Attachment_7_Q_and_A_0002.pdf
PDF 2 MB Posted
- Attached to
- Replace Lighthouse Well Pump, Point Reyes N. S. Federal contract opportunity
- Solicitation number
- 140P8325Q0014
About this file
This document is a Request for Quote (RFQ) Questions and Answers attachment for replacing a pump at the Lighthouse Well in Point Reyes National Seashore. The solicitation number is 140P8425Q0014, dated 9/9/25. Key details include the well's remote location with coordinates of 38.04685 degrees North and 122.98837 degrees West, and clarifications on specific technical requirements.
The Q&A addresses five critical points: site location, pump specifications, electrical supply, and drop pipe materials. Specifically, the correct pump is a Goulds 5G S20 2hp model, the electrical supply is single phase, and the existing drop pipe material is Schedule 80 PVC. The document includes photographs of the controller, well head, and site infrastructure, which provide visual context for potential bidders. The attachment appears designed to provide precise technical information to ensure accurate pump replacement at this National Park Service site.
View the file
Other files for this federal contract opportunity
| File | Type | Posted |
|---|---|---|
| Sol_140P8325Q0014_Amd_0002.pdf | ||
| Attachment_6_Revised_Performacne_Work_Statement_0002.pdf | ||
| Sol_140P8325Q0014_Amd_0001.pdf | ||
| Attachment__1_Terms_Provisions_Clauses.pdf | ||
| Attachment_3_Performacne_Work_Statement.pdf | ||
| Attachment_2_DOL_Service_Wage_Rates_2015-5725.pdf | ||
| Sol_140P8325Q0014.pdf | ||
| Attachment_4_Forms_and_Provisions_to_Return_with_Quote.docx | DOCX document | |
| Attachment_5_Optional_Past_Performance_Questionnaire.docx | DOCX document |
On GovTribe
Work with this file on GovTribe
- Download the original file
- Contacts named in this file
- Similar government files
- Ask GovTribe AI about this file
Text version
Solicitation (RFQ) no. 140P8425Q0014, Attachment 7 – Questions & Answers (Q&A) (9/9/25)
Replace Pump at Lighthouse Well, Point Reyes National Seashore (PORE)
Question 1: Please confirm the exact site address.
Answer 1: The site is in a remote area in a pasture and has no address. The coordinates of the site are 38.04685 degrees North and 122.98837 degrees West.
Question 2: The pump model listed in the specifications is for a 5 HP pump, but the specifications state a 2 hp pump is required. Please clarify.
Answer 2: The pump model listed in the specifications is incorrect. The correct pump model is a Goulds 5G S20 which is a 2hp pump.
Question 3: Is the electrical supply single phase or three phase?
Answer 3: The electrical supply at the site is single phase.
Question 4: Do you prefer drop pipe material – Schedule 80 PVC or galvanized steel?
Answer 4: The existing drop pipe materials is Schedule 80 PVC. Material that’s the same or better will be acceptable.
Question 5: Can you provide photographs of the existing well-headed site and any associated well pump equipment?
Answer 5: Photos of the controller and well head are below.