20252030_A1_Attachment B_Drawings.pdf
PDF 2 MB Posted
- Attached to
- Oregon Libraries E-Rate Consultant Project
- Solicitation number
- S-12300-00013679
- Issued by
- Oregon
About this file
This file consists of architectural permit documents for a fitness room remodel project at the City of Eugene Public Works facility located at 1820 Roosevelt Boulevard, Eugene, Oregon. The project involves renovating an existing tool storage room into a new exercise room for employee use on a 10.53-acre property (Tax Lot 100, Map 17-04-25-30). The architect of record is Robert Nicholls Architecture & Design, with Robert J. Nicholls, AIA serving as the point of contact. The scope of work includes new thin-set cementitious flooring, insulated furring walls at the building perimeter, new wall openings, a new suspended ceiling assembly, and associated finishes with no increase to building area. The project is classified as Assembly occupancy (gymnasium without fixed seats) under construction type 5B, with an occupant load of 22 persons and one required exit. The design documents are dated April 7, 2025, and are presented as permit-phase drawings (Project No. 2437) consisting of site plans, floor plans, elevations, sections, and detailed specifications including door and window schedules.
The project incorporates energy efficiency measures compliant with ASHRAE Standard 90.1-2022 for climate zone 4C, with ceiling insulation upgraded to R-49 total and wall assemblies upgraded to R-21 minimum. Mechanical, electrical, and plumbing work is specified to be performed under a separate design-build agreement with the general contractor, with individual trades responsible for associated design, engineering, and permitting. Equipment specifications include a Mitsubishi mini-split HVAC system (48K BTU), Big Ass Fans i6 84-inch indoor ceiling fan, LED lay-in light fixtures, and Elkay water bottle filler. The design incorporates accessibility compliance with ANSI A117.1 standards and requires hazardous materials abatement by the owner prior to project commencement. The drawings include specifications for wall types with varying insulation values, structural details for metal stud framing, and coordination requirements for electrical panel installation with a 200-amp sub-panel fed from Panel 2 at 120/208V.
View the file
Other files
Show all 11
On GovTribe
Work with this file
- Download the original file
- Contacts named in this file
- Similar government files
- Ask GovTribe AI about this file
Text version
PROJECT INFORMATION
G100 GENERAL INFORMATION
A100 PLANS
A200 ELEVATIONS & SECTION
A300 DETAILS
SHEET LIST
SITE ADDRESS
1820 ROOSEVELT BLVD.
EUGENE, OREGON 97405
MAP + TAXLOT
MAP:17042530
TAXLOT: 100
SIZE: 10.53 ACRES
OWNER
CITY OF EUGENE
1820 ROOSEVELT BLVD.
EUGENE, OREGON 97405
