154-B5154-003_DMV Widgeon CSC-Drawings_Final Bid Set.pdf
PDF 2 MB Posted
- Attached to
- DMV Norfolk Widgeon HVAC
- Solicitation number
- IFB-128682
- Issued by
- Nathalie CDP, Virginia
About this file
This file consists of final bid set drawings for the DMV Widgeon HVAC Replacement project located at 850 Widgeon Road, Norfolk, Virginia 23513 (Project Code 2026-039). The project involves the removal and replacement of existing HVAC systems, including demolition of existing equipment and installation of new air handling units, heat pumps, refrigerant piping, ductwork, and associated controls. The scope encompasses mechanical and electrical work, with the building to remain occupied during construction, requiring potential night and weekend work to maintain climate control. A mandatory pre-bid meeting is scheduled for October 8, 2026, at 10:00 a.m. at the DMV facility, with attendance required for all bidders. Questions regarding specifications must be submitted in writing to the Contracting Officer by 4:00 p.m. on October 15, 2026, directed to Brenda.Williams@dmv.virginia.gov. The drawings are dated September 17, 2026, and serve as the basis for bid preparation and equipment procurement coordination.
The specifications detail compliance with the Virginia Uniform Statewide Building Code (VUSBC 2021), the National Electrical Code (NFPA 70, 2020), and the Virginia Energy Conversion Code (VECC 2021). The mechanical design is based on Trane TWE/TWA equipment utilizing R-454B refrigerant with specific requirements for testing, adjusting, and balancing (TAB), refrigerant recovery and recycling, and A2L refrigerant safety protocols including leak detection systems. Electrical work includes new panelboard connections, circuit breaker upgrades, duct smoke detection systems with remote test/reset stations, and coordination with mechanical equipment installations. The project requires contractor coordination with other trades, as-built documentation, all necessary inspections, and comprehensive labeling of electrical systems. All materials removed during demolition become contractor property unless otherwise designated, and the contractor is responsible for refrigerant recovery costs and any additional work incurred by other trades resulting from equipment selection changes.
View the file
Other files
| File | Type | Posted |
|---|---|---|
| Small_Business_Reporting_Form.xls | XLS spreadsheet | |
| Addendum 1.pdf | ||
| dgs-30-090_07-21_co-10_2 bid bond.pdf | ||
| 154-B5154-003_DMV Widgeon CSC-Specifications_Final Bid Set.pdf | ||
| dgs-30-384_01-21_eva-registration.pdf |
On GovTribe
Work with this file
- Download the original file
- Contacts named in this file
- Similar government files
- Ask GovTribe AI about this file
Text version
PROJECT CODE
RFS JOB #
OF
DATE
D
ES
C R
IP
TI
O N
R
EV
IS
IO
N S
D A
TE
D
M V
W
ID
G
EO
N C
SC
H
VA
C R
EP
LA
C
EM
EN
T
W
ID
G
EO
N R
O A
D N
O R
FO
LK
, V A
2026-039
09/17/26
T
IT
L E S
H E E T
OF
DATE
D
ES
C R
IP
TI
O N
R
EV
IS
IO
N S
D A
TE
D
M V
W
ID
G
EO
N C
SC
H
VA
C R
EP
LA
C
EM
EN
T
W
ID
G
EO
N R
O A
D N
O R
FO
LK
, V A
2026-039
09/17/26
E N
L A
R G
E D
D E M
O L
IT
IO
N
N
E W
W O
R K
F L O
O R
P L A
N S
GENERAL NOTES
DEMOLITION
EXISTING HVAC PIPING, DUCTWORK, AND EQUIPMENT SHOWN IS BASED ON EXISTING PLANS
AND FIELD OBSERVATION WITHOUT DEMOLITION. AFTER DEMOLITION, ANY CLARIFICATION
REQUIRED TO DETERMINE SCOPE OF WORK SHALL BE BROUGHT TO THE ATTENTION OF THE
ARCHITECT.
THE CONTRACTOR SHALL VISIT THE JOB SITE AND THOROUGHLY FAMILIARIZE HIMSELF WITH
THE EXISTING CONDITIONS.
DRAWINGS DO NOT SHOW EVERY EXISTING PIPE, CONDUIT, DUCT, ETC. CONTRACTOR SHALL
TAKE CARE TO REMOVE ONLY ITEMS REQUIRED TO BE REMOVED AND VERIFY PIPES, DUCTS,
ETC. BEFORE REMOVAL.
REMOVAL OF ITEMS SHALL INCLUDE ASSOCIATED HANGERS, ANCHOR BOLTS AND OTHER
APPURTENANCES. WHERE SUCH REMOVAL RESULTS IN OPEN HOLES, VOIDS OR EXPOSURE
OF DAMAGED SURFACES, THE CONTRACTOR SHALL BE RESPONSIBLE FOR REPAIRING AND
FINISHING THE SURFACE TO MATCH ADJACENT CONDITIONS. THIS WORK SHALL BE
COORDINATED WITH ARCHITECTURAL FINISH SCHEDULES WHERE APPLICABLE.
BUILDING IS TO REMAIN OCCUPIED DURING CONSTRUCTION. REMOVAL OR SHUT-DOWN OF
EQUIPMENT THAT AFFECTS ANY OCCUPIED AREA'S AIR CONDITIONING OR HEATING SHALL
ONLY BE DONE AS APPROVED OR TEMPORARY AIR CONDITIONING OR HEATING SHALL BE
PROVIDED AT CONTRACTOR'S EXPENSE. THIS MAY REQUIRE NIGHT AND WEEKEND WORK TO
KEEP BUILDING IN OPERATION.
REMOVE EXISTING DUCTWORK AND PIPING NOT TO BE REUSED.
ALL MATERIALS REMOVED UNDER DEMOLITION, NOT TO BE RELOCATED OR DESIGNATED TO
BE TURNED OVER TO THE OWNER, SHALL BECOME THE PROPERTY OF THE CONTRACTOR,
UNLESS OTHERWISE NOTED, AND SHALL BE REMOVED COMPLETELY FROM THE SITE.
GENERAL ITEMS
GENERAL NOTES ON THIS DRAWING ARE APPLICABLE TO EACH HVAC DRAWING OF THIS SET.
SEE EACH DRAWING FOR SPECIFIC NOTES APPLICABLE TO THAT DRAWING.
OVERHEAD PIPING IN SPACES WITHOUT HUNG CEILINGS SHALL BE RUN AS CLOSE TO ROOF
DECK OR STRUCTURE ABOVE, AS PRACTICAL, AS CLOSE TO PARALLEL JOISTS AS POSSIBLE
AND ABOVE LIGHTING FIXTURES TO CONCEAL PIPING.
OVERHEAD DUCTWORK AND PIPING IN SPACES WITH CEILINGS SHALL BE CONCEALED
UNLESS OTHERWISE NOTED.
PROVIDE PIPE SLEEVES LARGE ENOUGH TO ALLOW FOR REQUIRED LATERAL MOVEMENT OF
PIPING.
CONTRACTOR SHALL VERIFY REQUIRED REFRIGERANT PIPE SIZES AND QUANTITIES WITH
EQUIPMENT MANUFACTURER FOR THE INDICATED INSTALLATION.
COORDINATE LOCATION AND INSTALLATION OF EQUIPMENT WITH OTHER TRADES.
DO NOT SCALE DRAWINGS. SEE ARCHITECTURAL DRAWINGS FOR EXACT LOCATIONS OF
DOORS, WINDOWS, ETC.
PIPING, DUCTWORK, VENTS, ETC., EXTENDING THROUGH EXTERIOR WALLS AND ROOF
SHALL BE FLASHED AND COUNTER FLASHED IN A WEATHERPROOF MANNER.
VALVES AND SPECIALTIES SHALL BE LINE SIZE EXCEPT FOR CONTROL VALVES OR UNLESS
NOTED OTHERWISE.
EXTEND DRAIN LINES AS INDICATED. ROUTING SHALL NOT INTERFERE WITH PASSAGEWAYS
AND MAINTENANCE. DRAINS FROM AIR CONDITIONING CONDENSATE DRAIN PANS SHALL BE
TRAPPED. SLOPE CONDENSATE DRAIN PIPING AT 1/4" PER FOOT. VERIFY INVERT IS
ESTABLISHED AFTER AIR HANDLING UNIT IS INSTALLED BUT PRIOR TO DUCTWORK
INSTALLATION.
PIPING AND DUCTWORK INSULATION SHALL BE RUN CONTINUOUSLY THROUGH NON-RATED
FLOORS, WALLS, ROOF AND PARTITIONS, UNLESS OTHERWISE INDICATED.
NO PIPING SHALL BE SMALLER THAN 3/4" UNLESS OTHERWISE NOTED.
LOCATE AND SIZE CONCRETE PADS AND CURBS FOR MECHANICAL EQUIPMENT IN
ACCORDANCE WITH ACTUAL EQUIPMENT PURCHASED.
THROUGH-PENETRATION FIRESTOP ASSEMBLIES
PROVIDE UL LISTED THROUGH-PENETRATION ASSEMBLIES FOR FIRE RATED PARTITIONS,
WALLS, AND FLOORS. REVIEW ARCHITECTURAL DRAWINGS FOR FIRE PARTITION LOCATIONS
AND UL LISTINGS.
