This document package includes construction drawings and specifications for a federal construction project. The Jefferson Barracks VAMC is seeking a general contractor to renovate the first floor of Building 24 to provide approximately 12,000 square feet of training and administrative support space for the EHRM program. The project scope includes demolition, fire protection system work, and construction in accordance with the drawings and specifications. The solicitation number is 36C77622B0052 and the project number is 657-21-703JB. The construction work must meet all applicable VA and NFPA standards.
View the file
Other files
Show all 41
On GovTribe
Work with this file
- Download the original file
- Contacts named in this file
- Similar government files
- Ask GovTribe AI about this file
Text version
SPRINKLER ZONING
LEVEL 0
12"12"
12"12"
PLAN VIEW
2'x4' TILE
2'x2' TILE
SPRINKLERS SHALL BE POSITIONED AS
SHOWN WITH A 3" TOLERANCE.
HOWEVER, SHOULD ANY PART OF THE
TOLERANCE BE USED, THEN ALL
THE SPRINKLERS IN THE ROW SHALL BE
OFFSET BY THE SAME
DISTANCE IN THE SAME DIRECTION.
SPRINKLERS SHALL BE POSITIONED AS
SHOWN AND WITH A MINIMUM
1'-0" CLEARANCE FROM THE PRIVACY
CURTAIN CEILING TRACK.
D
A
OR WOOD TRUSS
OPEN WEB STEEL
C
CEILING
3'-0" TO LESS THAN 3'-6" 9-1/2"
2'-6" TO LESS THAN 3'-0" 7-1/2"
2'-0" TO LESS THAN 2'-6" 5-1/2"
1'-6" TO LESS THAN 2'-0" 3-1/2"
1' TO LESS THAN 1'-6" 2-1/2"
LESS THAN 1' 0
6'-0" TO LESS THAN 6'-6" 24"
5'-6" TO LESS THAN 6'-0" 20"
3'-6" TO LESS THAN 4'-0" 12"
OBSTRUCTION
B
A
CEILING
5'-0" TO LESS THAN 5'-6" 18"
4'-0" TO LESS THAN 4'-6" 14"
4'-6" TO LESS THAN 5'-0" 16 1/2"
6'-6" TO LESS THAN 7'-0" 30"
7'-0" TO LESS THAN 7'-6" 35"
(A) POSITIONING OF SPRINKLERS
TO AVOID OBSTRUCTION TO
DISCHARGE (SSU/SSP)
OBSTRUCTION
A
B
CEILING
(B) A>(D-8 in)+B
WHERE D< 30"
D
DISTANCE FROM SPRINKLERS TO
SIDE OF OBSTRUCTION (A)
MAXIMUM ALLOWABLE DISTANCE OF DEFLECTOR
ABOVE BOTTOM OF OBSTRUCTION (IN) (B)
ELEVATION VIEW
ELEVATION VIEW
ELEVATION VIEW
POSITIONING OF SPRINKLERS TO AVOID OBSTRUCTION TO DISCHARGE
(SSU/SSP).
A>3C OR 3D
A> 24 INCHES
USE DIMENSION C OR D,
WHICHEVER IS GREATER
EXISTING
SPRINKLER
FIRST
FLOOR/SECOND
FLOOR
EXISTING
SPRINKLER
BASEMENT
EXISTING TO
REMAIN
SPRINKLER
ATTIC
SPRINKLER ZONING
LEVEL 3
SYM POSITION FINISH TEMP K NPT SIN MFG. MODEL#
PENDENT WHITE 155 5.60 1/2" TY323* *TYCO* TY-FRB
UPRIGHT BRASS 155 5.60 1/2" TY313* *TYCO* TY-FRB
*OR EQUIVALENT *
SEMI-RECESSED
EXISTING HEADS
ORDINARY GROUP 1
HAZARD
.15 GPM / 1500 SQ. FT
250 GPM HOSE
WET SYSTEM
LIGHT HAZARD
.10 GPM / 1500 SQ. FT
100 GPM HOSE
WET SYSTEM
SPRINKLER HAZARD
LEGEND
ORDINARY GROUP 2
HAZARD
.20 GPM / 1500 SQ. FT
250 GPM HOSE
WET SYSTEM
EXISTING ATTIC DRY
SYSTEM
.10 GPM / 1500 SQ. FT
100 GPM HOSE
DRY SYSTEM
Address:
City: State: Zip/Postal Code:
Contract #: Date:
Job:
Contractor: Designer:
Address:
City: State: Zip/Postal Code:
Phone: Fax: Email:
Approving Authority:
Design Defaults Default Sprig Size:
Default Sprig Material:
Default Sprig Elevation:
Default Drop Size:
Default Drop Material:
Default Drop Elevation:
Standards:
Job Name
NFPA13
15'
8'
SPRINKLER ZONING
LEVEL 0
SPRINKLER ZONING
LEVEL 1
SPRINKLER ZONING
LEVEL 2
SPRINKLER HEAD
FLEXIBLE ARM-OVER
CEILING
TILE
T-BAR BRACKET "B"
ICTAULIC
FIRELOCK
4"
IC
TAU
LIC
FIR
ELO
C
K 4"
IC
TAU
LIC
FIR
ELO
C
K 4"
A. FIELD VERIFICATION IS REQUIRED OF EXISTING SPRINKLER ZONES. ZONES
WILL BE REQUIRED TO MATCH ALARM ZONES / SMOKE ZONES.
B. ALL EXISTING EQUIPMENT TO REMAIN AS IS EXCEPT IN NEW WORK AREAS.
C. REFERENCE SHEET GI002 FOR WALL TYPES AND FIRE/SMOKE WALL
RATINGS.
D. BUILDING IS FED BY AN 4" AND 3" UNDERGROUND.
E. ATTIC HAS AN EXISTING DRY SYSTEM TO REMAIN
F. 2nd FLOOR TO BE FED FROM EXISTING 3" FEEDING EXISTING STAGE AREA
G. DESIGN BASED ON LIGHT/ORDINARY HAZARD OCCUPANCY PER PROJECT
SPECIFICATIONS.
H. MATERIALS, FABRICATION AND INSTALLATION SHALL BE IN ACCORDANCE
WITH PROJECT SPECIFICATIONS.
I. COORDINATION WITH OTHER TRADE SHALL BE DONE.
J. LIGHTING AND STORAGE OBSTRUCTIONS SHALL BE A MINIMUM OF 18"
BELOWDEFLECTOR.
