This solicitation seeks a general contractor to renovate the first floor of Building 24 at the Jefferson Barracks VAMC in St. Louis, Missouri to provide training and administrative support space for the EHRM activation project. The scope of work includes demolishing existing structures, preparing the site for construction, and furnishing all labor, materials, equipment and supervision to complete the construction project in accordance with the specifications and drawings. The contractor must furnish testing, labor and materials to fully construct the EHRM Training and Administrative Support Space identified in project number 657-21-703JB. The solicitation was issued by the Department of Veterans Affairs Technology Acquisition Center Austin.
View the file
Other files
Show all 41
On GovTribe
Work with this file
- Download the original file
- Contacts named in this file
- Similar government files
- Ask GovTribe AI about this file
Text version
EXISTING FIRE ALARM CONTROL PANEL
NAC#
F
AUXILIARY POWER SUPPLY
SMOKE DETECTOR
MANUAL PULL STATION
AOM
AIM
HEAT DETECTOR(L=LINEAR HEAT DETECTOR)
MONITOR MODULE
CONTROL RELAY MODULE
STROBE ONLY(WALL MOUNT)
SPEAKER ONLY(WALL MOUNT)
FACP
DOOR HOLDER
EXISTING ANNUNCIATOR PANELANN
VS
WF
TAMPER SWITCH
WATER FLOW SWITCH
SPEAKER/STROBE(WALL MOUNT)
DUCT DETECTOR
KITCHEN HOOD MODULE
CO DETECTOR
15cd
CEILING MOUNT STROBE ONLY
WALL MOUNT STROBE ONLY
WALL MOUNT HORN/STROBE
CEILING MOUNT HORN/STROBE
SB
RTS REMOTE TEST SWITCH
FIRE/SMOKE DAMPER
SMOKE DETECTOR (SOUNDER BASE
WITH LOW FREQUENCY)
SPEAKER/STROBE(CEILING)
SPEAKER ONLY(CEILING)
FATC EXISTING FIRE ALARM TERMINAL CABINET
EX = EXISTING TO REMAIN
ABBREVIATIONS LEGEND
C = CEILING MOUNT
TXT FA/MN SCROLLING TEXT SIGN
PAD EXISTING NAC CIRCUIT EXTENDER / POWER SUPPLY
PS PRESSURE SWITCH
RL = RELOCATE DEVICE
RLN = RELOCATE DEVICE NEW LOCATION
DEMO = REMOVE DEVICE
VAC EXISTING SITE VOICE CONTROL PANEL
NAC #2
EXISTING FACP PANEL
FACP
V (TYP)
To dedicated 20A branch on light and power service. Circuit breaker to be labeled
"Fire Alarm Circuit Control", red in color, with lock installed.
V (TYP)
NAC #2
NAC #1
V (TYP)
NAC #3
NAC #4
V (TYP)
NAC #4
NOT ALL DEVICES SHOWN
NAC#
POWER
SUPPLIES SHALL
BE LOCATED IN
ELECTRICAL OR
TELECOM ROOM
NAC #3
NAC #1
EXISTING ALARM ZONING
DESIGNATIONS TO REMAIN
EXISTING AC
POWER IN
EXISTING
COMMUNICATOR
ALARM ZONING
LEVEL 0
ALARM ZONING
LEVEL 1
ALARM ZONING
LEVEL 2
ALARM ZONING
LEVEL 3
00KEYNOTES
GENERAL NOTES
Drawing Title
VA FORM 08 - 6231
F
CONSULTANTS:
750 W HAMPDEN AVE
SUITE 300
ENGLEWOOD, CO 80110
(720) 550-6307 WWW.VALHALLAENGINEERING.COMDate:Revisions:
10987654321
10987654321
E
D
C
B
A
F
E
D
C
B
A
ARCHITECT/ENGINEERS: STAMP:
Approved: Project Director
Phase Project Title
Location
Issue Date Checked Drawn
Project Number
Drawing Number
Building Number
Number:
VETERANS
HEALTH
ADMINISTRATION
FIRE ALARM LEGENDS, NOTES,
AND SYMBOLS
EHRM TRAINING AND ADMIN
SPACE SUPPORT
1 JEFFERSON BARRACKS DR ST. LOUIS, MO 63125
KLM BAEVEG 21.21
LEGEND
H
ACTUATOR
TOP OF UNIT
FACP NAC#
TOP OF CABINET
ENTIRE LENS OF STROBE
TOP OF DEVICE
CEILING
DIFFUSER
LIGHT
135° F
P
F Min
7'6" (90")
Min 6'8"
(80") 6'0" (72")
5'4" (64")
4'0" (48")
Max 6" below ceiling
Max 8"0"
(96")
ALL HEIGHTS ARE
MEASURED FROM (AFF)
ABOVE FINISHED FLOOR
3'0" (36")
1'6" (18")
TYPICAL DEVICE MOUNTING HEIGHTS
FIRE ALARM ONE-LINE
1. ALL FIRE ALARM EQUIPMENT SHALL BE INSTALLED PER PROJECT
SPECIFICATION 28 31 00 AND THE MANUFACTURER'S INSTRUCTIONS.
2. ALL INITIATING DEVICES SHALL BE FIELD LOCATED BASED UPON THE
LOCATION OF DIFFUSERS, LIGHTS, AND OTHER POTENTIAL
OBSTRUCTIONS.
3. ALL WIRING INSTALLATION SHALL CONFORM TO THE PROJECT
SPECIFICATIONS.
4. IT SHALL BE THE RESPONSIBILITY OF THE CONTRACTOR TO RETURN ALL
WIRES TO THE PANEL FREE OF OPENS, GROUNDS, SHORTS AND/OR ANY
OTHER CONDITION THAT MAY PREVENT THE PROPER OPERATION OF
THE FIRE ALARM SYSTEM.
5. REFERENCE ARCHITECTURAL PLANS TO IDENTIFY ALL SMOKE BARRIERS
AND SMOKE COMPARTMENT ZONES SO THAT PROPER SURVIVABILITY IS
ADDRESSED IN THE DESIGN.
6. THE BIDDING CONTRACTOR SHALL FAMILIARIZE THEMSELVES WITH THE
COMPLEXITIES OF THIS BUILDING. THESE DRAWINGS ARE
DIAGRAMMATIC ONLY. THE AWARDED CONTRACTOR SHALL BE
RESPONSIBLE FOR PRODUCTION OF ALL DESIGN AND SUBMITTAL
DOCUMENTS AND OBTAINING ALL REQUIRED INFORMATION FOR
APPROVALS.
7. PROVIDE REQUIRED MODULES TO ALLOW MAG DOOR LOCKS OR DOORS
WITH STRIKES FOR EGRESS. SEE DATA/ IT OR ELECTRICAL SHEETS
8. SEQUENCE OF OPERATIONS TO REMAIN AS IS
9. FIRE ALARM PANEL TO REMAIN IN CURRENT LOCATION. DEDICATED
ELECTRICAL POWER TO REMAIN. SEE ELECTRICAL SHEETS.
10. NEW EQUIPMENT TO MATCH AND BE COMPATIBLE WITH EXISTING
CAMPUS SYSTEM EQUIPMENT.
11. BEFORE ANY DEMO AND INSTALLATION, SIEMENS NEEDS TO BE
INVOLVED TO REMOVE/ADD ANY DEVICES THAT MAY BE AFFECTED BY
THE CONSTRUCTION
CONTACT SIEMENS
BRUCE W. ERICKSON
FIRE SAFETY AND SECURITY REPRESENTATIVE
SIEMENS INDUSTRY, INC. | SMART INFRASTRUCTURE DIVISION
DIRECT/MOBILE: (314) 575-4810 | BRUCE.ERICKSON@SIEMENS.COM
12364 W. ALAMEDA PKWY.
SUITE #135
LAKEWOOD CO 80228
(303) 985-2050
WWW.VERITASFIRE.COM
24-F-001
PROJECT SHEET NOTES
1. THESE DRAWINGS DEPICT GENERAL LOCATIONS OF LIFE SAFETY EQUIPMENT & FIELD DEVICES.
EXACT ROUTING OF CONDUITS TO BE DETERMINED IN THE FIELD BY THE INSTALLING CONTRACTOR TO SUIT CONDITIONS. ALL CHANGES SHALL BE CLEARLY INDICATED ON THE RECORD DRAWINGS.
