22521.00 - Columbia Schools HVAC Upgrades - Mechanical Set - 1 of 3.pdf
PDF 5 MB Posted
- Attached to
- HVAC Bid Information
- Solicitation number
- RFP - CSD - 240000000475
- Issued by
- Jackson County, Michigan
About this file
This document is a set of mechanical and electrical drawings for HVAC upgrades at the Columbia Schools in Brooklyn, Michigan. The project involves the replacement of rooftop HVAC units, modification of ductwork and piping, and rebalancing of existing systems at the Columbia Intermediate School and Columbia Elementary School. The drawings include a drawing index, general HVAC notes, and mechanical/electrical symbols. Demolition plans and new work plans are provided. The project is identified as Matrix Project Number 22521.00.
The drawings indicate that the HVAC upgrades will be bid as base bids and add alternates. Bid information for this opportunity is included in a separate document. Contractors will need to coordinate the work with other trades and comply with local building codes and regulations. The contractor will also be responsible for maintaining equipment in new condition during construction.
View the file
Other files
Show all 11
On GovTribe
Work with this file
- Download the original file
- Contacts named in this file
- Similar government files
- Ask GovTribe AI about this file
Text version
COLUMBIA SCHOOLS
COLUMBIA SCHOOL DISTRICT - HVAC UPGRADES
MECHANICAL AND PLUMBING DRAWING INDEX ELECTRICAL DRAWING INDEX
11775 HEWITT RD.
BROOKLYN, MI 49230
MATRIX PROJECT NUMBER: 22521.00
DRAWING INDEX
MECHANICAL/ELECTRICAL ENGINEER
COLUMBIA INTERMEDIATE SCHOOL
COLUMBIA ELEMENTARY SCHOOL
BIDDING DESCRIPTION
M A
T R
I X
GENERAL HVAC NOTES
1. LOCATE EXHAUST OUTLETS OF VENTILATION SYSTEMS,
COMBUSTION EQUIPMENT STACKS, MEDICAL-SURGICAL
VACUUM SYSTEMS, & PLUMBING VENTS AT LEAST 10 FEET
FROM OUTDOOR AIR INTAKES.
2. INSTALL ALL EQUIPMENT, MATERIALS, AND ACCESSORIES PER
MANUFACTURERS WRITTEN INSTRUCTIONS.
3. BOTTOM OF EQUIPMENT ON ROOF SHALL BE A MINIMUM OF 12"
ABOVE ROOF MEMBRANE. CONTRACTOR SHALL COORDINATE
ASSOCIATED ROOF CURB HEIGHT AS REQUIRED.
4. ALL EXISTING SYSTEMS (INCLUDING EXHAUST FANS; AIR
HANDLING UNITS; PUMPS) THAT SERVES AREAS BEING
RENOVATED SHALL BE REBALANCED AS REQUIRED.
5. NOTIFY OWNER OF ANY PIPING OR DUCTWORK DEMOLITION
THAT MAY AFFECT NORMAL OPERATION OF OTHER AREAS.
6. FIELD VERIFY LOCATIONS OF EXISTING PIPING THAT MAY
CONFLICT WITH NEW CONSTRUCTION AND RELOCATE AS
NEEDED.
7. LOCATIONS OF THE THERMOSTATS TO BE VERIFIED IN FIELD.
8. PROVIDE BALANCE DAMPERS FOR EACH DIFFUSER/GRILLE
AND BRANCH DUCT.
9. PROVIDE FLEXIBLE DUCT IN ACCESSIBLE CEILINGS. 6 FT MAX
LENGTH. KEEP BENDS TO A MINIMUM.
10. ALL REHEAT COIL HS&R RUNOUT PIPES SHALL BE 3/4" UNLESS
OTHERWISE NOTED.
11. PROVIDE ACCESS PANELS ON EACH SIDE OF REHEAT COILS.
12. PROVIDE 5 FT MIN BEFORE ANY DUCT TAKEOFF FOR
DUCTWORK DOWNSTREAM OF VAV BOXES.