SHEET METAL
PROVIDE ACCESS DOORS IN DUCTWORK WHERE INDICATED OR REQUIRED FOR ACCESS TO
SYSTEM COMPONENTS INCLUDING THE FOLLOWING:
DAMPER MOTORS AND/OR MOTOR OPERATED DAMPERS
FILTERS
BOTH SIDES OF HEATING AND COOLING COILS
SMOKE DETECTORS
PROVIDE A MINIMUM OF THREE TIMES THE FAN DIAMETER OF STRAIGHT DUCTWORK OFF
THE SUPPLY AIR FAN DISCHARGE BEFORE ANY TAKEOFFS OR ELBOWS.
A2L PIPING REQUIREMENTS
REFRIGERANT PIPING LOCATED IN AREAS OTHER THAN THE ROOM OR SPACE WHERE THE
REFRIGERATING EQUIPMENT IS LOCATED SHALL BE LABELED. THE PERMANENT PIPE LABELS
SHALL BE LOCATED AT INTERVALS NOT EXCEEDING 20 FEET. MINIMUM TEXT SHALL BE 1/2
INCH AND SHALL INDICATE THE REFRIGERANT DESIGNATION AND SAFETY GROUP
CLASSIFICATION OF REFRIGERANT USED IN THE PIPING SYSTEM AND INCLUDE "DANGER--
RISK OF FIRE OR EXPLOSION. FLAMMABLE REFRIGERANT."
REFRIGERANT PIPING USED WITH GROUP A2L REFRIGERANTS AND LOCATED IN CONCEALED
LOCATIONS WHERE TUBING IS INSTALLED IN STUDS, JOISTS, RAFTERS OR SIMILAR MEMBER
SPACES, AND LOCATED LESS THAN 1-1/2 INCHES FROM THE NEAREST EDGE OF THE
STRUCTURAL MEMBER, SHALL BE CONTINUOUSLY PROTECTED BY SHIELD PLATES.
PROTECTIVE STEEL SHIELD PLATES SHALL HAVE A MINIMUM THICKNESS OF 0.0575 INCH
((NO. 16 GAGE) AND SHALL COVER THE AREA OF THE TUBE PLUS THE AREA EXTENDING NOT
LESS THAN 2 INCHES BEYOND BOTH SIDES OF THE TUBE.
MAINTENANCE
EQUIPMENT WITH FILTERS SHALL BE INSTALLED SO THAT FILTERS CAN BE EASILY REMOVED
AND REPLACED.
PROVIDE ACCESS TO ANY INSPECTION OR MAINTAINABLE DEVICE, EQUIPMENT, ETC. -
ACCESS OR ACCESS DOOR SHALL BE OF ADEQUATE SIZE TO WORK ON DEVICE.
EXAMINE MANUFACTURER'S LITERATURE TO DETERMINE RECOMMENDED CLEARANCES.
THESE CLEARANCES, IN ADDITION TO MINIMUM CLEARANCES REQUIRED BY THE NATIONAL
ELECTRICAL CODE, SHALL BE ESTABLISHED AND MAINTAINED. THIS APPLIES TO NEW AND
EXISTING EQUIPMENT IMPACTED BY THIS PROJECT AS WELL. THE CONTRACTOR SHALL BE
RESPONSIBLE FOR COORDINATING THESE REQUIREMENTS WITH ALL OTHER TRADES.
INTERDISCIPLINARY COORDINATION
IF THIS CONTRACTOR SHOULD ELECT TO PROPOSE ANY EQUIPMENT THAT HAS DIFFERENT
PHYSICAL OR ELECTRICAL CHARACTERISTICS, ETC. WHEN COMPARED TO THE BASIS OF
DESIGN EQUIPMENT, THIS CONTRACTOR IS RESPONSIBLE FOR COORDINATING THESE
CHANGES WITH THE OTHER TRADES PRIOR TO BID AND AGAIN BEFORE ORDERING OF
EQUIPMENT. IF THERE SHOULD BE ANY ADDITIONAL WORK INCURRED BY THE OTHER
TRADES AS A RESULT OF THIS CONTRACTOR'S EQUIPMENT SELECTION, ALL COSTS
ASSOCIATED WITH THE ADDITIONAL WORK SHALL BE BORNE BY THIS CONTRACTOR.
TESTING, ADJUSTING, AND BALANCING (TAB)
AIRSIDE TAB SHALL BE PERFORMED ON ALL DUCTED AND NON-DUCTED HVAC SYSTEMS.
NON-DUCT HVAC SYSTEMS, INCLUDE, BUT ARE NOT LIMITED TO, UNIT HEATERS, CABINET
UNIT HEATERS, BASEBOARD HEATERS, DUCTLESS MINI-SPLITS, DESTRATIFICATION FANS,
LARGE CEILING FANS, INFRARED SPACE HEATERS, AIR CURTAINS, ETC. IT SHALL BE THE
RESPONSIBILITY OF THE TAB CONTRACTOR TO DETERMINE APPROPRIATE TESTING,
ADJUSTING AND BALANCING PROCEDURES FOR SYSTEMS NOT LISTED BY THE PROCEDURAL
STANDARDS CERTIFYING BODY (NEBB, AABC, ETC.).
DUCT TURNING DOWN
MITERED ELBOW WITH TURNING VANES
DUCT TURNING UP
VOLUME DAMPER
SMOKE DETECTOR
MOTORIZED DAMPER
S
M
REFRIGERANT SUCTION/LIQUID PIPINGRS/RL
°F
Ø DIAMETER
DEGREE FAHRENHEIT
L-1 LOUVER DESIGNATION
AIR HANDLING UNIT DESIGNATION
HEAT PUMP DESIGNATIONHP-1
AHU-1
POINT OF DEMOLITION LIMIT
POINT OF CONNECTION NEW TO EXISTING
NEW WORK NOTE DESIGNATION
DEMOLITION NOTE DESIGNATION
LEGEND AND ABBREVIATIONS
EXTERNAL STATIC PRESSURE
ENTERING WATER TEMPERATURE
LEAVING AIR TEMPERATURE
MAX OVERCURRENT PROTECTION
1000 BRITISH THERMAL UNITS PER HOUR
WET BULB TEMPERATURE
PIPE TURNING DOWN
D CONDENSATE DRAIN
DIRECTION OF FLOW
DIRECTION OF PITCH DOWN
RETURN AIRRA
WB
SA SUPPLY AIR
OA
MOCP
MCA
MIN
MBH
OUTSIDE AIR
MIN CIRCUIT AMPACITY
MINIMUM
PIPE TURNING UP LAT
FLA
ESP
EWT
ETR
FULL LOAD AMPS
EXISTING TO REMAIN
ABOVE FINISHED FLOOR
CUBIC FEET PER MINUTE
ENTERING AIR TEMPERATUREEAT
EA
CFM
APPROX
EXHAUST AIR
APPROXIMATELY
AFF
(TYP) TYPICAL
DRY BULB TEMPERATUREDB
FT FEET
IN INCH
SEER SEASONAL ENERGY EFFICIENCY RATING
TSP TOTAL STATIC PRESSURE
VOLTV
SENS SENSIBLE
WATTW
LEAVING DRY BULB TEMPERATURELDB
LEAVING WET BULB TEMPERATURELWB
ENTERING DRY BULB TEMPERATUREEDB
EWB ENTERING WET BULB TEMPERATURE
ENERGY CODE COMPLIANCE PATH
ASHRAE 90.1
VECC CHAPTER 4 - PRESCRIPTIVE
VECC CHAPTER 4 - PERFORMANCE
PIPE CAPPED
DUCTLESS SPLIT SYSTEM DESIGNATIONDSS-1
KW KILOWATT
PROJECT CODE
RFS JOB #
OF
DATE
D E S C
R
IP
T
IO
N
R E V
IS
IO
N S
D A
T E
D M
V W
ID
G
E O
N C
S C
H
V A
C R
E P L A
C E M
E N
T
W
ID
G E O
N R
O A
D N
O R
F O
L K
, V A
2026-039
09/17/26
M001
GE
NE
RA
L N
OT
ES
A
ND
LE
GE
ND
PERFORM AN AIRSIDE PRE-BALANCE (AIRFLOW, TEMPERATURE AND TOTAL
STATIC PRESSURE) ON AHU-1 IN FULL COOLING MODE PRIOR TO ANY
DEMOLITION WORK. SUBMIT PRE-BALANCE DATA TO ARCHITECT.
PRE-TAB NOTE:
DSS, ETR
HP-2, ETR
HP-1
AHU-1
RS/RL, ETR
1-1/4" D
1-1/4" D
ETR-10'-0" x 3'-0" BLANKED OFF INTAKE
LOUVER ETR (BOTTOM AT 7'-0" A.F.F.)
16x14 OA, ETR 20x16 OA, ETR
1-1/4", ETR
AHU-2, ETR
D
26x26
12x12 OA, ETR x1
6 S A, E
TR
x1
8 R A, E
TR
x1
8 S A, E
TR
30x16 RA, ETR
RS/RL
RS/RL, ETR
PAD, ETR
INTAKE LOUVER ETR
26x26, ETR
DOMESTIC WATER
LINES, ETR
T
EXISTING EQUIPMENT YARD
EXISTING STORAGE
EXISTING STORAGE
DSS, ETR
HP-2, ETR
HP-1
AHU-1
1-1/4" D
1-1/4" D
ETR-10'-0" x 3'-0" BLANKED OFF INTAKE
LOUVER ETR (BOTTOM AT 7'-0" A.F.F.)
