This document is a Facility Planning Report Supporting Data Volume II for the Carville Job Corps Center in Louisiana, completed in June 2022. The report provides comprehensive facility survey information including site layout, building descriptions, space utilization analysis, environmental management status, and identified deficiencies across the center's infrastructure.
The Carville Job Corps Center occupies approximately 116,346 gross square feet across nine buildings and six structures situated on a campus in Carville, Louisiana. Key facilities include a vocational education/maintenance building (12,700 GSF), education/light vocation building (13,877 GSF), recreation/gymnasium (20,034 GSF), cafeteria (10,212 GSF), administration/medical-dental building (12,095 GSF), dormitory with 200-bed capacity serving 153 students (37,926 GSF), receiving building (2,000 GSF), vocational building (7,442 GSF), and guard house (60 GSF), plus storage structures and gazebos. The dormitory accommodates 77 males and 76 females across four wings with 52 rooms. Utility systems include municipal water service, gravity-fed sanitary sewage treatment through the adjacent Gillis W. Long Center, underground electrical service from Entergy Gulf States Louisiana with backup diesel generators (600 kW serving Buildings 4 and 6; 300 kW serving Building 5), natural gas service from Atmos Energy, and a fiber optic communication network managed by JCDC. The survey identifies multiple deficiencies including deteriorated asphalt roofing requiring replacement on five buildings, ground moisture migration causing floor finish deterioration in several facilities, inadequate storm water drainage with debris-filled swales, and malfunctioning HVAC controls in multiple buildings. All facilities maintain addressable fire alarm systems connected to a central annunciator panel, sprinkler systems, and security infrastructure including CCTV monitoring and access card readers throughout the center.
View the file
Other files
Show all 12
On GovTribe
Work with this file
- Download the original file
- Contacts named in this file
- Similar government files
- Ask GovTribe AI about this file
Text version
CARVILLE
Job Corps Center Carville, LA
Facility Planning Report Supporting Data
Volume II
Final June 2022
CARVILLE JOB CORPS CENTER
PY2021 FACILITY SURVEY REPORT
VOLUME II – TABLE OF CONTENTS
1.0 EXECUTIVE SUMMARY
2.0 SITE LAYOUT AND PLANS
Location Map
Existing Site Plan
3.0 DESCRIPTIONS
Buildings and Structures
Space Utilization by function
NSF by Building
Environmental Management Report
Radon Report
Site Description
Building Descriptions and Structures, Floor Plans
4.0 DEFICIENCIES
APPENDICES – CORRESPONDENCE AND REPORTS
APPENDIX A
Survey Brief ............................................................................................................................... A-1
APPENDIX B
Life Safety Deficiencies and List ................................................................................................ B-1
APPENDIX C
O&M Deficiencies List ............................................................................................................... C-1 i
Dorm Bed Capacity
Page Intentionally Left Blank ii
1.0 EXECUTIVE SUMMARY
1.0 EXECUTIVE
SUMMARY
• Existing site layout
• Overall status of existing building and structures
• Space utilization by building and function compared to recommended standards
• Status of environmental elements of the Center’s operations
• Details on the site and buildings and structures based on architectural, electrical, and mechanical survey and supporting documentation
• Presentation of the status of historical deficiencies and compilation of deficiencies documented through this survey
• Supporting documentation, as presented in the appendices of the center review meeting; survey brief and student questionnaire; life safety IA/IIA transmittal; and active warranties
Section 1.0 of this volume addresses site layout and plans while Section 2.0 presents details on the buildings and structures. Section 3.0 presents deficiencies and their status as well as new ones identified in this survey. The appendices provide additional information as noted below:
• Appendix A. Survey Brief Questionnaire
• Appendix B. Life Safety Deficiencies and List
• Appendix C. O&M Deficiencies List
EXECUTIVE SUMMARY
The Program Year 2021 facility survey for Carville Job Corps Center was completed the week of March 21, 2022. The information presented in Volume II - Supporting Data, represents the current status of the campus.
The information includes the following:
2.0 SITE LAYOUT AND PLANS
2.0 SITE LAYOUT
AND PLANS
x x x x x x x x
P o i n t
C l a i r
R o a d
Gillis W. Long Center
OAK TREES
ELEC.
TRANSFORMER
RESTORE SWALES
GOVT. VEHICLE
PARKING
B e t t y
M a r t i n
R o a d
Carville Job Corps Center
Carville, Louisiana
BUILDINGS
1 - VOCATIONAL EDUCATION/MAINTENANCE
2 - EDUCATION/LIGHT VOCATION
3 - RECREATION/GYMNASIUM
4 - CAFETERIA
5 - ADMINISTRATION/MED-DENTAL
6 - DORMITORY
7 - RECEIVING
8 - VOCATIONAL
9 - GUARD HOUSE
STRUCTURES
10 - GAZEBO
11 - GAZEBO
12 - GAZEBO
13 - STORAGE
14 - STORAGE
15 - HOME BUILDERS STORAGE
Existing Site Plan
400 Feet2001000
STORAGE
RECREATION
MEDICAL/DENTAL
EDUCATION
DORMITORY
CAFETERIA
ADMINISTRATION
FUNCTION LEGEND
VACANT
AS OF 05/13/2021 FROM
INVENTORY VALIDATION
AutoCAD SHX Text
VAN
AutoCAD SHX Text H
AutoCAD SHX Text H
AutoCAD SHX Text
VAN
AutoCAD SHX Text H
AutoCAD SHX Text H
AutoCAD SHX Text H
3.0 DESCRIPTIONS
3.0 DESCRIPTIONS
BUILDINGS AND STRUCTURES
00618 CARVILLE 06/27/2022
Page: 1 of Date:
0001 - VOCATIONAL
EDUCATION/MAINTENANCE
0002 - EDUCATION/LIGHT VOCATION
0003 - RECREATION/GYMNASIUM
0004 - CAFETERIA
0005 - ADMINISTRATION/MED-DENTAL
0006 - DORMITORY
0007 - RECEIVING
0008 - VOCATIONAL
0009 - GUARD HOUSE
0010 - GAZEBO (295Ft Diameter) 0011 - GAZEBO (295Ft Diameter) 0012 - GAZEBO (295Ft Diameter) 0013 - STORAGE (12Ft x 12Ft) 0014 - STORAGE (12Ft x 12Ft) 0015 - HOME BUILDERS STORAGE (12Ft x 20Ft)
Name GSF
12,700
13,877 20,034 10,212 12,095 37,926 2,000 7,442
Active
Active Active Active Active Active Active Active Active Active Active Active Active Active Active
StatusType
Building
Building Building Building Building Building Building Building Building Structure Structure Structure Structure Structure Structure
Use Group Built Flrs Const
Business
Business Assembly Assembly Business Residential Storage Business Business Residential Residential Residential Storage Storage Storage
