Appendix B - Survey Volume 2.pdf

PDF 4 MB Posted

Attached to
Carville Job Corps Center Caretaker Services
Solicitation number
1605AE-27-Q-00001
Issued by

About this file

This document is a Facility Planning Report Supporting Data Volume II for the Carville Job Corps Center in Louisiana, completed in June 2022. The report provides comprehensive facility survey information including site layout, building descriptions, space utilization analysis, environmental management status, and identified deficiencies across the center's infrastructure.

The Carville Job Corps Center occupies approximately 116,346 gross square feet across nine buildings and six structures situated on a campus in Carville, Louisiana. Key facilities include a vocational education/maintenance building (12,700 GSF), education/light vocation building (13,877 GSF), recreation/gymnasium (20,034 GSF), cafeteria (10,212 GSF), administration/medical-dental building (12,095 GSF), dormitory with 200-bed capacity serving 153 students (37,926 GSF), receiving building (2,000 GSF), vocational building (7,442 GSF), and guard house (60 GSF), plus storage structures and gazebos. The dormitory accommodates 77 males and 76 females across four wings with 52 rooms. Utility systems include municipal water service, gravity-fed sanitary sewage treatment through the adjacent Gillis W. Long Center, underground electrical service from Entergy Gulf States Louisiana with backup diesel generators (600 kW serving Buildings 4 and 6; 300 kW serving Building 5), natural gas service from Atmos Energy, and a fiber optic communication network managed by JCDC. The survey identifies multiple deficiencies including deteriorated asphalt roofing requiring replacement on five buildings, ground moisture migration causing floor finish deterioration in several facilities, inadequate storm water drainage with debris-filled swales, and malfunctioning HVAC controls in multiple buildings. All facilities maintain addressable fire alarm systems connected to a central annunciator panel, sprinkler systems, and security infrastructure including CCTV monitoring and access card readers throughout the center.

View the file

Other files

Show all 12

On GovTribe

Work with this file

  • Download the original file
  • Contacts named in this file
  • Similar government files
  • Ask GovTribe AI about this file

Text version

CARVILLE

Job Corps Center Carville, LA

Facility Planning Report Supporting Data

Volume II

Final June 2022

CARVILLE JOB CORPS CENTER

PY2021 FACILITY SURVEY REPORT

VOLUME II – TABLE OF CONTENTS

1.0 EXECUTIVE SUMMARY

2.0 SITE LAYOUT AND PLANS

Location Map

Existing Site Plan

3.0 DESCRIPTIONS

Buildings and Structures

Space Utilization by function

NSF by Building

Environmental Management Report

Radon Report

Site Description

Building Descriptions and Structures, Floor Plans

4.0 DEFICIENCIES

APPENDICES – CORRESPONDENCE AND REPORTS

APPENDIX A

Survey Brief ............................................................................................................................... A-1

APPENDIX B

Life Safety Deficiencies and List ................................................................................................ B-1

APPENDIX C

O&M Deficiencies List ............................................................................................................... C-1 i

Dorm Bed Capacity

Page Intentionally Left Blank ii

1.0 EXECUTIVE SUMMARY

1.0 EXECUTIVE

SUMMARY

• Existing site layout

• Overall status of existing building and structures

• Space utilization by building and function compared to recommended standards

• Status of environmental elements of the Center’s operations

• Details on the site and buildings and structures based on architectural, electrical, and mechanical survey and supporting documentation

• Presentation of the status of historical deficiencies and compilation of deficiencies documented through this survey

• Supporting documentation, as presented in the appendices of the center review meeting; survey brief and student questionnaire; life safety IA/IIA transmittal; and active warranties

Section 1.0 of this volume addresses site layout and plans while Section 2.0 presents details on the buildings and structures. Section 3.0 presents deficiencies and their status as well as new ones identified in this survey. The appendices provide additional information as noted below:

• Appendix A. Survey Brief Questionnaire

• Appendix B. Life Safety Deficiencies and List

• Appendix C. O&M Deficiencies List

EXECUTIVE SUMMARY

The Program Year 2021 facility survey for Carville Job Corps Center was completed the week of March 21, 2022. The information presented in Volume II - Supporting Data, represents the current status of the campus.

The information includes the following:

2.0 SITE LAYOUT AND PLANS

2.0 SITE LAYOUT

AND PLANS

x x x x x x x x

P o i n t

C l a i r

R o a d

Gillis W. Long Center

OAK TREES

ELEC.

TRANSFORMER

RESTORE SWALES

GOVT. VEHICLE

PARKING

B e t t y

M a r t i n

R o a d

Carville Job Corps Center

Carville, Louisiana

BUILDINGS

1 - VOCATIONAL EDUCATION/MAINTENANCE

2 - EDUCATION/LIGHT VOCATION

3 - RECREATION/GYMNASIUM

4 - CAFETERIA

5 - ADMINISTRATION/MED-DENTAL

6 - DORMITORY

7 - RECEIVING

8 - VOCATIONAL

9 - GUARD HOUSE

STRUCTURES

10 - GAZEBO

11 - GAZEBO

12 - GAZEBO

13 - STORAGE

14 - STORAGE

15 - HOME BUILDERS STORAGE

Existing Site Plan

400 Feet2001000

STORAGE

RECREATION

MEDICAL/DENTAL

EDUCATION

DORMITORY

CAFETERIA

ADMINISTRATION

FUNCTION LEGEND

VACANT

AS OF 05/13/2021 FROM

INVENTORY VALIDATION

AutoCAD SHX Text

VAN

AutoCAD SHX Text H

AutoCAD SHX Text H

AutoCAD SHX Text

VAN

AutoCAD SHX Text H

AutoCAD SHX Text H

AutoCAD SHX Text H

3.0 DESCRIPTIONS

3.0 DESCRIPTIONS

BUILDINGS AND STRUCTURES

00618 CARVILLE 06/27/2022

Page: 1 of Date:

0001 - VOCATIONAL

EDUCATION/MAINTENANCE

0002 - EDUCATION/LIGHT VOCATION

0003 - RECREATION/GYMNASIUM

0004 - CAFETERIA

0005 - ADMINISTRATION/MED-DENTAL

0006 - DORMITORY

0007 - RECEIVING

0008 - VOCATIONAL

0009 - GUARD HOUSE

0010 - GAZEBO (295Ft Diameter) 0011 - GAZEBO (295Ft Diameter) 0012 - GAZEBO (295Ft Diameter) 0013 - STORAGE (12Ft x 12Ft) 0014 - STORAGE (12Ft x 12Ft) 0015 - HOME BUILDERS STORAGE (12Ft x 20Ft)

Name GSF

12,700

13,877 20,034 10,212 12,095 37,926 2,000 7,442

Active

Active Active Active Active Active Active Active Active Active Active Active Active Active Active

StatusType

Building

Building Building Building Building Building Building Building Building Structure Structure Structure Structure Structure Structure

Use Group Built Flrs Const

Business

Business Assembly Assembly Business Residential Storage Business Business Residential Residential Residential Storage Storage Storage

Good

Good Good Good Good Fair

Good Good Good Good Good Good Good Good Good

ConditionAsset Number

0061808008

0061808009 0061808010 0061808011 0061808012 0061808013 0061808014 0061808015 0061808016 0061808017 0061808018 0061808019 0061808020 0061808021 0061808024

9 116,346

6 1,413

15 117,759

Buildings

Structures

Total

GSF

GSF

GSF

Summary

06/27/2022

Space Utilization By Function 00618 Carville Page: 1 of 3

HOUSING

EDUCATION

FOOD SERVICE

SUGGESTED

NSF/

ENROLLEE

SUGGESTED

TOTAL

NSF

ACTUAL

TOTAL

NSF

TYPE OF SPACE

SUB TOTAL

SUB TOTAL

SUB TOTAL

Resident Men Resident Women Total Residents

Date:

