1. ALL EXISTING FIRE ALARM APPLIANCES, INCLUDING
ASSOCIATED CIRCUITS AND CONDUITS, SHALL BE REMOVED.
C
T C
H L I N
E M
A T
C H
L I N
E
T C
H L I N
E M
A T
C H
L I N
E
MATCHLINE MATCHLINE
MATCHLINE MATCHLINE
EXISTING SILENT KNIGHT 5820 FACP TO REMAIN AND BE RELOCATED. REFER TO
DRAWING FA1.18 FOR NEW LOCATION OF PANEL.
T C
H L I N
E M
A T
C H
L I N
E M
A T
C H
L I N
E
TS
TS
W1
C
C
C
C
C
C
C
C
C
C
C
C
C
C
C
C
C
C
C
C
C
C
TS
TS
C
W
C
W
C
PROVIDE NEW SILENT KNIGHT MODEL SK5820XL-EVS OR
EQUIVALENT FIRE ALARM CONTROL PANEL.
PROVIDE DEDICATED 120 VAC 20 AMP CIRCUIT TO FACP.
REFER TO ELECTRICAL DRAWINGS FOR ADDITIONAL
INFORMATION.
PROVIDE TWO TELEPHONE LINES WITHIN FACP BUILT-IN
DIGITAL ALARM COMMUNICATION TRANSMITTER.
PROVIDE ADDRESSABLE MONITOR MODULES TO MONITOR
WATER FLOW AND VALVE SUPERVISION OF THE FIRST
FLOOR ZONE CONTROL VALVE ASSEMBLY. REFER TO FIRE
SUPPRESSION DRAWING SP1.1 FOR LOCATION.
PROVIDE TAMPER SWITCH FOR FACP CABINET DOOR.
PROVIDE ADDRESSABLE MONITOR TAMPER SWITCH TO
INDICATE WHEN FACP CABINET DOOR IS OPENED.
PROVIDE ADDRESSABLE MONITOR MODULE FOR VALVE
SUPERVISION OF BOTTOM OF ELEVATOR SHAFT CONTROL
VALVE. REFER TO FIRE SUPPRESSION DRAWING SP1.1
FOR LOCATION.
TAP SPEAKER AT
WATT.
PROVIDE ADDRESSABLE MONITOR MODULE FOR VALVE
SUPERVISION OF BASE OF RISER CONTROL VALVE. REFER
TO FIRE SUPPRESSION DRAWING SP1.1 FOR LOCATION.
PROVIDE MANUAL PULL STATION ON MULLION. ROUTE
FIRE ALARM CABLE CONCEALED WITHIN MULLION.
PROVIDE DEDICATED 120 VAC 20 AMP CIRCUIT TO SERVE
AMP AND NAP PANEL. REFER TO ELECTRICAL DRAWINGS
FOR ADDITIONAL INFORMATION.
PROVIDE NOTIFICATION APPLIANCE UNDER LOBBY
BRIDGE. COORDINATE CONDUIT ROUTING AND APPLIANCE
LOCATION WITH ELECTRICAL AND ARCHITECTURAL.
PROVIDE HEAT DETECTOR IN VESTIBULE PER IBC
SECTION 903.1.1.1. DETECTOR SHALL BE RATED FOR HIGH
TEMPERATURE.
PROVIDE TWO ADDRESSABLE MONITOR MODULES FOR
GENERATOR RUNNING AND TWO ADDRESSABLE MONITOR
MODULES FOR GENERATOR FAULT. TWO MODULES SHALL
BE CONNECTED TO WINGS A, B, AND C FIRE ALARM
SYSTEM AND TWO SHALL BE CONNECTED TO WING D FIRE
ALARM SYSTEM. CONTRACTOR SHALL PROVIDE
CONNECTION TO WING D. ALL MODULES SHALL BE
INSTALLED WITHIN 3 FEET OF THE GENERATOR
CONTROLLER/ANNUNCIATOR PANEL.
PROVIDE DUCT SMOKE SENSOR PRIOR TO RETURN AIR
RISER FOR AHU-1. REFER TO MECHANICAL DRAWINGS
FOR LOCATION OF RETURN RISER.
PROVIDE ADDRESSABLE RELAY MODULE WITHIN THREE
FEET OF SECURITY ACCESS CONTROL PANEL. SWITCH
ACTIVATION AT THE FACP SHALL UNLOCK ALL STAIRWELL
DOORS WITHIN WING A.
PROVIDE SWITCH INTEGRAL TO FACP FOR STAIR
UNLOCKING. UPON ACTIVATION ALL STAIRWAY DOORS IN
WINGS A, B, AND C SHALL UNLOCK.
PROVIDE REMOTE TEST STATIONS FOR DUCT SMOKE
DETECTORS IN AN ACCESSIBLE LOCATION STACKED ON
WALL WITHIN ROOM A153.
1. UNO, TAP SPEAKER AT 1/2 WATT.
T C
H L I N
E M
A T
C H
L I N
E M
A T
C H
L I N
E
C
C
C
C
C
C
C
C
C
C
C
C
C
C
C
C
C
C
C
TS
C
C
W
C
C
W W
C
C
C
C
TAP SPEAKER AT
WATT.
PROVIDE ADDRESSABLE MONITOR MODULES FOR VALVE
SUPERVISION AND WATER FLOW DETECTION OF SECOND
FLOOR ZONE CONTROL ASSEMBLY. REFER TO FIRE
SUPPRESSION DRAWING SP1.2 FOR LOCATION.
PROVIDE DEDICATED 120VAC, 20AMP CIRCUIT TO NAP. REFER
TO ELECTRICAL DRAWINGS FOR ADDITIONAL INFORMATION.
PROVIDE SMOKE SENSOR ON SECOND FLOOR CEILING ABOVE
FIRE ALARM CONTROL EQUIPMENT LOCATED ON FIRST FLOOR
BELOW.
PROVIDE DUCT SMOKE SENSOR PRIOR TO RETURN AIR RISER
FOR AHU-1. REFER TO MECHANICAL DRAWINGS FOR LOCATION
OF RETURN RISER.
PROVIDE REMOTE TEST STATIONS FOR DUCT SMOKE
DETECTORS IN AN ACCESSIBLE LOCATION STACKED ON WALL
WITHIN ROOM A254A.
TS
C
C
C
C
C
C
C C
C
C
C
C
C
C
C
C
C
C
C
C
E
TS
C
C
C
C
C
C
TAP SPEAKER AT
WATT.
PROVIDE ADDRESSABLE MONITOR MODULE FOR VALVE
SUPERVISION OF TOP OF ELEVATOR SHAFT SPRINKLERS.
REFER TO FIRE SUPPRESSION DRAWING SP1.3 FOR LOCATION.
PROVIDE HEAT DETECTOR WITHIN 24-INCHES OF SPRINKLER.
PROVIDE ADDRESSABLE MONITOR MODULES FOR VALVE
SUPERVISION AND WATER FLOW DETECTION OF SECOND
FLOOR ZONE CONTROL ASSEMBLY. REFER TO FIRE
SUPPRESSION DRAWING SP1.3 FOR LOCATION.
PROVIDE SMOKE SENSOR PRIOR TO RETURN AIR RISER FOR
AHU-1. PROVIDE SENSOR IN ACCORDANCE WITH NFPA 72
SECTION A.17.7.5.4.2.2. REFER TO MECHANICAL DRAWINGS FOR
LOCATION OF OPENINGS.
TS
W
W W
W
W
W
W
W
TS
AR
AR
W
TS
C
E
C
E
W
E T
C R
E T
C S
PROVIDE ADDRESSABLE MONITOR MODULES FOR VALVE
SUPERVISION AND WATER FLOW DETECTION OF
PENTHOUSE FLOOR ZONE CONTROL ASSEMBLY. REFER
TO FIRE SUPPRESSION DRAWING SP1.4 FOR LOCATION.
PROVIDE ADDRESSABLE MONITOR MODULES FOR VALVE
SUPERVISION OF ELEVATOR MACHINE ROOM
SPRINKLERS. REFER TO FIRE SUPPRESSION DRAWING
SP1.4 FOR LOCATION.
PROVIDE HEAT DETECTOR WITHIN 24-INCHES OF EACH
SPRINKLER.
PROVIDE DUCT SMOKE SENSOR ON RETURN SIDE OF
AHU-1 IN AN ACCESSIBLE LOCATION. REFER TO
MECHANICAL DRAWINGS FOR LOCATION OF RETURN
RISER.
PROVIDE DUCT SMOKE SENSOR ON RETURN SIDE OF
AHU-2 IN AN ACCESSIBLE LOCATION. REFER TO
MECHANICAL DRAWINGS FOR LOCATION OF RETURN
RISER.
PROVIDE ADDRESSABLE RELAY MODULE FOR AHU
RETURN DUCT SMOKE SENSOR AND ANY SMOKE
SENSOR ASSOCIATED WITH THE RETURN AIR SYSTEM.
RELAY SHALL BE LOCATED WITHIN 3 FEET OF AHU
MOTOR. UPON ANY SMOKE SENSOR ACTIVATION
ASSOCIATED WITH THE RETURN AIR SYSTEM, AHU SHALL
SHUT DOWN. REFER TO MECHANICAL DRAWINGS FOR
MOTOR LOCATION.
PROVIDE ADDRESSABLE MODULES WITHIN 3 FEET OF
ELEVATOR CONTROLLER. REFER TO ELECTRICAL
DRAWINGS FOR LOCATION OF ELEVATOR CONTROLLER
PROVIDE ADDRESSABLE MODULES FOR ELEVATOR
PRIMARY DESIGNATED RECALL, SECONDARY
ALTERNATIVE RECALL AND FIREFIGHTER HAT
LIGHT INTERMITTENT FLASHING. REFER TO DETAIL 6 ON
FA5.1.
PROVIDE ADDRESSABLE MODULES WITHIN 3 FEET OF
EACH SHUNT TRIP BREAKER. REFER TO ELECTRICAL
DRAWINGS FOR LOCATION OF ELEVATOR SHUNT TRIP
BREAKER. PROVIDE ADDRESSABLE RELAY MODULE FOR
ELEVATOR SHUNT TRIP AND ADDRESSABLE MONITOR
MODULE FOR SHUNT TRIP POWER CIRCUIT MONITORING.
REFER TO DETAIL 5 ON FA5.1.
TAP SPEAKER AT 1/4 WATT.
PROVIDE REMOTE TEST STATIONS FOR DUCT SMOKE
DETECTORS IN AN ACCESSIBLE LOCATION STACKED ON
WALL WITHIN PENTHOUSE.
1. UNO, TAP SPEAKER AT 1-WATT.
T C
H L I N
E M
A T
C H
L I N
E
C
C
C
C
C
C
C
C
C
C
C
C
C
C
C
C
W
110 WP
PROVIDE TWO ADDRESSABLE MONITOR MODULES FOR THE
O.S.&Y. BACKFLOW PREVENTER VALVES. REFER TO FIRE
SUPPRESSION DRAWING SP1.5 FOR LOCATION.
PROVIDE ADDRESSABLE MONITOR MODULE FOR LOW WATER
PRESSURE SENSOR SWITCH.
TAP SPEAKER AT
-WATT.
PROVIDE WEATHER-PROOF AUDIO-VISUAL NOTIFICATION
APPLIANCE ON DEDICATED CIRCUIT FROM THE FACP WHICH
SHALL ANNUNCIATE UPON WATER FLOW.
