HALON FIRE SUPPRESSION SYSTEM REPLACEMEN
Solicitation number
140P8625Q0045
Issued by

About this file

This document is a comprehensive fire suppression system inspection report for the San Francisco Maritime 38 (Building E 3rd Floor Art Rare) facility, conducted by Sabah International A Division of Sciens Building on February 25, 2025. The inspection covered a clean agent Halon 1301 fire suppression system installed in a rare book vault, with all 17 inspected system components passing the evaluation.

Key details include a Kidde KDR-100 control panel and system installed in 1982, with four Fenwal smoke detectors, two sealed lead acid batteries, an abort station, manual pull station, bell, horn, and horn/strobe notification devices. The Halon tank weighs 300.4 pounds with an actual agent weight of 155 pounds, and the system's last hydrostatic test was performed on September 6, 2001. The inspection report comprehensively documents the system's condition, testing results, device inventory, and warranty status, indicating the fire suppression system is fully operational and maintained.

View the file

Other files

Show all 13

On GovTribe

Work with this file

  • Download the original file
  • Contacts named in this file
  • Similar government files
  • Ask GovTribe AI about this file

Text version

SAN FRANCISCO MARITIME 38

(BLDG E 3RD FLR ART RARE)

38 FORT MASON

BLDG E 3RD FLR ART RM RARE VAULT

SAN FRANCISCO, CA 94123

415-561-7022

Building Contact: Stephen Taylor Horton Title: -

Company: Sabah International A Division of Sciens Building Contact: Suraj Narayan Title: Service Technician

Fire Suppression Systems

INSPECTION

CERTIFICATE

Annual Inspection Feb 25, 2025Inspection Date:

This Inspection was performed in accordance with applicable Standards. The subsequent pages of this report provide performance measurements, listed ranges of acceptable results, and complete documentation of the inspection. Whenever discrepancies exist between acceptable performance standards and actual test results, notes and/or recommended solutions have been proposed or provided for immediate review and approval.

Page of 1 12 Executive Summary

Sabah International A Division of Sciens Building Download Date: 02/27/2025

EXECUTIVE SUMMARY

Generated by: BuildingReports.com

Building Information

SAN FRANCISCO MARITIME 38(BLDG E

3RD FLR ART RARE)

38 FORT MASON

BLDG E 3RD FLR ART RM RARE VAULT

SAN FRANCISCO, CA 94123

United States of America

Contact: Stephen Taylor Horton

Phone: 415-561-7022

Fax:

Mobile:

Email: taylor_horton@nps.gov

Inspection Performed By Sabah International A Division of Sciens Building 5925 Stoneridge Drive Pleasanton, California 94588 United States of America

Inspector: Suraj Narayan

Phone: 925-872-5871

Fax:

Mobile:

Email: snarayan@sciensbuildingsolutions.

com

System Control Unit Manufacturer: Kidde Discharge Time: Predischarge Delay:

Model Number: KDR-100 Install Date: 01/01/1982

Software Version: Version Date: 01/01/1982

Location: 3rd BLDG E RARE BOOK

VAULT HALON FACP 22740968

Current Protection: Fuse

Systems Inspected System Type Protected Area Devices

Clean Agent Rare Book Vault 1

Clean Agent Rare Vault 16

Page of 2 12 Executive Summary

Sabah International A Division of Sciens Building Download Date: 02/27/2025

Building: SAN FRANCISCO MARITIME 38

(BLDG E 3RD FLR ART RARE)

Contact: Stephen Taylor Horton

Signed: Feb 25, 2025

Company: Sabah International A Division of Sciens Building Inspector: Suraj Narayan

Signed: Feb 25, 2025

Inspection Summary

Category

Total Items Serviced Passed Failed/Other

Qty % Qty % Qty % Qty %

Auxiliary 3 17.65% 3 100.00% 3 100.00% 0 0.00%

Container 2 11.76% 2 100.00% 2 100.00% 0 0.00%

Controls 3 17.65% 3 100.00% 3 100.00% 0 0.00%

Detecting 4 23.53% 4 100.00% 4 100.00% 0 0.00%

Initiating 2 11.76% 2 100.00% 2 100.00% 0 0.00%

Notification 3 17.65% 3 100.00% 3 100.00% 0 0.00%

Totals 17 100% 17 100.00% 17 100.00% 0 0.00%

Certification

Page of 3 12 Inspection & Testing

Sabah International A Division of Sciens Building Download Date: 02/27/2025

INSPECTION & TESTING

Generated by: BuildingReports.com

The Inspection & Testing section lists all of the items inspected in your building. Items are grouped by Passed or Failed/Other .