Residents Non Residents Total Students

(153)

(0)

(153)

DIFFERENCE

16,524

10,170

2,142

24,844

22,156

6,375

Lounge Other Shower/Toilet Sleeping excl. SPD(52 rooms; 200 beds) Storage

Academic (0) Non-Academic

24 -- API Field Operator Assistant + 15 -- Automotive Mechanic + 30 -- Computer Operations 12 -- Culinary Arts + 24 -- Facilities Maint. and Const. + 30 -- Health Occupations + 10 -- Medical Assistant 15 -- Welding +

Vocational Theory (120)

Dining (2 Servings) Food Preparation

5,000 2,628 4,168

12,728

2,674 5,602

2,894 4,485 1,009

3,399 1,334

1,875 4,500

1,530 1,224 1,836

11,016

1,800 1,125

1,800 1,200

1,125

1,200

1,224

3,470 1,404 2,332 1,712

-598

1,094 3,360

1,599

-441

3,582

Vocations

8,320

11,986

4,233

Page: 2 of Date:

RECREATION

MEDICAL/DENTAL

ADMINISTRATION

STORAGE/SUPPORT

SECURITY

VACANT

SUGGESTED

NSF/

ENROLLEE

SUGGESTED

TOTAL

NSF

ACTUAL

TOTAL

NSF

TYPE OF SPACE

SUB TOTAL

SUB TOTAL

SUB TOTAL

SUB TOTAL

SUB TOTAL

SUB TOTAL

TOTAL 290.92 44,510 81,696

(153)

(153)

(153)

(153)

(153)

(0)

DIFFERENCE

7,650

1,445

3,060

3,060

14,778

2,695

4,987

5,715

Activity Room Arts & Crafts Canteen Computer Lab Gymnasium Hair Salon Men's Exercise Room Recreation Office Recreation Storage Women's Exercise Room

Medical/Dental

Administration

Operations & Maintenance Warehouse

SECURITY

Vacant

9.44

2,054

8,297

1,164

2,695

4,987

3,325 2,390

1,445

3,060

1,224 1,836

1,250

1,927

2,101

-409

RESIDENT

NON-RESIDENT

(153)

(0) 15

50 7,650

7,128

1,250

1,927

2,655

-409

37,186

Page: 3 of Date:

SUGGESTED

NSF/

ENROLLEE

SUGGESTED

TOTAL

NSF

ACTUAL

TOTAL

NSF

TYPE OF SPACE DIFFERENCE

116,346

0.70

TOTAL GSF

NET TO GROSS RATIO

Net Square Footage By Building Page: 1 of 3

Date: 06/27/2022Center: CARVILLE (00618)

HOUSING

EDUCATION

Sleeping excl. SPD

Lounge

Storage

Shower/Toilet

Other

Academic

Vocational Theory (120)

Health Occupations

Facilities Maint. and Const.

Non-Academic

Automotive Mechanic

Computer Operations

API Field Operator Assistant

Function Suggested

NSF

12,728

5,000

4,168

2,628

1,432

1,334

3,399

2,428

4,485

1,009

2,894

0006 - DORMITORY

0006 - DORMITORY

0006 - DORMITORY

0006 - DORMITORY

0006 - DORMITORY

0002 - EDUCATION/LIGHT VOCATION

0002 - EDUCATION/LIGHT VOCATION

0002 - EDUCATION/LIGHT VOCATION

0001 - VOCATIONAL EDUCATION/MAINTENANCE

0008 - VOCATIONAL

0008 - VOCATIONAL

0008 - VOCATIONAL

0002 - EDUCATION/LIGHT VOCATION

0001 - VOCATIONAL EDUCATION/MAINTENANCE

0002 - EDUCATION/LIGHT VOCATION

0002 - EDUCATION/LIGHT VOCATION

0002 - EDUCATION/LIGHT VOCATION

0002 - EDUCATION/LIGHT VOCATION

0002 - EDUCATION/LIGHT VOCATION

0001 - VOCATIONAL EDUCATION/MAINTENANCE

0008 - VOCATIONAL

0001 - VOCATIONAL EDUCATION/MAINTENANCE

Bldg Name Actual NSF Difference

12,728

5,000

4,168

2,628

2,674

1,334

3,399

5,602

4,485

1,009

2,894

Sub Total:

Sub Total:

24,844

22,156

11,016

1,530

1,836

1,224

1,200

1,200

1,800

1,125

1,800

16,524

8,025

1,712

3,470

-598

2,332

1,404

2,674

-441

1,599

5,602

3,360

1,094

8,320

14,131

52 rooms; 200 beds

Net Square Footage By Building Date: 06/27/2022 Page: 2

Center: CARVILLE (00618) of 3

FOOD SERVICE

RECREATION

MEDICAL/DENTAL

ADMINISTRATION

Dining (2 Servings)

Food Preparation

Arts & Crafts

Gymnasium

Canteen

Activity Room

Hair Salon

Men's Exercise Room

Women's Exercise Room

Computer Lab

Recreation Storage

Recreation Office

Medical/Dental

Administration

Function Suggested

NSF

1,875

4,500

8,297

2,054

1,164

2,695

4,113

0004 - CAFETERIA

0004 - CAFETERIA

0003 - RECREATION/GYMNASIUM

0003 - RECREATION/GYMNASIUM

0003 - RECREATION/GYMNASIUM

0003 - RECREATION/GYMNASIUM

0003 - RECREATION/GYMNASIUM

0003 - RECREATION/GYMNASIUM

0003 - RECREATION/GYMNASIUM

0003 - RECREATION/GYMNASIUM

0003 - RECREATION/GYMNASIUM

0003 - RECREATION/GYMNASIUM

0005 - ADMINISTRATION/MED-DENTAL

0005 - ADMINISTRATION/MED-DENTAL

0002 - EDUCATION/LIGHT VOCATION

Bldg Name Actual NSF Difference

1,875

4,500

8,297

2,054

1,164

2,695

4,987

Sub Total:

Sub Total:

Sub Total:

Sub Total:

6,375

14,778

2,695

4,987

1,224

1,445

3,060

2,142

7,650

1,445

3,060

3,582

1,250

1,927

4,233

7,128

1,250

1,927

Net Square Footage By Building Date: 06/27/2022 Page: 3

Center: CARVILLE (00618) of 3

STORAGE/SUPPORT

SECURITY

VACANT

Warehouse

Operations & Maintenance

SECURITY

Vacant

Function Suggested

NSF

1,800

3,325

0007 - RECEIVING

0003 - RECREATION/GYMNASIUM

0001 - VOCATIONAL EDUCATION/MAINTENANCE

0009 - GUARD HOUSE

0003 - RECREATION/GYMNASIUM

Bldg Name Actual NSF Difference

2,390

3,325

Sub Total:

Sub Total:

Sub Total:

5,715

1,836

1,224

3,060

2,101

-409

2,655

-409

Page Intentionally Left Blank

Center CARVILLE (00618)

Dorm Bed Capacity Date: 06/27/2022

Page: 1 of 2

Female

Resident Student

Non Resident Student Total 76

Male

Contract Strength 153 as of On Board Strength 153 as of

Resident Student

Non Resident Student Total

Female Male

Total

Total

0006 - DORMITORY

Wing 1

Wing 2

Physical Capacity

#Rooms #Beds

Male

Male

Current Occupancy of Rooms

#Students Vacant Beds (Need Repares)

Vacant Beds (Due to OBS)

Vacant Beds (due to no Furn)

Reason For Less than Full Occupancy

52 200 0

0 0 0

52Grand Total 200 0 0 0 0

Building Name Wing Name Gender

Center CARVILLE (00618)

Dorm Bed Capacity Date: 06/27/2022

Page: 2 of 2

0006 - DORMITORY

0006 - DORMITORY

Wing 1

Wing 2

Building Name Wing Name bed beds beds beds beds beds beds beds beds beds beds beds beds beds beds