PROVIDE ADDRESSABLE MONITOR MODULE FOR THE
STANDPIPE WATER FLOW SWITCH. REFER TO FIRE
SUPPRESSION DRAWING SP1.5 FOR LOCATION.
PROVIDE THREE ADDRESSABLE MONITOR MODULES FOR THE
LOADING DOCK DRY SYSTEM VALVE SUPERVISORY SWITCH,
HI/LOW AIR SUPERVISORY SWITCH AND ALARM PRESSURE
SWITCH. REFER TO FIRE SUPPRESSION DRAWING SP1.5 FOR
LOCATION.
PROVIDE ADDRESSABLE RELAY MODULE WITHIN THREE FEET
OF SECURITY ACCESS CONTROL PANEL. SWITCH ACTIVATION
AT THE FACP SHALL UNLOCK ALL STAIRWELL DOORS WITHIN
WING C.
PROVIDE REMOTE TEST STATIONS FOR DUCT SMOKE
DETECTORS FOR RTU-1 AND RTU-2 LOCATED ON THE ROOF OF
WING C IN AN ACCESSIBLE LOCATION STACKED ON WALL
WITHIN CLOSET ADJACENT TO WAITING AREA C126.
T C
H L I N
E M
A T
C H
L I N
E
MATCHLINE MATCHLINE
C
C
C
C
C
C
CC
C
C
C
C
TS
C, WP
C
C, WP
C
C
C
TAP SPEAKER AT
WATT.
PROVIDE ADDRESSABLE MONITOR MODULE FOR VALVE
SUPERVISION OF BASE OF RISER CONTROL VALVE. REFER TO
FIRE SUPPRESSION DRAWING SP1.6 FOR LOCATION.
PROVIDE DEDICATED 120VAC, 20AMP CIRCUIT TO NAP. REFER
TO ELECTRICAL DRAWINGS FOR ADDITIONAL INFORMATION.
PROVIDE ONE ADDRESSABLE MONITOR MODULE FOR
GENERATOR RUNNING AND ONE ADDRESSABLE MONITOR
MODULES FOR GENERATOR FAULT. MODULES SHALL BE
CONNECTED TO WINGS A, B, AND C FIRE ALARM SYSTEM.
PROVIDE DUCT SMOKE SENSOR PRIOR TO RETURN AIR RISER
FOR AHU-2. REFER TO MECHANICAL DRAWINGS FOR LOCATION
OF RETURN RISER.
PROVIDE REMOTE TEST STATION FOR DUCT SMOKE DETECTOR
IN AN ACCESSIBLE LOCATION ON WALL WITHIN ROOM B128A.
C
C
C
C
C
C
C
C
C
C
C
C
C
C CC
C
C
C
C
C
C
W
AR
AR
AR
TAP SPEAKER AT
WATT.
PROVIDE DUCT SMOKE SENSOR ON RETURN SIDE OF RTU-1 IN AN
ACCESSIBLE LOCATION. REFER TO MECHANICAL DRAWINGS FOR
LOCATION OF RETURN RISER.
PROVIDE DUCT SMOKE SENSOR ON RETURN SIDE OF RTU-2 IN AN
ACCESSIBLE LOCATION. REFER TO MECHANICAL DRAWINGS FOR
LOCATION OF RETURN RISER.
PROVIDE ADDRESSABLE RELAY MODULE FOR AHU RETURN DUCT SMOKE
SENSOR. RELAY SHALL BE LOCATED WITHIN 3 FEET OF AHU MOTOR FOR
AHU SHUTDOWN UPON DUCT SMOKE SENSOR ACTIVATION. REFER TO
MECHANICAL DRAWINGS FOR MOTOR LOCATION.
PROVIDE ADDRESSABLE RELAY MODULE WITHIN THREE FEET OF
SECURITY ACCESS CONTROL PANEL. SWITCH ACTIVATION AT THE FACP
SHALL UNLOCK ALL STAIRWELL DOORS WITHIN WING B.
PROVIDE DUCT SMOKE SENSOR PRIOR TO RETURN AIR RISER FOR AHU-2.
REFER TO MECHANICAL DRAWINGS FOR LOCATION OF RETURN RISER.
PROVIDE REMOTE TEST STATION FOR DUCT SMOKE DETECTOR IN AN
ACCESSIBLE LOCATION ON WALL WITHIN ROOM B228.
TS
TSAI
AI
AI
TS
AP
N A
P
T V
S S
C
C
C
C
C
C
C
CC
C
C
C
TSAI
W, WP
C
RELOCATE EXISTING SILENT KNIGHT 5820 FACP TO THIS LOCATION.
PROVIDE DEDICATED 120 VAC 20 AMP CIRCUIT TO FACP. REFER TO
ELECTRICAL DRAWINGS FOR ADDITIONAL INFORMATION.
PROVIDE TWO TELEPHONE LINES WITHIN FACP BUILT-IN DIGITAL ALARM
COMMUNICATION TRANSMITTER.
PROVIDE TAMPER SWITCH FOR FACP CABINET DOOR. PROVIDE
ADDRESSABLE MONITOR TAMPER SWITCH TO INDICATE WHEN FACP
CABINET DOOR IS OPENED.
PROVIDE TWO ADDRESSABLE MONITOR MODULES FOR THE O.S.&Y.
BACKFLOW PREVENTER VALVES. REFER TO FIRE SUPPRESSION DRAWING
SP1.8 FOR LOCATION.
PROVIDE ADDRESSABLE MONITOR MODULE FOR LOW WATER PRESSURE
SENSOR SWITCH. REFER TO FIRE SUPPRESSION DRAWING SP1.8 FOR
LOCATION.
PROVIDE DEDICATED 120VAC, 20AMP CIRCUIT TO NAP. REFER TO
ELECTRICAL DRAWINGS FOR ADDITIONAL INFORMATION.
PROVIDE ADDRESSABLE MONITOR MODULES TO MONITOR WATER FLOW
AND VALVE SUPERVISION OF THE FIRST FLOOR ZONE CONTROL VALVE
ASSEMBLY.REFER TO FIRE SUPPRESSION DRAWING SP1.8 FOR LOCATION.
PROVIDE ADDRESSABLE MONITOR MODULE FOR VALVE SUPERVISION OF
BOTTOM OF ELEVATOR SHAFT CONTROL VALVE. REFER TO FIRE
SUPPRESSION DRAWING SP1.8 FOR LOCATION.
PROVIDE MANUAL PULL STATION ON MULLION. ROUTE FIRE ALARM CABLE
CONCEALED WITHIN MULLION.
PROVIDE WEATHER-PROOF AUDIO-VISUAL NOTIFICATION APPLIANCE ON
DEDICATED CIRCUIT FROM THE FACP WHICH SHALL ANNUNCIATE UPON
WATER FLOW.
PROVIDE DUCT SMOKE SENSOR PRIOR TO RETURN AIR RISER FOR AHU-3. .
REFER TO MECHANICAL DRAWINGS FOR LOCATION OF RETURN RISER.
PROVIDE ADDRESSABLE RELAY MODULE WITHIN THREE FEET OF SECURITY
ACCESS CONTROL PANEL. SWITCH ACTIVATION AT THE FACP SHALL
UNLOCK ALL STAIRWELL DOORS WITHIN WING A.
PROVIDE SWITCH INTEGRAL TO FACP FOR STAIR UNLOCKING. UPON
ACTIVATION ALL STAIRWAY DOORS IN WING D SHALL UNLOCK.
PROVIDE REMOTE TEST STATION FOR DUCT SMOKE DETECTOR IN AN
ACCESSIBLE LOCATION ON WALL WITHIN ROOM D144.
AI
AI TS
C
C
E
AI TS
PROVIDE ADDRESSABLE MONITOR MODULES FOR VALVE
SUPERVISION AND WATER FLOW DETECTION OF SECOND
FLOOR ZONE CONTROL ASSEMBLY. REFER TO FIRE
SUPPRESSION DRAWING SP1.9 FOR LOCATION.
PROVIDE HEAT SENSOR WITHIN 24-INCHES OF SPRINKLER.
PROVIDE ADDRESSABLE MONITOR MODULE FOR VALVE
SUPERVISION OF TOP OF ELEVATOR SHAFT SPRINKLERS.
REFER TO FIRE SUPPRESSION DRAWING SP1.9 FOR LOCATION.
PROVIDE DUCT SMOKE SENSOR PRIOR TO RETURN AIR RISER
FOR AHU-3. REFER TO MECHANICAL DRAWINGS FOR LOCATION
OF RETURN RISER.
PROVIDE REMOTE TEST STATION FOR DUCT SMOKE DETECTOR
IN AN ACCESSIBLE LOCATION ON WALL WITHIN ROOM D244.
AI TS
AI
W
P
W3
W 7
AI TS
AR
PROVIDE ADDRESSABLE MONITOR MODULES FOR VALVE SUPERVISION AND
WATER FLOW DETECTION OF PENTHOUSE FLOOR ZONE CONTROL ASSEMBLY.
REFER TO FIRE SUPPRESSION DRAWING SP1.10 FOR LOCATION.
PROVIDE ADDRESSABLE MONITOR MODULES FOR VALVE SUPERVISION OF
ELEVATOR MACHINE ROOM SPRINKLERS. REFER TO FIRE SUPPRESSION DRAWING
SP1.10 FOR LOCATION.
PROVIDE HEAT DETECTOR WITHIN 24-INCHES OF EACH SPRINKLER.
PROVIDE DUCT SMOKE SENSOR ON RETURN SIDE OF AHU-3 IN AN ACCESSIBLE
LOCATION. REFER TO MECHANICAL DRAWINGS FOR LOCATION OF RETURN RISER.
PROVIDE ADDRESSABLE RELAY MODULE FOR AHU RETURN DUCT SMOKE SENSOR
AND ANY SMOKE SENSOR ASSOCIATED WITH THE RETURN AIR SYSTEM. RELAY
SHALL BE LOCATED WITHIN 3 FEET OF AHU MOTOR. UPON ANY SMOKE SENSOR
ACTIVATION ASSOCIATED WITH THE RETURN AIR SYSTEM, AHU SHALL SHUT
DOWN. REFER TO MECHANICAL DRAWINGS FOR MOTOR LOCATION.
PROVIDE ADDRESSABLE MODULE WITHIN 3 FEET OF ELEVATOR CONTROLLER.
REFER TO ELECTRICAL DRAWINGS FOR LOCATION OF ELEVATOR CONTROLLER
PROVIDE ADDRESSABLE MODULES FOR ELEVATOR PRIMARY DESIGNATED
RECALL, SECONDARY ALTERNATIVE RECALL AND FIREFIGHTER HAT LIGHT
INTERMITTENT FLASHING. REFER TO DETAIL 6 ON FA5.1.
PROVIDE ADDRESSABLE MODULES WITHIN 3 FEET OF EACH SHUNT TRIP
BREAKER. REFER TO ELECTRICAL DRAWINGS FOR LOCATION OF ELEVATOR
SHUNT TRIP BREAKER. PROVIDE ADDRESSABLE RELAY MODULE FOR ELEVATOR
SHUNT TRIP AND ADDRESSABLE MONITOR MODULE FOR SHUNT TRIP POWER
CIRCUIT MONITORING. REFER TO DETAIL 5 ON FA5.1.