ARCHITECT
ROBERT NICHOLLS ARCHITECTURE & DESIGN
999 S. 71ST STREET
SPRINGFIELD, OREGON 97478
POC: ROBERT J. NICHOLLS, AIA
EMAIL: bnicholls@rnarchdesign.com
PHONE: 530.613.5580
COPYRIGHT ROBERT NICHOLLS
ARCHITECTURE & DESIGN INC
C
IT
Y O
F
EU
G
EN
E
- P
U
BL
IC
W
O R
KS
R O
O
SE
VE
LT
B
LV
D . E
U G
EN
E, O R
REVISIONS
NO. DATE TITLE
ISSUE DATE:
PROJECT NO:
PROJECT PHASE:
PERMIT DOCUMENTS
FI
TN
ES
S
R O
O M
R
EM
O D
EL
G100
GENERAL
INFORMATION
07 APR 2025
PROPERTY LINE
EXISTING WALL TO REMAIN
NEW WALL ASSEMBLY
NEW WINDOW, SEE ALSO WINDOW SCHEDULE
NEW DOOR, SEE ALSO DOOR SCHEDULE
(E) 6" SANITARY SEWER LINE
TYPE 2A10BC BRACKET MOUNT FIRE EXTINGUISHER
-MOUNT HANDLE @ 48" AFF MAX
(N) DUPLEX RECEPTACLE, 18" AFF, UON
(N) DATA RECEPTACLE, 18" AFF, UON
-PROVIDE CONDUIT PATHWAY & ROUGH-IN BOX ONLY
-CABELING AND TERMINATION BY OWNER
GENERAL NOTES
1. DRAWINGS AND SPECIFICATIONS AS INSTRUMENTS OF SERVICE ARE AND SHALL REMAIN THE
PROPERTY OF THE ARCHITECT. THEY ARE NOT TO BE USED ON EXTENSIONS OF THE PROJECT,
OR OTHER PROJECTS, EXCEPT BY AGREEMENT IN WRITING WITH THE ARCHITECT. THE
GENERAL CONTRACTOR IS RESPONSIBLE FOR CONFIRMING AND CORRELATING DIMENSIONS
AT THE JOB SITE. THE ARCHITECT WILL NOT BE RESPONSIBLE FOR CONSTRUCTION MEANS,
METHODS, TECHNIQUES, SEQUENCES, OR PROCEDURES, OR FOR SAFETY PRECAUTIONS AND
PROGRAMS IN CONNECTION WITH THE ARCHITECT
2. FIELD VERIFY EXISTING CONDITIONS & DIMENSIONS
3. BRING CONFLICTS & INCONSISTENCIES WITHIN PROJECT DOCUMENTS AND/OR FIELD
CONDITIONS TO ATTENTION OF ARCHITECT BEFORE PROCEEDING WITH WORK
4. DO NOT SCALE DRAWINGS. COORDINATE DIMENSIONS SHOWN ON DRAWINGS WITH ACTUAL
FIELD MEASUREMENTS. NOTIFY ARCHITECT OF DISCREPANCIES
5. CLEAN CONSTRUCTION CAVITIES PRIOR TO ENCLOSING, INCLUDING ABOVE CEILING GRID AND
WITHIN WALL CAVITIES
6. PROTECT (E) ITEMS TO REMAIN FOR DURATION OF WORK
7. DIMENSIONS ARE TO FACE OF FINISH, UON
8. VERIFY LOCATIONS AND MOUNTING HEIGHT FOR ELECTRICAL DEVICES PRIOR TO ROUGH-IN
9. PROVIDE SOLID BLOCKING AT CASEWORK, ACCESSORIES, EQUIPMENT, AND FIXTURES AS
REQUIRED
SITE PLAN
1/64" = 1'-0"1 NORTH
CITY OF EUGENE, PUBLIC WORKS - FITNESS ROOM REMODEL
SCOPE OF WORK:
RENOVATE EXISTING TOOL STORAGE ROOM INTO NEW EXERCISE
ROOM FOR EMPLOYEE USE. WORK GENERALLY INCLUDES NEW
THIN SET CEMENTITIOUS FLOORING, INSULATED FURRING WALL @
PERIMETER OF BUILDING, NEW OPENINGS, NEW SUSPENDED
CEILING ASSEMBLY, AND FINISHES.
NO NEW BUILDING AREA
MEP SCOPE NOTE:
PLUMBING, MECHANICAL, AND ELECTRICAL SCOPE IS UNDER A
SEPARATE DESIGN-BUILD AGREEMENT WITH THE GENERAL
CONTRACTOR. INDIVIDUAL TRADES ARE RESPONSIBLE FOR
ASSOCIATED DESIGN, ENGINEERING, PERMITS, AND PERMIT
REQUIREMENTS.
ABATEMENT:
ANY NECESSARY ABATEMENT OF HAZARDOUS MATERIALS IN THE
AFFECTED SPACES TO BE COMPLETED BY OWNER PRIOR TO THE
COMMENCEMENT OF THIS PROJECT.
