This document provides details on a federal solicitation for construction services. The solicitation number is 140P8420R0004 and seeks to replace the operations building at the Brandy Creek Wastewater Treatment Plant in Whiskeytown National Recreation Area, Shasta County, California. The attached file contains construction drawings related to the project. The solicitation was issued by the Department of the Interior National Park Service Pacific West Region to replace the existing operations building. The response due date, award date, pricing terms, and other contract details are not provided in this document.
View the file
Other files
Show all 19
On GovTribe
Work with this file
- Download the original file
- Contacts named in this file
- Similar government files
- Ask GovTribe AI about this file
Text version
S
ELECTRICAL ABBREVIATIONS
NOTE: THIS IS A SUPPLEMENTAL STANDARD LEGEND. SOME SYMBOLS OR
ABBREVIATIONS MAY APPEAR ON THIS LEGEND AND NOT ON THE PLANS
CONDUIT EXPOSED
CONDUIT CONCEALED or BURIED
HOME RUN-DESTINATION SHOWN
CONDUIT DOWN
CONDUIT UP
CONNECTION POINT (CONTRACTOR SHALL DETERMINE CONNECTION CONFIGURATION)
MAJOR ELECTRICAL COMPONENT OR DEVICE NAME OR
IDENTIFYING SYMBOL AS SHOWN
EXOTHERMIC WELD, TERMINATION OR SPLICE POINT
GROUND ROD
CIRCUIT BREAKER
CURRENT TRANSFORMER, NUMBER INDICATED
ELECTRICAL SYMBOLS
LA-2
MCC
TICK MARKS WITHOUT BARS INDICATES NUMBER OF #12 CONDUCTORS WITH #12 GROUND
DUPLEX RECEPTACLE
SURFACE MOUNT PANELBOARD
RECESS MOUNT PANELBOARD
JUNCTION BOXJ
DEVICE BOXES SHALL BE 18" COD
UNLESS OTHERWISE NOTED
KEYNOTE1
A - AMMETER, AMPERE
AC - ALTERNATING CURRENT
AFF - ABOVE FINISHED FLOOR OR GRADE
AIC - AMPS INTERRUPTING CAPACITY
ATS - AUTOMATIC TRANSFER SWITCH
BGES - BUILDING GROUND ELECTRODE SYSTEM
BRKR - BREAKER
BOD - BOTTOM OF DEVICE
C or COND - CONDUIT
CEC - CALIFORNIA ELECTRIC CODE
CKT - CIRCUIT
COD - CENTER OF DEVICE
CT - CURRENT TRANSFORMER
DC - DIRECT CURRENT
(E) or EXIST - EXISTING
EEOR - ELECTRICAL ENGINEER OF RECORD
EGC - EQUIPMENT GROUNDING CONDUCTOR
ENC - ENCLOSURE
G - EQUIPMENT GROUNDING CONDUCTOR
GEC - GROUNDING ELECTRODE CONDUCTOR
GFCI - GROUND FAULT CIRCUIT INTERRUPT
J - JUNCTION BOX
LAUN - LAUNDRY
LTG - LIGHTING
MBJ - MAIN BONDING JUMPER
MCB - MAIN CIRCUIT BREAKER
MFR - MANUFACTURER
MLO - MAIN LUG ONLY
MOCP - MAXIMUM OVERCURRENT PROTECTION
MSB - MAIN SWITCH BOARD
NEC - NATIONAL ELECTRIC CODE
NEMA - NATIONAL ELECTRIC MANUFACTURER'S ASSOCIATION
N - NEUTRAL
(N) - NEW
OFCI - OWNER FURNISHED, CONTRACTOR INSTALLED
OFOI - OWNER FURNISHED, OWNER INSTALLED
PB - PULLBOX
PNL - PANELBOARD
RCPT - RECEPTACLE
RM - ROOM
SWBD - SWITCHBOARD
SBJ - SYSTEM BONDING JUMPER
SSBJ - SUPPLY SIDE BONDING JUMPER
TOD - TOP OF DEVICE
TR - TAMPER
TYP - TYPICAL
V - VOLTMETER, VOLT
W - WATT
WW - WIREWAY
WP - WEATHERPROOF (NEMA 3R)
XFMR - TRANSFORMER
NOTE: THIS IS A SUPPLEMENTAL STANDARD ELECTRICAL LEGEND. SOME SYMBOLS MAY APPEAR ON THIS LEGEND AND NOT ON THE
PLANS. SEE LIGHTING CONTROL SHEET FOR LIGHTING LEGEND.
