J-9_Arecibo_Facilty_Survey_Part2.pdf

PDF 21 MB Posted

Attached to
Operation of the Puerto Rico Job Corps Center with OA/CTS
Solicitation number
1630J1-18-R-00010
Issued by

About this file

Attachment J.9 Facility Survey (Arecibo) 2 of 2

View the file

Other files

File Type Posted
1630J1-18-R-00010_Amendment_0006.pdf PDF
J-13_-_GSA_Leased_Vehicles_FY_18_Puerto_Rico_-_Amended_9-26-2018.xlsx XLSX spreadsheet
J.16_Davis_Bacon_Wage_Determination_(Amended).pdf PDF
Answers_to_Puerto_Rico_RFP_Questions.docx DOCX document
J-5_-_Puerto_Rico_CTST_Offerings_-_Amended_-_9-25,_2018.pdf PDF
Barranquitas_November_2017_mold_report.pdf PDF
Barranquitas_November_2017_water_report.pdf PDF
Arecibo_December_2017_mold_report_(002).pdf PDF
Arecibo_November_2017_water_report.pdf PDF
1630J1-18-R-00010_Amendment_0005.pdf PDF
1630J1-18-R-00010_Amendment_4.pdf PDF
Amendment_Three.pdf PDF
J-15_Ramey_June_2018_MSO_20.pdf PDF
J-15_Arecibo_June_2018_CTT_10.pdf PDF
J-15_Arecibo_June_2018_MSO_20.pdf PDF
v2_J-1_Update_for_Combo_FFP_Template.xlsx XLSX spreadsheet
J-15_Arecibo_MPO35_~_June_2018.pdf PDF
Sol_1630J1-18-R-00010_Amd_0002_Signed_by_CO.pdf PDF
J-15_Ramey_MPO35_~_June_2018.pdf PDF
J-15_Ramey_June_2018_CTT_10.pdf PDF
J4_OJC_Revision_Final.docx DOCX document
Amendment_0001_1630J1-18-R-00010_Signed.pdf PDF
J-9_Ramey_Facilty_Survey_Part1.pdf PDF
J-9_Ramey_Facilty_Survey_Part2.pdf PDF
J-9_Arecibo_Facilty_Survey_Part1.pdf PDF
SECTION_J_(List_of_Attachments).docx DOCX document
1630J1-18-R-00010_-Operation_of_the_Puerto_Rico_Job_Corps_center_with_OA-CTS.pdf PDF
Show all 27

On GovTribe

Work with this file

  • Download the original file
  • Contacts named in this file
  • Similar government files
  • Ask GovTribe AI about this file

Text version

ARECIBO

Job Corps Center Garrochales, PR

Facility Planning Report Volume II

Supporting Data

Preliminary May 2016

Department of Labor/ Office of Job Corps

ARECIBO

Job Corps Center Garrochales, PR

Facility Planning Report Volume II

Supporting Data

Preliminary May 2016

Student Plaza

VOLUME II - SUPPORTING DATA

EXECUTIVE SUMMARY

1.0 SITE LAYOUT AND PLANS

• Location Map

• Exisiting Site Plan

2.0 DESCRIPTIONS

• Buildings and Structures

• Space Utilization By Function

• NSF by Building

• Environmental Management Report

• Asbestos Report

• Radon Report

• Site Descriptions

• Building Descriptions

3.0 DEFICIENCIES

APPENDICES - CORRESPONDENCE AND REPORTS

Appendix A.

• Center Review Meeting Minutes

• Survey Brief

• Student Questionnaire

Appendix B.

• Life Safety Defi ciencies and List

Appendix C.

• O&M Defi ciencies List

Appendix D.

• Active Warranty List

Executive Summary

The Facility Survey for the Arecibo Job Corps Center (Arecibo JCC) was completed between January 12, 2016 and January 14, 2016. The information presented in Volume II, Supporting Data, represents the current status of the campus.

The information includes the following:

Existing site layout Overall status of existing buildings and structures Space utilization by building and function compared to recommended standards Status of environmental elements of the Center’s operations Details on the site and buildings and structures based on architectural, electrical, and mechanical survey, and supporting documentation Presentation of the status of historical deficiencies and compilation of deficiencies documented through this Survey Supporting documentation, as presented in the appendices of the Center Review Meeting; Survey Brief and Student Questionnaire; Life Safety IA/IIA Transmittal;

Active Warranties; and Federal Real Property Council (FRPC) Measures Matrix

Section 1.0 of this volume addresses site layout and plans while Section 2.0 presents details on the buildings and structures. Section 3.0 presents historic deficiencies and their status as well as new ones identified in the current Survey. The appendices provide additional information as noted below:

Appendix A. Survey Brief Questionnaire Appendix B. Life Safety Deficiencies and List Appendix C. Operations and maintenance (O&M) Deficiencies List Appendix D. Active Warranty Report, and Appendix E. FRPC Performance Measures Matrix

EXECUTIVE SUMMARY

1.0 - Site Layout and Plans

ARECIBO

JOB CORPS CENTER

GARROCHALES, PUERTO RICO

ARECIBO JCC

20 MI100

2.0 - Descriptions

BUILDINGS AND STRUCTURES

00204 ARECIBO 06/07/2016

1Page: of Date:

0001 - DISPENSARY

0003 - SECURITY/COVERED PARKING

0004 - FM&C/RETAIL/CPP

0005 - CDSS

0006 - EDUCATION

0009 - RECREATION

0011 - ADMIN/WAREHOUSE

0012 - EDUCATION

0013 - CAFETERIA

0014 - ACADEMIC

0015 - NURSING/BOT

0017 - SOLAR PV

0018 - ELECTRICAL/EDUCATION

0021 - VACANT

0022 - VACANT

0026 - WOMEN'S DORMITORY

0027 - VACANT

0028 - MEN'S DORMITORY

0029 - LAUNDRY

0034 - GYMNASIUM

0002 - FLAMMABLE STORAGE (6Ft x 20Ft) 0008 - CTST STORAGE (30Ft x 30Ft) 0030 - EMERGENCY GENERATOR (8Ft x 20Ft) 0035 - GAZEBO (16Ft x 16Ft)

0036 - FLAMMABLE & GEN STORAGE

(20Ft x 20Ft) 0037 - GAZEBO (16Ft x 16Ft) 0038 - VACANT (24Ft x 34Ft) 0039 - GAS SHED (6Ft x 14Ft) 0040 - STUDENTS' SHOP (12Ft x 22Ft) 0041 - COVERED WALKWAY (6Ft x 224Ft) 0042 - STORAGE (12Ft x 16Ft) 0043 - SMALL WATER TANK (20Ft x 20Ft) 0044 - LARGE WATER TANK (25Ft x 25Ft) 0045 - GENERATOR (10Ft x 15Ft) 0046 - FIRE HOSE STATION (4Ft x 4Ft) 0047 - FIRE HOSE STATION (4Ft x 4Ft) 0048 - BARBEQUE (2Ft x 6Ft) 0049 - PLANTER (8Ft x 8Ft)

Name GSF

1,740 1,200 5,480 1,000 1,650 3,900 4,985 1,200 4,100 3,040 5,743 1,900 4,100 3,100 2,200

13,800 2,200

13,800

13,290

Active Active Active Active Active Active Active Active Active Active Active Active Active Active Active Active Active Active Active Active Active Active Active

Active Active

Active Active Active Active Active Active Active Active Active Active Active Active Active

StatusType

Building Building Building Building Building Building Building Building Building Building Building Building Building Building Building Building Building Building Building Building Structure Structure Structure

Structure Structure

Structure Structure Structure Structure Structure Structure Structure Structure Structure Structure Structure Structure Structure

Use Group Built Flrs Const

B B B B B A-3,B,S-1 B,S-1 B A-2 B B,H B B R-2 R-2 Residential S-1 R-2 B A-3 H S-1 U

U H,S-1

U B U B A-3 S-1 Utility/Misc.

Utility/Misc.

