Section_J_-_Att_No__009_2025-02-25_SAN-FRANCISCO-MARITIME-38-BLDG-E_SuppressionScan_0004.pdf
PDF 742 KB Posted
- Attached to
- HALON FIRE SUPPRESSION SYSTEM REPLACEMEN
- Solicitation number
- 140P8625Q0045
About this file
This document is a comprehensive fire suppression system inspection report for the San Francisco Maritime 38 (Building E 3rd Floor Art Rare) facility, conducted by Sabah International A Division of Sciens Building on February 25, 2025. The inspection covered a clean agent Halon 1301 fire suppression system installed in a rare book vault, with all 17 inspected system components passing the evaluation.
Key details include a Kidde KDR-100 control panel and system installed in 1982, with four Fenwal smoke detectors, two sealed lead acid batteries, an abort station, manual pull station, bell, horn, and horn/strobe notification devices. The Halon tank weighs 300.4 pounds with an actual agent weight of 155 pounds, and the system's last hydrostatic test was performed on September 6, 2001. The inspection report comprehensively documents the system's condition, testing results, device inventory, and warranty status, indicating the fire suppression system is fully operational and maintained.
View the file
Other files
Show all 13
On GovTribe
Work with this file
- Download the original file
- Contacts named in this file
- Similar government files
- Ask GovTribe AI about this file
Text version
SAN FRANCISCO MARITIME 38
(BLDG E 3RD FLR ART RARE)
38 FORT MASON
BLDG E 3RD FLR ART RM RARE VAULT
SAN FRANCISCO, CA 94123
415-561-7022
Building Contact: Stephen Taylor Horton Title: -
Company: Sabah International A Division of Sciens Building Contact: Suraj Narayan Title: Service Technician
Fire Suppression Systems
INSPECTION
CERTIFICATE
Annual Inspection Feb 25, 2025Inspection Date:
This Inspection was performed in accordance with applicable Standards. The subsequent pages of this report provide performance measurements, listed ranges of acceptable results, and complete documentation of the inspection. Whenever discrepancies exist between acceptable performance standards and actual test results, notes and/or recommended solutions have been proposed or provided for immediate review and approval.
Page of 1 12 Executive Summary
Sabah International A Division of Sciens Building Download Date: 02/27/2025
EXECUTIVE SUMMARY
Generated by: BuildingReports.com
Building Information
SAN FRANCISCO MARITIME 38(BLDG E
3RD FLR ART RARE)
38 FORT MASON
BLDG E 3RD FLR ART RM RARE VAULT
SAN FRANCISCO, CA 94123
United States of America
Contact: Stephen Taylor Horton
Phone: 415-561-7022
Fax:
Mobile:
Email: taylor_horton@nps.gov
Inspection Performed By Sabah International A Division of Sciens Building 5925 Stoneridge Drive Pleasanton, California 94588 United States of America
Inspector: Suraj Narayan
Phone: 925-872-5871
Fax:
Mobile:
Email: snarayan@sciensbuildingsolutions.
com
System Control Unit Manufacturer: Kidde Discharge Time: Predischarge Delay:
Model Number: KDR-100 Install Date: 01/01/1982
Software Version: Version Date: 01/01/1982
Location: 3rd BLDG E RARE BOOK
VAULT HALON FACP 22740968
Current Protection: Fuse
Systems Inspected System Type Protected Area Devices
Clean Agent Rare Book Vault 1
Clean Agent Rare Vault 16
Page of 2 12 Executive Summary
Sabah International A Division of Sciens Building Download Date: 02/27/2025
Building: SAN FRANCISCO MARITIME 38
(BLDG E 3RD FLR ART RARE)
Contact: Stephen Taylor Horton
Signed: Feb 25, 2025
Company: Sabah International A Division of Sciens Building Inspector: Suraj Narayan
Signed: Feb 25, 2025
Inspection Summary
Category
Total Items Serviced Passed Failed/Other
Qty % Qty % Qty % Qty %
Auxiliary 3 17.65% 3 100.00% 3 100.00% 0 0.00%
Container 2 11.76% 2 100.00% 2 100.00% 0 0.00%
Controls 3 17.65% 3 100.00% 3 100.00% 0 0.00%
Detecting 4 23.53% 4 100.00% 4 100.00% 0 0.00%
Initiating 2 11.76% 2 100.00% 2 100.00% 0 0.00%
Notification 3 17.65% 3 100.00% 3 100.00% 0 0.00%
Totals 17 100% 17 100.00% 17 100.00% 0 0.00%
Certification
Page of 3 12 Inspection & Testing
Sabah International A Division of Sciens Building Download Date: 02/27/2025
INSPECTION & TESTING
Generated by: BuildingReports.com
The Inspection & Testing section lists all of the items inspected in your building. Items are grouped by Passed or Failed/Other .