PROVIDE REMOTE TEST STATION FOR DUCT SMOKE DETECTOR IN AN
ACCESSIBLE LOCATION STACKED ON WALL WITHIN PENTHOUSE.
E T
C R
E T
C S
C
E
C
E
W
UTILIZE SPRINKLER/STANDPIPE RISER OR EXPRESS DRAIN FLOOR
PENETRATION FOR CONDUIT PASSAGE THROUGH FLOOR. TYPICAL
FOR ALL FIRE ALARM RISERS IN STAIRWELLS. COORDINATE WITH
SPRINKLER CONTRACTOR.
FIRE ALARM CONDUIT RISER
EXPRESS DRAIN RISER
SPRINKLER/STANDPIPE RISER
TO VALVE TAMPER/SUPERVISORY SWITCH
WATERFLOW SWITCH
ADDRESSABLE INTERFACE DEVICE
TO SPRINKLER SYSTEM
MANUAL PULL STATION
CONDUIT TO NEXT DEVICES OR FACP
48"
4" SQUARE, DEEP BACKBOX
4" SQUARE EXTENSION RING
CEILING SUPPORT BRIDGE
SUSPENDED CEILING TILE
WITH HOLE CUT AS NEEDED
COMBINATION AUDIO-VISUAL
FIRE ALARM NOTIFICATION DEVICE
FIRE ALARM AUDIO
NOTIFICATION DEVICE
FIRE ALARM VISUAL
NOTIFICATION DEVICE
STANDARD OR DEEP 4"
OCTAGON WIRING BOX
DETECTOR IDENTIFICATION
CLEAR LED LENS
NOTES:
1. PROVIDE MINIMUM 12"x12"x4" DEEP NEMA 1 TERMINAL BOX WITH SCREW COVER (CONTRACTOR
SHALL VERIFY REQUIRED BOX SIZE). LABEL "FIRE ALARM-ELEVATOR RECALL CONNECTIONS" WITH
ASSOCIATED ELEVATOR NUMBERS.
2. LOCATE ERTC WITHIN THREE FEET OF ASSOCIATED ELEVATOR DISPATCH CONTROL CENTER.
3. ONE CONTROL RELAY SHALL CAUSE FIRE HAT LIGHT TO ILLUMINATE STEADILY UPON ACTIVATION
OF FIRE ALARM INITIATING DEVICE LOCATED ON EACH FLOOR SERVED BY THE ELEVATOR AND
ARRANGED TO INITIATE PHASE 1 EMERGENCY RECALL OPERATIONS. THE SECOND CONTROL RELAY
SHALL CAUSE FIRE HAT LIGHT TO ILLUMINATE INTERMITTENTLY ONLY UPON ACTIVATION OF FIRE
ALARM DEVICE IN ELEVATOR EQUIPMENT ROOM, ELEVATOR PULLEY ROOM OR HOISTWAY.
SLC TO NEXT DEVICE
SLC TO NEXT DEVICE
TO ELEVATOR CONTROLLERS
ELEVATOR DESIGNATED PRIMARY
AND SECONDARY (ALTERNATE)
RECALL FLOOR CONTROL CIRCUITS,
INTERFACE POINTS
SEE NOTES 1 AND
2, THIS DETAIL
EMT (TYPICAL)
ELEVATOR DESIGNATED FIRE HAT LIGHT
CONTROL CIRCUIT INTERFACE POINT.
SEE NOTE 3, THIS DETAIL
NOTES:
1. POWER SUPPLY TO ALL SHUNT TRIP CIRCUIT BREAKERS IN EMR.
ADDRESSABLE
INTERFACE
MODULE
NO
NC
120VAC RELAY
TERMINAL
STRIP
ADDRESSABLE
OUTPUT MODULE
120VAC SHUNT
TRIP POWER
TO ELEVATOR
POWER
PANEL(S)
SHUNT TRIP
CIRCUIT
BREAKER, SEE
NOTE 1 THIS
DETAIL
END OF LINE SUPERVISION
DEVICE
ADDRESSABLE INTERFACE MODULE TO
MONITOR ACTIVATION OF SHUNT TRIP
TO NEXT DEVICE
1. PROVIDE MINIMUM 12"x12"x4" DEEP NEMA 1 TERMINAL BOX WITH SCREW COVER
(CONTRACTOR SHALL VERIFY REQUIRED BOX SIZE). LABEL "FIRE ALARM ELEVATOR SHUNT
TRIP CONNECTION" WITH ASSOCIATED ELEVATOR NUMBERS.
2. LOCATE TERMINAL BOX, WITHIN THREE FEET OF ASSOCIATED SHUNT TRIP CIRCUIT
BREAKER/DISCONNECT DEVICE. REFER TO ELECTRICAL DRAWINGS FOR EXACT LOCATION.
NOTES
AI
AR
R
SLC TO NEXT DEVICE
120v SHUNT TRIP POWER
TO ELEVATOR POWER PANEL
SHUNT TRIP CIRCUIT BREAKER
SLC TO NEXT DEVICE
EMT (TYPICAL)
SEE NOTES 1 & 2
ELEVATOR POWER SHUT TRIP
CONTROL CIRCUIT INTERFACE
POINT
ADDRESSABLE LOAD CONTROL FIELD
RELAY WITH 24DC COIL AND 2 SETS
OF NORMALLY OPEN AND NORMALLY
CLOSED (DPDT) CONTACTS RATED AT
120 VAC, 4 AMPS, INDUCTIVE.
ADDRESSABLE INTERFACE
MODULE
ADDRESSABLE RELAY
FACP NAP4
TVSS
DACT
TVSS
AI
W,WP
AI
TS
AI
AI
TS
AI
AI
TS
AI
P
AR
P
E
AI
TS
AI
TS
AI
AP
E
P
FACP
DACT
TVSS
AI
AI
TS
AI AI
TS
AI
TS
NAP1
TVSS
NAP2
TVSS
NAP3
TVSS
AI
TS
AI
AI
TS
AI
AI
TS
AI
AI
TS
AI AI
APTS
AI
TS
W,WP
P
E
E
E
P
AMP
AI
TS
AI
WF
AI
AP
AI
PS
AR
EXISTING SILENT KNIGHT 5820 FACP.
DEDICATED 120 VAC 20 AMP CIRCUIT TO PANEL.
TAMPER SWITCH FOR FACP CABINET DOOR.
NEW SILENT KNIGHT FACP.
DEDICATED CIRCUIT FROM FACP TO EXTERIOR NOTIFICATION
APPLIANCE. ACTIVATION SHALL OCCUR UPON WATER FLOW.
ADDRESSABLE MONITOR MODULES FOR THE LOADING DOCK
DRY SYSTEM VALVE SUPERVISORY SWITCH, HI/LOW AIR
SUPERVISORY SWITCH AND ALARM PRESSURE SWITCH. .
POWER CIRCUIT FOR FRACTIONAL HP RISER MOUNT AIR
COMPRESSOR. REFER TO ELECTRICAL DRAWINGS FOR
ADDITIONAL INFORMATION.
ADDRESSABLE MONITOR MODULE FOR LOW WATER PRESSURE
SENSOR SWITCH.
ADDRESSABLE MONITOR MODULES FOR VALVE SUPERVISORY
AND WATER FLOW SWITCH FOR FLOOR ZONE CONTROL
ASSEMBLY.
1. RISER DIAGRAM IS SCHEMATIC IN NATURE, REFER TO
INDIVIDUAL FLOOR PLANS FOR EXACT LOCATIONS AND
QUANTITIES OF EQUIPMENT.
2. REFER TO PANEL/CIRCUIT SCHEDULE ON FA6.1 FOR CIRCUIT
QUANTITY, ORIGINATION, AND ASSOCIATE ZONE.
3. REFER TO CIRCUIT SCHEDULE FOR ADDITIONAL INFORMATION
ON NOTIFICATION APPLIANCES.
1. THE SCOPE OF THIS PROJECT INCLUDES PROVIDING A COMPLETE COMBINATION
AUTOMATIC SPRINKLER/MANUAL WET STANDPIPE SYSTEM THROUGHOUT THE NCR
HEADQUARTERS BUILDING (WINGS A, B, AND C) AND PROVIDING A COMPLETE
AUTOMATIC SPRINKLER SYSTEM THROUGHOUT THE USPP BUILDING (WING D) AS
INDICATED ON THE DRAWINGS AND AS DESCRIBED IN THE SPECIFICATIONS. THIS
INCLUDES ALL PIPING, WATER FLOW ALARM SWITCHES, VALVE SUPERVISORY
SWITCHES, CHECK VALVES, CONTROL VALVES, BACKFLOW PREVENTERS, FIRE
DEPARTMENT CONNECTIONS, PIPING, HANGERS, SPRINKLERS, AND ALL
ASSOCIATED EQUIPMENT. ALL EQUIPMENT PROVIDED SHALL BE UL LISTED.
2. ALL WORK AND INSTALLATION SHALL CONFORM TO THE APPLICABLE CODES AND
STANDARDS INCLUDING:
NFPA 13: STANDARD FOR THE INSTALLATION OF SPRINKLER SYSTEMS (2010).
NFPA 14: STANDARD FOR THE INSTALLATION OF STANDPIPE AND HOSE
SYSTEMS (2010)
NFPA 25: STANDARD FOR THE INSPECTION, TESTING, AND MAINTENANCE OF
WATER-BASED FIRE PROTECTION SYSTEMS (2011).
NPS-NCR FIRE PROTECTION SYSTEM REQUIREMENTS REV 9/30/2014.
INTERNATIONAL BUILDING CODE (2012)
3. AVAILABLE FLOW AND PRESSURE FOR THE NEW SPRINKLER SYSTEMS ARE
HYDRAULICALLY BASED ON THE WATER DISTRIBUTION SYSTEM IMPROVEMENTS
TO NPS-NCR & USPP HEADQUARTERS PROJECT (PMIS 201409 DATED 8/15/14) BEING
CONSTRUCTED AHEAD OF THE NCRO HAINS POINT FACILITIES PROJECT. IF THE
NEW WATERLINE IS NOT CONSTRUCTED AS INDICATED ON PMIS 201409, THE
EXISTING SITE WATER SUPPLY MAY NOT PROVIDE THE NFPA 13 REQUIRED
PRESSURE AND FLOW TO THE WINGS A,B,C AND WING D SPRINKLER SYSTEMS.
4. UNLESS NOTED OTHERWISE ON THE DRAWINGS, THE DESIGN INTENT IS TO
CONCEAL ALL SPRINKLER PIPE ABOVE THE CEILINGS ON ALL FLOORS OF THE
BUILDINGS.
5. FINAL SPRINKLER LOCATIONS SHALL BE COORDINATED IN THE FIELD. COORDINATE
SPRINKLERS WITH ALL OBSTRUCTIONS SUCH CEILING JOISTS, BEAMS AND
DUCTWORK. SPRINKLER SHOP DRAWINGS SHALL BE PREPARED AND SUBMITTED
IN ACCORDANCE WITH NFPA 13.
6. QUICK RESPONSE, ORDINARY TEMPERATURE SPRINKLERS SHALL BE PROVIDED
THROUGHOUT UNLESS REQUIRED TO BE INTERMEDIATE OR HIGH TEMPERATURE
RATED PER NFPA 13.