SUMMARY OF WORK
CODES:
2022 OREGON STRUCTURAL SPECIALTY CODE
ENERGY CODE: ASHRAE STANDARD 90.1, 2022
2017 ANSI A117.1 ACCESSIBILITY STANDARDS
CHAPTER 3: USE AND OCCUPANCY
OCCUPANCY: ASSEMBLY (GYMNASIUM WITHOUT FIXED SEATS)
USE: EXERCISE ROOM
CHAPTER 5: GENERAL BUILDING HEIGHTS AND AREAS
NO PROPOSED CHANGE TO BUILDING HEIGHT OR AREA
CHAPTER 6: TYPES OF CONSTRUCTION
CONSTRUCTION TYPE: 5B
CHAPTER 10: MEANS OF EGRESS
COMMON PATH OF EGRESS TRAVEL, PER TABLE 1006.2.1
REQUIRED: 75' MAX (ASSEMBLY SPACE W/ LESS THAN 30 OCCS)
PROPOSED: 60'
EXIT ACCESS TRAVEL DISTANCE, PER TABLE 1017.2
REQUIRED: 200' MAX (ASSEMBLY SPACE W/OUT SPRINKLERS)
PROPOSED: 60'
EXIT SIGN PROVIDED IN THE DIRECTION OF EGRESS TRAVEL
OCCUPANT LOAD PER 1004
EXERCISE ROOM
1,085 SF / 50 GROSS = 22 OCCS
ONE EXIT REQ'D, ONE EXIT PROVIDED
ENERGY CODE (ASHRAE STANDARD 90.1)
CLIMATE ZONE: 4C
INSULATION VALUES:
CEILING: R-19 EXISTING, ADDING R-30 FOR TOTAL OF R-49
WALL: R-9 EXISTING, ADDING R-11 FOR TOTAL OF R-21
R-21 AT NEW EXTERIOR WALL INFILL
FLOOR: EXISTING SLAB ON GRADE
OPAQUE DOORS - SWINGING: U-0.37
OPAQUE DOORS - NON-SWINGING: U-0.31
FENESTRATIONS - FIXED: U-0.36, SHGC-0.36
FENESTRATIONS - OPERABLE: U-0.45, SHGC-0.33
ENTRANCE DOOR: U-0.63, SHGC-0.33
ANSI A117.1 ACCESSIBILITY CODE:
SEE DRAWINGS FOR COMPLIANCE WITH ANSI A117.1 ACCESSIBILITY
CODE ANALYSIS
AREA OF WORK
VICINITY MAP
NTSA NORTH
PROJECT SITE
1820 ROOSEVELT
BLVD.
W. 6TH AVE.
W. 7TH AVE.
HWY 99
ROOSEVELT
BLVD
CHAMBERS ST.
LEGEND
NEW
SS
FE
ACT ACOUSTICAL CEILING TILE
ADJ ADJUSTABLE
AFF ABOVE FINISH FLOOR
APPROX APPROXIMATE
ARCH ARCHITECTURAL
AVG AVERAGE
BD BOARD
BLDG BUILDING
BLK BLOCK
BLKG BLOCKING
BLW BELOW
BOT BOTTOM
CAB CABINET
CB CEMENT BOARD
CLR CLEAR
CPT CARPET
COL COLUMN
CONC CONCRETE
CONT CONTINUOUS
DBL DOUBLE
DET DETAIL
DIA DIAMETER
DIM DIMENSION
DN DOWN
DWG DRAWING
E EXISTING
EA EACH
ELEC ELECTRICAL
ELEV ELEVATION
EP ELECTRICAL PANEL
EQ EQUAL
EQUIP EQUIPMENT
EXT EXTERIOR
FA FIRE ALARM
FD FLOOR DRAIN
FDN FOUNDATION
FE FIRE EXTINGUISHER
FEC FIRE EXTINGUISHER CABINET
FF FACTORY FINISH
FIN FINISH
FLR FLOOR
F.O. FACE OF
FR FIRE RATED
FRP FIBERGLASS REINFORCED
PLASTIC
FT FOOT OR FEET
FTG FOOTING
GA GAUGE
GALV GALVANIZED
GB GYPSUM BOARD
HDWE HARDWARE