13. PROVIDE 1 1/2 DUCT DIAMETERS MIN. DUCT LENGTH OF HIGH
PRESSURE BRANCH DUCTWORK ON THE UPSTREAM SIDE OF
VAV BOXES.
14. CONTRACTOR SHALL COORDINATE ALL WORK WITH OTHER
DISCIPLINES PRIOR TO CONSTRUCTION TO AVOID CONFLICTS.
15. PROVIDE MANUAL AIR VENTS WITH 3/4" HOSE CONNECTION AT
ALL HIGH POINTS.
16. OFFSET PIPING TO ACCOMMODATE LARGE DUCTWORK.
17. THE CONTRACTOR SHALL FIELD VERIFY THE SIZES, LOCATION,
ELEVATIONS, AND DETAILS OF ALL EXISTING CONDITIONS THAT
MAY AFFECT THE WORK.
18. THE CONTRACTOR SHALL BE RESPONSIBLE FOR MAINTAINING
THE INTEGRITY OF ALL EQUIPMENT AND MATERIALS IN A "NEW"
CONDITION DURING CONSTRUCTION.
19. ALL WORK SHALL BE PERFORMED BY LICENSED
CONTRACTORS AND SUBCONTRACTORS AS REQUIRED BY LAW.
20. ALL WORK SHALL CONFORM TO MICHIGAN MECHANICAL CODE,
LATEST APPLICABLE EDITION.
21. CONTRACTOR SHALL USE LOW PRESSURE LOSS DUCT
FITTINGS IN ACCORDANCE WITH SMACNA. (WYES, RADIUSED
OR VANED TEES, ETC.) DUCTWORK SHALL BE GALVANIZED
SHEET METAL, MIN. 26 GA.
22. ALL DUCT DIMENSIONS SHOWN ARE INSIDE CLEAR DIMENSION.
INCREASE DUCT SIZE FOR LINING.
23. LINE 10'-0" OF SUPPLY DUCTWORK AFTER EACH VAV BOX.
24. ALL EXTERNALLY ISOLATED HVAC EQUIPMENT SHALL HAVE
FLEXIBLE DUCT CONNECTORS.
25. ALL CONDENSATE DRAIN PIPING SET @ MIN. 1% SLOPE.
26. ALL CONDENSATE DRAIN PIPING TO TERMINATE TO DRAIN VIA
AIR GAP.
27. IF THERE IS CONFLICTING INFORMATION IN THE PLANS OR
SPECIFICATIONS THE MORE STRINGENT AND GREATER COST
ITEM SHALL BE USED.
28. DRAWINGS INDICATE REQUIRED SIZES AND POINTS OF
TERMINATION OF PIPES AND DUCTS AND SUGGESTED ROUTES.
IT IS NOT INTENTION OF DRAWINGS TO INDICATE ALL
NECESSARY OFFSETS. INSTALL WORK IN MANNER TO
CONFORM TO STRUCTURE, AVOID OBSTRUCTIONS, PRESERVE
HEADROOM AND KEEP OPENINGS AND PASSAGEWAYS CLEAR.
DO NOT SCALE FROM DRAWINGS.