K. PROVIDE AIR VENT ON WET PIPE SYSTEMS
L. REFERENCE GC SHEETS FOR PHASING
FIRE PROTECTION SYMBOL LEGEND
HORN STROBE
SYSTEM RISER
FIRE DEPT CONNECTION
LEGEND
SPRINKLER HEAD POSITION
SPRINKLER HEADS LEGEND
HYDRANT FLOW / HYDRANT SITE MAP
HYD #30 STATIC PRESSURE: 110 PSI
HYD #32 RESIDUAL PRESSURE: 100 PSI
FLOW GPM: 1490.48 GPM
TEST LOCATION: HYDRANT 32 AND 30 FOR SITE ON
9-13-2016
HYDRANT TEST REPORT SUPPLY BY VA 02-01-22
10% SAFETY FACTOR REQUIRE PER VA
FLOW TEST WITH 1 YEAR WILL BE REQUIRED
MAXIMUM DISTANCE BETWEEN HANGERS
1" 1-1/4" 1-1/2" 2"NOMINAL PIPE
STEEL PIPE
THREADED LIGHTWALL
STEEL PIPE EXCEPT
THREADED LIGHTWALL 12-0
12-0
12-0
12-0
15-0
12-0 12-0
15-0
4"
N/A
15-0
2-1/2"
15-0
N/A
3"
15-0
N/A
HANGER DETAIL
FIRE SPRINKLER AND FIRE ALARM
ZONES
EXISTING ZONE 1-1 - NORTH - 10,553
EXISTING ZONE 1-2 - SOUTH -
EXISTING ZONE 1-3 - ATTIC -
APPROXIMATE 9025(SHOWN)
FIRE PROTECTION DESIGN INFORMATION
SYSTEM RISER
12364 W. ALAMEDA PKWY.
SUITE #135
LAKEWOOD CO 80228
(303) 985-2050
WWW.VERITASFIRE.COM
OBSTRUCTION DETAILS
MINIMUM SPRINKLER WATER SUPPLY REQUIREMENTS
1500 SQ.FT. x .20 GPM/SQ.FT + PRESS BAL = 320 GPM
INSIDE AND OUTSIDE HOSE STREAM = 250 GPM
TOTAL WATER DEMAND = 570 GPM
HYDRAULIC CALCULATIONS SHALL BE BASED ON A
CURRENT FIRE HYDRANT FLOW TEST. REMOTE AREA
REDUCTION IS ALLOWED PER VA GUIDELINES
00KEYNOTES
GENERAL NOTES
Drawing Title
VA FORM 08 - 6231
F
CONSULTANTS:
750 W HAMPDEN AVE
SUITE 300
ENGLEWOOD, CO 80110
(720) 550-6307 WWW.VALHALLAENGINEERING.COMDate:Revisions:
10987654321
10987654321
E
D
C
B
A
F
E
D
C
B
A
ARCHITECT/ENGINEERS: STAMP:
Approved: Project Director
Phase Project Title
Location
Issue Date Checked Drawn
Project Number
Drawing Number
Building Number
Number:
VETERANS
HEALTH
ADMINISTRATION
24-F-002
FIRE SUPPRESSION LEGENDS,
NOTES, AND SYMBOLS
EHRM TRAINING AND ADMIN
SPACE SUPPORT
1 JEFFERSON BARRACKS DR ST. LOUIS, MO 63125
07/07/2022 KLM BAEVEG 21.21
SUPPLY DETAIL FOR SEMI RECESSED SPRINKLER HEADS TYPICAL FLEXIBLE ARM OVER DETAIL
FIG. 100 ALL
THREAD ROD
FIG. 200
ADJUSTABLE RING
HANGER
SAMMY VERTICAL
CONCRETE ANCHOR
CST-20
NEW RISER DETAIL
EXISTING UNDERGROUND - RECONFIGURE 2 FEEDS INTO ONE BACKFLOW -
REMOVE EXISTING GATE VALVES
BACKFLOW DOUBLE CHECK WITH GRV - BUTTERFLY VALVES & TAMPER SWITCHES
READY RISER WITH PRV
PRESSURE GAUGE - SUPPLY SIDE
NEW BACK FLOW FORWARD FLOW SYSTEM FLUSHING CONNECTION
BUTTERFLY VALVE WITH TAMPERS (NORMALLY CLOSED) PIPED TO OUTSIDE
TO FIRE DEPARTMENT CONNECTION 4" x 2-1/2" x 2-1/2" CONNECTION
-COORDINATION WITH EXISTING FDC PIPING IN BUILDING
CHECK VALVE FOR FDC - COORDINATE WITH EXISTING LOCATION
TO SPRINKLER SYSTEM WET PIPE SPRINKLER SYSTEMS
SPRINKLER HEAD BOX & HYDRAULIC CALCULATION PLACARDS
PIPE STANDS OR HANGERS TO SUPPORT PIPE
PRESSURE GAUGE - SYSTEM SIDE
DEMOLISH EXISTING PIPING TO
ALLOW INSTALLATION OF NEW
BACKFLOW PREVENTOR SYSTEM
BACK TO WALL FLANGE. PROVIDE
NEW PIPING TO EXISTING SYSTEM.
13 PROVIDE NEW PIPING TO EXISTING DRY PIPE VALVE
FEEDING ATTIC SYSTEM SYSTEM TO REMAIN
FLOOR
EXISTING DRY PIPE VALVE DETAIL
14 FROM WET PIPE SPRINKLER SYSTEM TO DRY SYSTEM
15 EXISTING BUTTERY VALVE - WITH TAMPER SWITCH
16 MAIN DRAIN - TO FLOOR DRAIN - RECONNECT EXISTING
17 EXISTING AIR MAINTENANCE DEVICE TO EXISTING AIR COMPRESSOR
18 EXISTING PS40 PRESSURE SWITCH - (SUPERVISOR)
19 EXISTING PS10 PRESSURE SWITCH - (FLOW)
20 TO EXISTING DRY SYSTEM IN ATTIC
21 EXISTING DRY PIPE VALVE
22 EXISTING AIR COMPRESSOR
3/8" TOP BEAM
C-CLAMP - 4"
AND SMALLER
3/8" ZINC
PLATED ROD -
4" AND
SMALLER
ADJUSTABLE
RING
HANGER
1" CAST IRON 90
DEG. ELL
1" CAST IRON 90 ELL OR
TEE (AS REQUIRED)
SPRINKLER BRANCH LINE
PIPING (SPRINKLER OUTLET
MAY BE TURNED DOWN,
DEPENDING ON SITUATION.)
1" PIPING TO PENDENT
SPRINKLER HEAD
LINE OF
SUSPENDED
CEILING
HARD PIPE OPTION
1" BLACK SCHEDULE
40 NIPPLE
TYPICAL SPRINKLER HEAD
1/2" NUT,
BOLT &
WASHER (2
PLACES)
DECKQUICK END THREADLESS
BRACE FITTING
QUICK END
THREADLESS
BRACE FITTING
BRACE PIPING
QUICK CLAMP SWAY
BRACE ATTACHMENT
JOIST
4-WAY SWAY BRACE
DECK
1/2" NUT, BOLT
& WASHER (2
PLACES)
QUICK END THREADLESS
BRACE FITTING
BRACE PIPING
QUICK CLAMP SWAY
BRACE ATTACHMENT
2-WAY SWAY BRACE
JOIST
SWAY BRACE DETAIL
PARTIAL EXISTING RISER DETAIL
S:
\P
RO
JE
CT
F
OL
DE
R\ Va lha lla
E ng ine er ing \21
.21 E
HR
M
-1
8\D
W G\
FP
\E
HR
M
.21
F P.