2. CONTRACTOR IS RESPONSIBLE FOR MAKING AND OBTAINING APPROVAL FOR ALL NECESSARY
ADJUSTMENTS IN CIRCUITING AS REQUIRED TO ACCOMMODATE THE RELOCATION OF EQUIPMENT
AND/OR DEVICES WHICH ARE AFFECTED BY ANY AUTHORIZED CHANGE. ALL CHANGES SHALL BE
CLEARLY INDICATED ON THE RECORD DRAWINGS.
3. A STAMPED SET OF APPROVED FIRE ALARM DRAWINGS SHALL BE AT THE JOB SITE AND SHALL BE
USED FOR INSTALLATION.
4. THE POWER CIRCUIT TO THE FACP AND TO THE FIRE ALARM POWER SUPPLIES SHALL BE ON A DEDICATED 120V, 20A BRANCH CIRCUIT BREAKER, AND SHALL HAVE A RED MARKING, LOCK-ON PROVISION AND SHALL BE IDENTIFIED AS "LIFE SAFETY BRANCH CIRCUIT." THE LOCATION OF THE CIRCUIT DISCONNECT MEANS (CIRCUIT BREAKER) SHALL BE PERMANENTLY IDENTIFIED AT THE FIRE
ALARM CONTROL UNIT.
5. DO NOT APPLY POWER EXCEPT IN THE PRESENCE OF A FACTORY TRAINED SIEMENS TECHNICAL
REPRESENTATIVE.
6. ANY SMOKE DETECTOR HEAD INSTALLED BEFORE THE BUILDING IS CLEANED AND ACCEPTED SHALL
BE COVERED TO PROTECT FROM DUST. ANY FALSE ALARMS DUE TO DIRT CONTAMINATED HEADS
SHALL BE THE RESPONSIBILITY OF THE FIRE ALARM INSTALLER.
7. PROJECT WILL MAINTAIN THE FIRE RESISTANCE INTEGRITY OF ALL WALL, CEILING, AND ROOF
ASSEMBLIES ANY TIME THAT WORK IS NOT ACTIVELY BEING PERFORMED.
8. INSTALLATION OF DEVICES SHALL BE IN ACCORDANCE WITH MANUFACTURER'S INSTRUCTIONS.
POWER LIMITED AND NON-POWER LIMITED FIELD WIRING MUST BE INSTALLED WITHIN THE FACP
ENCLOSURE IN ACCORDANCE WITH MANUFACTURER'S INSTRUCTIONS AND NEC.
9. ALL WIRING SHALL BE INSTALLED ACCORDING TO 2020 NFPA 70 (NEC).
10. FIRE ALARM CIRCUITS SHALL BE IDENTIFIED IN ACCORDANCE WITH APPROPRIATE SECTION OF NEC
760. MARK ALL FIRE ALARM WIRES IN ACCORDANCE WITH NEC 760 SECTIONS FOR POWER LIMITED
AND NON-POWER LIMITED WIRE.
11. FIRE ALARM CABLE SHALL BE INSTALL IN (RED) EMT CONDUIT RACEWAYS.
12. FIRE ALARM CABLE INSTALLED IN UNDERGROUND CONDUIT OR OTHER WET LOCATIONS SHALL BE UL
LISTED FOR WET LOCATIONS.
13. FIRE ALARM CIRCUITS EXTENDING BEYOND ONE BUILDING AND RUN OUTDOOR SHALL BE INSTALLED
IN ACCORDANCE WITH NFPA 70 ARTICLES 760, 770, 725 AND 800 WHERE APPLICABLE.
14. ALL WIRING, INCLUDING SHIELDS MUST BE DRY AND FREE OF SHORTS AND GROUNDS.
15. ALL SHIELDED WIRE MUST HAVE SHIELD CONTINUITY AT FULL LENGTH OF THE WIRE.
16. ONLY SYSTEM WIRING CAN BE RUN IN THE SAME CONDUIT.
17. 120VAC IS NOT PERMITTED IN THE SAME CONDUIT WITH LOW VOLTAGE WIRING.
18. MAINTAIN 40 PERCENT CONDUIT FILL RATIO AS PER NEC REQUIREMENTS.
07/07/2022
S:
\P
RO
JE
CT
F
OL
DE
R\ Va lha lla
E ng ine er ing \21
.21 E
HR
M
-1
8\D
W G\
FA
\E
HR
M
.21
F A.
dw g_
Br ya n 7/7
/20
7:
:18 A
M
657-21-703JB100% BID DOCS
0 100% BID DOCS 07/07/20220 100% BID DOCS 07/07/2022
T
OPKI
A B C D E F G H J L M N Q R S
G10
G10A
H001
G01D
HOISTWAYG01B
G02A
G03
G03A
S101
STAIR 1
G01C
G05
G06
G05A
G01A
G07
G15
G09
G01
G08
G11A G13
G11 G12
L
F
EX
EX
EX
EX
RTSRTS
RTS
EX
EX EX
EX
FACP
FATC
PAD
EX
F
EX
EX
F
F
EX
F
EX VS
WFWF
VSVS
EX
PS
EXISTING
TX
T
EX
EX
RL
EX
EX
EX
F
EX
TXT
EX
TXT
EX
EX
EXEX
EX
EX
EX
VS
WF
VS
EX PIV
EX
EX
EX
EX
EX
VAC
EXISTING FIRE ALARM CONTROL PANEL
MANUAL PULL STATION
AOM
AIM
HEAT DETECTOR(L=LINEAR HEAT DETECTOR)
MONITOR MODULE
CONTROL RELAY MODULE
STROBE ONLY(WALL MOUNT)
SPEAKER ONLY(WALL MOUNT)
FACP
DOOR HOLDER
EXISTING ANNUNCIATOR PANELANN
VS
WF
TAMPER SWITCH
WATER FLOW SWITCH
SPEAKER/STROBE(WALL MOUNT)
DUCT DETECTOR
KITCHEN HOOD MODULE
CO DETECTOR
15cd
CEILING MOUNT STROBE ONLY
WALL MOUNT STROBE ONLY
WALL MOUNT HORN/STROBE
CEILING MOUNT HORN/STROBE
SB
RTS REMOTE TEST SWITCH
FIRE/SMOKE DAMPER
SMOKE DETECTOR (SOUNDER BASE
WITH LOW FREQUENCY)
SPEAKER/STROBE(CEILING)
SPEAKER ONLY(CEILING)
FATC EXISTING FIRE ALARM TERMINAL CABINET
EX = EXISTING TO REMAIN
ABBREVIATIONS LEGEND
C = CEILING MOUNT
TXT FA/MN SCROLLING TEXT SIGN
PAD EXISTING NAC CIRCUIT EXTENDER / POWER SUPPLY
PS PRESSURE SWITCH
RL = RELOCATE DEVICE
RLN = RELOCATE DEVICE NEW LOCATION
DEMO = REMOVE DEVICE
VAC EXISTING SITE VOICE CONTROL PANEL
00KEYNOTES
GENERAL NOTES
Drawing Title
VA FORM 08 - 6231
F
CONSULTANTS:
750 W HAMPDEN AVE
SUITE 300
ENGLEWOOD, CO 80110
(720) 550-6307 WWW.VALHALLAENGINEERING.COMDate:Revisions:
10987654321
10987654321
E
D
C
B
A
F
E
D
C
B
A
ARCHITECT/ENGINEERS: STAMP:
Approved: Project Director
Phase Project Title
Location
Issue Date Checked Drawn
Project Number
Drawing Number
Building Number
Number:
VETERANS
HEALTH
ADMINISTRATION
24-FA-110
FIRE ALARM PLAN - FLOOR 00 EHRM TRAINING AND ADMIN
SPACE SUPPORT
1 JEFFERSON BARRACKS DR ST. LOUIS, MO 63125
07/07/2022 KLM BAEVEG 21.21
24'12'6'3'1'-6"0'
Plan North
True North
3/16" = 1'-0"
FIRE ALARM PLAN - FLOOR 001
12364 W. ALAMEDA PKWY.
SUITE #135
LAKEWOOD CO 80228
(303) 985-2050
WWW.VERITASFIRE.COM
A. ALL FIRE ALARM EQUIPMENT SHALL BE INSTALLED PER NFPA
72 AND THE MANUFACTURER'S INSTRUCTIONS.
B. ALL INITIATING DEVICES SHALL BE FIELD LOCATED BASED
UPON THE LOCATION OF DIFFUSERS, LIGHTS, AND OTHER
POTENTIAL OBSTRUCTIONS.