LI
N
E T
Y P
E S
A N
D S
Y M
B O
LS
E Q
U
IP
M E N
T
(A : B) INDICATES INTERCONNECTION OF PATHWAYS AND/OR CONDUCTORS, E.G., 4"C-4#500,1#3G (MSB : PNL A) INDICATES CONDUIT AND CONDUCTORS ROUTED FROM THE MAIN SWITCHBOARD TO PANELBOARD A.
INDICATES FIRE RATED WALL
200A, 120/240V, 3Ø, 4W , 22kAIC
M UTILITY
METER
200A 3P
(E)
UTILITY XFMR
(E) SERVICE PEDESTAL
(E)
OFFICE
LAB
(N) 2"C-4#3/0,1#6G G
(N) GENERATOR
80kW, 3Ø
200A 3P
(E) 30A
2P
(E) 70A
3P
(E) 70A
2P
(E) 30A
2P
(N) ATS
200A/3P
(N) 2"C-4#3/0,1#6G
*IT IS ASSUMED THAT PHASE B IS HIGH LEG. IF ACTUAL
CONDITIONS DIFFER FROM WHAT IS SHOWN ON THE
DRAWINGS, NOTIFY THE EEOR IMMEDIATELY.
(E)
SPAYFIELD
PUMPS
(E) R & A
PUMP
(E)
PROCESS
CONTROL
(N) 20A
1P
(N) 20A
1P
(N)
GEN.
BLOCK
HEATER
(N) GEN.
BATTERY
CHARGER/
CONTROL
PANEL
"C
-2
,1
G
"C
-2
,1
G
1 1
(A) (C)
GND BUS
1"C-#/4 BARE CU
CONDUCTOR
GND BUS
(E) GND ROD
(N) 2"C-4#3/0,1#6G
AREA OF WORK
RE
G
IS
TE
RE
D
PROFESSIONAL
ENG
IN
EE
R
ST AT E O F C A L I F O R N IA
No. E 22477
EL ECT R I CAL
C A L V I N A.
EI
HSBA
R
SUB SHEET NO.DESIGNED:
TECH. REVIEW:
DATE:
SHEET
PMIS/PKG NO.
DRAWING NO.
OF
TITLE OF SHEET
148519
PACE
ENGINEERING
REDDING, CA.
253759
C R e v it L o c a l F ile s \2
.0
W h is k e y to w n
N P
S G e n e ra to r A d d it io n B
W R
IG
H
T
R
.r v t
/2
/2
:4
:3
P
M
GENERATOR - ONE-LINE
DIAGRAM
E01 5/29/20
KC
CA
CA
WHISKEYTOWN-SHASTA-TRINITY N.R.A.
BRANDY CREEK WASTEWATER TREATMENT PLANT
1. PROVIDE AND INSTALL NEW BREAKER IN EXISTING SPACE. NEW BREAKER SHALL BE OF SAME
TYPE AND RATING AS EXISTING. UPDATE CIRCUIT DIRECTORY ACCORDINGLY.
2. BREAK CONNECTION FROM LOAD SIDE OF BREAKER TO BUS. PROVIDE LUGS ON LOAD SIDE
AND PROVIDE AND INSTALL CONDUCTOR CONNECTIONS AS SHOWN.
3. CONNECT NEW GENERATOR GROUND BUS TO EXISTING GROUND ELECTRODE.
KEYNOTES
NOTE
1. DO ALL WORK AND INSTALL PRODUCTS IN ACCORDANCE APPLICABLE NECA
REQUIREMENTS, APPLICABLE STATE LAWS, LOCAL LAWS, CODES AND ORDINANCES. THE
CONTRACTOR SHALL ADHERE TO THE SPECIFIC PRODUCT AND INSTALLATION
REQUIREMENTS OF THE UTILITY COMPANIES AND MANUFACTURER'S PROVIDING MATERIALS
TO THE JOB. CONFLICTS, IF ANY, WILL BE RESOLVED AT THE DISCRETION OF THE EEOR.
2. IT IS OF THE UTMOST IMPORTANCE THAT THE INSTALLING CONTRACTOR HAVE A MASTERY OF
THE PROJECT-SPECIFIC REQUIREMENTS SHOWN IN SPECIFICATIONS AND CONSTRUCTION
DRAWINGS. IT IS STRONGLY ADVISED THAT THE CONTRACTOR CONTACT THE EEOR FOR
CLARIFICATION OR RFI THE EEOR IF FURTHER INFORMATION IS REQUIRED. THE EEOR SHALL
REQUIRE REVISIONS TO BE MADE IN THE FIELD IF THE INSTALLATION DOES NOT FALL WITHIN
THESE PROJECT-SPECIFIC GUIDELINES. NO ALLOWANCE SHALL BE MADE FOR
INSTALLATIONS NOT ADHERING TO THESE REQUIREMENTS.
