Section_J_-_Att_No__008_2025-02-25_SAN-FRANCISCO-MARITIME-38--1ST-F_SuppressionScan_0004.pdf
PDF 743 KB Posted
- Attached to
- HALON FIRE SUPPRESSION SYSTEM REPLACEMEN
- Solicitation number
- 140P8625Q0045
About this file
This document is a Fire Suppression Systems Inspection Certificate for the San Francisco Maritime 38 (1st Floor Fine Arts Room) located at Fort Mason Center in San Francisco, California. The comprehensive inspection report, conducted by Sabah International A Division of Sciens Building on February 25, 2025, details a thorough evaluation of the clean agent fire suppression system.
The inspection covered 17 total devices across multiple categories including auxiliary, container, controls, detecting, initiating, and notification systems. All devices were manufactured by Fenwal and installed between 1989 and 2021, with some components over 25 years old. The system uses a Halon 1301 agent and includes smoke detectors, an abort station, manual pull station, control panel, batteries, relays, horn, and bell. The report indicates all tested components passed inspection, with no failed or problematic items noted. The system's control unit is a Fenwal 2200 model installed in 1989, and the agent tank was last hydrostatically tested on 08/15/2013.
View the file
Other files
Show all 13
On GovTribe
Work with this file
- Download the original file
- Contacts named in this file
- Similar government files
- Ask GovTribe AI about this file
Text version
SAN FRANCISCO MARITIME 38
(1ST FLR FINE ARTS ROOM)
FORT MASON CENTER
1ST FLR FINE ARTS ROOM
SAN FRANCISCO, CA 94123
415-561-7022
Building Contact: Stephen Taylor t. Horton Title: FACILITES
Company: Sabah International A Division of Sciens Building Contact: Suraj Narayan Title: Service Technician
Fire Suppression Systems
INSPECTION
CERTIFICATE
Annual Inspection Feb 25, 2025Inspection Date:
This Inspection was performed in accordance with applicable Standards. The subsequent pages of this report provide performance measurements, listed ranges of acceptable results, and complete documentation of the inspection. Whenever discrepancies exist between acceptable performance standards and actual test results, notes and/or recommended solutions have been proposed or provided for immediate review and approval.
Page of 1 12 Executive Summary
Sabah International A Division of Sciens Building Download Date: 02/27/2025
EXECUTIVE SUMMARY
Generated by: BuildingReports.com
Building Information
SAN FRANCISCO MARITIME 38 (1ST
FLR FINE ARTS ROOM)
FORT MASON CENTER
1ST FLR FINE ARTS ROOM
SAN FRANCISCO, CA 94123
United States of America
Contact: Stephen Taylor t. Horton
Phone: 415-561-7022
Fax:
Mobile:
Email: taylor_horton@nps.gov
Inspection Performed By Sabah International A Division of Sciens Building 5925 Stoneridge Drive Pleasanton, California 94588 United States of America
Inspector: Suraj Narayan
Phone: 925-872-5871
Fax:
Mobile:
Email: snarayan@sciensbuildingsolutions.
com
System Control Unit Manufacturer: Fenwal Discharge Time: Predischarge Delay:
Model Number: 2200 Install Date: 01/04/1989
Software Version: Version Date: 01/04/1989
Location: 1st BLDG E FINE ARTS 102
FACP 22740976
Current Protection: Breaker
Systems Inspected System Type Protected Area Devices
Clean Agent Fine Arts 17
Page of 2 12 Executive Summary
Sabah International A Division of Sciens Building Download Date: 02/27/2025
Building: SAN FRANCISCO MARITIME 38 (1ST
FLR FINE ARTS ROOM)
Contact: Stephen Taylor t. Horton
Signed: Feb 25, 2025
Company: Sabah International A Division of Sciens Building Inspector: Suraj Narayan
Signed: Feb 25, 2025
Inspection Summary
Category
Total Items Serviced Passed Failed/Other
Qty % Qty % Qty % Qty %
Auxiliary 2 11.76% 2 100.00% 2 100.00% 0 0.00%
Container 2 11.76% 2 100.00% 2 100.00% 0 0.00%
Controls 3 17.65% 3 100.00% 3 100.00% 0 0.00%
Detecting 6 35.29% 6 100.00% 6 100.00% 0 0.00%
Initiating 2 11.76% 2 100.00% 2 100.00% 0 0.00%
Notification 2 11.76% 2 100.00% 2 100.00% 0 0.00%
Totals 17 100% 17 100.00% 17 100.00% 0 0.00%
Certification
Page of 3 12 Inspection & Testing
Sabah International A Division of Sciens Building Download Date: 02/27/2025
INSPECTION & TESTING
Generated by: BuildingReports.com
The Inspection & Testing section lists all of the items inspected in your building. Items are grouped by Passed or Failed/Other .