Utility/Misc.

Utility/Misc.

Utility/Misc.

Utility/Misc.

Utility/Misc.

Poor Good Good Good Good Good Good Good Good Good Fair

Good Good Poor Poor Good Poor Good Poor Good Good Good Good

Good Good

Good Fair

Good Good Good Good Fair Fair

Good Good Good Good Good

ConditionAsset Number

0020400002 0020400003 0020400004 0020400039 0020400024 0020400009 0020400007 0020400008 0020400005 0020400010 0020400011 0020400013 0020400014 0020400016 0020400017 0020408142 0020400022 0020408141 0020400023 0020400034 0020400027 0020400031 0020400028

0020400035 0020400036

0020400037 0020408134 0020408140 0020408135 0020408143 0020408144 0020408145 0020408146 0020408147 0020408148 0020408149 0020408150 0020408151

20 88,668

18 4,223

38 92,891

Buildings

Structures

Total

GSF

GSF

GSF

Summary

06/07/2016

Space Utilization By Function 00204 Arecibo Page: 1 of Date:

HOUSING

EDUCATION

FOOD SERVICE

RECREATION

SUGGESTED

NSF/

ENROLLEE

SUGGESTED

TOTAL

NSF

ACTUAL

TOTAL

NSF

TYPE OF SPACE

SUB TOTAL

SUB TOTAL

SUB TOTAL

SUB TOTAL

Resident Men Resident Women Total Residents

Residents 129 Non Residents 48

177Total Students

(129)

(200)

(177)

(177)

DIFFERENCE

13,932

13,530

3,186

7,170

20,580

19,664

3,529

14,507

Lounge Other Shower/Toilet Sleeping excl. SPD( rooms; beds) Storage

Academic (200) Non-Academic

6 -- ACT (Off-Ctr) 24 -- Electrical + 24 -- Facilities Maint. and Const. +

50 -- LPN +

30 -- Office Administration 20 -- Retail Sales + 20 -- Solar +

Vocational Theory (138)

Dining (2 Servings) Food Preparation Food Storage

Arts & Crafts Gymnasium Recreation Hall Recreation Office Weight Room

2,320 2,680 3,640

11,440

2,739 5,323

1,758 2,179 2,797 1,590 1,312

1,966

1,758 1,321

10,555 1,974

1,235

1,290 1,032 1,548 9,288

2,000 2,000

1,200 1,800 2,000 1,350

1,000

1,380

1,416 1,062

1,030 1,648 2,092 2,152

-274

3,323

-1,000

-258

10,555 1,974

1,235

Vocations

RESIDENT

NON-RESIDENT

(129)

(48) 15

50 6,450

6,648

6,134

7,337

06/07/2016

Space Utilization By Function 00204 Arecibo Page: 2 of Date:

MEDICAL/DENTAL

ADMINISTRATION

STORAGE/SUPPORT

VACANT

SUGGESTED

NSF/

ENROLLEE

SUGGESTED

TOTAL

NSF

ACTUAL

TOTAL

NSF

TYPE OF SPACE

SUB TOTAL

SUB TOTAL

SUB TOTAL

SUB TOTAL

TOTAL 260.75 46,153 71,966

(177)

(177)

(177)

(0)

DIFFERENCE

88,668

0.81

TOTAL GSF

NET TO GROSS RATIO

1,255

3,540

3,540

1,128

3,298

1,738

7,522

Medical Only

Administration

Operations & Maintenance Warehouse

Vacant

7.09

1,128

3,298

1,020

7,522

1,255

3,540

1,416 2,124

-127

-242

-698 -1,104

7,522

-127

-242

-1,802

7,522

25,813

Net Square Footage By Building Date: 06/07/2016 Page: 1

Center: ARECIBO (00204) of 4

HOUSING

Sleeping excl. SPD

Lounge

Storage

Shower/Toilet

Other

Function Suggested

NSF

5,720 5,720

1,160 1,160

1,820 1,820

1,240

1,240

0026 - WOMEN'S DORMITORY

0028 - MEN'S DORMITORY

0028 - MEN'S DORMITORY

0026 - WOMEN'S DORMITORY

0026 - WOMEN'S DORMITORY

0028 - MEN'S DORMITORY

0026 - WOMEN'S DORMITORY

0028 - MEN'S DORMITORY

0028 - MEN'S DORMITORY

0029 - LAUNDRY

0026 - WOMEN'S DORMITORY

Bldg Name Actual NSF Difference

11,440

2,320

3,640

2,680

Sub Total: 20,580

9,288

1,290

1,548

1,032

13,932

2,152

1,030

-274

2,092

1,648

( 129

6,648 rooms; beds rooms; beds

Page: 2

Center: ARECIBO (00204) of 4

EDUCATION

Academic

Vocational Theory (138)

Electrical

Retail Sales

Facilities Maint. and Const.

LPN

Non-Academic

Office Administration

Function Suggested

NSF

1,758

1,312

2,179

1,410 1,387

1,590

0014 - ACADEMIC

0014 - ACADEMIC

0014 - ACADEMIC

0014 - ACADEMIC

0015 - NURSING/BOT

0014 - ACADEMIC

0014 - ACADEMIC

0004 - FM&C/RETAIL/CPP

0017 - SOLAR PV

0018 - ELECTRICAL/EDUCATION

0015 - NURSING/BOT

0018 - ELECTRICAL/EDUCATION

0004 - FM&C/RETAIL/CPP

0004 - FM&C/RETAIL/CPP

0017 - SOLAR PV

0015 - NURSING/BOT

0009 - RECREATION

0006 - EDUCATION

0018 - ELECTRICAL/EDUCATION

0012 - EDUCATION

0006 - EDUCATION

0009 - RECREATION

0018 - ELECTRICAL/EDUCATION

0005 - CDSS

0004 - FM&C/RETAIL/CPP

0015 - NURSING/BOT

Bldg Name Actual NSF Difference

2,739

1,966

1,758

1,312

2,179

2,797

5,323

1,590

Sub Total: 19,664

2,000

1,380

1,200

1,800

2,000

2,000

1,350

12,530

3,323

( 200

7,134

Page: 3

Center: ARECIBO (00204) of 4

FOOD SERVICE

RECREATION

MEDICAL/DENTAL

ADMINISTRATION

STORAGE/SUPPORT

Dining (2 Servings)

Food Preparation

Food Storage

Recreation Hall

Arts & Crafts

Gymnasium

Weight Room

Recreation Office

Medical Only

Administration

Warehouse

Operations & Maintenance

Function Suggested

NSF

1,758

1,321

1,974

10,555

1,235

1,128

2,615

1,020

0013 - CAFETERIA

0013 - CAFETERIA

0013 - CAFETERIA

0009 - RECREATION

0034 - GYMNASIUM

0034 - GYMNASIUM

0034 - GYMNASIUM

0034 - GYMNASIUM

0001 - DISPENSARY

0003 - SECURITY/COVERED PARKING

0011 - ADMIN/WAREHOUSE

0011 - ADMIN/WAREHOUSE

0009 - RECREATION

0015 - NURSING/BOT

Bldg Name Actual NSF Difference

1,758

1,321

1,974

10,555

1,235

1,128

3,298

1,020

Sub Total:

Sub Total:

Sub Total:

Sub Total:

Sub Total:

3,529

14,507

1,128

3,298

1,738

1,416

1,062

1,255

3,540

2,124

1,416

3,186

7,170

1,255

3,540

3,540

-258

-127

-242

-1,104

-698

7,337

-127

-242

-1,802

Page: 4

Center: ARECIBO (00204) of 4

VACANT

Vacant

Function Suggested

NSF

1,455 1,910 1,906 2,251

0015 - NURSING/BOT

0022 - VACANT

0027 - VACANT

0021 - VACANT

Bldg Name Actual NSF Difference

7,522

Sub Total: 7,522

7,522

( 0

7,522

Environmental Management Report

Center: ARECIBO (00204) Page: 1 Date: 06/07/2016 of 1

SOLID & HAZARDOUS WASTE MANAGEMENT (RCRA)

