2021-03-26 Bid Documents - Drawing PDFs 03a_Life Safety.pdf
PDF 716 KB Posted
- Solicitation number
- 36C24423R0002
About this file
This document package includes bid documents and drawings for the renovation of a boiler plant located at 1700 S. Lincoln Ave in Lebanon, PA, as part of solicitation 36C24423R0002 issued by the Department of Veterans Affairs Veterans Health Administration Veterans Integrated Service Network 4. The project involves life safety upgrades to the boiler and chiller rooms, including the addition of a fire escape ladder to correct an existing common path of travel deficiency on the upper mezzanine level. Drawings show the existing floor plans and details for sprinkler and fire protection systems, exit routes, travel distances, and occupancy requirements in accordance with IBC, NFPA, and VA codes. Products and services required include mechanical, electrical, and structural engineering work.
View the file
Other files
Show all 31
On GovTribe
Work with this file
- Download the original file
- Contacts named in this file
- Similar government files
- Ask GovTribe AI about this file
Text version
DN
UP
UP
UP
UP
STORAGE
CHILLER
ROOM
STAIR#1GENERATOR
ROOM
BOILER ROOM
TOILET/LOCKER
ROOM
CONTROL ROOM OFFICE
TOOL ROOM
PUMP
PIT
PUMP ROOM
STAIR#4
164' MTD (CONTD. FROM ABOVE)
45' CPT
170 N/A
38 (34)5
270 N/A
58 (54)3
160 N/A
36 (32)1
380 N/A
84 (76)4
160 N/A
36 (32)1
160 N/A
36 (32)1
17' MDE
117' MTD (CONTD. FROM ABOVE)
270 N/A
58 (54)1
160 N/A
36 (32)3
FE
C
FE
C
FE
C
FEC
FE
C
FEC
FE
C
UP
UP
UP
UP
STAIR#2B
BOILER ROOM
PUMP ROOM
MID-LEVEL
MEZZANINE
STAIR#2A
STAIR#3
STAIR#4
STAIR#5
STAIR#1
DN
MTD (CONTD. FROM ABOVE)
30' CPT
MTD (CONT. BELOW)
17' MDE
FE
C
FEC
STAIR#3
STAIR#5
WALKABLE CEILING
UPPER-LEVEL
MEZZANINE
T/LOWER CATWALK
PUMP ROOM
DN
DN
MTD (CONT. BELOW)
5 N/A
36 (32)1
FIRE ESCAPE
LADDER
FE
C
FEC
XX' MTD
GROSS DOOR WIDTH
(NET CLEAR WIDTH)
(INCHES)
EXIT
1/2-HOUR PARTITION
1-HOUR FIRE PARTITION
1-HOUR FIRE BARRIER
2-HOUR FIRE BARRIER
3-HOUR FIRE WALL
FIRE EXTINGUISHER
AVAILABLE EGRESS PATH
(CATWALK AREA ONLY)
XXX XXX
XXXXXX
CAPACITY
# OF PEOPLE
STAIR WIDTH
(INCHES)
ACTUAL LOAD
# OF PEOPLE
LEGEND
XX' CPT
K O
F F
E L
ASSOCIATES
ENGINEERS
Fire Protection
R
8815 Centre Park Drive, Suite 200 Columbia, Maryland 21045 410-750-2246 / www.koffel.com
Project Number
Building Number
Drawing Number
Project Title
Location
Issue Date Checked Drawn
Drawing Title
Approved:
VA FORM 08 - 6231
Office of Construction and Facilities Management
U.S. Department of Veterans Affairs
21 4 5 6 7 8 9 10
PhaseENGINEER OF RECORD MILLER-REMICK LLC
PROFESSIONAL ENGINEERCONSULTANT
321 4 5 6 7 8 9 10
PRINTS OF THIS DRAWING SHALL NOT BE USED FOR ANY PURPOSE
WHATSOEVER WITHOUT THE SEAL AND SIGNATURE OF THE
PROFESSIONAL ENGINEEER
o n e e ig h th in c h o n e fo o t o n e q u a rt e r in c h o n e fo o t th re e e ig th s in c h o n e fo o t o n e h a lf in c h o n e fo o t th re e q u a rt e r in c h o n e fo o t o n e in c h o n e fo o t o n e a n d o n e h a lf in c h o n e fo o t th re e in c h o n e fo o t 6
PLAN
NORTH
ACTUAL
NORTH
5/
/2
5:
:4
PM
LEBANON BOILER PLANT
RENOVATION
1700 S. LINCOLN AVE. LEBANON, PA 17042
595-13-101
Project Director
BID DOCUMENTS
FULLY SPRINKLERED
Revisions: Date:
Miller-Remick LLC
1010 KINGS HIGHWAY SOUTH
CHERRY HILL, NEW JERSEY 08034
PHONE: (856)429-4000
FAX: (856)429-5002
M.E.P. & Structural Engineering A Service Disabled Veteran Owned Small Business
A Serv ic e D i s ab l e d Ve t e r an Owned Sma ll Business
SDVOSB
CVE
MR PROJECT NO: 0499-0106
1/8" = 1'-0"SCALE:
LIFE SAFETY PLAN - BOILER ROOM AND CHILLER ROOM NEW WORK
TRAVEL DISTANCE TO EXIT
COMMON PATH OF TRAVEL
DEAD END DISTANCE
EXIT CAPACITY
FEC
LS101
LIFE SAFETY - CATWALK FLOOR PLANS
2020-08-31 CPA MLD
3/16" = 1'-0"SCALE:
LIFE SAFETY PLAN - LOWER CATWALK NEW WORK
3/16" = 1'-0"SCALE:
LIFE SAFETY PLAN - UPPER CATWALK NEW WORK
GENERAL NOTES:
1. NEW FIRE ESCAPE LADDER USED TO CORRECT EXISTING
COMMON PATH OF TRAVEL DEFICIENCY ON UPPER
MEZZANINE LEVEL IS SUBJECT TO AHJ APPROVAL
2. SEE ELECTRICAL DRAWINGS FOR INFORMATION
REGARDING THE FIRE ALARM SYSTEM.
3. EXISTING FIRE-RESISTANCE AND/OR SMOKE-RESISTANCE
RATED BARRIERS WILL NOT BE MODIFIED AS PART OF THIS
PROJECT.
IBC: TYPE IIB
NFPA 220: TYPE II (000)
FIRE-RESISTANCE RATING OF ROOF: 0-HOURS
CONSTRUCTION TYPE
· NFPA 101®, LIFE SAFETY CODE®, 2018 EDITION
· INTERNATIONAL BUILDING CODE, 2018 EDITION
· VA FIRE PROTECTION DESIGN MANUAL (FPDM), 2015 EDITION
APPLICABLE CODES & STANDARDS
BUILDING WILL BE COMPLETELY SPRINKLER-PROTECTED
IBC: GROUP F-1 (SECTION 306.2)
NFPA 101: SPECIAL PURPOSE INDUSTRIAL (SECTION 40.1.2.1.2)
USE AND OCCUPANCY TYPE
XX' CPT