20058 Specifications Part 8.pdf

PDF 5 MB Posted

Attached to
511/20058. CAK; Camp Grayling - Building 3 Renovation
Solicitation number
RFQ - 171 - 230000000515
Issued by
Crawford County, Michigan

About this file

This document is an asbestos and lead-based paint survey report for Building #3 located at Camp Grayling in Grayling, Michigan. The survey was conducted by Northern Analytical Services, LLC and identified six suspect asbestos-containing materials, one of which tested positive for 6% chrysotile asbestos. Several other materials were assumed to contain asbestos. The report provides detailed information on each identified material, including its location, quantity, friability, and asbestos content. The report recommends contracting a licensed asbestos abatement contractor to properly remove any asbestos-containing materials that will be disturbed during upcoming renovation activities. It also recommends providing asbestos awareness training to maintenance and custodial staff, and periodically re-inspecting and assessing the condition of known or assumed asbestos-containing materials.

The report also indicates that paint samples collected did not detect lead, though it recommends treating all painted surfaces as lead-containing and demolition/renovation activities should be conducted by properly trained personnel. The report provides details on the survey methodology, findings, and recommendations to ensure the building is properly remediated and maintained in compliance with applicable regulations.

View the file

Other files

File Type Posted
20058 Drawings Pgs 65-72.pdf PDF
20058 Drawings Pgs 32-40.pdf PDF
20058 Specifications Part 9.pdf PDF
Addendum 2 20058.pdf PDF
20058 Drawings Pgs 51-56.pdf PDF
20058 Specifications Part 7.pdf PDF
_Advertisement 20058.pdf PDF
20058 Drawings Pgs 73-76.pdf PDF
20058 Specifications Part 3.pdf PDF
20058 Specifications Part 5.pdf PDF
20058 Specifications Part 4.pdf PDF
Sign in Sheet - 20058.pdf PDF
20058 Drawings Pgs 1-14.pdf PDF
20058 Specifications Part 1.pdf PDF
20058 Drawings Pgs 15-31.pdf PDF
20058 Drawings Pgs 57-64.pdf PDF
20058 Specifications Part 2.pdf PDF
Grayling Addendum 1.pdf PDF
20058 Specifications Part 6.pdf PDF
20058 Drawings Pgs 41-50.pdf PDF
Show all 20

On GovTribe

Work with this file

  • Download the original file
  • Contacts named in this file
  • Similar government files
  • Ask GovTribe AI about this file

Text version

6JBK RD

DOWNLIGHTING: One Lithonia Way, Conyers, GA 30012 Phone: 800-315-4935 Fax: 770-860-3129 www.lithonia.com © 2019 Acuity Brands Lighting, Inc. All rights reserved. Rev. 01/14/19

DATE: PRINT DATE: TEST NO:

MANUFACTURER:

LUMINAIRE CATALOG NO.:

LUMINAIRE DESCRIPTION:

LAMP DESCRIPTION:

LUMENS PER LAMP:

[_PRODUCTID]

[_LAMPPOSITION]

[_MOUNTING]

[_TOTALLUMINAIRELUMENS]

[_PHYSICALDIMENSIONS]

[_VLC_SIGNALING_APERTURE]

[_ABSOLUTE]

[_ABSOLUTELUMENS]

[_INPUT_ELECTRICAL]

[_TEMP0]

6/29/2017 November 6, 2017 ISF 35031

Lithonia Lighting

6JBK RD 30K 90CRI

6" Gen 5 Kit Round Baffle 3000K Bridgelux LEDs

LED

840.4214

954f2f8c-c161-4183-b5cd-4b011bd06449

0 , 0

RECESSED DOWNLIGHT

840.4

0.5, 0.5, 0

0, 0, 0

NOTE: DATA SHOWN IS ABSOLUTE FOR THE SAMPLE PROVIDED.

841.1

120.0 VOLTS, 10.9 WATTS, 0.0912 AMPS

AMBIENT: 25.0

0° 20°

40°

60°

80°

Ave Lumens

Zone Lumens % Lamp

0° - 30°

0° - 40°

0° - 60°

0° - 90°

90° - 120°

90° - 130°

90° - 150°

90° - 180°

0° - 180°

285.5

462.2

756.0

840.4

0.0

0.0

0.0

0.0

840.4

34.0

55.0

90.0

100.0

0.0

0.0

0.0

0.0

*100.0

*Efficiency

Coefficients of Utilization pf 20% pc 80% 70% 50% pw 50% 30% 10% 50% 30% 10% 50% 30% 10%

R C

R

50% beam -

63.3°

10% beam -

104.8°

Mounting

Height

Inital FC

Center

Beam Diameter FC Diameter FC

8.0

10.0

12.0

14.0

16.0

12.2

6.6

4.1

2.8

2.0

6.8

9.2

11.7

14.2

16.6

6.1

3.3

2.1

1.4

1.0

14.3

19.5

24.7

29.9

35.0

1.2

0.7

0.4

0.3

0.2

Spacing to Mounting Height:1.2

6JBK RD OneUP™ Direct-Wire LED

PHOTOMETRICS

6JBK RD 30K, 3000 K LEDs, input watts: 10.9, delivered lumens: 841.1, LM/W=77.16, test no. ISF 35031

Distribution Curve Distribution Data Output Data Coefficient of Utilization Illuminance Data at 30” Above Floor for a Single Luminaire

ENERGY DATA

LIGHTING FACTS

COMPATIBLE DIMMERS

Lutron Leviton Pass & Seymour Synergy/Leviton Sensorswitch DV-603P-LA 6633-PA HCL453PTCCCV6 ISD 600 I 120 / IPI06 nSP5 PCD 2W CT-603PR-WH 6615-P LS 603 PWV ISD 1000 I 120 / IPI10 nSP5 PCD ELV 120

DVELV-300P ISD 400 ELV 120 / IPE04

300P SELV

DV-600P

NTELV-300P

NLV-600

Caseta PD-6WCL dimmer (requires Lutron Smart Bridge L-BDG2-WH which is sold separately from the dimmer)

DIMMER COMPATIBILITY

6" ROUND ENERGY DATA

Color Temperature 2700K 3000K 4000K 5000K

Lumens 820 850 870 880

CRI 90

Lumens/Watt 75.23 77.98 79.82 80.73

Min. starting temperature -18°C (-0°F)

EMI/RFI FCC Title 47 CFR, Part 15, Class B

Sound rating Class A Standards

Input voltage 120V AC

Min. power factor 0.9

Input frequency 50/60HZ

Rated wattage 10.9W

Input power 10.9W

Input current 0.09A

RENOVATE ARMORY BUILDING 3

GRAYLING, MICHIGAN

File No. 511/20058.CAK DMVA No. 26B1520017

LUMINAIRE PRODUCT DATA

26 57 00 - 41 http://www.lithonia.com

EMERGENCY LHQM-LED

Catalog Number

Notes

Type

FEATURES & SPECIFICATIONS

INTENDED USE — Suitable for applications requiring both exit sign and unit equipment. Attractive, 8" tall, streamlined design is great for above-the-door applications and other tight fits. Optional high-output version with remote lamps are ideal for emergency egress lighting. Certain airborne contaminants can diminish integrity of acrylic and/or polycarbonate. Click here for Acrylic- Polycarbonate Compatibility table for suitable uses.

