22521.00 - Columbia Schools HVAC Upgrades - Mechanical Set - 1 of 3.pdf

PDF 5 MB Posted

Attached to
HVAC Bid Information
Solicitation number
RFP - CSD - 240000000475
Issued by
Jackson County, Michigan

About this file

This document is a set of mechanical and electrical drawings for HVAC upgrades at the Columbia Schools in Brooklyn, Michigan. The project involves the replacement of rooftop HVAC units, modification of ductwork and piping, and rebalancing of existing systems at the Columbia Intermediate School and Columbia Elementary School. The drawings include a drawing index, general HVAC notes, and mechanical/electrical symbols. Demolition plans and new work plans are provided. The project is identified as Matrix Project Number 22521.00.

The drawings indicate that the HVAC upgrades will be bid as base bids and add alternates. Bid information for this opportunity is included in a separate document. Contractors will need to coordinate the work with other trades and comply with local building codes and regulations. The contractor will also be responsible for maintaining equipment in new condition during construction.

View the file

Other files

Show all 11

On GovTribe

Work with this file

  • Download the original file
  • Contacts named in this file
  • Similar government files
  • Ask GovTribe AI about this file

Text version

COLUMBIA SCHOOLS

COLUMBIA SCHOOL DISTRICT - HVAC UPGRADES

MECHANICAL AND PLUMBING DRAWING INDEX ELECTRICAL DRAWING INDEX

11775 HEWITT RD.

BROOKLYN, MI 49230

MATRIX PROJECT NUMBER: 22521.00

DRAWING INDEX

MECHANICAL/ELECTRICAL ENGINEER

COLUMBIA INTERMEDIATE SCHOOL

COLUMBIA ELEMENTARY SCHOOL

BIDDING DESCRIPTION

M A

T R

I X

GENERAL HVAC NOTES

1. LOCATE EXHAUST OUTLETS OF VENTILATION SYSTEMS,

COMBUSTION EQUIPMENT STACKS, MEDICAL-SURGICAL

VACUUM SYSTEMS, & PLUMBING VENTS AT LEAST 10 FEET

FROM OUTDOOR AIR INTAKES.

2. INSTALL ALL EQUIPMENT, MATERIALS, AND ACCESSORIES PER

MANUFACTURERS WRITTEN INSTRUCTIONS.

3. BOTTOM OF EQUIPMENT ON ROOF SHALL BE A MINIMUM OF 12"

ABOVE ROOF MEMBRANE. CONTRACTOR SHALL COORDINATE

ASSOCIATED ROOF CURB HEIGHT AS REQUIRED.

4. ALL EXISTING SYSTEMS (INCLUDING EXHAUST FANS; AIR

HANDLING UNITS; PUMPS) THAT SERVES AREAS BEING

RENOVATED SHALL BE REBALANCED AS REQUIRED.

5. NOTIFY OWNER OF ANY PIPING OR DUCTWORK DEMOLITION

THAT MAY AFFECT NORMAL OPERATION OF OTHER AREAS.

6. FIELD VERIFY LOCATIONS OF EXISTING PIPING THAT MAY

CONFLICT WITH NEW CONSTRUCTION AND RELOCATE AS

NEEDED.

7. LOCATIONS OF THE THERMOSTATS TO BE VERIFIED IN FIELD.

8. PROVIDE BALANCE DAMPERS FOR EACH DIFFUSER/GRILLE

AND BRANCH DUCT.

9. PROVIDE FLEXIBLE DUCT IN ACCESSIBLE CEILINGS. 6 FT MAX

LENGTH. KEEP BENDS TO A MINIMUM.

10. ALL REHEAT COIL HS&R RUNOUT PIPES SHALL BE 3/4" UNLESS

OTHERWISE NOTED.

11. PROVIDE ACCESS PANELS ON EACH SIDE OF REHEAT COILS.

12. PROVIDE 5 FT MIN BEFORE ANY DUCT TAKEOFF FOR

DUCTWORK DOWNSTREAM OF VAV BOXES.

