This is a technical addendum to RFP 20262020 issued by the City of Eugene, Oregon, specifying detailed electrical equipment specifications for Building 10 in the Community Renewable Energy Project. The addendum provides comprehensive technical specifications for an SB3 Switchboard (Alternative #1 MTS) comprising four sections designed for outdoor installation with flat roof configuration. The switchboard operates on a 480Y/277 volt, three-phase four-wire wye AC system with a 65,000 ampere capacity and features a 65C copper bus rated for 3,000 amperes incoming service. Section 1 functions as a distribution panel containing four 800-ampere branch breakers, one 200-ampere branch breaker, and two 100-ampere branch breaker spaces with associated cable specifications. Section 2 serves as the main service section equipped with a 3,000-ampere main breaker, dynamic arc-flash sentry maintenance mode, ground fault protection with ETU776 trip unit, and a surge protective device rated at 200 kiloamperes with SPD surge counter. Section 3 is configured as a bussed utility section containing provisions for Eugene Water & Electric Utility metering with 3,000-ampere capacity. Section 4 functions as an incoming bussed pull section with future connection provisions for both incoming and outgoing 3,000-ampere connections.

All four sections incorporate outdoor-rated construction with 4.125-inch front extensions, flat roof gasket-sealed enclosures (3R outdoor rating), copper ground buses, special shipping skids for large sections, and rear and section barriers. The switchboard includes 3,000-ampere interconnection components throughout, wire marker labels, and standardized bus configurations with top and bottom thru-bus arrangements. This electrical infrastructure is foundational to the renewable energy project's power distribution system, supporting the integration of the 120-kilowatt solar photovoltaic array and 440-kilowatt-hour battery energy storage system scheduled for operation by January 25, 2028.

View the file

Other files

On GovTribe

Work with this file

  • Download the original file
  • Contacts named in this file
  • Similar government files
  • Ask GovTribe AI about this file

Text version

SWB BLDG 10 ALT #1 MTS--SB3 SWITCHBOARD - 4 SECTIONS

SB3, Material group 3: VD7, Incoming Location: Bottom, Incoming Position: Right, Service Entrance: Yes, System: 480Y/277 3Ø4W WYE AC, 65,000 A, Bus Bracing:

65,000 A, Bus Material: 65°C Copper, Bus Rating: Non-Tapered, Incoming Bus

Amperage: 3,000 A, Enclosure Rating: 3R - Outdoor(w/gaskets), Flat Roof.

SECT.1-DISTRIBUTION

Section Type: Distribution Panel.

1 - Rear Bus Barrier

1 - Section Barrier

1 - Standard Frame

1 - Hinged Gutter Covers

1 - 3,000 Copper Section Bus

1 - 3,000 Amp Top Thru Bus

1 - Outdoor Construction, Flat Roof, 4.125 Front Extension

1 - Extra Section Depth

1 - Copper Ground Bus

1 - Special shipping skid for large sections

1 - 1,200 A/3P SHND6 Branch Breaker Space

1 - Standard DAS (Dynamic Arc-Flash Sentry) Maintenance Mode

4 - 800 A/3P 3VA55-HMAS Branch

1 - Catalog #: 3VA55806EC320AA0

1 - 800 A/3P 3VA55

1 - Model TM230 FTAM

1 - (3)4/0-500 KCMIL CU/AL

1 - 200 A/3P 3VA52-HFAS Branch

1 - Catalog #: 3VA52206EC310AA0

1 - 200 A/3P 3VA52

1 - Model TM230 FTAM

1 - (1)#6-350 KCMIL Cu/Al

1 - 100 A/3P 3VA41-HEAB Branch

1 - Catalog #: 3VA41106ED340AA0

1 - 100 A/3P 3VA41

1 - Model TM210 FTFM

1 - (1)#14-3/0 KCMIL CU/AL

1 - 100 A/3P 3VA41-HEAB Branch Space

1 - Space - Panel Mount 125A 3VA MCCB

1 - AUXILIARY COMPARTMENT

SECT.2-MAIN

Section Type: Main Service.

1 - Heavy Duty Frame

1 - Rear Bus Barrier

1 - Section Barrier

1 - 3,000 Copper Section Bus

1 - 3,000 Amp Top Thru Bus

1 - 65°C Copper Neutral

1 - 3,000 Amp Bottom Thru Bus

1 - Outdoor Construction, Flat Roof, 4.125 Front Extension

1 - Copper Ground Bus

1 - Special shipping skid for large sections

1 - Wire Marker Labels

1 - 3,000 Amp Interconnection Components

1 - 3,000 A/3 Main WL Breaker

1 - 3000 A/3P WL Breaker 3,000 A Rating Plug

1 - Catalog #: L2F330WYXXXXXXJ

1 - COM35 Module for DAS only

1 - Fixed Mounted UL489

1 - L Class - Frame Size 2

1 - ETU776 Trip Unit w/ GF Alarm + Trip LSIG

1 - 24VDC WL LCD Power Supply

1 - Standard DAS (Dynamic Arc-Flash Sentry) Maintenance Mode

1 - Ground Fault Type: Standard Residual

1 - AUXILIARY COMPARTMENT

1 - Surge Protective Device - 200kA Service SPD

1 - SPD Surge Counter

1 - US2:TPS4E0620X2

SECT.3-AUXILIARY

Section Type: Bussed Utility.

1 - Heavy Duty Frame

1 - Rear Bus Barrier

1 - Section Barrier

1 - 3,000 Copper Section Bus

1 - 3,000 Amp Bottom Thru Bus

1 - 65°C Copper Neutral

1 - 3,000 Amp Top Thru Bus

1 - Outdoor Construction, Flat Roof, 4.125 Front Extension

1 - Copper Ground Bus

1 - EUGENE WATER ELEC UTILITY METERING COMPARTMENT

1 - 3000A EUSERC Utility Meter Provision

SECT.4-AUXILIARY

Section Type: Incoming Bussed Pull.

1 - Standard Frame

1 - Rear Bus Barrier

1 - 3000 Future Connection (Incoming)

1 - Master Nameplate

1 - 3000 Future Connection (Outgoing)

1 - 3,000 Amp Top Thru Bus

1 - 65°C Copper Neutral

1 - Outdoor Construction, Flat Roof, 4.125 Front Extension

1 - Copper Ground Bus

1 - 500 Kcmil Provision Only 3000-3200A Comp Lug Provisions

1 - INCOMING LUGS: N/A