CONSTRUCTION — Engineering-grade thermoplastic housing is impact-resistant, scratch-resistant and corrosion-proof. UL94V-O flame rating. UV-stable resin resists discoloration from natural and man-made light sources.

Rugged unibody housing snaps together with no additional fasteners. Faceplate and back cover are inter-changeable on housing. Positive snap-fit tabs hold faceplate securely, yet are easily removable for lamp compartment access. Universal, directional chevron inserts are easily removed and reinserted.

Uniform graphics illumination without shadows or hot spots. Letters are 6" high with 3/4" stroke, with 100 ft.

viewing distance rating based upon UL924 standard.

LEDs mounted on primary circuit boards for sign illumination. Low-energy LED lamp in sign operates in normal (AC input) and emergency (DC input) modes.

Low-profile, integrated test switch/pilot light. Easily viewed bright red status indicator.

Unique track-and-swivel arrangement permits full range of direction of lamp head adjustment. Universal J-box mounting pattern. Tool-less access for maintenance. Conduit entry position on top of unit.

U.S. Patent No. 6,848,798; 6,499,866; 6,142,648; 5,797,673; D379,373; 5,526,251; D484,272;

D473,672; 5,611,163; 5,646,502.

OPTICS — Twin LED lamp heads operate in emergency (DC input) mode with 12 series-parallel white LEDs in each head. Provides redundant light sources to ensure emergency lighting performance. The typical life of the exit LED lamp is 10 years.

ELECTRICAL — Dual-voltage input capability (120/277V). Edge connector on printed circuit board ensures long-term durability.

Current-limiting charger maximizes battery life and minimizes energy consumption. Provides low operating costs.

Short-circuit protection — current-limiting charger circuitry protects printed circuit board from shorts.

Thermal compensation adjusts charger output to provide optimum charge voltage relative to ambient temperature.

Regulated charge voltage maintains constant-charge voltage over a wide range of line voltages. Prevents over/ undercharging that shortens battery life and reduces capacity.

Filtered charger input minimizes charge voltage ripple and extends battery life.

AC/LVD reset allows battery connection before AC power is applied and prevents battery damage from deep discharge.

Single multi-color LED indicator to display two-state charging, test activation and three-state diagnostic test.

Test switch provides manual activation of 30-second diagnostic testing for on-demand visual inspection.

Self-diagnostic testing for 30 seconds every 30 days, 30 minutes at 180-day interval, and 90 minutes annually.

Diagnostic evaluation of LED light source, AC-to-DC transfer, charging and battery condition.

Battery: Sealed, maintenance-free nickel-cadmium battery delivers 90-minute capacity to emergency lamps. Two-state contstant-current charge maximizes battery life and automatically recharges after battery discharge. Low-voltage disconnect prevents excessively deep discharge that can permanently damage the bat-tery. Optional high-output battery to power both local and optional LED remote lamp heads simultaneously.

INSTALLATION — Universal mounting canopy for top or end mount. Back mount standard for single face only.

Housing snaps to canopy with positive-locking tabs. Cam locking pin secures housing to canopy.

Easily removed mounting knockouts. Conduit entry knockout for 1/2" flexible conduit. J-box pattern on back panel.

LISTINGS — UL damp location listed standard 50°-104°F (10°-40°C). Meets UL 924, NFPA 101 (current Life Safety Code), NEC and OSHA illumination standards. Meets all applicable FCC Title 47, Part 15, Subpart B requirements.

WARRANTY — 5-year limited warranty. (Battery is prorated). Complete warranty terms located at:

www.acuitybrands.com/support/warranty/terms-and-conditions Note: Actual performance may differ as a result of end-user environment and application.

All values are design or typical values, measured under laboratory conditions at 25 °C.

Specifications subject to change without notice.

Thermoplastic Exits

LHQM LED

LED Lamp Head

Nickel-Cadmium Battery

LHQM LED

Family Lamp type Housing color Letter color Options

LHQM Stencil face, single face plate with extra face plate

LED Two 1.5W/9.6V white LED

(blank) White B Black

R Red G Green

HO High-output Ni-cad 1

HO R0 High-output option, less lamp heads SD Self-diagnostics

NOM Meets Mexican standards 2

NOM SALIDA Salida signage (non-UL) 3

USPOM Assembled in the US

ORDERING INFORMATION Lead times will vary depending on options selected. Consult with your sales representative. Example: LHQM LED G

HO R0

Looking for Contractor Select readily available configurations? Click here to visit Contractor Select™ spec sheet or go to www.contractorselect.com

† Exit Signs Certified in the CA Title 20 Appliance Efficiency Database.

Notes 1 When operating ELMRW T, ELMRE T or ERE SQ T remotes off of HO battery, temperature range of LHQM LED is limited to 68°-104°F (20°-40°C).

2 Available in black or white. Consult factory for options.

3 Only available in white. NOM standard.

4 Only compatible with self-diagnostic option. (ex: HO SD) 5 Only compatible with HO or HO R0 with SD option. See spec sheet

ELA-Q-LED.

6 Only available with HO or HO R0 option. Not available with SD option. See spec sheet ELMRW or ELMRE for more information and other color options. See page 2 for product images. When operat-ing ELMRW T or ELMRE T remotes off of HO battery, temperature range of LHQM LED is limited to 68°-104°F (20°-40°C).

7 See spec sheet ELA-WG.

8 See spec sheet ELA-Stemkits.

9 See spec sheet ERE. When operating ERE SQ T remotes off of HO battery, temperature range of LHQM LED is limited to 68°-104°F (20°-40°C).

10 Not available with SD. Only compatible with HO or HO R0 option.

When operating ERE SQ T remotes off of HO battery, temperature range of LHQM LED is limited to 68°-104°F (20°-40°C).