HM HOLLOW METAL
HORIZ HORIZONTAL
HT HEIGHT
ID INSIDE DIAMETER
INSUL INSULATION
INT INTERIOR
JT JOINT
LAM LAMINATE
LAV LAVATORY
LT LIGHT
MAX MAXIMUM
MECH MECHANICAL
MFR MANUFACTURER
MIN MINIMUM
MISC MISCELLANEOUS
N NEW
N.I.C. NOT IN CONTRACT
NO. NUMBER
NOM NOMINAL
NTS NOT TO SCALE
O.C. ON CENTER
OD OUTSIDE DIAMETER
OFCI OWNER-FURNISHED,
CONTRACTOR- INSTALLED
OFOI OWNER FURNISHED, OWNER
INSTALLED
OPP OPPOSITE
OSSC OREGON STRUCTURAL
SPECIALTY CODE
PERP PERPENDICULAR
PL PLATE
PLAM PLASTIC LAMINATE
PLYWD PLYWOOD
PS PAINT SYSTEM
R RELOCATE
RB RUBBER BASE
RCP REFLECTED CEILING PLAN
REQ'D REQUIRED
RM ROOM
SCWD SOLID CORE WOOD
SECT SECTION
SIM SIMILAR
SQ SQUARE
SS STAINLESS STEEL
STD STANDARD
STRUCT STRUCTURAL
SUSP SUSPENDED
T TEMPERED GLAZING
THK THICK
T.O. TOP OF
TYP TYPICAL
UON UNLESS OTHERWISE NOTED
VERT VERTICAL
VFY VERIFY
W/ WITH
WD WOOD
W/O WITHOUT
WRGB WATER-RESISTANT GYPSUM
BOARD
WB WOOD BASE
ABBREVIATIONS
ROOSEVELT BLVD.
RAILROAD
7.
TAX LOT: 100
10.53 ACRES
FE
EX
IT
SSS
T
COPYRIGHT ROBERT NICHOLLS
ARCHITECTURE & DESIGN INC
C
IT
Y O
F
EU
G
EN
E
- P
U
BL
IC
W
O R
KS
R O
O
SE
VE
LT
B
LV
D . E
U G
EN
E, O R
REVISIONS
NO. DATE TITLE
ISSUE DATE:
PROJECT NO:
PROJECT PHASE:
PERMIT DOCUMENTS
FI
TN
ES
S
R O
O M
R
EM
O D
EL
A100
PLANS
07 APR 2025
FLOOR PLAN - DEMOLITION
1/4" = 1'-0"1
0 1 2 4
NORTH FLOOR PLAN - NEW
1/4" = 1'-0"2 NORTH REFLECTED CEILING PLAN - NEW
1/4" = 1'-0"3 NORTH
DEMOLISH INTERIOR NON-LOAD BEARING WALL
DEMOLISH DOOR, FRAME, AND HARDWARE
DEMOLISH OVERHEAD DOOR, FRAME, AND HARDWARE
DEMOLISH WINDOW ASSEMBLY
DEMOLISH WALL AS REQ'D FOR NEW WORK
DEMOLISH CASEWORK
DEMOLISH WD RAMP
DEMOLISH ELECTRICAL PANEL
DEMOLISH FIRE HEAT SENSOR, SALVAGE FOR
RELOCATION
D1
DEMOLITION KEYNOTES
(N) SELF LEVELING THIN-SET CEMENTITIOUS FLOOR
COATING
-AVERAGE DEPTH OF MATERIAL = 1"
-COORDINATE WITH OWNER FOR OFCI RUBBER MAT
FLOOR FINISH AND SUBSTRATE REQUIREMENTS
INFILL WALL, MATCH ADJACENT ASSEMBLY AND FINISH @
OFFICE SIDE
WATER BOTTLE FILLER
-MFR: ELKAY, MODEL: LZS8WS1F
-CONNECT TO (E) ADJACENT WATER SUPPLY LINE
-CONNECT TO (E) 6" SANITARY SEWER LINE AS SHOWN
-PATCH ASSEMBLIES AS REQ'D BY NEW WORK AND
PLUMBING CONNECTIONS
-PROVIDE POWER AS REQ'D
-INSTALL PER MFR INSTRUCTIONS