C. WALL MOUNT THE BOTTOM OF ALL AUDIBLE/VISUAL
APPLIANCES AT MIN. 80" A.F.F., NO MORE THAN 96" AFF OR TOP
AT 6" BELOW THE CEILING, WHICHEVER IS LOWER.
D. ALL WIRING INSTALLATION SHALL CONFORM TO THE NEC.
E. ALL WIRING SHALL BE INSTALLED IN CONDUIT.
F. IT SHALL BE THE RESPONSIBILITY OF THE CONTRACTOR TO
RETURN ALL WIRES TO THE PANEL FREE OF OPENS,
GROUNDS, SHORTS AND/OR ANY OTHER CONDITION THAT MAY
PREVENT THE PROPER OPERATION OF THE FIRE ALARM
SYSTEM.
G. ALL MATERIALS SHALL BE COMPATIBLE WITH THE EXISTING
CAMPUS SYSTEMS.
H. CIRCUIT NEW EQUIPMENT INTO THE SAME FIRE ALARM ZONE
THAT IS SERVING THE SPRINKLER ZONE.
I. PROVIDE THE NECESSARY FIRE ALARM DEVICE IN THE
ELEVATOR SHAFT AND MACHINE ROOMS PER
NON-COMBUSTIBLE ELEVATOR EQUIPMENT.
J. PROVIDE PROPER DEVICE PROTECTION DURING
CONSTRUCTION TO UNSURE EXISTING DEVICE ARE NOT
DAMAGED.
1. EXISTING SPRINKLER RISER BUILDING 24
2. ADJUST DEVICE AS NEEDED FOR NEW CEILING TILE
3. PROVIDE NEW DEVICES FOR NEW HYDRAULIC ELEVATOR
4. NOT IN SCOPE OF WORK
5. EXISTING PANEL AND EQUIPMENT TO REMAIN
S:
\P
RO
JE
CT
F
OL
DE
R\ Va lha lla
E ng ine er ing \21
.21 E
HR
M
-1
8\D
W G\
FA
\E
HR
M
.21
F A.
dw g_
Br ya n 7/7
/20
7:
:18 A
M
657-21-703JB
LEGEND
100% BID DOCS
ROOM NUMBER KEY
NUMBER ROOM NAME
G01 CANTEEN DINING AREA
G01A FOOD SERVICE
G01B ELEV LOBBY
G01C EXT VESTIBULE
G01D HOISTWAY
G02A TELECOM
G03 CANTEEN STORE
G03A STORAGE
G04 CANTEEN STORE
G05 FOOD PREP
G05A FOOD PREP
G06 KITCHEN STORAGE
G07 KITCHEN
G08 HAC
G09 FOOD PREP
G10 CANTEEN / STORAGE
G10A STORAGE
G11 OFFICE
G11A OFFICE
G12 TOILET FEMALE
G13 TOILET MALE
G15 MECHANICAL RM
H001 CORRIDOR
S101 STAIR 1
OPKI
A B C D E F G H J L M N Q R S
103A 103
103B
110 112
102A
114B
S201
107A
107B
104B
S101
STAIR 1
G01D
HOISTWAY
H002
104A
114C
B001
NAC#
TX
T
EX
F
ELEVATOR
SHUNT
TRIP
MODULES
AOM
FATC
PAD
EX
EX NEW
NEW
F
EX
EX
TXT
EX
RNL
TXT F
EXEX
RNL
RNL
RNL
EXISTING FIRE ALARM CONTROL PANEL
MANUAL PULL STATION
AOM
AIM
HEAT DETECTOR(L=LINEAR HEAT DETECTOR)
MONITOR MODULE
CONTROL RELAY MODULE
STROBE ONLY(WALL MOUNT)
SPEAKER ONLY(WALL MOUNT)
FACP
DOOR HOLDER
EXISTING ANNUNCIATOR PANELANN
VS
WF
TAMPER SWITCH
WATER FLOW SWITCH
SPEAKER/STROBE(WALL MOUNT)
DUCT DETECTOR
KITCHEN HOOD MODULE
CO DETECTOR
15cd
CEILING MOUNT STROBE ONLY
WALL MOUNT STROBE ONLY
WALL MOUNT HORN/STROBE
CEILING MOUNT HORN/STROBE
SB
RTS REMOTE TEST SWITCH
FIRE/SMOKE DAMPER
SMOKE DETECTOR (SOUNDER BASE
WITH LOW FREQUENCY)
SPEAKER/STROBE(CEILING)
SPEAKER ONLY(CEILING)
FATC EXISTING FIRE ALARM TERMINAL CABINET
EX = EXISTING TO REMAIN
ABBREVIATIONS LEGEND
C = CEILING MOUNT
TXT FA/MN SCROLLING TEXT SIGN
PAD EXISTING NAC CIRCUIT EXTENDER / POWER SUPPLY
PS PRESSURE SWITCH
RL = RELOCATE DEVICE
RLN = RELOCATE DEVICE NEW LOCATION
DEMO = REMOVE DEVICE
VAC EXISTING SITE VOICE CONTROL PANEL
00KEYNOTES
GENERAL NOTES
Drawing Title
VA FORM 08 - 6231
F
CONSULTANTS:
750 W HAMPDEN AVE
SUITE 300
ENGLEWOOD, CO 80110
(720) 550-6307 WWW.VALHALLAENGINEERING.COMDate:Revisions:
10987654321
10987654321
E
D
C
B
A
F
E
D
C
B
A
ARCHITECT/ENGINEERS: STAMP:
Approved: Project Director
Phase Project Title
Location
Issue Date Checked Drawn
Project Number
Drawing Number
Building Number
Number:
VETERANS
HEALTH
ADMINISTRATION
24-FA-111
FIRE ALARM PLAN - FLOOR 01 EHRM TRAINING AND ADMIN
SPACE SUPPORT
1 JEFFERSON BARRACKS DR ST. LOUIS, MO 63125
07/07/2022 KLM BAEVEG 21.21
12364 W. ALAMEDA PKWY.
SUITE #135
LAKEWOOD CO 80228
(303) 985-2050
WWW.VERITASFIRE.COM
1 1. USE EXISTING NAC PANEL MOVED FROM ROOM 114C.
UNLESS SPACE SPARE CAPACITY IS REDUCED BELOW VA
REQUIREMENT OF 20% WITH THE NEW ADDITIONAL
EQUIPMENT ADD AN ADDITIONAL NAC PANEL
2. RE-USE EXISTING DEVICES IN LOCATIONS IF NECESSARY
3. RE-USE EXISTING TERMINAL CABINET MOVED FROM 114C
24'12'6'3'1'-6"0'
Plan North
True North
3/16" = 1'-0"
FIRE ALARM PLAN - FLOOR 011
S:
\P
RO
JE
CT
F
OL
DE
R\ Va lha lla
E ng ine er ing \21
.21 E
HR
M
-1
8\D
W G\
FA
\E
HR
M
.21
F A.
dw g_
Br ya n 7/7
/20
7:
:19 A
M
657-21-703JB
LEGEND
A. ALL FIRE ALARM EQUIPMENT SHALL BE INSTALLED PER NFPA
72 AND THE MANUFACTURER'S INSTRUCTIONS.
B. ALL INITIATING DEVICES SHALL BE FIELD LOCATED BASED
UPON THE LOCATION OF DIFFUSERS, LIGHTS, AND OTHER
POTENTIAL OBSTRUCTIONS.