X

RENOVATE ARMORY BUILDING 3

GRAYLING, MICHIGAN

26 57 00 - 42 http://www.acuitybrandslighting.com/library/ll/documents/specsheets/acrylic-polycarbonate-compatibility.pdf http://www.acuitybrandslighting.com/library/ll/documents/specsheets/acrylic-polycarbonate-compatibility.pdf http://www.acuitybrands.com/support/warranty/terms-and-conditions https://www.acuitybrands.com/products/detail/999379/lithonia-lighting/contractor-select-lhqm-led/quantumr-led-exit-unit-combo https://img.acuitybrands.com/public-assets/catalog/110819/ela-q-led.pdf?abl_version=05%2f28%2f2019+06:02:26&DOC_Type=SPEC_SHEET https://img.acuitybrands.com/public-assets/catalog/1022747/elmrw.pdf?abl_version=05%2f18%2f2021+20:04:31&DOC_Type=SPEC_SHEET https://img.acuitybrands.com/public-assets/catalog/804139/elmre.pdf?abl_version=05%2f18%2f2021+20:04:32&DOC_Type=SPEC_SHEET https://img.acuitybrands.com/public-assets/catalog/47579/ela-wg.pdf https://img.acuitybrands.com/public-assets/catalog/47579/ela-stemkits.pdf https://lithonia.acuitybrands.com/products/detail/832782/Lithonia-Lighting/ERE-Emergency-Remote-Light-Head/Lithonia-Lighting-LED-Emergency-Remote-Light-Head

LHQM-LED

EMERGENCY: One Lithonia Way Conyers, GA 30012 Phone: 800-705-SERV (7378) www.lithonia.com techsupport-emergency@acuitybrands.com © 2012-2021 Acuity Brands Lighting, Inc. All rights reserved. Rev. 07/13/21

LHQM LED QUANTUM® Exit/Unit Combo

ELMRE LP220L SGL ELMRE SP640L SGLELMRE LP220L T

ELMRW LP220L DDBTXD SGL ELMRW LP220L DDBTXD T ELMRW SP640L DDBTXD SGL

Accessories: Order as separate catalog number.

ELA SD Q L0309 Single, LED indoor remote head, white, self-diagnostics, 9.6V 4,5

ELA T SD Q L0309 Twin, LED indoor remote head, white, self-diagnostics, 9.6V 4,5

ELA SD QWP L0309 Single, LED weather-proof remote head, gray, self-diagnostics, 9.6V 4,5

ELA T SD QWP L0309 Twin, LED weather-proof remote head, gray, self-diagnostics, 9.6V 4,5

ELA B SD QWP L0309 Single, LED weather-proof remote head, black, self-diagnostics, 9.6V 4,5

ELA B T SD QWP L0309 Twin, LED weather-proof remote head, black, self-diagnostics, 9.6V 4,5

ELMRW LP220L DWHXD SGL Single LED Wet Location remote head, white, 1.2W, 110 lumens 6

ELMRE LP220L SGL Single LED Indoor remote head, white, 1.2W, 110 lumens 6

ELMRW LP220L DWHXD T Twin LED Wet Location remote head, white, 1.2W, 220 lumens 6

ELMRE LP220L T Twin LED Indoor remote head, white, 1.2W, 110 lumens 6

ELA WG3 Wireguard, 30” W x 13-1/2” H x 6” D 7

ELA LQMUS12 12” white stem kit 8

ERE W SGL SQ M12 Single, LED indoor remote head, square, ivory white, .75W, 3.6V-12V voltage sensing9,10

ERE W T SQ M12 Twin, LED indoor remote head, square, ivory white, 1.5W, 3.6V-12V voltage sensing 9,10

ERE GY SGL WP SQ M12 Single, LED weather-proof remote head, square, gray, 1W, 3.6V-12V voltage sensing 9,10

ERE GY T WP SQ M12 Twin, LED weather-proof remote head, square, gray, 2W, 3.6V-12V voltage sensing 9,10

Indoor/Wet location ELMRE and ELMRW remotes

Remotes Compatability Matrix

LHQM LED Catalog Non-SD Indoor Non-SD Outdoor SD Indoor SD Outdoor

SINGLE TWIN SINGLE TWIN SINGLE TWIN SINGLE TWIN

LHQM LED HO ELMRE LP220L SGL* ELMRE LP220L T* ELMRW LP220L SGL* ELMRW LP220L T* X X X X

LHQM LED HO R0 ELMRE LP220L SGL* ELMRE LP220L T* ELMRW LP220L SGL* ELMRW LP220L T* X X X X LHQM LED HO SD X X X X ELA SD Q L0309 ELA T SD Q L0309 ELA SD QWP L0309 ELA T SD QWP L0309

LHQM LED HO R0 SD X X X X ELA SD Q L0309 ELA T SD Q L0309 ELA SD QWP L0309 ELA T SD QWP L0309

*Available in alternate colors. See spec sheet for more information. When operating twin configurations (ELMRW/ELMRE/ERE SQ) the temperature range of the LHQM LED HO is limited to 68°-104°F (20° - 40°C).

RENOVATE ARMORY BUILDING 3

GRAYLING, MICHIGAN

26 57 00 - 43 https://www.acuitybrands.com/products/detail/888213/lithonia-lighting/elmre-emergency-remote-light-head/quantumr-led-adjustable-emergency-remote-light-head https://www.acuitybrands.com/products/detail/888213/lithonia-lighting/elmre-emergency-remote-light-head/quantumr-led-adjustable-emergency-remote-light-head https://www.acuitybrands.com/products/detail/888213/lithonia-lighting/elmre-emergency-remote-light-head/quantumr-led-adjustable-emergency-remote-light-head https://www.acuitybrands.com/products/detail/1022747/lithonia-lighting/elmrw-emergency-remote-light-head/quantumr-led-adjustable-emergency-wet-location-remote-light-head https://www.acuitybrands.com/products/detail/1022747/lithonia-lighting/elmrw-emergency-remote-light-head/quantumr-led-adjustable-emergency-wet-location-remote-light-head https://www.acuitybrands.com/products/detail/1022747/lithonia-lighting/elmrw-emergency-remote-light-head/quantumr-led-adjustable-emergency-wet-location-remote-light-head

LHQM LED QUANTUM® Exit/Unit Combo

LHQM-LED

EMERGENCY: One Lithonia Way Conyers, GA 30012 Phone: 800-705-SERV (7378) www.lithonia.com techsupport-emergency@acuitybrands.com © 2012-2021 Acuity Brands Lighting, Inc. All rights reserved. Rev. 07/13/21

EXTENDED RUN-TIME FOR HIGH-OUTPUT EXITS

Product Run time LHQM LED HO (no remotes) 3.8 hours LHQM LED HO R0 (no remotes) 7.5 hours

LAMP PHOTOMETRICS

QUANTUM LED SERIES – SINGLE COVERAGE

3W Total White LEDs Using a single unit at a typical 7.5’ mounting height delivers an average illuminance of 1.0 FC over a distance of 24’ on a 3’ path of egress and 18’ on a 6’ path of egress.

24'

3'

1 FC average

18'

1 FC average

6'

1 FC average

25'

3' 6'

20'

1 FC average

Example of single LHQM LED exit illuminating a 3' path of egress

Example of single LHQM LED exit illuminating a 6' path of egress

Example of multiple LHQM LED exits illuminating a 3' path of egress

Example of multiple LHQM LED exits illuminating a 6' path of egress

QUANTUM LED SERIES – MULTIPLE COVERAGE

3W Total White LEDs Using multiple units at a typical 7.5’ mounting height delivers 25’ center-to-center spacing on a 3’ path of egress and 20’ center-to-center spacing on a 6’ path of egress.

