B09_Waterline_Pressure_WHIS_Hydrant_Info_Amd4_0004.xlsx
XLSX spreadsheet 23 KB Posted
- Attached to
- WHIS 267466 Replace Oak Bottom Consolidated Ranger Federal contract opportunity
- Solicitation number
- 140P2021R0170
About this file
This document contains a hydrant testing and flushing report for 2021 from the WHIS federal agency. It lists hydrant inventory numbers, dates tested, locations, models, sizes, and test results including static pressure, residual pressure, pitot pressure, and flow for numerous hydrants located at WHIS headquarters, Brandy Creek, Oak Bottom, the 333 Well System, and N.E.E.D. Camp. It also notes needed repairs and that all hydrants require painting.
The related federal contract opportunity is solicitation number 140P2021R0170 from the Department of the Interior National Park Service to replace the Oak Bottom Consolidated Ranger Operations Building under opportunity WHIS 267466.
View the file
Other files for this federal contract opportunity
Show all 26
On GovTribe
Work with this file on GovTribe
- Download the original file
- Contacts named in this file
- Similar government files
- Ask GovTribe AI about this file
Text version
Sheet1 WHIS Attachment B Hydrant testing and flushing report for 2021
| HEADQUARTERS | |||||||||
| Inventory # | Date | Location | Model | Hyd Size | Water Main Size | Static Pressure (psi) | Residual Pressure (psi) | Pitot (psi) | Flow (gpm) |
| HQ,VC 1 | 9/23/21 | Visitors Center | Mueller | 5 1/2" | 6" | 95 | 20 | 20 | 750.4 |
| HQ 2 | 9/23/21 | HQ, north end of building | Waterous | 5 1/2" | 6" | 106 | 25 | 25 | 839.0 |
| HQ 3 | 10/14/21 | South of Resource/Interp | Waterous | 5 1/2" | 6" | 110 | 32 | 26.5 | 863.8 |
| HQ 4 | 10/26/21 | Trails/ Shop building | Waterous | 5 1/2" | 6" | 108 | 31 | 26 | 855.6 |
| HQ 5 | 10/26/21 | Heli Pad | Mueller | #2 | 4" | 119 | 3 | 0.5 | 118.6 |
| HQ 6 | 9/23/21 | Boat Docks | Mueller | #2 | 4" | 110 | 2.5 | 0.4 | 106.1 |
| Notes: HQ 2 hydrant needs auxilary valve inspected. | ||||||||||
| HQ 4 hydrant needs riser to correct height. | ||||||||||
| All need painted | ||||||||||
| BRANDY CREEK | ||||||||||
| Inventory # | Date | Location | Model | Hyd Size | Water Main Size | Static Pressure (psi) | Residual Pressure (psi) | Pitot (psi) | Flow (gpm) | |
| BC 1 | 4/2/21 | Brandy Creek: A lot | Clow | 5 1/2" | 6" | 55 | 8.65 | 8.65 | 493.5 | |
| BC 2 | 4/2/21 | Brandy Creek: B lot beach | Eclipse | #2 | 2" | 48 | 0.8 | 0.8 | 150.1 | |
| BC3 | 4/2/21 | Brandy Creek: B lot CS | Eclipse | #2 | 3" | 125 | 4.25 | 4.25 | 345.9 | NEW |
| BC 4 | 4/9/21 | Brandy Creek: Marina | Waterous | 4 1/2 | 6" | 130 | 13.2 | 13.2 | 609.6 | |
| Notes: BC 2 hydrant operating valve has been repaired. 5-14-2020 | ||||||||||
| All need painted. |
| OAK BOTTOM | |||||||||
| Inventory # | Date | Location | Model | Hyd Size | Water Main Size | Static Pressure (psi) | Residual Pressure (psi) | Pitot (psi) | Flow (gpm) |
| OB 1 | 9/24/21 | Fire Station | Waterous | 5 1/4 | 4" | 65 | 20 | 20 | 750.4 |
| OB 2 | 10/26/21 | OB Camp Grounds | Mueller | 5 1/4 | 4" | 56 | 4.5 | 4.5 | 355.9 |
| OB 3 | 4/11/21 | OB Marina | Waterous | 5 1/4 | 4" | 83 | 1 | 0.8 | 150.1 |
Notes:All need painted
| 333 SYSTEM | |||||||||
| Inventory # | Date | Location | Model | Hyd Size | Water Main Size | Static Pressure (psi) | Residual Pressure (psi) | Pitot (psi) | Flow (gpm) |
| 333-1 | 4/10/21 | 333 Well | Mueller | #2 | 4" | 135 | N/A | 1.2 | 183.8 |
| 333-2 | 4/10/21 | 321 House. Dispatch | Mueller | #2 | 4" | 135 | N/A | 0.91 | 160.1 |
| Notes:low pressure during flow testing. |
| Both need painted |
| N.E.E.D. Camp | |||||||||
| Inventory # | Date | Location | Model | Hyd Size | Water Main Size | Static Pressure (psi) | Residual Pressure (psi) | Pitot (psi) | Flow (gpm) |
| NC 1 | 10/8/21 | 10106 Paige Bar Rd | Waterous | 5 1/4 | 4" | 92 | 2 | 0.8 | 150.1 |
| 0.0 |
Notes: Needs Painted
File details come from the government source that posted it. Updated .