16x14 OA, ETR 20x16 OA, ETR
1-1/4", ETR
AHU-2, ETR
D
26x26
12x12 OA, ETR x1
6 S A, E
TR
x1
8 R A, E
TR
x1
8 S A, E
TR
30x16 RA, ETR
RS/RL
RS/RL, ETR
PAD, ETR
INTAKE LOUVER ETR
26x26, ETR
T
AHU-12
NEW ACCESS
PANEL
RS/RL, ETR
PROJECT CODE
RFS JOB #
OF
DATE
D E S C
R
IP
T
IO
N
R E V
IS
IO
N S
D A
T E
1/4" = 1'-0" 5' 10'0' 5'
D M
V W
ID
G
E O
N C
S C
H
V A
C R
E P L A
C E M
E N
T
W
ID
G E O
N R
O A
D N
O R
F O
L K
2026-039
09/17/26
M101
PROVIDE DOMESTIC WATER PIPING, INSULATION, HANGERS, AND
SUPPORTS COMPLETE. ROUTE THE WATER LINE TO AVOID PASSING
DIRECTLY ABOVE THE NEW ELECTRICAL PANEL LOCATION.
PROVIDE 7-DAY PROGRAMMABLE SPACE THERMOSTAT WITH
PUSH-BUTTON OVERRIDE AND VENTED LOCK BOX COVER. PROVIDE
CONTROL WIRING FOR AHU-1.
PROVIDE VERTICAL AIR HANDLING UNIT AS SHOWN AND SCHEDULED.
PROVIDE RETURN AIR / OUTSIDE AIR PLENUM FULL SIZE OF UNIT'S
RETURN AIR CONNECTION AS REQUIRED TO MAKE PROPER DUCT
CONNECTIONS.
PROVIDE HEAT PUMP, REFRIGERANT PIPING, AND SUPPORTS. MOUNT
UNIT ON EXISTING CONCRETE PAD.
PROVIDE DUCT TRANSITION TO AIR HANDLING UNIT'S SUPPLY
DISCHARGE, RETURN PLENUM BOX AND OUTDOOR AIR CONNECTION.
PROVIDE TRAPPED CONDENSATE DRAIN PIPING AND RUN TO EXISTING
FLOOR DRAIN LOCATED IN MECHANICAL ROOM. SIZE AS INDICATED.
ROUTE PIPING AS CLOSE TO FACE OF UNIT TO AVOID ANY TRIPPING
HAZARD.
INSTALL NEW SMOKE DETECTOR PROVIDED BY ELECTRICAL
CONTRACTOR.
NOTES THIS SHEET
RECOVER REFRIGERANT FROM SYSTEM. REMOVE AHU PIPING,
SUPPORTS, AND ACCESSORIES COMPLETE. REMOVE EXPOSED
RETURN DUCTWORK, EXPOSED SUPPLY DUCTWORK, AND EXPOSED
OUTDOOR DUCTWORK TO ALLOW INSTALLATION OF NEW AHU
THROUGH ACCESS PANEL. REMOVE AHU AND HP COMPLETE.
REMOVE DOMESTIC WATER LINE TO AVOID PASSING DIRECTLY ABOVE
THE NEW ELECTRICAL PANEL PROVIDED UNDER THE NEW WORK
PHASE.
REMOVE IN-DUCT SMOKE DETECTOR.
REMOVE THERMOSTAT, CONTROL WIRING AND VENTED LOCK BOX
COVER. EXISTING CONTROL WIRING NOT TO BE REUSED.
NOTES THIS SHEET
DEMOLITION WORK
SCALE: 1/4" = 1'-0"
NEW WORK
SCALE: 1/4" = 1'-0"
ME
CH
AN
IC
AL
D
EM
O
AN
D
NE
W
W
OR
K
REFRIGERANT RECOVERY NOTE:
REFRIGERANT FROM EXISTING MECHANICAL SYSTEMS SHALL BE RECOVERED AND
RECYCLED FOR RECLAIM. EQUIPMENT CAPABLE OF PULLING A VACUUM OF LESS THAN
1000 MICRONS OF MERCURY SHALL BE USED TO RECOVER REFRIGERANT. MECHANICAL
SYSTEMS SHALL NOT BE OPENED TO ATMOSPHERE UNTIL ALL REFRIGERANT IS FULLY
RECOVERED. THE CONTRACTOR SHALL PROVIDE CONTAINERS FOR THE STORAGE OF
THE REFRIGERANT. REFRIGERANT SHALL BECOME THE PROPERTY OF THE CONTRACTOR.
OF
DATE
D E S C
R
IP
T
IO
N
R E V
IS
IO
N S
D A
T E
D M
V W
ID
G
E O
N C
S C
H
V A
C R
E P L A
C E M
E N
T
W
ID
G E O
N R
O A
D N
O R
F O
L K
2026-039
09/17/26
M401
SC
HE
DU
LE
S
AN
D
DE
TA
ILSCONDENSATE DRAIN TRAP DETAIL
NO SCALE
L = H + J + PIPE DIAMETER WHERE:
J = 1/2 H
L = H + J + PIPE DIAMETER WHERE:
H = 1/2 INCH (MINIMUM)
CLEANOUT (TYP. FOR 3)
H
J
L
DRAIN PAN
SEE NOTE 1
1.
2.
NOTES:
DRAIN LINE SHALL BE AT LEAST
THE SAME SIZE AS THE NIPPLE
ON THE DRAIN PAN
PITCH DOWN TOWARD
DRAIN, ROUTE AS
INDICATED ON PLAN
DRAIN PAN TRAPPING FOR SECTION
UNDER NEGATIVE PRESSURE:
DRAIN PAN TRAPPING FOR SECTION UNDER
POSITIVE PRESSURE:
H = 1 INCH FOR EACH INCH OF
NEGATIVE PRESSURE PLUS 1 INCH
J = 1/2 INCH PLUS THE UNIT POSITIVE STATIC
PRESSURE AT COIL DISCHARGE (LOADED FILTERS)
FOR INDOOR AIR HANDLING UNITS, UNITARY AIR CONDITIONERS, AND DEHUMIDIFERS,
PROVIDE RECTORSEAL EZ TRAP 83230 EXT-230 WITH INTEGRAL OVERFLOW SENSOR,
OR APPROVED EQUAL.
FOR ROOF MOUNTED HVAC UNITS, THE CONTRACTOR SHALL PROVIDE MOISTURE
SENSOR IN DRAIN PAN TO DE-ENERGIZE UNIT SHOULD PRIMARY DRAIN GET CLOGGED.
NEW GROUT
ESCUTCHEON
PIPE W/OUT
INSULATION
PIPE W/
INSULATION
INSULATION
NEW GROUT
EXISTING WALL
NOTE: SLEEVES FOR NEW WALLS SIMILAR.
PIPE SLEEVE
BACKFILL
MATERIAL
SEALANT
SEALANT
BACKFILL
MATERIAL
PIPE SLEEVE
EXISTING WALL
PIPE SLEEVE DETAIL
SPLIT SYSTEM DUAL CIRCUIT HEAT PUMP SCHEDULE - AIR TO AIR
SUPPLEMENTAL ELECTRIC ELECTRICAL DATA ELECTRICAL DATA
FAN DATA COOLING DATA HEATING DATA HEATER INDOOR UNIT OUTDOOR UNIT
INDOOR OUTDOOR
TOTAL OA ESP MOTOR TOTAL SENS EDB EWB LDB LWB MIN MIN TOTAL COP COP SIZE MODEL MODEL TAG CFM CFM (IN. WG) BHP MBH MBH (ºF) (ºF) (ºF) (ºF) IEER EER MBH 17ºF DB / 15ºF WB 47ºF DB / 43ºF WB KW STAGES MCA MOCP VOLTS PHASE NUMBER TAG MCA MOCP VOLTS PHASE NUMBER REMARKS
AHU-1 6280 1260 0.9 2.72 256.6 155.4 77.7 68.0 55.9 55.3 12.5 10.0 147.9 2.05 3.2 49.8 2 149.0 150.0 208 3 TWE HP-1 93 125 208 3 TWA SEE NOTES
NOTES:
1. THE DESIGN SHOWN IS BASED ON TRANE TWE/TWA EQUIPMENT WITH REFRIGERANT TYPE R-454B AND IS INTENDED ONLY TO SHOW THE GENERAL SIZE, CONFIGURATION, LOCATION, CONNECTIONS AND SUPPORT FOR EQUIPMENT OR SYSTEMS SPECIFIED WITH RELATION TO THE OTHER BUILDING SYSTEMS.
SEE SPECIFICATION SECTION 238126 SPLIT-SYSTEM AIR-CONDITIONERS FOR TECHNICAL REQUIREMENTS PERTAINING TO THE EQUIPMENT.
2. EXTERNAL STATIC PRESSURE INCLUDES SUPPLY, RETURN AND OUTSIDE AIR DISTRIBUTION SYSTEMS.
3. LEAVING AIR TEMPERATURE IS TO BE PROVIDED AT THE UNIT DISCHARGE, TOTAL AND SENSIBLE CAPACITIES ARE "NET" VALUES TO BE PROVIDED DOWNSTREAM OF THE SUPPLY AIR FAN.
4. PROVIDE AHU-1 WITH DUCT FLANGE KIT, SUBBASE AND RUBBER IN SHEER FLOOR MOUNT ISOLATORS. PROVIDE HP-1 WITH RUBBER IN SHEER ISOLATORS.
5. PROVIDE WITH CONDENSER GUARDS, LOW AMBIENT KIT DOWN TO 0ºF, DEFROST CONTROL, INTEGRAL TIME DELAY BETWEEN COMPRESSORS, REFRIGERANT LEAK DETECTION AND MITIGATION ACTIONS.