Commercial Waste Service

HAZARDOUS MATERIALS STORAGE (EPCRA)

No Buildings 4, 13, 29, and Structures 2 and 36

Oil-based paint (12 gals), propane (1000 gals), organic solvent (5 gals) Yes

PETROLEUM UNDERGROUND STORAGE TANKS (RCRA)

N/A0

PETROLEUM ABOVEGROUND STORAGE TANKS (CWA)

ASBESTOS AND PCB MANAGEMENT (TSCA)

AIR POLLUTION CONTROL (CAA)

N/A None

Attainment

Solid Waste Disposal :

Hazardous Waste Generator :

Hazardous Waste ID :

Generator Classification :

Hazadous Materials Storage :

Hazardous Materials ID :

HazMat Storage Area :

HazMat Spill Response Plan :

Number of Regulated USTs :

Number of Un-regulated USTs :

Local Hazardous Use Permit :

LEPC Notification :

EPA Generator ID Number :

Hazardous Waste Disposal :

RCRA Compliance :

ID LocationFuel Type Capacity

Number of ASTs :

Asbestos Survey Date :

Asbestos Type :

Asbestos Coordinator :

Coordinator Training Date:

Custodial/Maintenance Training :

AHERA Regulated :

Management Plan Approval :

PCB Transformer Testing :

PCB Transformers :

PCB-Contaminated Transformers :

Transformers Labelled :

Regional Air Quality :

Permitted Air Pollution Source :

Source Description :

Chico Waste No N/A

N/A N/A N/A N/A

No No

Overfill Leak Corrosion

SPCC Plan Required : SPCC Plan Completed :

No N/A

05/25/1990 Non-Friable Only Glenda Padilla 02/19/2004 Yes No N/A Yes Yes

ID Fuel Type Capacity Location Overfill

Prevention Secondary Containment

1 Petroleum - Heating Oil 1000 Behind Structure 30 Yes Yes

Tank Status Active

Tank Status Prevention/Detection

Asbestos-Containing Materials Inventory

Date: 06/07/2016Center : Arecibo (00204) Page: 1 of 1

Roof Repair/Replacement

Electrical (Bldg)

Bldg System

Bldg System

Roof tar sealant

Vibration isolation collar

Category Description

Category Description

Sq. Ft.

Lin. Ft.

Location

Location

Unit

Unit

Quantity

Quantity

Metal pan roof

Generator exhaust

Building :

Building :

0006 - EDUCATION

0030 - EMERGENCY GENERATOR (8Ft x 20Ft)

Radon

Page: 1 of 1

0001 - DISPENSARY

0003 - SECURITY/COVERED PARKING

0004 - FM&C/RETAIL/CPP

0005 - CDSS

0006 - EDUCATION

0009 - RECREATION

0011 - ADMIN/WAREHOUSE

0012 - EDUCATION

0013 - CAFETERIA

0014 - ACADEMIC

0015 - NURSING/BOT

0017 - SOLAR PV

0018 - ELECTRICAL/EDUCATION

0021 - VACANT

0022 - VACANT

0026 - WOMEN'S DORMITORY

0027 - VACANT

0028 - MEN'S DORMITORY

0029 - LAUNDRY

0034 - GYMNASIUM

Bldg Name

12/11/1990

12/11/1990

12/11/1990

12/11/1990

12/11/1990

12/11/1990

12/11/1990

12/11/1990

12/11/1990

12/11/1990

12/11/1990

12/11/1990

12/11/1990

12/11/1990

12/11/1990

Test Date

Yes

No

Yes

No

Yes

Yes

Yes

Yes

Yes

Yes

Yes

Yes

Yes

Yes

Yes

No

Yes

No

Yes

No

Radon Testing

< 4 pCi

< 4 pCi

< 4 pCi

< 4 pCi

< 4 pCi

< 4 pCi

< 4 pCi

< 4 pCi

< 4 pCi

< 4 pCi

< 4 pCi

< 4 pCi

< 4 pCi

< 4 pCi

< 4 pCi

Test Result

N/A

N/A

N/A

N/A

N/A

N/A

N/A

N/A

N/A

N/A

N/A

N/A

N/A

N/A

N/A

N/A

N/A

N/A

N/A

N/A

Mitigation Mitigation Date

RADON EXPLANATORY NOTES

The US Environmental Protection Agency (EPA) has established a radon action level of 4.0 picoCuries per liter (pCi/L). Occupied buildings with radon concentrations less than 4.0 pCi/L do not require radon mitigation; un-occupied buildings, or those buildings which are occupied only infrequently for brief periods of time, also do not require radon mitigation. Occupied buildings with radon concentrations greater than

4.0 pCi/L require radon mitigation and verification of radon reductions as soon as possible, with priority given to dormitories and student recreation buildings. Occupied buildings with radon concentrations greater than 20.0 pCi/L should be considered significant radon exposure hazards, and priority for mitigation should be given to buildings with these highly elevated radon concentrations.

Radon mitigation techniques include: (1) adjustment of the building HVAC system to create a positive pressure within the building; (2) sealing of foundation wall cracks, penetrations, or other openings;

(3) sealing crawlspace openings and sump pits; (4) installing an active subslab depressurization (ASD) system.

Site Description

Aerial View of Arecibo JCC

Page: 1 Date: 06/07/2016 of 4

Comments:

Paving Type for Roads & Parking

The lower campus is prone to flooding.

Paving Type for Sidewalks

Asphalt Concrete

Comments:

Topography Buildings and Structures

Center is fully enclosed by fencing.

ROADS, PARKING & SIDEWALKS

Water Source Water Authority Service Meter On-Site Treatment Plant

1. Water System

Treatment Type Storage Type Storage Capacity(Gallons)

NoMasterAAA (Autoridad de Acueductos y AlcantariPublic Water Authority

Water Softener 40,000Aboveground

Potable water system provided with a booster pump and softener. As of the Januiary 2016 Facility Survey, one of two booster pumps had been removed. The water softener brine tank was empty.

Comments:

Comments:

Fire Hydrants On-Site Water Supply Storage Capacity

(Gallons) Pressure Source FD Response Time

(Minutes)

Yes 30,000 15Aboveground Tank Elevated Tank

Upon sensing a flow of fire protection water, a pump is activated to increase pressure and flow. As of the January 2016 Facility Survey, the jockey pump was out of service due to a controls failure. The pressure and flow of fire protection water was limited to that provided by the elevation of the tank and the resistance of the piping.

Number of Deficiencies = 1

Number of Deficiencies = 2

Number of Deficiencies = 1

SITE FEATURES

UTILITIES

2. Fire Protection System

Buildings Structures20 18Gently Sloping

Surrounding

Outdoor Recreation

Residential

Field Arecibo County Arboretum

Entire Site Chain Link

Location Type

Maintenance Responsibility System Capacity Adequate System Condition

Lessor Center Yes Fair

Separate Loop

No

Ownership Maintenance Responsibility System Capacity Adequate System Condition

Lessor Center Yes Poor

Ownership

Roads & Parking Adequate Roads & Parking Condition Sidewalks Adequate Sidewalk Condition Yes Fair Yes Good

Fencing

Other Features

Page: 2 Date: 06/07/2016 of 4

Comments:

Sewage Treatment Flow

There are a number of septic tanks distributed throughout the center located as follows:

Near Building 13: 2,800 gallons.

Near Building 4: 610 gallons.

Near Building 5: 500 gallons.

Near Building 13: 2,010 gallons.

Near Building 9: 900 gallons.

Near Building 1: 600 gallons.

Near Building 15: 1,530 gallons.

Four septic tanks near Buildings 26 and 28: 14,000 gallons, total.

One holding tank near Building 26: 38,200 gallons.

There is a percolation field to the north of Building 26. Its performance was compromised and raw water was present on the surface at the time of the January 2016 Facility Survey.