7. PRIOR TO CLOSE IN OF CEILINGS, WALLS OR SOFFITS CONTAINING SPRINKLER
PIPE, THE CONTRACTOR SHALL HAVE THE COR WITNESS AND VERIFY
HYDROSTATIC TESTING WITHOUT ANY LOSS IN PRESSURE AND VISUAL LEAKAGE.
8. A COMBINATION INSPECTOR'S TEST CONNECTION, DRAIN ASSEMBLY AND RELIEF
VALVE SHALL BE PROVIDED FOR EACH SPRINKLER ZONE CONTROL VALVE
ASSEMBLY.
9. THE FOLLOWING WATER FLOW TEST DATA WAS PERFORMED BY DC WATER
(REFER TO WATER SITE PLAN).
DATE - 2/20/2014
STATIC - 66 PSI
RESIDUAL - 59 PSI
FLOW - 2,859 GPM
THIS DATA IS FOR INFORMATIONAL PURPOSES ONLY. THE CONTRACTOR AND
PROVIDE A NEW WATER FLOW TEST WITHIN ONE YEAR FROM THE START OF
INSTALLATION.
10. PIPE SIZES SHOWN HAVE BEEN VERIFIED BY HYDRAULIC CALCULATIONS.
ALTERNATE PIPE SIZES IS PERMITTED IF HYDRAULIC CALCULATIONS ARE
SUBMITTED AND APPROVED BY THE COR.
11. SPRINKLERS SHALL BE PROVIDED AT LEAST 18 INCHES FROM ANY AIR DEVICES.
12. INSPECTOR'S TEST CONNECTION SHALL BE LOCATED AT THE MOST REMOTE
HYDRAULIC POINT OF THE SYSTEM. PIPING SHALL BE TERMINATED AT THE
EXTERIOR OF THE BUILDING ONTO A SPLASH BLOCK.
13. A MINIMUM OF 80 INCHES SHALL BE MAINTAINED BETWEEN FLOOR AND LOWEST
POINT OF VALVES, FITTINGS, AND PIPE IN STAIRWELLS AND OTHER AREAS OF
EXPOSED PIPE. IN MECHANICAL ROOMS AND UNOCCUPIED SPACES. CONTRACTOR
SHALL MAINTAIN 80 INCHES HEADROOM CLEARANCE TO THE EXTENT PRACTICAL.
14. ALL AREAS OF THE BUILDINGS ARE CONSIDERED CONDITIONED; THAT IS
TEMPERATURES WILL REMAIN ABOVE 40 F.
15. ALL SPRINKLER PIPING SHALL BE BLACK IRON, SCHEDULE 40 FM LISTED AND
APPROVED PIPE, WITH ROLLED GROOVES.
16. THE STEEL PIPING SYSTEMS INCLUDING VALVES, PIPING, PIPE SLEEVES, HANGERS
AND ACCESSORIES SHALL BE CLEANED, PRE-TREATED, PRIMED AND PAINTED.
COATINGS SHALL BE APPLIED ONLY TO CLEAN, DRY SURFACES USING CLEAN
BRUSHES. SURFACES SHALL BE CLEANED TO REMOVE ALL DUST, DIRT, RUST AND
LOOSE MILL SCALE. DUE CARE SHALL BE EXERCISED TO AVOID PAINTING OF
SPRINKLERS OR ALLOWING ANY PAINT TO DRIP OR SPLATTER ANYWHERE IN THE
BUILDINGS. ANY EXPOSED SPRINKLER PIPE SHALL BE PAINTED ONE COAT TO
MATCH EXISTING ADJACENT WALL OR CEILING SURFACE, AND RED ENAMEL BANDS
4 INCHES WIDE SHALL BE PAINTED AT 10 FOOT INTERVALS. ALL OTHER AREAS
SHALL BE PAINTED ONE COAT IN ITS ENTIRETY WITH RED ENAMEL.
17. ANY INFORMATION CONFLICTS BETWEEN THE SPECIFICATIONS AND DRAWINGS
SHALL BE BROUGHT TO THE ATTENTION OF THE CONTRACTING OFFICER. THE
CONTRACTOR SHALL NOT PROCEED WITH ANY WORK, EXCEPT AT THEIR OWN
RISK, UNTIL CLARIFICATIONS OF THE CONFLICTS ARE ISSUED TO THE
CONTRACTOR BY THE COR.
18. ALL DIMENSIONS AND CONDITIONS SHALL BE VERIFIED AT JOB SITE CONCERNING
THE WORK BEFORE PROCEEDING WITH EITHER FABRICATION OR INSTALLATION OF
NEW WORK. LOCATION OF SYSTEMS, PIPING, RISERS AND SPRINKLERS ARE
APPROXIMATE. IT SHALL BE THE RESPONSIBILITY OF THE CONTRACTOR TO VERIFY
THE LOCATION OF ALL SYSTEM COMPONENTS. ANY DISCREPANCIES WITH THESE
DRAWINGS SHALL BE REPORTED TO THE COR IMMEDIATELY.
19. CONTRACTOR SHALL BE RESPONSIBLE FOR AVOIDING CONFLICTS WITH LIGHTS,
FIXTURES, DIFFUSERS, GRILLS, FIRE ALARM DEVICES, DUCTS, PIPING, CONDUIT,
STRUCTURAL MEMBERS AND ALL OTHER OBSTRUCTIONS ENCOUNTERED. THE
CONTRACTOR IS ADVISED SOME AREAS REQUIRE EXTENSIVE COORDINATION OF
SPRINKLER PIPE WITHIN EXISTING SPACES, SUCH AS MECHANICAL EQUIPMENT,
DUCTS, PIPING, CONDUIT, STRUCTURAL MEMBERS, WIRE TROUGH, ETC.
20. ALL SPRINKLER AND STANDPIPE PIPING SHALL BE INSTALLED SO THAT ALL
PORTIONS FOR EACH SYSTEM CAN BE DRAINED BACK THROUGH THE DRAIN
VALVE(S). WHERE PIPING CANNOT BE DRAINED BACK TO THE SPRINKLER ZONE
CONTROL ASSEMBLY DRAIN VALVES, PROVIDE AUXILIARY DRAINS IN ACCORDANCE
WITH NFPA 13. ALL DRAINS SHALL BE PIPING TO THE OUTSIDE.
21. ALL DAMAGE TO WALLS, CEILINGS, FLOORS, AND STRUCTURAL MEMBERS FROM
PENETRATIONS, INSTALLATIONS OR OTHER ACTIONS OF THE CONTRACTOR SHALL
BE PATCHED, REPAIRED AND PAINTED WITH NEW MATERIALS BY THE
CONTRACTOR TO MATCH ADJACENT WORK, WHETHER SPECIFICALLY NOTED OR
NOT.
22. ALL NECESSARY PERMITS AND APPROVALS SHALL BE OBTAINED PRIOR TO
CONDUCTING ANY WELDING AND CUTTING OPERATIONS.
23. ALL WALL AND FLOOR PARTITIONS SHALL BE CORE DRILLED. PROVIDE PIPE
SLEEVES FOR ALL WALL AND FLOOR PENETRATIONS AS INDICATED IN THE
SPECIFICATIONS. ALL PENETRATIONS SHALL IN WALLS, CEILINGS AND FLOORS
SHALL BE SEALED TO THE FULL THICKNESS OF THE PENETRATIONS WITH
APPROVED FIRE STOPPING MATERIAL OF EQUAL OR GREATER FIRE RESISTANCE.
REFER TO ARCHITECTURAL DRAWINGS FOR FIRE RESISTANCE RATING
REQUIREMENTS AND LOCATIONS.
24. CONTRACTOR SHALL NOT CUT, DRILL OR BURN ANY STRUCTURAL MEMBERS
UNLESS PREVIOUSLY APPROVED BY THE CONTRACTING OFFICER. THE
CONTRACTOR SHALL NOT CUT OR PATCH STRUCTURAL WORK IN A MANNER THAT
WOULD RESULT IN A REDUCTION OF LOAD-CARRYING OR LOAD-DEFLECTION
RATIO.
25. ALL WORK SHALL BE COORDINATED WITH THE COR, INCLUDING ACCESS TO THE
SITE AND BUILDINGS. SCHEDULE WORK TO MINIMIZE DISRUPTION TO OCCUPANTS.
WORK SHALL BE PROPERLY SECURED WITH BARRIERS SO AS NOT TO CREATE A
SAFETY HAZARD. MATERIALS SUCH AS TOOLS, LADDERS AND INSTALLATION
MATERIAL SHALL BE KEPT TO A MINIMUM.
26. CONTRACTOR SHALL BE RESPONSIBLE FOR PROTECTING ALL EQUIPMENT,
FURNISHINGS, FIXTURES AND CONTENTS OF THE SPACE FROM DAMAGE, DUST
WATER AND DEBRIS ASSOCIATED WITH WORK. CONTRACTOR IS RESPONSIBLE
FOR DAILY CLEAN UP, INCLUDING REMOVAL OF ALL TRASH, DEBRIS AND
CONSTRUCTION MATERIALS ON A DAILY BASIS, AND RESTORING TO
PRE-CONSTRUCTION CONDITION AS WORK IS COMPLETED.
27. ANY NEW CORES IN EXISTING REINFORCED CONCRETE SLABS SHALL BE LOCATED
TO AVOID CUTTING JOISTS, BEAMS OR REBAR. CONTRACTOR IS REQUIRED TO
LOCATE BY GPR SCAN OR SIMILAR INVESTIGATION AND MARK LOCATIONS ON
FLOOR. CORES SHALL BE PLACED TO AVOID CUTTING EXISTING REBAR. IF IT IS
NOT FEASIBLE TO AVOID CUTTING REBAR THAN CONTRACTOR IS REQUIRED
SUBMIT SKETCHES INDICATING REBAR LOCATIONS ALONG WITH SUGGESTED
OPENING LOCATIONS TO CONTRACTING OFFICIAL FOR APPROVAL. ALLOW 2
WEEKS FOR REVIEW. FOR OPENINGS IN ROOF DECK OR COMPOSITE SLAB ON
DECK REFER TO TYPICAL DETAILS.
28. THE TERM "PROVIDE" SHALL MEAN THE CONTRACTOR SHALL FURNISH, INSTALL
AND CONNECT FOR A COMPLETE AND OPERATIONAL SYSTEM.
NEW WORK DEVICE LINE TYPE
PIPE SIZE
SPRINKLER RISER
EXPRESS DRAIN RISER
O.S.&Y. CONTROL VALVE WITH SUPERVISORY SWITCH
BUTTERFLY CONTROL VALVE WITH SUPERVISORY SWITCH
BUTTERFLY CONTROL VALVE WITH SUPERVISORY SWITCH ON
RISER OR ELBOW
DELUGE VALVE IN VERTICAL POSITION
BACKFLOW PREVENTOR IN VERTICAL POSITION
DRY PIPE VALVE
DRY PIPE VALVE IN VERTICAL POSITION
GLOBE VALVE
CHECK VALVE
ZONE CONTROL ASSEMBLY
WATER FLOW SWITCH
90° ELBOW TURNED AWAY FROM VIEWER
45° ELBOW TURNED AWAY FROM VIEWER
TEE TURNED AWAY FROM VIEWER
PIPE CONTINUATION
CAP
PRESSURE GAUGE
QUICK RESPONSE UPRIGHT SPRINKLER
CONCEALED PENDENT SPRINKLER
DRY SIDEWALL SPRINKLER
FIRE HOSE VALVE - PLAN VIEW
FIRE HOSE VALVE - SIDE VIEW
SPRINKLER ZONE
START OF WORK INDICATOR
KEY NOTE INDICATOR
HYDRAULIC NODE INDICATOR
DETAIL IDENTIFICATION NUMBER
DETAIL BUBBLE
SHEET DETAIL IS SHOWN ON
SECTION IDENTIFICATION NUMBER
SECTION BUBBLE
SHEET SECTION IS SHOWN ON
ACM
AFF
ATC
BM
BOB
CON
CONC
CONF
COR
CSA
CSM
DEMO
DN
ELEC
EXIST
ETR
FDC
FL
FM
F.S.