C. WALL MOUNT THE BOTTOM OF ALL AUDIBLE/VISUAL
APPLIANCES AT MIN. 80" A.F.F., NO MORE THAN 96" AFF OR TOP
AT 6" BELOW THE CEILING, WHICHEVER IS LOWER.
D. ALL WIRING INSTALLATION SHALL CONFORM TO THE NEC.
E. ALL WIRING SHALL BE INSTALLED IN CONDUIT.
F. IT SHALL BE THE RESPONSIBILITY OF THE CONTRACTOR TO
RETURN ALL WIRES TO THE PANEL FREE OF OPENS,
GROUNDS, SHORTS AND/OR ANY OTHER CONDITION THAT MAY
PREVENT THE PROPER OPERATION OF THE FIRE ALARM
SYSTEM.
G. ALL MATERIALS SHALL BE COMPATIBLE WITH THE EXISTING
CAMPUS SYSTEMS.
H. CIRCUIT NEW EQUIPMENT INTO THE SAME FIRE ALARM ZONE
THAT IS SERVING THE SPRINKLER ZONE.
I. PROVIDE THE NECESSARY FIRE ALARM DEVICE IN THE
ELEVATOR SHAFT AND MACHINE ROOMS PER
NON-COMBUSTIBLE ELEVATOR EQUIPMENT.
J. PROVIDE PROPER DEVICE PROTECTION DURING
CONSTRUCTION TO UNSURE EXISTING DEVICE ARE NOT
DAMAGED.
100% BID DOCS
ROOM NUMBER KEY
NUMBER ROOM NAME
100 VEST
101 ELEV LOBBY
102 LOD OFFICE
102A LOD TRAINING
103 CORRIDOR
103A CORRIDOR
103B CORRIDOR
104 PHOTO STUDIO
104A STORAGE
104B LOD PHOTO
105 CR-1
106 STORAGE
107 CR-2
107A STORAGE
107B STORAGE
108 CR-5
109 CR-4
110 MEN
111 JAN
112 WOMEN
114 CR-3
114B TELECOM
114C OI&T
115 STORAGE
116 OFFICE
117 MECH
B001 BALCONY
H002 CORRIDOR
S201 STAIR 2
OPKI
A B C D E F G H J L M N Q R S
218 X200
S201 210 208 G01D
205A
218A
216A 201A
S101
201B
206 S206
217A
205C
NAC#
F
FATC
TXT
F
RNL
RNL
F
RNL
EX
EX
EX
RNL
RNL
EX
RNL
EX
RNL
EXISTING FIRE ALARM CONTROL PANEL
MANUAL PULL STATION
AOM
AIM
HEAT DETECTOR(L=LINEAR HEAT DETECTOR)
MONITOR MODULE
CONTROL RELAY MODULE
STROBE ONLY(WALL MOUNT)
SPEAKER ONLY(WALL MOUNT)
FACP
DOOR HOLDER
EXISTING ANNUNCIATOR PANELANN
VS
WF
TAMPER SWITCH
WATER FLOW SWITCH
SPEAKER/STROBE(WALL MOUNT)
DUCT DETECTOR
KITCHEN HOOD MODULE
CO DETECTOR
15cd
CEILING MOUNT STROBE ONLY
WALL MOUNT STROBE ONLY
WALL MOUNT HORN/STROBE
CEILING MOUNT HORN/STROBE
SB
RTS REMOTE TEST SWITCH
FIRE/SMOKE DAMPER
SMOKE DETECTOR (SOUNDER BASE
WITH LOW FREQUENCY)
SPEAKER/STROBE(CEILING)
SPEAKER ONLY(CEILING)
FATC EXISTING FIRE ALARM TERMINAL CABINET
EX = EXISTING TO REMAIN
ABBREVIATIONS LEGEND
C = CEILING MOUNT
TXT FA/MN SCROLLING TEXT SIGN
PAD EXISTING NAC CIRCUIT EXTENDER / POWER SUPPLY
PS PRESSURE SWITCH
RL = RELOCATE DEVICE
RLN = RELOCATE DEVICE NEW LOCATION
DEMO = REMOVE DEVICE
VAC EXISTING SITE VOICE CONTROL PANEL
00KEYNOTES
GENERAL NOTES
Drawing Title
VA FORM 08 - 6231
F
CONSULTANTS:
750 W HAMPDEN AVE
SUITE 300
ENGLEWOOD, CO 80110
(720) 550-6307 WWW.VALHALLAENGINEERING.COMDate:Revisions:
10987654321
10987654321
E
D
C
B
A
F
E
D
C
B
A
ARCHITECT/ENGINEERS: STAMP:
Approved: Project Director
Phase Project Title
Location
Issue Date Checked Drawn
Project Number
Drawing Number
Building Number
Number:
24-FA-112
FIRE ALARM PLAN - FLOOR 02 EHRM TRAINING AND ADMIN
SPACE SUPPORT
1 JEFFERSON BARRACKS DR ST. LOUIS, MO 63125
07/07/2022 KLM BAEVEG 21.21
12364 W. ALAMEDA PKWY.
SUITE #135
LAKEWOOD CO 80228
(303) 985-2050
WWW.VERITASFIRE.COM
1. USE EXISTING TERMINALCABINET PANEL MOVED FROM ROOM
205C.
2. UNLESS SPACE SPARE CAPACITY IS REDUCED BELOW VA
REQUIREMENT OF 20% WITH THE NEW ADDITIONAL
EQUIPMENT ADD AN ADDITIONAL NAC PANEL
3. NOTIFICATION DEVICES ON WALLS BELOW ON SHEET FA111.
4. RELOCATE EXISTING DEIVER
VETERANS
HEALTH
ADMINISTRATION
24'12'6'3'1'-6"0'
Plan North
True North
3/16" = 1'-0"
FIRE ALARM PLAN - FLOOR 021
S:
\P
RO
JE
CT
F
OL
DE
R\ Va lha lla
E ng ine er ing \21
.21 E
HR
M
-1
8\D
W G\
FA
\E
HR
M
.21
F A.
dw g_
Br ya n 7/7
/20
7:
:20 A
M
3 3
657-21-703JB
LEGEND
A. ALL FIRE ALARM EQUIPMENT SHALL BE INSTALLED PER NFPA
72 AND THE MANUFACTURER'S INSTRUCTIONS.
B. ALL INITIATING DEVICES SHALL BE FIELD LOCATED BASED
UPON THE LOCATION OF DIFFUSERS, LIGHTS, AND OTHER
POTENTIAL OBSTRUCTIONS.
C. WALL MOUNT THE BOTTOM OF ALL AUDIBLE/VISUAL
APPLIANCES AT MIN. 80" A.F.F., NO MORE THAN 96" AFF OR TOP
AT 6" BELOW THE CEILING, WHICHEVER IS LOWER.
D. ALL WIRING INSTALLATION SHALL CONFORM TO THE NEC.
E. ALL WIRING SHALL BE INSTALLED IN CONDUIT.
F. IT SHALL BE THE RESPONSIBILITY OF THE CONTRACTOR TO
RETURN ALL WIRES TO THE PANEL FREE OF OPENS,
GROUNDS, SHORTS AND/OR ANY OTHER CONDITION THAT MAY
PREVENT THE PROPER OPERATION OF THE FIRE ALARM
SYSTEM.
G. ALL MATERIALS SHALL BE COMPATIBLE WITH THE EXISTING
CAMPUS SYSTEMS.
H. CIRCUIT NEW EQUIPMENT INTO THE SAME FIRE ALARM ZONE
THAT IS SERVING THE SPRINKLER ZONE.
I. PROVIDE THE NECESSARY FIRE ALARM DEVICE IN THE
ELEVATOR SHAFT AND MACHINE ROOMS PER
NON-COMBUSTIBLE ELEVATOR EQUIPMENT.