dw g_
Br ya n 7/7
/20
7:
:08 A
M
657-21-703JB100% BID DOCS
0 100% BID DOCS 07/07/2022
T
OPKI
A B C D E F G H J L M N Q R S
ORDINARY GROUP 1
HAZARD
.15 GPM / 1500 SQ. FT
250 GPM HOSE
WET SYSTEM
LIGHT HAZARD
.10 GPM / 1500 SQ. FT
100 GPM HOSE
WET SYSTEM
SPRINKLER HAZARD
LEGEND
ORDINARY GROUP 2
HAZARD
.20 GPM / 1500 SQ. FT
250 GPM HOSE
WET SYSTEM
EXISTING ATTIC DRY
SYSTEM
.10 GPM / 1500 SQ. FT
100 GPM HOSE
DRY SYSTEM
G10
G10A
G13 G11
G02A
G03
S002G01
G05
G06
S001
G09
E01
G15
G08
G07
G02
G02B
G12
G03A
G05A
G01A
00KEYNOTES
GENERAL NOTES
Drawing Title
VA FORM 08 - 6231
F
CONSULTANTS:
750 W HAMPDEN AVE
SUITE 300
ENGLEWOOD, CO 80110
(720) 550-6307 WWW.VALHALLAENGINEERING.COMDate:Revisions:
10987654321
10987654321
E
D
C
B
A
F
E
D
C
B
A
ARCHITECT/ENGINEERS: STAMP:
Approved: Project Director
Phase Project Title
Location
Issue Date Checked Drawn
Project Number
Drawing Number
Building Number
Number:
24-FX-110
HAZARD PLAN - FLOOR 00 EHRM TRAINING AND ADMIN
SPACE SUPPORT
1 JEFFERSON BARRACKS DR ST. LOUIS, MO 63125
07/07/2022VEG 21.21
24'12'6'3'1'-6"0'
Plan North
True North
3/16" = 1'-0"
HAZARD PLAN - FLOOR 001
12364 W. ALAMEDA PKWY.
SUITE #135
LAKEWOOD CO 80228
(303) 985-2050
WWW.VERITASFIRE.COM KLM BAE
VETERANS
HEALTH
ADMINISTRATION
S:
\P
RO
JE
CT
F
OL
DE
R\ Va lha lla
E ng ine er ing \21
.21 E
HR
M
-1
8\D
W G\
FP
\E
HR
M
.21
F P.
dw g_
Br ya n 7/7
/20
7:
:09 A
M
657-21-703JB100% BID DOCS
ROOM NUMBER KEY
NUMBER ROOM NAME
G01 CANTEEN DINING AREA
G01A FOOD SERVICE
G01B ELEV LOBBY
G01C EXT VESTIBULE
G01D HOISTWAY
G02A TELECOM
G03 CANTEEN STORE
G03A STORAGE
G04 CANTEEN STORE
G05 FOOD PREP
G05A FOOD PREP
G06 KITCHEN STORAGE
G07 KITCHEN
G08 HAC
G09 FOOD PREP
G10 CANTEEN / STORAGE
G10A STORAGE
G11 OFFICE
G11A OFFICE
G12 TOILET FEMALE
G13 TOILET MALE
G15 MECHANICAL RM
H001 CORRIDOR
S101 STAIR 1
OPKI
A B C D E F G H J L M N Q R S
105107
103A 103
103B
110 112
102A
114B
100S201
107A
107B
104B
S101
G01D
H002
104A
114C
ORDINARY GROUP 1
HAZARD
.15 GPM / 1500 SQ. FT
250 GPM HOSE
WET SYSTEM
LIGHT HAZARD
.10 GPM / 1500 SQ. FT
100 GPM HOSE
WET SYSTEM
SPRINKLER HAZARD
LEGEND
ORDINARY GROUP 2
HAZARD
.20 GPM / 1500 SQ. FT
250 GPM HOSE
WET SYSTEM
EXISTING ATTIC DRY
SYSTEM
.10 GPM / 1500 SQ. FT
100 GPM HOSE
DRY SYSTEM
00KEYNOTES
GENERAL NOTES
Drawing Title
VA FORM 08 - 6231
F
CONSULTANTS:
750 W HAMPDEN AVE
SUITE 300
ENGLEWOOD, CO 80110
(720) 550-6307 WWW.VALHALLAENGINEERING.COMDate:Revisions:
10987654321
10987654321
E
D
C
B
A
F
E
D
C
B
A
ARCHITECT/ENGINEERS: STAMP:
Approved: Project Director
Phase Project Title
Location
Issue Date Checked Drawn
Project Number
Drawing Number
Building Number
Number:
24-FX-111
HAZARD PLAN - FLOOR 01 EHRM TRAINING AND ADMIN
SPACE SUPPORT
1 JEFFERSON BARRACKS DR ST. LOUIS, MO 63125
07/07/2022 KLM BAEVEG 21.21
24'12'6'3'1'-6"0'
Plan North
True North
3/16" = 1'-0"
HAZARD PLAN - FLOOR 011
12364 W. ALAMEDA PKWY.
SUITE #135
LAKEWOOD CO 80228
(303) 985-2050
WWW.VERITASFIRE.COM
VETERANS
HEALTH
ADMINISTRATION
S:
\P
RO
JE
CT
F
OL
DE
R\ Va lha lla
E ng ine er ing \21
.21 E
HR
M
-1
8\D
W G\
FP
\E
HR
M
.21
F P.
dw g_
Br ya n 7/7
/20
7:
:10 A
M
657-21-703JB100% BID DOCS
ROOM NUMBER KEY
NUMBER ROOM NAME
100 VEST
101 ELEV LOBBY
102 LOD OFFICE
102A LOD TRAINING
103 CORRIDOR
103A CORRIDOR
103B CORRIDOR
104 PHOTO STUDIO
104A STORAGE
104B LOD PHOTO
105 CR-1
106 STORAGE
107 CR-2
107A STORAGE
107B STORAGE
108 CR-5
109 CR-4
110 MEN
111 JAN
112 WOMEN
114 CR-3
114B TELECOM
114C OI&T
115 STORAGE
116 OFFICE
117 MECH
B001 BALCONY
H002 CORRIDOR
S201 STAIR 2
OPKI
A B C D E F G H J L M N Q R S
218 X200 S201
STAIR 2
210 208 G01D 205A
218A
216A 201A
S101
STAIR 1
201B
S206
E STAIR
205C
ORDINARY GROUP 1
HAZARD
.15 GPM / 1500 SQ. FT
250 GPM HOSE
WET SYSTEM
LIGHT HAZARD
.10 GPM / 1500 SQ. FT
100 GPM HOSE
WET SYSTEM
SPRINKLER HAZARD
LEGEND
ORDINARY GROUP 2
HAZARD
.20 GPM / 1500 SQ. FT
250 GPM HOSE
WET SYSTEM
EXISTING ATTIC DRY
SYSTEM
.10 GPM / 1500 SQ. FT
100 GPM HOSE
DRY SYSTEM
00KEYNOTES
GENERAL NOTES
Drawing Title
VA FORM 08 - 6231
F
CONSULTANTS:
750 W HAMPDEN AVE
SUITE 300
ENGLEWOOD, CO 80110
(720) 550-6307 WWW.VALHALLAENGINEERING.COMDate:Revisions:
10987654321
10987654321
E
D
C
B
A
F
E
D
C
B
A
ARCHITECT/ENGINEERS: STAMP:
Approved: Project Director
Phase Project Title
Location
Issue Date Checked Drawn
Project Number
Drawing Number
Building Number
Number:
24-FX-112
HAZARD PLAN - FLOOR 02 EHRM TRAINING AND ADMIN
SPACE SUPPORT
1 JEFFERSON BARRACKS DR ST. LOUIS, MO 63125
07/07/2022 KLM BAEVEG 21.21
24'12'6'3'1'-6"0'
Plan North
True North
3/16" = 1'-0"