FT
GYP
IBC
IN
LAT
LTH
MECH
NFPA
NIC
NO
NPS
OH1
OH2
RM
SERV
SPH
STL
TELE
UL
UNO
ASBESTOS CONTAINING MATERIAL
ABOVE FINISHED FLOOR
ACOUSTICAL TILE CEILING
BEAM
BOTTOM OF BEAM
CONCRETE SLAB AND BEAMS
CONCRETE
CONFERENCE
CONTRACTING OFFICER REPRESENTATIVE
CONCEALED SPLINE SUSPENDED ACOUSTICAL TILE
CONCEALED METAL SPLINE SUSPENDED ACOUSTICAL
TILE
DEMOLITION
DOWN
ELECTRICAL
EXISTING
EXISTING TO REMAIN
FIRE DEPARTMENT CONNECTION
FLOOR
FACTORY MUTUAL
FLOW SWITCH
FEET
GYPSUM BOARD ON WOOD OR METAL JOISTS
INTERNATIONAL BUILDING CODE
INCH
LAY-IN ACOUSTICAL TILE - SUSPENDED
LIGHT HAZARD
MECHANICAL
NATIONAL FIRE PROTECTION ASSOCIATION
NOT IN CONTRACT
NUMBER
NATIONAL PARK SERVICE
ORDINARY HAZARD-GROUP 1
ORDINARY HAZARD-GROUP 2
ROOM
SERVICE
SPECIAL HAZARD
STEEL DECK
TELEPHONE
UNDERWRITERS LABORATORIES
UNLESS NOTED OTHERWISE
ALL AREAS ARE TO BE CONSIDERED LIGHT HAZARD (0.10 GPM/SQ FT
OVER 1500 SQ FT) UNLESS NOTED OTHERWISE.
ORDINARY HAZARD, GROUP 1
0.15 GPM/SQ FT OVER 1500 SQ FT
FLOW HYDRANT 2
TEST HYDRANT
FLOW HYDRANT 1
PROJECT SITE
D
T C
H L I N
E M
A T
C H
L I N
E M
A T
C H
L I N
E
D
1. CONTRACTOR SHALL BE RESPONSIBLE FOR PROTECTING ALL
EQUIPMENT, FURNISHINGS. FIXTURES AND CONTENTS OF THE
SPACES FROM DAMAGE, DUST, WATER AND DEBRIS
ASSOCIATED WITH WORK. CONTRACTOR IS RESPONSIBLE FOR
DAILY CLEAN UP, INCLUDING REMOVAL OF ALL TRASH, DEBRIS
AND CONSTRUCTION MATERIALS ON A DAILY BASIS, AND
RESTORING TO PRE-CONSTRUCTION CONDITION AS WORK IS
COMPLETED.
2. PROVIDE SPRINKLER PIPING SUCH THAT THE ENTIRE
SPRINKLER SYSTEM WILL DRAIN BACK TO THE EXPRESS DRAIN
RISER.
3. MAINTAIN ALL REQUIRED STAIR EGRESS CLEARANCES FOR
ALL STANDPIPE AND SPRINKLER COMPONENTS IN THE STAIRS,
INCLUDING BUT NOT LIMITED TO THE VERTICAL STANDPIPE
RISER, VERTICAL DRAIN RISER, THE FIRE HOSE VALVES AND
THE SPRINKLER ZONE CONTROL ASSEMBLIES.
4. SEE ARCHITECTURAL DRAWINGS FOR ADDITIONAL WALL AND
CEILING INFORMATION. SEE LIFE SAFETY DRAWINGS FOR FIRE
RATED WALL LOCATIONS.
PROVIDE 4" STANDPIPE ISOLATION INDICATING CONTROL VALVE WITH
SUPERVISORY SWITCH.
PROVIDE 2
" EXPRESS MAIN DRAIN PIPED TO THE EXTERIOR.
TERMINATE DRAIN AT GALVANIZED 45-DEGREE ELBOW
APPROXIMATELY 6" ABOVE FINISHED GRADE. PROVIDE A CONCRETE
SPLASH BLOCK.
PROVIDE 2
" FIRE HOSE VALVE, CAP AND CHAIN. HOSE VALVE
LOCATION SHOWN ROTATED FOR CLARITY, LOCATE ADJACENT TO
WALL BELOW SPRINKLER ZONE CONTROL ASSEMBLY. PROVIDE A
SECOND 2
" FIRE HOSE VALVE IN STAIR FOR FORWARD FLOW
TESTING THE BACKFLOW PREVENTER. LABEL AS "FORWARD FLOW
TEST FOR BACKFLOW PREVENTER"
PROVIDE 4" SPRINKLER ZONE CONTROL ASSEMBLY FOR FIRST FLOOR
SPRINKLER ZONE, INCLUDING INDICATING CONTROL VALVE WITH
SUPERVISORY SWITCH, CHECK VALVE, WATER FLOW SWITCH,
PRESSURE GAUGE, COMBINATION INSPECTOR'S TEST AND DRAIN
INCLUDING RELIEF VALVE. RELIEF VALVE TO BE
-INCH IN SIZE AND
SET TO OPERATE AT 175 PSI. TEST AND DRAIN TO BE CONNECTED
TO COMMON DRAIN RISER.
PROVIDE CONCEALED SPRINKLER PROTECTION UNDERNEATH LOBBY
BRIDGE. COORDINATE WITH ARCHITECTURAL AND ELECTRICAL FOR
PIPE ROUTING. REFER TO DETAIL A ON SHEET SP5.2 FOR
INSTALLATION DETAIL.
PROVIDE A SUPERVISED CONTROL VALVE FOR ELEVATOR PIT
SPRINKLER.
PROVIDE DRY SIDEWALL SPRINKLER IN VESTIBULE. COORDINATE
WITH ARCHITECTURAL FOR SPRINKLER PIPE ROUTING WITHIN MENS
ROOM.
SUPPRESSION SHALL NOT BE PROVIDED IN VESTIBULE PER IBC
SECTION 903.3.1.1.1 EXCEPTION 4.
ROUTE 6" PIPE TO SERVE STANDPIPE RISER AND 2
" EXPRESS MAIN
DRAIN ABOVE DOOR IN STAIRWELL.
T C
H L I N
E M
A T
C H
L I N
E M
A T
C H
L I N
E
PROVIDE 2
" FIRE HOSE VALVE, CAP AND CHAIN. HOSE VALVE
LOCATION SHOWN ROTATED FOR CLARITY, LOCATE ADJACENT
TO WALL BELOW SPRINKLER ZONE CONTROL ASSEMBLY.
PROVIDE 4" SPRINKLER ZONE CONTROL ASSEMBLY FOR
SECOND FLOOR SPRINKLER ZONE, INCLUDING INDICATING
CONTROL VALVE WITH SUPERVISORY SWITCH, CHECK VALVE,
WATER FLOW SWITCH, PRESSURE GAUGE, COMBINATION
INSPECTOR'S TEST AND DRAIN INCLUDING RELIEF VALVE.
RELIEF VALVE TO BE
-INCH IN SIZE AND SET TO OPERATE AT
175 PSI.
SPRINKLER HEAD LAYOUT IN TWO STORY LOBBY IS SHOWN
FOR ARCHITECTURAL PURPOSES. LOCATIONS HAVE BEEN
COORDINATED WITH OBSTRUCTIONS IN THE CEILING. HEADS
SHALL BE LOCATED AS SYMMETRICALLY AS POSSIBLE. ALL
HEADS SHALL BE SPACED AND INSTALLED IN ACCORDANCE
WITH NFPA 13. DEVIATIONS FROM THE LAYOUT SHALL BE
COORDINATED WITH THE ARCHITECT.
1. CONTRACTOR SHALL BE RESPONSIBLE FOR PROTECTING ALL
EQUIPMENT, FURNISHINGS. FIXTURES AND CONTENTS OF THE
SPACES FROM DAMAGE, DUST, WATER AND DEBRIS
ASSOCIATED WITH WORK. CONTRACTOR IS RESPONSIBLE FOR
DAILY CLEAN UP, INCLUDING REMOVAL OF ALL TRASH, DEBRIS
AND CONSTRUCTION MATERIALS ON A DAILY BASIS, AND
RESTORING TO PRE-CONSTRUCTION CONDITION AS WORK IS
COMPLETED.
2. PROVIDE SPRINKLER PIPING SUCH THAT THE ENTIRE
SPRINKLER SYSTEM WILL DRAIN BACK TO THE EXPRESS DRAIN
RISER.
3. MAINTAIN ALL REQUIRED STAIR EGRESS CLEARANCES FOR
ALL STANDPIPE AND SPRINKLER COMPONENTS IN THE STAIRS,
INCLUDING BUT NOT LIMITED TO THE VERTICAL STANDPIPE
RISER, VERTICAL DRAIN RISER, THE FIRE HOSE VALVES AND
THE SPRINKLER ZONE CONTROL ASSEMBLIES.
4. SEE ARCHITECTURAL DRAWINGS FOR ADDITIONAL WALL AND
CEILING INFORMATION. SEE LIFE SAFETY DRAWINGS FOR FIRE
RATED WALL LOCATIONS.
PROVIDE 2
" FIRE HOSE VALVE, CAP AND CHAIN. HOSE VALVE
LOCATION SHOWN ROTATED FOR CLARITY, LOCATE ADJACENT
TO WALL BELOW SPRINKLER ZONE CONTROL ASSEMBLY.
PROVIDE 4" SPRINKLER ZONE CONTROL ASSEMBLY FOR THIRD
FLOOR SPRINKLER ZONE, INCLUDING INDICATING CONTROL
VALVE WITH SUPERVISORY SWITCH, CHECK VALVE, WATER
FLOW SWITCH, PRESSURE GAUGE, COMBINATION INSPECTOR'S
TEST AND DRAIN INCLUDING RELIEF VALVE. RELIEF VALVE TO
BE
-INCH IN SIZE AND SET TO OPERATE AT 175 PSI.
PROVIDE SUPERVISED CONTROL VALVE FOR TOP OF
ELEVATOR SHAFT SPRINKLER.
1. CONTRACTOR SHALL BE RESPONSIBLE FOR PROTECTING ALL
EQUIPMENT, FURNISHINGS. FIXTURES AND CONTENTS OF THE
SPACES FROM DAMAGE, DUST, WATER AND DEBRIS
ASSOCIATED WITH WORK. CONTRACTOR IS RESPONSIBLE FOR
DAILY CLEAN UP, INCLUDING REMOVAL OF ALL TRASH, DEBRIS
AND CONSTRUCTION MATERIALS ON A DAILY BASIS, AND
RESTORING TO PRE-CONSTRUCTION CONDITION AS WORK IS
COMPLETED.