MECHANICAL SYMBOLS LEGEND
HVAC PIPING SYMBOLSHVAC PIPING
HVAC DUCTWORK
F/S
F/S s s
TEMPERATURE CONTROL SYMBOLS
MISCELLANEOUS NOTES
HVAC DUCTWORK SYMBOLS HVAC DUCTWORK & DIFFUSER TAGS HVAC PIPING VALVES
MECHANICAL ABBREVIATIONS
AFF ABOVE FINISH FLOOR
AC AIR COMPRESSOR
AHU AIR HANDLING UNIT
AS AIR SEPARATOR
A.T.C. ARCHITECTURAL TRADES CONTRACTOR
B BOILER
B.A.S. BUILDING AUTOMATION SYSTEM
CAF COMBUSTION AIR FAN
CC COOLING COIL
CFM CUBIC FEET PER MINUTE
CHLR CHILLER
CHP CONSOLE HEAT PUMP
CONV CONVECTOR
CT COOLING TOWER
CU CONDENSING UNIT
CUH CABINET UNIT HEATER
CV CONTROL VALVE
CWP CHILLED WATER PUMP
DB DRY BULB
DFU DUCT FURNACE
DIA DIAMETER
DN DOWN
DPR DAMPER
DS DUCT SILENCER
EAT ENTERING AIR TEMPERATURE
EF EXHAUST FAN
EG EXHAUST GRILLE
E.T.C. ELECTRICAL TRADES CONTRACTOR
EVR EVAPORATOR
EWT ENTERING WATER TEMPERATURE
EXH EXHAUST
EXIST EXISTING
FF FINISH FLOOR
FPM FEET PER MINUTE
FT FEET
FTR FINNED TUBE RADIATION
FU FURNACE
GAL GALLON
GFRH GAS FIRED RADIANT HEATER
GR GRILLE
H HUMIDIFIER
HC HEATING COIL
HD HEAD (FT)
HP HORSE POWER
HHP HORIZONTAL HEAT PUMP
HTG HEATING
HVAC HEATING, VENTILATION, & AIR CONDITIONING
HWP HEATING WATER PUMP
HX HEAT EXCHANGER
ID INSIDE DIAMETER
I.E. INVERT ELEVATION
IAH INTAKE HOOD
LAT LEAVING AIR TEMPERATURE
LH LATENT HEAT (MBH)
LL LIQUID LINE
LWT LEAVING WATER TEMPERATURE
MAX MAXIMUM
MBH BTU PER HOUR (THOUSAND)
MIN MINIMUM
M.T.C. MECHANICAL TRADES CONTRACTOR
N.C. NOISE CRITERIA
NFPA NATIONAL FIRE PROTECTION ASSOCIATION
NTS NOT TO SCALE
P PUMP
PCR PUMPED CONDENSATE RETURN
PD PRESSURE DROP
RCP RADIANT CEILING PANEL
REQ'D REQUIRED
RG RETURN GRILLE
RH RELATIVE HUMIDITY
RLH RELIEF HOOD
RTU ROOF TOP UNIT
SD SUPPLY DIFFUSER
SF SUPPLY FAN
SG SUPPLY GRILLE
SH SENSIBLE HEAT (MBH)
SL SUCTION LINE
SM SHEET METAL
SQ. FT. SQUARE FEET
SST SATURATED SUCTION TEMPERATURE
STR STRAINER
TC TOTAL COOLING (MBH)
TCL TEMPERATURE CONTROL
T&P TEMPERATURE & PRESSURE RELIEF VALVE
TYP TYPICAL
UH UNIT HEATER
VAV VARIABLE AIR VOLUME BOX
VRH VARIABLE AIR VOLUME REHEAT BOX
FPVAV FAN POWERED VARIABLE AIR VOLUME BOX
V.F.D VARIABLE FREQUENCY DRIVE
ZD ZONE DAMPER
X-SA EXISTING ITEM (EXISTING SUPPLY AIR DUCT)
ITEM
EXISTING
CHILLED WATER SUPPLY
CHILLED WATER RETURN
CONDENSATE DRAIN
CONDENSER WATER SUPPLY
CONDENSER WATER RETURN
COOLING TOWER WATER SUPPLY
COOLING TOWER WATER RETURN
DIRECT EXPANSION
HEAT PUMP WATER SUPPLY
HEAT PUMP WATER RETURN
HEATING WATER SUPPLY
HEATING WATER RETURN
SUCTION (REFRIGERANT)
LIQUID (REFRIGERANT)
SUCTION (DIRECT EXPANSION)
LIQUID (DIRECT EXPANSION)
LOW PRESSURE STEAM (0-20 LBS.)
MEDIUM PRESSURE STEAM (21-75 LBS.)
HIGH PRESSURE STEAM (76 LBS. & ABV.)
