Attachment 5 - Product Spec Model.pdf

PDF 436 KB Posted

Attached to
Lightning Protection Systems Repair Building 2024 PSFB CO
Solicitation number
21CONSLPSSmith
Issued by

About this file

This document is a Lightning Protection Plan technical drawing for a facility, detailing the installation of lightning protection systems across a building's roof and exterior. The plan includes multiple air terminal masts positioned strategically around the building's perimeter, with each mast specified to be installed at a minimum height of 15'-6" above the roof. The technical drawing provides side and end view perspectives, along with a detailed legend explaining the lightning protection cable specifications, including 24-gauge stranded aluminum wire and 228 copper conductor connections. Key installation components include Superstrut support clamps, bronze bonding connections, and specific mounting instructions for the air terminals. The drawing appears to be part of a Department of Air Force Space Command project (Solicitation Number 21CONSLPSSmith) for lightning protection system repairs, with precise technical specifications for ensuring comprehensive lightning protection for the facility.

View the file

Other files

On GovTribe

Work with this file

  • Download the original file
  • Contacts named in this file
  • Similar government files
  • Ask GovTribe AI about this file

Text version

F

O O

T

F

O O

T

F

O O

T

F

O O

T

1 2 3 4 5

B A

24" SOLID

AIR TERMINAL

SUPERSTRUT SUPPORT CLAMP

(TWO PER MAST)

AIR TERMINAL MAST DETAIL

N.T.S.

AIR TEMINAL MAST

TIE AIR TERMINAL MAST

228 COPPER CONDUCTOR

TO THRU WALL

Typ. Cable Bend Requirements

Not to Scale

8" Radius Min.

8" Radius

NOT ACCEPTABLE

NOT ACCEPTABLE

ACCEPTABLE

Less Than 8" Radius

Less Than 90°

90° Min.

90° Min.

Typ. Cable Connectors

Not to Scale

EXTERIOR WALL

BRONZE BONDING

L

R N

O I

T C

E T

O

U

P

OR EQUAL

INSTALL MAST TO UNISTRUT

15'-6" MINUMUM

ABOVE ROOF

AutoCAD SHX Text

LIGHTNING PROTECTION PLAN

AutoCAD SHX Text

SCALE 1/8" = 1'

AutoCAD SHX Text 16'

AutoCAD SHX Text 32'

AutoCAD SHX Text

AutoCAD SHX Text 8'

AutoCAD SHX Text 16'

AutoCAD SHX Text 48'

AutoCAD SHX Text

LIGHTNING PROTECTION

AutoCAD SHX Text

PLOT DATE

AutoCAD SHX Text

PROJECT

AutoCAD SHX Text

DATE

AutoCAD SHX Text

NUMBER

AutoCAD SHX Text

LP001

AutoCAD SHX Text

SHEET

AutoCAD SHX Text 3-17-21

AutoCAD SHX Text

NUMBER

AutoCAD SHX Text 3-17-21

AutoCAD SHX Text

MR. LIGHTNING / LIGHTNING PRO

AutoCAD SHX Text

LIGHTNING PROTECTION

AutoCAD SHX Text

COLORADO SPRINGS, COLORADO

AutoCAD SHX Text

DRAWING TITLE

AutoCAD SHX Text

ROOF LEVEL -

AutoCAD SHX Text

COLORADO SPRINGS, COLORADO

AutoCAD SHX Text

ANTENNA PLATFORM B2024

AutoCAD SHX Text

PETERSON AFB

AutoCAD SHX Text Bret A. Peifer

AutoCAD SHX Text Master Installer Designer

AutoCAD SHX Text # 1042

AutoCAD SHX Text www.lightning.org

AutoCAD SHX Text Date

AutoCAD SHX Text Signature

AutoCAD SHX Text 3-17-21

AutoCAD SHX Text

REVISION

AutoCAD SHX Text

DATE:

AutoCAD SHX Text

BONDING CONNECTION BETWEEN MAIN CONDUCTOR AND METAL OBJECT WITHIN 6'

AutoCAD SHX Text

EXISTING GROUND TERMINAL - COPPER CLAD STEEL GROUND ROD, 3/4" DIA. X 10' LONG.

AutoCAD SHX Text LIGHTNING PROTECTION CABLE - 24 STRANDS OF 14 GA. ALUMINUM WIRE, AREA OF CONDUCTIVITY 98,640 cmil.

AutoCAD SHX Text AIR TERMINAL - BARE ALUMINUM 1/2" DIA. X 12" LONG, MOUNTING HARDWARE AS REQUIRED FOR EACH SPECIFIC TYPE OF LOCATION.

AutoCAD SHX Text

LEGEND

AutoCAD SHX Text

STANDARDS

AutoCAD SHX Text SYSTEM SHALL BE DESIGNED AN INSTALLED TO MEET THE STANDARDS SET FORTH BY THE NATIONAL FIRE PROTECTION ASSOCIATION (NFPA-780, 2014 EDITION), AND UNDERWRITER'S LABORATORIES STANDARD (UL96A, 2014 EDITION). DESIGN, MATERIALS, WORKMANSHIP AND INSPECTION SHALL BE BASED ON THE LPI (LIGHTNING PROTECTION INSTITUTE) LPI-175 STANDARD OF PRACTICE. DESIGN MAY VARY DUE TO FIELD CONDITIONS.

AutoCAD SHX Text MAST AIR TERMINAL - FIBERGLASS 2" X 21'-3" WITH 25' #228 CLASS II LIGHTNING PROTECTION CONDUCTOR WITH 24" BLUNT TIP AIR TERMINAL.

AutoCAD SHX Text

EXISTING SYSTEM TO REMAIN. (TYP.)

AutoCAD SHX Text

NOTE:

AutoCAD SHX Text THRU ROOF PENETRATION- EXISTING 1" PVC SLEEVE. FLASHING DONE BY ROOFING CONTRACTOR.

AutoCAD SHX Text

GLOBAL ASNT

AutoCAD SHX Text

AFCPT FIXED ANTENNA

AutoCAD SHX Text

FAB-T ANTENNA

AutoCAD SHX Text

2 MMP

AutoCAD SHX Text

FAB-T ANTENNA

AutoCAD SHX Text 150' Radius

AutoCAD SHX Text 150' Radius

AutoCAD SHX Text

SIDE VIEW

AutoCAD SHX Text

END VIEW

Sheets and Views
Model