This document is a product submittal for XTherm Type WH water heaters to be used in replacing boilers at Building 346 for the Department of Justice Bureau of Prisons South Central Regional Office under solicitation number 15B50023Q00000004. The submittal provides specifications for three water heater models in the 1005A to 2005A size range, including dimensions, power requirements, recovery rates, clearances, and venting and control options. Required features include a copper or cupronickel heat exchanger, ASME stamping, low NOx emissions certification, and touchscreen or remote control interfaces.

View the file

Other files for this federal contract opportunity

Other files attached to SCRO-REPLACE BOILERS BUILDING 346, newest first.
File Type Posted
QUESTIONS.pdf PDF
Amendment 00004.pdf PDF
Amendment 004- Building 346 Replace Boilers SOW_1.pdf PDF
Amendment 00003.pdf PDF
Building 346 Replace Boilers SOW_1 - REVISED.pdf PDF
Site Visit 9-5-2023.pdf PDF
Amendment 00002.pdf PDF
Boiler Pictures.pdf PDF
QUESTIONS.pdf PDF
Amendment 00001.pdf PDF
04. Building 346 Replace Boilers SOW_1.pdf PDF
BRQ 15B50023Q00000004.pdf PDF
INSTRUCTIONS TO OFFERORS.pdf PDF
Show all 13

On GovTribe

Work with this file on GovTribe

  • Download the original file
  • Contacts named in this file
  • Similar government files
  • Ask GovTribe AI about this file

Text version

Part no.: 241872 Rev. 1 Effective: 09-01-20 Replaces 3500.291B Page 1 of 4

Product Submittal for XTherm®- Type WH

Water Heater

Models 1005A-2005A

Location:

Contractor:

Gas Type: Natural Gas Propane

97% Thermal efficiency at full rate

100% Factory fire-tested

VERSA IC® modulating controller with 7" color touchscreen display

Raymote™ remote connectivity provided standard

Soft-start ignition; 60% minimum fire

Full safety diagnostics with history

Status display lights

Cascade up to 8 heaters – no external sequencer required

Modbus RTU BMS Port

Maximum outlet water temperature: 180°F (82°C)

Maximum tank setpoint: 160°F (71°C)

Limited 25-year thermal shock warranty

Limited 5-year copper/10-year cupronickel primary heat exchanger warranty

Limited 10-year secondary heat exchanger warranty

SCAQMD Rule 1146.2 certified, Low NOx < 20 ppm

Must be used in conjunction with a storage tank for proper operation

Proudly assembled in the USA

Date:

Equipment Tags:

Model:

Prepared by:

Job:

Engineer:

Notes:

Indoor Outdoor

15B50023Q00000004 bop37573 Highlight

Part no.: 241872 Rev. 1 Effective: 09-01-20 Page 2 of 4

Job:

Features and Options

Heat Exchanger

Q Bronze headers

Q ASME HLW stamped; 160 PSIG MAWP

Q National board registered

Q Fin tubing

Copper (standard)

A-3 cupronickel

Q ASME powder-coated tube sheet

Q Silicone high-temp O-Rings

Q ASME pressure relief valve

125 PSIG (standard)

____PSIG (optional)

Q Air bleed valve, manual (2)

Q T&P gauge

Q Four-pass primary heat exchanger

Q Secondary stainless steel condensing heat exchanger - U stamped

Q Stainless steel evaporator plate

Q Boiler pump: bronze, 120V, 1Ø, 60Hz

Q Water hardness:____________ GPG

Power

Q 120V, 60Hz, 1Ø, power supply

Q 120/24V, 60Hz, transformer

Control

Q VERSA IC® built-in controller

Q 7" color HD touchscreen display

Q Raymote™ Wi-Fi remote connectivity

Q Cascade up to 8 heaters

Q Ignition module

3-Try (standard)

C-6 Single-try

Q Remote flame sensor

Q Fixed high limit, manual reset, 200ºF

Q On/off power switch

Q Flow switch

Q Blocked vent pressure switch

Q Freeze protection

Q Alarm dry contact

Q Pump outputs – pilot duty system

Q Programmable pump time delays

Q Water temperature sensor 10KΩ (2 mtd, 1 loose, 1 well)

Q Cold water protection

Q Blocked condensate switch

Q Modbus RTU BMS Port (Up to 115K baud rate, see Cat. 5000.73)

B-85 BMS Gateway, Modbus RTU to Modbus TCP, N2 Metasys, BACnet IP, or BACnet MS/TP

B-86 BMS Gateway, Modbus RTU to LonWorks

Burner

Q Hot surface ignition (HSI)

Q Radially-fired knitted burner

Gas Train

Q Fuel

Natural gas

Propane (minimum grade HD-5)

Q Dual-seat combination valve

Q Electronic modulating firing mode (WH7)

Construction

Q Indoor/outdoor construction

Q Enclosed front controls

Q PolyTuf powder coat finish

Q Rear connections (water, gas, vent, combustion air, condensate drain)

Q Design certified ANSI Z21.10.3/CSA 4.3

Q CSA Low-lead certified ≤ .25% lead

Q Front connection low-voltage wiring

Venting, cat IV

D-11 Vent termination, outdoor

D-15 Vent termination, sidewall

D-18 Adapter, boiler flue

D-19 Adapter, vent termination

D-32 Adapter, PVC vent, with vent temp limit, max return temp 170ºF (Factory-mounted only)

D-33 Adapter, CentrothermTM polypro vent, with vent temp limit, max return temp 190ºF (shipped loose)

D-37 Motorized combustion air damper

Options

B-31 Sensor well assembly (can be used for tank or system sensor)