13. PROVIDE 1 1/2 DUCT DIAMETERS MIN. DUCT LENGTH OF HIGH

PRESSURE BRANCH DUCTWORK ON THE UPSTREAM SIDE OF

VAV BOXES.

14. CONTRACTOR SHALL COORDINATE ALL WORK WITH OTHER

DISCIPLINES PRIOR TO CONSTRUCTION TO AVOID CONFLICTS.

15. PROVIDE MANUAL AIR VENTS WITH 3/4" HOSE CONNECTION AT

ALL HIGH POINTS.

16. OFFSET PIPING TO ACCOMMODATE LARGE DUCTWORK.

17. THE CONTRACTOR SHALL FIELD VERIFY THE SIZES, LOCATION,

ELEVATIONS, AND DETAILS OF ALL EXISTING CONDITIONS THAT

MAY AFFECT THE WORK.

18. THE CONTRACTOR SHALL BE RESPONSIBLE FOR MAINTAINING

THE INTEGRITY OF ALL EQUIPMENT AND MATERIALS IN A "NEW"

CONDITION DURING CONSTRUCTION.

19. ALL WORK SHALL BE PERFORMED BY LICENSED

CONTRACTORS AND SUBCONTRACTORS AS REQUIRED BY LAW.

20. ALL WORK SHALL CONFORM TO MICHIGAN MECHANICAL CODE,

LATEST APPLICABLE EDITION.

21. CONTRACTOR SHALL USE LOW PRESSURE LOSS DUCT

FITTINGS IN ACCORDANCE WITH SMACNA. (WYES, RADIUSED

OR VANED TEES, ETC.) DUCTWORK SHALL BE GALVANIZED

SHEET METAL, MIN. 26 GA.

22. ALL DUCT DIMENSIONS SHOWN ARE INSIDE CLEAR DIMENSION.

INCREASE DUCT SIZE FOR LINING.

23. LINE 10'-0" OF SUPPLY DUCTWORK AFTER EACH VAV BOX.

24. ALL EXTERNALLY ISOLATED HVAC EQUIPMENT SHALL HAVE

FLEXIBLE DUCT CONNECTORS.

25. ALL CONDENSATE DRAIN PIPING SET @ MIN. 1% SLOPE.

26. ALL CONDENSATE DRAIN PIPING TO TERMINATE TO DRAIN VIA

AIR GAP.

27. IF THERE IS CONFLICTING INFORMATION IN THE PLANS OR

SPECIFICATIONS THE MORE STRINGENT AND GREATER COST

ITEM SHALL BE USED.

28. DRAWINGS INDICATE REQUIRED SIZES AND POINTS OF

TERMINATION OF PIPES AND DUCTS AND SUGGESTED ROUTES.

IT IS NOT INTENTION OF DRAWINGS TO INDICATE ALL

NECESSARY OFFSETS. INSTALL WORK IN MANNER TO

CONFORM TO STRUCTURE, AVOID OBSTRUCTIONS, PRESERVE

HEADROOM AND KEEP OPENINGS AND PASSAGEWAYS CLEAR.

DO NOT SCALE FROM DRAWINGS.