MOUNTING

All dimensions are inches (centimeters).

Shipping weight: 3.6 lbs. (1.6 kgs.).

Top End

19-1/4 (48.9)

(30.5)

(20.3)

Test switch/ pilot light

4-3/4 (11.1)

(22.9)

2-1/4 (5.7)

5-5/8 (14.3)

1/2” flexible conduit entry knockout

(15.2)

(30.5)

(10.2)

(20.3)

Universal knockout pattern for various standard j-boxes

Backplate

Face

SPECIFICATIONS

1 Based on continuous operation.

2 At 77°F (25°C).

3 All life safety equipment, including emergency lighting path of egress, must be maintained, serviced and tested in accordance with all National Fire Protection Association and local codes. Failure to perform the required maintenance, service or testing could jeopardize the safety of occupants and will void all warranties.

4 Optimum ambient temperature range where unit will provide capacity for 90 minutes. Higher and lower temperatures affect life and capacity.

5. Battery life is negatively impacted by many variables including temperature, charging rates, number of cycles and deep discharges due to long periods of time without AC power.

Electrical Primary Circuit

Typical LED life1

Supply voltage

Max amps

Max watts

Red and green LED 10 years 120 .05 4.3 277 .03 4.3

Ni-Cad

Voltage Typical Shelf life2

Typical life2 Maintenance3 Temperature range4

9.6 3 years 7-9 years none 50-104°F (10-40°C)

BATTERY

Remote Output Capacity

Standard unit Combo Combo/high-output battery(HO) Combo/high-output (HO) and no heads (RO)

NA NA 3W 6W

RENOVATE ARMORY BUILDING 3

GRAYLING, MICHIGAN

26 57 00 - 44

RENOVATE ARMORY BUILDING 3 File No. 511/20058.CAK

GRAYLING, MICHIGAN DMVA No. 26B1520017

VOICE AND DATA COMMUNICATION SYSTEM 27 05 00 - 1

SECTION 27 05 00 – VOICE AND DATA COMMUNICATION SYSTEM

PART 1 - GENERAL

1.1 SUMMARY

1.2 SUBMITTALS

1.3 SUBMITTALS

1.4 SYSTEM OVERVIEW

1.5 QUALITY ASSURANCE

PART 2 - PRODUCTS

2.1 CONDUIT, OUTLET BOXES, AND COVER

2.2 TWISTED PAIR CABLE

2.3 CONNECTORS

2.4 FACEPLATES

2.5 CABLE AND FACEPLATE IDENTIFICATION

2.6 RACK, INTERCONNECT TRAY, AND PATCH PANELS:

2.7 PUNCH-DOWN BLOCKS

PART 3 - EXECUTION

3.1 INSTALLATION

3.2 CABLE IDENTIFICATION

3.3 TESTING REPAIR/REPLACEMENT

3.4 AS-BUILT DOCUMENTATION

PART 1 - GENERAL

1.1 SUMMARY

A. Provide premise wiring for voice, data, and Net distribution, three (3) CAT 6 cables to each outlet.

1.2 SUBMITTALS

A. Product data for each product indicated/specified.

1. Cables.

2. Arrestors.

3. Connector blocks.

4. Terminal blocks

5. Uninterrupted Power Source units.

6. Racks.

7. Patch panels.

8. Fiber Switch and Modules.

9. Punch-down Blocks.

B. Field Test Report.

VOICE AND DATA COMMUNICATION SYSTEM 27 05 00 - 2

1.3 SUBMITTALS

A. Product data for each type of product specified.

B. Test data and as-built drawings. Test Data is due to DMVA design department before substantial completion is reached. All data jacks and cable connections systems shall be certified Category 6E.

1.4 SYSTEM OVERVIEW

A. This section specifies the requirements for wire, cable, connections devices, installation, and testing for wiring systems to be used as signal pathways for voice and high-speed data transmission. Voice and data operate over the same distribution system.

1.5 QUALITY ASSURANCE

A. All cable shall be installed and terminated to meet 100-Base T standards as defied by EIA- TIA-568 standards.

B. The contractor shall be responsible for most efficient routing of the cable in conduit. The cable route must avoid any electrical equipment, such as fluorescent lighting, transformers, etc. that could induce noise on the cable.

C. Codes and Standards

1. IEEE Compliance – Comply with Std 241, “IEEE Recommended Practice for Electric Power Systems in Commercial Buildings” pertaining to communication systems.

2. EIA Compliance – Comply with EIA Standards RS-453, 455, and 464 pertaining to installation of telephone systems.

3. ANSI/ICEA S-80-576 (1988) Communication Wire and Cable for Wiring Premises.

4. NFPA National Electrical Code.

5. REA 345-52 Service Entrance and Station Protector Installations (PC-5A).

6. REA 345-78 Carbon Arrestor Assemblies for Use in Protectors.

7. ANSI/TIA/EIA – 568-B.2-1 Transmission Performance Specifications for 4-Pair 100 ohm Category 6 Cabling.

PART 2 - PRODUCTS

2.1 CONDUIT, OUTLET BOXES, AND COVER

A. Provide boxes and conduit in accordance with Sections GENERAL ELECTRICAL

REQUIREMENTS.

1. Mount boxes flush in finish walls to match height of 120-volt receptacles, unless indicated otherwise.

VOICE AND DATA COMMUNICATION SYSTEM 27 05 00 - 3

2.2 TWISTED PAIR CABLE

A. All of the voice and data locations shall be wired with unshielded twisted pair (UTP) cable that is category 6E rated and has a total of four (4) pair of copper conductors. Each voice and data connector (2 total) at each outlet shall have separate cables. All of the category 6E rated cables shall be plenum rated.

B. Voice and Data Cable Jacket Color: Cable jacket color shall be factory applied and continuous along the entire length of the cable. Colors as follows:

1. Jacket color for the voice and data cable shall be blue in color.

C. The wiring code of the cable will follow the ANSI/TIA/EIT-T568B (AT&T), option B standards:

Pair 1 Blue/White Pin 4 White/Blue Pin 5 Pair 2 White/Orange Pin 1 Orange/White Pin 2 Pair 3 White/Green Pin 3 Green/White Pin 6 Pair 4 White/Brown Pin 7 Brown/White Pin 8

2.3 CONNECTORS

A. All category 6 UTP cabling (Wall Jacks) shall be terminated into snap-in 110 type CAT 6 RJ-45 connectors and meet TIA/EIA-568-B2.1, Cabling Transmission Performance Specification for 4-pair 100 ohm Category 6 Cabling. Products from Hubbell are preferred, PJ-45 Model HXJ 6 OR-orange, HXJ 6W-white. Two data jacks will be provided at each customer interface point (voice/data outlet).

1. Each voice and data jack shall be orange in color.

2.4 FACEPLATES

A. Faceplates shall be high impact 94V-0 rated thermoplastic of the appropriate type. Each faceplate shall fit a single-gang box opening and hold two jacks in a vertical orientation.