6. PROVIDE HP-1 WITH TWO DIRECT DRIVE HERMETIC SCROLL COMPRESSORS WITH MINIMUM 2 STAGES OF COOLING AND HEATING, STAND ALONE DISCONNECT, AND 672 HOUR SALT SPRAY.
7. PROVIDE WITH TWO SPEED SUPPLY FAN. MINIMUM SPEED SHALL NOT BE GREATER THAN 66 PERCENT OF FULL SPEED.
NO SCALE
TURNING VANES,
DOUBLE THICKNESS
ELBOW
TEE
DUCTWORK FITTING DETAILS
NO SCALE
SUPPORT FROM
STRUCTURE ABOVE
THREADED
ROD
CLEVIS HANGER (SIZE
AS REQUIRED)
SUPPORT FROM
STRUCTURE ABOVE
BOLT AND CLAMPING
NUT (TYP.)
STEEL PIPE
STRAP
1-5/8" x 1-5/8" x 12 GAUGE
STEEL CHANNEL
INSULATION SADDLE
THREADED ROD
LENGTH AS REQUIRED
INSULATION SADDLE (TYP)MULTIPLE PIPE RUNS
PIPE SUPPORT DETAILS
NO SCALE
SINGLE PIPE RUN
1.0 GENERAL:
THE UNIT SHALL BE PROVIDED WITH A 7-DAY PROGRAMMABLE THERMOSTAT (BASIS OF
DESIGN: HONEYWELL VISION PRO 8000 TH321WF1001) THAT SHALL OPERATE WITHOUT BAS
INTEGRATION AND IS EQUIPPED WITH THE FOLLOWING FEATURES:
FAN SPEED CONTROL: TWO-SPEED
CONDENSER TYPE: AIR-COOLED
DX COIL TYPE: DX HEAT PUMP
HEATING COIL TYPE: ELECTRIC
OUTDOOR AIR CONTROL: MOTORIZED DAMPER
EXHAUST AIR CONTROL: NONE
DEHUMIDIFICATION CONTROL: NONE
1.1 TWO-SPEED SUPPLY FAN SPEED CONTROL:
THE SUPPLY FAN SHALL STAGE BETWEEN MINIMUM AND MAXIMUM FAN SPEED BASED ON
THE FOLLOWING MODES:
FAN SPEED MODES:
MINIMUM FAN SPEED:
DEADBAND (NO HEATING OR COOLING CALL)
STAGE 1 COOLING
MAXIMUM FAN SPEED
STAGE 2 COOLING
HEAT PUMP HEATING
AUXILIARY HEATING
2.0 UNOCCUPIED MODE:
WHENEVER THE BUILDING ENTERS THE UNOCCUPIED MODE, THE SUPPLY FAN SHALL BE
DISABLED, AND THE MIXED AIR DAMPER ASSEMBLY SHALL BE FULLY OPEN TO THE RETURN
AND FULLY CLOSED TO THE OUTDOOR AIR.
ON A RISE IN SPACE TEMPERATURE ABOVE THE UNOCCUPIED COOLING SETPOINT (85°F,
ADJ.), THE SUPPLY FAN SHALL BE ENABLED, THE MIXED AIR DAMPER ASSEMBLY SHALL BE
FULLY OPEN TO THE RETURN AND FULLY CLOSED TO THE OUTDOOR AIR, ENGAGE THE
REVERSING VALVE TO COOLING, AND THE COMPRESSOR(S) SHALL STAGE AS REQUIRED TO
MAINTAIN SPACE TEMPERATURE SETPOINT. UPON A FALL IN SPACE TEMPERATURE BELOW
THE UNOCCUPIED COOLING SETPOINT, THE SUPPLY FAN SHALL BE DISABLED, THE MIXED AIR
DAMPER ASSEMBLY SHALL BE FULLY OPEN TO THE RETURN AND FULLY CLOSED TO THE
OUTDOOR AIR, AND COOLING SHALL BE DISABLED.
ON A FALL IN SPACE TEMPERATURE BELOW ITS UNOCCUPIED HEATING SETPOINT (55°F,
ADJ.), THE SUPPLY FAN SHALL BE ENABLED, THE MIXED AIR DAMPER ASSEMBLY SHALL BE
FULLY OPEN TO THE RETURN AND FULLY CLOSED TO THE OUTDOOR AIR, ENGAGE THE
REVERSING VALVE TO HEATING, AND THE COMPRESSOR(S)/ELECTRIC HEATING COIL SHALL
STAGE AS REQUIRED TO MAINTAIN SPACE TEMPERATURE SETPOINT. UPON A RISE IN SPACE
TEMPERATURE ABOVE THE UNOCCUPIED HEATING SETPOINT, THE SUPPLY FAN SHALL BE
DISABLED, THE MIXED AIR DAMPER ASSEMBLY SHALL BE FULLY OPEN TO THE RETURN AND
FULLY CLOSED TO THE OUTDOOR AIR, AND HEATING SHALL BE DISABLED.
2.1 OCCUPIED OVERRIDE:
THE UNIT IS EQUIPPED WITH AN OCCUPANCY OVERRIDE SWITCH THAT IS LOCATED ON THE
THERMOSTAT. DURING THE UNOCCUPIED MODE, IF THE OCCUPANCY OVERRIDE SWITCH IS
ACTIVATED, THE UNIT SHALL BE INDEXED TO THE OCCUPIED MODE FOR A DETERMINED
AMOUNT OF TIME (INITIALLY SET AT 2 HOURS (ADJ.). AFTER THE OCCUPANCY OVERRIDE TIME
EXPIRES, THE SYSTEM SHALL RETURN TO THE UNOCCUPIED MODE.
TRANSITION FROM UNOCCUPIED TO OCCUPIED SHALL BE AUTOMATIC THROUGH THE
THERMOSTAT UTILIZING PRESET TIME SCHEDULE.
3.0 ADAPTIVE START:
THE THERMOSTAT SHALL EMPLOY AN ADAPTIVE START PROGRAM TO AUTOMATICALLY
ADJUST THE DAILY START TIME SO THAT SPACE CONDITIONS REACH THE OCCUPIED
SETPOINTS PRIOR TO SCHEDULED OCCUPANCY. DURING THIS MODE OF OPERATION, THE
SUPPLY FAN SHALL BE ENABLED, THE MIXED AIR DAMPER ASSEMBLY SHALL BE FULLY OPEN
TO THE RETURN AND FULLY CLOSED TO THE OUTDOOR AIR, AND STAGE HEATING OR
COOLING WITHOUT OVERLAP TO ACHIEVE THE ACTIVE OCCUPIED SPACE TEMPERATURE
SETPOINTS.
ONCE THE BUILDING REACHES OCCUPIED SETPOINTS -OR- IF THE OCCUPANCY OVERRIDE
SWITCH IS ENABLED, THE UNIT SHALL BE INDEXED TO THE OCCUPIED MODE.
4.0 OCCUPIED MODE:
WHENEVER THE BUILDING ENTERS THE OCCUPIED MODE, THE SUPPLY FAN SHALL BE
ENABLED, AND THE MIXED AIR DAMPER ASSEMBLY SHALL MODULATE TO MAINTAIN THE
HIGHEST OF THE FOLLOWING:
- BASE MINIMUM OUTDOOR AIR VOLUME
ON A RISE IN SPACE TEMPERATURE ABOVE THE OCCUPIED COOLING SETPOINT (74°F, ADJ.),
THE UNIT SHALL ENGAGE THE REVERSING VALVE TO COOLING, AND STAGE THE
COMPRESSOR(S) AS REQUIRED TO MAINTAIN SPACE TEMPERATURE SETPOINT. UPON A FALL
IN SPACE TEMPERATURE BELOW THE OCCUPIED COOLING SETPOINT, COOLING SHALL BE
DISABLED.
ON A FALL IN SPACE TEMPERATURE BELOW ITS OCCUPIED HEATING SETPOINT (68°F, ADJ.),
THE UNIT SHALL ENGAGE THE REVERSING VALVE TO HEATING, AND STAGE THE
COMPRESSOR(S)/ELECTRIC HEATING COIL AS REQUIRED TO MAINTAIN SPACE TEMPERATURE
SETPOINT. UPON A RISE IN SPACE TEMPERATURE ABOVE THE OCCUPIED HEATING SETPOINT,
HEATING SHALL BE DISABLED.
5.0 SAFETIES AND ALARMS:
ALL SAFETY DEVICES IDENTIFIED WITH (SAFE) SHALL BE HARDWIRE-INTERLOCKED TO
PREVENT UNIT OPERATION DURING A SAFETY EVENT UNLESS NOTED OTHERWISE.
5.1 REFRIGERANT LEAK DETECTION SYSTEM:
FOR SYSTEMS EQUIPPED WTH A2L REFRIGERANT, THE UNIT SHALL BE PROVIDED WITH A
MANUFACTURER-INSTALLED REFRIGERANT DETECTION SYSTEM THAT IS COMPLIANT WITH UL
60335-2-40. UPON ACTIVATION OF THE REFRIGERANT DETECTION SYSTEM, THE SUPPLY FAN
SHALL BE ENABLED AND INDEXED TO MAXIMUM AIRFLOW. ALL ELECTRIC RESISTANCE
HEATERS OR ANY OTHER POTENTIAL IGNITION SOURCES THAT ARE INSTALLED WITHIN THE
UNIT OR CONNECTED DUCTWORK SHALL BE DISABLED. MITIGATION ACTIONS SHALL BE
INITIATED WITHIN 15 SECONDS OR LESS OF DETECTION AND MUST CONTINUE FOR AT LEAST
5 MINUTES AFTER THE DETECTOR HAS SENSED A DROP IN REFRIGERANT CONCENTRATION
BELOW THE SETPOINT VALUE.