Items are listed by Category. Each item includes the services performed, and the time & date at which testing occurred.

Building: SAN FRANCISCO MARITIME 38(BLDG E 3RD FLR ART RARE)

Device Type Location Service Time Date

PASSED

Clean Agent Rare Book Vault

Control Panel 3rd BLDG E RARE BOOK VAULT HALON FACP Tested 1:26:23 PM 02/25/2025

Clean Agent Rare Vault

Abort Station 3rd BLDG E RARE BOOK VAULT ABORT

STATION

Tested 1:26:13 PM 02/25/2025

Agent Tank 3rd BLDG E RARE BOOK VAULT HALON

TANK

Tested 1:23:24 PM 02/25/2025

Battery 3rd BLDG E RARE BOOK VAULT FACP

BATTERY

Tested 1:25:25 PM 02/25/2025

Battery 3rd BLDG E RARE BOOK VAULT FACP

BATTERY

Tested 1:25:37 PM 02/25/2025

Bell 3rd BLDG E RARE BOOK VAULT BELL Tested 1:26:39 PM 02/25/2025

Horn 3rd BLDG E RARE BOOK VAULT HORN Tested 1:26:41 PM 02/25/2025

Horn/Strobe 3rd BLDG E RARE BOOK VAULT

HORNSTROBE

Tested 1:26:44 PM 02/25/2025

Manual Station 3rd BLDG E RARE BOOK VAULT PULL

STATION

Tested 1:26:05 PM 02/25/2025

Nozzle 3rd BLDG E RARE BOOK VAULT NOZZLE Tested 1:26:18 PM 02/25/2025

Relay 3rd BLDG E RARE BOOK VAULT ALARM

RELAY TO FACP

Tested 1:26:32 PM 02/25/2025

Relay 3rd BLDG E RARE BOOK VAULT TROUBLE

RELAY TO FACP

Tested 1:26:28 PM 02/25/2025

Releasing Device 3rd BLDG E RARE BOOK VAULT SOLENOID Tested 1:23:45 PM 02/25/2025

Page of 4 12 Inspection & Testing

Sabah International A Division of Sciens Building Download Date: 02/27/2025

Device Type Location Service Time Date

PASSED (continued)

Clean Agent Rare Vault (continued)

Smoke Detector 3rd BLDG E RARE BOOK VAULT SMOKE Tested 1:26:48 PM 02/25/2025

Smoke Detector 3rd BLDG E RARE BOOK VAULT SMOKE Tested 1:26:51 PM 02/25/2025

Smoke Detector 3rd BLDG E RARE BOOK VAULT SMOKE Tested 1:26:53 PM 02/25/2025

Smoke Detector 3rd BLDG E RARE BOOK VAULT SMOKE Tested 1:26:55 PM 02/25/2025

Page of 5 12 Auxiliary Functions Testing

Sabah International A Division of Sciens Building Download Date: 02/27/2025

All Protected AreasBuilding: SAN FRANCISCO MARITIME 38(BLDG E

3RD FLR ART RARE)

AUXILIARY FUNCTIONS TESTING

Generated by: BuildingReports.com

The Auxiliary Functions Testing section lists each of the ancillary items, systems, and emergency equipment that are controlled by the system control unit. Items are grouped by Passed or Failed/Other. The items are listed by device type, and a check box is provided to indicate if the test conducted was simulated.

Type Location Comment ScanID Simulated

PASSED

Relay

Non-programmable 3rd BLDG E RARE BOOK VAULT ALARM

RELAY TO FACP

Passed 22740967 ☐

Non-programmable 3rd BLDG E RARE BOOK VAULT TROUBLE

RELAY TO FACP

Passed 22740966 ☐

Releasing Device

Solenoid 3rd BLDG E RARE BOOK VAULT SOLENOID Passed 22740961 ☐

Page of 6 12 Notification Report

Sabah International A Division of Sciens Building Download Date: 02/27/2025

NOTIFICATION REPORT

Generated by: BuildingReports.com

Message, signals, signage and communications for occupants of areas protected within this inspection.

