The document is a set of architectural and electrical design drawings for the 7th Air Support Operations Squadron (7 ASOS) Facility Power and Data Installation at Dyess Air Force Base in Texas. The drawings include a cover sheet, site plan for new construction, and detailed electrical wiring and rack installation specifications. Key technical details include:
The site plan shows a new facility layout with multiple building structures, located at 1113 SSGT Sims St, Ft. Bliss, TX 79906. The electrical design includes a detailed wiring riser diagram depicting a new main disconnect switch, meter installation, electrical conduit routing, grounding electrode installation, and connections to existing electrical infrastructure. The drawings specify technical requirements such as 5/8" Unistrut mounting, PVC to rigid conduit transitions, and comprehensive electrical system integration for the facility power and data installation.
View the file
Other files
| File | Type | Posted |
|---|---|---|
| QA Sheet (8-5-25).xlsx | XLSX spreadsheet | |
| Outside SCIF.jpg | JPG image | |
| Solicitation Amendment 0002.pdf | ||
| Rack 1.jpg | JPG image | |
| Rack 2.jpg | JPG image | |
| Solicitation Amendment 0001.pdf | ||
| 40ft Adjoined SCIF Drawings 1.03.24 REV.3.pdf | ||
| ASOS Site_2 .jpg | JPG image | |
| Solicitation - FA466125R0011.pdf | ||
| 7ASOS SOW Electrical_Communications_SCIF_2.pdf | ||
| ASOS Site_1.jpg | JPG image | |
| ASOS Site_3.jpg | JPG image | |
| QA Sheet.docx | DOCX document | |
| TX20250245_WD_06-13-2025.pdf |
Show all 14
On GovTribe
Work with this file
- Download the original file
- Contacts named in this file
- Similar government files
- Ask GovTribe AI about this file
Text version
ARCHITECTURAL
1 A001 COVER SHEET, GENERAL INFORMATION
2 A201 SITE PLAN - NEW CONSTRUCTION
3 A502 DETAILS
'-0
'-8
1-5/8" UNISTRUT
12"
NOTES INDICATED BY NUMBER IN :
1. PROVIDE HALF-LAPPED WRAP OF 2" ELECTRICAL TAPE OR PLASTIC PIPE
WRAPPING TAPE FOR ENTIRE LENGTH OF RGS STANCHIONS.
2. PROVIDE HALF-LAPPED WRAP OF 2" ELECTRICAL TAPE OR PLASTIC PIPE
WRAPPING TAPE FOR ENTIRE LENGTH OF BURIED RGS CONDUIT PLUS 2" ABOVE
GRADE.
3. CONDUIT FOR GROUNDING ELECTRODE CONDUCTOR TO GROUND ROD.
200A., 3P, FUSIBLE WP MAIN
DISCONNECT SWITCH
EXISTING PAD
MOUNTED XFMR
NEW
METER
EXISTING CONNEX
EXIST PNL.
NEW CONDUCTORS. TRANSITION
FROM PVC TO WP RIGID ABOVE
GRADE
NEW METER MOUNTED
TO XFMR
NEW MAIN
DISCONNECT. SEAL
ALL PENETRATIONS
TIE DISCONNECT TO EXIST
PANEL
CAP, TYP.