HAZARD PLAN - FLOOR 021
12364 W. ALAMEDA PKWY.
SUITE #135
LAKEWOOD CO 80228
(303) 985-2050
WWW.VERITASFIRE.COM
VETERANS
HEALTH
ADMINISTRATION
S:
\P
RO
JE
CT
F
OL
DE
R\ Va lha lla
E ng ine er ing \21
.21 E
HR
M
-1
8\D
W G\
FP
\E
HR
M
.21
F P.
dw g_
Br ya n 7/7
/20
7:
:11 A
M
657-21-703JB100% BID DOCS
ROOM NUMBER KEY
NUMBER ROOM NAME
201 OFFICE
201A OFFICE
201B CORRIDOR
204 RESTROOM
205 CLOS
205A TELECOM
205C OI&T
206 STORAGE
207 CORRIDOR
208 ELEV LOBBY
210 CORRIDOR
211 OFFICE
216 STORAGE
216A STORAGE
217 OFFICE
217A OFFICE
218 OFFICE
218A PASSAGE
S206 E STAIR
X200 MECH CHASE
OPKI
A B C D E F G H J L M N Q R S
ATTIC
S101
STAIR 1
ORDINARY GROUP 1
HAZARD
.15 GPM / 1500 SQ. FT
250 GPM HOSE
WET SYSTEM
LIGHT HAZARD
.10 GPM / 1500 SQ. FT
100 GPM HOSE
WET SYSTEM
SPRINKLER HAZARD
LEGEND
ORDINARY GROUP 2
HAZARD
.20 GPM / 1500 SQ. FT
250 GPM HOSE
WET SYSTEM
EXISTING ATTIC DRY
SYSTEM
.10 GPM / 1500 SQ. FT
100 GPM HOSE
DRY SYSTEM
00KEYNOTES
GENERAL NOTES
Drawing Title
VA FORM 08 - 6231
F
CONSULTANTS:
750 W HAMPDEN AVE
SUITE 300
ENGLEWOOD, CO 80110
(720) 550-6307 WWW.VALHALLAENGINEERING.COMDate:Revisions:
10987654321
10987654321
E
D
C
B
A
F
E
D
C
B
A
ARCHITECT/ENGINEERS: STAMP:
Approved: Project Director
Phase Project Title
Location
Issue Date Checked Drawn
Project Number
Drawing Number
Building Number
Number:
VETERANS
HEALTH
ADMINISTRATION
24-FX-113
HAZARD PLAN - FLOOR 03 EHRM TRAINING AND ADMIN
SPACE SUPPORT
1 JEFFERSON BARRACKS DR ST. LOUIS, MO 63125
07/07/2022 KLM BAEVEG 21.21
24'12'6'3'1'-6"0'
Plan North
True North
3/16" = 1'-0"
HAZARD PLAN - FLOOR 031
12364 W. ALAMEDA PKWY.
SUITE #135
LAKEWOOD CO 80228
(303) 985-2050
WWW.VERITASFIRE.COM
1. EXISTING ATTIC TO REMAIN
2. RECONNECT ATTIC DRY SYSTEM TO NEW SPRINKLER RISER
S:
\P
RO
JE
CT
F
OL
DE
R\ Va lha lla
E ng ine er ing \21
.21 E
HR
M
-1
8\D
W G\
FP
\E
HR
M
.21
F P.
dw g_
Br ya n 7/7
/20
7:
:11 A
M
OPKI
A B C D E F G H J L M N Q R S
S101
STAIR 1
G01D
HOISTWAY
G02A
G03A
G01C
G01
G01A
G09
G01B
G07
G06
G05
G05A
G10
G10A
G15
H001
G03
G08
G11
G11A G13
G12
6'-3"
00KEYNOTES
GENERAL NOTES
Drawing Title
VA FORM 08 - 6231
F
CONSULTANTS:
750 W HAMPDEN AVE
SUITE 300
ENGLEWOOD, CO 80110
(720) 550-6307 WWW.VALHALLAENGINEERING.COMDate:Revisions:
10987654321
10987654321
E
D
C
B
A
F
E
D
C
B
A
ARCHITECT/ENGINEERS: STAMP:
Approved: Project Director
Phase Project Title
Location
Issue Date Checked Drawn
Project Number
Drawing Number
Building Number
Number:
24-FX-120
FIRE SUPPRESSION RCP - FLOOR
EHRM TRAINING AND ADMIN
SPACE SUPPORT
1 JEFFERSON BARRACKS DR ST. LOUIS, MO 63125
07/07/2022VEG 21.21
24'12'6'3'1'-6"0'
Plan North
True North
3/16" = 1'-0"
FIRE SUPPRESSION RCP - FLOOR 001
12364 W. ALAMEDA PKWY.
SUITE #135
LAKEWOOD CO 80228
(303) 985-2050
WWW.VERITASFIRE.COM KLM BAE
1. SUPPLY PIPING TO SPRINKLER RISER
2. RE-SPACE SPRINKLERS AS NEEDED FOR NEW OFFICES
3. ENSURE SPRINKLER SPACE IS PER VA GUIDELINES AND PER NFPA 13
4. PROVIDE SPRINKLER HEAD IN SHAFT FOR HYDRAULIC ELEVATOR
5. ADD BACKFLOW TO SPRINKLER SYSTEM
6. EXISTING FIRE DEPARTMENT CONNECTION
7. EXISTING SPRINKLER RISER LOCATION
8. NOT IN CONTRACT
VETERANS
HEALTH
ADMINISTRATION
A. FIELD VERIFICATION IS REQUIRED OF EXISTING SPRINKLER ZONES. ZONES
WILL BE REQUIRED TO MATCH ALARM ZONES / SMOKE ZONES.
B. ALL EXISTING EQUIPMENT TO REMAIN AS IS EXCEPT IN NEW WORK AREAS.
C. REFERENCE SHEET GI002 FOR WALL TYPES AND FIRE/SMOKE WALL
RATINGS.
D. BUILDING IS FED BY AN 4" AND 3" UNDERGROUND.
E. ATTICS HAS AN EXISTING DRY SYSTEM TO REMAIN
F. DESIGN BASED ON LIGHT / ORDINARY HAZARD OCCUPANCY PER PROJECT
SPECIFICATIONS.
G. MATERIALS, FABRICATION AND INSTALLATION SHALL BE IN ACCORDANCE
WITH PROJECT SPECIFICATIONS.