5.2 CONDENSATE OVERFLOW SWITCH:
UPON ACTIVATION OF THE CONDENSATE OVERFLOW SWITCH, THE DX COOLING SHALL BE
DISABLED. UPON DE-ACTIVATION OF THE CONDENSATE OVERFLOW SWITCH, THE DX
COOLING SHALL RETURN TO NORMAL OPERATION.
5.3 SMOKE DETECTOR ACTIVATION:
FOR SYSTEMS REQUIRED TO HAVE DUCT-MOUNTED SMOKE DETECTORS, UPON ACTIVATION
OF THE SMOKE DETECTOR, THE SUPPLY FAN SHALL STOP, AND THE MIXED AIR DAMPER
ASSEMBLY SHALL BE FULLY OPEN TO THE RETURN AND FULLY CLOSED TO THE OUTDOOR
AIR.
SEQUENCE OF OPERATION
OF
DATE
D E S C
R
IP
T
IO
N
R E V
IS
IO
N S
D A
T E
D M
V W
ID
G
E O
N C
S C
H
V A
C R
E P L A
C E M
E N
T
W
ID
G E O
N R
O A
D N
O R
F O
L K
2026-039
E001
GE
NE
RA
L N
OT
ES
A
ND
LE
GE
ND
GENERAL ELECTRICAL NOTES
GENERAL: UNLESS SPECIFICALLY INDICATED OTHERWISE, ALL WORK
SHOWN ON ELECTRICAL DRAWINGS IS NEW WORK TO BE PROVIDED
UNDER THIS CONTRACT.
COORDINATION: COORDINATE AND COOPERATE WITH ALL TRADES ON
THE PROJECT. THE CONTRACTOR SHALL REVIEW ALL CONTRACT
DOCUMENTS INCLUDING ARCHITECTURAL DRAWINGS AND
SPECIFICATIONS. CONTRACTOR SHALL COORDINATE AND ADJUST
ACCORDINGLY AS DIRECTED BY THE ENGINEER.
AS-BUILT DRAWINGS: SECURE AN EXTRA SET OF ELECTRICAL DRAWINGS
TO BE KEPT ON SITE AND MARK, DAILY, THE DRAWINGS IN RED AS THE
PROJECT PROGRESSES IN ORDER TO KEEP AN ACCURATE RECORD OF
ALL DEVIATIONS BETWEEN THE WORK SHOWN ON THE DRAWINGS AND
THE WORK WHICH IS ACTUALLY INSTALLED. THESE MARKED DRAWINGS
SHALL REFLECT ANY AND ALL CHANGES AND REVISIONS TO THE ORIGINAL
DESIGN WHICH EXISTS IN THE COMPLETED WORK. DELIVER THE MARKED
DRAWINGS TO THE OWNER AT PROJECT CLOSE-OUT.
TESTS: TEST ALL WIRING FOR CONTINUITY AND GROUNDS BEFORE
CONNECTING ANY FIXTURES OR DEVICES. PERFORM INSULATION
RESISTANCE TESTS ON ALL WIRING #6 OR LARGER TO ENSURE THAT ALL
PORTIONS ARE FREE FROM SHORT-CIRCUITS AND GROUNDS.
INSPECTIONS: ARRANGE ALL NECESSARY INSPECTIONS. DELIVER ALL
REQUIRED INSPECTION CERTIFICATES TO THE OWNER.
GROUNDING: PROVIDE GROUNDING IN ACCORDANCE WITH THE NEC FOR
THE ELECTRICAL SYSTEM INCLUDING EQUIPMENT FRAMES, CONDUITS,
SWITCHES, CONTROLLERS, WIRE-WAYS, NEUTRAL CONDUCTORS, AND
OTHER EQUIPMENT. PROVIDE A GROUNDING CONDUCTOR IN ALL POWER
CONDUITS.
LABELS: PROVIDE LABELS FOR ALL PANELBOARDS, CABINETS, SAFETY
SWITCHES, MOTOR-DISCONNECT SWITCHES, AND MOTOR CONTROLLERS.
LABELS SHALL BE MACHINE ENGRAVED, LAMINATED PLASTIC,
PERMANENTLY ATTACHED WITH SELF-TAPPING SCREWS OR RIVETS. DO
NOT USE SELF-ADHESIVE LABELS. LABEL SHALL INDICATE EQUIPMENT
DESIGNATION AND ASSOCIATED PANEL AND CIRCUIT THAT SERVES IT.
J-BOX LABELING: LABEL ALL JUNCTION BOXES WITH PERMANENT
MARKER IDENTIFYING CIRCUIT NUMBER AND PANELBOARD OF CIRCUITS
WITHIN.
WIRING DEVICES: LABEL ALL WIRING DEVICES WITH PANELBOARD AND
CIRCUIT DESIGNATION PERMANENTLY ATTACHED WITH BLACK TYPED
DESIGNATION ON CLEAR TAPE.
PANEL DIRECTORY: PROVIDE UPDATED TYPEWRITTEN PANELBOARD
DIRECTORY CARD IN EACH PANELBOARD WITH CIRCUIT LOAD
INFORMATION AND ROOM NUMBER CLEARLY IDENTIFIED. USE ACTUAL
ROOM NUMBERS IN THE BUILDING, NOT THE ROOM NUMBERS SHOWN ON
THE CONTRACT DRAWINGS, AS THEY ARE OFTEN DIFFERENT.
MOTOR COORDINATION: MOTORS, MOTOR STARTERS, CONTROLLERS,
INTEGRAL DISCONNECT SWITCHES, AND CONTACTORS SHALL BE
PROVIDED WITH THEIR RESPECTIVE PIECES OF EQUIPMENT BY THE
EQUIPMENT SUPPLIER. COMMUNICATE WITH THE TRADES PROVIDING THE
EQUIPMENT, VERIFYING ALL REQUIREMENTS, PROVIDE ALL ELECTRICAL
CONNECTIONS REQUIRED THEREIN, AND INSTALL MOTOR STARTERS.
MOTOR DISCONNECTS: ALL MOTORS SHALL HAVE DISCONNECTING
MEANS.
MOTOR CONTROLLERS: ALL 3-PHASE MOTORS SHALL HAVE MAGNETIC
MOTOR CONTROLLERS WITH SOLID STATE OVERLOAD RELAY
PROTECTION. THE SOLID STATE OVERLOAD RELAY SHALL HAVE PHASE
LOSS AND PHASE OVERCURRENT PROTECTION WITH AUTOMATIC RESET
UPON RETURN OF NORMAL POWER.
MOTOR FUSE PROTECTION: WHERE FUSE PROTECTION IS SPECIFICALLY
REQUIRED BY THE EQUIPMENT MANUFACTURER, PROVIDE FUSED
SWITCHES IN LIEU OF NON-FUSED SWITCHES OR IN LIEU OF ENCLOSED
CIRCUIT BREAKERS, OR OTHER DEVICES INDICATED.
CONNECTION DETAILS: SECURE APPROVED SHOP DRAWINGS SHOWING
WIRING DIAGRAMS, ROUGH-IN AND HOOK UP DETAILS FROM OTHER
INVOLVED CONTRACTORS FOR EQUIPMENT WHICH MUST BE CONNECTED
ELECTRICALLY.
COORDINATION DETAILS: MECHANICAL EQUIPMENT WILL BE FURNISHED
AND INSTALLED BY THE MECHANICAL CONTRACTOR. THE LOCATIONS
SHOWN ON THE ELECTRICAL DRAWINGS ARE APPROXIMATE. COORDINATE
WITH THE MECHANICAL CONTRACTOR TO DETERMINE THE EXACT
LOCATION OF EACH PIECE OF EQUIPMENT AND DETERMINE THE EXACT
ROUGH-IN AND CONNECTION REQUIREMENTS.
WORKING CLEARANCE: COORDINATE FINAL LOCATIONS OF ELECTRICAL
EQUIPMENT WITH MECHANICAL DUCTWORK, PIPING ETC. AND ENSURE
WORKING CLEARANCE REQUIRED BY NEC WILL BE MET. SUFFICIENT
ACCESS AND WORKING SPACE SHALL BE PROVIDED AND MAINTAINED
AROUND ELECTRICAL EQUIPMENT AS REQUIRED BY THE NATIONAL
ELECTRICAL CODE. CONTRACTOR SHALL COORDINATE FINAL LOCATION
OF EQUIPMENT PROVIDED AND INSTALLED BY OTHER TRADES.
STARTER MOUNTING: WHERE AN INDIVIDUALLY MOUNTED SAFETY
SWITCH, STARTER OR CIRCUIT BREAKER IS SHOWN ADJACENT TO ITS
RESPECTIVE LOAD OR LISTED IN A SCHEDULE, PROVIDE ALL SUPPORTS,
BRACKETS, ANCHORING, ETC. NECESSARY TO PROPERLY SUPPORT THE
DEVICE.
MATERIAL COORDINATION: VERIFY CEILING AND WALL CONSTRUCTION
AND MATERIAL PRIOR TO ORDERING DEVICES TO ENSURE PROPER
DEVICE IS FURNISHED TO MATCH CONSTRUCTION.