APPROX LOCATION OF DRAIN LINE CONNECTION TO (E) 6"
SANITARY SEWER LINE
PLAM CLAD WD CUBBIES, SEE ALSO ELEVATIONS
6' LONG FIXED WD BENCH, SEE ALSO ELEVATIONS
(N) SUSPENDED CEILING ASSEMBLY
2X4 LED LAY-IN LIGHT FIXTURE
-MATCH BLDG STANDARD W/ COLOR SELECT, COORD W/
OWNER
(N) CEILING CASSETTE
-BASIS-OF-DESIGN: MITSUBISHI PLFY-EP-NEMU 48K BTU,
OR EQUAL AND AS REQ'D BY CODE
-PROVIDE POWER AS REQ'D
KEYNOTES
FITNESS RM
FITNESS RM
100 100
8' -1
1"
'-5
'-5
8'
-1 1"
5'-11 2"
26'-71 4"
'-8
8' -0
6'
-1 0"
9' -1
0"
D2
D3
D4
D5
D6
D1
D1
D2
D2
D7
D7
D3
D4
D5
D5
D5
D2 D5
D6
D6
D6
±11'-0" AFF
(N) CEILING
A200
B
B
A
C
B
N100A
N
0B
C
(N) MINI-SPLIT OUTDOOR UNIT
-BASIS-OF-DESIGN: MITSUBISHI 48K, OR EQUAL AND AS
REQ'D BY CODE
-PROVIDE HOUSEKEEPING PAD PER MFR REQ'S
-PROVIDE POWER AS REQ'D, INCLUDE 60 AMP
DISCONNECT
(N) THERMOSTAT
-BASIS-OF-DESIGN: MITSUBISHI MHK2, OR EQUAL AND AS
REQ'D BY CODE
-MOUNT ON WALL @ 48" AFF MAX
(N) CEILING FAN
-MFR: BIG ASS FANS, MODEL: i6 84" INDOOR
-MOUNT TO (E) I-BEAM ABV (N) SUSPENDED CEILING ASSY
-MOUNT FAN PER MFR INSTRUCTIONS
-PROVIDE POWER AS REQ'D
-INSTALL PER MFR INSTRUCTIONS
(R) CEILING MOUNT FIRE HEAT SENSOR
(R) EMERGENCY EGRESS LIGHT
(R) EMERGENCY EGRESS STROBE
SAFETY LIGHT, CONSTANT ON
PROVIDE (2) 3 4" CONDUITS FOR PROXY ACCESS CONTROL
AND DOOR SECURITY SENSOR
-TERMINATE CONDUIT ABOVE CEILING GRID & @ CARD
READER LOCATION
-CARD READER OFOI
(N) 200 AMP SUB PANEL
-FEED FROM PANEL 2, 120/208V, COORD W/ OWNER
MOUNT DEVICE @ ±6'-0" AFF, COORDINATE W/ OFCI
MONITOR AND BRACKET
(E) I-BEAM ABOVE, DASHED FOR REFERENCE
TYP
A2002
D8
D8
SS
SS
SS
SS
SS
SS
SS
SS
SS
SS
SS
DEMOLISH EMERGENCY EGRESS LIGHT, SALVAGE FOR
RELOCATION
DEMOILSH EMERGENCY EGRESS STROBE, SALVAGE FOR
RELOCATION
DEMOLISH WALL HUNG FIRE EXTINGUISHER, SALVAGE
FOR RELOCATION
DEMOLISH WATER LINE AND PLYWOOD SURROUND BACK
TO (N) WATER BOTTLE FILLER LOCATION
D9
D10
D11
D9
ABV
D10
D11
D12
D12
±6'-0" AFF
±6'-0" AFF
D13
D13
1' -1
01 2" ±5
'-7 1 2"
M 6'x3' M 6'x3' M 6'x3'
COPYRIGHT ROBERT NICHOLLS
ARCHITECTURE & DESIGN INC
C
IT
Y O
F
EU
G
EN
E
- P
U
BL
IC
W
O R
KS
R O
O
SE
VE
LT
B
LV
D . E
U G
EN
E, O R
REVISIONS
NO. DATE TITLE
ISSUE DATE:
PROJECT NO:
PROJECT PHASE:
PERMIT DOCUMENTS
FI
TN
ES
S
R O
O M
R