SP

beds

Total beds

8 192Total Beds:

Summary

Female

Resident Student

Non Resident Student Total 76

Male

Contract Strength 153 as of On Board Strength 153 as of

Resident Student

Non Resident Student Total

Female Male

Total

Total

Gender

Male

Male

Environmental Management Report

Center: CARVILLE (00618) Page: 1 Date: 06/27/2022 of 1

SOLID & HAZARDOUS WASTE MANAGEMENT (RCRA)

HAZARDOUS MATERIALS STORAGE (EPCRA)

Gasoline

Building One - Warehouse

Yes

PETROLEUM UNDERGROUND STORAGE TANKS (RCRA)

Compliance0

PETROLEUM ABOVEGROUND STORAGE TANKS (CWA)

ASBESTOS AND PCB MANAGEMENT (TSCA)

AIR POLLUTION CONTROL (CAA)

Ozone None

Non-Attainment

Solid Waste Disposal :

Hazardous Waste Generator :

Hazardous Waste ID :

Generator Classification :

Hazardous Materials Storage :

Hazardous Materials ID :

HazMat Storage Area :

Number of Regulated USTs :

Number of Un-regulated USTs :

HazMat Spill Response Plan :

Local Hazardous Use Permit :

LEPC Notification :

EPA Generator ID Number :

Hazardous Waste Disposal :

RCRA Compliance :

Capacity LocationID Fuel Type

Number of ASTs :

Asbestos Survey Date :

Asbestos Type :

Asbestos Coordinator :

Coordinator Training Date:

Custodial/Maintenance Training :

Management Plan Approval :

PCB Transformer Testing :

PCB Transformers :

PCB-Contaminated Transformers :

Transformers Labelled :

Regional Air Quality :

Permitted Air Pollution Source :

Source Description :

Commercial Waste Service Innovative Waste Systems No

N/A N/A N/A

Prevention/Detection Overfill Leak Corrosion

SPCC Plan Required : SPCC Plan Completed :

No No

No Survey Performed None

N/A N/A

No

No

ID Fuel Type Capacity Location Overfill

Prevention Secondary ContainmentTank Status

Tank Status

Radon

Date: 06/27/2022Center : Carville (00618) Page: 1 of 1

0001 - VOCATIONAL EDUCATION/MAINTENANCE

0002 - EDUCATION/LIGHT VOCATION

0003 - RECREATION/GYMNASIUM

0004 - CAFETERIA

0005 - ADMINISTRATION/MED-DENTAL

0006 - DORMITORY

0007 - RECEIVING

0008 - VOCATIONAL

0009 - GUARD HOUSE

Bldg Name Test Date

No

No

No

No

No

No

No

No

No

Radon Testing

Test Result

N/A

N/A

N/A

N/A

N/A

N/A

N/A

N/A

N/A

Mitigation Mitigation Date

RADON EXPLANATORY NOTES

The US Environmental Protection Agency (EPA) has established a radon action level of 4.0 picoCuries per liter (pCi/L). Occupied buildings with radon concentrations less than 4.0 pCi/L do not require radon mitigation; un-occupied buildings, or those buildings which are occupied only infrequently for brief periods of time, also do not require radon mitigation. Occupied buildings with radon concentrations greater than

4.0 pCi/L require radon mitigation and verification of radon reductions as soon as possible, with priority given to dormitories and student recreation buildings. Occupied buildings with radon concentrations greater than 20.0 pCi/L should be considered significant radon exposure hazards, and priority for mitigation should be given to buildings with these highly elevated radon concentrations.

Radon mitigation techniques include: (1) adjustment of the building HVAC system to create a positive pressure within the building; (2) sealing of foundation wall cracks, penetrations, or other openings;

(3)3) sealing crawlspace openings and sump pits; (4) installing an active subslab depressurizat (ASD) system.

Site Description

Aerial view of Carville JCC

Page: 1 Date: 06/27/2022 of 4

Paving Type for Roads & Parking Paving Type for Sidewalks

Asphalt Concrete

Comments:

Topography Buildings and Structures

Center is fully enclosed by fencing. The brick and wrought iron fence bordering the west edge of the site belongs to the Gillis W. Long Center of State of Louisiana Military Department (GWLC).

ROADS, PARKING & SIDEWALKS

Water Source Water Authority Service Meter On-Site Treatment Plant

1.. Water Syst

Treatment Type Storage Type Storage Capacity(Gallons)

NoIndividualLessor GWLCPublic Water Authority

None 0None

Comments: Water is supplied by contract. Lessor: Gillis W. Long Center of State of Louisiana Military Department (GWLC).

Fire Hydrants On-Site Water Supply Storage Capacity

(Gallons) Pressure Source FD Response Time

(Minutes)

Yes 0 4None Municipal

Comments:

Sewage Treatment Flow

Sanitary sewage is treated by contract with lessor. Lessor: Gillis W. Long Center of State of Louisiana Military Department. Building 8 is served by a small lift station.

Center

Publicly Owned Treatment Works

Center

Gravity

Maintenance ResponsibilityOwnership

Number of Deficiencies = 6

SITE FEATURES

UTILITIES

3.. Sanitary Sewer System/ Sewage Treatment Pla

2.. Fire Protection Syst

Buildings 9 Structures 6Flat

Surrounding

Outdoor Recreation

Institution/Military Housing, Mississippi River, Rural

Basketball, Soccer/football, Soft/Baseball Drainage Swales, Specimen Oak Trees

GSA Vehicle Parking Chain Link

Location Type

Maintenance Responsibility System Capacity Adequate System Condition

Lessor Center Yes Good

Separate Loop

No

Ownership Maintenance Responsibility System Capacity Adequate System Condition

Center Center Yes Good

System Capacity Adequate System Condition

Yes Good

Ownership

Roads & Parking Adequate Roads & Parking Condition Sidewalks Adequate Sidewalk Condition Yes Good Yes Good

Fencing

Other Features

Page: 2 Date: 06/27/2022 of 4

Atmos Energy

Comments:

Electric Company PCB Trans.

Transformer Mounting Transformer Ownership

Systems Ownership Maintenance Responsibility

Entergy Gulf States Louisiana, L.L.C.

Underground electrical service is brought from overhead power lines along the Center eastern perimeter on Betty Martin Road. Service enters the Center from a riser pole with fused cutouts located across from Educational Building 2. The underground service emanates and terminates in pad-mounted, utility-owned transformers. Each transformer with corresponding meter serves the respective building with the exception of Buildings 1, 7 and 8.

Building 1 and Building 8 are served from the same transformer, but separately metered. Building 7 is sub fed from Building 8 and shares the same meter. Cafeteria Building 4 and Dormitory Building 6 each has a 600 kW diesel engine generator and associated automatic transfer switch (ATS) located outside the respective building.

Likewise Administration/Dental-Medical Building 5 has a 300 kW, diesel engine generator and associated ATS located outside near the transformer.

Pad Utility

Utility Utility

No

34.5/19.92 kV, 3-Phase

480/277 Volt, 3-Phase, 4 WireUnderground

OverheadPrimary Service

Secondary Service

Distribution Characteristics

5. Fuel Distribution System

Number of Deficiencies = 1

4. Storm Water System Number of Deficiencies = 1

Drain Type On-Site Storm Water Management

Surface Runoff N/A

Ownership Maintenance Responsibility System Capacity Adequate System Condition

Center Yes FairCenter

Comments: The site drainage is through surface run-off, swales and underground piping leading to a drainage ditch running the full length of the Center along the west edge of the site. The adequacy of the system is not good. The drainage swales are full of debris and vegetation. Some areas on the campus have excessive standing water after heavy rain that drain ver slowly.