Items are listed by Category. Each item includes the services performed, and the time & date at which testing occurred.
Building: SAN FRANCISCO MARITIME 38(BLDG E 3RD FLR ART RARE)
Device Type Location Service Time Date
PASSED
Clean Agent Rare Book Vault
Control Panel 3rd BLDG E RARE BOOK VAULT HALON FACP Tested 1:26:23 PM 02/25/2025
Clean Agent Rare Vault
Abort Station 3rd BLDG E RARE BOOK VAULT ABORT
STATION
Tested 1:26:13 PM 02/25/2025
Agent Tank 3rd BLDG E RARE BOOK VAULT HALON
TANK
Tested 1:23:24 PM 02/25/2025
Battery 3rd BLDG E RARE BOOK VAULT FACP
BATTERY
Tested 1:25:25 PM 02/25/2025
Battery 3rd BLDG E RARE BOOK VAULT FACP
BATTERY
Tested 1:25:37 PM 02/25/2025
Bell 3rd BLDG E RARE BOOK VAULT BELL Tested 1:26:39 PM 02/25/2025
Horn 3rd BLDG E RARE BOOK VAULT HORN Tested 1:26:41 PM 02/25/2025
Horn/Strobe 3rd BLDG E RARE BOOK VAULT
HORNSTROBE
Tested 1:26:44 PM 02/25/2025
Manual Station 3rd BLDG E RARE BOOK VAULT PULL
STATION
Tested 1:26:05 PM 02/25/2025
Nozzle 3rd BLDG E RARE BOOK VAULT NOZZLE Tested 1:26:18 PM 02/25/2025
Relay 3rd BLDG E RARE BOOK VAULT ALARM
RELAY TO FACP
Tested 1:26:32 PM 02/25/2025
Relay 3rd BLDG E RARE BOOK VAULT TROUBLE
RELAY TO FACP
Tested 1:26:28 PM 02/25/2025
Releasing Device 3rd BLDG E RARE BOOK VAULT SOLENOID Tested 1:23:45 PM 02/25/2025
Page of 4 12 Inspection & Testing
Sabah International A Division of Sciens Building Download Date: 02/27/2025
Device Type Location Service Time Date
PASSED (continued)
Clean Agent Rare Vault (continued)
Smoke Detector 3rd BLDG E RARE BOOK VAULT SMOKE Tested 1:26:48 PM 02/25/2025
Smoke Detector 3rd BLDG E RARE BOOK VAULT SMOKE Tested 1:26:51 PM 02/25/2025
Smoke Detector 3rd BLDG E RARE BOOK VAULT SMOKE Tested 1:26:53 PM 02/25/2025
Smoke Detector 3rd BLDG E RARE BOOK VAULT SMOKE Tested 1:26:55 PM 02/25/2025
Page of 5 12 Auxiliary Functions Testing
Sabah International A Division of Sciens Building Download Date: 02/27/2025
All Protected AreasBuilding: SAN FRANCISCO MARITIME 38(BLDG E
3RD FLR ART RARE)
AUXILIARY FUNCTIONS TESTING
Generated by: BuildingReports.com
The Auxiliary Functions Testing section lists each of the ancillary items, systems, and emergency equipment that are controlled by the system control unit. Items are grouped by Passed or Failed/Other. The items are listed by device type, and a check box is provided to indicate if the test conducted was simulated.
Type Location Comment ScanID Simulated
PASSED
Relay
Non-programmable 3rd BLDG E RARE BOOK VAULT ALARM
RELAY TO FACP
Passed 22740967 ☐
Non-programmable 3rd BLDG E RARE BOOK VAULT TROUBLE
RELAY TO FACP
Passed 22740966 ☐
Releasing Device
Solenoid 3rd BLDG E RARE BOOK VAULT SOLENOID Passed 22740961 ☐
Page of 6 12 Notification Report
Sabah International A Division of Sciens Building Download Date: 02/27/2025
NOTIFICATION REPORT
Generated by: BuildingReports.com
Message, signals, signage and communications for occupants of areas protected within this inspection.