Lessor

On-site Septic Systems

Center

Gravity

Maintenance ResponsibilityOwnership

Number of Deficiencies = 13. Sanitary Sewer System/ Sewage Treatment Plant

System Capacity Adequate System Condition

Yes Fair

4. Storm Water System Number of Deficiencies = 1

Drain Type On-Site Storm Water Management

Surface Run-off None

Ownership Maintenance Responsibility System Capacity Adequate System Condition

Center Yes FairCenter

Comments: The ball field has an underground water drainage system. Drainage can be slow after a heavy storm.

5. Fuel Distribution System: None

6. Central Plant: None

Page: 3 Date: 06/07/2016 of 4

Comments:

Electric Company PCB Trans.

Transformer Mounting Transformer Ownership

Systems Ownership Maintenance Responsibility

Puerto Rico Energy Power Authority

Overhead primary service is provided to a single-point connection at the Center main entrance northeast of the site behind Security Building 3. The utility service meter is mounted on a near by pole. The overhead distribution is radial which provides services to buildings via pole-mounted and pad-mounted transformers. The majority of buildings and the ballfield on the Center are served by pole-mounted transformers. The two newer buildings, Women's Dormitory Building 26 and Men's Dormitory Building 28, are served by their respective pad-mounted transformers. Each service in the dormitory buildings has a secondary meter located in the electrical room. There are two diesel engine generators, a 130 kW and a 80 kW, each with a 400A automatic transfer switch (ATS) located out side Cafeteria Building 13. The 80 kW generator is dedicated to Building 13 while the 130 kW generator supports part of Buildings 13, 15, 18, 22 and 34. Another 80 kW diesel engine generator located in the back of Building 28 which supports both dormitory Buildings 26 and 28 via their respective ATS. The two buildings also have lightning protection system installed on the roof. Due to severe weather conditions most of lighting and power poles are made of concrete which is the local utility standard.

Pole and Pad Center

Lessor Center

No

Comments:

Telephone Company

On-site Line Owner

The main telecommunication closet, main cross connect (MC), is located in Building 11. Server and router equipment in this room is by Cisco systems, and has an approximate 15-minute uninterrupted power supply.

From this location, fiber optic cable serves as a backbone connecting to IC cabinets in other buildings. Within buildings, Cat 6 cable connects from IC cabinets to data outlets for LAN, WAN and VoIP user access. Four T1 connections enter to the MC. MCI provides IP and long distance phone service. Puerto Rico Telephone Company provides local phone service. In addition to phones, a system of call boxes and speakers is provided in vocational and academic buildings allowing two way communications and announcements. The main fire alarm control panel is located in Building 11, and a remote annunciator panel is located in Building 3.

Puerto Rico Telephone Company

Maint. Responsibility

Center Center

Outside Security Cameras throughout the center and in New Dormitory

4,160V, 3-Phase, 3 Wire

120/208V, 3-Ph., 4 Wire & 120/240V, 1-Ph., 3 WireOverhead

OverheadPrimary Service

Secondary Service

Distribution Characteristics

Number of Deficiencies = 5

9. Electrical (Communication/Alarm/Security)

7. Electrical (Service)

No

Central/Stand-Alone

VOIP

System Capacity Adequate System Condition

GoodYes

Transformer Maint Resp

Center

System Capacity Adequate System Condition

Yes Good

Generator

Diesel

8. Electrical (Site Lighting)

Roadways Parking Walkways Building Outdoor Sports

Mounting

Control

Pole Pole Pole Building Pole

Photocell Photocell Photocell Photocell Switch

System Ownership Maintenance Responsibility System Capacity Adequate System Condition

Center Center Yes Good

ATS MTS

Yes Yes

Number of Deficiencies = 3

Number of Deficiencies = 9

Fire Alarm Security

Metering Master

Page: 4 Date: 06/07/2016 of 4

ACCESSIBILITY

Yes

UnknownUnknownNoNo

Nationally Registered Site

Site Eligible for National Register

Located in Historic District

Archaeological Significance

07/01/2003

12/01/2002

12/01/2002

Center

Private

Private

Active

Active

Active

Aboveground

Aboveground

Aboveground

Behind Structure 30

Behind Building 29

Behind Building 13

Propane is used for dryers in Building 29.

Yes

Yes

Yes

Petroleum - Heating Oil

Propane

Propane

STORAGE TANKS

Comments:

TypeStatus Location Owner Fuel Type Capacity (Gallons) Install Date

Earthquake Risk

High High MediumLow LowIBC High

LightningEarthquake Def. Authority Flooding Tornado Hurricane Forest

Fire

ID

Reg.

Number of Deficiencies = 5

Accessible Parking: Accessible Slope:

Yes

Curb Cuts:

Yes

Ramps:

YesYes

Site Accessible Route:

GENERAL SITE CONDITION

Rating X

Good Fair Poor

The lower campus is prone to flooding. There are frequent power outages.

HISTORIC PRESERVATION

NATURAL HAZARDS

The site condition is not impacting the functional use of the facilities.

The site condition IS impacting the functional use of the facilities.

The site condition IS SIGNIFICANTLY impacting the functional use of the facilities.

Generator

Other

Cooking

Purpose

Active Energy Use Reduction Program

Active Water Use Reduction Program

Approximate or Measured Waste Recycled

Use of School Dude or CMMS for Preventative Maintenance

Green Purchasing Policy Practiced

Site Stormwater Absorption Measures in Place

Center has Onsite Renewable Energy (PV or Wind)

Center has a Chartered Green Committee & Roster

Center Uses Green Cleaning Practices

SUSTAINABILITY

Comments: Center is in the process of installing a Solar PV system on the gymnasium.

NO

Yes

NO

NO

Yes

NO

Yes

Yes

35 %

Building Descriptions and Structures

BUILDING 1 - DISPENSARY

Building Descriptions

Page: 1 of 99

Building: 0001 - DISPENSARY

BUILDING ENVELOPE

Foundation RoofBuilding

Concrete Structural Steel Steel

CMU with Plaster Finish Ornamental CMU

Wall Roof None None

AccessibilityFeature

GSF NSF Year Built Use Group Historic Ownership #Floors

B 1,740 1,128 1 Owned 1989 Not Evaluated

REAL ESTATE

Access to Building

Ramps

Entrance

2nd Egress

Visual Alarm

Corridor/Aisle

Rooms

Stairs

Elevator

Restrooms

Drinking Fountain

Telephone

Yes

Yes

Yes

No

N/A

No

No

N/A

N/A

No

N/A

N/A

ACCESSIBILITY

Structural Systems1.

Exterior Walls2.

Insulation4.

Material

Galvalum, a galvanized aluminum alloy, has a life expectancy of approximately 20 years.

Drainage Year Life

Type Area Served

Galvalum

Built-up Roofing

Clay Tile

Surface Run-off

Surface Run-off

Surface Run-off

Gable

Flat

Shed

Front Part of the Building

Ward Area

Porch

Comments:

3. Roof

Entire Building

Area Served

Page: 2 of 99

Building: 0001 - DISPENSARY

Comments: The casement windows have jalousie side-lights.

INTERIOR FINISH

Ceramic Tile Vinyl Tile

Ceramic Tile Plaster

Metal Unit - Metal Frame Wood Unit - Wood Frame

Mechanical Toilet/Shower

Ventilation Area Served

VERTICAL CIRCULATION

Ramp

Glass Entrance - Vinyl-Clad Metal Frame Metal Unit - Metal Frame

Casement - Vinyl-Clad Metal Frame; Single Glazing; Jal - Aluminum Frame; None Glazing;

Jal - Aluminum Frame; Single Glazing; Sliding - Vinyl-Clad Metal Frame; Single Glazing;

Acoustical Tile Plaster

Exhaust Ventilation

Exterior Doors5.

Windows6.

Floors1.

Interior Walls2.

3.

Interior Doors4.

Heat Source

Heat Distribution

Piping System

Control System

Fresh Air Intake

Energy Conservation

Measure

Area Served

HVAC

Heat1.