EM
O D
EL
A200
ELEVATIONS
& SECTION
07 APR 2025
ELEVATION - NORTH
1/4" = 1'-0"1 ELEVATION - WEST
1/4" = 1'-0"2
ELEVATION - SOUTH
1/4" = 1'-0"4ELEVATION - EAST
1/4" = 1'-0"3
T T
T T
T T
T 1 1
N100A N100B
T 2 T 2 T
HATCH INDICATES APPROX
AREA OF (N) INFILL WALL
(WITHIN (E) OVERHEAD DR
BAY)
PLAM CLAD WOOD CUBBIES
BOTTLE FILLER & DRINKING
FOUNTAIN
6' -0
3' -0
4" FRAMELESS MIRROR
T = TEMPERED GLAZING
6' -0
6' -0
4' -0
4' -0
OFCI 84" MONITOR
-PROVIDE POWER AS REQ'D
-PROVIDE ADDITIONAL
CONDUIT PATHWAY FOR OFOI
DATA CABLING AND
TERMINATION
-PROVIDE BACKING AS REQ'D
T T
BUILDING SECTION
1/4" = 1'-0"5
FITNESS RM
100 11
'-0
(E) STRUCTURE TO REMAIN
ROOF ASSEMBLY
-(E) SM ROOF PANEL, WEATHER BARRIER, SUBSTRATE, &
STRUCTURE TO REMAIN
-(E) R-19 BATT INSULATION W/ VAPOR BARRIER (CUT EACH
BAY PRIOR TO COVERING)
-(N) R-30 FIBERGLASS BATT INSULATION. HOLD TIGHT TO (E)
INSULATION W/ FSK PAPER, OR APPROVED EQUAL
-TOTAL R-49 ROOF ASSEMBLY
(N) SUSPENDED CEILING
ASSEMBLY
A300
A300
OFCI 84" MONITOR
-PROVIDE POWER AS REQ'D
-PROVIDE ADDITIONAL
CONDUIT PATHWAY FOR OFOI
DATA CABLING AND
TERMINATION
-PROVIDE BACKING AS REQ'D
T T
HATCH INDICATES FROSTED
GLAZING FILM
6'W WOODEN BENCH
COPYRIGHT ROBERT NICHOLLS
ARCHITECTURE & DESIGN INC
C
IT
Y O
F
EU
G
EN
E
- P
U
BL
IC
W
O R
KS
R O
O
SE
VE
LT
B
LV
D . E
U G
EN
E, O R
REVISIONS
NO. DATE TITLE
ISSUE DATE:
PROJECT NO:
PROJECT PHASE:
PERMIT DOCUMENTS
FI
TN
ES
S
R O
O M
R
EM
O D
EL
A300
DETAILS
07 APR 2025
MARK SIZE
WIDTH HEIGHT THICKNESS
DOOR
TYPE MATERIAL FINISH
FRAME
TYPE MATERIAL FINISH
HDWR
TYPE
FIRE
RATING
COMMENTS
3'-0" 6'-8" 1-3/4" A HM PS F1 1
DOOR SCHEDULE
HM PS -
N/AN100B
N100A 6'-0" 1-3/4" N/A N/A N/A N/A N/A8'-0" B -
INSULATED DR & GLAZING
HARDWARE TYPE 1
-HEAVY DUTY HINGES
-LOCKSET: LEVER HARDWARE - ENTRANCE FUNCTION
-COORDINATE WITH OWNER FOR CITY STANDARD LOCKSET,KEYING, INSTALLATION, AND CORES
-CLOSER/HOLD-OPENS
-(R) ELECTRONIC ACCESS CONTROL & CARD READER
OVERHEAD DR
MARK SIZE
WIDTH HEIGHT
FRAME
MATERIAL FINISH
GLAZING TYPE COMMENTS
5'-0" 3'-8" ALUM FF, NOTE 1
WINDOW SCHEDULE
1 -
NOTES
1. MATCH (E) DARK BRONZE FINISH, LOW-E COATING
PROVIDE SCREENS, SEE ELEVATIONS FOR SLIDING FUNCITON
2 4'-0" 2'-0" ALUM TEMPERED AWNING FUNCTION