Gas Company Metering

Individual

Ownership Maintenance Responsibility System Capacity Adequate System Condition

Center Center Yes Good

7. Electrical (Service)

Transformer Maint Resp

Utility

System Capacity Adequate System Condition

Yes Good

Generator

Diesel

ATS MTS

Yes No

6. Central Plant: None

Metering Individual

Page: 3 Date: 06/27/2022 of 4

Comments:

Telephone Company

On-site Line Owner

AT & T provides telephone service to the Center with two T1 lines coming from a pole located at the southeast corner of the Center near the substation. The T1 lines terminate in the telephone service main closet (MC) located in Building 5. AT&T manages the T1 circuits that grant connectivity to Job Corps Data Center (JCDC).

AT&T provides local telephone service. JCDC provides digital voice long distance telephone voice over Internet protocol (VoIP) through voice gateway Cisco 1800 and Cisco 6500 switch. The MC provides connections to other buildings via underground fiber optics for voice and data communication. Connections in buildings from the switches to the outlets are by CAT 5. Two 3 kVA uninterruptible power supply (UPS) module protect sensitive data communication equipment in the MC from power surges and drops in the line voltage and maintains the power requirement of the system for 15 to 20 minutes in case of an outage. The fire alarm system on Center is network configured with the central fire alarm control/annunciator panel located in Security Office in Building 5 and is monitored by Simplex Grinnell via telephone lines. Fire alarm systems in Buildings 3 and 4 have speakers with pre-recorded voice announcement and microphones at the panel locations. The Center currently has a fire alarm maintenance contract. The security system includes pad-mounted electric vehicular barrier arm operator, DOL/JCDC installed interior and exterior surveillance closed circuit television CCTV cameras and access card readers at buildings main entrance, multi-display color monitors, scanner, metal detector and door alarms with magnetic contacts. Cameras are strategically installed inside and outside the buildings. JCDC maintains and monitors the cameras on-line 24/7. JCDC grants the Center limited access to cameras monitoring from web-based computer with password. Dormitory, recreation, education and administration facilities have TV cable network for entertainment.

AT&T (local) and JCDC by AT&T (long distance)

Maint. Responsibility

Utility Utility

Security Surveillance Closed Circuit Television, Magnetic Contacts

9. Electrical (Communication/Alarm/Security)

Yes

Central

VOIP

System Capacity Adequate System Condition

GoodYes

8. Electrical (Site Lighting)

Roadways Parking Walkways Building Outdoor Sports

Mounting

Control

Pole Pole Pole Building Sport Light

Photocell, Switch, Contactor

Photocell, Switch, Contactor

Photocell, Switch, Contactor

Photocell, Switch, Contactor

Switch, Lighting Contactor

System Ownership Maintenance Responsibility System Capacity Adequate System Condition

Center Center Yes Good

Comments: The site lighting includes building-mounted, pole-mounted HID lights and bollards, which are controlled by photocells. The utility company owns and maintains all pole lights along the roadways. The Center owns and maintains all pole lights along the walkways, building-mounted exterior lights and bollards. The bollards are installed in the front and back courtyard of the dormitory.

Number of Deficiencies = 1

Number of Deficiencies = 10

STORAGE TANKS: None

Fire Alarm Security

Page: 4 Date: 06/27/2022 of 4

ACCESSIBILITY

Yes

UnknownNoNoNo

Nationally Registered Site

Site Eligible for National Register

Located in Historic District

Archaeological Significance

Earthquake Risk Low High LowHigh HighIBC High

LightningEarthquake Def. Authority Flooding Tornado Hurricane Forest

Fire

Accessible Parking: Accessible Slope:

Yes

Curb Cuts:

Yes

Ramps:

YesYes

Site Accessible Route:

GENERAL SITE CONDITION

Rating X

Good Fair Poor

Drainage swales do not adequately conduct water away from site.

HISTORIC PRESERVATION

NATURAL HAZARDS

The site condition is not impacting the functional use of the facilities.

The site condition IS impacting the functional use of the facilities.

The site condition IS SIGNIFICANTLY impacting the functional use of the facilities.

Active Energy Use Reduction Program

Active Water Use Reduction Program

Approximate or Measured Waste Recycled

Use of School Dude or CMMS for Preventative Maintenance

Green Purchasing Policy Practiced

Site Stormwater Absorption Measures in Place

Center has Onsite Renewable Energy (PV or Wind)

Center has a Chartered Green Committee & Roster

Center Uses Green Cleaning Practices

SUSTAINABILITY

Comments: The automotive shop has a compliant vehicle parts washer to collect contaminated water.

Yes

Yes

NO

NO

Yes

Yes

Yes

Yes

0 %

Building Descriptions and Structures

BUILDING 1 - VOCATIONAL EDUCATION/MAINTENANCE

AUTOMOTIVE

INSTRUCTOR

CLASSROOM

STORAGE

TOOLS

API VOCATION

(ROUSTABOUT)

INSTRUCTOR

MAINTENANCE

MAINTENANCE

OFFICE

CTT

SUPERVISOR

CTC

COUNSELOR

COMMUNICATIONS

PROPERTY OFFICER

TOOLS

MEZZANINE

MEZZANINE

FIRST FLOOR

MECH/

STORAGE

STORAGE

M W

UNISEX

TOILET

OUTSIDE

STORAGE

FLAMMABLE

STORAGE

COMPUTER

ROOM

CLASSROOM

STORAGE

JAN

ELEC

UP

SHIPS LADDER

DN

CARVILLE, LOUISIANA

CARVILLE JOB CORPS CENTER

BUILDING 1

MAINTENANCE

60'30'15'0

VOCATIONAL EDUCATION/

VOCATION/THEORY

STORAGE SUPPORT

NON-ACADEMIC

Building Descriptions

Page: 1 of 45

Building: 0001 - VOCATIONAL EDUCATION/MAINTENANCE

BUILDING ENVELOPE

Foundation RoofBuilding

Concrete Structural Steel Steel

Brick Masonry Metal Siding

Wall Roof Rigid Batt

Metal Overhead - Metal Frame Metal Unit - Metal Frame Storefront - Storefront Frame

AccessibilityFeature

GSF NSF Year Built Use Group Historic Ownership #Floors

Business 12,700 11,269 2 Owned 2004 Not Evaluated

Comments: The stairs to the storage mezzanine have open risers.

REAL ESTATE

Access to Building

Ramps

Entrance

2nd Egress

Visual Alarm

Corridor/Aisle

Rooms

Stairs

Elevator

Restrooms

Drinking Fountain

Telephone

Yes

Yes

Yes

Yes

Yes

Yes

Yes

No

No

Yes

Yes

N/A

ACCESSIBILITY

Structural Systems1.

Exterior Walls2.

Insulation4.

Exterior Doors5. Number of Deficiencies = 1

Material Drainage Year Life

Type Area Served

Metal Gutters and Downspouts 2004 21 Gable Entire Building

Number of Deficiencies = 13. Roof

Entire Building

Area Served

Page: 2 of 45

Building: 0001 - VOCATIONAL EDUCATION/MAINTENANCE

INTERIOR FINISH

Carpet Tile Ceramic Tile Concrete Epoxy Paint Vinyl Tile

Comments: Ground moisture migration to buildings cause vinyl tile floor finish deterioration. The corridor and common areas of the building are especially affected.

CMU Ceramic Tile Drywall Fence

Metal Unit - Metal Frame Overhead Grille - Metal Frame

Wood Unit - Metal Frame

VERTICAL CIRCULATION

Metal Ladder Metal Stairs Comments: Metal ladders lead to the storage mezzanine in the automotive repair vocational shop and the center maintenance shop. These ladders have locked metal closures that prevent access to the ladders without the proper key.

Double Hung - Aluminum Frame; Single Glazing; Fixed - Aluminum Frame; Single Glazing;

Fixed - Metal Frame; Single Glazing; Fixed - Metal Frame; Wire Glass Glazing;

Acoustical Tile Exposed Structure Gypsum Board

Windows6.

Floors1.