None None None None Natural None None

Ventilation2.

Ceilings

Page: 3 of 99

Building: 0001 - DISPENSARY

Domestic water is heated by a Bradford-White model M230L6DS 30-gallon, 4.5 kW electric water heater on an outdoor pad.

Comments:

PVC None None

Hose Bibb Lavatory Shower Sink Water Closet (Tank)

None

None None ABC Type Fire Extinguisher

None Copper Electric None No

Hot Water Cold Water Water Heater Water Treatment HW Storage Tank

Grease InterceptorWaste / Vent Interior Storm

Split Direct Expansion (Air

Source)

Packaged Direct

Expansion (Air Source)

Fan Coil

Window Unit

Refrigerant

None

Electric

Electric

Natural

Mechanical

None

None

Common Area

Offices

Sprinkler System Stand Pipe System Fire Suppression

PLUMBING

The waiting room is served by a Panasonic model CU-E18EKU split ductless system.

The offices, wards and isolation rooms are served by eight window units.

Comments:

Comments:

System Type

Air Distribution

Piping System

Control System

Fresh Air Intake

Energy Conservation Area

Served

Water Distribution1.

Sanitary Distribution2.

Fixtures3.

Fuel Distribution4.

FIRE PROTECTION

3. Number of Deficiencies = 1Air Conditioning

Page: 4 of 99

Building: 0001 - DISPENSARY

Comments: Service is brought to the building from three 50 kVA pole-mounted transformer outside Cafeteria Building13. Service terminates in a 200A MLO loadcenter located in the exam office.

FIRE ALARM

Comments: The fire alarm system devices are connected to the main fire alarm control/annunciator panel (FACP) located in Administration Building 11.

Comments: This building is connected to the center LAN system.

Service Entrance Electrical Characteristics Distribution Equipment Wiring Devices

Exterior Audio/Visual Alarm Manual Pull Station Smoke Detector

Connected to Main System None None None

Telephone Security Public Address Television

Comments: Recorded footcandle levels include natural light contribution.

High Intensity Discharge (HID) Comments: Exterior building-mounted and surrounding area pole-mounted light fixtures are controlled by time clock and photocells.

T8 - Fluorescent

T8 - Fluorescent

T8 - Fluorescent

T8 - Fluorescent

T8 - Fluorescent

Compact Fluorescent

T8 - Fluorescent

T8 - Fluorescent

Offices

Corridors & Stairs

Reception

Toilets

Storage Rooms

Shower

Medical/Dental

Wards (Patient)

Area Recommended Recorded Light Type

Battery Backup Battery Backup

Main Panelboard 120/240V, 1-Phase, 3 Wire Service Equipment Only Receptacles, GFCI, Switches

Emergency Exit

ELECTRICAL SERVICES

Exterior Lighting1.

Interior Lighting2. Number of Deficiencies = 1

Emergency /Exit Lighting3.

COMMUNICATION

Type Location N/A N/A

The building does not contain fuel using equipment, with carbon monoxide (CO) as a by-product.

CARBON MONOXIDE DETECTION

LIGHTING

Detection Required No

Number of Deficiencies = 0

Page: 5 of 99

Building: 0001 - DISPENSARY

GENERAL BUILDING CONDITION

Rating

Comments:

X

Good Fair Poor

The interior is poorly configured for the current use and is non-compliant with applicable codes. The window air conditioners are inappropriate for offices requiring private conversations.

The facility condition is not impacting the functional use of the facility.

The facility condition IS impacting the functional use of the facility.

The facility condition IS SIGNIFICANTLY impacting the functional use of the facility.

Electric Water Gas No N/ANo

BUILDING UTILITY METERING

Structure: Fair Exterior: Fair Interior: Poor Mechanical: Poor Electrical: Fair

This building has been recommended for demolition in the Long Range Development Plan.

DEMOLITION RECOMMENDATION

IMPAIRMENT

Potentially Impaired

DOL Responded

DOL Determination

Potential Impaired Comments DOL Determination Discussion/Comments

BUILDING 3 - SECURITY/COVERED PARKING

Page: 6 of 99

Building: 0003 - SECURITY/COVERED PARKING

BUILDING ENVELOPE

Foundation RoofBuilding

Concrete Concrete Steel

CMU with plaster finish Ornamental CMU

Wall Roof None None

AccessibilityFeature

GSF NSF Year Built Use Group Historic Ownership #Floors

B 1,200 683 1 Leased 1968 Not Evaluated

REAL ESTATE

Access to Building

Ramps

Entrance

2nd Egress

Visual Alarm

Corridor/Aisle

Rooms

Stairs

Elevator

Restrooms

Drinking Fountain

Telephone

Yes

No

No

N/A

N/A

No

No

Yes

N/A

No

No

N/A

ACCESSIBILITY

Structural Systems1.

Exterior Walls2. Number of Deficiencies = 1

Insulation4.

Material Drainage Year Life

Type Area Served

Metal

Clay Tile

Surface Run-off

Surface Run-off

Flat

Gable

Entire Building

Entrance and Porch

3. Roof

Page: 7 of 99

Building: 0003 - SECURITY/COVERED PARKING

INTERIOR FINISH

Ceramic Tile Concrete

Exposed Structure Plaster

Wood Unit - Metal Frame Wood Unit - Wood Frame

Mechanical Restroom

Ventilation Area Served

VERTICAL CIRCULATION

Concrete Exterior Stairs

Metal Unit - Metal Frame

Fixed - Vinyl-Clad Metal Frame; Single Glazing; Jal - Vinyl-Clad Metal Frame; Single Glazing;

Acoustical Tile Exposed Structure

Exhaust Ventilation

Exterior Doors5.

Windows6.

Floors1.

Interior Walls2.

3.

Interior Doors4.

Heat Source

Heat Distribution

Piping System

Control System

Fresh Air Intake

Energy Conservation

Measure

Area Served

HVAC

Heat1.

None None None None Natural None None

Page: 8 of 99

Building: 0003 - SECURITY/COVERED PARKING

None None None

Lavatory Portable Bottled Water Cooler Shower Water Closet (Tank)

None

None None ABC Type Fire Extinguisher

None Copper None None No

Hot Water Cold Water Water Heater Water Treatment HW Storage Tank

Grease InterceptorWaste / Vent Interior Storm

Packaged Direct

Expansion (Air Cooled)

Through-The- Wall Unit

None Electric Mechanical None Offices

Sprinkler System Stand Pipe System Fire Suppression

PLUMBING

The three offices are served by these three units.Comments:

System Type

Air Distribution

Piping System

Control System

Fresh Air Intake

Energy Conservation Area

Served

Water Distribution1.

Sanitary Distribution2.

Fixtures3.

Fuel Distribution4.

3. Air Conditioning

Page: 9 of 99

Building: 0003 - SECURITY/COVERED PARKING

Comments: Service is brought to the building from a power pole outside and terminates in the 200A main-lug-only (MLO) weatherproof panel. The panel has 12 breakers, and is located under the covered parking structure. The panel serves a 100A MLO loadcenter located in the security office. The service is backed up by a 130 kW generator located in Emergency Generator Structure 30. The two electric gate operators at the center entrance are remotely controlled from this building.

FIRE ALARM

Comments: A Simplex remote annunciator panel with very limited zone status indication capability is connected to the main fire alarm control/annunciator panel located in Administration Building 11.

Comments: This building is connected to the center LAN system. Two motor-operated center entrance gates are located adjacent to and controlled from this building. Exterior speaker is located at the covered parking roof eave. Call box is not provided in the building.

Service Entrance Electrical Characteristics Distribution Equipment Wiring Devices

Remote Annunciator Panel

Connected to Main System None Connected to Main System TV with VCR

Telephone Security Public Address Television

Comments: Recorded footcandle levels include natural light contribution.

Fluorescent High Intensity Discharge (HID) Incandescent Comments: Exterior building-mounted and surrounding area pole-mounted light fixtures are controlled by time clock and photocells. Additionally, there is a 1000W HID flood light mounted on the roof to illuminates the center entrance.