J. PROVIDE PROPER DEVICE PROTECTION DURING
CONSTRUCTION TO UNSURE EXISTING DEVICE ARE NOT
DAMAGED.
100% BID DOCS
ROOM NUMBER KEY
NUMBER ROOM NAME
201 OFFICE
201A OFFICE
201B CORRIDOR
204 RESTROOM
205 CLOS
205A TELECOM
205C OI&T
206 STORAGE
207 CORRIDOR
208 ELEV LOBBY
210 CORRIDOR
211 OFFICE
216 STORAGE
216A STORAGE
217 OFFICE
217A OFFICE
218 OFFICE
218A PASSAGE
S206 E STAIR
X200 MECH CHASE
OPKI
A B C D E F G H J L M N Q R S
ATTIC
S101
STAIR 1
F
EX
EX
EXISTING FIRE ALARM CONTROL PANEL
MANUAL PULL STATION
AOM
AIM
HEAT DETECTOR(L=LINEAR HEAT DETECTOR)
MONITOR MODULE
CONTROL RELAY MODULE
STROBE ONLY(WALL MOUNT)
SPEAKER ONLY(WALL MOUNT)
FACP
DOOR HOLDER
EXISTING ANNUNCIATOR PANELANN
VS
WF
TAMPER SWITCH
WATER FLOW SWITCH
SPEAKER/STROBE(WALL MOUNT)
DUCT DETECTOR
KITCHEN HOOD MODULE
CO DETECTOR
15cd
CEILING MOUNT STROBE ONLY
WALL MOUNT STROBE ONLY
WALL MOUNT HORN/STROBE
CEILING MOUNT HORN/STROBE
SB
RTS REMOTE TEST SWITCH
FIRE/SMOKE DAMPER
SMOKE DETECTOR (SOUNDER BASE
WITH LOW FREQUENCY)
SPEAKER/STROBE(CEILING)
SPEAKER ONLY(CEILING)
FATC EXISTING FIRE ALARM TERMINAL CABINET
EX = EXISTING TO REMAIN
ABBREVIATIONS LEGEND
C = CEILING MOUNT
TXT FA/MN SCROLLING TEXT SIGN
PAD EXISTING NAC CIRCUIT EXTENDER / POWER SUPPLY
PS PRESSURE SWITCH
RL = RELOCATE DEVICE
RLN = RELOCATE DEVICE NEW LOCATION
DEMO = REMOVE DEVICE
VAC EXISTING SITE VOICE CONTROL PANEL
00KEYNOTES
GENERAL NOTES
Drawing Title
VA FORM 08 - 6231
F
CONSULTANTS:
750 W HAMPDEN AVE
SUITE 300
ENGLEWOOD, CO 80110
(720) 550-6307 WWW.VALHALLAENGINEERING.COMDate:Revisions:
10987654321
10987654321
E
D
C
B
A
F
E
D
C
B
A
ARCHITECT/ENGINEERS: STAMP:
Approved: Project Director
Phase Project Title
Location
Issue Date Checked Drawn
Project Number
Drawing Number
Building Number
Number:
24-FA-113
FIRE ALARM PLAN - FLOOR 03 EHRM TRAINING AND ADMIN
SPACE SUPPORT
1 JEFFERSON BARRACKS DR ST. LOUIS, MO 63125
07/07/2022 KLM BAEVEG 21.21
24'12'6'3'1'-6"0'
Plan North
True North
3/16" = 1'-0"
FIRE ALARM PLAN - FLOOR 031
12364 W. ALAMEDA PKWY.
SUITE #135
LAKEWOOD CO 80228
(303) 985-2050
WWW.VERITASFIRE.COM
1. EXISTING HEATS TO REMAIN
2. EXISTING DEVICES TO REMAIN ABOVE OLD STAGE AREA
VETERANS
HEALTH
ADMINISTRATION
S:
\P
RO
JE
CT
F
OL
DE
R\ Va lha lla
E ng ine er ing \21
.21 E
HR
M
-1
8\D
W G\
FA
\E
HR
M
.21
F A.
dw g_
Br ya n 7/7
/20
7:
:20 A
M
657-21-703JB
LEGEND
A. ALL FIRE ALARM EQUIPMENT SHALL BE INSTALLED PER NFPA
72 AND THE MANUFACTURER'S INSTRUCTIONS.
B. ALL INITIATING DEVICES SHALL BE FIELD LOCATED BASED
UPON THE LOCATION OF DIFFUSERS, LIGHTS, AND OTHER
POTENTIAL OBSTRUCTIONS.
C. WALL MOUNT THE BOTTOM OF ALL AUDIBLE/VISUAL
APPLIANCES AT MIN. 80" A.F.F., NO MORE THAN 96" AFF OR TOP
AT 6" BELOW THE CEILING, WHICHEVER IS LOWER.
D. ALL WIRING INSTALLATION SHALL CONFORM TO THE NEC.
E. ALL WIRING SHALL BE INSTALLED IN CONDUIT.
F. IT SHALL BE THE RESPONSIBILITY OF THE CONTRACTOR TO
RETURN ALL WIRES TO THE PANEL FREE OF OPENS,
GROUNDS, SHORTS AND/OR ANY OTHER CONDITION THAT MAY
PREVENT THE PROPER OPERATION OF THE FIRE ALARM
SYSTEM.
G. ALL MATERIALS SHALL BE COMPATIBLE WITH THE EXISTING
CAMPUS SYSTEMS.
H. CIRCUIT NEW EQUIPMENT INTO THE SAME FIRE ALARM ZONE
THAT IS SERVING THE SPRINKLER ZONE.
I. PROVIDE THE NECESSARY FIRE ALARM DEVICE IN THE
ELEVATOR SHAFT AND MACHINE ROOMS PER
NON-COMBUSTIBLE ELEVATOR EQUIPMENT.
J. PROVIDE PROPER DEVICE PROTECTION DURING
CONSTRUCTION TO UNSURE EXISTING DEVICE ARE NOT
DAMAGED.
100% BID DOCS
OPKI
A B C D E F G H J L M N Q R S
RTSRTS
RTS
F
EX
F
EX
EX
EX
EX
F
EX
TXT
EX
EX
EX
EXEX
EX
TXTF
EX EX
F
EX
EX
EX DEMO
EX
EX
EX
EX
RL
EX
EX
EX
EX
EX
FACP
FATC
PAD
AN
N
EX
VS
WF
VS
EX PIV
EX
EX
EX
EX
EX EX
TX
T
EX
EX
EX
EX
EX
VAC
G10
G10A
G13 G11
G02A
G03
S002G01
G05
G06
S001
G09
E01
G15
G08
G07
G02
G02B
G12
G03A
G05A
G01A
EXISTING FIRE ALARM CONTROL PANEL
MANUAL PULL STATION
AOM
AIM
HEAT DETECTOR(L=LINEAR HEAT DETECTOR)
MONITOR MODULE
CONTROL RELAY MODULE
STROBE ONLY(WALL MOUNT)
SPEAKER ONLY(WALL MOUNT)
FACP
DOOR HOLDER
EXISTING ANNUNCIATOR PANELANN
VS
WF
TAMPER SWITCH
WATER FLOW SWITCH
SPEAKER/STROBE(WALL MOUNT)
DUCT DETECTOR
KITCHEN HOOD MODULE
CO DETECTOR
15cd
CEILING MOUNT STROBE ONLY
WALL MOUNT STROBE ONLY
WALL MOUNT HORN/STROBE
CEILING MOUNT HORN/STROBE
SB
RTS REMOTE TEST SWITCH
FIRE/SMOKE DAMPER
SMOKE DETECTOR (SOUNDER BASE
WITH LOW FREQUENCY)
SPEAKER/STROBE(CEILING)
SPEAKER ONLY(CEILING)
FATC EXISTING FIRE ALARM TERMINAL CABINET
EX = EXISTING TO REMAIN
ABBREVIATIONS LEGEND
C = CEILING MOUNT
TXT FA/MN SCROLLING TEXT SIGN
PAD EXISTING NAC CIRCUIT EXTENDER / POWER SUPPLY
PS PRESSURE SWITCH
RL = RELOCATE DEVICE
RLN = RELOCATE DEVICE NEW LOCATION
DEMO = REMOVE DEVICE
VAC EXISTING SITE VOICE CONTROL PANEL
00KEYNOTES
GENERAL NOTES
Drawing Title
VA FORM 08 - 6231
F
CONSULTANTS:
750 W HAMPDEN AVE
SUITE 300
ENGLEWOOD, CO 80110
(720) 550-6307 WWW.VALHALLAENGINEERING.COMDate:Revisions:
10987654321
10987654321
E
D
C
B
A
F
E
D
C
B
A
ARCHITECT/ENGINEERS: STAMP:
Approved: Project Director
Phase Project Title
Location
Issue Date Checked Drawn
Project Number
Drawing Number
Building Number
Number:
24-FD-110
DEMOLITION PLAN - FLOOR 00 EHRM TRAINING AND ADMIN
SPACE SUPPORT
1 JEFFERSON BARRACKS DR ST. LOUIS, MO 63125
07/07/2022 KLM BAEVEG 21.21
24'12'6'3'1'-6"0'
Plan North
True North
3/16" = 1'-0"