MECHANICAL SYMBOLS LEGEND

HVAC PIPING SYMBOLSHVAC PIPING

HVAC DUCTWORK

F/S

F/S s s

TEMPERATURE CONTROL SYMBOLS

MISCELLANEOUS NOTES

HVAC DUCTWORK SYMBOLS HVAC DUCTWORK & DIFFUSER TAGS HVAC PIPING VALVES

MECHANICAL ABBREVIATIONS

AFF ABOVE FINISH FLOOR

AC AIR COMPRESSOR

AHU AIR HANDLING UNIT

AS AIR SEPARATOR

A.T.C. ARCHITECTURAL TRADES CONTRACTOR

B BOILER

B.A.S. BUILDING AUTOMATION SYSTEM

CAF COMBUSTION AIR FAN

CC COOLING COIL

CFM CUBIC FEET PER MINUTE

CHLR CHILLER

CHP CONSOLE HEAT PUMP

CONV CONVECTOR

CT COOLING TOWER

CU CONDENSING UNIT

CUH CABINET UNIT HEATER

CV CONTROL VALVE

CWP CHILLED WATER PUMP

DB DRY BULB

DFU DUCT FURNACE

DIA DIAMETER

DN DOWN

DPR DAMPER

DS DUCT SILENCER

EAT ENTERING AIR TEMPERATURE

EF EXHAUST FAN

EG EXHAUST GRILLE

E.T.C. ELECTRICAL TRADES CONTRACTOR

EVR EVAPORATOR

EWT ENTERING WATER TEMPERATURE

EXH EXHAUST

EXIST EXISTING

FF FINISH FLOOR

FPM FEET PER MINUTE

FT FEET

FTR FINNED TUBE RADIATION

FU FURNACE

GAL GALLON

GFRH GAS FIRED RADIANT HEATER

GR GRILLE

H HUMIDIFIER

HC HEATING COIL

HD HEAD (FT)

HP HORSE POWER

HHP HORIZONTAL HEAT PUMP

HTG HEATING

HVAC HEATING, VENTILATION, & AIR CONDITIONING

HWP HEATING WATER PUMP

HX HEAT EXCHANGER

ID INSIDE DIAMETER

I.E. INVERT ELEVATION

IAH INTAKE HOOD

LAT LEAVING AIR TEMPERATURE

LH LATENT HEAT (MBH)

LL LIQUID LINE

LWT LEAVING WATER TEMPERATURE

MAX MAXIMUM

MBH BTU PER HOUR (THOUSAND)

MIN MINIMUM

M.T.C. MECHANICAL TRADES CONTRACTOR

N.C. NOISE CRITERIA

NFPA NATIONAL FIRE PROTECTION ASSOCIATION

NTS NOT TO SCALE

P PUMP

PCR PUMPED CONDENSATE RETURN

PD PRESSURE DROP

RCP RADIANT CEILING PANEL

REQ'D REQUIRED

RG RETURN GRILLE

RH RELATIVE HUMIDITY

RLH RELIEF HOOD

RTU ROOF TOP UNIT

SD SUPPLY DIFFUSER

SF SUPPLY FAN

SG SUPPLY GRILLE

SH SENSIBLE HEAT (MBH)

SL SUCTION LINE

SM SHEET METAL

SQ. FT. SQUARE FEET

SST SATURATED SUCTION TEMPERATURE

STR STRAINER

TC TOTAL COOLING (MBH)

TCL TEMPERATURE CONTROL

T&P TEMPERATURE & PRESSURE RELIEF VALVE

TYP TYPICAL

UH UNIT HEATER

VAV VARIABLE AIR VOLUME BOX

VRH VARIABLE AIR VOLUME REHEAT BOX

FPVAV FAN POWERED VARIABLE AIR VOLUME BOX

V.F.D VARIABLE FREQUENCY DRIVE

ZD ZONE DAMPER

X-SA EXISTING ITEM (EXISTING SUPPLY AIR DUCT)

ITEM

EXISTING

CHILLED WATER SUPPLY

CHILLED WATER RETURN

CONDENSATE DRAIN

CONDENSER WATER SUPPLY

CONDENSER WATER RETURN

COOLING TOWER WATER SUPPLY

COOLING TOWER WATER RETURN

DIRECT EXPANSION

HEAT PUMP WATER SUPPLY

HEAT PUMP WATER RETURN

HEATING WATER SUPPLY

HEATING WATER RETURN

SUCTION (REFRIGERANT)

LIQUID (REFRIGERANT)

SUCTION (DIRECT EXPANSION)

LIQUID (DIRECT EXPANSION)

LOW PRESSURE STEAM (0-20 LBS.)

MEDIUM PRESSURE STEAM (21-75 LBS.)

HIGH PRESSURE STEAM (76 LBS. & ABV.)