MOUNTING HEIGHTS: MOUNTING HEIGHTS INDICATED ARE FROM THE
FINISHED FLOOR TO THE CENTERLINE OF THE WIRING DEVICE UNLESS
OTHERWISE NOTED. MOUNTING HEIGHTS OF LIGHTING FIXTURES ARE TO
THE BOTTOM OF THE FIXTURE UNLESS OTHERWISE NOTED.
DEVICE LOCATIONS: COORDINATE LOCATIONS OF SWITCHES,
RECEPTACLES, AND TELE/DATA OUTLETS WITH OTHER WALL MOUNTED
DEVICES SUCH AS THERMOSTATS AND CONTROL STATIONS.
DEVICE COORDINATION: THOROUGHLY REVIEW AND COORDINATE ALL
CASEWORK AND CABINET DRAWINGS AND ARCHITECTURAL ELEVATIONS
WITH DEVICE LOCATIONS PRIOR TO ROUGH-IN OF OUTLET BOXES.
MULTI-GANG JUNCTION BOXES: WHERE OUTLETS AND SWITCHES ARE
SHOWN ON PLAN TO BE INSTALLED ADJACENT TO EACH OTHER AND AT
THE SAME MOUNTING HEIGHT, THE DEVICES SHALL BE INSTALLED IN A
MULTI-GANG OUTLET BOX, UON. THE SIZE OF THE OUTLET BOX SHALL BE
DETERMINED BY THE NUMBER OF DEVICES AND CONDUCTORS THAT
SHALL BE INSTALLED IN THE MULTI-GANG OUTLET BOX.
BARRIERS: WHERE A MULTIPLE-GANG BOX HAS CIRCUITS OF DIFFERENT
VOLTAGES OR SYSTEMS WHICH ARE REQUIRED TO BE SEPARATED,
PROVIDE THE CODE-REQUIRED SEPARATION USING A FULL HEIGHT AND
DEPTH BARRIER PLATE.
CLEAN UP: ON PROJECT CLOSE-OUT CLEAN ALL ELECTRICAL DEVICES,
LIGHTING FIXTURES, LENSES, AND REMOVE ALL PAINT SPATTERS FROM
DEVICES, FIXTURES AND PLATES. REPAIR ALL INOPERATIVE LIGHTING
FIXTURES.
GROUND FAULT PROTECTION: RECEPTACLES LOCATED WITHIN 6'-0" OF
THE EDGE OF SINKS SHALL BE PROVIDED WITH GROUND FAULT
PROTECTION WHETHER SHOWN OR NOT.
HVAC DAMPERS, ETC: CONTRACTORS SHALL COORDINATE WITH THE
EQUIPMENT AND SYSTEM BEING PROVIDED AND PROVIDE POWER
CONNECTIONS ACCORDINGLY. THESE CONNECTIONS SHALL BE FOR
FIRE/SMOKE DAMPERS, DDC CONTROL DEVICES, ETC. CONTRACTOR
SHALL COORDINATE THE VOLTAGE REQUIREMENTS AND PROVIDE ALL
NECESSARY CONNECTIONS, COMPONENTS, ETC. THIS INCLUDES
TRANSFORMERS, BOXES, ETC.
CEILING PLENUM: THE CEILING SPACE IS A RETURN AIR PLENUM. ALL LOW
VOLTAGE CABLE SHALL BE PLENUM RATED. REFER TO NEC ART. 300.22
FOR PROVISIONS APPLICABLE TO PLENUMS.
OWNER STANDARDS: ALL WORK SHALL COMPLY WITH THE OWNER'S
PUBLISHED STANDARDS WHICH ARE AVAILABLE DIRECTLY FROM THE
OWNER.
EXISTING TO REMAIN DEVICES: CONTRACTOR SHALL REINSTALL DEVICES
THAT WERE TEMPORARILY SUPPORTED OR STORED FOR REINSTALLATION
IN EXISTING LOCATIONS ONCE CEILING WORK IS COMPLETE. PROVIDE
ADDITIONAL MOUNTING HARDWARE AND EXTEND EXISTING
CONDUIT/WIRING AS REQUIRED.
ELECTRICAL DEMOLITION NOTES
GENERAL: DEMOLITION DRAWINGS ARE BASED ON EXISTING PLANS AND FIELD
INVESTIGATION PRIOR TO DEMOLITION. VISIT THE EXISTING BUILDING PRIOR
TO BID IN ORDER TO BECOME FAMILIAR WITH THE EXISTING CONDITIONS AND
IN ORDER TO AVOID CONFLICTS.
DASHED ITEMS: ALL ITEMS SHOWN DASHED ON DEMOLITION PLANS ARE
EXISTING AND SHALL BE REMOVED.
SOLID ITEMS: ALL ITEMS SHOWN SOLID ON DEMOLITION PLANS ARE EXISTING
TO REMAIN.
CIRCUITING TO REMAIN: EXISTING CIRCUITING TO REMAIN SHALL BE
REROUTED OR RECONNECTED, AS REQUIRED, WHERE AFFECTED BY NEW
WORK IN ORDER TO MAINTAIN CONTINUITY OF THE CIRCUIT.
REUSE OF EXISTING CIRCUITRY: EXISTING CIRCUITRY SERVING LIGHTING
FIXTURES AND/OR RECEPTACLES FOR A GIVEN AREA SHALL BE REUSED
WHERE INDICATED TO SERVE THE NEW LAYOUT. PROVIDE CIRCUIT
MODIFICATIONS INDICATED OR AS OTHERWISE REQUIRED TO MAINTAIN THE
CONTINUITY OF EXISTING CIRCUITS THAT REMAIN.
EXISTING CONDUIT: ALL EXISTING CONDUITS AND WIRING THAT WILL NOT BE
REUSED SHALL BE REMOVED WHERE THEY WILL BE EXPOSED UPON
COMPLETION OF NEW WORK. EXISTING CONDUIT TO REMAIN CONCEALED IN
WALLS SHALL BE ABANDONED. EXISTING CONDUIT TO REMAIN BELOW FLOOR
SLAB SHALL BE CUT OFF ONE INCH BELOW ROUGH FLOOR AND GROUTED
FLUSH. ALL EXISTING WIRING IN CONDUITS TO BE ABANDONED SHALL BE
DISCONNECTED FROM POWER SOURCE AND REMOVED.
REPAIR DAMAGE: EXERCISE CARE IN REMOVAL OF DEMOLITION ITEMS.
REPAIR, AT NO ADDITIONAL COST TO THE OWNER, ANY DAMAGE CAUSED TO
EXISTING CONSTRUCTION AND/OR EQUIPMENT TO REMAIN.
ASSOCIATED APPURTENANCES: REMOVE ALL ELECTRICAL APPURTENANCES
(DISCONNECTS, STARTERS, WIRING, CONDUIT, ETC.) ASSOCIATED WITH ITEMS
TO BE REMOVED INCLUDING EQUIPMENT TO BE REMOVED BY OTHERS.
KNOCKOUT PLUGS AND COVERS: ALL CONDUIT REMOVED SHALL BE REMOVED
IN ITS ENTIRETY, INCLUDING FITTINGS, MOUNTING DEVICES, MOUNTING
HARDWARE, ETC. PROVIDE CONDUIT PLUGS AND BLANKS FOR ALL OPENINGS
CREATED BY THE REMOVAL OF CONDUIT. PROVIDE BLANK COVER PLATES FOR
ALL OPENED OUTLET BOXES CREATED BY THE REMOVAL OF EQUIPMENT
AND/OR DEVICES
DEMOLISHED MATERIALS: ALL MATERIALS REMOVED UNDER DEMOLITION,
NOT TO BE RELOCATED OR DESIGNATED TO BE TURNED OVER TO THE
OWNER, SHALL BECOME THE PROPERTY OF THE CONTRACTOR AND SHALL BE
REMOVED COMPLETELY FROM THE SITE.
SCHEDULE OUTAGES: ALL WORK AND ALL POWER OUTAGES IN THE EXISTING
BUILDING SHALL BE SCHEDULED AT TIMES CONVENIENT TO THE OWNER.
NOTIFICATION: NOTIFY THE OWNER PRIOR TO TURNING OFF ANY CIRCUITS.
ABANDONED COMMUNICATIONS CABLING: ABANDONED COMMUNICATIONS
CABLING (TELEPHONE OR DATA) ABOVE THE CEILING SHALL BE REMOVED PER
NEC ARTICLE 645.
EXISTING TO REMAIN DEVICES: ALL EXISTING TO REMAIN DEVICES LOCATED IN
CEILINGS TO BE REMOVED/REPLACED, WHETHER SHOWN OR NOT, SHALL BE
TEMPORARILY SUPPORTED, OR REMOVED AND STORED FOR REINSTALLATION.
RIGHT OF REFUSAL: THE OWNER SHALL HAVE THE FIRST RIGHT OF REFUSAL
FOR ALL SALVAGED EQUIPMENT.