Interior Walls2.

3.

Interior Doors4.

Ceilings

Page: 3 of 45

Building: 0001 - VOCATIONAL EDUCATION/MAINTENANCE

Mechanical

Mechanical

Automobile Exhaust

Restroom

Shop Area

Shop Area

Comments:

Comments:

Each of the three shops is ventilated by at least one sidewall exhaust fan (typical, Loren Cook, 3/4 HP, 2300 CFM @ 3/8" water gage) interlocked with a motor-operated damper at one or more wall intake louvers.

The automotive shop has an auto exhaust system with two flexible drops.

Ventilation Area Served

Split Direct Expansion (Air

Source)

Packaged Direct

Expansion (Air Source)

Single Duct

Window Unit

Refrigerant

Refrigerant

Electric

Electric

Mechanical

Mechanical

None

None

Classrooms and Offices

Classrooms

Exhaust Ventilation

The DX coils (Trane) in both maintenance and automotive shops are provided cooling by condensing units (Trane #2TTAOO60A3000AA, 5 ton, built 8/2003).

The classroom in API has a window A/C for cooling.

Comments:

Comments:

Number of Deficiencies = 1

Heat Source

Heat Distribution

Piping System

Control System

Fresh Air Intake

Energy Conservation

Measure

Area Served

The American Petroleum Institute (API) vocation is located in the middle third of the building. The classroom in the API is heated by a Carrier window unit with an electric resistance heater.

There are ten unit heaters (typical, Trane #GPND004ADF2000E, 36.5 MBH output, built 2003) that serve the shops and storage rooms.

The classrooms and offices in each of the maintenance and automotive shops are served by a furnace (Trane 96 MBH output, built 8/2003).

Comments:

Comments:

Comments:

HVAC

Heat1.

Electric Resistance

Gas-Fired

Gas-Fired Furnace

Window Unit

Unit Heater

Single Duct

None

None

None

Electric

Electric

Electric

Mechanical

Mechanical

Mechanical

None

None

None

Classrooms

Shop Area

Classrooms and Offices

Ventilation2.

System Type

Number of Deficiencies = 3

Air Distribution

Piping System

Control System

Fresh Air Intake

Energy Conservation Area

Served

3. Air Conditioning

Page: 4 of 45

Building: 0001 - VOCATIONAL EDUCATION/MAINTENANCE

Domestic hot water is provided by two water heaters (Rheem #EGSP20, 20 gallon, 2 kW, 9/2003), each located on the mezzanine level at each end of the building.

Comments:

Cast Iron None Cast Iron

Electric Water Cooler Fixed Emergency Eyewash Hose Bibb Lavatory Mop Sink Urinal Wall Hydrant Water Closet (Flush Valve)

Gas (Natural)

None None ABC Type Fire Extinguisher

Comments: Underground service is provided from a 150 kVA pad-mounted, utility-owned transformer located north of the building. The utility meter is installed on the building north exterior wall. Service enters the building and terminates in a 200A MCB, 480/277V, 3-phase, 4 wire main distribution panel (MDP) located in the main electrical room. The MDP serves a 30 kVA and a 45 kVA dry type, step-down transformers and a 60A MCB panel which serves 480/277V loads in the automotive shop. The step-down transformers serve all 120/208V loads via panels located in the maintenance, automotive and API shops. The automotive shop additionally has a 125A, 120/208V shunt trip panel which provides emergency shut off for power tools. The same 200A MDP panelboard also sub-feeds Building 8.

Copper Copper Electric None No

Hot Water Cold Water Water Heater Water Treatment HW Storage Tank

Grease InterceptorWaste / Vent Interior Storm

Service Entrance Electrical Characteristics Distribution Equipment Wiring Devices

Compact Fluorescent Fluorescent High Intensity Discharge (HID) Comments: Building-mounted site lighting is controlled by the building-mounted photocell. The main building entrance is accented with two wall-mounted decorative fluorescent sconces and two canopy-mounted recessed compact fluorescent down lights.

Main Panelboard 277/480V, 3-Phase, 4 Wire Panelboards Receptacles, GFCI, Switches

Sprinkler System Stand Pipe System Fire Suppression

PLUMBING

Water Distribution1.

Sanitary Distribution2.

Fixtures3. Number of Deficiencies = 1

Fuel Distribution4.

FIRE PROTECTION

ELECTRICAL SERVICES

Exterior Lighting1.

LIGHTING

Page: 5 of 45

Building: 0001 - VOCATIONAL EDUCATION/MAINTENANCE

FIRE ALARM

Comments: The fire alarm control/annunciator panel is an addressable Simplex 4100U panel, located in the main lobby area and connected to the central fire alarm system annunciator panel located in the security office in Building 5.

Comments: The building is connected to the center LAN system by fiber optic cable, utilizing Cisco switches.

Interior and exterior security cameras are remotely monitored by JCDC and from the security office in Building 5. Access card readers are installed at the building entrances.

Audible Alarm Control/Annunciator Panel Duct Smoke Detector Heat Detector Manual Pull Station Smoke Detector Visual Alarm

Connected to Main System Closed Circuit TV None TV with VCR

Telephone Security Public Address Television

Comments: Recorded footcandle levels include natural light contribution. Explosion proof light fixtures and on/off switch are provided in the flammable storage.

Comments: Combination type exit sign emergency light fixtures are provided at building exits.

High Intensity Discharge (HID)

T8 - Fluorescent

T8 - Fluorescent

T8 - Fluorescent

T8 - Fluorescent

T8 - Fluorescent

T8 - Fluorescent

High Intensity Discharge (HID)

Vocational

Storage/Warehouse-Active

Classrooms

Corridors & Stairs

Toilets

Offices

Equipment Rooms (Elec/Mech)

Maintenance Shop

Area Recommended Recorded Light Type

Battery Backup Battery Backup

Emergency Exit

Number of Deficiencies = 1

Interior Lighting2. Number of Deficiencies = 1

Emergency /Exit Lighting3.

COMMUNICATION

Electric Water Gas Yes YesYes

BUILDING UTILITY METERING

Type Location N/A N/A

CARBON MONOXIDE DETECTION

Detection Required No

Number of Deficiencies = 0

Page: 6 of 45

Building: 0001 - VOCATIONAL EDUCATION/MAINTENANCE

GENERAL BUILDING CONDITION

Rating X Good

Fair Poor

The facility condition is not impacting the functional use of the facility.

The facility condition IS impacting the functional use of the facility.

The facility condition IS SIGNIFICANTLY impacting the functional use of the facility.

Structure: Good Exterior: Good Interior: Good Mechanical: Good Electrical: Good

IMPAIRMENT

Potentially Impaired

DOL Responded

DOL Determination

Potential Impaired Comments DOL Determination Discussion/Comments

BUILDING 2 - EDUCATION/LIGHT VOCATION

MECH

ELEC

HC

HC

J

J

M

W

READING II/MATH

HISET

API

VOCATIONAL

CLASSROOM

(ROUSTABOUT)

CAREER

SKILLS

INSTRUCTOR

WOW/LIBRARY

INTRODUCTION

TO CENTER LIFE

SCHEDULING

TEST SPECIALIST

CTR

SPECIALIST

CPP/CT SUPERVISOR

FIBER OPTICS/

COMMUNICATIONS

STAFF LOUNGE

STORAGE

COPY ROOM

ACADEMIC

CLERK

STOR

CLOTHING/

INTERVIEW

PRACTICE

CAREER PREP.