Items are listed by Category. Each item includes the services performed, and the time & date at which testing occurred.
Building: SAN FRANCISCO MARITIME 38 (1ST FLR FINE ARTS ROOM)
Device Type Location Service Time Date
PASSED
Clean Agent Fine Arts
Abort Station 1st BLDG E FINE ARTS 102 ABORT STATION Tested 12:26:59 PM 02/25/2025
Agent Tank 1st BLDG E FINE ARTS 102 HALON TANK Tested 12:31:59 PM 02/25/2025
Battery 1st BLDG E FINE ARTS 102 FACP BATTERY Tested 12:26:17 PM 02/25/2025
Battery 1st BLDG E FINE ARTS 102 FACP BATTERY Tested 12:26:36 PM 02/25/2025
Bell 1st BLDG E FINE ARTS 102 BELL Tested 12:27:52 PM 02/25/2025
Control Panel 1st BLDG E FINE ARTS 102 FACP Tested 12:27:04 PM 02/25/2025
Discharge Device 1st BLDG E FINE ARTS 102 HALON TANK Tested 12:27:56 PM 02/25/2025
Horn 1st BLDG E FINE ARTS 102 HORN Tested 1:27:26 PM 02/25/2025
Manual Station 1st BLDG E FINE ARTS 102 PULL STATION Tested 12:27:27 PM 02/25/2025
Relay 1st BLDG E FINE ARTS 102 ALARM RELAY
TO FACP
Tested 12:27:18 PM 02/25/2025
Relay 1st BLDG E FINE ARTS 102 TROUBLE RELAY
TO FACP
Tested 12:27:08 PM 02/25/2025
Smoke Detector 1st BLDG E FINE ARTS 102 SMOKE Tested 12:27:22 PM 02/25/2025
Smoke Detector 1st BLDG E FINE ARTS 102 SMOKE Tested 12:27:27 PM 02/25/2025
Smoke Detector 1st BLDG E FINE ARTS 102 SMOKE Tested 12:27:33 PM 02/25/2025
Smoke Detector 1st BLDG E FINE ARTS 102 SMOKE Tested 12:27:37 PM 02/25/2025
Smoke Detector 1st BLDG E FINE ARTS 102 SMOKE Tested 12:27:43 PM 02/25/2025
Smoke Detector 1st BLDG E FINE ARTS 102 SMOKE Tested 12:27:47 PM 02/25/2025
Page of 4 12 Auxiliary Functions Testing
Sabah International A Division of Sciens Building Download Date: 02/27/2025
All Protected AreasBuilding: SAN FRANCISCO MARITIME 38 (1ST FLR
FINE ARTS ROOM)
AUXILIARY FUNCTIONS TESTING
Generated by: BuildingReports.com
The Auxiliary Functions Testing section lists each of the ancillary items, systems, and emergency equipment that are controlled by the system control unit. Items are grouped by Passed or Failed/Other. The items are listed by device type, and a check box is provided to indicate if the test conducted was simulated.
Type Location Comment ScanID Simulated
PASSED
Relay
Non-programmable 1st BLDG E FINE ARTS 102 ALARM RELAY TO
FACP
Passed 22740975 ☐
Non-programmable 1st BLDG E FINE ARTS 102 TROUBLE RELAY
TO FACP
Passed 22740974 ☐
Page of 5 12 Notification Report
Sabah International A Division of Sciens Building Download Date: 02/27/2025
NOTIFICATION REPORT
Generated by: BuildingReports.com
Message, signals, signage and communications for occupants of areas protected within this inspection.