E-5 Boiler alarm with 4" bell factory mounted shipped loose

E-15 Alarm with buzzer factory mounted shipped loose

F-10 Low water cut-off, manual reset & test button

I-5 High limit, adj. manual reset, 200ºF max

I-13 High limit, adj. auto reset, 200ºF max

I-14 High limit, adj. auto reset, 180ºF max

I-20 High limit, adj. manual reset, 180ºF max

M-1 Safety valve, motorized

M-10 Safety valve, solenoid

M-15 Safety valve, vent valve (requires M-1 or M-10)

S-1 Low gas pressure switch, manual reset

Z-4 T & P relief valve

Z-9 Thermometer

Z-12 Condensate treatment kit

TempTracker Mod+ Hybrid multi-unit controllers

(shipped loose)

B-36 2-4 heaters

B-37 5-10 heaters

B-38 11-16 heaters

B-39* EMS 4-20 mA remote setpoint interface

B-62* BACnet interface module (*requires B-36 to B-38)

Additional options or accessories

Part no.: 241872 Rev. 1 Effective: 09-01-20 Page 3 of 4

Job:

(1) For natural gas. Propane all sizes 1" NPT.

Ratings shown are for elevations up to 4,500 ft. De-rate above 4,500 ft; consult factory. No hardware changes required below 10,000 ft.

For direct vent applications, please contact the factory about relocating the pump.

CLEARANCES

Heater Side Minimum Clearances from

Combustible Surfaces

in. (mm)

Minimum Service Clearance

in. (mm)

Floor 0 0

Rear 12" (305) 36" (914)

Right Side 1" (25) 24" (610)

Left Side 1" (25) 1" (25)

Top Unobstructed 0

Front Open 24" (610)

Vent 1" (25) 1" (25)

* Separate power connections are factory-supplied and separate supply breakers must be field-supplied.

** Current draw is for heater only (Supply breaker must have delayed trip).

POWER REQUIREMENTS – AMPS*

Model

(WH7-)

Heater Amp

Draw*

Pump Amp Draw*

Soft 1-4 Gr.

Medium 5-15 Gr.

Hard 16-25 Gr.

1005A 12** 10 10 14

1505A 12** 10 14 17

2005A 18** 17 17 N/A

Model

(WH7-)

MBTUH (kW/h) Dimensions - inches (mm) Ship Weight

Lbs. (Kg)Input Output B Height D E F G(1)

NPT

K

Flue Ø L M N C/A Ø P R V Y

1005A

(293)

(284) 55-1/4 (1403)

(1143)

(194)

(940)

1-1/4 (32)

(152)

(1041)

11-1/2 (292)

(152)

47-1/8 (1197)

8-5/16 (211)

(330)

6-1/4 (159)

(483)

1505A (440)

(426)

67-1/8 (1705)

(1448)

(1499)

38-5/8 (981)

1-1/4 (32)

(203)

(1346)

12-5/8 (321)

(203)

59-1/8 (1197)

8-3/16 (208)

(330)

6-1/4 (159)

(560)

2005A (586)

(568)

81-1/8 (2061)

(1803)

(1829)

39-5/8 (1007)

(50)

(203)

65-1/2 (1664)

12-5/8 (321)

(203)

73-1/8 (1857)

8 3/16 (208)

(254)

6-1/2 (165)

(663)

*NOTE: Must be used in conjunction with storage tank for proper operation.

bop37573 Highlight

Part no.: 241872 Rev. 1 Effective: 09-01-20 Page 4 of 4

Job:

Model RECOVERY RATES (GPH) at stated ΔT (°F) (L/H)

20°F 30°F 40°F 50°F 60°F 70°F 80°F 90°F 100°F 110°F

1005A

(22231)

(14819)

(11113)

(9232)

(7411)

(6351)

(5556)

(4939)

(4447)

(4042)

1505A

(33379)

(22254)

(16689)

(13351)

(11125)

(9535)

(8346)

(7419)

(6677)

(6068)

2005A 11752

(44486)

(29654)

(22243)

(17795)

(14827)

(12711)

(11121)

(9883)

(8895)

(8089)

Raypak, Inc. 2151 Eastman Avenue, Oxnard, CA 93030 (805) 278-5300 www.raypak.com bop37573 Highlight

Date: 09/08/2023
Job:
Location: 344 Marine Forces Drive, Grand Prairie TX 75051
Equipment Tags:
Engineer:
Contractor:
Model: 1505A
Notes:
Prepared by:
Indoor: On
Outdoor: Off
Gas Type Natural Gas: On
Propane: Off
Copper standard: On
A3 cupronickel: Off
125 PSIG standard: On
undefined:
Boiler pump bronze 120V 1Ø 60Hz:
3Try standard: On
C6 Singletry: Off
Product Submittal for XTherm Type WH: 15B50023Q00000004
B85 BMS Gateway Modbus RTU to Modbus: On
B86 BMS Gateway Modbus RTU to LonWorks: Off
Natural gas: On
Propane minimum grade HD5: Off
D11: Off
D15: Off
D18: Off
D19: Off
D32: Off
D33: Off
D37 Motorized combustion air damper: Off
B31: Off
E5: Off
E15: On
F10: On
I5: On
I13: Off
I14: Off
I20: Off
M1: Off
M10: On
M15: Off
S1: On
Z4: On
Z9: On
Z12: Off
factory mounted: Off
factory mounted_2: Off
shipped loose: Off
shipped loose_2: Off
B36: Off
B37: Off
B38: Off
B39: Off
B62: On
Additional options or accessories:
undefined_2:
Product Submittal for XTherm Type WH_2:
1005A: Off
1505A: On
2005A: Off
1005A_2: Off
1505A_2: On
2005A_2: Off
Job_2:
1005A_3: Off
1505A_3: On
2005A_3: Off