MANAGER

COUNSELOR

CAREER

COUNSELOR

SPECIALIST

HIGHSCHOOL

DIPLOMA

HIGHSCHOOL

DIPLOMA

PROGRAM DIRECTOR

CAREER

COUNSELOR

SPECIALIST

MECH/ELEC

EQUIPMENT

CARVILLE, LOUISIANA

CARVILLE JOB CORPS CENTER

BUILDING 2

VOCATION

60'30'15'0

EDUCATION/ LIGHT

ACADEMIC

NON-ACADEMIC

VOCATION/THEORY

ADMINISTRATION

Page: 7 of 45

Building: 0002 - EDUCATION/LIGHT VOCATION

BUILDING ENVELOPE

Foundation RoofBuilding

Concrete Loadbearing Masonry Wood

Brick Masonry

Wall Roof Rigid Batt

Metal Unit - Metal Frame Storefront - Storefront Frame

AccessibilityFeature

GSF NSF Year Built Use Group Historic Ownership #Floors

Business 13,877 8,882 1 Owned 2004 Not Evaluated

REAL ESTATE

Access to Building

Ramps

Entrance

2nd Egress

Visual Alarm

Corridor/Aisle

Rooms

Stairs

Elevator

Restrooms

Drinking Fountain

Telephone

Yes

N/A

Yes

Yes

Yes

Yes

Yes

N/A

N/A

Yes

Yes

N/A

ACCESSIBILITY

Structural Systems1.

Exterior Walls2.

Insulation4.

Exterior Doors5.

Material

Roof’s asphalt shingle have deteriorated, are no longer flexible but brittle and leaking. Roof life estimated from observation during the March, 2022 Facility Survey.

Drainage Year Life

Type Area Served

Asphalt Shingles Scuppers and Downspouts 2004 0 Gable Entire Building

Number of Deficiencies = 1

Comments:

3. Roof

Page: 8 of 45

Building: 0002 - EDUCATION/LIGHT VOCATION

INTERIOR FINISH

Carpet Ceramic Tile Concrete Vinyl Tile

Acoustical Folding Partition CMU Ceramic Tile Drywall

Metal Unit - Metal Frame Wood Unit - Metal Frame

Mechanical

Mechanical

Restroom

Janitor's Closet

Ventilation Area Served

VERTICAL CIRCULATION

None

Double Hung - Aluminum Frame; Single Glazing; Fixed - Metal Frame; Single Glazing;

Acoustical Tile Exposed Structure Gypsum Board

Exhaust Ventilation

Number of Deficiencies = 1

Number of Deficiencies = 3

Windows6.

Floors1.

Interior Walls2.

3.

Interior Doors4.

Heat Source

Heat Distribution

Piping System

Control System

Fresh Air Intake

Energy Conservation

Measure

Area Served

Two air handlers, AHU-2A & B, (Trane #MCCB021, 15 HP & #MCCB014, 10 HP; both 460/3 and built in 2003) supply air to the entire building, the larger to the west side and the other to the east. Each of the two main supply ducts branch both north and south. Duct-mounted electric resistance heaters are just downstream of each change in direction, therefore, requiring four heaters and creating four zones (NE, SE, SW and NW).

Comments:

HVAC

Heat1.

Electric Resistance

Multi- Zone/Single

AHU

None Direct Digital Control (DDC)

Mechanical None Entire Building

Ventilation2. Number of Deficiencies = 2

Page: 9 of 45

Building: 0002 - EDUCATION/LIGHT VOCATION

The water heater (Rheem #ELD52, 50 gallon, 4.5 kW, built 01/2003) is located in a janitor's closet.Comments:

Cast Iron None None

Electric Water Cooler Hose Bibb Lavatory Portable Bottled Water Cooler Sink Urinal Water Closet (Flush Valve)

None

None None ABC Type Fire Extinguisher

Copper Copper Electric None No

Hot Water Cold Water Water Heater Water Treatment HW Storage Tank

Grease InterceptorWaste / Vent Interior Storm

Split Direct Expansion (Air

Source)

Single Duct Refrigerant Direct Digital Control (DDC)

Mechanical None Entire Building

Sprinkler System Stand Pipe System Fire Suppression

PLUMBING

Three condensing units provide cooling to the air handlers, AHU-2A & B, (Trane #MCCB021, 15 HP & #MCCB014, 10 HP; both 460/3 and built in 2003). Condensing unit ACCU-2A (Trane #RAUCC404BX03, 40 ton) serves AHU-2A and two condensing units (both Trane #TTA180C400FA, 15 ton each) serve AHU-2B. All condensing units are 460/3 and were built in 2003. The AHUs supply air to the entire building, the larger system to the west side and the other to the east. Each of the two main supply ducts branch both north and south. Duct-mounted electric resistance heaters are just downstream of each change in direction, therefore, requiring four heaters (for reheat or dehumidification) and creating four zones (NE, SE, SW and NW).

Comments:

System Type

Air Distribution

Piping System

Control System

Fresh Air Intake

Energy Conservation Area

Served

Water Distribution1.

Sanitary Distribution2.

Fixtures3.

Fuel Distribution4.

Number of Deficiencies = 1FIRE PROTECTION

Page: 10 of 45

Building: 0002 - EDUCATION/LIGHT VOCATION

Comments: Underground service is provided from a 300 kVA pad-mounted utility-owned transformer with a meter mounted on the transformer. The service enters the building to a 400A main distribution panel (MDP) with a 400A main circuit breaker (MCB) located in the electrical room. The panel serves a 125A main-lug-only (MLO) panel providing for the building lighting loads. A 45 kVA step-down transformer is utilized for 120/208 system voltage and feeds a 250A, 120/208V two section panel with a 150A MCB. The 45 kVA transformer and both panels are located in the main electrical room. Lightning arresters (by Delta) protect the 400A main distribution panel and condensing units.

FIRE ALARM

Comments: The fire alarm control/annunciator panel is an addressable Simplex 4100U panel, located in the main lobby area, connected to the central fire alarm system annunciator panel located in the security office in Building 5.

Service Entrance Electrical Characteristics Distribution Equipment Wiring Devices

Audible Alarm Control/Annunciator Panel Duct Smoke Detector Heat Detector Manual Pull Station Smoke Detector Visual Alarm

Comments: Recorded footcandle levels include natural light contribution. Building lighting is served from a 277V power. Occupancy sensors are provided for lighting control in the offices and toilet rooms.

Compact Fluorescent Fluorescent High Intensity Discharge (HID) Comments: Building-mounted and pole-mounted site lighting is controlled by a building-mounted photocell through a lighting contactor with an override switch. The lighting contactor and the override switch are located in the electrical room. The main building entrances are accented with wall-mounted decorative fluorescent sconces and canopy-mounted recessed compact fluorescent down lights.

T8 - Fluorescent

T8 - Fluorescent

T8 - Fluorescent

T8 - Fluorescent

T8 - Fluorescent

T8 - Fluorescent

T8 - Fluorescent

Classrooms

Vocational

Toilets

Equipment Rooms (Elec/Mech)

Storage Rooms

Corridors & Stairs

Offices

Area Recommended Recorded Light Type

Selected Lighting w/ Battery Battery Backup

Main Distribution Panel 277/480V, 3-Phase, 4 Wire Panelboards Receptacles, GFCI, Switches

Emergency Exit

Number of Deficiencies = 2

ELECTRICAL SERVICES

Exterior Lighting1.

Interior Lighting2.

Emergency /Exit Lighting3.

Page: 11 of 45

Building: 0002 - EDUCATION/LIGHT VOCATION

Comments: The building is connected to the center LAN system by fiber optic cable, utilizing Cisco switches.

Interior and exterior security cameras are remotely monitored by JCDC and from the security office in Building 5. Access card readers are installed at the building entrances. A timer (by Simplex) is located in the main lobby area near the main fire alarm panel. TVs with VCRs are also provided.

Connected to Main System Closed Circuit TV None None

Telephone Security Public Address Television

GENERAL BUILDING CONDITION

Rating

Comments:

X Good Fair Poor

HVAC controls are malfunctioning. Roofing is deteriorated

COMMUNICATION

The facility condition is not impacting the functional use of the facility.

The facility condition IS impacting the functional use of the facility.

The facility condition IS SIGNIFICANTLY impacting the functional use of the facility.