2. PROVIDE SPRINKLER PIPING SUCH THAT THE ENTIRE
SPRINKLER SYSTEM WILL DRAIN BACK TO THE EXPRESS DRAIN
RISER.
3. MAINTAIN ALL REQUIRED STAIR EGRESS CLEARANCES FOR
ALL STANDPIPE AND SPRINKLER COMPONENTS IN THE STAIRS,
INCLUDING BUT NOT LIMITED TO THE VERTICAL STANDPIPE
RISER, VERTICAL DRAIN RISER, THE FIRE HOSE VALVES AND
THE SPRINKLER ZONE CONTROL ASSEMBLIES.
4. SEE ARCHITECTURAL DRAWINGS FOR ADDITIONAL WALL AND
PROVIDE TWO 2
" FIRE HOSE VALVE, CAP AND CHAIN. HOSE
VALVE LOCATION SHOWN ROTATED FOR CLARITY, LOCATE
ADJACENT TO WALL.
PROVIDE 4" SPRINKLER ZONE CONTROL ASSEMBLY FOR THE
PENTHOUSE SPRINKLER ZONE, INCLUDING INDICATING
CONTROL VALVE WITH SUPERVISORY SWITCH, CHECK VALVE,
WATER FLOW SWITCH, PRESSURE GAUGE, COMBINATION
INSPECTOR'S TEST AND DRAIN INCLUDING RELIEF VALVE.
RELIEF VALVE TO BE
-INCH IN SIZE AND SET TO OPERATE AT
175 PSI.
PROVIDE SUPERVISED CONTROL VALVE FOR ELEVATOR
MACHINE ROOM SPRINKLER(S).
1. CONTRACTOR SHALL BE RESPONSIBLE FOR PROTECTING ALL
EQUIPMENT, FURNISHINGS. FIXTURES AND CONTENTS OF THE
SPACES FROM DAMAGE, DUST, WATER AND DEBRIS
ASSOCIATED WITH WORK. CONTRACTOR IS RESPONSIBLE FOR
DAILY CLEAN UP, INCLUDING REMOVAL OF ALL TRASH, DEBRIS
AND CONSTRUCTION MATERIALS ON A DAILY BASIS, AND
RESTORING TO PRE-CONSTRUCTION CONDITION AS WORK IS
COMPLETED.
2. PROVIDE SPRINKLER PIPING SUCH THAT THE ENTIRE
SPRINKLER SYSTEM WILL DRAIN BACK TO THE EXPRESS DRAIN
RISER.
3. MAINTAIN ALL REQUIRED STAIR EGRESS CLEARANCES FOR
ALL STANDPIPE AND SPRINKLER COMPONENTS IN THE STAIRS,
INCLUDING BUT NOT LIMITED TO THE VERTICAL STANDPIPE
RISER, VERTICAL DRAIN RISER, THE FIRE HOSE VALVES AND
THE SPRINKLER ZONE CONTROL ASSEMBLIES.
4. SEE ARCHITECTURAL DRAWINGS FOR ADDITIONAL WALL AND
CEILING INFORMATION. SEE LIFE SAFETY DRAWINGS FOR FIRE
RATED WALL LOCATIONS.
5. SPRINKLERS AND SPRINKLER MAINS ARE SHOWN FOR
INFORMATION PURPOSES ONLY. CONTRACTOR SHALL
PROVIDE THEIR OWN SPRINKLER PIPING CONFIGURATION AND
SPRINKLER LAYOUT PER NFPA 13 TO MEET ALL HYDRAULIC
REQUIREMENTS.
BUILDING A PENTHOUSE
0.15
VARIES
62.6 487.0
65.8 487.0
T C
H L I N
E M
A T
C H
L I N
E
6" INCOMING FIRE SUPPRESSION WATER SUPPLY - REFER TO
PLUMBING DRAWINGS FOR ADDITIONAL INFORMATION.
PROVIDE 6" VERTICAL DOUBLE DETECTOR CHECK BACKFLOW
PREVENTER INCLUDING OS&Y INDICATING CONTROL VALVES
WITH SUPERVISORY SWITCHES. UTILIZE STANDPIPE FIRE
DEPARTMENT HOSE VALVE(S) IN STAIR TO PERFORM FORWARD
FLOW TEST OF BACKFLOW PREVENTER. PROVIDE WATER
FLOW SWITCH UPSTREAM OF THE BACKFLOW PREVENTER FOR
THE STANDPIPE SYSTEM.
PROVIDE 6" RISER FOR THE FEED TO THE FIRE DEPARTMENT
CONNECTION INCLUDING CHECK VALVE AND AUTOMATIC BALL
DRIP.
PROVIDE 2" DRY PIPE VALVE FOR THE LOADING DOCK DRY
SPRINKLER SYSTEM. ROUTE DRY VALVE DRAIN TO BUILDING
EXTERIOR. PROVIDE CONCRETE SPLASH BLOCK.
PROVIDE BRASS WALL MOUNTED FOUR WAY (6 x (4) 2
") FIRE
DEPARTMENT CONNECTION. PROVIDE CAST IRON SLEEVE AND
WEATHERPROOF SEAL AROUND THE ENTRY PIPE.
PROVIDE LOW WATER PRESSURE SENSOR SET TO THE
LOWEST PRESSURE REQUIRED TO OPERATE THE
HYDRAULICALLY MOST DEMANDING SYSTEM.
PROVIDE AN INSPECTOR'S TEST CONNECTION AT THE REMOTE
END OF THE DRY PIPE SYSTEM. PROVIDE CONCRETE SPLASH
BLOCK.
1. CONTRACTOR SHALL BE RESPONSIBLE FOR PROTECTING ALL
EQUIPMENT, FURNISHINGS. FIXTURES AND CONTENTS OF THE
SPACES FROM DAMAGE, DUST, WATER AND DEBRIS
ASSOCIATED WITH WORK. CONTRACTOR IS RESPONSIBLE FOR
DAILY CLEAN UP, INCLUDING REMOVAL OF ALL TRASH, DEBRIS
AND CONSTRUCTION MATERIALS ON A DAILY BASIS, AND
RESTORING TO PRE-CONSTRUCTION CONDITION AS WORK IS
COMPLETED.
2. PROVIDE SPRINKLER PIPING SUCH THAT THE ENTIRE
SPRINKLER SYSTEM WILL DRAIN BACK TO THE EXPRESS DRAIN
RISER.
3. MAINTAIN ALL REQUIRED STAIR EGRESS CLEARANCES FOR
ALL STANDPIPE AND SPRINKLER COMPONENTS IN THE STAIRS,
INCLUDING BUT NOT LIMITED TO THE VERTICAL STANDPIPE
RISER, VERTICAL DRAIN RISER, THE FIRE HOSE VALVES AND
THE SPRINKLER ZONE CONTROL ASSEMBLIES.
4. SEE ARCHITECTURAL DRAWINGS FOR ADDITIONAL WALL AND
CEILING INFORMATION. SEE LIFE SAFETY DRAWINGS FOR FIRE
RATED WALL LOCATIONS.
5. ALL DRY SPRINKLER SYSTEM PIPING SHALL BE SLOPED IN
ACCORDANCE WITH NFPA 13. BRANCHLINES SHALL BE
PITCHED AT LEAST 1/2" PER 10 FEET AND MAINS SHALL BE
PITCHED AT LEAST 1/4" PER 10 FEET. CONTRACTOR SHALL BE
RESPONSIBLE FOR ENSURING PROPER SLOPE THROUGHOUT
THE SYSTEM. PIPING SHALL DRAIN BACK TO THE DRY VALVE
WHERE POSSIBLE. AUXILIARY DRAINS SHALL BE PROVIDED IN
ANY AREAS WHERE DRAINAGE BACK TO THE VALVE IS NOT
POSSIBLE.
T C
H L I N
E M
A T
C H
L I N
E
MATCHLINE MATCHLINE
1. CONTRACTOR SHALL BE RESPONSIBLE FOR PROTECTING ALL
EQUIPMENT, FURNISHINGS. FIXTURES AND CONTENTS OF THE
SPACES FROM DAMAGE, DUST, WATER AND DEBRIS
ASSOCIATED WITH WORK. CONTRACTOR IS RESPONSIBLE FOR
DAILY CLEAN UP, INCLUDING REMOVAL OF ALL TRASH, DEBRIS
AND CONSTRUCTION MATERIALS ON A DAILY BASIS, AND
RESTORING TO PRE-CONSTRUCTION CONDITION AS WORK IS
COMPLETED.
2. PROVIDE SPRINKLER PIPING SUCH THAT THE ENTIRE
SPRINKLER SYSTEM WILL DRAIN BACK TO THE EXPRESS DRAIN
RISER.
3. MAINTAIN ALL REQUIRED STAIR EGRESS CLEARANCES FOR
ALL STANDPIPE AND SPRINKLER COMPONENTS IN THE STAIRS,
INCLUDING BUT NOT LIMITED TO THE VERTICAL STANDPIPE
RISER, VERTICAL DRAIN RISER, THE FIRE HOSE VALVES AND
THE SPRINKLER ZONE CONTROL ASSEMBLIES.
4. SEE ARCHITECTURAL DRAWINGS FOR ADDITIONAL WALL AND
CEILING INFORMATION. SEE LIFE SAFETY DRAWINGS FOR FIRE
RATED WALL LOCATIONS.
PROVIDE 4" STANDPIPE ISOLATION INDICATING CONTROL
VALVE WITH SUPERVISORY SWITCH.
1. CONTRACTOR SHALL BE RESPONSIBLE FOR PROTECTING ALL
EQUIPMENT, FURNISHINGS. FIXTURES AND CONTENTS OF THE
SPACES FROM DAMAGE, DUST, WATER AND DEBRIS
ASSOCIATED WITH WORK. CONTRACTOR IS RESPONSIBLE FOR
DAILY CLEAN UP, INCLUDING REMOVAL OF ALL TRASH, DEBRIS
AND CONSTRUCTION MATERIALS ON A DAILY BASIS, AND
RESTORING TO PRE-CONSTRUCTION CONDITION AS WORK IS
COMPLETED.
2. PROVIDE SPRINKLER PIPING SUCH THAT THE ENTIRE
SPRINKLER SYSTEM WILL DRAIN BACK TO THE EXPRESS DRAIN
RISER.
3. MAINTAIN ALL REQUIRED STAIR EGRESS CLEARANCES FOR
ALL STANDPIPE AND SPRINKLER COMPONENTS IN THE STAIRS,
INCLUDING BUT NOT LIMITED TO THE VERTICAL STANDPIPE
RISER, VERTICAL DRAIN RISER, THE FIRE HOSE VALVES AND
THE SPRINKLER ZONE CONTROL ASSEMBLIES.
4. SEE ARCHITECTURAL DRAWINGS FOR ADDITIONAL WALL AND
CEILING INFORMATION. SEE LIFE SAFETY DRAWINGS FOR FIRE
RATED WALL LOCATIONS.
COORDINATE FIRE HOSE VALVE LOCATION WITH
ARCHITECTURAL TO ALLOW NEEDED CLEARANCE AROUND
ROOF HATCH LADDER.