5'-0" 3'-8" ALUM3 - FIXED, (E) OPENING
WALL TYPES
1" = 1'-0"4
(E) WALL ASSY TO
REMAIN
WALL TYPE - A WALL TYPE - B
WEATHER BARRIER
(N) T-111 SIDING, MATCH
EXISTING ADJACENT SIDING
-PRIME & PAINT TO MATCH
WALL TYPE - CA B C
(E) WALL ASSY TO
REMAIN
ACOUSTICAL BATT
INSULATION
2" RC-CHANNEL @ 24"
OC MAX
8" TYPE 'X' GYP BD
W/ #6 TYPE S
DRYWALL SCREWS
MIN @ 12" OC MAX
-PS FINISH
3-5/8" SM STUD @ 24"
OC MAX, SSMA
362S125-30 33 KSI OR
EQUAL
VAPOR BARRIER
(E) WALL ASSY TO
REMAIN
(E) WALL ASSY TO
REMAIN
R-11 BATT INSULATION (TOTAL
WALL ASSEMBLY = R-21 MIN)
VAPOR BARRIER
R-21 BATT INSULATION
6" SM STUD @ 16" OC
MAX, SSMA
600S137-43 33 KSI OR
EQUAL
VAPOR BARRIER
HEADER SCHEDULE
3" = 1'-0"3
STUD WALL ABV, WHERE
OCCURS, TYP
SSMA 600S137-43 33KSI OR
EQUIVALENT
STUD TRACK 54 MIL. MIN. #10 SMS @ 12" OC MAX
4'-0" TO 5'-0" OPENING
DOOR TYPE A
1/4" = 1'-0"
3' -7
" M
AX
6" 6"
T
HALF-LITE TEMPERED
GLAZING AND FRAME
T = TEMPERED GLAZING
FRAME TYPE F1
1/4" = 1'-0"
M
AT
CH
D
R
MATCH DR16 GA. HM FRAME
-PS FINISH
HM INSULATED DOOR
-PS FINISH
FF, NOTE 1
FF, NOTE 1
WALL BASE DETAIL
3" = 1'-0"2
(E) CONCRETE STEMWALL TO
REMAIN
WALL ASSY PER PLAN
4" RUBBER BASE, TYP
THROUGHOUT
FASTEN METAL STUD TRACK TO
(E) SLAB FOUNDATION W/ 3 8" DIA
SIMPSON STRONGBOLT2
ANCHORS @ 48" OC W/ 1.5"
EFFECTIVE EMBEDMENT
(E) CONCRETE SLAB ON
GRADE
3-5/8" SM STUD @ 24"
OC MAX, SSMA
362S125-30 33 KSI OR
EQUAL
8" TYPE 'X' GYP BD
W/ #6 TYPE S
DRYWALL SCREWS
MIN @ 12" OC MAX
-PS FINISH
8" TYPE 'X' GYP BD
W/ #6 TYPE S
DRYWALL SCREWS
MIN @ 12" OC MAX
-PS FINISH
OPENING DETAIL
3" = 1'-0"1
HEADER PER SCHEDULE
(E) SIDING TO REMAIN
(N) PREFIN SM FLASHING W/ 3"
UPTURNED LEG BEHIND (E)
WEATHER BATTIER & DRIP
EDGE
(N) FLEXIBLE SELF-ADHESIVE
FLASHING @ PERIMETER OF OPENING
-CONTIN. OVER FACE/FRAME 3" MIN,
INTEGRATE W/ WEATHER BARRIER &
FLASHINGS TO DRAIN
BACKER ROD & SEALANT, TYP
ALUM WINDOW ASSY PER
SCHEDULE
(N) FLEXIBLE SELF-ADHESIVE
FLASHING @ PERIMETER OF OPENING
-CONTIN. OVER FACE/FRAME 3" MIN,
INTEGRATE W/ WEATHER BARRIER &
FLASHINGS TO DRAIN
(E) WEATHER BARRIER
(E) WEATHER BARRIER
PREFIN SM FLASHING W/ END
DAMS & HEMMED EDGE
DOOR TYPE B
1/4" = 1'-0"
T = TEMPERED GLAZING
T T
T T
T T
T T
*NOTE*
WEB STIFFENERS REQ'D
@ ENDS OF BOXED STUD
HEADERS