Building: SAN FRANCISCO MARITIME 38(BLDG E 3RD FLR ART RARE)

Device Type Type Location Comment ScanID

CLEAN AGENT RARE VAULT

Bell Alarm 3rd BLDG E RARE BOOK VAULT BELL Passed 22740958

Horn/Strobe Alarm 3rd BLDG E RARE BOOK VAULT

HORNSTROBE

Passed 22740959

Horn Alarm 3rd BLDG E RARE BOOK VAULT HORN Passed 22740971

Page of 7 12 Battery & Power Supply Testing

Sabah International A Division of Sciens Building Download Date: 02/27/2025

All Protected AreasBuilding: SAN FRANCISCO MARITIME 38(BLDG E

3RD FLR ART RARE)

BATTERY & POWER SUPPLY TESTING

Generated by: BuildingReports.com

The Battery & Power Supply Testing section details the readings and measurements of batteries and power supplies used to provide power to the fire alarm and life safety systems. Items are grouped by Passed or Failed/Other.

Type Location Rated

Ah Rated Volts Pre Test

Post Test Min Ah

Tested Ah

PASSED

Clean Agent Rare Vault

Battery

Sealed Lead Acid 3rd BLDG E RARE BOOK VAULT

FACP BATTERY

7.0 12.0 13 12.96 4.6 7.4

Sealed Lead Acid 3rd BLDG E RARE BOOK VAULT

FACP BATTERY

7.0 12.0 13 12.96 4.6 7.4

Page of 8 12 Agent Container Report

Sabah International A Division of Sciens Building Download Date: 02/27/2025

All Protected AreasBuilding: SAN FRANCISCO MARITIME 38(BLDG E

3RD FLR ART RARE)

AGENT CONTAINER REPORT

Generated by: BuildingReports.com

A container of stored agent to be used in case of a fire emergency.

CLEAN AGENT RARE VAULT

Agent Tank

Location Manufacturer Model # Container ScanID

3rd BLDG E RARE BOOK VAULT HALON

TANK

Kidde Central Storage 22740960

Gross Weight Tare Weight Agent Actual Weight Agent Weight Temperature

300.4 146.4 Halon 1301 301.4 155 22 c

Pressure Lvl. Indicator Liquid Level Release Type Supply Hydro Date Serial #

370 ☐ NA Electrical Primary 09/06/2001 WF19779AA

Nozzle

Location Manufacturer Model # Qty Install Date ScanID

3rd BLDG E RARE BOOK VAULT

NOZZLE

Kidde 4 01/01/1982 60792306

Page of 9 12 Clean Agent Fire Suppression

Sabah International A Division of Sciens Building Download Date: 02/27/2025

Clean Agent Rare VaultBuilding: SAN FRANCISCO MARITIME 38(BLDG E

3RD FLR ART RARE)

Clean Agent Rare Book VaultBuilding: SAN FRANCISCO MARITIME 38(BLDG E

3RD FLR ART RARE)

CLEAN AGENT FIRE SUPPRESSION

Generated by: BuildingReports.com

Electrically non-conducting, volatile, or gaseous fire extinguishant that does not leave a residue upon evaporation. The agents were introduced in response to international restrictions on the production of certain halon fire-extinguishing agents under the Montreal Protocol signed September 16, 1987, as amended.

Device Type Location Manufacturer Model Number ScanID

PASSED

Controls

Control Panel 3rd BLDG E RARE BOOK VAULT

HALON FACP

Kidde KDR-100 22740968

Device Type Location Manufacturer Model Number ScanID

PASSED

Auxiliary

Relay 3rd BLDG E RARE BOOK VAULT

ALARM RELAY TO FACP

Kidde KDR-100 22740967

Relay 3rd BLDG E RARE BOOK VAULT

TROUBLE RELAY TO FACP

Kidde KDR-100 22740966

Releasing Device 3rd BLDG E RARE BOOK VAULT

SOLENOID

Kidde 22740961

Container

Agent Tank 3rd BLDG E RARE BOOK VAULT

HALON TANK

Kidde 22740960

Nozzle 3rd BLDG E RARE BOOK VAULT

NOZZLE

Kidde 60792306

Controls

Battery 3rd BLDG E RARE BOOK VAULT

FACP BATTERY

Power Patrol FAS1075 22740970

Page of 10 12 Clean Agent Fire Suppression

Sabah International A Division of Sciens Building Download Date: 02/27/2025

Device Type Location Manufacturer Model Number ScanID

PASSED (continued)