1. CONTRACTOR SHALL BE RESPONSIBLE FOR PROTECTING ALL
EQUIPMENT, FURNISHINGS. FIXTURES AND CONTENTS OF THE
SPACES FROM DAMAGE, DUST, WATER AND DEBRIS
ASSOCIATED WITH WORK. CONTRACTOR IS RESPONSIBLE FOR
DAILY CLEAN UP, INCLUDING REMOVAL OF ALL TRASH, DEBRIS
AND CONSTRUCTION MATERIALS ON A DAILY BASIS, AND
RESTORING TO PRE-CONSTRUCTION CONDITION AS WORK IS
COMPLETED.
2. PROVIDE SPRINKLER PIPING SUCH THAT THE ENTIRE
SPRINKLER SYSTEM WILL DRAIN BACK TO THE EXPRESS DRAIN
RISER.
3. MAINTAIN ALL REQUIRED STAIR EGRESS CLEARANCES FOR
ALL SPRINKLER COMPONENTS IN THE STAIRS, INCLUDING BUT
NOT LIMITED TO THE VERTICAL SPRINKLER RISER, VERTICAL
DRAIN RISER AND THE SPRINKLER ZONE CONTROL
ASSEMBLIES.
4. SEE ARCHITECTURAL DRAWINGS FOR ADDITIONAL WALL AND
CEILING INFORMATION. SEE LIFE SAFETY DRAWINGS FOR FIRE
RATED WALL LOCATIONS.
6" INCOMING FIRE SUPPRESSION WATER SUPPLY - REFER TO PLUMBING
DRAWINGS FOR ADDITIONAL INFORMATION.
PROVIDE 6" VERTICAL DOUBLE DETECTOR CHECK BACKFLOW PREVENTE
INCLUDING OS&Y INDICATING CONTROL VALVES WITH SUPERVISORY
SWITCHES.
PROVIDE 4" SPRINKLER RISER. INCLUDE (2) 2
" FIRE HOSE VALVES IN
STAIR FOR FORWARD FLOW TESTING THE BACKFLOW PREVENTE. LABEL
AS "FORWARD FLOW TEST VALVES FOR BACKFLOW PREVENTER
PROVIDE 4" RISER FOR THE FEED TO THE FIRE DEPARTMENT
CONNECTION INCLUDING CHECK VALVE AND AUTOMATIC BALL DRIP.
PROVIDE LOW WATER PRESSURE SENSOR SET TO THE LOWEST
PRESSURE REQUIRED TO OPERATE THE HYDRAULICALLY MOST
DEMANDING SYSTEM.
PROVIDE BRASS WALL MOUNTED TWO WAY (4 x (2) 2
") FIRE
DEPARTMENT CONNECTION. PROVIDE CAST IRON SLEEVE AND
WEATHERPROOF SEAL AROUND THE ENTRY PIPE.
PROVIDE 2
" EXPRESS MAIN DRAIN PIPED TO THE EXTERIOR. TERMINATE
DRAIN AT GALVANIZED 45-DEGREE ELBOW APPROXIMATELY 6" ABOVE
FINISHED GRADE. PROVIDE A CONCRETE SPLASH BLOCK.
PROVIDE 4" SPRINKLER ZONE CONTROL ASSEMBLY FOR FIRST FLOOR
SPRINKLER ZONE, INCLUDING INDICATING CONTROL VALVE WITH
SUPERVISORY SWITCH, CHECK VALVE, WATER FLOW SWITCH, PRESSURE
GAUGE COMBINATION INSPECTOR'S TEST AND DRAIN INCLUDING RELIEF
VALVE. RELIEF VALVE TO BE
-INCH IN SIZE AND SET TO OPERATE AT 175
PSI. TEST AND DRAIN TO BE CONNECTED TO COMMON DRAIN RISER.
PROVIDE SUPERVISED CONTROL VALVE FOR ELEVATOR PIT SPRINKLER.
B
PROVIDE 4" SPRINKLER ZONE CONTROL ASSEMBLY FOR FIRST
FLOOR SPRINKLER ZONE, INCLUDING INDICATING CONTROL
VALVE WITH SUPERVISORY SWITCH, CHECK VALVE, WATER
FLOW SWITCH, PRESSURE GAUGE, COMBINATION INSPECTOR'S
TEST AND DRAIN INCLUDING RELIEF VALVE. RELIEF VALVE TO
BE
-INCH IN SIZE AND SET TO OPERATE AT 175 PSI. TEST AND
DRAIN TO BE CONNECTED TO COMMON DRAIN RISER.
PROVIDE SUPERVISED CONTROL VALVE FOR TOP OF
ELEVATOR SHAFT SPRINKLER.
1. CONTRACTOR SHALL BE RESPONSIBLE FOR PROTECTING ALL
EQUIPMENT, FURNISHINGS. FIXTURES AND CONTENTS OF THE
SPACES FROM DAMAGE, DUST, WATER AND DEBRIS
ASSOCIATED WITH WORK. CONTRACTOR IS RESPONSIBLE FOR
DAILY CLEAN UP, INCLUDING REMOVAL OF ALL TRASH, DEBRIS
AND CONSTRUCTION MATERIALS ON A DAILY BASIS, AND
RESTORING TO PRE-CONSTRUCTION CONDITION AS WORK IS
COMPLETED.
2. PROVIDE SPRINKLER PIPING SUCH THAT THE ENTIRE
SPRINKLER SYSTEM WILL DRAIN BACK TO THE EXPRESS DRAIN
RISER.
3. MAINTAIN ALL REQUIRED STAIR EGRESS CLEARANCES FOR
ALL SPRINKLER COMPONENTS IN THE STAIRS, INCLUDING BUT
NOT LIMITED TO THE VERTICAL SPRINKLER RISER, VERTICAL
DRAIN RISER AND THE SPRINKLER ZONE CONTROL
ASSEMBLIES.
4. SEE ARCHITECTURAL DRAWINGS FOR ADDITIONAL WALL AND
PROVIDE 4" SPRINKLER ZONE CONTROL ASSEMBLY FOR FIRST
FLOOR SPRINKLER ZONE, INCLUDING INDICATING CONTROL
VALVE WITH SUPERVISORY SWITCH, CHECK VALVE, WATER
FLOW SWITCH, PRESSURE GAUGE, COMBINATION INSPECTOR'S
TEST AND DRAIN INCLUDING RELIEF VALVE. RELIEF VALVE TO
BE
-INCH IN SIZE AND SET TO OPERATE AT 175 PSI. TEST AND
DRAIN TO BE CONNECTED TO COMMON DRAIN RISER.
PROVIDE SUPERVISED CONTROL VALVE FOR ELEVATOR
MACHINE ROOM SPRINKLER(S).
1. CONTRACTOR SHALL BE RESPONSIBLE FOR PROTECTING ALL
EQUIPMENT, FURNISHINGS. FIXTURES AND CONTENTS OF THE
SPACES FROM DAMAGE, DUST, WATER AND DEBRIS
ASSOCIATED WITH WORK. CONTRACTOR IS RESPONSIBLE FOR
DAILY CLEAN UP, INCLUDING REMOVAL OF ALL TRASH, DEBRIS
AND CONSTRUCTION MATERIALS ON A DAILY BASIS, AND
RESTORING TO PRE-CONSTRUCTION CONDITION AS WORK IS
COMPLETED.
2. PROVIDE SPRINKLER PIPING SUCH THAT THE ENTIRE
SPRINKLER SYSTEM WILL DRAIN BACK TO THE EXPRESS DRAIN
RISER.
3. MAINTAIN ALL REQUIRED STAIR EGRESS CLEARANCES FOR
ALL SPRINKLER COMPONENTS IN THE STAIRS, INCLUDING BUT
NOT LIMITED TO THE VERTICAL SPRINKLER RISER, VERTICAL
DRAIN RISER AND THE SPRINKLER ZONE CONTROL
ASSEMBLIES.
4. SEE ARCHITECTURAL DRAWINGS FOR ADDITIONAL WALL AND
CEILING INFORMATION. SEE LIFE SAFETY DRAWINGS FOR FIRE
RATED WALL LOCATIONS.
5. SPRINKLERS AND SPRINKLER MAINS ARE SHOWN FOR
INFORMATION PURPOSES ONLY. CONTRACTOR SHALL
PROVIDE THEIR OWN SPRINKLER PIPING CONFIGURATION AND
SPRINKLER LAYOUT PER NFPA 13 TO MEET ALL HYDRAULIC
REQUIREMENTS.
BUILDING D PENTHOUSE
0.15
VARIES
55.5 465.0
65.7 465.0
PROVIDE 6" VERTICAL DOUBLE DETECTOR CHECK BACKFLOW
PREVENTER INCLUDING OS&Y INDICATING CONTROL VALVES
WITH SUPERVISORY SWITCHES.
PROVIDE FEED TO THE FIRE DEPARTMENT CONNECTION
INCLUDING CHECK VALVE AND AUTOMATIC BALL DRIP.
PROVIDE STANDPIPE RISER INDICATING CONTROL VALVE WITH
SUPERVISORY SWITCH.
PROVIDE 2
" FIRE HOSE VALVE, CAP AND CHAIN.
PROVIDE 2
" FIRE HOSE VALVE, CAP AND CHAIN. PROVIDE A
SECOND 2
" FIRE HOSE VALVE IN STAIR FOR FORWARD FLOW
TESTING THE BACKFLOW PREVENTER. LABEL AS "FORWARD
FLOW TEST FOR BACKFLOW PREVENTER"
PROVIDE 4" SPRINKLER ZONE CONTROL ASSEMBLY FOR
SPRINKLER ZONE, INCLUDING INDICATING CONTROL VALVE
WITH SUPERVISORY SWITCH, CHECK VALVE, WATER FLOW
SWITCH, PRESSURE GAUGE, COMBINATION INSPECTOR'S TEST
AND DRAIN INCLUDING RELIEF VALVE.
PROVIDE 2" DRY PIPE VALVE FOR THE LOADING DOCK DRY
SPRINKLER SYSTEM.
1. RISER DIAGRAM IS SCHEMATIC IN NATURE, REFER TO
SPRINKLER PLANS FOR EQUIPMENT LOCATIONS AND
QUANTITIES. NOT ALL SPRINKLER EQUIPMENT IS SHOWN ON
RISER DIAGRAM.
04/25/2016
1. DRAWINGS, SPECIFICATIONS, ADDENDUMS, SKETCHES AND OTHER DOCUMENTATION
COMPRISE THE PROJECT CONTRACT DOCUMENTS AND MUST BE USED IN
COMBINATION, TO FACILITATE THE REMOVAL OF THE EXISTING TELECOMMUNICATIONS
SYSTEM PER THE DRAWINGS AND SPECIFICATIONS.
2. THE DRAWINGS INDICATE THE GENERAL PROPOSED LOCATION OF EQUIPMENT, CABLE
PATHWAYS AND OUTLETS. LOCATION OF EQUIPMENT AND OUTLETS AND OTHER
SUPPORTING ITEMS TO BE COORDINATED WITH ALL OTHER EXISTING UTILITIES AND
TRADES.
3. THE TERM "CONTRACTOR" MEANS CONTRACTOR RESPONSIBLE FOR ALL WORK
DEFINED IN THE DRAWINGS AND SPECIFICATIONS.
4. THE TERM "REMOVE" MEANS DISCONNECT ALL COMPONENTS OF THE LOW VOLTAGE
COMMUNICATIONS SYSTEM AND REMOVE FROM SITE.