T8 - Fluorescent

T8 - Fluorescent

T8 - Fluorescent

Offices

Toilets

Storage Rooms

Area Recommended Recorded Light Type

Battery Backup Battery Backup

Main Panelboard 120/240V, 1-Phase, 3 Wire Loadcenter Receptacles, Switches

Emergency Exit

ELECTRICAL SERVICES Number of Deficiencies = 1

Exterior Lighting1.

Interior Lighting2. Number of Deficiencies = 1

Emergency /Exit Lighting3.

COMMUNICATION

Type Location N/A N/A

The building does not contain fuel using equipment, with carbon monoxide (CO) as a by-product.

CARBON MONOXIDE DETECTION

LIGHTING

Detection Required

Page: 10 of 99

Building: 0003 - SECURITY/COVERED PARKING

GENERAL BUILDING CONDITION

Rating X Good

Fair Poor

The facility condition is not impacting the functional use of the facility.

The facility condition IS impacting the functional use of the facility.

The facility condition IS SIGNIFICANTLY impacting the functional use of the facility.

Electric Water Gas No N/ANo

BUILDING UTILITY METERING

Structure: Good Exterior: Good Interior: Fair Mechanical: Good Electrical: Good

IMPAIRMENT

Potentially Impaired

DOL Responded

BUILDING 4 - FM&C/RETAIL/CPP

Page: 11 of 99

Building: 0004 - FM&C/RETAIL/CPP

BUILDING ENVELOPE

Foundation RoofBuilding

Concrete Loadbearing Masonry Steel

Metal Grates Ornamental CMU Stucco

AccessibilityFeature

GSF NSF Year Built Use Group Historic Ownership #Floors

B 5,480 4,695 1 Leased 1968 Not Evaluated

Comments: Visual alarm device is not provided in the men's and women's rooms.

REAL ESTATE

Access to Building

Ramps

Entrance

2nd Egress

Visual Alarm

Corridor/Aisle

Rooms

Stairs

Elevator

Restrooms

Drinking Fountain

Telephone

Yes

Yes

Yes

Yes

Yes

Yes

Yes

Yes

N/A

No

No

N/A

ACCESSIBILITY

Structural Systems1.

Exterior Walls2.

Material

Galvalum, a galvanized aluminum alloy, has a life expectancy of approximately 20 years. The structural steel portion of this building has low slope galvalun roof.

The concrete frame portion of the building has a flat concrete deck which was sealed in 2005.

Drainage Year Life

Type Area Served

Galvalum

Concrete

Metal

Clay Tile

Surface Run-off

Surface Run-off

Gutters and Downspouts

Surface Run-off

Flat

Flat

Shed

Shed

Classrooms & Storage

Outside Toilet

Entrance Canopy

Window Overhang

Comments:

Comments:

3. Roof

Page: 12 of 99

Building: 0004 - FM&C/RETAIL/CPP

Wall Roof None None

INTERIOR FINISH

Ceramic Tile Concrete

Ceramic Tile Drywall Plaster Wood

Metal Rollup - Metal Frame Metal Unit - Metal Frame

Wood Unit - Wood Frame

VERTICAL CIRCULATION

Concrete Stairs Ramp Comments: Concrete stairs and a ramp are from ground to the entrance.

Metal Grate - Metal Frame Metal Rollup - Metal Frame Metal Unit - Metal Frame Wood Unit - Wood Frame

Fixed - Aluminum Frame; Wireglass Glazing; Fixed - Vinyl-Clad Metal Frame; Single Glazing;

Fixed - Wood Frame; Wireglass Glazing; Jal - Aluminum Frame; None Glazing;

Jal - Vinyl-Clad Metal Frame; Single Glazing;

Acoustical Tile Concrete Plaster Plywood

Insulation4.

Exterior Doors5.

Windows6.

Floors1.

Interior Walls2.

3.

Interior Doors4. Number of Deficiencies = 1

Heat Source

Heat Distribution

Piping System

Control System

Fresh Air Intake

Energy Conservation

Measure

Area Served

HVAC

Heat1.

None None None None Natural None Entire Building

Page: 13 of 99

Building: 0004 - FM&C/RETAIL/CPP

Mechanical

Mechanical

Natural

Restroom

Paint Booth

Shop Area

Comments:

Comments:

The paint booth is no longer used.

The outside perimeter walls of the facility maintenance shop are steel fences, putting it outdoors.

PVC None None

Fixed Emergency Eyewash Hose Bibb Lavatory Portable Bottled Water Cooler Shower Urinal Water Closet (Tank)

None

Ventilation Area Served

None Copper None None No

Hot Water Cold Water Water Heater Water Treatment HW Storage Tank

Grease InterceptorWaste / Vent Interior Storm

Split Direct Expansion (Air

Cooled)

Packaged Direct

Expansion (Air Cooled)

Fan Coil

Window Unit

Refrigerant

None

Electric

Electric

Natural

Mechanical

None

None

Classrooms

Classrooms and Offices

PLUMBING

Exhaust Ventilation

There are two split ductless systems serving the retail sales areas. One is a York system, the other is a TGM indoor unit with a Mitisubishi condensing unit.

Comments:

Ventilation2.

System Type

Air Distribution

Piping System

Control System

Fresh Air Intake

Energy Conservation Area

Served

Water Distribution1.

Sanitary Distribution2.

Fixtures3.

Fuel Distribution4.

Page: 14 of 99

Building: 0004 - FM&C/RETAIL/CPP

None None ABC Type Fire Extinguisher, Dry Chemical

Comments: The dry fire suppression system serves the spray booth (not in use) area.

Comments: Service is brought from a power pole outside and terminates in the main distribution panel (MDP) with a 300A main circuit breaker (MCB) located on the building exterior wall. The MDP feeds one 100A panel, one 150A panel and two 200A panels which serve the facility maintenance and retail sales vocations.

FIRE ALARM

Comments: The fire alarm system devices are connected to the main fire alarm control/annunciator panel located in Administration Building 11.

Service Entrance Electrical Characteristics Distribution Equipment Wiring Devices

Audible Alarm Heat Detector Manual Pull Station Smoke Detector Visual Alarm

Comments: Recorded footcandle levels include natural light contribution.

Compact Fluorescent High Intensity Discharge (HID) Comments: Most building exterior light fixtures are photocell controlled, while others are switch controlled.

T8 - Fluorescent

T8 - Fluorescent

T8 - Fluorescent

T8 - Fluorescent

T8 - Fluorescent

Offices

Toilets

Storage Rooms

Classrooms

Vocational

Area Recommended Recorded Light Type

Battery Backup Battery Backup

Main Distribution Panel 120/240V, 1-Phase, 3 Wire Panelboards, Loadcenters Receptacles, GFCI, Switches

Sprinkler System Stand Pipe System Fire Suppression

Emergency Exit

Number of Deficiencies = 1

FIRE PROTECTION

ELECTRICAL SERVICES

Exterior Lighting1.

Interior Lighting2.

Emergency /Exit Lighting3.

Type Location N/A N/A

The building does not contain fuel using equipment, with carbon monoxide (CO) as a by-product.

CARBON MONOXIDE DETECTION

LIGHTING

Detection Required

Page: 15 of 99

Building: 0004 - FM&C/RETAIL/CPP

Comments: This building is connected to the center LAN system. Call boxes and speakers are provided for announcements. Closed circuit TV (CCTV) cameras are locally monitored from a color monitor located in the retail sales classroom. Additionally a metal detector is installed at the retail sales entrance.

Connected to Main System CCTV, Color Monitor, Metal Det

Connected to Main System TV with VCR

Telephone Security Public Address Television

GENERAL BUILDING CONDITION

Rating X Good

Fair Poor

COMMUNICATION

The facility condition is not impacting the functional use of the facility.

The facility condition IS impacting the functional use of the facility.