Building: SAN FRANCISCO MARITIME 38(BLDG E 3RD FLR ART RARE)
Device Type Type Location Comment ScanID
CLEAN AGENT RARE VAULT
Bell Alarm 3rd BLDG E RARE BOOK VAULT BELL Passed 22740958
Horn/Strobe Alarm 3rd BLDG E RARE BOOK VAULT
HORNSTROBE
Passed 22740959
Horn Alarm 3rd BLDG E RARE BOOK VAULT HORN Passed 22740971
Page of 7 12 Battery & Power Supply Testing
Sabah International A Division of Sciens Building Download Date: 02/27/2025
All Protected AreasBuilding: SAN FRANCISCO MARITIME 38(BLDG E
3RD FLR ART RARE)
BATTERY & POWER SUPPLY TESTING
Generated by: BuildingReports.com
The Battery & Power Supply Testing section details the readings and measurements of batteries and power supplies used to provide power to the fire alarm and life safety systems. Items are grouped by Passed or Failed/Other.
Type Location Rated
Ah Rated Volts Pre Test
Post Test Min Ah
Tested Ah
PASSED
Clean Agent Rare Vault
Battery
Sealed Lead Acid 3rd BLDG E RARE BOOK VAULT
FACP BATTERY
7.0 12.0 13 12.96 4.6 7.4
Sealed Lead Acid 3rd BLDG E RARE BOOK VAULT
FACP BATTERY
7.0 12.0 13 12.96 4.6 7.4
Page of 8 12 Agent Container Report
Sabah International A Division of Sciens Building Download Date: 02/27/2025
All Protected AreasBuilding: SAN FRANCISCO MARITIME 38(BLDG E
3RD FLR ART RARE)
AGENT CONTAINER REPORT
Generated by: BuildingReports.com
A container of stored agent to be used in case of a fire emergency.
CLEAN AGENT RARE VAULT
Agent Tank
Location Manufacturer Model # Container ScanID
3rd BLDG E RARE BOOK VAULT HALON
TANK
Kidde Central Storage 22740960
Gross Weight Tare Weight Agent Actual Weight Agent Weight Temperature
300.4 146.4 Halon 1301 301.4 155 22 c
Pressure Lvl. Indicator Liquid Level Release Type Supply Hydro Date Serial #
370 ☐ NA Electrical Primary 09/06/2001 WF19779AA
Nozzle
Location Manufacturer Model # Qty Install Date ScanID
3rd BLDG E RARE BOOK VAULT
NOZZLE
Kidde 4 01/01/1982 60792306
Page of 9 12 Clean Agent Fire Suppression
Sabah International A Division of Sciens Building Download Date: 02/27/2025
Clean Agent Rare VaultBuilding: SAN FRANCISCO MARITIME 38(BLDG E
3RD FLR ART RARE)
Clean Agent Rare Book VaultBuilding: SAN FRANCISCO MARITIME 38(BLDG E
3RD FLR ART RARE)
CLEAN AGENT FIRE SUPPRESSION
Generated by: BuildingReports.com
Electrically non-conducting, volatile, or gaseous fire extinguishant that does not leave a residue upon evaporation. The agents were introduced in response to international restrictions on the production of certain halon fire-extinguishing agents under the Montreal Protocol signed September 16, 1987, as amended.