H. COORDINATION WITH OTHER TRADES SHALL BE DONE.
I. LIGHTING AND STORAGE OBSTRUCTIONS SHALL BE A MINIMUM OF 18"
BELOW DEFLECTOR.
J. PROVIDE PROPER SPRINKLER HEAD PROTECTION DURING CONSTRUCTION
TO UNSURE EXISTING SPRINKLER HEADS ARE NOT DAMAGED.
K. REFERENCE GC SHEETS FOR PHASING
S:
\P
RO
JE
CT
F
OL
DE
R\ Va lha lla
E ng ine er ing \21
.21 E
HR
M
-1
8\D
W G\
FP
\E
HR
M
.21
F P.
dw g_
Br ya n 7/7
/20
7:
:12 A
M
657-21-703JB100% BID DOCS
ROOM NUMBER KEY
NUMBER ROOM NAME
G01 CANTEEN DINING AREA
G01A FOOD SERVICE
G01B ELEV LOBBY
G01C EXT VESTIBULE
G01D HOISTWAY
G02A TELECOM
G03 CANTEEN STORE
G03A STORAGE
G04 CANTEEN STORE
G05 FOOD PREP
G05A FOOD PREP
G06 KITCHEN STORAGE
G07 KITCHEN
G08 HAC
G09 FOOD PREP
G10 CANTEEN / STORAGE
G10A STORAGE
G11 OFFICE
G11A OFFICE
G12 TOILET FEMALE
G13 TOILET MALE
G15 MECHANICAL RM
H001 CORRIDOR
S101 STAIR 1
OPKI
A B C D E F G H J L M N Q R S
103A
103B
102A
114B
S201
STAIR 2
107A
107B 104B
S101
STAIR 1
G01D
HOISTWAY
H002
104A
114C
00KEYNOTES
GENERAL NOTES
Drawing Title
VA FORM 08 - 6231
F
CONSULTANTS:
750 W HAMPDEN AVE
SUITE 300
ENGLEWOOD, CO 80110
(720) 550-6307 WWW.VALHALLAENGINEERING.COMDate:Revisions:
10987654321
10987654321
E
D
C
B
A
F
E
D
C
B
A
ARCHITECT/ENGINEERS: STAMP:
Approved: Project Director
Phase Project Title
Location
Issue Date Checked Drawn
Project Number
Drawing Number
Building Number
Number:
24-FX-121
FIRE SUPPRESSION RCP - FLOOR
EHRM TRAINING AND ADMIN
SPACE SUPPORT
1 JEFFERSON BARRACKS DR ST. LOUIS, MO 63125
07/07/2022VEG 21.21
24'12'6'3'1'-6"0'
Plan North
True North
3/16" = 1'-0"
FIRE SUPPRESSION RCP - FLOOR 011
12364 W. ALAMEDA PKWY.
SUITE #135
LAKEWOOD CO 80228
(303) 985-2050
WWW.VERITASFIRE.COM KLM BAE
1. NOT IN CONTRACT
2. DUCT CHASE NO SPRINKLER
3. EXISTING SPRINKLER FEED MAIN
4. SPRINKLER FROM ABOVE
5. ADJUST SPRINKLER HEADS AS NEEDED FOR NEW CEILING
VETERANS
HEALTH
ADMINISTRATION
4 4 4
S:
\P
RO
JE
CT
F
OL
DE
R\ Va lha lla
E ng ine er ing \21
.21 E
HR
M
-1
8\D
W G\
FP
\E
HR
M
.21
F P.
dw g_
Br ya n 7/7
/20
7:
:13 A
M
657-21-703JB100% BID DOCS
A. FIELD VERIFICATION IS REQUIRED OF EXISTING SPRINKLER ZONES. ZONES
WILL BE REQUIRED TO MATCH ALARM ZONES / SMOKE ZONES.
B. ALL EXISTING EQUIPMENT TO REMAIN AS IS EXCEPT IN NEW WORK AREAS.
C. REFERENCE SHEET GI002 FOR WALL TYPES AND FIRE/SMOKE WALL
RATINGS.
D. BUILDING IS FED BY AN 4" AND 3" UNDERGROUND.
E. ATTICS HAS AN EXISTING DRY SYSTEM TO REMAIN
F. DESIGN BASED ON LIGHT / ORDINARY HAZARD OCCUPANCY PER PROJECT
SPECIFICATIONS.
G. MATERIALS, FABRICATION AND INSTALLATION SHALL BE IN ACCORDANCE
WITH PROJECT SPECIFICATIONS.
H. COORDINATION WITH OTHER TRADES SHALL BE DONE.
I. LIGHTING AND STORAGE OBSTRUCTIONS SHALL BE A MINIMUM OF 18"
BELOW DEFLECTOR.
J. PROVIDE PROPER SPRINKLER HEAD PROTECTION DURING CONSTRUCTION
TO UNSURE EXISTING SPRINKLER HEADS ARE NOT DAMAGED.
K. REFERENCE GC SHEETS FOR PHASING
ROOM NUMBER KEY
NUMBER ROOM NAME
100 VEST
101 ELEV LOBBY
102 LOD OFFICE
102A LOD TRAINING
103 CORRIDOR
103A CORRIDOR
103B CORRIDOR
104 PHOTO STUDIO
104A STORAGE
104B LOD PHOTO
105 CR-1
106 STORAGE
107 CR-2
107A STORAGE
107B STORAGE
108 CR-5
109 CR-4
110 MEN
111 JAN
112 WOMEN
114 CR-3
114B TELECOM
114C OI&T
115 STORAGE
116 OFFICE
117 MECH
B001 BALCONY
H002 CORRIDOR
S201 STAIR 2
OPKI
A B C D E F G H J L M N Q R S
218 X200
MECH
CHASE
S201 210 208 G01D
HOISTWAY
205A
218A
216A 201A
S101
STAIR 1
201B
217 206 S206
E STAIR
205C
00KEYNOTES
GENERAL NOTES
Drawing Title
VA FORM 08 - 6231
F
CONSULTANTS:
750 W HAMPDEN AVE
SUITE 300
ENGLEWOOD, CO 80110
(720) 550-6307 WWW.VALHALLAENGINEERING.COMDate:Revisions:
10987654321
10987654321
E
D
C
B
A
F
E
D
C
B
A
ARCHITECT/ENGINEERS: STAMP:
Approved: Project Director
Phase Project Title
Location
Issue Date Checked Drawn
Project Number
Drawing Number
Building Number
Number:
24-FX-122
FIRE SUPPRESSION RCP - FLOOR
EHRM TRAINING AND ADMIN
SPACE SUPPORT
1 JEFFERSON BARRACKS DR ST. LOUIS, MO 63125
07/07/2022VEG 21.21
24'12'6'3'1'-6"0'
Plan North
True North
3/16" = 1'-0"
FIRE SUPPRESSION RCP - FLOOR 021
12364 W. ALAMEDA PKWY.
SUITE #135
LAKEWOOD CO 80228
(303) 985-2050
WWW.VERITASFIRE.COM KLM BAE
1. 3" SPRINKLER FEED FROM BASEMENT LEVEL - USE THIS FEED TO SPRINKLER
ENTIRE 2ND FLOOR
2. WALL NOT FULL HEIGHT
3. ADJUST EXISTING SPRINKLER AS NEEDED TO PROVIDE COVERAGE
4. DUCT CHASE - NO SPRINKLER
5. PROVIDE SPRINKLER HEAD COVERAGE IN STAIR
6. NOT IN CONTRACT
VETERANS
HEALTH
ADMINISTRATION
S:
\P
RO
JE
CT
F
OL
DE
R\ Va lha lla
E ng ine er ing \21
.21 E
HR
M
-1
8\D
W G\
FP
\E
HR
M
.21
F P.
dw g_
Br ya n 7/7
/20
7:
:13 A
M
657-21-703JB100% BID DOCS
A. FIELD VERIFICATION IS REQUIRED OF EXISTING SPRINKLER ZONES. ZONES
WILL BE REQUIRED TO MATCH ALARM ZONES / SMOKE ZONES.