STEAM CONDENSATE (GRAVITY)

PUMPED STEAM CONDENSATE

STEAM CONDENSATE BOILER FEED

GATE VALVE

GAS COCK

CHECK VALVE

BALANCE COCK

CIRCUIT SETTER

TWO-WAY CONTROL VALVE

THREE-WAY CONTROL VALVE

GLOBE VALVE

BALL VALVE

SOLENOID VALVE

EXPANSION VALVE WITH

THERMOSTATIC BULB

PLUG VALVE

BUTTERFLY VALVE

RELIEF VALVE

HOSE & DRAIN END VALVE

PRESSURE RELIEF VALVE

PRESSURE REDUCING VALVE

TRIPLE DUTY VALVE

GAS PRESSURE REGULATOR

STRAINER (BLOW-OFF)

FLOW DIRECTION

PIPING DROP

PIPING RISE

INLINE PIPING DROP

INLINE PIPING RISE

PIPING TEE

PIPING ELBOW

THERMOMETER

PUMP

UNION

PIPE ANCHOR

PIPE GUIDE

BACK FLOW PREVENTER

PIPE CAP

PIPE BREAK

THERMOMETER WELL

EXPANSION LOOP

EXPANSION COMPENSATOR

FLOAT & THERMOSTATIC STEAM TRAP

INVERTED BUCKET STEAM TRAP

THERMOSTAT

PROGRAMMABLE THERMOSTAT

THERMOSTAT (W/ NIGHT SETBACK)

ROOM SENSOR

HUMIDISTAT

PRESSURE GAUGE

DAMPER (ELECTRIC OPERATION)

DAMPER (PNEUMATIC OPERATION)

DAMPER BLADES

SUPPLY AIR DUCT

EXIST SUPPLY AIR DUCT

RETURN AIR DUCT

EXIST RETURN AIR DUCT

OUTSIDE AIR DUCT

EXIST OUTSIDE AIR DUCT

EXHAUST AIR DUCT

EXIST EXHAUST AIR DUCT

SUPPLY AIR DUCT RISER

RETURN AIR DUCT RISER

OUTSIDE AIR DUCT RISER (AS NOTED)

EXHAUST AIR DUCT

INSULATED DUCTWORK (AS NOTED)

SUPPLY AIR DIFFUSER (SQUARE)

SUPPLY AIR DIFFUSER (INLINE)

TURNING VANES

SURFACE MTD. GRILLE

SUPPLY AIR DIFFUSER (ROUND)

90° TEE W/45° APPROACH

CONICAL TAKE-OFF

CONICAL TAKE-OFF W/ DAMPER

BALANCE DAMPER

RETURN AIR DUCT BOOT

ECCENTRIC REDUCER

CONCENTRIC REDUCER

VERTICAL FIRE DAMPER

EXISTING VERTICAL FIRE DAMPER

HORIZONTAL FIRE DAMPER

EXISTING HORIZONTAL FIRE DAMPER

VERTICAL SMOKE DAMPER

HORIZONTAL SMOKE DAMPER

VERTICAL FIRE / SMOKE DAMPER

HORIZONTAL FIRE / SMOKE DAMPER

DUCT SMOKE DETECTOR, INSTALLED BY M.T.C.,

PROVIDED & WIRED BY E.T.C.

UNIT HEATER

CEILING EXHAUST FAN

ROOF MOUNTED EXHAUST FAN

DEMOLITION

POINT OF CONNECTION BETWEEN NEW AND

EXISTING

POINT OF EXISTING TO REMAIN AND EXISTING

TO BE REMOVED

INDICATES PLAN NOTE

INDICATES DEMOLITION NOTE

DETAIL BUBBLE

DETAIL NUMBER

PAGE LOCATION INDICATES

DIRECTION OF DETAIL SECTION

X

X

XX

XXXX

XX

XXXX

SA

OA

X-OA

X-EA

EA

X-SA

X-RA

RA

SCP

SC

DXS

DXL

HR

CR

CD

CS

DX

CTR

HPR

HS

HPS

CTS

CWR

CWS

S

L

LPS

MPS

HPS

SC (BF)

TAG CFM

NECK REMARKS

SIZE

BT

FT

SD-1 250

8"ø ---

P

H

S

T

T P

T N

M

M

SD

M A

T R

X-RTU-101

X-RTU-103

X-RTU-104

X-RTU-102

X-G

X-G

DEMOLITION NOTES

1 DISCONNECT, REMOVE, AND DEMOLISH EXISTING

ROOFTOP UNIT AT LOCATION SHOWN. EXISTING CURB

TO REMAIN FOR NEW ROOFTOP UNIT. DEMO GAS

PIPING AS REQUIRED TO CONNECT TO NEW ROOFTOP

UNIT.