The jack layout and size of the faceplate shall be as follows:

1. Faceplate size: single-gang box opening.

a. Jack orientation: Two jacks in vertical alignment.

B. The Voice and Data faceplate color shall match the electrical device plate color. If the electrical device plate is metallic, then the voice and data faceplate shall be ivory in color.

VOICE AND DATA COMMUNICATION SYSTEM 27 05 00 - 4

2.5 CABLE AND FACEPLATE IDENTIFICATION

A. The finished installation shall have labeling provided at each end of each cable with a permanent wrap around tag that is 6” from the end of the cable. This label should not be discarded during the installation process.

B. All faceplates shall have each jack location identified with a permanent label that is neatly applied on the face of the outlet. This label will include the category of use, and the cable number (EX. To-001); coordinate labeling with DMVA telecommunications mechanic.

2.6 RACK, INTERCONNECT TRAY, AND PATCH PANELS:

A. All data and voice terminations shall be in patch panels.

B. PATCH PANEL: Basis-of-Design: Hubbell P6E48U patch panels. Provide the quantity of patch panels in the Communications Room #108 to meet requirements of the project (from wall jack count) plus 25% future ports. Patch panel shall have the following specifications.

1. Front access

2. Category 6E

3. T568B 48 port

4. 110 punch-down on rear of panels

C. Alarm conduit and wire is analog and terminates on 110 Blocks.

2.7 PUNCH-DOWN BLOCKS

A. PUNCH-DOWN BLOCKS: Basis-of-Design: Hellermann Tyton 48-Pair 110 Punch-down blocks #T110WBL48.

1. Wall-mounted 110 style punch-down blocks.

2. Certified for use on Cat-6 & Cat-6a wiring systems.

3. Electric ivory in color.

4. Meets or exceeds TIA/EIA-586-B.2-1 Category 6 Standard.

5. Integral stand-off legs.

6. ETL tested and approved for Category 6 component compliance.

PART 3 - EXECUTION

3.1 INSTALLATION

A. All customer interface (voice/data outlet) boxes shall be 4” x 4” boxes with a 2-gang plaster ring.

VOICE AND DATA COMMUNICATION SYSTEM 27 05 00 - 5

B. Install cabling concealed in ceiling and walls. Where cabling is routed through exposed construction, provide minimum 1 ¼” conduit for routing cable through the area. Cabling to be parallel and perpendicular to surfaces and follow surface contours. Secure and support cables by straps, staples, or similar fittings so designed and installed to avoid damage to cable. Secure cables at intervals not exceeding 30 inches and not more than 6 inches from cabinets, boxes, or fitting. All overhead hanging cabling, above ceiling, shall be supported by bridle rings or run in cable tray.

C. Install cabling using techniques, practices, and methods that are consistent with categories and RG type rating at components and that ensure category 6 and RG type performance of completed and linked signal path, end to end.

D. Install cables without damaging conductor’s shields or jackets. A minimum cable installation bending radius shall be observed. Minimum bend radius is defined as a radius of curvature no less than 4 times the outside diameter of the cable.

E. The contractor shall be responsible for the most efficient routing of the cable in conduit.

The cable route must avoid any electrical equipment, such as fluorescent lighting, transformers, etc. that could induct noise on the cable.

F. Each wall jack location shall have a single, continuous four (4) pair cable pulled to it from the source location. No splices between the patch panel and the wall jack will be accepted.

A minimum of 12-inches of excess cable will be left after termination, coiled neatly inside the 4” x 4” wall box, and the minimum bend radius for the coil will be observed. A service loop of no less than six feet of excess cable will be neatly coiled above the equipment rack while ensuring that minimum bend radius is observed.

G. 100% of the category 6E (UTP) cabling will be installed and tested in accordance with TIA/EIA-568-B2.1 Clause 11, Cabling Transmission Performance and Test Requirements.

The contractor shall use an electronic testing device to test each cable for the following:

(Submit printed output from this test device to DMVA for review.)

1. Attenuation

2. Impedance

3. Capacity

4. Resistance

5. Length

6. dB loss

7. Pin Assignments

8. Continuity

9. Polarity

10. Near end cross talk

H. Scan and test each cable using industry standard equipment for items 1 – 10 above. The results shall be produced in electronic and original documentation copies and provided to the DOIM/DMVA Network Engineer in MS Excel format.

I. Data for each measurement shall be documented. Data for submittals shall be printed in a summary report that is formatted similar to Table 10.1 in BICSI TDM, or transferred from the instrument to the computer, saved as text files, and printed and submitted.

VOICE AND DATA COMMUNICATION SYSTEM 27 05 00 - 6

J. Remove and replace cabling where test results indicate that they do not comply with specified requirements.

K. Retest and inspect cabling to determine compliance of replaced or additional work with specified requirements.

3.2 CABLE IDENTIFICATION

A. Common Areas & Office Marking Standard:

1. The connection boxes placed on walls or in the bases of cubical furniture shall be labeled clockwise from the main entrance door A, B, C, around the outside wall, then to interior walls and cubical connections until all interfaces are designated.

2. A two-letter system can be used in rooms where more than 26 interfaces exist, AA, AB, AC, etc.

3. Each jack position on the interface will be numbered 1, 2, 3, etc., from right to left, top to bottom on that jack below the connector with a label. The label will include the room number, interface designation, and port number. One the second line of the same label or separated with a ‘/’ the patch panel designation as defined below.

4. A standard labeling and marking system will be used to label each end of the IDF connections with permanent markings to identify the source or destination of the connection.

3.3 TESTING REPAIR/REPLACEMENT

A. Any cable that fails any one of the tests in the engineer’s opinion must be repaired or replaced at the contractor’s expense, and re-tested.

3.4 AS-BUILT DOCUMENTATION

A. Prior to final acceptance of this project, an as-built print with an electronic version shall be submitted to the DMVA showing:

1. Cable inventory

2. Final testing results of the entire voice cable plant and electronics.

3. Voice/Data drop jack numbers shown next to each 4” x 4” drop box in plain view.

4. The results shall be produced in electronic and original documentation copies and provided to the DMVA in MS Excel format.