B. ALL EXISTING EQUIPMENT TO REMAIN AS IS EXCEPT IN NEW WORK AREAS.
C. REFERENCE SHEET GI002 FOR WALL TYPES AND FIRE/SMOKE WALL
RATINGS.
D. BUILDING IS FED BY AN 4" AND 3" UNDERGROUND.
E. ATTICS HAS AN EXISTING DRY SYSTEM TO REMAIN
F. DESIGN BASED ON LIGHT / ORDINARY HAZARD OCCUPANCY PER PROJECT
SPECIFICATIONS.
G. MATERIALS, FABRICATION AND INSTALLATION SHALL BE IN ACCORDANCE
WITH PROJECT SPECIFICATIONS.
H. COORDINATION WITH OTHER TRADES SHALL BE DONE.
I. LIGHTING AND STORAGE OBSTRUCTIONS SHALL BE A MINIMUM OF 18"
BELOW DEFLECTOR.
J. PROVIDE PROPER SPRINKLER HEAD PROTECTION DURING CONSTRUCTION
TO UNSURE EXISTING SPRINKLER HEADS ARE NOT DAMAGED.
K. REFERENCE GC SHEETS FOR PHASING
ROOM NUMBER KEY
NUMBER ROOM NAME
201 OFFICE
201A OFFICE
201B CORRIDOR
204 RESTROOM
205 CLOS
205A TELECOM
205C OI&T
206 STORAGE
207 CORRIDOR
208 ELEV LOBBY
210 CORRIDOR
211 OFFICE
216 STORAGE
216A STORAGE
217 OFFICE
217A OFFICE
218 OFFICE
218A PASSAGE
S206 E STAIR
X200 MECH CHASE
OPKI
A B C D E F G H J L M N Q R S
ATTIC
S101
STAIR 1
A. EXISTING ATTIC TO REMAIN. ADJUST SPRINKLER LINES FOR ELEVATOR
SHAFT.
B. RECONNECT ATTIC DRY SYSTEM TO NEW SPRINKLER RISER
C. ATTIC LAYOUT WILL NEED TO BE FIELD VERIFIED
D. PROVIDE ADDITIONAL DRUM DRIPS AND AUX DRAINS AS REQUIRED.
E. PROVIDE PROPER SPRINKLER HEAD PROTECTION DURING CONSTRUCTION
TO UNSURE EXISTING SPRINKLER HEADS ARE NOT DAMAGED.
00KEYNOTES
GENERAL NOTES
Drawing Title
VA FORM 08 - 6231
F
CONSULTANTS:
750 W HAMPDEN AVE
SUITE 300
ENGLEWOOD, CO 80110
(720) 550-6307 WWW.VALHALLAENGINEERING.COMDate:Revisions:
10987654321
10987654321
E
D
C
B
A
F
E
D
C
B
A
ARCHITECT/ENGINEERS: STAMP:
Approved: Project Director
Phase Project Title
Location
Issue Date Checked Drawn
Project Number
Drawing Number
Building Number
Number:
VETERANS
HEALTH
ADMINISTRATION
24-FX-123
FIRE SUPPRESSION RCP - FLOOR
EHRM TRAINING AND ADMIN
SPACE SUPPORT
1 JEFFERSON BARRACKS DR ST. LOUIS, MO 63125
07/07/2022 KLM BAEVEG 21.21
24'12'6'3'1'-6"0'
Plan North
True North
3/16" = 1'-0"
FIRE SUPPRESSION RCP - FLOOR 031
12364 W. ALAMEDA PKWY.
SUITE #135
LAKEWOOD CO 80228
(303) 985-2050
WWW.VERITASFIRE.COM
1. RELOCATE "FLY LOFT / ABOVE STAGE" UPRIGHT SPRINKLER HEADS TO
PENDENT SPRINKLER IN PASSAGE 218A
2. EXISTING PIPE IS PIPE SCHEDULED SYSTEM. EXISTING MAY BE REUSED
PER NFPA 13 CHAPTER 29.
3. PROVIDE SPRINKLER HEAD COVERAGE IN STAIR AND FOR NEW WALL
LAYOUT
4. 3" SPRINKLER FEED FROM BASEMENT LEVEL - USE THIS FEED TO
SPRINKLER ENTIRE 2ND FLOOR
5. REVISE SPRINKLER LINES FOR NEW ELEVATOR SHAFT
S:
\P
RO
JE
CT
F
OL
DE
R\ Va lha lla
E ng ine er ing \21
.21 E
HR
M
-1
8\D
W G\
FP
\E
HR
M
.21
F P.
dw g_
Br ya n 7/7
/20
7:
:14 A
M
OPKI
A B C D E F G H J L M N Q R S
G10
G10A
G13 G11
G02A
G03
S002
STAIRWELL
NO 2
G01
G05
G06
S001
STAIRWELL
NO 1
G09
E01
ELEVATOR
SHAFT
G15
G08
G07
G02
G02B
G12
G03A
G05A
00KEYNOTES
GENERAL NOTES
Drawing Title
VA FORM 08 - 6231
F
CONSULTANTS:
750 W HAMPDEN AVE
SUITE 300
ENGLEWOOD, CO 80110
(720) 550-6307 WWW.VALHALLAENGINEERING.COMDate:Revisions:
10987654321
10987654321
E
D
C
B
A
F
E
D
C
B
A
ARCHITECT/ENGINEERS: STAMP:
Approved: Project Director
Phase Project Title
Location
Issue Date Checked Drawn
Project Number
Drawing Number
Building Number
Number:
VETERANS
HEALTH
ADMINISTRATION
24-FD-120
DEMOLITION RCP - FLOOR 00 EHRM TRAINING AND ADMIN
SPACE SUPPORT
1 JEFFERSON BARRACKS DR ST. LOUIS, MO 63125
07/07/2022 KLM BAEVEG 21.21
24'12'6'3'1'-6"0'
Plan North
True North
3/16" = 1'-0"
DEMOLITION RCP - FLOOR 001
12364 W. ALAMEDA PKWY.
SUITE #135
LAKEWOOD CO 80228
(303) 985-2050
WWW.VERITASFIRE.COM
1. NOT IN SCOPE
2. 3" FEED TO SPRINKLER SYSTEM OVER STAGE
3. SPRINKLER HEADS NEED TO BE RELOCATED DURING CONSTRUCTION
PHASING. SEE PHASING PLANS.