Good
Good Good Good Good Fair
Good Good Good Good Good Good Good Good Good
ConditionAsset Number
0061808008
0061808009 0061808010 0061808011 0061808012 0061808013 0061808014 0061808015 0061808016 0061808017 0061808018 0061808019 0061808020 0061808021 0061808024
9 116,346
6 1,413
15 117,759
Buildings
Structures
Total
GSF
GSF
GSF
Summary
06/27/2022
Space Utilization By Function 00618 Carville Page: 1 of 3
HOUSING
EDUCATION
FOOD SERVICE
SUGGESTED
NSF/
ENROLLEE
SUGGESTED
TOTAL
NSF
ACTUAL
TOTAL
NSF
TYPE OF SPACE
SUB TOTAL
SUB TOTAL
SUB TOTAL
Resident Men Resident Women Total Residents
Date:
Residents Non Residents Total Students
(153)
(0)
(153)
DIFFERENCE
16,524
10,170
2,142
24,844
22,156
6,375
Lounge Other Shower/Toilet Sleeping excl. SPD(52 rooms; 200 beds) Storage
Academic (0) Non-Academic
24 -- API Field Operator Assistant + 15 -- Automotive Mechanic + 30 -- Computer Operations 12 -- Culinary Arts + 24 -- Facilities Maint. and Const. + 30 -- Health Occupations + 10 -- Medical Assistant 15 -- Welding +
Vocational Theory (120)
Dining (2 Servings) Food Preparation
5,000 2,628 4,168
12,728
2,674 5,602
2,894 4,485 1,009
3,399 1,334
1,875 4,500
1,530 1,224 1,836
11,016
1,800 1,125
1,800 1,200
1,125
1,200
1,224
3,470 1,404 2,332 1,712
-598
1,094 3,360
1,599
-441
3,582
Vocations
8,320
11,986
4,233
Page: 2 of Date:
RECREATION
MEDICAL/DENTAL
ADMINISTRATION
STORAGE/SUPPORT
SECURITY
VACANT
SUGGESTED
NSF/
ENROLLEE
SUGGESTED
TOTAL
NSF
ACTUAL
TOTAL
NSF
TYPE OF SPACE
SUB TOTAL
SUB TOTAL
SUB TOTAL
SUB TOTAL
SUB TOTAL
SUB TOTAL
TOTAL 290.92 44,510 81,696
(153)
(153)
(153)
(153)
(153)
(0)
DIFFERENCE
7,650
1,445
3,060
3,060
14,778
2,695
4,987
5,715
Activity Room Arts & Crafts Canteen Computer Lab Gymnasium Hair Salon Men's Exercise Room Recreation Office Recreation Storage Women's Exercise Room
Medical/Dental
Administration
Operations & Maintenance Warehouse
SECURITY
Vacant
9.44
2,054
8,297
1,164
2,695
4,987
3,325 2,390
1,445
3,060
1,224 1,836
1,250
1,927
2,101
-409
RESIDENT
NON-RESIDENT
(153)
(0) 15
50 7,650
7,128
1,250
1,927
2,655
-409
37,186
Page: 3 of Date:
SUGGESTED
NSF/
ENROLLEE
SUGGESTED
TOTAL
NSF
ACTUAL
TOTAL
NSF
TYPE OF SPACE DIFFERENCE
116,346
0.70
TOTAL GSF
NET TO GROSS RATIO
Net Square Footage By Building Page: 1 of 3
Date: 06/27/2022Center: CARVILLE (00618)
HOUSING
EDUCATION
Sleeping excl. SPD
Lounge
Storage
Shower/Toilet
Other
Academic
Vocational Theory (120)
Health Occupations
Facilities Maint. and Const.
Non-Academic
Automotive Mechanic
Computer Operations
API Field Operator Assistant
Function Suggested
NSF
12,728
5,000
4,168
2,628
1,432
1,334
3,399
2,428
4,485
1,009
2,894
0006 - DORMITORY
0006 - DORMITORY
0006 - DORMITORY
0006 - DORMITORY
0006 - DORMITORY
0002 - EDUCATION/LIGHT VOCATION
0002 - EDUCATION/LIGHT VOCATION
0002 - EDUCATION/LIGHT VOCATION
0001 - VOCATIONAL EDUCATION/MAINTENANCE
0008 - VOCATIONAL
0008 - VOCATIONAL
0008 - VOCATIONAL
0002 - EDUCATION/LIGHT VOCATION
0001 - VOCATIONAL EDUCATION/MAINTENANCE
0002 - EDUCATION/LIGHT VOCATION
0002 - EDUCATION/LIGHT VOCATION
0002 - EDUCATION/LIGHT VOCATION
0002 - EDUCATION/LIGHT VOCATION
0002 - EDUCATION/LIGHT VOCATION
0001 - VOCATIONAL EDUCATION/MAINTENANCE
0008 - VOCATIONAL
0001 - VOCATIONAL EDUCATION/MAINTENANCE
Bldg Name Actual NSF Difference
12,728
5,000
4,168
2,628
2,674
1,334
3,399
5,602
4,485
1,009
2,894
Sub Total:
Sub Total:
24,844
22,156
11,016
1,530
1,836
1,224
1,200
1,200
1,800
1,125
1,800
16,524
8,025
1,712
3,470
-598
2,332
1,404
2,674
-441
1,599
5,602
3,360
1,094
8,320
14,131
52 rooms; 200 beds
Net Square Footage By Building Date: 06/27/2022 Page: 2
Center: CARVILLE (00618) of 3
FOOD SERVICE
RECREATION
MEDICAL/DENTAL
ADMINISTRATION
Dining (2 Servings)
Food Preparation
Arts & Crafts
Gymnasium
Canteen
Activity Room
Hair Salon
Men's Exercise Room
Women's Exercise Room
Computer Lab
Recreation Storage
Recreation Office
Medical/Dental
Administration
Function Suggested
NSF
1,875
4,500
8,297
2,054
1,164
2,695
4,113
0004 - CAFETERIA
0004 - CAFETERIA
0003 - RECREATION/GYMNASIUM
0003 - RECREATION/GYMNASIUM
0003 - RECREATION/GYMNASIUM
0003 - RECREATION/GYMNASIUM
0003 - RECREATION/GYMNASIUM
0003 - RECREATION/GYMNASIUM
0003 - RECREATION/GYMNASIUM
0003 - RECREATION/GYMNASIUM
0003 - RECREATION/GYMNASIUM
0003 - RECREATION/GYMNASIUM
0005 - ADMINISTRATION/MED-DENTAL
0005 - ADMINISTRATION/MED-DENTAL
0002 - EDUCATION/LIGHT VOCATION
Bldg Name Actual NSF Difference
1,875
4,500
8,297
2,054
1,164
2,695
4,987
Sub Total:
Sub Total:
Sub Total:
Sub Total:
6,375
14,778
2,695
4,987
1,224
1,445
3,060
2,142
7,650
1,445
3,060
3,582
1,250
1,927
4,233
7,128
1,250
1,927
Net Square Footage By Building Date: 06/27/2022 Page: 3
Center: CARVILLE (00618) of 3
STORAGE/SUPPORT
SECURITY
VACANT
Warehouse
Operations & Maintenance
SECURITY
Vacant
Function Suggested
NSF
1,800
3,325
0007 - RECEIVING
0003 - RECREATION/GYMNASIUM
0001 - VOCATIONAL EDUCATION/MAINTENANCE
0009 - GUARD HOUSE
0003 - RECREATION/GYMNASIUM
Bldg Name Actual NSF Difference
2,390
3,325
Sub Total:
Sub Total:
Sub Total:
5,715
1,836
1,224
3,060
2,101
-409
2,655
-409
Page Intentionally Left Blank
Center CARVILLE (00618)
Dorm Bed Capacity Date: 06/27/2022
Page: 1 of 2
Female
Resident Student
Non Resident Student Total 76
Male
Contract Strength 153 as of On Board Strength 153 as of
Resident Student
Non Resident Student Total
Female Male
Total
Total
0006 - DORMITORY
Wing 1
Wing 2
Physical Capacity
#Rooms #Beds
Male
Male
Current Occupancy of Rooms
#Students Vacant Beds (Need Repares)
Vacant Beds (Due to OBS)
Vacant Beds (due to no Furn)
Reason For Less than Full Occupancy
52 200 0
0 0 0
52Grand Total 200 0 0 0 0
Building Name Wing Name Gender
Center CARVILLE (00618)
Dorm Bed Capacity Date: 06/27/2022
Page: 2 of 2
0006 - DORMITORY
0006 - DORMITORY
Wing 1
Wing 2
Building Name Wing Name bed beds beds beds beds beds beds beds beds beds beds beds beds beds beds
SP
beds
Total beds
8 192Total Beds:
Summary
Female
Resident Student
Non Resident Student Total 76
Male
Contract Strength 153 as of On Board Strength 153 as of
Resident Student
Non Resident Student Total
Female Male
Total
Total
Gender
Male
Male
Environmental Management Report
Center: CARVILLE (00618) Page: 1 Date: 06/27/2022 of 1
SOLID & HAZARDOUS WASTE MANAGEMENT (RCRA)
HAZARDOUS MATERIALS STORAGE (EPCRA)
Gasoline
Building One - Warehouse
Yes
PETROLEUM UNDERGROUND STORAGE TANKS (RCRA)
Compliance0
PETROLEUM ABOVEGROUND STORAGE TANKS (CWA)
ASBESTOS AND PCB MANAGEMENT (TSCA)
AIR POLLUTION CONTROL (CAA)
Ozone None