END OF SECTION 27 05 00

FIRE ALARM 28 31 00 - 1

SECTION 28 31 00 - FIRE ALARM

GENERAL

1.1 RELATED DOCUMENTS

1.2 SUMMARY

1.3 DEFINITIONS

1.4 SYSTEM DESCRIPTION

1.5 PERFORMANCE REQUIREMENTS

1.6 SUBMITTALS

1.7 QUALITY ASSURANCE

1.8 PROJECT CONDITIONS

1.9 SEQUENCING AND SCHEDULING

1.10 EXTRA MATERIALS

PRODUCTS

2.1 MANUFACTURERS

2.2 FACP

2.3 MANUAL FIRE ALARM BOXES

2.4 SYSTEM SMOKE DETECTORS

2.5 NOTIFICATION APPLIANCES

2.6 REMOTE STATUS AND ALARM INDICATORS

2.7 REMOTE ANNUNCIATOR

2.8 ADDRESSABLE INTERFACE DEVICE

2.9 ADDRESSABLE CONTROL MODULE

2.10 DIGITAL ALARM COMMUNICATOR TRANSMITTER

2.11 GUARDS FOR PHYSICAL PROTECTION

2.12 WIRE AND CABLE

EXECUTION

3.1 EQUIPMENT INSTALLATION

3.2 WIRING INSTALLATION

3.3 IDENTIFICATION

3.4 GROUNDING

3.5 FIELD QUALITY CONTROL

3.6 PROGRAMMING

3.7 ADJUSTING

3.8 WARRANTY

3.9 DEMONSTRATION

GENERAL

1.1 RELATED DOCUMENTS

A. Drawings and general provisions of the Contract, including General and Supplementary Conditions and Division 1 Specification Sections, apply to this Section.

B. Related Sections include the following:

1. Division 26 Section “Electrical General Requirements.”

FIRE ALARM 28 31 00 - 2

1.2 SUMMARY

A. This Section includes design and installation of a new fire alarm system.

B. Related Sections include the following:

1. Division 8 Section "Door Hardware" for door closers and holders with associated smoke detectors, electric door locks, and release devices that interface with the fire alarm system.

1.3 DEFINITIONS

A. FACP: Fire alarm control panel.

B. LED: Light-emitting diode.

C. NICET: National Institute for Certification in Engineering Technologies.

D. Definitions in NFPA 72 apply to fire alarm terms used in this Section.

1.4 SYSTEM DESCRIPTION

A. Noncoded, analog-addressable system; automatic sensitivity control of certain smoke detectors; and multiplexed signal transmission dedicated to fire alarm service only.

B. Fire alarm system shall consist of the following:

1. All new fire alarm control panel, devices, and wiring.

2. System smoke detection above all control panels and notification appliance power supply panels.

3. System smoke detection as required at air handling units, smoke rated transfer openings, and smoke damper locations.

4. All flow and tamper switches to monitor fire sprinkler and standpipe systems and report appropriate alarm and supervisory signals.

5. Manual fire alarm boxes at each building exit (prior to entering exit stairwells at each floor).

6. Audible and visual notification appliances in all public and common areas of the building.

7. Emergency Generator Monitoring

1.5 PERFORMANCE REQUIREMENTS

A. Comply with NFPA 72.

B. Comply with NFPA 70.

C. Comply with NFPA 720.

FIRE ALARM 28 31 00 - 3

D. A complete functional system meeting the requirements of this specification, including alarm initiating devices and notification appliances at locations and ratings to meet the requirements of the Authorities Having Jurisdiction and all applicable codes shall be provided.

E. Coordinate and avoid conflicts with casework, markerboards, feature walls, and other areas where fire alarm devices would interfere with furnishings, finishes, etc.

F. Fire alarm system vendor shall provide sound pressure level calculations demonstrating compliance with NFPA 72 and establish quantities and tap settings of audible devices.

G. No additional charges for work or equipment required for a code compliant system approved by the Authority Having Jurisdiction will be allowed.

H. Obtain and refer to mechanical drawings for smoke damper locations, smoke rated transfer openings, and air handling equipment CFM’s. Provide smoke detection as required by applicable codes.

I. Premises protection includes Assembly type A - 3, Business type B, and Storage type S -1 building use group.

1. Refer to drawings for complete code analysis including construction type, use groups, special occupancy types, rated walls, smoke barriers and partitions, etc.

J. System functional performance shall be as indicated on the fire alarm matrix on the drawings.

1.6 SUBMITTALS

A. Product Data: For each type of product indicated.

B. Shop Drawings:

1. Shop Drawings shall be prepared by persons with the following qualifications:

a. Trained and certified by manufacturer in fire alarm system design.

b. Fire alarm certified by NICET, minimum Level III.

2. System Operation Description: Detailed description for this Project, including method of operation and supervision of each type of circuit and sequence of operations for manually and automatically initiated system inputs and outputs.

Manufacturer's standard descriptions for generic systems are not acceptable.

3. Device Address List: Include address descriptions that will appear on the FACP display.

4. System riser diagram with device addresses, conduit sizes, and cable and wire types and sizes.

5. Wiring Diagrams: Power, signal, and control wiring. Include diagrams for equipment and for system with all terminals and interconnections identified. Show wiring color code.

FIRE ALARM 28 31 00 - 4

6. Batteries: Provide battery sizing calculations. Battery size shall be a minimum of 125% of the calculated requirement.

7. Duct Smoke Detectors: Performance parameters and installation details for each detector, verifying that each detector is listed for the complete range of air velocity, temperature, and humidity possible when air-handling system is operating.

8. Floor Plans: Indicate final outlet locations showing address of each addressable device. Show device layout, size and route of cable and conduits.

C. Qualification Data: For Installer.

D. Field quality-control test reports.

E. Operation and Maintenance Data: For fire alarm system to include in emergency, operation, and maintenance manuals. Comply with NFPA 72, Appendix A, recommendations for Owner's manual. Include abbreviated operating instructions for mounting at the FACP.

F. Submittals to Authorities Having Jurisdiction: In addition to distribution requirements for submittals specified in Division 1 Section "Submittals," make an identical submittal to authorities having jurisdiction. To facilitate review, include copies of annotated Contract Drawings as needed to depict component locations. Resubmit if required to make clarifications or revisions to obtain approval. On receipt of comments from authorities having jurisdiction, submit them to Architect for review.

G. Documentation:

1. Approval and Acceptance: Provide the "Record of Completion" form according to NFPA 72 to Owner, Architect, and Authorities Having Jurisdiction.

2. Record of Completion Documents: Provide the "Permanent Records" according to NFPA 72 to Owner, Architect, and authorities having jurisdiction. Format of the written sequence of operation shall be the optional input/output matrix.

a. Hard copies on paper to Owner, Architect, and Authorities Having Jurisdiction.

b. Electronic media may be provided to Architect.

1.7 QUALITY ASSURANCE

A. Installer Qualifications: Personnel shall be trained and certified by manufacturer for installation of units required for this Project.

B. Installer Qualifications: Personnel certified by NICET as Fire Alarm Level III.

C. Electrical Components, Devices, and Accessories: Listed and labeled as defined in NFPA 70, Article 100, by a testing agency acceptable to authorities having jurisdiction, and marked for intended use.

FIRE ALARM 28 31 00 - 5

1.8 PROJECT CONDITIONS

A. Interruption of Existing Fire Alarm Service: Do not interrupt fire alarm service to facilities occupied by Owner or others unless permitted under the following conditions and then only after arranging to provide temporary guard service according to requirements indicated:

1. Notify Architect, Construction Manager and Owner no fewer than seven days in advance of proposed interruption of fire alarm service.