4. SEE FIRE ALARM DEMO SHEET 24-FD-110 FOR FIRE ALARM DEVICES
S:
\P
RO
JE
CT
F
OL
DE
R\ Va lha lla
E ng ine er ing \21
.21 E
HR
M
-1
8\D
W G\
FP
\E
HR
M
.21
F P.
dw g_
Br ya n 7/7
/20
7:
:15 A
M
657-21-703JB
100% BID DOCS
A. FIELD VERIFICATION IS REQUIRED OF EXISTING SPRINKLER ZONES. ZONES
WILL BE REQUIRED TO MATCH ALARM ZONES / SMOKE ZONES.
B. ALL EXISTING EQUIPMENT TO REMAIN AS IS EXCEPT IN NEW WORK AREAS.
C. REFERENCE SHEET GI002 FOR WALL TYPES AND FIRE/SMOKE WALL
RATINGS.
D. BUILDING IS FED BY AN 4" AND 3" UNDERGROUND.
E. ATTICS HAS AN EXISTING DRY SYSTEM TO REMAIN
F. DESIGN BASED ON LIGHT / ORDINARY HAZARD OCCUPANCY PER PROJECT
SPECIFICATIONS.
G. MATERIALS, FABRICATION AND INSTALLATION SHALL BE IN ACCORDANCE
WITH PROJECT SPECIFICATIONS.
H. COORDINATION WITH OTHER TRADES SHALL BE DONE.
I. LIGHTING AND STORAGE OBSTRUCTIONS SHALL BE A MINIMUM OF 18"
BELOW DEFLECTOR.
J. PROVIDE PROPER SPRINKLER HEAD PROTECTION DURING CONSTRUCTION
TO UNSURE EXISTING SPRINKLER HEADS ARE NOT DAMAGED.
K. REFERENCE GC SHEETS FOR PHASING
ROOM NUMBER KEY
NUMBER ROOM NAME
E01 ELEVATOR SHAFT
G01 DINING AREA
G01A FOOD SERVICE
G02 OFFICE
G02A OFFICE
G02B OI&T
G03 CANTEEN STORE
G03A STORAGE
G04 CANTEEN STORE
G05 KITCHEN
G05A FOOD PREP
G06 KITCHEN STORAGE
G06A VACANT
G07 KITCHEN
G08 HAC
G09 DISH WASH
G10 STORAGE
G10A STORAGE
G11 VESTIBULE
G12 TOILET, FEMALE
G13 TOILET, MALE
G15 MECHANICAL RM
S001 STAIRWELL NO 1
S002 STAIRWELL NO 2
OPKI
A B C D E F G H J L M N Q R S
E01
ELEVATOR
SHAFT
107A
107B
104B
104A
114C
114B
S001
STAIRWELL
NO 1
H100
101A 100
101B
101C
114A
105A 103
S003
STAIRWELL
NO 3
110A
102A
102D
00KEYNOTES
GENERAL NOTES
Drawing Title
VA FORM 08 - 6231
F
CONSULTANTS:
750 W HAMPDEN AVE
SUITE 300
ENGLEWOOD, CO 80110
(720) 550-6307 WWW.VALHALLAENGINEERING.COMDate:Revisions:
10987654321
10987654321
E
D
C
B
A
F
E
D
C
B
A
ARCHITECT/ENGINEERS: STAMP:
Approved: Project Director
Phase Project Title
Location
Issue Date Checked Drawn
Project Number
Drawing Number
Building Number
Number:
VETERANS
HEALTH
ADMINISTRATION
24-FD-121
DEMOLITION RCP - FLOOR 01 EHRM TRAINING AND ADMIN
SPACE SUPPORT
1 JEFFERSON BARRACKS DR ST. LOUIS, MO 63125
07/07/2022 KLM BAEVEG 21.21
24'12'6'3'1'-6"0'
Plan North
True North
3/16" = 1'-0"
DEMOLITION RCP - FLOOR 011
12364 W. ALAMEDA PKWY.
SUITE #135
LAKEWOOD CO 80228
(303) 985-2050
WWW.VERITASFIRE.COM
A. FIELD VERIFICATION IS REQUIRED OF EXISTING SPRINKLER ZONES. ZONES
WILL BE REQUIRED TO MATCH ALARM ZONES / SMOKE ZONES.
B. ALL EXISTING EQUIPMENT TO REMAIN AS IS EXCEPT IN NEW WORK AREAS.
C. REFERENCE SHEET GI002 FOR WALL TYPES AND FIRE/SMOKE WALL
RATINGS.
D. BUILDING IS FED BY AN 4" AND 3" UNDERGROUND.
E. ATTICS HAS AN EXISTING DRY SYSTEM TO REMAIN
F. DESIGN BASED ON LIGHT / ORDINARY HAZARD OCCUPANCY PER PROJECT
SPECIFICATIONS.
G. MATERIALS, FABRICATION AND INSTALLATION SHALL BE IN ACCORDANCE
WITH PROJECT SPECIFICATIONS.
H. COORDINATION WITH OTHER TRADE SHALL BE DONE.
I. LIGHTING AND STORAGE OBSTRUCTIONS SHALL BE A MINIMUM OF 18"
BELOW DEFLECTOR.
J. PROVIDE PROPER SPRINKLER HEAD PROTECTION DURING CONSTRUCTION
TO UNSURE EXISTING SPRINKLER HEADS ARE NOT DAMAGED.
K. REFERENCE GC SHEETS FOR PHASING
1. NOT IN SCOPE
2. 3" FEED TO SPRINKLER SYSTEM OVER STAGE
3. EXISTING PIPE IS PIPE SCHEDULED SYSTEM. EXISTING MAY BE REUSED
PER NFPA 13 CHAPTER 29.
4. SEE FIRE ALARM DEMO SHEET 24-FD-111 FOR FIRE ALARM DEVICES
S:
\P
RO
JE
CT
F
OL
DE
R\ Va lha lla
E ng ine er ing \21
.21 E
HR
M
-1
8\D
W G\
FP
\E
HR
M
.21
F P.