Non-Attainment
Solid Waste Disposal :
Hazardous Waste Generator :
Hazardous Waste ID :
Generator Classification :
Hazardous Materials Storage :
Hazardous Materials ID :
HazMat Storage Area :
Number of Regulated USTs :
Number of Un-regulated USTs :
HazMat Spill Response Plan :
Local Hazardous Use Permit :
LEPC Notification :
EPA Generator ID Number :
Hazardous Waste Disposal :
RCRA Compliance :
Capacity LocationID Fuel Type
Number of ASTs :
Asbestos Survey Date :
Asbestos Type :
Asbestos Coordinator :
Coordinator Training Date:
Custodial/Maintenance Training :
Management Plan Approval :
PCB Transformer Testing :
PCB Transformers :
PCB-Contaminated Transformers :
Transformers Labelled :
Regional Air Quality :
Permitted Air Pollution Source :
Source Description :
Commercial Waste Service Innovative Waste Systems No
N/A N/A N/A
Prevention/Detection Overfill Leak Corrosion
SPCC Plan Required : SPCC Plan Completed :
No No
No Survey Performed None
N/A N/A
No
No
ID Fuel Type Capacity Location Overfill
Prevention Secondary ContainmentTank Status
Tank Status
Radon
Date: 06/27/2022Center : Carville (00618) Page: 1 of 1
0001 - VOCATIONAL EDUCATION/MAINTENANCE
0002 - EDUCATION/LIGHT VOCATION
0003 - RECREATION/GYMNASIUM
0004 - CAFETERIA
0005 - ADMINISTRATION/MED-DENTAL
0006 - DORMITORY
0007 - RECEIVING
0008 - VOCATIONAL
0009 - GUARD HOUSE
Bldg Name Test Date
No
No
No
No
No
No
No
No
No
Radon Testing
Test Result
N/A
N/A
N/A
N/A
N/A
N/A
N/A
N/A
N/A
Mitigation Mitigation Date
RADON EXPLANATORY NOTES
The US Environmental Protection Agency (EPA) has established a radon action level of 4.0 picoCuries per liter (pCi/L). Occupied buildings with radon concentrations less than 4.0 pCi/L do not require radon mitigation; un-occupied buildings, or those buildings which are occupied only infrequently for brief periods of time, also do not require radon mitigation. Occupied buildings with radon concentrations greater than
4.0 pCi/L require radon mitigation and verification of radon reductions as soon as possible, with priority given to dormitories and student recreation buildings. Occupied buildings with radon concentrations greater than 20.0 pCi/L should be considered significant radon exposure hazards, and priority for mitigation should be given to buildings with these highly elevated radon concentrations.
Radon mitigation techniques include: (1) adjustment of the building HVAC system to create a positive pressure within the building; (2) sealing of foundation wall cracks, penetrations, or other openings;
(3)3) sealing crawlspace openings and sump pits; (4) installing an active subslab depressurizat (ASD) system.
Site Description
Aerial view of Carville JCC
Page: 1 Date: 06/27/2022 of 4
Paving Type for Roads & Parking Paving Type for Sidewalks
Asphalt Concrete
Comments:
Topography Buildings and Structures
Center is fully enclosed by fencing. The brick and wrought iron fence bordering the west edge of the site belongs to the Gillis W. Long Center of State of Louisiana Military Department (GWLC).
ROADS, PARKING & SIDEWALKS
Water Source Water Authority Service Meter On-Site Treatment Plant
1.. Water Syst
Treatment Type Storage Type Storage Capacity(Gallons)
NoIndividualLessor GWLCPublic Water Authority
None 0None
Comments: Water is supplied by contract. Lessor: Gillis W. Long Center of State of Louisiana Military Department (GWLC).
Fire Hydrants On-Site Water Supply Storage Capacity
(Gallons) Pressure Source FD Response Time
(Minutes)
Yes 0 4None Municipal
Comments:
Sewage Treatment Flow
Sanitary sewage is treated by contract with lessor. Lessor: Gillis W. Long Center of State of Louisiana Military Department. Building 8 is served by a small lift station.
Center
Publicly Owned Treatment Works
Center
Gravity
Maintenance ResponsibilityOwnership
Number of Deficiencies = 6
SITE FEATURES
UTILITIES
3.. Sanitary Sewer System/ Sewage Treatment Pla
2.. Fire Protection Syst
Buildings 9 Structures 6Flat
Surrounding
Outdoor Recreation
Institution/Military Housing, Mississippi River, Rural
Basketball, Soccer/football, Soft/Baseball Drainage Swales, Specimen Oak Trees
GSA Vehicle Parking Chain Link
Location Type
Maintenance Responsibility System Capacity Adequate System Condition
Lessor Center Yes Good
Separate Loop
No
Ownership Maintenance Responsibility System Capacity Adequate System Condition
Center Center Yes Good
System Capacity Adequate System Condition
Yes Good
Ownership
Roads & Parking Adequate Roads & Parking Condition Sidewalks Adequate Sidewalk Condition Yes Good Yes Good
Fencing
Other Features
Page: 2 Date: 06/27/2022 of 4
Atmos Energy
Comments:
Electric Company PCB Trans.
Transformer Mounting Transformer Ownership
Systems Ownership Maintenance Responsibility
Entergy Gulf States Louisiana, L.L.C.
Underground electrical service is brought from overhead power lines along the Center eastern perimeter on Betty Martin Road. Service enters the Center from a riser pole with fused cutouts located across from Educational Building 2. The underground service emanates and terminates in pad-mounted, utility-owned transformers. Each transformer with corresponding meter serves the respective building with the exception of Buildings 1, 7 and 8.
Building 1 and Building 8 are served from the same transformer, but separately metered. Building 7 is sub fed from Building 8 and shares the same meter. Cafeteria Building 4 and Dormitory Building 6 each has a 600 kW diesel engine generator and associated automatic transfer switch (ATS) located outside the respective building.
Likewise Administration/Dental-Medical Building 5 has a 300 kW, diesel engine generator and associated ATS located outside near the transformer.
Pad Utility
Utility Utility
No
34.5/19.92 kV, 3-Phase
480/277 Volt, 3-Phase, 4 WireUnderground
OverheadPrimary Service
Secondary Service
Distribution Characteristics
5. Fuel Distribution System
Number of Deficiencies = 1
4. Storm Water System Number of Deficiencies = 1
Drain Type On-Site Storm Water Management
Surface Runoff N/A
Ownership Maintenance Responsibility System Capacity Adequate System Condition
Center Yes FairCenter
Comments: The site drainage is through surface run-off, swales and underground piping leading to a drainage ditch running the full length of the Center along the west edge of the site. The adequacy of the system is not good. The drainage swales are full of debris and vegetation. Some areas on the campus have excessive standing water after heavy rain that drain ver slowly.