Building: SAN FRANCISCO MARITIME 38 (1ST FLR FINE ARTS ROOM)
Device Type Type Location Comment ScanID
CLEAN AGENT FINE ARTS
Horn Alarm 1st BLDG E FINE ARTS 102 HORN Passed 22740981
Bell Alarm 1st BLDG E FINE ARTS 102 BELL Passed 22740989
Page of 6 12 Battery & Power Supply Testing
Sabah International A Division of Sciens Building Download Date: 02/27/2025
All Protected AreasBuilding: SAN FRANCISCO MARITIME 38 (1ST FLR
FINE ARTS ROOM)
BATTERY & POWER SUPPLY TESTING
Generated by: BuildingReports.com
The Battery & Power Supply Testing section details the readings and measurements of batteries and power supplies used to provide power to the fire alarm and life safety systems. Items are grouped by Passed or Failed/Other.
Type Location Rated
Ah Rated Volts Pre Test
Post Test Min Ah
Tested Ah
PASSED
Clean Agent Fine Arts
Battery
Sealed Lead Acid 1st BLDG E FINE ARTS 102 FACP
BATTERY
7.0 12.0 13.0 12.79 4.6 5
Sealed Lead Acid 1st BLDG E FINE ARTS 102 FACP
BATTERY
7.0 12.0 13.0 12.79 4.6 5
Page of 7 12 Agent Container Report
Sabah International A Division of Sciens Building Download Date: 02/27/2025
All Protected AreasBuilding: SAN FRANCISCO MARITIME 38 (1ST FLR
FINE ARTS ROOM)
AGENT CONTAINER REPORT
Generated by: BuildingReports.com
A container of stored agent to be used in case of a fire emergency.
CLEAN AGENT FINE ARTS
Agent Tank
Location Manufacturer Model # Container ScanID
1st BLDG E FINE ARTS 102 HALON
TANK
Fenwal Init. Date Code
Sphere 22740990
Gross Weight Tare Weight Agent Actual Weight Agent Weight Temperature
293.2 103.2 Halon 1301 283.2 190 70
Pressure Lvl. Indicator Liquid Level Release Type Supply Hydro Date Serial #
300 ☐ NA Electrical Primary 08/15/2013 A-41942
Discharge Device
Location Manufacturer Model # Type ScanID
1st BLDG E FINE ARTS 102
HALON TANK
Fenwal Init. Date Code
Squib 37095184
Install Date Initiator Date Replacement Date Compensator Resistance Initiator Resistance
01/01/2007 01/24/2020 12/31/1969 10 Ohm
Page of 8 12 Clean Agent Fire Suppression
Sabah International A Division of Sciens Building Download Date: 02/27/2025
Clean Agent Fine ArtsBuilding: SAN FRANCISCO MARITIME 38 (1ST FLR
FINE ARTS ROOM)
CLEAN AGENT FIRE SUPPRESSION
Generated by: BuildingReports.com
Electrically non-conducting, volatile, or gaseous fire extinguishant that does not leave a residue upon evaporation. The agents were introduced in response to international restrictions on the production of certain halon fire-extinguishing agents under the Montreal Protocol signed September 16, 1987, as amended.
Device Type Location Manufacturer Model Number ScanID
PASSED
Auxiliary
Relay 1st BLDG E FINE ARTS 102 ALARM
RELAY TO FACP
Fenwal 2200 22740975
Relay 1st BLDG E FINE ARTS 102
TROUBLE RELAY TO FACP
Fenwal 2200 22740974
Container
Agent Tank 1st BLDG E FINE ARTS 102 HALON
TANK
Fenwal Init. Date Code 1646 22740990
Discharge Device 1st BLDG E FINE ARTS 102 HALON
TANK
Fenwal Init. Date Code 1646 37095184
Controls
Battery 1st BLDG E FINE ARTS 102 FACP
BATTERY
Power Patrol FAS1075 22740978
Battery 1st BLDG E FINE ARTS 102 FACP
BATTERY
Power Patrol FAS1075 22740977
Control Panel 1st BLDG E FINE ARTS 102 FACP Fenwal 2200 22740976
Detecting
Smoke Detector 1st BLDG E FINE ARTS 102 SMOKE Fenwal 22740984
Smoke Detector 1st BLDG E FINE ARTS 102 SMOKE Fenwal 22740983
Smoke Detector 1st BLDG E FINE ARTS 102 SMOKE Fenwal 22740982
Smoke Detector 1st BLDG E FINE ARTS 102 SMOKE Fenwal 22740988
Page of 9 12 Clean Agent Fire Suppression
Sabah International A Division of Sciens Building Download Date: 02/27/2025
Device Type Location Manufacturer Model Number ScanID
PASSED (continued)
Detecting (continued)
Smoke Detector 1st BLDG E FINE ARTS 102 SMOKE Fenwal 22740987
Smoke Detector 1st BLDG E FINE ARTS 102 SMOKE Fenwal 22740986
Initiating
Abort Station 1st BLDG E FINE ARTS 102 ABORT
STATION
Fenwal 22740979
Manual Station 1st BLDG E FINE ARTS 102 PULL
STATION
Fenwal 22740980
Notification
Bell 1st BLDG E FINE ARTS 102 BELL Fenwal 22740989
Horn 1st BLDG E FINE ARTS 102 HORN Fenwal 22740981
Page of 10 12 Inventory & Warranty Report
Sabah International A Division of Sciens Building Download Date: 02/27/2025
INVENTORY & WARRANTY REPORT
Generated by: BuildingReports.com
The Inventory & Warranty Report lists each of the devices and items that are included in your Inspection Report. A complete inventory count by device type and category is provided. Items installed within the last 90 days, within the last year, and devices installed for two years or more are grouped together for easy reference.
