATIC PRESSURE RISES ABOVE 1.7 INCHES OF W.C. (ADJ.) THE UNIT CONTROLLER SHALL DECREASE THE OUTPUT TO THE VARIABLE SPEED DRIVE TO MAINTAIN SETPOINT. UPON A CALL FOR HEATING OR COOLING IN THE UNOCCUPIED MODE THE UNIT CONTROLLER SHALL MODULATE THE SPEED OF THE VARIABLE SPEED DRIVE TO 100%.
STATIC PRESSURE HIGH LIMIT:
IF FOR ANY REASON THE SUPPLY AIR PRESSURE EXCEEDS THE SUPPLY AIR PRESSURE HIGH LIMIT, THE SUPPLY FAN SHALL SHUT DOWN. THE UNIT SHALL BE ALLOWED TO RESTART THREE TIMES AFTER A 15 MINUTE OFF PERIOD. IF THE OVERPRESSURIZATION CONDITION OCCURS ON THE FOURTH RESTART, THE UNIT SHALL SHUT DOWN AND A MANUAL RESET DIAGNOSTIC IS DISPLAYED AT THE REMOTE PANEL AND/OR THE BAS SYSTEM.
RELIEF AIR AND BUILDING PRESSURE CONTROL:
THE RELIEF AIR FAN SHALL ENABLE WHEN THE ECONOMIZER DAMPER POSITION IS EQUAL TO OR GREATER THAN
THE RELIEF AIR FAN SETPOINT.
A DIFFERENTIAL PRESSURE SWITCH SHALL MONITOR THE DIFFERENTIAL PRESSURE ACROSS THE RELIEF AIR FAN.
IF THE SWITCH IS DETECTED TO BE OPEN FOR 40 CONSECUTIVE SECONDS AFTER A REQUEST FOR RELIEF FAN OPERATION A FAN FAILURE ALARM SHALL ANNUNCIATE AT THE BAS AND THE RELIEF FAN SHALL STOP. A MANUAL
RESET SHALL BE REQUIRED.
FILTER STATUS:
A DIFFERENTIAL PRESSURE SWITCH SHALL MONITOR THE DIFFERENTIAL PRESSURE ACROSS THE FILTER(S) WHEN THE FAN IS RUNNING. IF THE SWITCH CLOSES DURING NORMAL OPERATION A DIRTY FILTER ALARM SHALL
ANNUNCIATE AT THE BAS.
SMOKE DETECTOR SHUTDOWN:
THE UNIT SHALL SHUT DOWN IN RESPONSE TO A SIGNAL FROM THE SMOKE DETECTOR INDICATING THE PRESENCE OF SMOKE. THE SMOKE DETECTOR SHALL BE INTERLOCKED TO THE UNIT THROUGH THE DRY CONTACTS OF THE SMOKE DETECTOR. A MANUAL RESET OF THE SMOKE DETECTOR SHALL BE REQUIRED TO
RESTART THE UNIT.
CONDENSATE OVERFLOW SHUTDOWN:
THE UNIT SHALL SHUT DOWN IN RESPONSE TO A SIGNAL FROM THE CONDENSATE OVERFLOW SENSOR. THE SENSOR SHALL BE INTERLOCKED TO THE UNIT COOLING CONTROLLER FOR IMMEDIATE SHUTDOWN OF COOLING.
POINTS LIST: RTU-111 & RTU-112
SYSTEM POINT DESCRIPTION POINTS ALARMS
NOTE: THE CONTROL POINTS FOR THE ASSOCIATE
EQUIPMENT INCLUDES, BUT IS NOT LIMITED TO, THE
FOLLOWING POINTS. THE CONTROLS CONTRACTOR
IS RESPONSIBLE FOR PROVIDING ALL NECESSARY
POINTS TO CONTROL THE EQUIPMENT PER THE
SEQUENCE OF OPERATION.