Gas Company Metering
Individual
Ownership Maintenance Responsibility System Capacity Adequate System Condition
Center Center Yes Good
7. Electrical (Service)
Transformer Maint Resp
Utility
System Capacity Adequate System Condition
Yes Good
Generator
Diesel
ATS MTS
Yes No
6. Central Plant: None
Metering Individual
Page: 3 Date: 06/27/2022 of 4
Comments:
Telephone Company
On-site Line Owner
AT & T provides telephone service to the Center with two T1 lines coming from a pole located at the southeast corner of the Center near the substation. The T1 lines terminate in the telephone service main closet (MC) located in Building 5. AT&T manages the T1 circuits that grant connectivity to Job Corps Data Center (JCDC).
AT&T provides local telephone service. JCDC provides digital voice long distance telephone voice over Internet protocol (VoIP) through voice gateway Cisco 1800 and Cisco 6500 switch. The MC provides connections to other buildings via underground fiber optics for voice and data communication. Connections in buildings from the switches to the outlets are by CAT 5. Two 3 kVA uninterruptible power supply (UPS) module protect sensitive data communication equipment in the MC from power surges and drops in the line voltage and maintains the power requirement of the system for 15 to 20 minutes in case of an outage. The fire alarm system on Center is network configured with the central fire alarm control/annunciator panel located in Security Office in Building 5 and is monitored by Simplex Grinnell via telephone lines. Fire alarm systems in Buildings 3 and 4 have speakers with pre-recorded voice announcement and microphones at the panel locations. The Center currently has a fire alarm maintenance contract. The security system includes pad-mounted electric vehicular barrier arm operator, DOL/JCDC installed interior and exterior surveillance closed circuit television CCTV cameras and access card readers at buildings main entrance, multi-display color monitors, scanner, metal detector and door alarms with magnetic contacts. Cameras are strategically installed inside and outside the buildings. JCDC maintains and monitors the cameras on-line 24/7. JCDC grants the Center limited access to cameras monitoring from web-based computer with password. Dormitory, recreation, education and administration facilities have TV cable network for entertainment.
AT&T (local) and JCDC by AT&T (long distance)
Maint. Responsibility
Utility Utility
Security Surveillance Closed Circuit Television, Magnetic Contacts
9. Electrical (Communication/Alarm/Security)
Yes
Central
VOIP
System Capacity Adequate System Condition
GoodYes
8. Electrical (Site Lighting)
Roadways Parking Walkways Building Outdoor Sports
Mounting
Control
Pole Pole Pole Building Sport Light
Photocell, Switch, Contactor
Photocell, Switch, Contactor
Photocell, Switch, Contactor
Photocell, Switch, Contactor
Switch, Lighting Contactor
System Ownership Maintenance Responsibility System Capacity Adequate System Condition
Center Center Yes Good
Comments: The site lighting includes building-mounted, pole-mounted HID lights and bollards, which are controlled by photocells. The utility company owns and maintains all pole lights along the roadways. The Center owns and maintains all pole lights along the walkways, building-mounted exterior lights and bollards. The bollards are installed in the front and back courtyard of the dormitory.
Number of Deficiencies = 1
Number of Deficiencies = 10
STORAGE TANKS: None
Fire Alarm Security
Page: 4 Date: 06/27/2022 of 4
ACCESSIBILITY
Yes
UnknownNoNoNo
Nationally Registered Site
Site Eligible for National Register
Located in Historic District
Archaeological Significance
Earthquake Risk Low High LowHigh HighIBC High
LightningEarthquake Def. Authority Flooding Tornado Hurricane Forest
Fire
Accessible Parking: Accessible Slope:
Yes
Curb Cuts:
Yes
Ramps:
YesYes
Site Accessible Route:
GENERAL SITE CONDITION
Rating X
Good Fair Poor
Drainage swales do not adequately conduct water away from site.
HISTORIC PRESERVATION
NATURAL HAZARDS
The site condition is not impacting the functional use of the facilities.
The site condition IS impacting the functional use of the facilities.
The site condition IS SIGNIFICANTLY impacting the functional use of the facilities.
Active Energy Use Reduction Program
Active Water Use Reduction Program
Approximate or Measured Waste Recycled
Use of School Dude or CMMS for Preventative Maintenance
Green Purchasing Policy Practiced
Site Stormwater Absorption Measures in Place
Center has Onsite Renewable Energy (PV or Wind)
Center has a Chartered Green Committee & Roster
Center Uses Green Cleaning Practices
SUSTAINABILITY
Comments: The automotive shop has a compliant vehicle parts washer to collect contaminated water.
Yes
Yes
NO
NO
Yes
Yes
Yes
Yes
0 %
Building Descriptions and Structures
BUILDING 1 - VOCATIONAL EDUCATION/MAINTENANCE
AUTOMOTIVE
INSTRUCTOR
CLASSROOM
STORAGE
TOOLS
API VOCATION
(ROUSTABOUT)
INSTRUCTOR
MAINTENANCE
MAINTENANCE
OFFICE
CTT
SUPERVISOR
CTC
COUNSELOR
COMMUNICATIONS
PROPERTY OFFICER
TOOLS
MEZZANINE
MEZZANINE
FIRST FLOOR
MECH/
STORAGE
STORAGE
M W
UNISEX
TOILET
OUTSIDE
STORAGE
FLAMMABLE
STORAGE
COMPUTER
ROOM
CLASSROOM
STORAGE
JAN
ELEC
UP
SHIPS LADDER
DN
CARVILLE, LOUISIANA
CARVILLE JOB CORPS CENTER
BUILDING 1
MAINTENANCE
60'30'15'0
VOCATIONAL EDUCATION/
VOCATION/THEORY
STORAGE SUPPORT
NON-ACADEMIC
Building Descriptions
Page: 1 of 45
Building: 0001 - VOCATIONAL EDUCATION/MAINTENANCE
BUILDING ENVELOPE
Foundation RoofBuilding
Concrete Structural Steel Steel
Brick Masonry Metal Siding
Wall Roof Rigid Batt
Metal Overhead - Metal Frame Metal Unit - Metal Frame Storefront - Storefront Frame
AccessibilityFeature
GSF NSF Year Built Use Group Historic Ownership #Floors
Business 12,700 11,269 2 Owned 2004 Not Evaluated
Comments: The stairs to the storage mezzanine have open risers.
REAL ESTATE
Access to Building
Ramps
Entrance
2nd Egress
Visual Alarm
Corridor/Aisle
Rooms
Stairs
Elevator
Restrooms
Drinking Fountain
Telephone
Yes
Yes
Yes
Yes
Yes
Yes
Yes
No
No
Yes
Yes
N/A
ACCESSIBILITY
Structural Systems1.
Exterior Walls2.
Insulation4.
Exterior Doors5. Number of Deficiencies = 1
Material Drainage Year Life
Type Area Served
Metal Gutters and Downspouts 2004 21 Gable Entire Building
Number of Deficiencies = 13. Roof
Entire Building
Area Served
Page: 2 of 45
Building: 0001 - VOCATIONAL EDUCATION/MAINTENANCE
INTERIOR FINISH
Carpet Tile Ceramic Tile Concrete Epoxy Paint Vinyl Tile
Comments: Ground moisture migration to buildings cause vinyl tile floor finish deterioration. The corridor and common areas of the building are especially affected.
CMU Ceramic Tile Drywall Fence
Metal Unit - Metal Frame Overhead Grille - Metal Frame
Wood Unit - Metal Frame
VERTICAL CIRCULATION
Metal Ladder Metal Stairs Comments: Metal ladders lead to the storage mezzanine in the automotive repair vocational shop and the center maintenance shop. These ladders have locked metal closures that prevent access to the ladders without the proper key.
Double Hung - Aluminum Frame; Single Glazing; Fixed - Aluminum Frame; Single Glazing;
Fixed - Metal Frame; Single Glazing; Fixed - Metal Frame; Wire Glass Glazing;
Acoustical Tile Exposed Structure Gypsum Board
Windows6.
Floors1.
Interior Walls2.
3.
Interior Doors4.