DEMOLITION FIRE PLAN - FLOOR 001
12364 W. ALAMEDA PKWY.
SUITE #135
LAKEWOOD CO 80228
(303) 985-2050
WWW.VERITASFIRE.COM
A. ALL EXISTING EQUIPMENT TO REMAIN AS IS EXCEPT IN
NEW WORK AREAS.
B. ALL FIRE ALARM EQUIPMENT SHALL BE INSTALLED PER
NFPA 72 AND THE MANUFACTURER'S INSTRUCTIONS.
C. ALL INITIATING DEVICES SHALL BE FIELD LOCATED BASED
UPON THE LOCATION OF DIFFUSERS, LIGHTS, AND OTHER
POTENTIAL OBSTRUCTIONS.
D. WALL MOUNT THE BOTTOM OF ALL AUDIBLE/VISUAL
APPLIANCES AT MIN. 80" A.F.F., NO MORE THAN 96" AFF OR
TOP AT 6" BELOW THE CEILING, WHICHEVER IS LOWER.
E. ALL WIRING INSTALLATION SHALL CONFORM TO THE NEC.
F. ALL WIRING SHALL BE INSTALLED IN CONDUIT.
G. IT SHALL BE THE RESPONSIBILITY OF THE CONTRACTOR
TO RETURN ALL WIRES TO THE PANEL FREE OF OPENS,
GROUNDS, SHORTS AND/OR ANY OTHER CONDITION THAT
MAY PREVENT THE PROPER OPERATION OF THE FIRE
ALARM SYSTEM.
H. ALL MATERIALS SHALL BE COMPATIBLE WITH THE
EXISTING CAMPUS SYSTEMS.
I. CIRCUIT NEW EQUIPMENT INTO THE SAME FIRE ALARM
ZONE THAT IS SERVING THE SPRINKLER ZONE.
J. PROVIDE THE NECESSARY FIRE ALARM DEVICE IN THE
ELEVATOR SHAFT AND MACHINE ROOMS PER
NON-COMBUSTIBLE ELEVATOR EQUIPMENT.
K. PROVIDE PROPER DEVICE PROTECTION DURING
CONSTRUCTION TO UNSURE EXISTING DEVICE ARE NOT
DAMAGED.
VETERANS
HEALTH
ADMINISTRATION
S:
\P
RO
JE
CT
F
OL
DE
R\ Va lha lla
E ng ine er ing \21
.21 E
HR
M
-1
8\D
W G\
FA
\E
HR
M
.21
F A.
dw g_
Br ya n 7/7
/20
7:
:21 A
M
1. REVISE ALARM DEVICES AS NEEDED DURING CONSTRUCTION PHASING.
657-21-703JB
LEGEND
100% BID DOCS
ROOM NUMBER KEY
NUMBER ROOM NAME
E01 ELEVATOR SHAFT
G01 DINING AREA
G01A FOOD SERVICE
G02 OFFICE
G02A OFFICE
G02B OI&T
G03 CANTEEN STORE
G03A STORAGE
G04 CANTEEN STORE
G05 KITCHEN
G05A FOOD PREP
G06 KITCHEN STORAGE
G06A VACANT
G07 KITCHEN
G08 HAC
G09 DISH WASH
G10 STORAGE
G10A STORAGE
G11 VESTIBULE
G12 TOILET, FEMALE
G13 TOILET, MALE
G15 MECHANICAL RM
S001 STAIRWELL NO 1
S002 STAIRWELL NO 2
OPKI
A B C D E F G H J L M N Q R S
F
EX
RL
EX
EX
TXT
EX
EX
EX
TXT F
EX
TX
T
EX
F
EX
EX
EX
EX
EX
RL
DEMO
EX
EX
EX
FATC
PAD
EX
EX
EX
F
EXEX
EX
EX
EX
EX
TXT
EX
RL
RL EX
EX
E01
107A
107B
S002
STAIRWELL NO 2
104B
104A
114C
114B
S001
H100
101A 100
101B
101C
114A
105A 103
S003
110A
102A
102D
EXISTING FIRE ALARM CONTROL PANEL
MANUAL PULL STATION
AOM
AIM
HEAT DETECTOR(L=LINEAR HEAT DETECTOR)
MONITOR MODULE
CONTROL RELAY MODULE
STROBE ONLY(WALL MOUNT)
SPEAKER ONLY(WALL MOUNT)
FACP
DOOR HOLDER
EXISTING ANNUNCIATOR PANELANN
VS
WF
TAMPER SWITCH
WATER FLOW SWITCH
SPEAKER/STROBE(WALL MOUNT)
DUCT DETECTOR
KITCHEN HOOD MODULE
CO DETECTOR
15cd
CEILING MOUNT STROBE ONLY
WALL MOUNT STROBE ONLY
WALL MOUNT HORN/STROBE
CEILING MOUNT HORN/STROBE
SB
RTS REMOTE TEST SWITCH
FIRE/SMOKE DAMPER
SMOKE DETECTOR (SOUNDER BASE
WITH LOW FREQUENCY)
SPEAKER/STROBE(CEILING)
SPEAKER ONLY(CEILING)
FATC EXISTING FIRE ALARM TERMINAL CABINET
EX = EXISTING TO REMAIN
ABBREVIATIONS LEGEND
C = CEILING MOUNT
TXT FA/MN SCROLLING TEXT SIGN
PAD EXISTING NAC CIRCUIT EXTENDER / POWER SUPPLY
PS PRESSURE SWITCH
RL = RELOCATE DEVICE
RLN = RELOCATE DEVICE NEW LOCATION
DEMO = REMOVE DEVICE
VAC EXISTING SITE VOICE CONTROL PANEL
00KEYNOTES
GENERAL NOTES
Drawing Title
VA FORM 08 - 6231
F
CONSULTANTS:
750 W HAMPDEN AVE
SUITE 300
ENGLEWOOD, CO 80110
(720) 550-6307 WWW.VALHALLAENGINEERING.COMDate:Revisions:
10987654321
10987654321
E
D
C
B
A
F
E
D
C
B
A
ARCHITECT/ENGINEERS: STAMP:
Approved: Project Director
Phase Project Title
Location
Issue Date Checked Drawn
Project Number
Drawing Number
Building Number
Number:
VETERANS
HEALTH
ADMINISTRATION
24-FD-111
DEMOLITION PLAN - FLOOR 01 EHRM TRAINING AND ADMIN
SPACE SUPPORT
1 JEFFERSON BARRACKS DR ST. LOUIS, MO 63125
07/07/2022 KLM BAEVEG 21.21
24'12'6'3'1'-6"0'
Plan North
True North
3/16" = 1'-0"
DEMOLITION FIRE PLAN - FLOOR 011
12364 W. ALAMEDA PKWY.
SUITE #135
LAKEWOOD CO 80228
(303) 985-2050
WWW.VERITASFIRE.COM
A. ALL EXISTING EQUIPMENT TO REMAIN AS IS EXCEPT IN
NEW WORK AREAS.