STEAM CONDENSATE (GRAVITY)
PUMPED STEAM CONDENSATE
STEAM CONDENSATE BOILER FEED
GATE VALVE
GAS COCK
CHECK VALVE
BALANCE COCK
CIRCUIT SETTER
TWO-WAY CONTROL VALVE
THREE-WAY CONTROL VALVE
GLOBE VALVE
BALL VALVE
SOLENOID VALVE
EXPANSION VALVE WITH
THERMOSTATIC BULB
PLUG VALVE
BUTTERFLY VALVE
RELIEF VALVE
HOSE & DRAIN END VALVE
PRESSURE RELIEF VALVE
PRESSURE REDUCING VALVE
TRIPLE DUTY VALVE
GAS PRESSURE REGULATOR
STRAINER (BLOW-OFF)
FLOW DIRECTION
PIPING DROP
PIPING RISE
INLINE PIPING DROP
INLINE PIPING RISE
PIPING TEE
PIPING ELBOW
THERMOMETER
PUMP
UNION
PIPE ANCHOR
PIPE GUIDE
BACK FLOW PREVENTER
PIPE CAP
PIPE BREAK
THERMOMETER WELL
EXPANSION LOOP
EXPANSION COMPENSATOR
FLOAT & THERMOSTATIC STEAM TRAP
INVERTED BUCKET STEAM TRAP
THERMOSTAT
PROGRAMMABLE THERMOSTAT
THERMOSTAT (W/ NIGHT SETBACK)
ROOM SENSOR
HUMIDISTAT
PRESSURE GAUGE
DAMPER (ELECTRIC OPERATION)
DAMPER (PNEUMATIC OPERATION)
DAMPER BLADES
SUPPLY AIR DUCT
EXIST SUPPLY AIR DUCT
RETURN AIR DUCT
EXIST RETURN AIR DUCT
OUTSIDE AIR DUCT
EXIST OUTSIDE AIR DUCT
EXHAUST AIR DUCT
EXIST EXHAUST AIR DUCT
SUPPLY AIR DUCT RISER
RETURN AIR DUCT RISER
OUTSIDE AIR DUCT RISER (AS NOTED)
EXHAUST AIR DUCT
INSULATED DUCTWORK (AS NOTED)
SUPPLY AIR DIFFUSER (SQUARE)
SUPPLY AIR DIFFUSER (INLINE)
TURNING VANES
SURFACE MTD. GRILLE
SUPPLY AIR DIFFUSER (ROUND)
90° TEE W/45° APPROACH
CONICAL TAKE-OFF
CONICAL TAKE-OFF W/ DAMPER
BALANCE DAMPER
RETURN AIR DUCT BOOT
ECCENTRIC REDUCER
CONCENTRIC REDUCER
VERTICAL FIRE DAMPER
EXISTING VERTICAL FIRE DAMPER
HORIZONTAL FIRE DAMPER
EXISTING HORIZONTAL FIRE DAMPER
VERTICAL SMOKE DAMPER
HORIZONTAL SMOKE DAMPER
VERTICAL FIRE / SMOKE DAMPER
HORIZONTAL FIRE / SMOKE DAMPER
DUCT SMOKE DETECTOR, INSTALLED BY M.T.C.,
PROVIDED & WIRED BY E.T.C.
UNIT HEATER
CEILING EXHAUST FAN
ROOF MOUNTED EXHAUST FAN
DEMOLITION
POINT OF CONNECTION BETWEEN NEW AND
EXISTING
POINT OF EXISTING TO REMAIN AND EXISTING
TO BE REMOVED
INDICATES PLAN NOTE
INDICATES DEMOLITION NOTE
DETAIL BUBBLE
DETAIL NUMBER
PAGE LOCATION INDICATES
DIRECTION OF DETAIL SECTION
X
X
XX
XXXX
XX
XXXX
SA
OA
X-OA
X-EA
EA
X-SA
X-RA
RA
SCP
SC
DXS
DXL
HR
CR
CD
CS
DX
CTR
HPR
HS
HPS
CTS
CWR
CWS
S
L
LPS
MPS
HPS
SC (BF)
TAG CFM
NECK REMARKS
SIZE
BT
FT
SD-1 250
8"ø ---
P
H
S
T
T P
T N
M
M
SD
M A
T R
X-RTU-101
X-RTU-103
X-RTU-104
X-RTU-102
X-G
X-G
DEMOLITION NOTES
1 DISCONNECT, REMOVE, AND DEMOLISH EXISTING
ROOFTOP UNIT AT LOCATION SHOWN. EXISTING CURB
TO REMAIN FOR NEW ROOFTOP UNIT. DEMO GAS
PIPING AS REQUIRED TO CONNECT TO NEW ROOFTOP
UNIT.