Ceilings
Page: 3 of 45
Building: 0001 - VOCATIONAL EDUCATION/MAINTENANCE
Mechanical
Mechanical
Automobile Exhaust
Restroom
Shop Area
Shop Area
Comments:
Comments:
Each of the three shops is ventilated by at least one sidewall exhaust fan (typical, Loren Cook, 3/4 HP, 2300 CFM @ 3/8" water gage) interlocked with a motor-operated damper at one or more wall intake louvers.
The automotive shop has an auto exhaust system with two flexible drops.
Ventilation Area Served
Split Direct Expansion (Air
Source)
Packaged Direct
Expansion (Air Source)
Single Duct
Window Unit
Refrigerant
Refrigerant
Electric
Electric
Mechanical
Mechanical
None
None
Classrooms and Offices
Classrooms
Exhaust Ventilation
The DX coils (Trane) in both maintenance and automotive shops are provided cooling by condensing units (Trane #2TTAOO60A3000AA, 5 ton, built 8/2003).
The classroom in API has a window A/C for cooling.
Comments:
Comments:
Number of Deficiencies = 1
Heat Source
Heat Distribution
Piping System
Control System
Fresh Air Intake
Energy Conservation
Measure
Area Served
The American Petroleum Institute (API) vocation is located in the middle third of the building. The classroom in the API is heated by a Carrier window unit with an electric resistance heater.
There are ten unit heaters (typical, Trane #GPND004ADF2000E, 36.5 MBH output, built 2003) that serve the shops and storage rooms.
The classrooms and offices in each of the maintenance and automotive shops are served by a furnace (Trane 96 MBH output, built 8/2003).
Comments:
Comments:
Comments:
HVAC
Heat1.
Electric Resistance
Gas-Fired
Gas-Fired Furnace
Window Unit
Unit Heater
Single Duct
None
None
None
Electric
Electric
Electric
Mechanical
Mechanical
Mechanical
None
None
None
Classrooms
Shop Area
Classrooms and Offices
Ventilation2.
System Type
Number of Deficiencies = 3
Air Distribution
Piping System
Control System
Fresh Air Intake
Energy Conservation Area
Served
3. Air Conditioning
Page: 4 of 45
Building: 0001 - VOCATIONAL EDUCATION/MAINTENANCE
Domestic hot water is provided by two water heaters (Rheem #EGSP20, 20 gallon, 2 kW, 9/2003), each located on the mezzanine level at each end of the building.
Comments:
Cast Iron None Cast Iron
Electric Water Cooler Fixed Emergency Eyewash Hose Bibb Lavatory Mop Sink Urinal Wall Hydrant Water Closet (Flush Valve)
Gas (Natural)
None None ABC Type Fire Extinguisher
Comments: Underground service is provided from a 150 kVA pad-mounted, utility-owned transformer located north of the building. The utility meter is installed on the building north exterior wall. Service enters the building and terminates in a 200A MCB, 480/277V, 3-phase, 4 wire main distribution panel (MDP) located in the main electrical room. The MDP serves a 30 kVA and a 45 kVA dry type, step-down transformers and a 60A MCB panel which serves 480/277V loads in the automotive shop. The step-down transformers serve all 120/208V loads via panels located in the maintenance, automotive and API shops. The automotive shop additionally has a 125A, 120/208V shunt trip panel which provides emergency shut off for power tools. The same 200A MDP panelboard also sub-feeds Building 8.
Copper Copper Electric None No
Hot Water Cold Water Water Heater Water Treatment HW Storage Tank
Grease InterceptorWaste / Vent Interior Storm
Service Entrance Electrical Characteristics Distribution Equipment Wiring Devices
Compact Fluorescent Fluorescent High Intensity Discharge (HID) Comments: Building-mounted site lighting is controlled by the building-mounted photocell. The main building entrance is accented with two wall-mounted decorative fluorescent sconces and two canopy-mounted recessed compact fluorescent down lights.
Main Panelboard 277/480V, 3-Phase, 4 Wire Panelboards Receptacles, GFCI, Switches
Sprinkler System Stand Pipe System Fire Suppression
PLUMBING
Water Distribution1.
Sanitary Distribution2.
Fixtures3. Number of Deficiencies = 1
Fuel Distribution4.
FIRE PROTECTION
ELECTRICAL SERVICES
Exterior Lighting1.
LIGHTING
Page: 5 of 45
Building: 0001 - VOCATIONAL EDUCATION/MAINTENANCE
FIRE ALARM
Comments: The fire alarm control/annunciator panel is an addressable Simplex 4100U panel, located in the main lobby area and connected to the central fire alarm system annunciator panel located in the security office in Building 5.
Comments: The building is connected to the center LAN system by fiber optic cable, utilizing Cisco switches.
Interior and exterior security cameras are remotely monitored by JCDC and from the security office in Building 5. Access card readers are installed at the building entrances.
Audible Alarm Control/Annunciator Panel Duct Smoke Detector Heat Detector Manual Pull Station Smoke Detector Visual Alarm
Connected to Main System Closed Circuit TV None TV with VCR
Telephone Security Public Address Television
Comments: Recorded footcandle levels include natural light contribution. Explosion proof light fixtures and on/off switch are provided in the flammable storage.
Comments: Combination type exit sign emergency light fixtures are provided at building exits.
High Intensity Discharge (HID)
T8 - Fluorescent
T8 - Fluorescent
T8 - Fluorescent
T8 - Fluorescent
T8 - Fluorescent
T8 - Fluorescent
High Intensity Discharge (HID)
Vocational
Storage/Warehouse-Active
Classrooms
Corridors & Stairs
Toilets
Offices
Equipment Rooms (Elec/Mech)
Maintenance Shop
Area Recommended Recorded Light Type
Battery Backup Battery Backup
Emergency Exit
Number of Deficiencies = 1
Interior Lighting2. Number of Deficiencies = 1
Emergency /Exit Lighting3.
COMMUNICATION
Electric Water Gas Yes YesYes
BUILDING UTILITY METERING
Type Location N/A N/A
CARBON MONOXIDE DETECTION
Detection Required No
Number of Deficiencies = 0
Page: 6 of 45
Building: 0001 - VOCATIONAL EDUCATION/MAINTENANCE
GENERAL BUILDING CONDITION
Rating X Good
Fair Poor
The facility condition is not impacting the functional use of the facility.
The facility condition IS impacting the functional use of the facility.
The facility condition IS SIGNIFICANTLY impacting the functional use of the facility.
Structure: Good Exterior: Good Interior: Good Mechanical: Good Electrical: Good
IMPAIRMENT
Potentially Impaired
DOL Responded
DOL Determination
Potential Impaired Comments DOL Determination Discussion/Comments
BUILDING 2 - EDUCATION/LIGHT VOCATION
MECH
ELEC
HC
HC
J
J
M
W
READING II/MATH
HISET
API
VOCATIONAL
CLASSROOM
(ROUSTABOUT)
CAREER
SKILLS
INSTRUCTOR
WOW/LIBRARY
INTRODUCTION
TO CENTER LIFE
SCHEDULING
TEST SPECIALIST
CTR
SPECIALIST
CPP/CT SUPERVISOR
FIBER OPTICS/
COMMUNICATIONS
STAFF LOUNGE
STORAGE
COPY ROOM
ACADEMIC
CLERK
STOR
CLOTHING/
INTERVIEW
PRACTICE
CAREER PREP.