Electric Water Gas Yes N/AYes

BUILDING UTILITY METERING

Structure: Good Exterior: Fair Interior: Good Mechanical: Fair Electrical: Good

Type Location N/A N/A

CARBON MONOXIDE DETECTION

Detection Required No

Number of Deficiencies = 0

IMPAIRMENT

Potentially Impaired

DOL Responded

DOL Determination

BUILDING 3 - RECREATION/GYMNASIUM

FIBER OPTICS

STORAGE

ELEC

ARTS & CRAFTS

WOMEN'S WEIGHT ROOM

GAME ROOM

UNIFORM STOR/

SUPPLIES

STUDENT

LEADERSHIP

RECREATION

SUPERVISOR

BARBER SHOP/

LAUNDRY

STORE

CANTEEN

STORAGE

MEDIA ROOM

WOMEN'S LOCKER ROOM

MEN'S LOCKER ROOM

J

MECH

PLATFORM

ABOVE

LOBBY

OFF.

MECH/ELEC

EQUIPMENT

OFF.

MECH/

ELEC

EQUIP

CARVILLE, LOUISIANA

CARVILLE JOB CORPS CENTER

BUILDING 3

RECREATION/GYMNASIUM

60'30'15'0

RECREATION

STORAGE SUPPORT

Page: 12 of 45

Building: 0003 - RECREATION/GYMNASIUM

BUILDING ENVELOPE

Foundation RoofBuilding

Concrete

Concrete

Loadbearing Masonry

Structural Steel

Wood

Steel

Brick Masonry

Wall Roof Rigid Batt

AccessibilityFeature

GSF NSF Year Built Use Group Historic Ownership #Floors

Assembly 20,034 15,464 1 Owned 2004 Not Evaluated

REAL ESTATE

Access to Building

Ramps

Entrance

2nd Egress

Visual Alarm

Corridor/Aisle

Rooms

Stairs

Elevator

Restrooms

Drinking Fountain

Telephone

Yes

N/A

Yes

Yes

Yes

Yes

Yes

N/A

N/A

Yes

Yes

N/A

ACCESSIBILITY

Structural Systems1.

Exterior Walls2.

Insulation4.

Material

Architectural Shingles

Drainage Year Life

Type Area Served

Asphalt Shingles

Asphalt Shingles

Gutters and Downspouts

Gutters and Downspouts

Gable

Gable

Gymnasium

Recreation Area

Number of Deficiencies = 1

Comments:

3. Roof

Recreation Area

Gymnasium

Page: 13 of 45

Building: 0003 - RECREATION/GYMNASIUM

INTERIOR FINISH

Carpet Ceramic Tile Concrete Resilient Rubber Gym Floor Vinyl Tile Wood Sport Floor

Acoustical Folding Partition CMU Ceramic Tile Drywall Exposed Structure Fence

Metal Rollup Fire Shutter - Metal Frame Roll-up Grille - Metal Frame

Wood Unit - Metal Frame

VERTICAL CIRCULATION

Metal Ladder Comments: Metal ladders lead to two mechanical equipment platforms which are located within the gymnasium.

These ladders have locked metal closures that prevent access to the ladders without the proper key.

Metal Unit - Metal Frame Storefront - Storefront Frame

Double Hung - Aluminum Frame; Single Glazing; Fixed - Aluminum Frame; Single Glazing;

Fixed - Metal Frame; Single Glazing;

Acoustical Tile Exposed Structure Gypsum Board Wood

Number of Deficiencies = 1

Exterior Doors5.

Windows6.

Floors1.

Interior Walls2.

3.

Interior Doors4. Number of Deficiencies = 2

Page: 14 of 45

Building: 0003 - RECREATION/GYMNASIUM

Mechanical

Mechanical

Mechanical

Toilet/Shower

Janitor's Closet

Gymnasium

Comments: The gymnasium is ventilated by the large sidewall propeller exhaust fan high in the SE wall.

Ventilation Area Served

Split Direct Expansion (Air

Source)

Split Direct Expansion (Air

Source)

Single Duct

Variable Air Volume

Refrigerant

Refrigerant

Direct Digital Control (DDC)

Direct Digital Control (DDC)

Mechanical

Mechanical

None

None

Gymnasium

Recreation Area

Exhaust Ventilation

There are four condensing units (Trane #TTA18044CAB00AE, 15 ton, manufactured in 3-2019 each unit) coupled to two air handling units (Trane #CSAA014UAL00, 7.5 hp) located on high platforms, one in the north and the other in the west corner of the gymnasium are providing cooling (30 ton each).

The up-flow air handler (Trane #MCCB021UA0B0UA, 15 HP, built 2003) in the NE mechanical equipment room supplies air to 16 VAV boxes. The air handler is provided cooling by a condensing unit (Trane #RAUCC404BX0300D, 40 ton, built 2003) set on-grade adjacent to the mechanical equipment room.

Comments:

Comments:

Heat Source

Heat Distribution

Piping System

Control System

Fresh Air Intake

Energy Conservation

Measure

Area Served

There are two air handlers (Trane #CSAA014UAL00) providing heat which are located on high platforms, one in the north and the other in the west corner of the gymnasium. Each air handler is equipped with a gas-fired duct furnace (Trane #GMND022AEF3000A, 225 MBH output).

The up-flow air handler (Trane #MCCB021UA0B0UA, 15 HP, built 2003) in the NE mechanical equipment room supplies air to 16 VAV boxes provided with electric heaters.

Comments:

Comments:

HVAC

Heat1.

Gas-Fired Furnace

Electric Resistance

Single Duct

Variable Air Volume

None

None

Electric

Direct Digital Control (DDC)

Mechanical

Mechanical

None

None

Gymnasium

Recreation Area

Ventilation2.

System Type

Number of Deficiencies = 2

Air Distribution

Piping System

Control System

Fresh Air Intake

Energy Conservation Area

Served

Page: 15 of 45

Building: 0003 - RECREATION/GYMNASIUM

Two electric water heaters (Rheem #ELD66, 65 gallon, built 9/2002; #ELD52, 50 gallon, built 1/2003;

both 4.5 kW) are located in a dedicated room at the SW end of the corridor.

Comments:

Cast Iron None None

Electric Water Cooler Hose Bibb Lavatory Mop Sink Service Sink Shower Urinal Water Closet (Flush Valve)

Gas (Natural)

None None ABC Type Fire Extinguisher

Comments: Underground service is provided from a 300 kVA pad-mounted, utility-owned transformer with a meter mounted on the transformer. The service enters the building to a 600A distribution panel with a 600A main circuit breaker (MCB) located in the electrical room. The panel serves a 125A MLO panel providing for the building lighting loads and a 400A main-lug-only (MLO) panelboard located on the north building wall and providing for the gymnasium's HVAC and lighting loads. A 45 kVA step-down transformer is utilized for 120/208 system voltage and feeds a 250A panel with a 150A MCB, both located in the electrical room. Lightning arresters (by Delta) protect the main distribution panel and condensing units.

Copper Copper Electric None No

Hot Water Cold Water Water Heater Water Treatment HW Storage Tank

Grease InterceptorWaste / Vent Interior Storm

Service Entrance Electrical Characteristics Distribution Equipment Wiring Devices

Compact Fluorescent Fluorescent High Intensity Discharge (HID) Comments: Building-mounted and pole-mounted site lighting are controlled by a building-mounted photocell through a lighting contactor with an override switch. The lighting contactor and the override switch are located in the electrical room. The main building entrances are accented with wall-mounted decorative fluorescent sconces and canopy-mounted recessed compact fluorescent down lights.

Main Distribution Panel 277/480V, 3-Phase, 4 Wire Panelboards Receptacles, GFCI, Switches

Sprinkler System Stand Pipe System Fire Suppression

PLUMBING

Water Distribution1.

Sanitary Distribution2.