M A
T R
I X
N
ELEMENTARY SCHOOL - ROOF PLAN - MECHANICAL DEMOLITION (ADD ALTERNATE #2)
SCALE: 1/16" = 1'-0"
10510 4020
UNIT 300
UNIT 200
UNIT 200
UNIT 300
UN
IT
UN
IT
UN
IT
UN
IT
X-UH X-2-1/2''
HS & HR
X-2-1/2'' HS & HR X-2'' HS & HR
X-4'' HS & HR
X-4'' HS & HR
X-3/4'' HS & HR
DEMOLITION NOTES
1 DISCONNECT, REMOVE, AND DEMOLISH EXISTING
HEATING HOT WATER SUPPLY AND RETURN PIPING TO
POINT INDICATED ON DRAWINGS.
N INTERMEDIATE SCHOOL - PARTIAL FLOOR PLAN - UNIT 200 - MECHANICAL DEMOLITION (ADD ALTERNATE #1)
M A
T R
I X
SCALE: 1/8" = 1'-0"
0 1 5 10 20
UNIT 200
UNIT 300
X-SD ---
10" Ø TYP. 4
X-SD ---
10" Ø TYP. 4
X-SD ---
10" Ø TYP. 4
X-SD ---
8" Ø ---
X-RG ---
10x10 ---
X-RG ---
24x24 ---
X-RG ---
24x24 ---
X-RG ---
24x24 ---
X-SA UP TO X-RTU-110
X-RA UP TO X-RTU-110
X-26x16 SA
X-24x12 SAX-20x12 SAX-20x12 SAX-14x12 SA
X-10x10 SA X-16x12 SA
X-10x10 RA
X-10x10 RA
X-28x12 RA X-32x14 RA X-16x12 RA
X-16x12 RA
X-26x16 SA
X-EA X-EA
X-SD ---
10" Ø TYP. 4
X-SD ---
10" Ø TYP. 4
X-SD ---
10" Ø TYP. 4
X-SD ---
8" Ø ---
X-SD ---
8" Ø ---
X-EG ---
X-EG ---
X-SA UP TO
X-RTU-111
X-RA UP TO
X-RTU-111
X-SD ---
X-36x16 SA
X-26x12 SAX-24x12 SAX-10x12 SA X-24x12 SA X-10x12 SA
X-36x16 SA
X-36x16 RA
X-RA
X-RA
X-RAX-RA
X-RG ---
X-RG ---
X-28x12 RA
X-18x12 RA X-28x12 RA
X-UVX-UV
X-UV
X-1-1/4''
HS & HR
X-1-1/4''
HS & HR
X-1-1/4''
HS & HR
X-2'' HS & HR
X-24x12 SA
X-16x8 SA
X-24x12 SA
X-24x12 SA
X-16x8 SA
DEMOLITION NOTES
1 DISCONNECT, REMOVE, AND DEMOLISH EXISTING
DUCTWORK TO POINT WHERE INDICATED ON
DRAWINGS.
DISCONNECT, REMOVE, AND DEMOLISH EXISTING
HEATING HOT WATER SUPPLY AND RETURN PIPING TO
POINT WHERE INDICATED ON DRAWINGS.