GENERAL NOTES
# NOTE
E013/16" = 1'-0"
2ONE-LINE DIAGRAM
E011" = 50'-0"
1ELECTRICAL SITE PLAN
(N) 80kW GENERATOR
(E) SERVICE PEDESTAL
(N) BOLLARD, TYP. SEE
MECHANICAL SHEET
P02 FOR DETAILS
36" M
IN
(N) 1000
GALLON
LPG TANK
(N) 1000
GALLON
LPG TANK
" M
IN
(N) 200A ATS
E02
E02
GEN. BATTERY CHARGER/CONTROL PANEL
GEN. BLOCK HEATER
11'-0" x 16'-0"
CONCRETE PAD
M
IN
T
Y P
1"C-10#14 (GEN START, GEN FAIL, GEN RUN, SPARES)
S01
S01
FINISH GRADE
D
2"MIN2"MIN
WARNING
TAPE
COMPACTED
TRENCH
BACKFILL
12"
BACKFILL W/ SAND
HAND TAMP
D=3" MIN FOR 2" AND LARGER CONDUIT
D=2" MIN FOR 1 1/2" AND SMALLER CONDUIT
M
IN
M
IN
M
IN
2" GALVANIZED PIPE CAP, TYP.
1-5/8" X 1 5/8" DEEP GALVANIZED STRUT CHANNEL, 12
GAUGE SLOTTED, B-LINE B225H OR APPROVED EQUAL
2" DIA X 10' SCHEDULE 40 GALVANIZED STEEL PIPE (ASTM A53 GR.B)
CONCRETE
FOOTING
CONDUIT
AS SHOWN
FINISHED GRADE
1 5/8" x 13/16 GALVANIZED STRUT CHANNEL SPRING NUT WITH 1/2" x 1" GALVANIZED BOLT, TYP. (B-LINE
B525H OR EQUAL)
2" GALVANIZED PIPE CLAMP, B-LINE
B2400-2 OR APPROVED EQUAL
VERTICAL STRUT ATTACHED
TO HORIZONTAL, TYP.
3'-9"
4'-3"
12"
DIA
5'-0" MAXIMUM
2'-0" MIN.
SEE STRUCTURAL
SHEET S01
CONCRETE PAD
3/4" CHAMFERED EDGE, TYP.
PLACE BEARING PADS BETWEEN FUEL TANK AND
CONCRETE PAD PER GENSET MANUFACTURER
GENERATOR
SOUND ENCLOSURE
FINISHED GRADE
CLR, TYP.
3"
CLR, TYP.
6"
EARTH
FINISHED GRADE
CONDUIT ENTRY AREA FOR
LOAD LEADS (BOTTOM ENTRY)
BLOCK HEATER, BATTERY HEATER AND
ENGINE START CONDUIT ENTRY
FUEL INLET LOCATION
8' - 8"
6' - 11"
3' - 7"
3' - 9 5/16"
/1
C
LR2
GENERATOR FRAME FLOOR PLAN - CONDUIT ENTRY
ELEVATION - FRONT
GENERATOR
80kW
3123 LBS MAX
140"
/1
CONCRETE PAD, SEE STRUCTURAL
SHEET S01
RE
G
IS
TE
RE
D
PROFESSIONAL
ENG
IN
EE
R
ST AT E O F C A L I F O R N IA
No. E 22477
EL ECT R I CAL
C A L V I N A.
EI
HSBA
R
SUB SHEET NO.DESIGNED:
TECH. REVIEW:
DATE:
SHEET
PMIS/PKG NO.
DRAWING NO.
OF
TITLE OF SHEET
148519
PACE
ENGINEERING
REDDING, CA.
253759
C R e v it L o c a l F ile s \2
.0
W h is k e y to w n
N P
S G e n e ra to r A d d it io n B
W R
IG
H
T
R
.r v t
/2
/2
:4
:3
P
M
GENERATOR -
ELECTRICAL SITE PLAN
E02 5/29/20
KC
CA
CA
WHISKEYTOWN-SHASTA-TRINITY N.R.A.