SAFETY SWITCH, 60A-3P, FU @ 30A, 3R
ELECTRICAL PANELBOARD
ELECTRICAL CIRCUIT RUN IN CONDUIT AND CIRCUIT HOMERUN TO
PANELBOARD (PANEL AND CIRCUIT DESIGNATION AS INDICATED). AS A
MINIMUM CONDITION, EACH SINGLE PHASE CIRCUIT SHALL HAVE 1 #12 PHASE
CONDUCTOR, 1 #12 NEUTRAL CONDUCTOR AND 1 #12 GROUNDING CONDUCTOR
IN 1/2" CONDUIT. PROVIDE ADDITIONAL PHASE CONDUCTORS AS REQUIRED
FOR "MULTIPLE PHASED" ELECTRICAL LOADS. PROVIDE NEUTRAL CONDUCTOR
TO ALL WALL SWITCH OUTLET BOXES WHETHER REQUIRED OR NOT. PROVIDE
ADDITIONAL "SWITCH LEG" CONDUCTORS TO PROVIDE THE LIGHT FIXTURE
CONTROL INDICATED. MULTIPLE SINGLE PHASE CONDUCTORS MAY BE
GROUPED TOGETHER IN A COMMON CONDUIT IN ACCORDANCE WITH THE NEC
AND AT THE CONTRACTOR'S DISCRETION. GROUNDING CONDUCTORS MAY BE
SHARED AS ALLOWED BY THE NEC. NEUTRAL CONDUCTORS SHALL NOT BE
SHARED. MULTI-POLE BREAKERS SHALL BE PROVIDED IN ACCORDANCE WITH
THE NEC WHERE MULTI-WIRE BRANCH CIRCUITS ARE REQUIRED. CONDUIT
LARGER THAN 1/2" AND CONDUCTORS LARGER THAN #12 SHALL BE AS
INDICATED.
POWER
GENERAL
NEW WORK NOTE SYMBOL
DEMOLITION NOTE SYMBOL
THE FOLLOWING SUBSCRIPTS SHALL APPLY TO RECEPTACLES WHERE USED:
ELECTRICAL LEGEND
AND
SWITCH RATING
NUMBER OF POLES
FUSE RATING (NF INDICATES NON-FUSED)
NEMA ENCLOSURE IF OTHER THAN NEMA 1
DUPLEX CONVENIENCE RECEPTACLE 20A, 120V, 18" AFF, UON
GFI: GROUND FAULT INTERRUPTING TYPE RECEPTACLE.
ABBREVIATIONS
A AMPERE
AFF ABOVE FINISHED FLOOR
AIC AMPERE INTERRUPTING CAPACITY
C CONDUIT
CFCI CONTRACTOR FURNISHED,
CONTRACTOR INSTALLED
CKT CIRCUIT
CB CIRCUIT BREAKER
EBU EMERGENCY BATTERY UNIT
EC EMPTY CONDUIT
EF EXHAUST FAN
EQUIP EQUIPMENT
ETR EXISTING TO REMAIN
EWC ELECTRIC WATER COOLER
EXIST EXISTING
FHP FRACTIONAL AC HORSEPOWER
FLA FULL LOAD AMPS
GFI GROUND FAULT INTERRUPTER
GND GROUND
KAIC THOUSAND AMPERE
INTERRUPTING CAPACITY
KVA KILO-VOLT-AMPERES
KW KILO-WATTS
LPW LUMENS PER WATT
LTG LIGHTING
MCA MINIMUM CIRCUIT AMPS
MCB MAIN CIRCUIT BREAKER
MFR MANUFACTURER
MLO MAIN LUGS ONLY
MTD MOUNTED
NEC NATIONAL ELECTRICAL CODE
NF NON-FUSED
NIC NOT IN CONTRACT
NTS NOT TO SCALE
OC ON CENTER
OFCI OWNER FURNISHED,
CONTRACTOR INSTALLED
OFOI OWNER FURNISHED,
OWNER INSTALLED
P POLE
PNL PANEL
PNLBD PANELBOARD
Ø PHASE
PRI PRIMARY
RECEPT RECEPTACLE
REQ'D REQUIRED
SEC SECONDARY
TBB TELEPHONE BACKBOARD
TYP TYPICAL
UON UNLESS OTHERWISE NOTED
V VOLT
W WATTS/WIRE
TFTI TENANT FURNISED, TENANT
INSTALLED
DUCT SMOKE DETECTION
D
RT
PHOTOELECTRIC DUCT SMOKE DETECTOR
REMOTE TEST/RESET/ANNUNCIATOR. CONTRACTOR TO PROVIDE KEY-
OPERATED REMOTE TEST AND RESET FUNCTIONS WITH INTEGRAL AUDIBLE
AND VISIBLE ANNUNCIATION OF THE ASSOCIATED DUCT SMOKE DETECTOR.
ALL LIFE SAFETY SYSTEMS (FIRE ALARM AND FIRE SPRINKLER) SHALL REMAIN OPERATIONAL DURING ALL PHASES OF
DEMOLITION AND NEW WORK.
LIFE SAFETY SYSTEMS NOTE:
PORTIONS OF THE BUILDING OUTSIDE OF THE AREA OF WORK SHALL REMAIN OCCUPIED THROUGHOUT THE DURATION OF CONSTRUCTION. CONTRACTOR SHALL TAKE CARE TO NOT INTERRUPT POWER, WATER, HVAC, ETC SERVING THE OCCUPIED AREAS OF THE BUILDING. IF SHUT DOWNS OR SHUT OFFS ARE REQUIRED, THE CONTRACTOR SHALL NOTIFY FACILITIES IN WRITING WITH THE PROPOSED SCHEDULE AND ANTICIPATED DURATION OF ANY REQUIRED UTILITY INTERRUPTIONS. SCHEDULE A MINIMUM OF 5 DAYS PRIOR TO COMMENCING WORK. CONTRACTOR SHALL NOT COMMENCE
WITH ANY INTERRUPTIONS WITHOUT WRITTEN AUTHORIZATION FROM THE OWNER.
OCCUPANCY NOTE: VIRGINIA UNIFORM STATEWIDE BUILDING CODE: VUSBC, 2021
CONSTRUCTION AND PROFESSIONAL SERVICES MANUAL: CPSM, 2025, REV 0
NATIONAL ELECTRICAL CODE: NFPA 70, 2020
AMERICANS WITH DISABILITIES ACT: ASAD, SEPTEMBER 15, 2010 - CH 2 SCOPING
NATIONAL FIRE ALARM AND SIGNALING CODE: NFPA 72, 2019
VIRGINIA ENERGY CONSERVATION CODE (VECC): 2021
CODE INFORMATION:
LIMITS OF DEMOLITION SYMBOL
LIMITS OF NEW WORK SYMBOL
F DUCT SMOKE DETECTION SYSTEM VISUAL ANNUNCIATION DEVICE
AHU-1AHU-2
HP-1
HP-2
DS
S
CURRENT
TRANSFORMER CABINET
METER
PANEL "A" - ETR
WP
ETR
100A-3P, FU@100A, 3R
100A-3P, FU@70A, 3R - ETR
30A-2P, NF, 3R - ETR
PANEL "A-1"
AHU-2; 100A-3P, NF
ETR
STACK ROOM
EQUIPMENT YARD
MECHANICAL ROOM
E B-13 1
D
ETR
D
FF
J JUNCTION BOX - ETR
PANEL "B" - ETR
AHU-1AHU-2
HP-1
HP-2
DS
S
PANEL "B" - ETR
CURRENT
TRANSFORMER CABINET
METER
PANEL "A" - ETR
WP
ETR
200A-3P, FU@125A, 3R
100A-3P, FU@70A, 3R - ETR
30A-2P, NF, 3R - ETR
3 #1, 1 #6 GND - 1 1/4"C
E
B-13; 3 #2, 1 #8 GND- 1 1/4"C
B-2; 3 #1/0, 1 #6 GND- 2"C
DD
NEW ACCESS PANEL
J
JUNCTION BOX - ETR
B-30; 3 #1, 1 #6 GND - EXISTING CONDUIT
F
PANEL "A-1"
PROJECT CODE
RFS JOB #
OF
DATE
D E S C
R
IP
T
IO
N
R E V
IS
IO
N S
D A
T E
1/4" = 1'-0" 5' 10'0' 5'
D M
V W
ID
G
E O
N C
S C
H
V A
C R
E P L A
C E M
E N
T
W
ID
G E O
N R
O A
D N
O R
F O
L K
2026-039
SCALE: 1/4" = 1'-0"
E101
AHU-2 ELECTRICAL CONNECTION. DISCONNECT AND REMOVE
CIRCUIT AND ASSOCIATED DISCONNECT BACK TO SOURCE.
AHU-1 ELECTRICAL CONNECTION. DISCONNECT AND REMOVE
CIRCUIT BACK TO PANEL "B".
HP-1 ELECTRICAL CONNECTION. DISCONNECT AND REMOVE CIRCUIT
AND ASSOCIATED DISCONNECT BACK TO SOURCE. RETAIN CONDUIT
AND JUNCTION BOX FOR REUSE IN NEW WORK AS INDICATED ON
PLAN.
PANEL "A-1" SEE POWER RISER FOR ADDITIONAL WORK.
DEMOLISH DUCT SMOKE DETECTOR AND ALL ASSOCIATED
CIRCUITRY.
DEMOLISH REMOTE STROBE SERVING AHU-1 DUCT SMOKE
DETECTOR.
DEMOLITION NOTES THIS SHEET
NEW WORK
SCALE: 1/4" = 1'-0"
NE
W
W
OR
K
AN
D
DE
MO
E
LE
CT
RI
CA
L P
LA
NS
PANEL "A-1", SEE POWER RISER FOR ADDITIONAL WORK.
AHU-1; 149 MCA, 150A MOCP, 208V, 3Ø.