Controls (continued)

Battery 3rd BLDG E RARE BOOK VAULT

FACP BATTERY

Power Patrol FAS1075 22740969

Detecting

Smoke Detector 3rd BLDG E RARE BOOK VAULT

SMOKE

Fenwal 22740973

Smoke Detector 3rd BLDG E RARE BOOK VAULT

SMOKE

Fenwal 22740972

Smoke Detector 3rd BLDG E RARE BOOK VAULT

SMOKE

Fenwal 22740963

Smoke Detector 3rd BLDG E RARE BOOK VAULT

SMOKE

Fenwal 22740962

Initiating

Abort Station 3rd BLDG E RARE BOOK VAULT

ABORT STATION

Kidde 22740964

Manual Station 3rd BLDG E RARE BOOK VAULT

PULL STATION

Kidde 22740965

Notification

Bell 3rd BLDG E RARE BOOK VAULT

BELL

Kidde 508676 22740958

Horn 3rd BLDG E RARE BOOK VAULT

HORN

Federal Signal Vibratone 22740971

Horn/Strobe 3rd BLDG E RARE BOOK VAULT

HORNSTROBE

Kidde 22740959

Page of 11 12 Inventory & Warranty Report

Sabah International A Division of Sciens Building Download Date: 02/27/2025

INVENTORY & WARRANTY REPORT

Generated by: BuildingReports.com

The Inventory & Warranty Report lists each of the devices and items that are included in your Inspection Report. A complete inventory count by device type and category is provided. Items installed within the last 90 days, within the last year, and devices installed for two years or more are grouped together for easy reference.

Building: SAN FRANCISCO MARITIME 38(BLDG E 3RD FLR ART RARE)

Device or Type Category % of Inventory Quantity

Abort Station Initiating 5.88% 1

Agent Tank Container 5.88% 1

Battery Controls 11.76% 2

Bell Notification 5.88% 1

Control Panel Controls 5.88% 1

Horn Notification 5.88% 1

Horn/Strobe Notification 5.88% 1

Manual Station Initiating 5.88% 1

Nozzle Container 5.88% 1

Relay Auxiliary 11.76% 2

Releasing Device Auxiliary 5.88% 1

Smoke Detector Detecting 23.53% 4

Type Qty Model # Description Install Date

IN SERVICE - 25 YEARS OR OLDER

Clean Agent Rare Book Vault

Control Panel 1 KDR-100 01/01/1982

IN SERVICE - 1 YEAR TO 2 YEARS

Clean Agent Rare Vault

Battery 2 FAS1075 Sealed Lead Acid 02/06/2024

IN SERVICE - 25 YEARS OR OLDER

Page of 12 12 Inventory & Warranty Report

Sabah International A Division of Sciens Building Download Date: 02/27/2025

Type Qty Model # Description Install Date

IN SERVICE - 25 YEARS OR OLDER (continued)

Clean Agent Rare Vault

Horn 1 Vibratone Alarm 01/01/1982

Smoke Detector 4 Ionization 01/01/1982

Abort Station 1 PUSH/HOLD 01/01/1982

Agent Tank 1 01/01/1982

Bell 1 508676 Alarm 01/01/1982

Horn/Strobe 1 Alarm 01/01/1982

Manual Station 1 Dual Action 01/01/1982

Nozzle 1 01/01/1982

Relay 2 KDR-100 Non-programmable 01/01/1982

Releasing Device 1 Solenoid 01/01/1982

Cover Page
Executive Summary
Inspection & Testing
Auxiliary Functions Testing
Notification Report
Battery & Power Supply Testing
Agent Container Report
Clean Agent Fire Suppression
Inventory & Warranty Report