BRANDY CREEK WASTEWATER TREATMENT PLANT
1. SEE ONE-LINE DIAGRAM FOR CONDUIT/CONDUCTOR INFORMATION.
KEYNOTES
NOTE#
E021/4" = 1'-0"
4POWER PLAN
NTS E02
1UNDERGROUND CONDUIT
NTS E02
2ATS 200A NEMA 3R - TRANSFER SWITCH MOUNTING DETAIL TO UNISTRUT
NTS E02
3GENERATOR FOUNDATION DETAIL
AREA OF WORK
SEE SHEET P03
PLUMBING ABBREVIATIONS
ø - DIAMETER/ROUND
(ABV) - ABOVE
APPRX - APPROXIMATE
BTU - BRITISH THERMAL UNIT
BTUH - BRITISH THERMAL UNIT PER HOUR
BTWN - BETWEEN
BV - BALL VALVE
(D) - DROP
DEMO - DEMOLISH
(E) - EXISTING
FC - FLEXIBLE CONNECTION
FG - FINISH GRADE
GPH - GALLONS PER HOUR
GPM - GALLONS PER MINUTE
HZ - HERTZ
IAW - IN ACCORDANCE WITH
KW - KILOWATT
LBS - POUNDS
LPG - LIQUEFIED PETROLEUM GAS
(N) - NEW
NC - NORMALLY CLOSED
NO - NORMALLY OPEN
PH - PHASE
POC - POINT OF CONNECTION
QTY - QUANTITY
RV - RELIEF VALVE
SOV - SHUTOFF VALVE
TYP - TYPICAL
(UG) - UNDER GROUND
UNO - UNLESS OTHERWISE NOTED
(US) - UNDER SLAB
V - VOLTS, VENT
WP - WORKING PRESSURE
NOTE: THIS IS A SUPPLEMENTAL STANDARD PLUMBING LEGEND. SOME SYMBOLS OR ABBREVIATIONS MAY
APPEAR ON THIS LEGEND AND NOT ON THE PLANS.
STRAINER
FLEXIBLE CONNECTOR
LIQUEFIED PETROLEUM GAS
NOTE: THIS IS A SUPPLEMENTAL STANDARD PLUMBING LEGEND. SOME
SYMBOLS MAY APPEAR ON THIS LEGEND AND NOT ON THE PLANS.
PLUMBING SYMBOLS
E Q
U
IP
M E N
T P
IP
IN
G
POINT OF CONNECTION
SY
M
B O
LS
KEY NOTE1
VALVE
SUB SHEET NO.DESIGNED:
TECH. REVIEW:
DATE:
SHEET
PMIS/PKG NO.
DRAWING NO.
OF
TITLE OF SHEET
148519
PACE
ENGINEERING
REDDING, CA
253759
C R e v it L o c a l F ile s \2
.0
W h is k e y to w n N
P S
G e n e ra to r
A d d it io n M
E C
H R a m ill e r.
rv t
/2
/2
:1 :1
P
M
GENERATOR -
PLUMBING SITE
PLANP01
5/29/20
BW
AM
AM
WHISKEYTOWN-SHASTA-TRINITY N.R.A.
BRANDY CREEK WASTEWATER TREATMENT PLANT
1. PRODUCTS, PROCEDURES, AND INSTALLATION SHALL BE IN ACCORDANCE WITH
APPLICABLE NFPA REQUIREMENTS, APPLICABLE STATE LAWS, LOCAL LAWS, CODES AND
ORDINANCES. THE CONTRACTOR SHALL ADHERE TO THE SPECIFIC PRODUCT AND
INSTALLATION REQUIREMENTS OF THE UTILITY COMPANIES AND MANUFACTURER'S
PROVIDING MATERIALS TO THE JOB. CONFLICTS, IF ANY, WILL BE RESOLVED AT THE
DISCRETION OF THE EOR (ENGINEER OF RECORD).
2. IT IS OF THE UTMOST IMPORTANCE THAT THE INSTALLING CONTRACTOR HAVE A MASTERY
OF THE PROJECT-SPECIFIC REQUIREMENTS SHOWN IN SPECIFICATIONS AND
CONSTRUCTION DRAWINGS. IT IS STRONGLY ADVISED THAT THE CONTRACTOR CONTACT
THE EOR FOR CLARIFICATION OR RFI THE EOR IF FURTHER INFORMATION IS REQUIRED. THE
EOR SHALL REQUIRE REVISIONS TO BE MADE IN THE FIELD IF THE INSTALLATION DOES NOT
FALL WITHIN THESE PROJECT-SPECIFIC GUIDELINES. NO ALLOWANCE SHALL BE MADE FOR
INSTALLATIONS NOT ADHERING TO THESE REQUIREMENTS.