5. COORDINATE ALL DRAWINGS AND SPECIFICATIONS PRIOR TO COMMENCING WORK.
ANY CONFLICT BETWEEN DRAWINGS AND SPECIFICATIONS SHALL BE BROUGHT TO THE
COR'S ATTENTION IMMEDIATELY. THE CONTRACTOR SHALL NOT PROCEED WITH ANY
WORK EXCEPT AT THEIR OWN RISK UNTIL CLARIFICATION OF CONFLICTS ARE ISSUED
TO THE CONTRACTOR BY THE COR.
6. FIELD VERIFY AND COORDINATE ALL DEVICE LOCATIONS AND POWER REQUIREMENTS.
WHERE CONFLICTS OCCUR, COORDINATE AND VERIFY FINAL LOCATIONS WITH THE
COR PRIOR TO INSTALLATION.
7. PROVIDE COORDINATION AND VERIFICATION OF ALL CONDITIONS INCLUDING
EQUIPMENT AND DEVICES INSTALLED BY OTHER TRADES, THE WORK OF THE
CONTRACTOR AND SUBCONTRACTORS.
8. DETAIL REFERENCES ARE NOT NECESSARILY NUMBERED INCREMENTALLY. A GAP IN
NUMBERING DOES NOT INDICATE MISSING INFORMATION. DETAIL NAMES AND
NUMBERS ARE SPECIFIC TO THIS DESIGN PACKAGE AND DO NOT CORRESPOND TO
OTHER PUBLISHED DOCUMENTS.
9. ALL EXISTING CONDUIT SHALL BE REMOVED UNLESS NOTED OTHERWISE.
AFF
AV
BCT
C
CAT
CATV
CM
COR
CT
EF
EMI
EMT
ER
FO
IMT
ITS
LAN
MAX
MIN
MISC
MM
MTD
NTS
OC
OPE
OSP
PC
PP
PR
RM
RMU
SM
SP
STP
TBB
TBD
TE
TGB
TMGB
TR
TYP
UON
UPS
UTP
VAC
VDC
VP
WM
WOA
WPE
ABOVE FINISHED FLOOR
AUDIO VISUAL
BONDING CONDUCTOR FOR TELECOMMUNICATIONS
CONDUIT
CATEGORY
COMMUNITY ANTENNA TELEVISION
CEILING MOUNTED
CONTRACTING OFFICER REPRESENTATIVE
CABLE TRAY
ENTRANCE FACILITY
ELECTRICAL MAGNETIC INTERFERANCE
ELECTRICAL METALLIC TUBING
EQUIPMENT ROOM
FIBER OPTIC
INTERMEDIATE METALLIC TUBING
INFORMATION TECHNOLOGY SYSTEMS
LOCAL AREA NETWORK
MAXIMUM
MINIMUM
MISCELLANEOUS
MULTIMODE
MOUNTED
NOT TO SCALE
ON CENTER
OWNER PROVIDED EQUIPMENT
OUTSIDE PLANT
PERSONAL COMPUTER
PATCH PANEL
PAIR
ROOM
RACK MOUNTING UNIT (1.75")
SINGLEMODE
SERVICE PROVIDER
SHIELDED TWISTED PAIR
TELECOMMUNICATIONS BONDING BACKBONE
TO BE DETERMINED
TELECOMMUNICATION ENCLOSURE
TELECOMMUNICATIONS GROUNDING BUSBAR
TELECOMMUNICATIONS MAIN GROUNDING BUSBAR
TELECOMMUNICATIONS ROOM
TYPICAL
UNLESS OTHERWISE NOTED
UNINTERRUPTED POWER SUPPLY
UNSHIELDED TWISTED PAIR
VOLTS ALTERNATING CURRENT
VOLTS DIRECT CURRENT
VANDAL PROOF
WALL MOUNTED
WORK AREA OUTLET
WEATHER PROOF ENCLOSURE
EXISTING TO REMAIN LINE-TYPE
EXISTING TO BE REMOVED LINE-TYPE
EXISTING WALL MOUNTED DROP SET TO BE REMOVED
CATV DISH ANTENNA
KEYNOTE TAG
DETAIL NUMBER
DETAIL IDENTIFICATION BUBBLE
SHEET DETAIL IS SHOWN ON
SHEET DETAIL IS TAKEN FROM
ELEVATION NUMBER
ELEVATION IDENTIFICATION BUBBLE
SHEET ELEVATION IS SHOWN ON
SHEET ELEVATION IS TAKEN FROM
T C
H L I N
E M
A T
C H
L I N
E M
A T
C H
L I N
E
REMOVE ALL HORIZONTAL WORK AREA OUTLET CABLING (i.e. 4-PAIR
UTP CAT-3 CABLE, JACKS, BACK BOXES, AND
" SUPPORT CONDUIT
ALONG WITH SUPPORT PATHWAYS SUCH AS CEILING MOUNTED
J-HOOKs, TO TR-138G. TO INCLUDE RELATED SUPPORT HARDWARE
INSIDE TR SUCH AS CROSS CONNECT WIRES, PATCH CORDS, PATCH
PANELS, AND 66 AND/OR 110 CONNECTING BLOCKS. REMOVE ALL
ABANDONED 25-PAIR COPPER UTP CABLES THAT ARE CUT NEAR THE
TR's CEILING.
ALL OUTSIDE PLANT COPPER AND FIBER CABLE ARE TO REMAIN,
(TWO-100-PAIR, AND ONE 12-STRAND FIBER). PROTECT IN PLACE
DURING RENOVATION UNTIL NEW CONSTRUCTION IS COMPLETE.
SEE NEW WORK SHEET SET FOR INFORMATION ABOUT OSP CABLING
SYSTEM.
TYP
1. REFERENCE TD0.0 FOR SYMBOLS AND ABBREVIATIONS.
TYP
TYP
TELECOM ROOM
TR-138G
T C
H L I N
E M
A T
C H
L I N
E
EXISTING TR SHALL BE REMOVED.
REMOVE ALL HORIZONTAL WORK AREA OUTLET CABLING (i.e.
4-PAIR UTP CAT-3 CABLE, JACKS, BACK BOXES, AND
SUPPORT CONDUIT ALONG WITH SUPPORT PATHWAYS SUCH
AS CEILING MOUNTED J-HOOKs, TO TR-240B. TO INCLUDE
RELATED SUPPORT HARDWARE INSIDE TR SUCH AS CROSS
CONNECT WIRES, PATCH CORDS, PATCH PANELS, AND 66
AND/OR 110 CONNECTING BLOCKS. REMOVE ALL ABANDONED
25-PAIR COPPER UTP CABLES THAT ARE CUT NEAR THE TR's
CEILING.
EXISTING VERIZON DEMARK ROOM. FUTURE LOCATION FOR
NEW SERVER ROOM. ALL OUTSIDE PLANT COPPER AND FIBER
CABLE ARE TO REMAIN, PROTECT IN PLACE DURING
RENOVATION. SEE NEW WORK SHEET SET FOR INFORMATION
ABOUT NEW SERVER ROOM AND NEW DEMARK LAYOUT.
1. REFERENCE TD0.0 FOR SYMBOLS AND ABBREVIATIONS.
TYP
TYP
1. REFERENCE TD0.0 FOR SYMBOLS AND ABBREVIATIONS.
EXISTING TR SHALL BE REMOVED.
REMOVE ALL HORIZONTAL WORK AREA OUTLET CABLING (i.e.
4-PAIR UTP CAT-3 CABLE, JACKS, BACK BOXES, AND
SUPPORT CONDUIT ALONG WITH SUPPORT PATHWAYS SUCH
AS CEILING MOUNTED J-HOOKs, TO TR-342A. TO INCLUDE
RELATED SUPPORT HARDWARE INSIDE TR SUCH AS CROSS
CONNECT WIRES, PATCH CORDS, PATCH PANELS, AND 66
AND/OR 110 CONNECTING BLOCKS. REMOVE ALL ABANDONED
25-PAIR COPPER UTP CABLES THAT ARE CUT NEAR THE TR's
CEILING.
TYP
EXISTING CATV DISH ANTENNA. OWNED AND MAINTAINED BY
OTHERS SHALL REMAIN IN PLACE.
REMOVE OLD CABLE TV CABLE THAT IS RESTING ON THE ROOF.
REMOVE OLD CONNECTORS AND ASSOCIATED SUPPORT
HARDWARE.
1. REFERENCE TD0.0 FOR SYMBOLS AND ABBREVIATIONS.
2. REMOVE ALL HORIZONTAL WORK AREA OUTLET CABLING AND
PATHWAYS TO TR 342A. TO INCLUDE RELATED CROSS
CONNECT WIRES, J-HOOK PATHWAYS, PATCH CORDS, PATCH
PANELS AND CONNECTING BLOCKS.
T C
H L I N
E M
A T
C H
L I N
E
M A
T C
H L I N
E M
A T
C H
L I N
E
1. REFERENCE TD0.0 FOR SYMBOLS AND ABBREVIATIONS.
TYP
REMOVE ALL HORIZONTAL WORK AREA OUTLET CABLING (i.e. 4-PAIR
UTP CAT-3 CABLE, JACKS, BACK BOXES, AND
" SUPPORT CONDUIT
ALONG WITH SUPPORT PATHWAYS SUCH AS CEILING MOUNTED
J-HOOKs, TO WALL MOUNT PATCH PANELS IN CLASS ROOM 182. TO
INCLUDE RELATED SUPPORT HARDWARE INSIDE TR SUCH AS CROSS
CONNECT WIRES, PATCH CORDS, PATCH PANELS, AND 66 AND/OR
110 CONNECTING BLOCKS. REMOVE ALL ABANDONED 25-PAIR
COPPER UTP CABLES THAT ARE CUT NEAR THE TR's CEILING.
WALL MOUNTED COPPER PATCH PANEL AND WALL MOUNTED FIBER
BOX. REMOVE ALL COPPER AND FIBER CABLING AND HARDWARE.
EXISTING CATV DISH ANTENNA OWNED AND MAINTAINED BY OTHERS
SHALL REMAIN IN PLACE.
T C
H L I N
E M
A T
C H
L I N
E
MATCHLINE MATCHLINE
TYP
REMOVE ALL HORIZONTAL WORK AREA OUTLET CABLING (i.e.
4-PAIR UTP CAT-3 CABLE, JACKS, BACK BOXES, AND
SUPPORT CONDUIT ALONG WITH SUPPORT PATHWAYS SUCH
AS CEILING MOUNTED J-HOOKs, TO TR-119. TO INCLUDE
RELATED SUPPORT HARDWARE INSIDE TR SUCH AS CROSS
CONNECT WIRES, PATCH CORDS, PATCH PANELS, AND 66
AND/OR 110 CONNECTING BLOCKS. REMOVE ALL ABANDONED
25-PAIR COPPER UTP CABLES THAT ARE CUT NEAR THE TR's
CEILING.
EXISTING MODULAR FURNITURE IS NOT SHOWN. REMOVE ALL
CABLING INFRASTRUCTURE FROM MODULAR FURNITURE
SYSTEM.
1. REFERENCE TD0.0 FOR SYMBOLS AND ABBREVIATIONS.
TYP
TYP
TYP
A
T C
H L I N
E M
A T
C H
L I N
E
1. REFERENCE TD0.0 FOR SYMBOLS AND ABBREVIATIONS.
TYP
REMOVE ALL HORIZONTAL WORK AREA OUTLET CABLING (i.e.
4-PAIR UTP CAT-3 CABLE,…