Section_J_-_Att_No__008_2025-02-25_SAN-FRANCISCO-MARITIME-38--1ST-F_SuppressionScan_0004.pdf

PDF 743 KB Posted

Attached to
HALON FIRE SUPPRESSION SYSTEM REPLACEMEN
Solicitation number
140P8625Q0045
Issued by

About this file

This document is a Fire Suppression Systems Inspection Certificate for the San Francisco Maritime 38 (1st Floor Fine Arts Room) located at Fort Mason Center in San Francisco, California. The comprehensive inspection report, conducted by Sabah International A Division of Sciens Building on February 25, 2025, details a thorough evaluation of the clean agent fire suppression system.

The inspection covered 17 total devices across multiple categories including auxiliary, container, controls, detecting, initiating, and notification systems. All devices were manufactured by Fenwal and installed between 1989 and 2021, with some components over 25 years old. The system uses a Halon 1301 agent and includes smoke detectors, an abort station, manual pull station, control panel, batteries, relays, horn, and bell. The report indicates all tested components passed inspection, with no failed or problematic items noted. The system's control unit is a Fenwal 2200 model installed in 1989, and the agent tank was last hydrostatically tested on 08/15/2013.

View the file

Other files

Show all 13

On GovTribe

Work with this file

  • Download the original file
  • Contacts named in this file
  • Similar government files
  • Ask GovTribe AI about this file

Text version

SAN FRANCISCO MARITIME 38

(1ST FLR FINE ARTS ROOM)

FORT MASON CENTER

1ST FLR FINE ARTS ROOM

SAN FRANCISCO, CA 94123

415-561-7022

Building Contact: Stephen Taylor t. Horton Title: FACILITES

Company: Sabah International A Division of Sciens Building Contact: Suraj Narayan Title: Service Technician

Fire Suppression Systems

INSPECTION

CERTIFICATE

Annual Inspection Feb 25, 2025Inspection Date:

This Inspection was performed in accordance with applicable Standards. The subsequent pages of this report provide performance measurements, listed ranges of acceptable results, and complete documentation of the inspection. Whenever discrepancies exist between acceptable performance standards and actual test results, notes and/or recommended solutions have been proposed or provided for immediate review and approval.

Page of 1 12 Executive Summary

Sabah International A Division of Sciens Building Download Date: 02/27/2025

EXECUTIVE SUMMARY

Generated by: BuildingReports.com

Building Information

SAN FRANCISCO MARITIME 38 (1ST

FLR FINE ARTS ROOM)

FORT MASON CENTER

1ST FLR FINE ARTS ROOM

SAN FRANCISCO, CA 94123

United States of America

Contact: Stephen Taylor t. Horton

Phone: 415-561-7022

Fax:

Mobile:

Email: taylor_horton@nps.gov

Inspection Performed By Sabah International A Division of Sciens Building 5925 Stoneridge Drive Pleasanton, California 94588 United States of America

Inspector: Suraj Narayan

Phone: 925-872-5871

Fax:

Mobile:

Email: snarayan@sciensbuildingsolutions.

com

System Control Unit Manufacturer: Fenwal Discharge Time: Predischarge Delay:

Model Number: 2200 Install Date: 01/04/1989

Software Version: Version Date: 01/04/1989

Location: 1st BLDG E FINE ARTS 102

FACP 22740976

Current Protection: Breaker

Systems Inspected System Type Protected Area Devices

Clean Agent Fine Arts 17

Page of 2 12 Executive Summary

Sabah International A Division of Sciens Building Download Date: 02/27/2025

Building: SAN FRANCISCO MARITIME 38 (1ST

FLR FINE ARTS ROOM)

Contact: Stephen Taylor t. Horton

Signed: Feb 25, 2025

Company: Sabah International A Division of Sciens Building Inspector: Suraj Narayan

Signed: Feb 25, 2025

Inspection Summary

Category

Total Items Serviced Passed Failed/Other

Qty % Qty % Qty % Qty %

Auxiliary 2 11.76% 2 100.00% 2 100.00% 0 0.00%

Container 2 11.76% 2 100.00% 2 100.00% 0 0.00%

Controls 3 17.65% 3 100.00% 3 100.00% 0 0.00%

Detecting 6 35.29% 6 100.00% 6 100.00% 0 0.00%

Initiating 2 11.76% 2 100.00% 2 100.00% 0 0.00%

Notification 2 11.76% 2 100.00% 2 100.00% 0 0.00%

Totals 17 100% 17 100.00% 17 100.00% 0 0.00%

Certification

Page of 3 12 Inspection & Testing

Sabah International A Division of Sciens Building Download Date: 02/27/2025

INSPECTION & TESTING

Generated by: BuildingReports.com

The Inspection & Testing section lists all of the items inspected in your building. Items are grouped by Passed or Failed/Other .