GENERAL NOTES
# NOTE
P011" = 50'-0"
1OVERALL PLUMBING SITE PLAN
(N) GENERATOR
(E) SERVICE PEDESTAL
P02
,TYP. OF 7(N) BOLLARD
(N) 1000
GALLON
LPG TANK
2" LPG (UG)
3 3
P02
P02
CONCRETE PAD PER
STRUCTURAL DRAWINGS
P02
,TYP. OF 6(N) BOLLARD
(N) 1000
GALLON
LPG TANK
48"
2" LPG
DROP (UG)
WHERE FEASIBLE
COORDINATE GAS LINE AND GENERATOR INSTALLATION.
CONNECT GAS LINE TO GENERATOR.
36" MIN
PROVIDE EMERGENCY SHUTOFF VALVE
IN ACCESSIBLE LOCATION
(N) ATS
1000 GALLON LP GAS STORAGE TANK FURNISHED WITH
REGULATOR & TANK LEVEL GAUGE. PAINT TANK WITH
ZINC PRIMER & ENAMEL FINISH. TANK TO MEET ALL
CURRENTLY APPLICABLE CODES & REGULATIONS.
SHUT-OFF VALVE
FLEXIBLE CONNECTOR
REGULATOR
SCH 40 POLYETHYLENE COATED BLACK STEEL,
SIZE PER PLAN
NOTE: CONTRACTOR SHALL PROVIDE ALL NECESSARY
PIPE, FITTINGS, OR OTHER TO PROVIDE FOR COMPLETE
INSTALLATION. SEE CURRENT NFPA 58 AND CPC.
"Y" STRAINER
"MEEDER" OR EQUAL
HEADER FOR (2) TANKS
SHUT-OFF VALVE
POLYETHYLENE PIPE DESIGNED FOR THE PURPOSE,
SIZE PER PLAN
GROUND LEVEL
SAND BACKFILL
MIN 4" THICK
SEE NOTE 4
NATIVE BACKFILL
(N) PIPE
SAND BEDDING
MIN 2" THICK
SEE NOTE 4
UNDISTURBED EARTH
(E) PIPE OR CONDUIT, VERIFY
STRUCTURAL INTEGRITY
(E) BACKFILL TO REMAIN
TOP OF GRADE,
PAVING OR SLAB
NOTES:
1. PROVIDE ACCESS CLEARANCE FOR INSPECTION, MAINTENANCE AND REPAIRS.
2. PROVIDE MINIMUM 12" OF BACKFILL. WHERE DAMAGE MAY OCCUR TO PIPING
FROM EXTERNAL LOADS, PROVIDE MINIMUM OF 18" BACKFILL.
3. PIPE BEDDING SHALL BE A MINIMUM OF 2" THICK AND CLEARANCE BETWEEN
OTHER SERVICES SHALL BE A MINIMUM OF 12".
4. SAND SHALL CONSIST OF NATURAL OR MANUFACTURED GRANULAR MATERIAL, OR
A COMBINATION THEREOF, FREE OF DELETERIOUS AMOUNTS OF ORGANIC
MATERIAL, MICA, LOAM, CLAY, AND OTHER SUBSTANCES NOT SUITABLE FOR THE
PURPOSE INTENDED. SAND SHALL BE SUCH SIZE THAT 90 PERCENT TO 100 PERCENT
WILL PASS A NO. 4 SIEVE AND NOT MORE THAN 5 PERCENT WILL PASS A NO. 200
SIEVE.
12" MIN
BETWEEN SERVICES
4' 0" 4' 0"
NO JOINTS IN THIS AREA
1' MIN ∅
PERMANENT
FILL & CAP W/ CONC
SAFETY REFLECTION
TAPE, TYP
4"∅ SCH 40 GPS
2 COATS SAFETY
YELLOW ENAMEL
PAINT
CLASS 420-C-2500
CONC
NOTES:
1. PERMANENT BOLLARDS SHALL BE INSTALLED, UNO.
2. HARD-TEMPERED ZINC PLATED STL CHAIN. 12 IN LENGTH, 3/8 IN ∅ W/ 1 1/2 IN
OPENING, 3 IN TO BE PARTIALLY CAST IN CONCRETE & WELDED TO SLEEVE.
SUB SHEET NO.DESIGNED:
TECH. REVIEW:
DATE:
SHEET
PMIS/PKG NO.
DRAWING NO.
OF
TITLE OF SHEET
148519
PACE
ENGINEERING
REDDING, CA
253759
C R e v it L o c a l F ile s \2
.0
W h is k e y to w n N
P S
G e n e ra to r
A d d it io n M
E C
H R a m ill e r.
rv t
/2
/2
:1 :1
P
M
GENERATOR -
PLUMBING PLAN
P02 5/29/20
BW
AM
AM
WHISKEYTOWN-SHASTA-TRINITY N.R.A.