The facility condition IS SIGNIFICANTLY impacting the functional use of the facility.

Electric Water Gas No N/ANo

BUILDING UTILITY METERING

Structure: Good Exterior: Good Interior: Good Mechanical: Good Electrical: Good

IMPAIRMENT

Potentially Impaired

DOL Responded

BUILDING 5 - CDSS

Page: 16 of 99

Building: 0005 - CDSS

BUILDING ENVELOPE

Foundation RoofBuilding

Concrete Loadbearing Masonry Concrete

CMU with Plaster Finish

Wall Roof None None

Glass Entrance - Metal Frame Wood Unit - Metal Frame Wood Unit - Wood Frame

AccessibilityFeature

GSF NSF Year Built Use Group Historic Ownership #Floors

B 1,000 754 1 Owned 1995 Not Evaluated

REAL ESTATE

Access to Building

Ramps

Entrance

2nd Egress

Visual Alarm

Corridor/Aisle

Rooms

Stairs

Elevator

Restrooms

Drinking Fountain

Telephone

No

No

No

No

Yes

No

Yes

Yes

N/A

No

No

N/A

ACCESSIBILITY

Structural Systems1.

Exterior Walls2.

Insulation4.

Exterior Doors5.

Material

The flat concrete roof deck was sealed in 2003.

Drainage Year Life

Type Area Served

Concrete Surface Run-off 1995 8 Flat Entire Building

Comments:

3. Roof

Page: 17 of 99

Building: 0005 - CDSS

Comments: The jalousie windows have clear plastic over the openings.

INTERIOR FINISH

Ceramic Tile

Ceramic Tile Plaster Wood Paneling

Wood Unit - Wood Frame

Mechanical Restroom

Ventilation Area Served

VERTICAL CIRCULATION

Concrete Exterior Stairs

Jal - Aluminum Frame; Single Glazing;

Plaster

Exhaust Ventilation

Windows6.

Floors1.

Interior Walls2.

3.

Interior Doors4.

Heat Source

Heat Distribution

Piping System

Control System

Fresh Air Intake

Energy Conservation

Measure

Area Served

HVAC

Heat1.

None None None None Natural None Entire Building

Page: 18 of 99

Building: 0005 - CDSS

PVC None None

Hose Bibb Lavatory Portable Bottled Water Cooler Shower/Bathtub Water Closet (Tank)

None

None None ABC Type Fire Extinguisher

None Copper None None No

Hot Water Cold Water Water Heater Water Treatment HW Storage Tank

Grease InterceptorWaste / Vent Interior Storm

Packaged Direct

Expansion (Air Cooled)

Window Unit None Electric Mechanical None Entire Building

Sprinkler System Stand Pipe System Fire Suppression

PLUMBING

System Type

Air Distribution

Piping System

Control System

Fresh Air Intake

Energy Conservation Area

Served

Water Distribution1.

Sanitary Distribution2.

Fixtures3.

Fuel Distribution4.

Page: 19 of 99

Building: 0005 - CDSS

Comments: Service is brought from a power pole outside and terminates in a 100 MCB panel located in the corridor.

Additionally, an overhead tap from the same service drop provides power to a disconnect switch located in CTST storage Structure 8.

FIRE ALARM

Comments: The fire alarm system devices are connected to the main fire alarm control/annunciator panel located in Administrative Building 11.

Comments: This building is connected to the center LAN system.

Service Entrance Electrical Characteristics Distribution Equipment Wiring Devices

Audible Alarm Manual Pull Station Smoke Detector Visual Alarm

Connected to Main System None None TV with VCR

Telephone Security Public Address Television

Comments: Recorded footcandle levels include natural light contribution.

Compact Fluorescent High Intensity Discharge (HID) Comments: Exterior building-mounted and surrounding area pole-mounted light fixtures are controlled by time clock and photocells.

T8 - Fluorescent

T8 - Fluorescent

T8 - Fluorescent

Compact Fluorescent

Offices

Corridors & Stairs

Reception

Toilets

Area Recommended Recorded Light Type

None Battery Backup

Main Panelboard 120/240V, 1-Phase, 3 Wire Service Equipment Only Receptacles, GFCI, Switches

Emergency Exit

ELECTRICAL SERVICES

Exterior Lighting1.

Interior Lighting2. Number of Deficiencies = 1

Emergency /Exit Lighting3.

COMMUNICATION

Electric Water Gas No N/ANo

BUILDING UTILITY METERING

Type Location N/A N/A

The building does not contain fuel using equipment, with carbon monoxide (CO) as a by-product.

CARBON MONOXIDE DETECTION

LIGHTING

Detection Required

Page: 20 of 99

Building: 0005 - CDSS

GENERAL BUILDING CONDITION

Rating X Good

Fair Poor

The facility condition is not impacting the functional use of the facility.

The facility condition IS impacting the functional use of the facility.

The facility condition IS SIGNIFICANTLY impacting the functional use of the facility.

Structure: Good Exterior: Good Interior: Good Mechanical: Good Electrical: Good

IMPAIRMENT

Potentially Impaired

DOL Responded

BUILDING 6 - EDUCATION

Page: 21 of 99

Building: 0006 - EDUCATION

BUILDING ENVELOPE

Foundation RoofBuilding

Concrete Structural Steel Steel

EIFS

Wall Roof None None

Metal Unit - None Frame Steel Bars - Steel Frame

AccessibilityFeature

GSF NSF Year Built Use Group Historic Ownership #Floors

B 1,650 1,401 1 Leased 1968 Not Evaluated

REAL ESTATE

Access to Building

Ramps

Entrance

2nd Egress

Visual Alarm

Corridor/Aisle

Rooms

Stairs

Elevator

Restrooms

Drinking Fountain

Telephone

Yes

N/A

Yes

Yes

Yes

N/A

Yes

N/A

N/A

No

No

N/A

ACCESSIBILITY

Structural Systems1.

Exterior Walls2.

Insulation4.

Exterior Doors5.

Material

Asbestos: Yes

Drainage Year Life

Type Area Served

Metal Gutters and Downspouts 2005 20 Gable Entire Building

3. Roof

Page: 22 of 99

Building: 0006 - EDUCATION

Comments: Fixed windows are interior windows.

INTERIOR FINISH

Ceramic Tile

Drywall Fiber Reinforced Paneling

Wood Unit - Wood Frame

Mechanical Restroom

Ventilation Area Served

VERTICAL CIRCULATION

None

Fixed - None Frame; Wireglass Glazing; Jal - Aluminum Frame; None Glazing;

Steel Bars - None Frame; None Glazing;

Acoustical Tile

Exhaust Ventilation

Windows6.

Floors1.

Interior Walls2.

3.

Interior Doors4.

Heat Source

Heat Distribution

Piping System

Control System

Fresh Air Intake

Energy Conservation

Measure

Area Served

HVAC

Heat1.

None None None None Natural None None

Page: 23 of 99

Building: 0006 - EDUCATION

PVC None None

Hose Bibb Lavatory Portable Bottled Water Cooler Water Closet (Tank)

None

None None ABC Type Fire Extinguisher

None Copper None None No

Hot Water Cold Water Water Heater Water Treatment HW Storage Tank

Grease InterceptorWaste / Vent Interior Storm

Split Direct Expansion (Air

Source)

Packaged Direct

Expansion (Air Cooled)

Fan Coil

Window Unit

Refrigerant

None

Electric

Electric

Natural

Mechanical

None

None

Classrooms

Classrooms and Offices

Sprinkler System Stand Pipe System Fire Suppression

PLUMBING

One classroom area is served by a Mitsubishi Mr. Slim split ductless system.Comments:

System Type

Air Distribution

Piping System

Control System

Fresh Air Intake

Energy Conservation Area

Served

Water Distribution1.

Sanitary Distribution2.

Fixtures3.

Fuel Distribution4.