M A

T R

I X

N

ELEMENTARY SCHOOL - ROOF PLAN - MECHANICAL DEMOLITION (ADD ALTERNATE #2)

SCALE: 1/16" = 1'-0"

10510 4020

UNIT 300

UNIT 200

UNIT 200

UNIT 300

UN

IT

UN

IT

UN

IT

UN

IT

X-UH X-2-1/2''

HS & HR

X-2-1/2'' HS & HR X-2'' HS & HR

X-4'' HS & HR

X-4'' HS & HR

X-3/4'' HS & HR

DEMOLITION NOTES

1 DISCONNECT, REMOVE, AND DEMOLISH EXISTING

HEATING HOT WATER SUPPLY AND RETURN PIPING TO

POINT INDICATED ON DRAWINGS.

N INTERMEDIATE SCHOOL - PARTIAL FLOOR PLAN - UNIT 200 - MECHANICAL DEMOLITION (ADD ALTERNATE #1)

M A

T R

I X

SCALE: 1/8" = 1'-0"

0 1 5 10 20

UNIT 200

UNIT 300

X-SD ---

10" Ø TYP. 4

X-SD ---

10" Ø TYP. 4

X-SD ---

10" Ø TYP. 4

X-SD ---

8" Ø ---

X-RG ---

10x10 ---

X-RG ---

24x24 ---

X-RG ---

24x24 ---

X-RG ---

24x24 ---

X-SA UP TO X-RTU-110

X-RA UP TO X-RTU-110

X-26x16 SA

X-24x12 SAX-20x12 SAX-20x12 SAX-14x12 SA

X-10x10 SA X-16x12 SA

X-10x10 RA

X-10x10 RA

X-28x12 RA X-32x14 RA X-16x12 RA

X-16x12 RA

X-26x16 SA

X-EA X-EA

X-SD ---

10" Ø TYP. 4

X-SD ---

10" Ø TYP. 4

X-SD ---

10" Ø TYP. 4

X-SD ---

8" Ø ---

X-SD ---

8" Ø ---

X-EG ---

X-EG ---

X-SA UP TO

X-RTU-111

X-RA UP TO

X-RTU-111

X-SD ---

X-36x16 SA

X-26x12 SAX-24x12 SAX-10x12 SA X-24x12 SA X-10x12 SA

X-36x16 SA

X-36x16 RA

X-RA

X-RA

X-RAX-RA

X-RG ---

X-RG ---

X-28x12 RA

X-18x12 RA X-28x12 RA

X-UVX-UV

X-UV

X-1-1/4''

HS & HR

X-1-1/4''

HS & HR

X-1-1/4''

HS & HR

X-2'' HS & HR

X-24x12 SA

X-16x8 SA

X-24x12 SA

X-24x12 SA

X-16x8 SA

DEMOLITION NOTES

1 DISCONNECT, REMOVE, AND DEMOLISH EXISTING

DUCTWORK TO POINT WHERE INDICATED ON

DRAWINGS.

DISCONNECT, REMOVE, AND DEMOLISH EXISTING

HEATING HOT WATER SUPPLY AND RETURN PIPING TO

POINT WHERE INDICATED ON DRAWINGS.