B. ALL FIRE ALARM EQUIPMENT SHALL BE INSTALLED PER
NFPA 72 AND THE MANUFACTURER'S INSTRUCTIONS.
C. ALL INITIATING DEVICES SHALL BE FIELD LOCATED BASED
UPON THE LOCATION OF DIFFUSERS, LIGHTS, AND OTHER
POTENTIAL OBSTRUCTIONS.
D. WALL MOUNT THE BOTTOM OF ALL AUDIBLE/VISUAL
APPLIANCES AT MIN. 80" A.F.F., NO MORE THAN 96" AFF OR
TOP AT 6" BELOW THE CEILING, WHICHEVER IS LOWER.
E. ALL WIRING INSTALLATION SHALL CONFORM TO THE NEC.
F. ALL WIRING SHALL BE INSTALLED IN CONDUIT.
G. IT SHALL BE THE RESPONSIBILITY OF THE CONTRACTOR
TO RETURN ALL WIRES TO THE PANEL FREE OF OPENS,
GROUNDS, SHORTS AND/OR ANY OTHER CONDITION THAT
MAY PREVENT THE PROPER OPERATION OF THE FIRE
ALARM SYSTEM.
H. ALL MATERIALS SHALL BE COMPATIBLE WITH THE
EXISTING CAMPUS SYSTEMS.
I. CIRCUIT NEW EQUIPMENT INTO THE SAME FIRE ALARM
ZONE THAT IS SERVING THE SPRINKLER ZONE.
J. PROVIDE THE NECESSARY FIRE ALARM DEVICE IN THE
ELEVATOR SHAFT AND MACHINE ROOMS PER
NON-COMBUSTIBLE ELEVATOR EQUIPMENT.
K. PROVIDE PROPER DEVICE PROTECTION DURING
CONSTRUCTION TO UNSURE EXISTING DEVICE ARE NOT
DAMAGED.
1. REMOVE OR RELOCATE FOR REVISED PLAN
2. RELOCATE TO 114B - COORDINATE WITH ELECTRICAL FOR POWER
3. REVISE ALARM DEVICES AS NEEDED DURING CONSTRUCTION
PHASING.
S:
\P
RO
JE
CT
F
OL
DE
R\ Va lha lla
E ng ine er ing \21
.21 E
HR
M
-1
8\D
W G\
FA
\E
HR
M
.21
F A.
dw g_
Br ya n 7/7
/20
7:
:21 A
M
657-21-703JB
LEGEND
100% BID DOCS
ROOM NUMBER KEY
NUMBER ROOM NAME
100 ENTRY
101 AUDITORIUM
101A BREAK RM
101B STORAGE
101C STORAGE
102 TRAINING
102A OFFICE
102D TRAINING
103 CLOSET
104 OFFICE
104A STORAGE
104B STORAGE
105 KITCHEN
105A TOILET
106 STAGE LEFT
107A TOILET, MALE
107B STORAGE
108 STAGE
109 TOILET, FEMALE
110 STAGE RIGHT
110A VESTIBULE
114A PIPE CHASE
114B OFFICE
114C OI&T
115 STORAGE
H100 CORRIDOR
S002 STAIRWELL NO 2
S003 STAIRWELL NO 3
OPKI
A B C D E F G H J L M N Q R S
F
F
DEMO
RL
EX
EX
DEMO EX EX
EX
EX
EX
EX
EX
DEMO
DEMO
RL
TXTF
FATC
DEMO
DEMO DEMO
RL
RLRL
216A
205C
205A
208210210A
211A
S005
STAIR 5
215A
S004
201A
206A
EXISTING FIRE ALARM CONTROL PANEL
MANUAL PULL STATION
AOM
AIM
HEAT DETECTOR(L=LINEAR HEAT DETECTOR)
MONITOR MODULE
CONTROL RELAY MODULE
STROBE ONLY(WALL MOUNT)
SPEAKER ONLY(WALL MOUNT)
FACP
DOOR HOLDER
EXISTING ANNUNCIATOR PANELANN
VS
WF
TAMPER SWITCH
WATER FLOW SWITCH
SPEAKER/STROBE(WALL MOUNT)
DUCT DETECTOR
KITCHEN HOOD MODULE
CO DETECTOR
15cd
CEILING MOUNT STROBE ONLY
WALL MOUNT STROBE ONLY
WALL MOUNT HORN/STROBE
CEILING MOUNT HORN/STROBE
SB
RTS REMOTE TEST SWITCH
FIRE/SMOKE DAMPER
SMOKE DETECTOR (SOUNDER BASE
WITH LOW FREQUENCY)
SPEAKER/STROBE(CEILING)
SPEAKER ONLY(CEILING)
FATC EXISTING FIRE ALARM TERMINAL CABINET
EX = EXISTING TO REMAIN
ABBREVIATIONS LEGEND
C = CEILING MOUNT
TXT FA/MN SCROLLING TEXT SIGN
PAD EXISTING NAC CIRCUIT EXTENDER / POWER SUPPLY
PS PRESSURE SWITCH
RL = RELOCATE DEVICE
RLN = RELOCATE DEVICE NEW LOCATION
DEMO = REMOVE DEVICE
VAC EXISTING SITE VOICE CONTROL PANEL
00KEYNOTES
GENERAL NOTES
Drawing Title
VA FORM 08 - 6231
F
CONSULTANTS:
750 W HAMPDEN AVE
SUITE 300
ENGLEWOOD, CO 80110
(720) 550-6307 WWW.VALHALLAENGINEERING.COMDate:Revisions:
10987654321
10987654321
E
D
C
B
A
F
E
D
C
B
A
ARCHITECT/ENGINEERS: STAMP:
Approved: Project Director
Phase Project Title
Location
Issue Date Checked Drawn
Project Number
Drawing Number
Building Number
Number:
VETERANS
HEALTH
ADMINISTRATION
24-FD-112
DEMOLITION PLAN - FLOOR 02 EHRM TRAINING AND ADMIN
SPACE SUPPORT
1 JEFFERSON BARRACKS DR ST. LOUIS, MO 63125
07/07/2022 KLM BAEVEG 21.21
24'12'6'3'1'-6"0'
Plan North
True North
3/16" = 1'-0"
DEMOLITION FIRE PLAN - FLOOR 021
12364 W. ALAMEDA PKWY.
SUITE #135
LAKEWOOD CO 80228
(303) 985-2050
WWW.VERITASFIRE.COM
A. ALL EXISTING EQUIPMENT TO REMAIN AS IS EXCEPT IN
NEW WORK AREAS.
B. ALL FIRE ALARM EQUIPMENT SHALL BE INSTALLED PER
NFPA 72 AND THE MANUFACTURER'S INSTRUCTIONS.
C. ALL INITIATING DEVICES SHALL BE FIELD LOCATED BASED
UPON THE LOCATION OF DIFFUSERS, LIGHTS, AND OTHER
POTENTIAL OBSTRUCTIONS.
D. WALL MOUNT THE BOTTOM OF ALL AUDIBLE/VISUAL
APPLIANCES AT MIN. 80" A.F.F., NO MORE THAN 96" AFF OR
TOP AT 6" BELOW THE CEILING, WHICHEVER IS LOWER.
E. ALL WIRING INSTALLATION SHALL CONFORM TO THE NEC.
F. ALL WIRING SHALL BE INSTALLED IN CONDUIT.
G. IT SHALL BE THE RESPONSIBILITY OF THE CONTRACTOR
TO RETURN ALL WIRES TO THE PANEL FREE OF OPENS,
GROUNDS, SHORTS AND/OR ANY OTHER CONDITION THAT
MAY PREVENT THE PROPER OPERATION OF THE FIRE
ALARM SYSTEM.
H. ALL MATERIALS SHALL BE COMPATIBLE WITH THE
EXISTING CAMPUS SYSTEMS.