Items are listed by Category. Each item includes the services performed, and the time & date at which testing occurred.

Building: SAN FRANCISCO MARITIME 38 (1ST FLR FINE ARTS ROOM)

Device Type Location Service Time Date

PASSED

Clean Agent Fine Arts

Abort Station 1st BLDG E FINE ARTS 102 ABORT STATION Tested 12:26:59 PM 02/25/2025

Agent Tank 1st BLDG E FINE ARTS 102 HALON TANK Tested 12:31:59 PM 02/25/2025

Battery 1st BLDG E FINE ARTS 102 FACP BATTERY Tested 12:26:17 PM 02/25/2025

Battery 1st BLDG E FINE ARTS 102 FACP BATTERY Tested 12:26:36 PM 02/25/2025

Bell 1st BLDG E FINE ARTS 102 BELL Tested 12:27:52 PM 02/25/2025

Control Panel 1st BLDG E FINE ARTS 102 FACP Tested 12:27:04 PM 02/25/2025

Discharge Device 1st BLDG E FINE ARTS 102 HALON TANK Tested 12:27:56 PM 02/25/2025

Horn 1st BLDG E FINE ARTS 102 HORN Tested 1:27:26 PM 02/25/2025

Manual Station 1st BLDG E FINE ARTS 102 PULL STATION Tested 12:27:27 PM 02/25/2025

Relay 1st BLDG E FINE ARTS 102 ALARM RELAY

TO FACP

Tested 12:27:18 PM 02/25/2025

Relay 1st BLDG E FINE ARTS 102 TROUBLE RELAY

TO FACP

Tested 12:27:08 PM 02/25/2025

Smoke Detector 1st BLDG E FINE ARTS 102 SMOKE Tested 12:27:22 PM 02/25/2025

Smoke Detector 1st BLDG E FINE ARTS 102 SMOKE Tested 12:27:27 PM 02/25/2025

Smoke Detector 1st BLDG E FINE ARTS 102 SMOKE Tested 12:27:33 PM 02/25/2025

Smoke Detector 1st BLDG E FINE ARTS 102 SMOKE Tested 12:27:37 PM 02/25/2025

Smoke Detector 1st BLDG E FINE ARTS 102 SMOKE Tested 12:27:43 PM 02/25/2025

Smoke Detector 1st BLDG E FINE ARTS 102 SMOKE Tested 12:27:47 PM 02/25/2025

Page of 4 12 Auxiliary Functions Testing

Sabah International A Division of Sciens Building Download Date: 02/27/2025

All Protected AreasBuilding: SAN FRANCISCO MARITIME 38 (1ST FLR

FINE ARTS ROOM)

AUXILIARY FUNCTIONS TESTING

Generated by: BuildingReports.com

The Auxiliary Functions Testing section lists each of the ancillary items, systems, and emergency equipment that are controlled by the system control unit. Items are grouped by Passed or Failed/Other. The items are listed by device type, and a check box is provided to indicate if the test conducted was simulated.

Type Location Comment ScanID Simulated

PASSED

Relay

Non-programmable 1st BLDG E FINE ARTS 102 ALARM RELAY TO

FACP

Passed 22740975 ☐

Non-programmable 1st BLDG E FINE ARTS 102 TROUBLE RELAY

TO FACP

Passed 22740974 ☐

Page of 5 12 Notification Report

Sabah International A Division of Sciens Building Download Date: 02/27/2025

NOTIFICATION REPORT

Generated by: BuildingReports.com

Message, signals, signage and communications for occupants of areas protected within this inspection.