PROVIDE KEY-OPERATED TEST RESET STATION WITH INTEGRAL
AUDIBLE SOUNDER AND VISIBLE INDICATOR. PROVIDE UNIT
LISTED AND COMPATIBLE WITH ASSOCIATED DUCT SMOKE
DETECTOR. LABEL WITH ASSOCIATED HVAC UNIT. UTILIZE
EXISTING PATHWAY FROM REMOTE STROBE TO AHU LOCATION
FOR CONNECTIVITY. EXTEND AND REWORK WIRING IN KIND AS
REQUIRED IN 1 1/4 C.
SURFACE MOUNT CONDUIT ALONG EXTERIOR WALL AND FLOOR
TO UNIT.
NOTES THIS SHEET
CONTRACTOR NOTE
CONTRACTOR SHALL PROVIDE (2) ADDITIONAL
SETS OF FUSES TO OWNER FOR SPARES.
DEMOLITION WORK
OF
DATE
D E S C
R
IP
T
IO
N
R E V
IS
IO
N S
D A
T E
D M
V W
ID
G
E O
N C
S C
H
V A
C R
E P L A
C E M
E N
T
W
ID
G E O
N R
O A
D N
O R
F O
L K
2026-039
E401
EL
EC
TR
IC
AL
P
AN
EL
S
CH
ED
UL
ES
A
ND
D
ET
AI
LS
EXISTING PANELBOARD A-1 SCHEDULE
100A MLO, 240/120 VOLT, 1 PHASE, 3 WIRE, 10 KAIC MINIMUM, SURFACE MOUNT, GROUND BUS
LOAD (AMPS) BKR CKT PHASE CKT BKR LOAD (AMPS)
LOAD SERVED A B TRIP NO. A B NO. TRIP A B LOAD SERVED
WATER COOLER 20/1P 1 2 20/1P SPARE
WTR COOLR, CAMERAS 20/1P 3 4 20/1P SPARE
O-MATIC MONITOR 20/1P 5 6 20/1P SPARE
VEND MACHINE 20/1P 7 8 20/1P SPARE
SPARE 20/1P 9 10 20/1P SPARE
SPACE ONLY 20/1P 11 12 30/2P SERVER ROOM A/C
SPACE ONLY 20/1P 13
SPACE ONLY 20/1P 15 16 60/2P WEST EXIT TRMP REC
SPACE ONLY 20/1P 17
SPACE ONLY 20/1P 19 20 50/2P EAST CORNER OPP
SPACE ONLY 20/1P 21
SPACE ONLY 20/1P 23 24 20/1P SPARE
FED BY PANEL "A" CIRCUIT A-14.
EXISTING SQUARE-D, QO LOAD CENTER, QOC24UF
MECHANICAL ROOM
EXISTING CURRENT TRANSFORMER
CABINET WITH 400:5A CURRENT
TRANSFORMERS
EXISTING DVP METER
#117950546
EXISTING 18" SQUARE WIREWAY
EXISTING 400A, 3P DISCONNECT SWITCH WITH
CURRENT LIMITING FUSES
CONDUCTORS, AND # 4/0 NEUTRAL, 4"C, ONE SPARE 4"C.
EXISTING DVP 150KVA PAD
MOUNTED TRANSFORMER 2
DISCONNECT AND RELOCATE PANEL "A-1". SEE FLOOR PLAN ON
SHEET E101 FOR LOCATION.
DISCONNECT AND REMOVE FEEDER.
DISCONNECT AND RETAIN TEMPORARY BRANCH CIRCUITS FOR
TEMPORARY A/C UNITS. RE-WORK CONDUIT AND WIRE AS
REQUIRED TO ACCOMMODATE DEMOLITION OF EXISTING WALL.
SEE NEW WORK NOTES THIS SHEET.
DISCONNECT AND RETAIN SERVER ROOM A/C BRANCH CIRCUIT.
RE-WORK CONDUIT AND WIRE AS REQUIRED TO
ACCOMMODATE DEMOLITION OF EXISTING WALL. SEE NEW
WORK NOTES THIS SHEET.
DISCONNECT AND RETAIN BRANCH CIRCUITS. RE-WORK
CONDUIT AND WIRE AS REQUIRED TO ACCOMMODATE
DEMOLITION OF EXISTING WALL. SEE NEW WORK NOTES THIS
SHEET.
3 #2, 1 #8 GND - 1 1/4"C
CONNECT SERVER ROOM A/C BRANCH CIRCUITS RETAINED DURING
DEMOLITION. EXTEND CONDUIT AND WIRE AS REQUIRED, MINIMUM OF #10
CONDUCTORS. PROVIDE CONDUIT EXTENSIONS, SPLICE BOXES, CONDUCTOR
SPLICING, AND REQUIRED SUPPORTS TO EXTEND CIRCUITS. FIELD-VERIFY
EXISTING CONDUCTOR SIZES. MAINTAIN CODE-COMPLIANT PHASE, NEUTRAL,
AND EQUIPMENT GROUNDING CONDUCTOR COLOR IDENTIFICATION PER NEC.
BRANCH CIRCUIT RETAINED DURING DEMOLITION. EXTEND CONDUIT AND WIRE
AS REQUIRED, MINIMUM OF #12 CONDUCTORS. PROVIDE CONDUIT EXTENSIONS,
SPLICE BOXES, CONDUCTOR SPLICING, AND REQUIRED SUPPORTS TO EXTEND
CIRCUITS. FIELD-VERIFY EXISTING CONDUCTOR SIZES. MAINTAIN
CODE-COMPLIANT PHASE, NEUTRAL, AND EQUIPMENT GROUNDING
CONDUCTOR COLOR IDENTIFICATION PER NEC.
CONTRACTOR SHALL CHECK AND TORQUE CONNECTIONS AND MECHANICAL
JOINTS IN SERVICE DISCONNECTS.
6 DUCT WIDTHS MINIMUM (OPTIMAL) 6 DUCT WIDTHS MINIMUM (OPTIMAL)
BEND OR OTHER
OBSTRUCTION AIR FLOW SUPPLY OR RETURN AIR FLOW
ENSURE PROPER SAMPLING TUBE SUPPORT, THAT THE SAMPLING
HOLES ARE DIRECTED FULLY INTO THE AIR PATH AND THAT THE
OTHER SIDE OF THE SAMPLING TUBE IS VISIBLE AND PLUGGED ON
THE OTHER SIDE OF THE DUCTWORK, IF REQUIRED BY THE DUCT
DETECTOR MANUFACTURER. ENSURE THE DETECTOR IS FULLY
INSTALLED IN ACCORDANCE WITH MANUFACTURER'S
RECOMMENDATIONS/INSTALLATION INSTRUCTIONS AND
PROPERLY TESTED UTILIZING A PROPERLY CALIBRATED
MANOMETER. PROVIDE READINGS AND EVIDENCE OF
CONTRACTOR PRELIMINARY TESTING BEFORE FINAL TESTS.
3 #3, 1 #8 GND - 1 1/4"C
EXISTING PANELBOARD B SCHEDULE
400A MLO, 208/120 VOLT, 3 PHASE, 4 WIRE, SURFACE MOUNT, GROUND BUS
LOAD (AMPS) BKR CKT PHASE CKT BKR LOAD (AMPS)
LOAD SERVED A B C TRIP NO. A B C NO. TRIP A B C LOAD SERVED
AHU-1 119.0 150/3P 1 2 20/1P 8.0 EXIST LIGHTS
NOTE 2 119.0 4 20/1P 7.0 EXIST EXHAUST FAN
119.0 6 20/1P 7.0 EXIST EXHAUST FAN
SPARE 20/1P 3 8 20/1P 8.0 BASEBOARD HEAT
SPARE 20/1P 5 10 20/1P 8.0 BASEBOARD HEAT
SPARE 20/1P 7 12 20/1P 8.0 BASEBOARD HEAT
SPARE 20/1P 9 14 20/1P 8.0 BASEBOARD HEAT
SPARE 20/1P 11 16 20/1P SPARE
SPARE 20/1P 13 18 20/1P SPARE
AHU-2 78.4 100/3P 13 20 20/1P SPARE
EXISTING 78.4 22 20/1P SPARE
78.4 24 30/2P 22.0 WATER HEATER
SURGE 60/3P 25 22.0
SUPPRESSOR 26 40/2P SPARE
EXISTING
BATHROOM EXH FAN 2.5 20/1P 19 28 70/3P 38.5 HP-2
EXISTING LOAD 10.0 20/1P 21 38.5
EXISTING LOAD 10.0 20/1P 23 38.5
SPACE ONLY 30 125/3P 74.4 HP-1
SPACE ONLY 74.4 NOTE 1
SPACE ONLY 74.4
TOTAL 199.9 207.4 207.4 158.9 127.9 149.9 TOTAL
TOTAL CONNECTED AMPS A: 358.8 B: 335.3 C: 357.3
EXISTING SQUARE-D, ALL LOADS INDICATED ARE EXISTING UNLESS IN BOLD.
1. REMOVE FA36100 CIRCUIT BREAKER AND REPLACE WITH 125A-3P CIRCUIT BREAKER.
2. REMOVE FA36175 CIRCUIT BREAKER AND REPLACE WITH 150A-3P CIRCUIT BREAKER.
PANEL "A-1", SEE FLOOR PLAN ON SHEET E101 FOR LOCATION.
CONNECT TEMPORARY BRANCH CIRCUITS FOR TEMPORARY A/C UNITS.
EXISTING UNDERGROUND 208Y/120V, 3Ø, 4W SERVICE ENTRANCE/LATERAL, 3-500KCMIL ALUMINUM
EXISTING SERVICE DISCONNECT SWITCH, TYPICAL