Fixtures3.

Fuel Distribution4.

FIRE PROTECTION

ELECTRICAL SERVICES Number of Deficiencies = 3

Exterior Lighting1.

Page: 16 of 45

Building: 0003 - RECREATION/GYMNASIUM

FIRE ALARM

Comments: The fire alarm control/annunciator panel is an addressable Simplex 4100U panel, located in the main lobby area, connected to the central fire alarm system annunciator panel located in the security office in Building 5. Also, system speakers with pre-recorded voice are provided throughout the building with a microphone at the panel location. Beam type smoke detectors are provided in the gymnasium.

Comments: The building is connected to the center LAN system by fiber optic cable, utilizing Cisco switches.

Interior and exterior security cameras are remotely monitored by JCDC and from the security office in Building 5. Access card readers are installed at the building entrances.

Audible/Speaker Alarm Beam Smoke Detector Control/Annunciator Panel Duct Smoke Detector Heat Detector Manual Pull Station Smoke Detector Visual Alarm

Connected to Main System Closed Circuit TV None Local Cable Company

Telephone Security Public Address Television

Comments: Recorded footcandle levels include natural light contribution. Building lighting is served from a 277V power. Occupancy sensors are provided for lighting control in the offices and toilet rooms. Gymnasium lighting is controlled through the lighting contactor. HID light fixtures in the gymnasium have quartz re-strike feature.

Comments: Battery backup emergency light fixtures are utilized in the gymnasium.

High Intensity Discharge (HID)

T8 - Fluorescent

T8 - Fluorescent

T8 - Fluorescent

T8 - Fluorescent

T8 - Fluorescent

T8 - Fluorescent

Compact Fluorescent

T8 - Fluorescent

Gymnasium

Recreation

Corridors & Stairs

Toilets

Offices

Storage Rooms

Locker Room

Shower

Equipment Rooms (Elec/Mech)

Area Recommended Recorded Light Type

Selected Lighting w/ Battery Battery Backup

Emergency Exit

Number of Deficiencies = 2

Interior Lighting2. Number of Deficiencies = 1

Emergency /Exit Lighting3.

COMMUNICATION

Type Location N/A N/A

CARBON MONOXIDE DETECTION

Detection Required No

Page: 17 of 45

Building: 0003 - RECREATION/GYMNASIUM

GENERAL BUILDING CONDITION

Rating

Comments:

X Good Fair Poor

Some air conditioning units not functioning. Exterior is Fair due to need for a roof replacement.

The facility condition is not impacting the functional use of the facility.

The facility condition IS impacting the functional use of the facility.

The facility condition IS SIGNIFICANTLY impacting the functional use of the facility.

Electric Water Gas Yes YesYes

BUILDING UTILITY METERING

Structure: Good Exterior: Fair Interior: Good Mechanical: Fair Electrical: Good

IMPAIRMENT

Potentially Impaired

DOL Responded

BUILDING 4 - CAFETERIA

DINING

KITCHEN

SUPPLIES

OFFICE

FREEZER

DRY FOOD

STORAGE

DISHWASHING

SERVING

SOFT DRINKING

J

EQUIPMENT/

GENERATOR

SALAD BAR

REFRIGERATOR

W

M

M

W

WATER

HEATERS

ELEC

J

LOADING

DOCK

UP

CARVILLE, LOUISIANA

CARVILLE JOB CORPS CENTER

BUILDING 4

CAFETERIA

60'30'15'0

FOOD SERVICE

Page: 18 of 45

Building: 0004 - CAFETERIA

BUILDING ENVELOPE

Foundation RoofBuilding

Concrete Loadbearing Masonry Wood

Brick Masonry Storefront

Wall Roof Rigid Batt

Metal Unit - Metal Frame Storefront - Storefront Frame

AccessibilityFeature

GSF NSF Year Built Use Group Historic Ownership #Floors

Assembly 10,212 6,375 1 Owned 2004 Not Evaluated

REAL ESTATE

Access to Building

Ramps

Entrance

2nd Egress

Visual Alarm

Corridor/Aisle

Rooms

Stairs

Elevator

Restrooms

Drinking Fountain

Telephone

Yes

N/A

Yes

Yes

Yes

Yes

Yes

N/A

N/A

Yes

Yes

N/A

ACCESSIBILITY

Structural Systems1.

Exterior Walls2.

Insulation4.

Exterior Doors5.

Material

Roof’s asphalt shingle have deteriorated, are no longer flexible but brittle and leaking. Roof life estimated from observation during the March 2022 Facility Survey.

Drainage Year Life

Type Area Served

Asphalt Shingles Gutters and Downspouts 2004 0 Hip Entire Building

Number of Deficiencies = 1

Comments:

3. Roof

Entire Building

Page: 19 of 45

Building: 0004 - CAFETERIA

INTERIOR FINISH

Ceramic Tile Concrete Quarry Tile Vinyl Tile

CMU Ceramic Tile Drywall

Aluminum Cafe Unit - Metal Frame Metal Unit - Metal Frame

Metal Unit - Wood Frame

VERTICAL CIRCULATION

Concrete Stairs Comments: There are exterior concrete steps leading from the loading dock to grade.

Fixed - Aluminum Frame; Single Glazing;

Acoustical Tile Gypsum Board Plaster

Number of Deficiencies = 2

Windows6.

Floors1.

Interior Walls2.

3.

Interior Doors4.

Heat Source

Heat Distribution

Piping System

Control System

Fresh Air Intake

Energy Conservation

Measure

Area Served

Air handler AHU-4A (Trane #MCCB021N0A, 15 HP, built 6/2003) serving the dining hall is provided with a gas-fired duct furnace (Trane #GMND030, 240 MBH output, direct vent, built 6/2003) and is located in the main mechanical room.

Air handler AHU-4B (Trane #MCCB012N0A, 7.5 HP, built 6/2003) serving the kitchen is provided with a gas-fired duct furnace (Trane #GMND022AEF, 180 MBH output, direct vent, built 6/2003) and is located in the main mechanical room.

Comments:

Comments:

HVAC

Heat1.

Gas-Fired Furnace

Gas-Fired Furnace

Single Duct

Single Duct

None

None

Direct Digital Control (DDC)

Direct Digital Control (DDC)

Mechanical

Mechanical

None

None

Kitchen

Dining Hall

Page: 20 of 45

Building: 0004 - CAFETERIA

Mechanical

Mechanical

Restroom

Kitchen Hood

Comments: The dishwasher and the server hood as well as the main kitchen hood (Avtec #AFDI, 15 LF X 10 LF) are ventilated by rooftop exhaust fans. Two units (Loren Cook #245SQNB) supply tempered make-up air to compensate for this exhaust.

Two gas-fired water heaters (PVI #40V125, 125 gallon, 399 MBH input, built 4/2003) provide the domestic hot water. A recirculating pump is also provided. The dishwasher is equipped with a booster water heater (Hatco #C-45, 45 kW).

Comments:

Comments:

Cast Iron Outdoor None

A 1,000-gallon grease interceptor is located outside the building.

Electric Water Cooler Hose Bibb Lavatory Mop Sink Multi-Compartment Sink Service Sink Sink Urinal Water Closet (Flush Valve)

Gas (Natural)

Ventilation Area Served

Copper Copper Gas-Fired None No

Hot Water Cold Water Water Heater Water Treatment HW Storage Tank

Grease InterceptorWaste / Vent Interior Storm

Split Direct Expansion (Air

Source)

Split Direct Expansion (Air

Source)

Single Duct

Single Duct

Refrigerant

Refrigerant

Direct Digital Control (DDC)

Direct Digital Control (DDC)

Mechanical

Mechanical

None

None

Kitchen

Dining Hall

PLUMBING

Exhaust Ventilation

The air handler AHU-4A (Trane #MCCB021N0A, 15 HP, built 6/2003) serving the kitchen and adjacent…