I. CIRCUIT NEW EQUIPMENT INTO THE SAME FIRE ALARM
ZONE THAT IS SERVING THE SPRINKLER ZONE.
J. PROVIDE THE NECESSARY FIRE ALARM DEVICE IN THE
ELEVATOR SHAFT AND MACHINE ROOMS PER
NON-COMBUSTIBLE ELEVATOR EQUIPMENT.
K. PROVIDE PROPER DEVICE PROTECTION DURING
CONSTRUCTION TO UNSURE EXISTING DEVICE ARE NOT
DAMAGED.
1. REMOVE OR RELOCATE FOR REVISED PLAN - SEE SHEET FA112
2. RELOCATION TERMINAL CABINET TO ROOM 205A.
COORDINATION MAY BE REQUIRED WITH ELECTRICAL
1 1
S:
\P
RO
JE
CT
F
OL
DE
R\ Va lha lla
E ng ine er ing \21
.21 E
HR
M
-1
8\D
W G\
FA
\E
HR
M
.21
F A.
dw g_
Br ya n 7/7
/20
7:
:22 A
M
657-21-703JB
LEGEND
100% BID DOCS
ROOM NUMBER KEY
NUMBER ROOM NAME
201 OFFICE
201A OFFICE
203 HAC
204 TOILET
205 OFFICE
205A OFFICE
205C OI&T
206 STORAGE
206A STORAGE
207 OFFICE
208 WORK RM
210 OFFICE
210A VACANT
211 STORAGE
211A VESTIBULE
212 TOILET
213 STORAGE
214 STORAGE
215 VESTIBULE
215A TOILET
216 STORAGE
216A STORAGE
217 SHARED OFFICE
218 STORAGE
S004 STAIR 4
S005 STAIR 5
0 100% BID DOCS 07/07/20220 100% BID DOCS 07/07/20220 100% BID DOCS 07/07/2022
OPKI
A B C D E F G H J L M N Q R S
EX
EX
EX
EX
EX
EX
EX
EX
EX
EX
EX
EX
EX
ATTIC
EXISTING FIRE ALARM CONTROL PANEL
MANUAL PULL STATION
AOM
AIM
HEAT DETECTOR(L=LINEAR HEAT DETECTOR)
MONITOR MODULE
CONTROL RELAY MODULE
STROBE ONLY(WALL MOUNT)
SPEAKER ONLY(WALL MOUNT)
FACP
DOOR HOLDER
EXISTING ANNUNCIATOR PANELANN
VS
WF
TAMPER SWITCH
WATER FLOW SWITCH
SPEAKER/STROBE(WALL MOUNT)
DUCT DETECTOR
KITCHEN HOOD MODULE
CO DETECTOR
15cd
CEILING MOUNT STROBE ONLY
WALL MOUNT STROBE ONLY
WALL MOUNT HORN/STROBE
CEILING MOUNT HORN/STROBE
SB
RTS REMOTE TEST SWITCH
FIRE/SMOKE DAMPER
SMOKE DETECTOR (SOUNDER BASE
WITH LOW FREQUENCY)
SPEAKER/STROBE(CEILING)
SPEAKER ONLY(CEILING)
FATC EXISTING FIRE ALARM TERMINAL CABINET
EX = EXISTING TO REMAIN
ABBREVIATIONS LEGEND
C = CEILING MOUNT
TXT FA/MN SCROLLING TEXT SIGN
PAD EXISTING NAC CIRCUIT EXTENDER / POWER SUPPLY
PS PRESSURE SWITCH
RL = RELOCATE DEVICE
RLN = RELOCATE DEVICE NEW LOCATION
DEMO = REMOVE DEVICE
VAC EXISTING SITE VOICE CONTROL PANEL
00KEYNOTES
GENERAL NOTES
Drawing Title
VA FORM 08 - 6231
F
CONSULTANTS:
750 W HAMPDEN AVE
SUITE 300
ENGLEWOOD, CO 80110
(720) 550-6307 WWW.VALHALLAENGINEERING.COMDate:Revisions:
10987654321
10987654321
E
D
C
B
A
F
E
D
C
B
A
ARCHITECT/ENGINEERS: STAMP:
Approved: Project Director
Phase Project Title
Location
Issue Date Checked Drawn
Project Number
Drawing Number
Building Number
Number:
VETERANS
HEALTH
ADMINISTRATION
S:
\P
RO
JE
CT
F
OL
DE
R\ Va lha lla
E ng ine er ing \21
.21 E
HR
M
-1
8\D
W G\
FA
\E
HR
M
.21
F A.
dw g_
Br ya n 7/7
/20
7:
:23 A
M
24-FD-113
DEMOLITION PLAN - FLOOR 03 EHRM TRAINING AND ADMIN
SPACE SUPPORT
1 JEFFERSON BARRACKS DR ST. LOUIS, MO 63125
07/07/2022 KLM BAEVEG 21.21
24'12'6'3'1'-6"0'
Plan North
True North
3/16" = 1'-0"
DEMOLITION FIRE PLAN - FLOOR 031
A. ALL EXISTING EQUIPMENT TO REMAIN AS IS EXCEPT IN
NEW WORK AREAS.
B. ALL FIRE ALARM EQUIPMENT SHALL BE INSTALLED PER
NFPA 72 AND THE MANUFACTURER'S INSTRUCTIONS.
C. ALL INITIATING DEVICES SHALL BE FIELD LOCATED BASED
UPON THE LOCATION OF DIFFUSERS, LIGHTS, AND OTHER
POTENTIAL OBSTRUCTIONS.
D. WALL MOUNT THE BOTTOM OF ALL AUDIBLE/VISUAL
APPLIANCES AT MIN. 80" A.F.F., NO MORE THAN 96" AFF OR
TOP AT 6" BELOW THE CEILING, WHICHEVER IS LOWER.
E. ALL WIRING INSTALLATION SHALL CONFORM TO THE NEC.
F. ALL WIRING SHALL BE INSTALLED IN CONDUIT.
G. IT SHALL BE THE RESPONSIBILITY OF THE CONTRACTOR
TO RETURN ALL WIRES TO THE PANEL FREE OF OPENS,
GROUNDS, SHORTS AND/OR ANY OTHER CONDITION THAT
MAY PREVENT THE PROPER OPERATION OF THE FIRE
ALARM SYSTEM.
H. ALL MATERIALS SHALL BE COMPATIBLE WITH THE
EXISTING CAMPUS SYSTEMS.
I. CIRCUIT NEW EQUIPMENT INTO THE SAME FIRE ALARM
ZONE THAT IS SERVING THE SPRINKLER ZONE.
J. PROVIDE THE NECESSARY FIRE ALARM DEVICE IN THE
ELEVATOR SHAFT AND MACHINE ROOMS PER
NON-COMBUSTIBLE ELEVATOR EQUIPMENT.
K. PROVIDE PROPER DEVICE PROTECTION DURING
CONSTRUCTION TO UNSURE EXISTING DEVICE ARE NOT
DAMAGED.
12364 W. ALAMEDA PKWY.
SUITE #135
LAKEWOOD CO 80228
(303) 985-2050
WWW.VERITASFIRE.COM
657-21-703JB
LEGEND
1. EXISTING HEAT DETECTORS TO REMAIN
1 1 1
100% BID DOCS
Sheets and Views
| 24-F-001 FIRE ALARM LEGENDS, NOTES, AND SYMBOLS |
| 24-FA-110 FIRE ALARM PLAN - FLOOR 00 |
| 24-FA-111 FIRE ALARM PLAN - FLOOR 01 |
| 24-FA-112 FIRE ALARM PLAN - FLOOR 02 |
| 24-FA-113 FIRE ALARM PLAN - FLOOR 03 |
| 24-FD-110 DEMOLITION PLAN - FLOOR 00 |
| 24-FD-111 DEMOLITION PLAN - FLOOR 01 |
| 24-FD-112 DEMOLITION PLAN - FLOOR 02 |
| 24-FD-113 DEMOLITION PLAN - FLOOR 03 |