GR
AP
HI
C
AN
AL
OG
H
AR
DW
AR
E
IN
PU
T (A
I)
BI
NA
RY
H
AR
DW
AR
E
IN
PU
T
(B I)
AN
AL
OG
H
AR
DW
AR
E
OU
TP
UT
(A
O)
BI
NA
RY
H
AR
DW
AR
E
OU
TP
UT
(B O)
SO
FT
W
AR
E
PO
IN
T
(S
FT
HA
RD
W
AR
E
IN
TE
RL
OC
K (H
DW
W
IR
EL
ES
S (W
LS
NE
TW
OR
K
(N
ET
HI
GH
A
NA
LO
G
LIM
IT
LO
W A
NA
LO
G
LIM
IT
BI
NA
RY
LA
TC
H
DI
AG
NO
ST
IC
SE
NS
OR
F
AI
L
CO
MM
UN
IC
AT
IO
N
FA
IL
COMPRESSOR 1 MODULATION COMMAND
CMP1
X X
COMPRESSOR 2 COMMAND
CMP2
X X
COMPRESSOR 3 COMMAND
CMP3
X X
CONDENSATE OVERFLOW DETECTION LOCAL
CND OVRFL
X X X
COOLING OUTPUT COMMAND
CLG
X X
DISCHARGE AIR STATIC PRESSURE LOCAL
DA SP
X X X X
DISCHARGE AIR TEMPERATURE
DAT
X X X
DX COIL FROST STAT
FROSTAT
X X X
HEATING OUTPUT COMMAND
HTG
X X
HOT GAS REHEAT VALVE COMMAND
HGRH
X X
MIXED AIR DAMPER
MAD
X X
OUTSIDE AIR DAMPER COMMAND
OAD
X X
OUTSIDE AIR HUMIDITY LOCAL
OAH
X X X
OUTSIDE AIR TEMPERATURE LOCAL
OAT
X X X
PRIMARY FILTER STATUS LOCAL
FIL
X X X
RELIEF AIR FAN START/STOP
RLF
X X
RELIEF AIR FAN STATUS LOCAL
RLF
X X
RETURN AIR CO2 LOCAL
RA CO2
X X X
RETURN AIR HUMIDITY LOCAL
RAH
X X X
RETURN AIR SMOKE DETECTION LOCAL
RA SD
X
RETURN AIR TEMPERATURE LOCAL
RAT
X X X
SPACE TEMPERATURE (COMMUNICATED)
SPT
X X
SPACE TEMPERATURE SETPOINT (COMMUNICATED)
SPT SP
X X
SUPPLY AIR SMOKE DETECTION LOCAL
SA SD
X
SUPPLY FAN SPEED
SAF
X
SUPPLY FAN START/STOP
SAF
X X
SUPPLY FAN STATUS LOCAL
SAF
X X
APPLICATION MODE
APP MODE
X
BAS COMMUNICATION STATE
BAS COM
X X
COMPRESSOR ENABLE
CMP ENA
X X
COMPRESSOR LOCKOUT STATUS
CMP LCK
X
COOL OUTPUT
CLG
X
DISCHARGE AIR STATIC PRESSURE SETPOINT
DA SP SPT
X X
ECONOMIZER ENABLE
ECON ENA
X
ECONOMIZER MINIMUM POSITION SETPOINT
ECON MIN POS SP
X X
FAN MODE COMMAND
FAN MODE
X
FILTER TIMER HOURS
FIL HRS
X
HEAT / COOL MODE REQUEST
H/C REQ
X X
HEAT OUTPUT
HTG
X
OCCUPANCY
OCC
X X
OCCUPIED COOLING SETPOINT
OCC CLG SP
X X
SPACE CO2 HIGH LIMIT
SP CO2 HL
X
SPACE TEMPERATURE SETPOINT ACTIVE
SPT SP ACT
X X
TIMED OVERRIDE STATUS
TOV
X
UNOCCUPIED COOLING SETPOINT
UNOCC CLG SP
X X
UNOCCUPIED HEATING SETPOINT
UNOCC HTG SP
X X
1 VAV RTU FLOW DIAGRAM
RAT (AI)
SAF (BI)
RAH (AI)
SAF (AO)
SAF (BO)
RA SD (HDW)
CMP1 (BO)
CMP2 (BO)
CMP3 (BO)
CND OVRFL (BI)OAT (AI)
MAD (AO)
SA SD (HDW)
RLF (BI)
HTG (AO)HGRH (BO)
OAH (AI)
FIL (BI) FROSTAT (BI)
SPT (NET)
SPT SP (NET)
RA CO2 (AI)
DA SP (AI)
RLF (BO)
DAT (AI)
T
DPT
RA
H
VSD
SD
D
T
ACT
RLF
SD
DPT
H
DPT
DA
LLT
T
D
D
CO2
DPT
MS
OA
T
M A
T R
| A000-2252100 |
| M100-2252100 |
| M300-2252100 |
| M301-2252100 |
| M302-2252100 |
| M303-2252100 |
| M304-2252100 |
| M305-2252100 |
| M400-2252100 |
| M401-2252100 |
| M402-2252100 |
| M403-2252100 |
| M404-2252100 |
| M600-2252100 |
| M601-2252100 |
| M800-2252100 |
| M801-2252100 |
| M802-2252100 |
| M803-2252100 |
| M804-2252100 |
| M900-2252100 |