BRANDY CREEK WASTEWATER TREATMENT PLANT
P021/4" = 1'-0"
4PLUMBING PLAN
GENERAL NOTES
NOTE
1. PRESSURE AT GENERATOR INLET SHALL BE SET AT 9 INCH WC, AND BE MAINTAINED
BETWEEN 7 AND 11 INCH WC.
2. CONTRACTOR SHALL LOCATE EXISTING UTILITIES.
3. CONTRACTOR SHALL PROVIDE TRENCHING, PIPE BEDDING, UNDERGROUND MARKERS,
AND TRENCH FILL, AND COORDINATE WITH TANK AND GAS LINE INSTALLER.
4. MAINTAIN A MINIMUM OF 10'-0" CLEARANCE FROM THE TANK FILL LOCATIONS, RELIEF,
AND VENTS TO IGNITION SOURCES, INCLUDING THE GENERATOR.
5. REMOVE ALL COMBUSTIBLE EXISTING STRUCTURES AND FOLIAGE WITHIN 10'-0" OF TANK.
6. TANKS SHALL BE INSTALLED IN ACCORDANCE WITH NFPA 58, 2019 CALIFORNIA
PLUMBING CODE, AND 2019 CALIFORNIA FIRE CODE.
7. ANY GAS VENT FROM TANK PERTINENCES SHALL BE 10' MINIMUM FROM ANY POTENTIAL
SOURCE OF IGNITION.
KEYNOTES
NOTE#
1. INSTALL BOLLARDS A MINIMUM 3' FROM PROPANE TANK. SPACE 4' APART. MAINTAIN A
MINIMUM 25' FROM TANK SURFACES TO BUILDING, PUBLIC WAYS, AND LOT LINES.
PRIVATE DRIVEWAYS ARE NOT CONSIDERED PUBLIC WAYS.
2. TRENCH AND ROUTE FUEL GAS PIPING UNDERGROUND TO GENERATOR CONNECTION.
3. INCLUDE SHUT-OFF VALVE ON FUEL GAS LINE NEAR TANK.
NTS P02
1LPG TANK INSTALLATION AND PIPING DIAGRAM
NTS P02
2PIPE CROSSING AND BEDDING
NTS P02
3BOLLARD DETAIL
ABBREVIATIONS:
AB Anchor Bolt, Aggregate Base
ACI American Concrete Institute
ADH AB Adhesive Anchor Bolt
APPROX Approximately
ASTM American Society of
Testing Materials
CBC California Building Code
CERT Certificate
CG Center of Gravity
CIP Cast in Place
C Centerline
CONC Concrete
CONT Continuous
CY Cubic yard
DIA, Ø Diameter
EA Each
EF Each Face
EG Existing Grade
FG, FIN GR Finish Grade
FND Foundation
FOC Face of Concrete
GALV Galvanized
HDG Hot Dip Galvanized
HORIZ Horizontal
MAX Maximum
MIN Minimum
MISC Miscellaneous
O/ Over
OC On Center
PSI Pounds per Square Inch
REQD Required
REV Reversed
SF Square Feet
SS, SST Stainless Steel
STL Steel
THRD, THD Threaded
TYP Typical
UNO Unless Noted Otherwise
VERT Vertical
W/ With
W/O Without
L
DD
d d
EXTENSION
4d OR 2-1/2" MIN
12d EXTENSION
180º HOOK
90º HOOK
NOTE:
D = 4d FOR #3 THRU #5
D = 6d FOR #3 THRU #8 BARS
D = 8d FOR #9, 10, 11 BARS
Class 2 aggregate base (AB), referred to as aggregate base material shall be 3/4" max. gradation conforming to Caltrans Standard Specifications, Section 26. Virgin crushed rock shall be utilized. All aggregate base shall be spread and compacted to 95% modified proctor in layers not more than
6" compacted thickness per ASTM D-1557 U.O.N.
AGGREGATE BASE (AB):
All disturbed soils within the footprint of the foundation pads shall be removed to expose dense native soils prior to placing aggregate base.
All areas of existing grade to receive compacted base shall be stripped of existing vegetation and debris and the exposed surface shall be compacted prior to placing aggregate base. Excavations depth under the full footprint of the foundations shall be the same depth so that the aggregate base thickness is consistent.