2. Do not proceed with interruption of fire alarm service without Architect, Construction Manager and Owner written permission.

1.9 SEQUENCING AND SCHEDULING

A. Existing Fire Alarm Equipment: Maintain fully operational until new equipment has been tested and accepted. As new equipment is installed, label it "NOT IN SERVICE" until it is accepted. Remove labels from new equipment when put into service and label existing fire alarm equipment "NOT IN SERVICE" until removed from the building.

B. Equipment Removal: After acceptance of the new fire alarm system, remove existing disconnected fire alarm equipment.

1.10 EXTRA MATERIALS

A. Furnish extra materials described below that match products installed and that are packaged with protective covering for storage and identified with labels describing contents.

1. Lamps for Strobe Units: Quantity equal to 10 percent of amount installed, but not less than 1 unit.

2. Smoke, Fire, and Flame Detectors: Quantity equal to 10 percent of amount of each type installed, but not less than 1 unit of each type.

3. Detector Bases: Quantity equal to 2 percent of amount of each type installed, but not less than 1 unit of each type.

4. Keys and Tools: One extra set for access to locked and tamperproofed components.

5. Audible and Visual Notification Appliances: One of each type installed.

6. Fuses: Two of each type installed in the system.

PRODUCTS

2.1 MANUFACTURERS

A. Manufacturers: Subject to compliance with requirements, provide products by one of the following:

1. FACP and Equipment:

FIRE ALARM 28 31 00 - 6

a. Edwards Systems Technology Inc.

b. SimplexGrinnell LP; a Tyco International Company.

c. National Time & Signal.

2.2 FACP

A. General Description:

1. Modular, power-limited design with electronic modules, UL 864, 9th edition, listed.

2. Addressable initiation devices that communicate device identity and status.

a. Smoke sensors shall additionally communicate sensitivity setting and allow for adjustment of sensitivity at the FACP.

b. Temperature sensors shall additionally test for and communicate the sensitivity range of the device.

3. Addressable control circuits for operation of mechanical equipment.

4. Mounting: Surface.

B. Alphanumeric Display and System Controls: Arranged for interface between human operator at the FACP and addressable system components including annunciation and supervision. Display alarm, supervisory, and component status messages and the programming and control menu.

1. Annunciator and Display: Liquid-crystal type, 80 characters, minimum.

2. Keypad: Arranged to permit entry and execution of programming, display, and control commands; and to indicate control commands to be entered into the system for control of smoke-detector sensitivity and other parameters.

C. Circuits:

1. Signaling Line Circuits between control panels: NFPA 72, Class A, Style 7

2. Signaling Line Circuits from control panel to devices: NFPA 72, Class B, Style 4.

a. System Layout: Install no more than 50 addressable devices on each signaling line circuit.

3. Notification-Appliance Circuits: NFPA 72, Class B, Style Y.

4. Actuation of alarm notification appliances shall occur within 10 seconds after the activation of an initiating device.

5. Electrical monitoring for the integrity of wiring external to the FACP for mechanical equipment shutdown and magnetic door-holding circuits is not required, provided a break in the circuit will cause doors to close and mechanical equipment to shut down.

D. Smoke-Alarm Verification:

1. Initiate audible and visible indication of an "alarm verification" signal at the FACP.

2. Activate a listed and approved "alarm verification" sequence at the FACP and the detector.

FIRE ALARM 28 31 00 - 7

3. Record events by the system printer.

4. Sound general alarm if the alarm is verified.

5. Cancel FACP indication and system reset if the alarm is not verified.

E. Notification-Appliance Circuit: Operation shall sound in a temporal pattern, complying with ANSI S3.41.

F. Power Supply for Supervision Equipment: Supply for audible and visual equipment for supervision of the ac power shall be from a dedicated dc power supply, and power for the dc component shall be from the ac supply.

G. Alarm Silencing, Trouble, and Supervisory Alarm Reset: Manual reset at the FACP and remote annunciators, after initiating devices are restored to normal.

1. Silencing-switch operation halts alarm operation of notification appliances and activates an "alarm silence" light. Display of identity of the alarm zone or device is retained.

2. Subsequent alarm signals from other devices or zones reactivate notification appliances until silencing switch is operated again.

3. When alarm-initiating devices return to normal and system reset switch is operated, notification appliances operate again until alarm silence switch is reset.

H. Walk Test: A test mode to allow one person to test alarm and supervisory features of initiating devices. Enabling of this mode shall require the entry of a password. The FACP and annunciators shall display a test indication while the test is underway. If testing ceases while in walk-test mode, after a preset delay, the system shall automatically return to normal.

I. Remote Smoke-Detector Sensitivity Adjustment: Controls shall select specific addressable smoke detectors for adjustment, display their current status and sensitivity settings, and control of changes in those settings. Allow controls to be used to program repetitive, time-scheduled, and automated changes in sensitivity of specific detector groups. Record sensitivity adjustments and sensitivity-adjustment schedule changes in system memory, and make a print-out of the final adjusted values on the system printer.

J. Transmission to Remote Alarm Receiving Station: Automatically transmit alarm, trouble, and supervisory signals to a remote alarm station through a digital alarm communicator transmitter and telephone lines.

K. Primary Power: 24-V dc obtained from 120-V ac service and a power-supply module.

Initiating devices, notification appliances, signaling lines, trouble signal, supervisory and digital alarm communicator transmitter shall be powered by the 24-V dc source.

1. The alarm current draw of the entire fire alarm system shall not exceed 80 percent of the power-supply module rating.

2. Power supply shall have a dedicated fused safety switch for this connection at the service entrance equipment. Paint the switch box red and identify it with "FIRE

ALARM SYSTEM POWER."

L. Secondary Power: 24-V dc supply system with batteries and automatic battery charger and an automatic transfer switch.

FIRE ALARM 28 31 00 - 8

1. Battery and Charger Capacity: Comply with NFPA 72.

M. Surge Protection:

1. Install surge protectors recommended by FACP manufacturer. Install on all system wiring external to the building housing the FACP.

N. Instructions: Computer printout or typewritten instruction card mounted behind a plastic or glass cover in a stainless-steel or aluminum frame. Include interpretation and describe appropriate response for displays and signals. Briefly describe the functional operation of the system under normal, alarm, and trouble conditions.

2.3 MANUAL FIRE ALARM BOXES

A. Description: UL 38 listed; finished in red with molded, raised-letter operating instructions in contrasting color. Station shall show visible indication of operation. Mounted on recessed outlet box; if indicated as surface mounted, provide manufacturer's surface back box.

1. Single-action mechanism, pull-lever type. With integral addressable module, arranged to communicate manual-station status (normal, alarm, or trouble) to the

FACP.