Building: SAN FRANCISCO MARITIME 38 (1ST FLR FINE ARTS ROOM)

Device Type Type Location Comment ScanID

CLEAN AGENT FINE ARTS

Horn Alarm 1st BLDG E FINE ARTS 102 HORN Passed 22740981

Bell Alarm 1st BLDG E FINE ARTS 102 BELL Passed 22740989

Page of 6 12 Battery & Power Supply Testing

Sabah International A Division of Sciens Building Download Date: 02/27/2025

All Protected AreasBuilding: SAN FRANCISCO MARITIME 38 (1ST FLR

FINE ARTS ROOM)

BATTERY & POWER SUPPLY TESTING

Generated by: BuildingReports.com

The Battery & Power Supply Testing section details the readings and measurements of batteries and power supplies used to provide power to the fire alarm and life safety systems. Items are grouped by Passed or Failed/Other.

Type Location Rated

Ah Rated Volts Pre Test

Post Test Min Ah

Tested Ah

PASSED

Clean Agent Fine Arts

Battery

Sealed Lead Acid 1st BLDG E FINE ARTS 102 FACP

BATTERY

7.0 12.0 13.0 12.79 4.6 5

Sealed Lead Acid 1st BLDG E FINE ARTS 102 FACP

BATTERY

7.0 12.0 13.0 12.79 4.6 5

Page of 7 12 Agent Container Report

Sabah International A Division of Sciens Building Download Date: 02/27/2025

All Protected AreasBuilding: SAN FRANCISCO MARITIME 38 (1ST FLR

FINE ARTS ROOM)

AGENT CONTAINER REPORT

Generated by: BuildingReports.com

A container of stored agent to be used in case of a fire emergency.

CLEAN AGENT FINE ARTS

Agent Tank

Location Manufacturer Model # Container ScanID

1st BLDG E FINE ARTS 102 HALON

TANK

Fenwal Init. Date Code

Sphere 22740990

Gross Weight Tare Weight Agent Actual Weight Agent Weight Temperature

293.2 103.2 Halon 1301 283.2 190 70

Pressure Lvl. Indicator Liquid Level Release Type Supply Hydro Date Serial #

300 ☐ NA Electrical Primary 08/15/2013 A-41942

Discharge Device

Location Manufacturer Model # Type ScanID

1st BLDG E FINE ARTS 102

HALON TANK

Fenwal Init. Date Code

Squib 37095184

Install Date Initiator Date Replacement Date Compensator Resistance Initiator Resistance

01/01/2007 01/24/2020 12/31/1969 10 Ohm

Page of 8 12 Clean Agent Fire Suppression

Sabah International A Division of Sciens Building Download Date: 02/27/2025

Clean Agent Fine ArtsBuilding: SAN FRANCISCO MARITIME 38 (1ST FLR

FINE ARTS ROOM)

CLEAN AGENT FIRE SUPPRESSION

Generated by: BuildingReports.com

Electrically non-conducting, volatile, or gaseous fire extinguishant that does not leave a residue upon evaporation. The agents were introduced in response to international restrictions on the production of certain halon fire-extinguishing agents under the Montreal Protocol signed September 16, 1987, as amended.

Device Type Location Manufacturer Model Number ScanID

PASSED

Auxiliary

Relay 1st BLDG E FINE ARTS 102 ALARM

RELAY TO FACP

Fenwal 2200 22740975

Relay 1st BLDG E FINE ARTS 102

TROUBLE RELAY TO FACP

Fenwal 2200 22740974

Container

Agent Tank 1st BLDG E FINE ARTS 102 HALON

TANK

Fenwal Init. Date Code 1646 22740990

Discharge Device 1st BLDG E FINE ARTS 102 HALON

TANK

Fenwal Init. Date Code 1646 37095184

Controls

Battery 1st BLDG E FINE ARTS 102 FACP

BATTERY

Power Patrol FAS1075 22740978

Battery 1st BLDG E FINE ARTS 102 FACP

BATTERY

Power Patrol FAS1075 22740977

Control Panel 1st BLDG E FINE ARTS 102 FACP Fenwal 2200 22740976

Detecting

Smoke Detector 1st BLDG E FINE ARTS 102 SMOKE Fenwal 22740984

Smoke Detector 1st BLDG E FINE ARTS 102 SMOKE Fenwal 22740983

Smoke Detector 1st BLDG E FINE ARTS 102 SMOKE Fenwal 22740982

Smoke Detector 1st BLDG E FINE ARTS 102 SMOKE Fenwal 22740988

Page of 9 12 Clean Agent Fire Suppression

Sabah International A Division of Sciens Building Download Date: 02/27/2025

Device Type Location Manufacturer Model Number ScanID

PASSED (continued)