DEMOLITION AND GRADING:
TESTING & INSPECTION CHECKLIST
ADHESIVE ANCHORS
ITEM TESTING
INSPECTION
BY TYPE
NOTES ON TESTING AND INSPECTION
CRITERIA AND METHODS
REBAR & ANCHORS STR ENGR
OR
SPECIAL
SPOT
CONCRETE SLUMP AIR
CONTENT
COMPR
CYLINDER
STR ENGR
OR
SPECIAL
CONT
STR ENGR
OR
SPECIAL
CONTNONE
Check for size, grade, spacing, clearance, bar support type and spacing, secureness, lap splice locations and lengths, bend diameters. No double or reverse bending. Verify no dirt or oil on rebar.
Hole ∅ & Depth; Brush & Air Clean; Specs for Adhesive Rod ∅ &
Length: Sufficient Adhesive, Cleanup. Installation shall conform with
MFR installation instructions.
NONE
Verify mix design. Prior to placement, measure air content and determine slump with slump cone. Make concrete cylinders (four cylinders minimum for each 100 yards or less of concrete per day).
Check weigh masters certificate to confirm specified concrete mix.
Prepare inspection report. Check consolidation, finishing, and curing methods.
STR ENGR denotes the Engineer responsible for the structural design or his representative.
CONT denotes full-time observation by the designated inspector while the item is being constructed.
SPECIAL denotes an inspector qualified to inspect the item under consideration. Special Inspectors shall not be employed by the contractor.
SPOT denotes observation by the designated inspector after the item is constructed to verify the item is in general conformance with the contract documents and is satisfactory for the next phase of construction.
FOUNDATION PREP STR ENGR
OR
SPECIAL
SPOTCOMPACTION Verify all loose soils and debris removed from foundation footprint an that native soild surface is compacted. Test compaction of AB fill per
ASTM D6983.
5/8" ADHESIVE ANCHORS,
PROVIDE (2) EACH SIDE, 4 TOTAL
MINIMUM WITH MINIMUM 0'-6"
EMBEDMENT INTO CONCRETE
PAD; VERIFY ANCHOR QUANTITY
AND SIZE WITH GENERATOR MFR.
CONCRETE PAD
3/4" CHAMFERED
EDGE, TYP.
PLACE BEARING PADS
BETWEEN FUEL TANK AND
CONCRETE PAD PER
GENSET MANUFACTURER
SOUND ENCLOSURE
FINISHED
GRADE
3" CLR
#4 AT 12" OC MAX
EA WAY AT BOTTOM
OVER EXCAVATE AS SHOWN
AND BACKFILL WITH
COMPACTED CALTRANS CLASS II
AGGREGATE BASE
6" CLR
EARTH
FINISHED
GRADE
3' - 9 5/16"
/1
C
LR
GENERATOR
AND
ENCLOSURE
WEIGHT =
3123 LB
#4x AT 12" OC
EA WAY AT TOP
TYP
TYP
NOTES:
1. CONTRACTOR SHALL VERIFY PAD DIMENSIONS AND SIZE AND
NUMBER OF ANCHORS WITH GENERATOR AND TANK MFR PRIOR TO
CONSTRUCTION OF CONCRETE PADS
3/4" CHAMFERED
EDGE, TYP 4-5/8" MIN
SS ADHESIVE
ANCHORS
PROPANE TANK
FINAL
GRADE
8" CONC SLAB W/ #4
AT 12" OC EA WAY AT
MID-DEPTH
CALTRANS CLASS II AGGREGATE
BASE COMPACT TO 95% RELATIVE
COMPACTION. TEST COMPACTION
PER ASTM D6938
NOTES:
1. SEE FOUNDATION & ANCHOR NOTES ON DETAIL
EARTH
M
IN6
M
IN
TYP ALL SIDES
1' - 0" MIN
S01
PROJECT DESIGN AND CONSTRUCTION NOTES
STRUCTURAL AND BUILDING DESIGN CRITERIA
GENERAL REQUIREMENTS
All construction shall conform with the adopted editions of the Building Codes and all other applicable codes, ordinances, laws and provisions set forth in these Construction
Documents. The Construction Documents are considered to be, but are not limited to, the plans and specifications, notifications, change orders, addendums, clarifications and instructions. Any construction that does not comply with the Construction
Documents shall be subject to rejection by the Engineer or Architect. This project is subject to American Iron and Steel requirements as mandated by the CWSRF Program.
STRUCTURAL REVIEWS AND INSPECTIONS
See CONCRETE section for mix design submittals.
See TESTING AND INSPECTIONS CHECKLIST for required inspections.
The Contractor shall notify the Engineer at least 2 days in advance of any construction activity which requires inspection. Failure of the Engineer to inspect the work when required due to lack of notification will be cause for the Engineer to be relieved of all liability associated with the work.