MANAGER
COUNSELOR
CAREER
COUNSELOR
SPECIALIST
HIGHSCHOOL
DIPLOMA
HIGHSCHOOL
DIPLOMA
PROGRAM DIRECTOR
CAREER
COUNSELOR
SPECIALIST
MECH/ELEC
EQUIPMENT
CARVILLE, LOUISIANA
CARVILLE JOB CORPS CENTER
BUILDING 2
VOCATION
60'30'15'0
EDUCATION/ LIGHT
ACADEMIC
NON-ACADEMIC
VOCATION/THEORY
ADMINISTRATION
Page: 7 of 45
Building: 0002 - EDUCATION/LIGHT VOCATION
BUILDING ENVELOPE
Foundation RoofBuilding
Concrete Loadbearing Masonry Wood
Brick Masonry
Wall Roof Rigid Batt
Metal Unit - Metal Frame Storefront - Storefront Frame
AccessibilityFeature
GSF NSF Year Built Use Group Historic Ownership #Floors
Business 13,877 8,882 1 Owned 2004 Not Evaluated
REAL ESTATE
Access to Building
Ramps
Entrance
2nd Egress
Visual Alarm
Corridor/Aisle
Rooms
Stairs
Elevator
Restrooms
Drinking Fountain
Telephone
Yes
N/A
Yes
Yes
Yes
Yes
Yes
N/A
N/A
Yes
Yes
N/A
ACCESSIBILITY
Structural Systems1.
Exterior Walls2.
Insulation4.
Exterior Doors5.
Material
Roof’s asphalt shingle have deteriorated, are no longer flexible but brittle and leaking. Roof life estimated from observation during the March, 2022 Facility Survey.
Drainage Year Life
Type Area Served
Asphalt Shingles Scuppers and Downspouts 2004 0 Gable Entire Building
Number of Deficiencies = 1
Comments:
3. Roof
Page: 8 of 45
Building: 0002 - EDUCATION/LIGHT VOCATION
INTERIOR FINISH
Carpet Ceramic Tile Concrete Vinyl Tile
Acoustical Folding Partition CMU Ceramic Tile Drywall
Metal Unit - Metal Frame Wood Unit - Metal Frame
Mechanical
Mechanical
Restroom
Janitor's Closet
Ventilation Area Served
VERTICAL CIRCULATION
None
Double Hung - Aluminum Frame; Single Glazing; Fixed - Metal Frame; Single Glazing;
Acoustical Tile Exposed Structure Gypsum Board
Exhaust Ventilation
Number of Deficiencies = 1
Number of Deficiencies = 3
Windows6.
Floors1.
Interior Walls2.
3.
Interior Doors4.
Heat Source
Heat Distribution
Piping System
Control System
Fresh Air Intake
Energy Conservation
Measure
Area Served
Two air handlers, AHU-2A & B, (Trane #MCCB021, 15 HP & #MCCB014, 10 HP; both 460/3 and built in 2003) supply air to the entire building, the larger to the west side and the other to the east. Each of the two main supply ducts branch both north and south. Duct-mounted electric resistance heaters are just downstream of each change in direction, therefore, requiring four heaters and creating four zones (NE, SE, SW and NW).
Comments:
HVAC
Heat1.
Electric Resistance
Multi- Zone/Single
AHU
None Direct Digital Control (DDC)
Mechanical None Entire Building
Ventilation2. Number of Deficiencies = 2
Page: 9 of 45
Building: 0002 - EDUCATION/LIGHT VOCATION
The water heater (Rheem #ELD52, 50 gallon, 4.5 kW, built 01/2003) is located in a janitor's closet.Comments:
Cast Iron None None
Electric Water Cooler Hose Bibb Lavatory Portable Bottled Water Cooler Sink Urinal Water Closet (Flush Valve)
None
None None ABC Type Fire Extinguisher
Copper Copper Electric None No
Hot Water Cold Water Water Heater Water Treatment HW Storage Tank
Grease InterceptorWaste / Vent Interior Storm
Split Direct Expansion (Air
Source)
Single Duct Refrigerant Direct Digital Control (DDC)
Mechanical None Entire Building
Sprinkler System Stand Pipe System Fire Suppression
PLUMBING
Three condensing units provide cooling to the air handlers, AHU-2A & B, (Trane #MCCB021, 15 HP & #MCCB014, 10 HP; both 460/3 and built in 2003). Condensing unit ACCU-2A (Trane #RAUCC404BX03, 40 ton) serves AHU-2A and two condensing units (both Trane #TTA180C400FA, 15 ton each) serve AHU-2B. All condensing units are 460/3 and were built in 2003. The AHUs supply air to the entire building, the larger system to the west side and the other to the east. Each of the two main supply ducts branch both north and south. Duct-mounted electric resistance heaters are just downstream of each change in direction, therefore, requiring four heaters (for reheat or dehumidification) and creating four zones (NE, SE, SW and NW).
Comments:
System Type
Air Distribution
Piping System
Control System
Fresh Air Intake
Energy Conservation Area
Served
Water Distribution1.
Sanitary Distribution2.
Fixtures3.
Fuel Distribution4.
Number of Deficiencies = 1FIRE PROTECTION
Page: 10 of 45
Building: 0002 - EDUCATION/LIGHT VOCATION
Comments: Underground service is provided from a 300 kVA pad-mounted utility-owned transformer with a meter mounted on the transformer. The service enters the building to a 400A main distribution panel (MDP) with a 400A main circuit breaker (MCB) located in the electrical room. The panel serves a 125A main-lug-only (MLO) panel providing for the building lighting loads. A 45 kVA step-down transformer is utilized for 120/208 system voltage and feeds a 250A, 120/208V two section panel with a 150A MCB. The 45 kVA transformer and both panels are located in the main electrical room. Lightning arresters (by Delta) protect the 400A main distribution panel and condensing units.
FIRE ALARM
Comments: The fire alarm control/annunciator panel is an addressable Simplex 4100U panel, located in the main lobby area, connected to the central fire alarm system annunciator panel located in the security office in Building 5.
Service Entrance Electrical Characteristics Distribution Equipment Wiring Devices
Audible Alarm Control/Annunciator Panel Duct Smoke Detector Heat Detector Manual Pull Station Smoke Detector Visual Alarm
Comments: Recorded footcandle levels include natural light contribution. Building lighting is served from a 277V power. Occupancy sensors are provided for lighting control in the offices and toilet rooms.
Compact Fluorescent Fluorescent High Intensity Discharge (HID) Comments: Building-mounted and pole-mounted site lighting is controlled by a building-mounted photocell through a lighting contactor with an override switch. The lighting contactor and the override switch are located in the electrical room. The main building entrances are accented with wall-mounted decorative fluorescent sconces and canopy-mounted recessed compact fluorescent down lights.
T8 - Fluorescent
T8 - Fluorescent
T8 - Fluorescent
T8 - Fluorescent
T8 - Fluorescent
T8 - Fluorescent
T8 - Fluorescent
Classrooms
Vocational
Toilets
Equipment Rooms (Elec/Mech)
Storage Rooms
Corridors & Stairs
Offices
Area Recommended Recorded Light Type
Selected Lighting w/ Battery Battery Backup
Main Distribution Panel 277/480V, 3-Phase, 4 Wire Panelboards Receptacles, GFCI, Switches
Emergency Exit
Number of Deficiencies = 2
ELECTRICAL SERVICES
Exterior Lighting1.
Interior Lighting2.
Emergency /Exit Lighting3.
Page: 11 of 45
Building: 0002 - EDUCATION/LIGHT VOCATION
Comments: The building is connected to the center LAN system by fiber optic cable, utilizing Cisco switches.
Interior and exterior security cameras are remotely monitored by JCDC and from the security office in Building 5. Access card readers are installed at the building entrances. A timer (by Simplex) is located in the main lobby area near the main fire alarm panel. TVs with VCRs are also provided.
Connected to Main System Closed Circuit TV None None
Telephone Security Public Address Television
GENERAL BUILDING CONDITION
Rating
Comments:
X Good Fair Poor
HVAC controls are malfunctioning. Roofing is deteriorated
COMMUNICATION
The facility condition is not impacting the functional use of the facility.
The facility condition IS impacting the functional use of the facility.
The facility condition IS SIGNIFICANTLY impacting the functional use of the facility.