2. Station Reset: Key- or wrench-operated switch.

2.4 SYSTEM SMOKE DETECTORS

A. General Description:

1. UL 268 listed, operating at 24-V dc, nominal.

2. Integral Addressable Module: Arranged to communicate detector status (normal, alarm, or trouble) to the FACP.

3. Plug-in Arrangement: Detector and associated electronic components shall be mounted in a plug-in module that connects to a fixed base. Provide terminals in the fixed base for connection of building wiring.

4. Self-Restoring: Detectors do not require resetting or readjustment after actuation to restore them to normal operation.

5. Integral Visual-Indicating Light: LED type. Indicating detector has operated and power-on status.

6. Remote Control: Unless otherwise indicated, detectors shall be analog-addressable type, individually monitored at the FACP for calibration, sensitivity, and alarm condition, and individually adjustable for sensitivity from the FACP.

a. Rate-of-rise temperature characteristic shall be selectable at the FACP for 15 or 20 deg F per minute.

b. Fixed-temperature sensing shall be independent of rate-of-rise sensing and shall be settable at the FACP to operate at 135 or 155 deg F.

c. Provide multiple levels of detection sensitivity for each sensor.

B. Photoelectric Smoke Detectors:

FIRE ALARM 28 31 00 - 9

1. Sensor: LED or infrared light source with matching silicon-cell receiver.

2. Detector Sensitivity: Between 2.5 and 3.5 percent/foot smoke obscuration when tested according to UL 268A.

C. Duct Smoke Detectors:

1. Photoelectric Smoke Detectors:

a. Sensor: LED or infrared light source with matching silicon-cell receiver.

b. Detector Sensitivity: Between 2.5 and 3.5 percent/foot smoke obscuration when tested according to UL 268A.

2. UL 268A listed, operating at 24-V dc, nominal.

3. Integral Addressable Module: Arranged to communicate detector status (normal, alarm, or trouble) to the FACP.

4. Plug-in Arrangement: Detector and associated electronic components shall be mounted in a plug-in module that connects to a fixed base. The fixed base shall be designed for mounting directly to the air duct. Provide terminals in the fixed base for connection to building wiring.

a. Weatherproof Duct Housing Enclosure: UL listed for use with the supplied detector. The enclosure shall comply with NEMA 250 requirements for Type 4X.

5. Self-Restoring: Detectors shall not require resetting or readjustment after actuation to restore them to normal operation.

6. Integral Visual-Indicating Light: LED type. Indicating detector has operated and power-on status. Provide remote status and alarm indicator and test station where required.

7. Remote Control: Unless otherwise indicated, detectors shall be analog-addressable type, individually monitored at the FACP for calibration, sensitivity, and alarm condition, and individually adjustable for sensitivity from the FACP.

8. Each sensor shall have multiple levels of detection sensitivity.

9. Sampling Tubes: Design and dimensions as recommended by manufacturer for the specific duct size, air velocity, and installation conditions where applied.

10. Relay Fan Shutdown: Provide two (2) sets of contacts rated to interrupt fan motor-control circuit.

2.5 NOTIFICATION APPLIANCES

A. Description: Equipped for mounting as indicated and with screw terminals for system connections.

1. Combination Devices: Factory-integrated audible and visible devices in a single-mounting assembly.

2. Finishes:

a. Wall mounted appliances: Provide red finish with white lettering.

b. Ceiling Mounted Appliances: Provide white finish.

FIRE ALARM 28 31 00 - 10

B. Horns: Electric-vibrating-polarized type, 24-V dc; with provision for housing the operating mechanism behind a grille. Horns shall produce a sound-pressure level of 90 dBA, measured 10 feet from the horn.

C. Visible Alarm Devices: Xenon strobe lights listed under UL 1971, with clear or nominal white polycarbonate lens mounted on an aluminum faceplate. The word "FIRE" is engraved in minimum 1-inch- high letters on the lens.

1. Rated Light Output: 15, 30, 60, 75, 110, 135, 185 candela as required to meet NFPA 72 requirements.

2. Strobe Leads: Factory connected to screw terminals.

2.6 REMOTE STATUS AND ALARM INDICATORS

A. Remote status and alarm indicator and test stations, with LED indicating lights. Light is connected to flash when the associated device is in an alarm or trouble mode. Lamp is flush mounted in a single-gang wall plate. A red, laminated, phenolic-resin identification plate at the indicating light identifies, in engraved white letters, device initiating the signal and room where the smoke detector or valve is located. For water-flow switches, the identification plate also designates protected spaces downstream from the water-flow switch.

2.7 REMOTE ANNUNCIATOR

A. Description: Duplicate annunciator functions of the FACP for alarm, supervisory, and trouble indications. Also duplicate manual switching functions of the FACP, including acknowledging, silencing, resetting, and testing.

1. Mounting: Flush cabinet, NEMA 250, Class 1.

B. Display Type and Functional Performance: Alphanumeric display same as the FACP.

Controls with associated LEDs permit acknowledging, silencing, resetting, and testing functions for alarm, supervisory, and trouble signals identical to those in the FACP.

2.8 ADDRESSABLE INTERFACE DEVICE

A. Description: Microelectronic monitor module listed for use in providing a system address for listed alarm-initiating devices for wired applications with normally open contacts.

2.9 ADDRESSABLE CONTROL MODULE

A. Provide for integration of auxiliary control functions into the analog signaling circuit.

Intelligent analog signaling circuit control module shall have the following capabilities:

1. Communication interaction with the analog signaling circuit having the capability of initiating a control function to an auxiliary device based on a specified event.

2. Provide NO/NC contact pairs rated at 2 amps 120 VAC or 24 VDC.

FIRE ALARM 28 31 00 - 11

2.10 DIGITAL ALARM COMMUNICATOR TRANSMITTER

A. Listed and labeled according to UL 632.

B. Functional Performance: Unit receives an alarm, supervisory, or trouble signal from the FACP, and automatically captures one or two telephone lines and dials a preset number for a remote central station. When contact is made with the central station(s), the signal is transmitted. The unit supervises up to two telephone lines. Where supervising 2 lines, if service on either line is interrupted for longer than 45 seconds, the unit initiates a local trouble signal and transmits a signal indicating loss of telephone line to the remote alarm receiving station over the remaining line. When telephone service is restored, unit automatically reports that event to the central station. If service is lost on both telephone lines, the local trouble signal is initiated.

C. Secondary Power: Integral rechargeable battery and automatic charger. Battery capacity is adequate to comply with NFPA 72 requirements.

D. Self-Test: Conducted automatically every 24 hours with report transmitted to central station.

2.11 GUARDS FOR PHYSICAL PROTECTION

A. Description: Welded wire mesh of size and shape for the manual station, smoke detector, gong, or other device requiring protection.

1. Factory fabricated and furnished by manufacturer of the device.

2. Finish: Paint of color to match the protected device.

2.12 WIRE AND CABLE

A. Wire and cable for fire alarm systems shall be UL listed and labeled as complying with NFPA 70, Article 760.

B. Fire alarm wire and cable shall be as specified by the system manufacturer including conductor gage, conductor quantity, conductor twists and shielding…