Detecting (continued)

Smoke Detector 1st BLDG E FINE ARTS 102 SMOKE Fenwal 22740987

Smoke Detector 1st BLDG E FINE ARTS 102 SMOKE Fenwal 22740986

Initiating

Abort Station 1st BLDG E FINE ARTS 102 ABORT

STATION

Fenwal 22740979

Manual Station 1st BLDG E FINE ARTS 102 PULL

STATION

Fenwal 22740980

Notification

Bell 1st BLDG E FINE ARTS 102 BELL Fenwal 22740989

Horn 1st BLDG E FINE ARTS 102 HORN Fenwal 22740981

Page of 10 12 Inventory & Warranty Report

Sabah International A Division of Sciens Building Download Date: 02/27/2025

INVENTORY & WARRANTY REPORT

Generated by: BuildingReports.com

The Inventory & Warranty Report lists each of the devices and items that are included in your Inspection Report. A complete inventory count by device type and category is provided. Items installed within the last 90 days, within the last year, and devices installed for two years or more are grouped together for easy reference.

Building: SAN FRANCISCO MARITIME 38 (1ST FLR FINE ARTS ROOM)

Device or Type Category % of Inventory Quantity

Abort Station Initiating 5.88% 1

Agent Tank Container 5.88% 1

Battery Controls 11.76% 2

Bell Notification 5.88% 1

Control Panel Controls 5.88% 1

Discharge Device Container 5.88% 1

Horn Notification 5.88% 1

Manual Station Initiating 5.88% 1

Relay Auxiliary 11.76% 2

Smoke Detector Detecting 35.29% 6

Type Qty Model # Description Install Date

IN SERVICE - 3 YEARS TO 5 YEARS

Clean Agent Fine Arts

Battery 2 FAS1075 Sealed Lead Acid 07/27/2021

IN SERVICE - 15 YEARS TO 25 YEARS

Clean Agent Fine Arts

Agent Tank 1 Init. Date Code 1646 01/01/2007

Discharge Device 1 Init. Date Code 1646 Squib 01/01/2007

IN SERVICE - 25 YEARS OR OLDER

Clean Agent Fine Arts

Page of 11 12 Inventory & Warranty Report

Sabah International A Division of Sciens Building Download Date: 02/27/2025

Type Qty Model # Description Install Date

IN SERVICE - 25 YEARS OR OLDER (continued)

Clean Agent Fine Arts (continued)

Abort Station 1 PUSH/HOLD 01/04/1989

Bell 1 Alarm 01/04/1989

Control Panel 1 2200 01/04/1989

Horn 1 Alarm 01/04/1989

Manual Station 1 Dual Action 01/04/1989

Relay 2 2200 Non-programmable 01/04/1989

Smoke Detector 6 Photoelectric 01/04/1989

Page of 12 12 Zone Address Report

Sabah International A Division of Sciens Building Download Date: 02/27/2025

Control Panel: 1 - Fenwal 2200Building: SAN FRANCISCO MARITIME 38 (1ST FLR

FINE ARTS ROOM)

ZONE ADDRESS REPORT

Generated by: BuildingReports.com

The Zone Address Report lists all of the devices and items that have an individual address, or are grouped together under a common zone. The device type, location, and description are included for your reference.

Address Device Type Location Type ScanID

ZONE/CIRCUIT: 1

Smoke Detector 1st BLDG E FINE ARTS 102 SMOKE Photoelectric 22740982

Smoke Detector 1st BLDG E FINE ARTS 102 SMOKE Photoelectric 22740983

Smoke Detector 1st BLDG E FINE ARTS 102 SMOKE Photoelectric 22740984

ZONE/CIRCUIT: 2

Smoke Detector 1st BLDG E FINE ARTS 102 SMOKE Photoelectric 22740986

Smoke Detector 1st BLDG E FINE ARTS 102 SMOKE Photoelectric 22740987

Smoke Detector 1st BLDG E FINE ARTS 102 SMOKE Photoelectric 22740988

Cover Page
Executive Summary
Inspection & Testing
Auxiliary Functions Testing
Notification Report
Battery & Power Supply Testing
Agent Container Report
Clean Agent Fire Suppression
Inventory & Warranty Report
Zone Address Report