Foundation Design Data
Allowable Bearing Stress: 1500 psf per CBC TBL 1806.2, class 4 material (Assumed)
Adopted Building Codes: 2019 California Building Code
Contact Engineer if unsuitable soils are encountered at foundations.
28 DAY COMPRESSIVE STRENGTH = 3000 PSI, SEE SPECIFICATIONS FOR ADDITIONAL
REQUIREMENTS.
CONCRETE:
SEE CAST-IN-PLACE CONRETE SPECIFICATIONS FOR ADHESIVE ANCHORS
ADHESIVE ANCHORS:
SUB SHEET NO.DESIGNED:
TECH. REVIEW:
DATE:
SHEET
PMIS/PKG NO.
DRAWING NO.
OF
TITLE OF SHEET
148519
PACE
ENGINEERING
REDDING, CA
253759
C M y F o ld e r\
P ro je c ts
\2
.0 W h is k e y to w n
N P
S G e n e ra to r\
.0
W h is k e y to w n
N P
S G e n e ra to r
V
M
R
.r v t
/2
/2
:2
:3
P
M
GENERATOR - STRUCTURAL
NOTES AND DETAILS
S01 5/29/20
VM
EJ
EJ
WHISKEYTOWN NPS GENERATOR ADDITION
NTS S01
3STANDARD REBAR HOOKS
NTS S01
1GENERATOR FOUNDATION DETAIL
NTS S01
2PROPANE TANK FOUNDATION DETAIL
5/29/20
| Sheets and Views |
| COVER SHEET |
| G02 GENERAL NOTES & LEGEND |
| G03 PROJECT LOCATION |
| C01 CIVIL EXISTING CONDITIONS AND DEMO PLAN |
| C02 CIVIL SITE PLAN |
| C03 CIVIL DETAILS |
| C04 CIVIL DETAILS |
| C05 CIVIL DETAILS |
| B01 COVER SHEET |
| B02 HANDLING INSTRUCTIONS |
| B03 FLOOR PLAN |
| B04 BUILDING ELEVATIONS |
| B05 BUILDING ELEVATIONS |
| B06 INTERIOR ELEVATIONS |
| B07 DETAILS |
| B08 WALL PANEL - MARK W1 |
| B09 WALL PANEL - MARK W2 |
| B10 WALL PANEL - MARK W3 |
| B11 WALL PANEL - MARK W4 |
| B12 WALL PANEL - MARK W5 |
| B13 WALL PANEL - MARK W6 |
| B14 WALL PANEL - MARK W7 |
| B15 WALL PANEL - MARK W8 |
| B16 WALL PANEL - MARK W9 |
| B17 FLOOR SLAB - MARK F1 |
| B18 FLOOR SLAB - MARK F2 |
| B19 ROOF SLAB - MARK R1-R |
| B20 ROOF SLAB - MARK R1-L |
| B21 ROOF SLAB - MARK R2-R |
| B22 ROOF SLAB - MARK R2-L |
| B23 FOUNDATION DETAIL |
| B24 FLOOR DRAIN LOCATIONS & BELOW FLOOR PIPING |
| B25 PLUMBING PLANS |
| B26 PLUMBING PLAN & DIAGRAMS |
| B27 PLUMBING DETAILS, DIAGRAMS, & SCHEDULES |
| B28 ELECTRICAL SCHEDULES |
| B29 ELECTRICAL SCHEDULES |
| B30 HVAC PLAN, DIAGRAM & SCHEDULE |
| B31 MATERIAL LIST |
| 2020-06-01T17:32:15-0700 | |
| Jeffrey M. Tasoff, PE | |
| I am approving this document |
| 2020-06-01T17:33:07-0700 | |
| Jeffrey M. Tasoff, PE | |
| I am approving this document |
| 2020-06-01T17:33:26-0700 | |
| Jeffrey M. Tasoff, PE | |
| I am approving this document |
| 2020-06-01T17:33:45-0700 | |
| Jeffrey M. Tasoff, PE | |
| I am approving this document |
| 2020-06-01T17:39:14-0700 | |
| Jeffrey M. Tasoff, PE | |
| I am approving this document |
| 2020-06-01T17:39:36-0700 | |
| Jeffrey M. Tasoff, PE | |
| I am approving this document |
| 2020-06-01T17:39:53-0700 | |
| Jeffrey M. Tasoff, PE | |
| I am approving this document |
| 2020-06-01T17:40:15-0700 | |
| Jeffrey M. Tasoff, PE | |
| I am approving this document |
File details come from the government source that posted it. Updated .