dw g_
Br ya n 7/7
/20
7:
:15 A
M
657-21-703JB
100% BID DOCS
ROOM NUMBER KEY
NUMBER ROOM NAME
100 ENTRY
101 AUDITORIUM
101A BREAK RM
101B STORAGE
101C STORAGE
102 TRAINING
102A OFFICE
102D TRAINING
103 CLOSET
104 OFFICE
104A STORAGE
104B STORAGE
105 KITCHEN
105A TOILET
106 STAGE LEFT
107A TOILET, MALE
107B STORAGE
108 STAGE
109 TOILET, FEMALE
110 STAGE RIGHT
110A VESTIBULE
114A PIPE CHASE
114B OFFICE
114C OI&T
115 STORAGE
H100 CORRIDOR
S002 STAIRWELL NO 2
S003 STAIRWELL NO 3
OPKI
A B C D E F G H J L M N Q R S
216A
201A
205C
205A
208210210A
211A
215A
206A
206217
S005
00KEYNOTES
GENERAL NOTES
Drawing Title
VA FORM 08 - 6231
F
CONSULTANTS:
750 W HAMPDEN AVE
SUITE 300
ENGLEWOOD, CO 80110
(720) 550-6307 WWW.VALHALLAENGINEERING.COMDate:Revisions:
10987654321
10987654321
E
D
C
B
A
F
E
D
C
B
A
ARCHITECT/ENGINEERS: STAMP:
Approved: Project Director
Phase Project Title
Location
Issue Date Checked Drawn
Project Number
Drawing Number
Building Number
Number:
VETERANS
HEALTH
ADMINISTRATION
24-FD-122
DEMOLITION RCP - FLOOR 02 EHRM TRAINING AND ADMIN
SPACE SUPPORT
1 JEFFERSON BARRACKS DR ST. LOUIS, MO 63125
07/07/2022 KLM BAEVEG 21.21
24'12'6'3'1'-6"0'
Plan North
True North
3/16" = 1'-0"
DEMOLITION RCP - FLOOR 021
12364 W. ALAMEDA PKWY.
SUITE #135
LAKEWOOD CO 80228
(303) 985-2050
WWW.VERITASFIRE.COM
1. 3" FEED TO SPRINKLER SYSTEM OVER STAGE
2. REUSE EXISTING AUX DRAIN LOCATION IF POSSIBLE
3. SEE FIRE ALARM DEMO SHEET 24-FD-112 FOR FIRE ALARM DEVICES
S:
\P
RO
JE
CT
F
OL
DE
R\ Va lha lla
E ng ine er ing \21
.21 E
HR
M
-1
8\D
W G\
FP
\E
HR
M
.21
F P.
dw g_
Br ya n 7/7
/20
7:
:16 A
M
657-21-703JB
3 33
3 3
100% BID DOCS
A. FIELD VERIFICATION IS REQUIRED OF EXISTING SPRINKLER ZONES. ZONES
WILL BE REQUIRED TO MATCH ALARM ZONES / SMOKE ZONES.
B. ALL EXISTING EQUIPMENT TO REMAIN AS IS EXCEPT IN NEW WORK AREAS.
C. REFERENCE SHEET GI002 FOR WALL TYPES AND FIRE/SMOKE WALL
RATINGS.
D. BUILDING IS FED BY AN 4" AND 3" UNDERGROUND.
E. ATTICS HAS AN EXISTING DRY SYSTEM TO REMAIN
F. DESIGN BASED ON LIGHT / ORDINARY HAZARD OCCUPANCY PER PROJECT
SPECIFICATIONS.
G. MATERIALS, FABRICATION AND INSTALLATION SHALL BE IN ACCORDANCE
WITH PROJECT SPECIFICATIONS.
H. COORDINATION WITH OTHER TRADES SHALL BE DONE.
I. LIGHTING AND STORAGE OBSTRUCTIONS SHALL BE A MINIMUM OF 18"
BELOW DEFLECTOR.
J. PROVIDE PROPER SPRINKLER HEAD PROTECTION DURING CONSTRUCTION
TO UNSURE EXISTING SPRINKLER HEADS ARE NOT DAMAGED.
K. REFERENCE GC SHEETS FOR PHASING
ROOM NUMBER KEY
NUMBER ROOM NAME
201 OFFICE
201A OFFICE
203 HAC
204 TOILET
205 OFFICE
205A OFFICE
205C OI&T
206 STORAGE
206A STORAGE
207 OFFICE
208 WORK RM
210 OFFICE
210A VACANT
211 STORAGE
211A VESTIBULE
212 TOILET
213 STORAGE
214 STORAGE
215 VESTIBULE
215A TOILET
216 STORAGE
216A STORAGE
217 SHARED OFFICE
218 STORAGE
S004 STAIR 4
S005 STAIR 5
OPKI
A B C D E F G H J L M N Q R S
ATTIC
00KEYNOTES
GENERAL NOTES
Drawing Title
VA FORM 08 - 6231
F
CONSULTANTS:
750 W HAMPDEN AVE
SUITE 300
ENGLEWOOD, CO 80110
(720) 550-6307 WWW.VALHALLAENGINEERING.COMDate:Revisions:
10987654321
10987654321
E
D
C
B
A
F
E
D
C
B
A
ARCHITECT/ENGINEERS: STAMP:
Approved: Project Director
Phase Project Title
Location
Issue Date Checked Drawn
Project Number
Drawing Number
Building Number
Number:
VETERANS
HEALTH
ADMINISTRATION
24-FD-123
DEMOLITION RCP - FLOOR 03 EHRM TRAINING AND ADMIN
SPACE SUPPORT
1 JEFFERSON BARRACKS DR ST. LOUIS, MO 63125
07/07/2022 KLM BAEVEG 21.21
24'12'6'3'1'-6"0'
Plan North
True North
3/16" = 1'-0"
DEMOLITION RCP - FLOOR 031
A. EXISTING ATTIC TO REMAIN
B. PROVIDE PROPER SPRINKLER HEAD PROTECTION DURING CONSTRUCTION
TO UNSURE EXISTING SPRINKLER HEADS ARE NOT DAMAGED.
12364 W. ALAMEDA PKWY.
SUITE #135
LAKEWOOD CO 80228
(303) 985-2050
WWW.VERITASFIRE.COM
1. 3" FEED FROM BASEMENT LEVEL TO SPRINKLER SYSTEM OVER "FLY LOFT /
ABOVE STAGE"
2. EXISTING PIPE IS PIPE SCHEDULED SYSTEM. EXISTING MAY BE REUSED
PER NFPA 13 CHAPTER 29.
3. ADJUST SPRINKLER SPRINKLER LAYOUT FOR NEW ELEVATOR AND STAIR
S:
\P
RO
JE
CT
F
OL
DE
R\ Va lha lla
E ng ine er ing \21
.21 E
HR
M
-1
8\D
W G\
FP
\E
HR
M
.21
F P.
dw g_
Br ya n 7/7
/20
7:
:17 A
M
| Sheets and Views |
| 24-F-002 FIRE SUPPRESSION LEGENDS, NOTES, AND SYMBOLS |
| 24-FX-110 HAZARD PLAN - FLOOR 00 |
| 24-FX-111 HAZARD PLAN - FLOOR 01 |
| 24-FX-112 HAZARD PLAN - FLOOR 02 |
| 24-FX-113 HAZARD PLAN - FLOOR 03 |
| 24-FX-120 FIRE SUPPRESSION RCP - FLOOR 00 |
| 24-FX-121 FIRE SUPPRESSION RCP - FLOOR 01 |
| 24-FX-122 FIRE SUPPRESSION RCP - FLOOR 02 |
| 24-FX-123 FIRE SUPPRESSION RCP - FLOOR 03 |
| 24-FD-120 DEMOLITION RCP - FLOOR 00 |
| 24-FD-121 DEMOLITION RCP - FLOOR 01 |
| 24-FD-122 DEMOLITION RCP - FLOOR 02 |
| 24-FD-123 DEMOLITION RCP - FLOOR 03 |