Building: SAN FRANCISCO MARITIME 38 (1ST FLR FINE ARTS ROOM)
Device or Type Category % of Inventory Quantity
Abort Station Initiating 5.88% 1
Agent Tank Container 5.88% 1
Battery Controls 11.76% 2
Bell Notification 5.88% 1
Control Panel Controls 5.88% 1
Discharge Device Container 5.88% 1
Horn Notification 5.88% 1
Manual Station Initiating 5.88% 1
Relay Auxiliary 11.76% 2
Smoke Detector Detecting 35.29% 6
Type Qty Model # Description Install Date
IN SERVICE - 3 YEARS TO 5 YEARS
Clean Agent Fine Arts
Battery 2 FAS1075 Sealed Lead Acid 07/27/2021
IN SERVICE - 15 YEARS TO 25 YEARS
Clean Agent Fine Arts
Agent Tank 1 Init. Date Code 1646 01/01/2007
Discharge Device 1 Init. Date Code 1646 Squib 01/01/2007
IN SERVICE - 25 YEARS OR OLDER
Clean Agent Fine Arts
Page of 11 12 Inventory & Warranty Report
Sabah International A Division of Sciens Building Download Date: 02/27/2025
Type Qty Model # Description Install Date
IN SERVICE - 25 YEARS OR OLDER (continued)
Clean Agent Fine Arts (continued)
Abort Station 1 PUSH/HOLD 01/04/1989
Bell 1 Alarm 01/04/1989
Control Panel 1 2200 01/04/1989
Horn 1 Alarm 01/04/1989
Manual Station 1 Dual Action 01/04/1989
Relay 2 2200 Non-programmable 01/04/1989
Smoke Detector 6 Photoelectric 01/04/1989
Page of 12 12 Zone Address Report
Sabah International A Division of Sciens Building Download Date: 02/27/2025
Control Panel: 1 - Fenwal 2200Building: SAN FRANCISCO MARITIME 38 (1ST FLR
FINE ARTS ROOM)
ZONE ADDRESS REPORT
Generated by: BuildingReports.com
The Zone Address Report lists all of the devices and items that have an individual address, or are grouped together under a common zone. The device type, location, and description are included for your reference.
Address Device Type Location Type ScanID
ZONE/CIRCUIT: 1
Smoke Detector 1st BLDG E FINE ARTS 102 SMOKE Photoelectric 22740982
Smoke Detector 1st BLDG E FINE ARTS 102 SMOKE Photoelectric 22740983
Smoke Detector 1st BLDG E FINE ARTS 102 SMOKE Photoelectric 22740984
ZONE/CIRCUIT: 2
Smoke Detector 1st BLDG E FINE ARTS 102 SMOKE Photoelectric 22740986
Smoke Detector 1st BLDG E FINE ARTS 102 SMOKE Photoelectric 22740987
Smoke Detector 1st BLDG E FINE ARTS 102 SMOKE Photoelectric 22740988
| Cover Page |
| Executive Summary |
| Inspection & Testing |
| Auxiliary Functions Testing |
| Notification Report |
| Battery & Power Supply Testing |
| Agent Container Report |
| Clean Agent Fire Suppression |
| Inventory & Warranty Report |
| Zone Address Report |