Electric Water Gas Yes N/AYes
BUILDING UTILITY METERING
Structure: Good Exterior: Fair Interior: Good Mechanical: Fair Electrical: Good
Type Location N/A N/A
CARBON MONOXIDE DETECTION
Detection Required No
Number of Deficiencies = 0
IMPAIRMENT
Potentially Impaired
DOL Responded
DOL Determination
BUILDING 3 - RECREATION/GYMNASIUM
FIBER OPTICS
STORAGE
ELEC
ARTS & CRAFTS
WOMEN'S WEIGHT ROOM
GAME ROOM
UNIFORM STOR/
SUPPLIES
STUDENT
LEADERSHIP
RECREATION
SUPERVISOR
BARBER SHOP/
LAUNDRY
STORE
CANTEEN
STORAGE
MEDIA ROOM
WOMEN'S LOCKER ROOM
MEN'S LOCKER ROOM
J
MECH
PLATFORM
ABOVE
LOBBY
OFF.
MECH/ELEC
EQUIPMENT
OFF.
MECH/
ELEC
EQUIP
CARVILLE, LOUISIANA
CARVILLE JOB CORPS CENTER
BUILDING 3
RECREATION/GYMNASIUM
60'30'15'0
RECREATION
STORAGE SUPPORT
Page: 12 of 45
Building: 0003 - RECREATION/GYMNASIUM
BUILDING ENVELOPE
Foundation RoofBuilding
Concrete
Concrete
Loadbearing Masonry
Structural Steel
Wood
Steel
Brick Masonry
Wall Roof Rigid Batt
AccessibilityFeature
GSF NSF Year Built Use Group Historic Ownership #Floors
Assembly 20,034 15,464 1 Owned 2004 Not Evaluated
REAL ESTATE
Access to Building
Ramps
Entrance
2nd Egress
Visual Alarm
Corridor/Aisle
Rooms
Stairs
Elevator
Restrooms
Drinking Fountain
Telephone
Yes
N/A
Yes
Yes
Yes
Yes
Yes
N/A
N/A
Yes
Yes
N/A
ACCESSIBILITY
Structural Systems1.
Exterior Walls2.
Insulation4.
Material
Architectural Shingles
Drainage Year Life
Type Area Served
Asphalt Shingles
Asphalt Shingles
Gutters and Downspouts
Gutters and Downspouts
Gable
Gable
Gymnasium
Recreation Area
Number of Deficiencies = 1
Comments:
3. Roof
Recreation Area
Gymnasium
Page: 13 of 45
Building: 0003 - RECREATION/GYMNASIUM
INTERIOR FINISH
Carpet Ceramic Tile Concrete Resilient Rubber Gym Floor Vinyl Tile Wood Sport Floor
Acoustical Folding Partition CMU Ceramic Tile Drywall Exposed Structure Fence
Metal Rollup Fire Shutter - Metal Frame Roll-up Grille - Metal Frame
Wood Unit - Metal Frame
VERTICAL CIRCULATION
Metal Ladder Comments: Metal ladders lead to two mechanical equipment platforms which are located within the gymnasium.
These ladders have locked metal closures that prevent access to the ladders without the proper key.
Metal Unit - Metal Frame Storefront - Storefront Frame
Double Hung - Aluminum Frame; Single Glazing; Fixed - Aluminum Frame; Single Glazing;
Fixed - Metal Frame; Single Glazing;
Acoustical Tile Exposed Structure Gypsum Board Wood
Number of Deficiencies = 1
Exterior Doors5.
Windows6.
Floors1.
Interior Walls2.
3.
Interior Doors4. Number of Deficiencies = 2
Page: 14 of 45
Building: 0003 - RECREATION/GYMNASIUM
Mechanical
Mechanical
Mechanical
Toilet/Shower
Janitor's Closet
Gymnasium
Comments: The gymnasium is ventilated by the large sidewall propeller exhaust fan high in the SE wall.
Ventilation Area Served
Split Direct Expansion (Air
Source)
Split Direct Expansion (Air
Source)
Single Duct
Variable Air Volume
Refrigerant
Refrigerant
Direct Digital Control (DDC)
Direct Digital Control (DDC)
Mechanical
Mechanical
None
None
Gymnasium
Recreation Area
Exhaust Ventilation
There are four condensing units (Trane #TTA18044CAB00AE, 15 ton, manufactured in 3-2019 each unit) coupled to two air handling units (Trane #CSAA014UAL00, 7.5 hp) located on high platforms, one in the north and the other in the west corner of the gymnasium are providing cooling (30 ton each).
The up-flow air handler (Trane #MCCB021UA0B0UA, 15 HP, built 2003) in the NE mechanical equipment room supplies air to 16 VAV boxes. The air handler is provided cooling by a condensing unit (Trane #RAUCC404BX0300D, 40 ton, built 2003) set on-grade adjacent to the mechanical equipment room.
Comments:
Comments:
Heat Source
Heat Distribution
Piping System
Control System
Fresh Air Intake
Energy Conservation
Measure
Area Served
There are two air handlers (Trane #CSAA014UAL00) providing heat which are located on high platforms, one in the north and the other in the west corner of the gymnasium. Each air handler is equipped with a gas-fired duct furnace (Trane #GMND022AEF3000A, 225 MBH output).
The up-flow air handler (Trane #MCCB021UA0B0UA, 15 HP, built 2003) in the NE mechanical equipment room supplies air to 16 VAV boxes provided with electric heaters.
Comments:
Comments:
HVAC
Heat1.
Gas-Fired Furnace
Electric Resistance
Single Duct
Variable Air Volume
None
None
Electric
Direct Digital Control (DDC)
Mechanical
Mechanical
None
None
Gymnasium
Recreation Area
Ventilation2.
System Type
Number of Deficiencies = 2
Air Distribution
Piping System
Control System
Fresh Air Intake
Energy Conservation Area
Served
Page: 15 of 45
Building: 0003 - RECREATION/GYMNASIUM
Two electric water heaters (Rheem #ELD66, 65 gallon, built 9/2002; #ELD52, 50 gallon, built 1/2003;
both 4.5 kW) are located in a dedicated room at the SW end of the corridor.
Comments:
Cast Iron None None
Electric Water Cooler Hose Bibb Lavatory Mop Sink Service Sink Shower Urinal Water Closet (Flush Valve)
Gas (Natural)
None None ABC Type Fire Extinguisher
Comments: Underground service is provided from a 300 kVA pad-mounted, utility-owned transformer with a meter mounted on the transformer. The service enters the building to a 600A distribution panel with a 600A main circuit breaker (MCB) located in the electrical room. The panel serves a 125A MLO panel providing for the building lighting loads and a 400A main-lug-only (MLO) panelboard located on the north building wall and providing for the gymnasium's HVAC and lighting loads. A 45 kVA step-down transformer is utilized for 120/208 system voltage and feeds a 250A panel with a 150A MCB, both located in the electrical room. Lightning arresters (by Delta) protect the main distribution panel and condensing units.
Copper Copper Electric None No
Hot Water Cold Water Water Heater Water Treatment HW Storage Tank
Grease InterceptorWaste / Vent Interior Storm
Service Entrance Electrical Characteristics Distribution Equipment Wiring Devices
Compact Fluorescent Fluorescent High Intensity Discharge (HID) Comments: Building-mounted and pole-mounted site lighting are controlled by a building-mounted photocell through a lighting contactor with an override switch. The lighting contactor and the override switch are located in the electrical room. The main building entrances are accented with wall-mounted decorative fluorescent sconces and canopy-mounted recessed compact fluorescent down lights.
Main Distribution Panel 277/480V, 3-Phase, 4 Wire Panelboards Receptacles, GFCI, Switches
Sprinkler System Stand Pipe System Fire Suppression
PLUMBING
Water Distribution1.
Sanitary Distribution2.
Fixtures3.