N INTERMEDIATE SCHOOL - PARTIAL FLOOR PLAN - UNIT 300 - MECHANICAL DEMOLITION (ADD ALTERNATE #1)
M A
T R
I X
X-RTU-112
X-RTU-113
X-RTU-110
X-RTU-111
X-RTU
X-RTU
X-RTU-108
X-RTU-107
X-EF
X-EF
X-RTU
X-G
X-G
X-G
X-G
X-G
X-G
DEMOLITION NOTES
1 DISCONNECT, REMOVE, AND DEMOLISH EXISTING
ROOFTOP UNIT AT LOCATION SHOWN. EXISTING CURB
TO REMAIN FOR NEW ROOFTOP UNIT. DEMO GAS
PIPING AS REQUIRED TO CONNECT TO NEW ROOFTOP
UNIT.
EXISTING ROOFTOP UNIT TO REMAIN.2
N
INTERMEDIATE SCHOOL - ROOF PLAN - MECHANICAL DEMOLITION (ADD ALTERNATE #1)
M A
T R
I X
SCALE: 1/16" = 1'-0"
10510 4020
X-6''Ø EA
X-6''Ø EA
X-6''Ø EA
X-6''Ø EA
X-10''Ø EA
X-10''Ø EA
X-6''Ø EA
X-6''Ø EA
X-6''Ø EA X-6''Ø EA
X-6''Ø EA
X-10''Ø EA
X-8''Ø SA
X-14''Ø SA
X-8''Ø SA
X-12''Ø SA
X-8''Ø SA
X-8''Ø SA
X-FCU-501
X-FCU-502
X-14''Ø V
THRU ROOF
X-14''Ø V
THRU ROOF
X-EF X-EF
X-SD 330
X-SD 330
--- TYP.2 X-SD 330
--- TYP.2
330X-SD
X-EG 150
6''x6'' ---
X-EG 175
6''x6'' ---
175X-EG
---6''x6''
350X-EG
TYP.28''x8''
75X-EG
---6''x6''
75X-EG
---6''x6'' 100X-SD
---8''Ø
100X-SD
---8''Ø
X-10''x20''
OA DN
X-LOUVER
X-54''x20'' OA DN X-56''x20'' RA
UP
X-6''Ø EA (TYP. 3) X-12''Ø EA
X-48''x20'' SA UP
X-CC-502
X-SG
X-RG
X-AHU-502
X-SL & LL
X-4'' G
X-1'' HS & HR
X-2'' HS & HR
TO X-CU-502
DEMOLITION NOTES
1 MODIFY EXISTING FAN COIL UNIT AS NECESSARY TO
PREPARE FOR RETROFIT WITH DX COOLING COIL.
DISCONNECT, REMOVE, AND DEMOLISH EXISTING
REFRIGERANT PIPING TO POINT INDICATED ON
DRAWINGS.
N
HIGH SCHOOL - PARTIAL FLOOR PLAN - UNIT 500 - MECHANICAL DEMOLITION (BASE BID)
M A
T R
I X
SCALE: 1/8" = 1'-0"
0 1 5 10 20 N
HIGH SCHOOL - MEZZANINE PLAN - UNIT 500 - MECHANICAL DEMOLITION (BASE BID)
RTURTURTU
RTU
RTU RTU RTU
RTU
RTU
RTU
RTU
RTU
RTU
RTU
RTU RTU
RTU
RTU
RTU
RTU
RTU
RTU
CU
CU
CU
CU
CU
X-RTU
X-RTUX-RTU
X-RTU
X-RTUX-AHU
X-RTUX-RTUX-RTU
X-RTU
X-RTU
X-RTU
X-RTU
X-RTU
X-RTU
X-RTU-394
X-RTU-305
X-RTU
X-RTU
X-RTU
X-RTU
X-RTU
X-EF X-EF
X-CU
X-EF
X-CU-502
X-SL & LL
X-1'' G
X-1'' G
X-2-1/2'' G
X-1'' G
X-4'' GX-2'' G
X-3'' G
TO X-CC-502
X-SL & LL
DEMOLITION NOTES
1 DISCONNECT, REMOVE, AND DEMOLISH EXISTING
ROOFTOP UNIT AT LOCATION SHOWN. EXISTING CURB
TO REMAIN FOR NEW ROOFTOP UNIT. DEMO GAS
PIPING AS REQUIRED TO CONNECT TO ROOFTOP UNIT.