Device Type Location Manufacturer Model Number ScanID
PASSED
Controls
Control Panel 3rd BLDG E RARE BOOK VAULT
HALON FACP
Kidde KDR-100 22740968
Device Type Location Manufacturer Model Number ScanID
PASSED
Auxiliary
Relay 3rd BLDG E RARE BOOK VAULT
ALARM RELAY TO FACP
Kidde KDR-100 22740967
Relay 3rd BLDG E RARE BOOK VAULT
TROUBLE RELAY TO FACP
Kidde KDR-100 22740966
Releasing Device 3rd BLDG E RARE BOOK VAULT
SOLENOID
Kidde 22740961
Container
Agent Tank 3rd BLDG E RARE BOOK VAULT
HALON TANK
Kidde 22740960
Nozzle 3rd BLDG E RARE BOOK VAULT
NOZZLE
Kidde 60792306
Controls
Battery 3rd BLDG E RARE BOOK VAULT
FACP BATTERY
Power Patrol FAS1075 22740970
Page of 10 12 Clean Agent Fire Suppression
Sabah International A Division of Sciens Building Download Date: 02/27/2025
Device Type Location Manufacturer Model Number ScanID
PASSED (continued)
Controls (continued)
Battery 3rd BLDG E RARE BOOK VAULT
FACP BATTERY
Power Patrol FAS1075 22740969
Detecting
Smoke Detector 3rd BLDG E RARE BOOK VAULT
SMOKE
Fenwal 22740973
Smoke Detector 3rd BLDG E RARE BOOK VAULT
SMOKE
Fenwal 22740972
Smoke Detector 3rd BLDG E RARE BOOK VAULT
SMOKE
Fenwal 22740963
Smoke Detector 3rd BLDG E RARE BOOK VAULT
SMOKE
Fenwal 22740962
Initiating
Abort Station 3rd BLDG E RARE BOOK VAULT
ABORT STATION
Kidde 22740964
Manual Station 3rd BLDG E RARE BOOK VAULT
PULL STATION
Kidde 22740965
Notification
Bell 3rd BLDG E RARE BOOK VAULT
BELL
Kidde 508676 22740958
Horn 3rd BLDG E RARE BOOK VAULT
HORN
Federal Signal Vibratone 22740971
Horn/Strobe 3rd BLDG E RARE BOOK VAULT
HORNSTROBE
Kidde 22740959
Page of 11 12 Inventory & Warranty Report
Sabah International A Division of Sciens Building Download Date: 02/27/2025
INVENTORY & WARRANTY REPORT
Generated by: BuildingReports.com
The Inventory & Warranty Report lists each of the devices and items that are included in your Inspection Report. A complete inventory count by device type and category is provided. Items installed within the last 90 days, within the last year, and devices installed for two years or more are grouped together for easy reference.
Building: SAN FRANCISCO MARITIME 38(BLDG E 3RD FLR ART RARE)
Device or Type Category % of Inventory Quantity
Abort Station Initiating 5.88% 1
Agent Tank Container 5.88% 1
Battery Controls 11.76% 2
Bell Notification 5.88% 1
Control Panel Controls 5.88% 1
Horn Notification 5.88% 1
Horn/Strobe Notification 5.88% 1
Manual Station Initiating 5.88% 1
Nozzle Container 5.88% 1
Relay Auxiliary 11.76% 2
Releasing Device Auxiliary 5.88% 1
Smoke Detector Detecting 23.53% 4
Type Qty Model # Description Install Date
IN SERVICE - 25 YEARS OR OLDER
Clean Agent Rare Book Vault
Control Panel 1 KDR-100 01/01/1982
IN SERVICE - 1 YEAR TO 2 YEARS
Clean Agent Rare Vault
Battery 2 FAS1075 Sealed Lead Acid 02/06/2024
IN SERVICE - 25 YEARS OR OLDER
Page of 12 12 Inventory & Warranty Report
Sabah International A Division of Sciens Building Download Date: 02/27/2025
Type Qty Model # Description Install Date
IN SERVICE - 25 YEARS OR OLDER (continued)
Clean Agent Rare Vault
Horn 1 Vibratone Alarm 01/01/1982
Smoke Detector 4 Ionization 01/01/1982
Abort Station 1 PUSH/HOLD 01/01/1982
Agent Tank 1 01/01/1982
Bell 1 508676 Alarm 01/01/1982
Horn/Strobe 1 Alarm 01/01/1982
Manual Station 1 Dual Action 01/01/1982
Nozzle 1 01/01/1982
Relay 2 KDR-100 Non-programmable 01/01/1982
Releasing Device 1 Solenoid 01/01/1982
| Cover Page |
| Executive Summary |
| Inspection & Testing |
| Auxiliary Functions Testing |
| Notification Report |
| Battery & Power Supply Testing |
| Agent Container Report |
| Clean Agent Fire Suppression |
| Inventory & Warranty Report |