N INTERMEDIATE SCHOOL - PARTIAL FLOOR PLAN - UNIT 300 - MECHANICAL DEMOLITION (ADD ALTERNATE #1)

M A

T R

I X

X-RTU-112

X-RTU-113

X-RTU-110

X-RTU-111

X-RTU

X-RTU

X-RTU-108

X-RTU-107

X-EF

X-EF

X-RTU

X-G

X-G

X-G

X-G

X-G

X-G

DEMOLITION NOTES

1 DISCONNECT, REMOVE, AND DEMOLISH EXISTING

ROOFTOP UNIT AT LOCATION SHOWN. EXISTING CURB

TO REMAIN FOR NEW ROOFTOP UNIT. DEMO GAS

PIPING AS REQUIRED TO CONNECT TO NEW ROOFTOP

UNIT.

EXISTING ROOFTOP UNIT TO REMAIN.2

N

INTERMEDIATE SCHOOL - ROOF PLAN - MECHANICAL DEMOLITION (ADD ALTERNATE #1)

M A

T R

I X

SCALE: 1/16" = 1'-0"

10510 4020

X-6''Ø EA

X-6''Ø EA

X-6''Ø EA

X-6''Ø EA

X-10''Ø EA

X-10''Ø EA

X-6''Ø EA

X-6''Ø EA

X-6''Ø EA X-6''Ø EA

X-6''Ø EA

X-10''Ø EA

X-8''Ø SA

X-14''Ø SA

X-8''Ø SA

X-12''Ø SA

X-8''Ø SA

X-8''Ø SA

X-FCU-501

X-FCU-502

X-14''Ø V

THRU ROOF

X-14''Ø V

THRU ROOF

X-EF X-EF

X-SD 330

X-SD 330

--- TYP.2 X-SD 330

--- TYP.2

330X-SD

X-EG 150

6''x6'' ---

X-EG 175

6''x6'' ---

175X-EG

---6''x6''

350X-EG

TYP.28''x8''

75X-EG

---6''x6''

75X-EG

---6''x6'' 100X-SD

---8''Ø

100X-SD

---8''Ø

X-10''x20''

OA DN

X-LOUVER

X-54''x20'' OA DN X-56''x20'' RA

UP

X-6''Ø EA (TYP. 3) X-12''Ø EA

X-48''x20'' SA UP

X-CC-502

X-SG

X-RG

X-AHU-502

X-SL & LL

X-4'' G

X-1'' HS & HR

X-2'' HS & HR

TO X-CU-502

DEMOLITION NOTES

1 MODIFY EXISTING FAN COIL UNIT AS NECESSARY TO

PREPARE FOR RETROFIT WITH DX COOLING COIL.

DISCONNECT, REMOVE, AND DEMOLISH EXISTING

REFRIGERANT PIPING TO POINT INDICATED ON

DRAWINGS.

N

HIGH SCHOOL - PARTIAL FLOOR PLAN - UNIT 500 - MECHANICAL DEMOLITION (BASE BID)

M A

T R

I X

SCALE: 1/8" = 1'-0"

0 1 5 10 20 N

HIGH SCHOOL - MEZZANINE PLAN - UNIT 500 - MECHANICAL DEMOLITION (BASE BID)

RTURTURTU

RTU

RTU RTU RTU

RTU

RTU

RTU

RTU

RTU

RTU

RTU

RTU RTU

RTU

RTU

RTU

RTU

RTU

RTU

CU

CU

CU

CU

CU

X-RTU

X-RTUX-RTU

X-RTU

X-RTUX-AHU

X-RTUX-RTUX-RTU

X-RTU

X-RTU

X-RTU

X-RTU

X-RTU

X-RTU

X-RTU-394

X-RTU-305

X-RTU

X-RTU

X-RTU

X-RTU

X-RTU

X-EF X-EF

X-CU

X-EF

X-CU-502

X-SL & LL

X-1'' G

X-1'' G

X-2-1/2'' G

X-1'' G

X-4'' GX-2'' G

X-3'' G

TO X-CC-502

X-SL & LL

DEMOLITION NOTES

1 DISCONNECT, REMOVE, AND DEMOLISH EXISTING

ROOFTOP UNIT AT LOCATION SHOWN. EXISTING CURB

TO REMAIN FOR NEW ROOFTOP UNIT. DEMO GAS

PIPING AS REQUIRED TO CONNECT TO ROOFTOP UNIT.