DISCONNECT, REMOVE, AND DEMOLISH EXISTING AIR
HANDLING UNIT. EXISTING ROOF OPENING AND CURB
TO BE RE-USED FOR REPLACEMENT.
DISCONNECT, REMOVE, AND DEMOLISH EXISTING
CONDENSING UNIT. PREPARE FOR DIRECT
REPLACEMENT IN SAME LOCATION.
N
HIGH SCHOOL - ROOF PLAN - MECHANICAL DEMOLITION (BASE BID)
SCALE: 1/32" = 1'-0"
0 51 10 25 80
M A
T R
X-G
X-G
RTU-101
RTU-103
RTU-104
RTU-102 1
MECHANICAL KEY NOTES
1 FURNISH AND INSTALL NEW ROOFTOP UNIT IN LOCATION OF
PREVIOUSLY DEMOLISHED UNIT. PROVIDE MANUFACTURERS
CURB ADAPTER FOR INSTALLATION ON EXISTING CURB.
MODIFY SA AND RA DUCTWORK AS NECESSARY TO CONNECT
TO NEW RTU. EXTEND GAS PIPING AS REQUIRED FOR A
COMPLETE CONNECTION.
N
ELEMENTARY SCHOOL - ROOF PLAN - MECHANICAL NEW (ADD ALTERNATE #2)
SCALE: 1/16" = 1'-0"
10510 4020
M A
T R
UNIT 200
UNIT 300
X-RG ---
10x10 ---
X-RG ---
24x24 ---
X-RG ---
24x24 ---
X-RG ---
24x24 ---
X-26x16 SA
X-24x12 SAX-20x12 SAX-20x12 SAX-14x12 SA
X-10x10 SA X-16x12 SA
X-10x10 RA
X-10x10 RA
X-28x12 RA X-32x14 RA X-16x12 RA
X-16x12 RA
X-26x16 SA
X-EA X-EA
X-EG ---
X-EG ---
X-36x16 SA
X-26x12 SAX-10x12 SA X-10x12 SA
X-36x16 SA
X-36x16 RA
X-RA
X-RA
X-RAX-RA
X-RG ---
X-RG ---
X-28x12 RA
X-18x12 RA X-28x12 RA
X-24x12 SA
X-16x8 SA
X-24x12 SA
X-24x12 SA
X-16x8 SA
X-SA UP TO RTU-110
X-RA UP TO RTU-110
X-SA UP TO
RTU-111
X-RA UP TO
RTU-111
VAV-1
VAV-2 VAV-3
VAV-4 VAV-6
VAV-5
X-SD 290
10" Ø TYP. 4
X-SD 290
10" Ø TYP. 4
X-SD 290
10" Ø TYP. 4
X-SD 220
8" Ø ---
X-SD 280
10" Ø TYP. 4
X-SD 280
10" Ø TYP. 4
X-SD 280
10" Ø TYP. 4
X-SD 150
8" Ø ---
X-SD 150
8" Ø ---
X-SD 40
18x12 SA
20x12 SA
18x12 SA
14x12 SA 18x16 SA
18x12 SA 16x12 SA
10x6 SA
30x16 SA 14x12 SA 16x12 SA
18x12 SA
TT T
MECHANICAL KEY NOTES
1 INSTALL AND MODIFY NEW SA DUCTWORK AS SHOWN.
M A
T R
I X
N INTERMEDIATE SCHOOL - PARTIAL FLOOR PLAN - UNIT 300 - MECHANICAL NEW (ADD ALTERNATE #1)
| A000-2252100 |
| M100-2252100 |
| M300-2252100 |
| M301-2252100 |
| M302-2252100 |
| M303-2252100 |
| M304-2252100 |
| M305-2252100 |
| M400-2252100 |
| M401-2252100 |
| M402-2252100 |
| M403-2252100 |
| M404-2252100 |
| M600-2252100 |
| M601-2252100 |
| M800-2252100 |
| M801-2252100 |
| M802-2252100 |
| M803-2252100 |
| M804-2252100 |
| M900-2252100 |
File details come from the government source that posted it. Updated .