Fuel Distribution4.
FIRE PROTECTION
ELECTRICAL SERVICES Number of Deficiencies = 3
Exterior Lighting1.
Page: 16 of 45
Building: 0003 - RECREATION/GYMNASIUM
FIRE ALARM
Comments: The fire alarm control/annunciator panel is an addressable Simplex 4100U panel, located in the main lobby area, connected to the central fire alarm system annunciator panel located in the security office in Building 5. Also, system speakers with pre-recorded voice are provided throughout the building with a microphone at the panel location. Beam type smoke detectors are provided in the gymnasium.
Comments: The building is connected to the center LAN system by fiber optic cable, utilizing Cisco switches.
Interior and exterior security cameras are remotely monitored by JCDC and from the security office in Building 5. Access card readers are installed at the building entrances.
Audible/Speaker Alarm Beam Smoke Detector Control/Annunciator Panel Duct Smoke Detector Heat Detector Manual Pull Station Smoke Detector Visual Alarm
Connected to Main System Closed Circuit TV None Local Cable Company
Telephone Security Public Address Television
Comments: Recorded footcandle levels include natural light contribution. Building lighting is served from a 277V power. Occupancy sensors are provided for lighting control in the offices and toilet rooms. Gymnasium lighting is controlled through the lighting contactor. HID light fixtures in the gymnasium have quartz re-strike feature.
Comments: Battery backup emergency light fixtures are utilized in the gymnasium.
High Intensity Discharge (HID)
T8 - Fluorescent
T8 - Fluorescent
T8 - Fluorescent
T8 - Fluorescent
T8 - Fluorescent
T8 - Fluorescent
Compact Fluorescent
T8 - Fluorescent
Gymnasium
Recreation
Corridors & Stairs
Toilets
Offices
Storage Rooms
Locker Room
Shower
Equipment Rooms (Elec/Mech)
Area Recommended Recorded Light Type
Selected Lighting w/ Battery Battery Backup
Emergency Exit
Number of Deficiencies = 2
Interior Lighting2. Number of Deficiencies = 1
Emergency /Exit Lighting3.
COMMUNICATION
Type Location N/A N/A
CARBON MONOXIDE DETECTION
Detection Required No
Page: 17 of 45
Building: 0003 - RECREATION/GYMNASIUM
GENERAL BUILDING CONDITION
Rating
Comments:
X Good Fair Poor
Some air conditioning units not functioning. Exterior is Fair due to need for a roof replacement.
The facility condition is not impacting the functional use of the facility.
The facility condition IS impacting the functional use of the facility.
The facility condition IS SIGNIFICANTLY impacting the functional use of the facility.
Electric Water Gas Yes YesYes
BUILDING UTILITY METERING
Structure: Good Exterior: Fair Interior: Good Mechanical: Fair Electrical: Good
IMPAIRMENT
Potentially Impaired
DOL Responded
BUILDING 4 - CAFETERIA
DINING
KITCHEN
SUPPLIES
OFFICE
FREEZER
DRY FOOD
STORAGE
DISHWASHING
SERVING
SOFT DRINKING
J
EQUIPMENT/
GENERATOR
SALAD BAR
REFRIGERATOR
W
M
M
W
WATER
HEATERS
ELEC
J
LOADING
DOCK
UP
CARVILLE, LOUISIANA
CARVILLE JOB CORPS CENTER
BUILDING 4
CAFETERIA
60'30'15'0
FOOD SERVICE
Page: 18 of 45
Building: 0004 - CAFETERIA
BUILDING ENVELOPE
Foundation RoofBuilding
Concrete Loadbearing Masonry Wood
Brick Masonry Storefront
Wall Roof Rigid Batt
Metal Unit - Metal Frame Storefront - Storefront Frame
AccessibilityFeature
GSF NSF Year Built Use Group Historic Ownership #Floors
Assembly 10,212 6,375 1 Owned 2004 Not Evaluated
REAL ESTATE
Access to Building
Ramps
Entrance
2nd Egress
Visual Alarm
Corridor/Aisle
Rooms
Stairs
Elevator
Restrooms
Drinking Fountain
Telephone
Yes
N/A
Yes
Yes
Yes
Yes
Yes
N/A
N/A
Yes
Yes
N/A
ACCESSIBILITY
Structural Systems1.
Exterior Walls2.
Insulation4.
Exterior Doors5.
Material
Roof’s asphalt shingle have deteriorated, are no longer flexible but brittle and leaking. Roof life estimated from observation during the March 2022 Facility Survey.
Drainage Year Life
Type Area Served
Asphalt Shingles Gutters and Downspouts 2004 0 Hip Entire Building
Number of Deficiencies = 1
Comments:
3. Roof
Entire Building
Page: 19 of 45
Building: 0004 - CAFETERIA
INTERIOR FINISH
Ceramic Tile Concrete Quarry Tile Vinyl Tile
CMU Ceramic Tile Drywall
Aluminum Cafe Unit - Metal Frame Metal Unit - Metal Frame
Metal Unit - Wood Frame
VERTICAL CIRCULATION
Concrete Stairs Comments: There are exterior concrete steps leading from the loading dock to grade.
Fixed - Aluminum Frame; Single Glazing;
Acoustical Tile Gypsum Board Plaster
Number of Deficiencies = 2
Windows6.
Floors1.
Interior Walls2.
3.
Interior Doors4.
Heat Source
Heat Distribution
Piping System
Control System
Fresh Air Intake
Energy Conservation
Measure
Area Served
Air handler AHU-4A (Trane #MCCB021N0A, 15 HP, built 6/2003) serving the dining hall is provided with a gas-fired duct furnace (Trane #GMND030, 240 MBH output, direct vent, built 6/2003) and is located in the main mechanical room.
Air handler AHU-4B (Trane #MCCB012N0A, 7.5 HP, built 6/2003) serving the kitchen is provided with a gas-fired duct furnace (Trane #GMND022AEF, 180 MBH output, direct vent, built 6/2003) and is located in the main mechanical room.
Comments:
Comments:
HVAC
Heat1.
Gas-Fired Furnace
Gas-Fired Furnace
Single Duct
Single Duct
None
None
Direct Digital Control (DDC)
Direct Digital Control (DDC)
Mechanical
Mechanical
None
None
Kitchen
Dining Hall
Page: 20 of 45
Building: 0004 - CAFETERIA
Mechanical
Mechanical
Restroom
Kitchen Hood
Comments: The dishwasher and the server hood as well as the main kitchen hood (Avtec #AFDI, 15 LF X 10 LF) are ventilated by rooftop exhaust fans. Two units (Loren Cook #245SQNB) supply tempered make-up air to compensate for this exhaust.
Two gas-fired water heaters (PVI #40V125, 125 gallon, 399 MBH input, built 4/2003) provide the domestic hot water. A recirculating pump is also provided. The dishwasher is equipped with a booster water heater (Hatco #C-45, 45 kW).
Comments:
Comments:
Cast Iron Outdoor None
A 1,000-gallon grease interceptor is located outside the building.
Electric Water Cooler Hose Bibb Lavatory Mop Sink Multi-Compartment Sink Service Sink Sink Urinal Water Closet (Flush Valve)
Gas (Natural)
Ventilation Area Served
Copper Copper Gas-Fired None No
Hot Water Cold Water Water Heater Water Treatment HW Storage Tank
Grease InterceptorWaste / Vent Interior Storm
Split Direct Expansion (Air
Source)
Split Direct Expansion (Air
Source)
Single Duct
Single Duct
Refrigerant
Refrigerant
Direct Digital Control (DDC)
Direct Digital Control (DDC)
Mechanical
Mechanical
None
None
Kitchen
Dining Hall
PLUMBING
Exhaust Ventilation
The air handler AHU-4A (Trane #MCCB021N0A, 15 HP, built 6/2003) serving the kitchen and adjacent…