DISCONNECT, REMOVE, AND DEMOLISH EXISTING AIR

HANDLING UNIT. EXISTING ROOF OPENING AND CURB

TO BE RE-USED FOR REPLACEMENT.

DISCONNECT, REMOVE, AND DEMOLISH EXISTING

CONDENSING UNIT. PREPARE FOR DIRECT

REPLACEMENT IN SAME LOCATION.

N

HIGH SCHOOL - ROOF PLAN - MECHANICAL DEMOLITION (BASE BID)

SCALE: 1/32" = 1'-0"

0 51 10 25 80

M A

T R

X-G

X-G

RTU-101

RTU-103

RTU-104

RTU-102 1

MECHANICAL KEY NOTES

1 FURNISH AND INSTALL NEW ROOFTOP UNIT IN LOCATION OF

PREVIOUSLY DEMOLISHED UNIT. PROVIDE MANUFACTURERS

CURB ADAPTER FOR INSTALLATION ON EXISTING CURB.

MODIFY SA AND RA DUCTWORK AS NECESSARY TO CONNECT

TO NEW RTU. EXTEND GAS PIPING AS REQUIRED FOR A

COMPLETE CONNECTION.

N

ELEMENTARY SCHOOL - ROOF PLAN - MECHANICAL NEW (ADD ALTERNATE #2)

SCALE: 1/16" = 1'-0"

10510 4020

M A

T R

UNIT 200

UNIT 300

X-RG ---

10x10 ---

X-RG ---

24x24 ---

X-RG ---

24x24 ---

X-RG ---

24x24 ---

X-26x16 SA

X-24x12 SAX-20x12 SAX-20x12 SAX-14x12 SA

X-10x10 SA X-16x12 SA

X-10x10 RA

X-10x10 RA

X-28x12 RA X-32x14 RA X-16x12 RA

X-16x12 RA

X-26x16 SA

X-EA X-EA

X-EG ---

X-EG ---

X-36x16 SA

X-26x12 SAX-10x12 SA X-10x12 SA

X-36x16 SA

X-36x16 RA

X-RA

X-RA

X-RAX-RA

X-RG ---

X-RG ---

X-28x12 RA

X-18x12 RA X-28x12 RA

X-24x12 SA

X-16x8 SA

X-24x12 SA

X-24x12 SA

X-16x8 SA

X-SA UP TO RTU-110

X-RA UP TO RTU-110

X-SA UP TO

RTU-111

X-RA UP TO

RTU-111

VAV-1

VAV-2 VAV-3

VAV-4 VAV-6

VAV-5

X-SD 290

10" Ø TYP. 4

X-SD 290

10" Ø TYP. 4

X-SD 290

10" Ø TYP. 4

X-SD 220

8" Ø ---

X-SD 280

10" Ø TYP. 4

X-SD 280

10" Ø TYP. 4

X-SD 280

10" Ø TYP. 4

X-SD 150

8" Ø ---

X-SD 150

8" Ø ---

X-SD 40

18x12 SA

20x12 SA

18x12 SA

14x12 SA 18x16 SA

18x12 SA 16x12 SA

10x6 SA

30x16 SA 14x12 SA 16x12 SA

18x12 SA

TT T

MECHANICAL KEY NOTES

1 INSTALL AND MODIFY NEW SA DUCTWORK AS SHOWN.

M A

T R

I X

N INTERMEDIATE SCHOOL - PARTIAL FLOOR PLAN - UNIT 300 - MECHANICAL NEW (ADD ALTERNATE #1)

A000-2252100
M100-2252100
M300-2252100
M301-2252100
M302-2252100
M303-2252100
M304-2252100
M305-2252100
M400-2252100
M401-2252100
M402-2252100
M403-2252100
M404-2252100
M600-2252100
M601-2252100
M800-2252100
M801-2252100
M802-2252100
M803-2252100
M804-2252100
M900-2252100