Page: 24 of 99

Building: 0006 - EDUCATION

Comments: Service is brought from a power pole near Building 1, transit to underground and terminates in a 200A main fused disconnect switch located on the north exterior wall of Building 6. The switch in-turn serves two 100A MLO loadcenters located in the classrooms.

FIRE ALARM

Comments: The fire alarm system devices are connected to the main fire alarm control/annunciator panel located in Administrative Building 11.

Comments: This building is connected to the center LAN system. A small telecommunications closet houses server equipment for computer managed instruction (CMI).

Service Entrance Electrical Characteristics Distribution Equipment Wiring Devices

Manual Pull Station Smoke Detector

Connected to Main System None None TV with VCR

Telephone Security Public Address Television

Comments: Recorded footcandle levels include natural light contribution. The equipment room is a CMI server room partitioned off from an existing classroom.

High Intensity Discharge (HID) Comments: Exterior building-mounted light fixtures are controlled by timeclock and photocell.

T8 - Fluorescent

Incandescent

T8 - Fluorescent

Equipment Rooms (Elec/Mech)

Toilets

Classrooms

Area Recommended Recorded Light Type

Battery Backup Battery Backup

Main Disconnect Switch 120/240V, 1-Phase, 3 Wire Loadcenter Receptacles, Switches

Emergency Exit

ELECTRICAL SERVICES

Exterior Lighting1.

Interior Lighting2. Number of Deficiencies = 1

Emergency /Exit Lighting3. Number of Deficiencies = 1

COMMUNICATION

Electric Water Gas No N/ANo

BUILDING UTILITY METERING

Type Location N/A N/A

The building does not contain fuel using equipment, with carbon monoxide (CO) as a by-product.

CARBON MONOXIDE DETECTION

LIGHTING

Detection Required

Page: 25 of 99

Building: 0006 - EDUCATION

GENERAL BUILDING CONDITION

Rating X Good

Fair Poor

The facility condition is not impacting the functional use of the facility.

The facility condition IS impacting the functional use of the facility.

The facility condition IS SIGNIFICANTLY impacting the functional use of the facility.

Structure: Good Exterior: Good Interior: Good Mechanical: Good Electrical: Good

IMPAIRMENT

Potentially Impaired

DOL Responded

BUILDING 9 - RECREATION

Page: 26 of 99

Building: 0009 - RECREATION

BUILDING ENVELOPE

Foundation RoofBuilding

Concrete Structural Steel Steel, Wood

A second floor covered deck has a wooden roof frame.

CMU with Ceramic Tile CMU with Plaster Finish

Wall Roof None Batt

AccessibilityFeature

GSF NSF Year Built Use Group Historic Ownership #Floors

A-3,B,S-1 3,900 3,112 2 Owned 1988 Not Evaluated

Comments: The maintenance department, which is on the second floor is not accessible.

REAL ESTATE

Access to Building

Ramps

Entrance

2nd Egress

Visual Alarm

Corridor/Aisle

Rooms

Stairs

Elevator

Restrooms

Drinking Fountain

Telephone

Yes

No

Yes

No

Yes

Yes

No

No

No

No

No

N/A

ACCESSIBILITY

Structural Systems1.

Exterior Walls2.

Insulation4.

Material

Galvalum, a galvanized aluminum alloy, has a life expectancy of approximately 20 years.

The estimated remaining roof life is based on visual observation during the December 2012 Facility Survey.

Drainage Year Life

Type Area Served

Galvalum

Metal

Surface Run-off

Surface Run-off

Gable

Shed

Entire Building

Maintenance Deck

Comments:

Comments:

3. Roof

Entire Building

Comments:

Page: 27 of 99

Building: 0009 - RECREATION

INTERIOR FINISH

Ceramic Tile Concrete Terrazzo

Ceramic Tile Plaster Wood Paneling

Metal Unit - Metal Frame Wood Unit - Wood Frame

Mechanical Toilet/Shower

Ventilation Area Served

VERTICAL CIRCULATION

Concrete Stairs Comments: Exterior stairs access the maintenance shop.

Metal Unit - Metal Frame Wood Unit - Wood Frame

Jal - Aluminum Frame; None Glazing; Steel Bars - None Frame; None Glazing;

Acoustical Tile Exposed Structure

Exhaust Ventilation

Exterior Doors5. Number of Deficiencies = 1

Windows6.

Floors1.

Interior Walls2.

3.

Interior Doors4.

Heat Source

Heat Distribution

Piping System

Control System

Fresh Air Intake

Energy Conservation

Measure

Area Served

HVAC

Heat1.

None None None None Natural None Entire Building

Page: 28 of 99

Building: 0009 - RECREATION

The electric water heater (Bradford White model MI40L6DS13, 9 kW, 40 gallon) serves only the maintenance supervisor's toilet and shower room on the second floor.

Comments:

PVC None None

Electric Water Cooler Hose Bibb Lavatory Portable Bottled Water Cooler Shower Sink Water Closet (Tank)

None

None None ABC Type Fire Extinguisher

Copper Copper Electric None No

Hot Water Cold Water Water Heater Water Treatment HW Storage Tank

Grease InterceptorWaste / Vent Interior Storm

Split Direct Expansion (Air

Source)

Packaged Direct

Expansion (Air Cooled)

Split Direct Expansion (Air

Cooled)

Fan Coil

Window Unit

Single Duct

Refrigerant

None

Refrigerant

Electric

Electric

Electric

Natural

Mechanical

Mechanical

None

None

None

Offices

Offices

Recreation Area

Sprinkler System Stand Pipe System Fire Suppression

PLUMBING

A Goodman model CKH301L (2-1/2 tons) split system provides cooling to the second floor maintenance office.

Five split systems (One Goodman model CKX60-1B 5 ton system and four Misubishi Citi-Muiti ceiling casettes served by two four ton outdoor air cooled condensing units) serve the first floor recreation hall.

Comments:

Comments:

System Type

Air Distribution

Piping System

Control System

Fresh Air Intake

Energy Conservation Area

Served

Water Distribution1.

Sanitary Distribution2.

Fixtures3.

Fuel Distribution4.

Page: 29 of 99

Building: 0009 - RECREATION

Comments: This building has two services. One service is brought from a power pole outside and terminates in an enclosed 225A main circuit breaker (MCB) which serves a 125A main-lug-only (MLO) loadcenter. Both the breaker and loadcenter are located in the recreation hall. The second service is brought from a 200A disconnect switch mounted on the exterior wall of Building 12 and terminates in a 100A MCB loadcenter located in the maintenance office on the second floor.

FIRE ALARM

Comments: The fire alarm system devices are connected to the main fire alarm control/annunciator panel located in Administrative Building 11.

Service Entrance Electrical Characteristics Distribution Equipment Wiring Devices

Audible Alarm Heat Detector Manual Pull Station Smoke Detector Visual Alarm

Comments: Recorded footcandle levels include natural light contribution.

LED

Comments: Exterior building-mounted and surrounding area pole-mounted light fixtures are controlled by time clock and photocells.

T12 and T8 - Fluorescent

Compact Fluorescent

Compact Fluorescent

T8 - Fluorescent

T8 - Fluorescent

T12 - Fluorescent

Offices

Toilets

Storage Rooms

Study Room

Recreation

Maintenance Shop

Area Recommended Recorded Light Type

Battery Backup Battery Backup

Main Circuit Breaker 120/240V, 1-Phase, 3 Wire Loadcenters Receptacles, GFCI, Switches

Emergency Exit

ELECTRICAL SERVICES Number of Deficiencies = 1

Exterior Lighting1.

Interior Lighting2.

Emergency /Exit Lighting3.

Type Location N/A N/A

The building does not contain fuel using equipment, with carbon monoxide (CO) as a by-product.

CARBON MONOXIDE DETECTION

LIGHTING

Detection Required

Page: 30 of 99

Building: 0009 - RECREATION

Comments: This building is connected to the center LAN system. A local sound system is provided in the recreation area.

Connected to Main System None None Local Cable Company

Telephone Security Public Address Television

GENERAL BUILDING CONDITION

Rating X Good