Drawings_Volume_I_pgs_1-174.pdf

PDF 35 MB Posted

Attached to
Construction Services for Repair/Alteration of Office Building - Solicitation 140P2019R0068
Solicitation number
140P2019R0068
Issued by

About this file

B08 Solic Sec J Attachment 2 - NCRO Drawing Package (Part 2 - Vol 1_pgs 1 - 174 Drawings)

View the file

Other files

File Type Posted
B09_Amendment0010_SF30_140P2019R0068.pdf PDF
Door_Sched_NPS_A6.23.pdf PDF
B09_Solit_General_References_Form.pdf PDF
B09_Solit_Hazardous_Materials.pdf PDF
Door_Sched_NPS_A6.20.pdf PDF
NCRO_251176_-_Prebid_RFI_Summary_190626.1_Amend_0010_Responses.pdf PDF
Door_Sched_NPS_A6.22.pdf PDF
Door_Sched_NPS_A6.24.pdf PDF
Door_Sched_NPS_A6.21.pdf PDF
B08_Solit_PSP_Vol_II_Equals.pdf PDF
B08__Amendment_0009_140P2019R0068_FINAL.pdf PDF
B09_Amendment0008_Form_SF30_.pdf PDF
140P2019R0068_-_Interested_Parties_List.pdf PDF
B09_Amendment0004_Form_SF30_.pdf PDF
B09_Amendment0003_Form_SF30.pdf PDF
B09_Amendment0002_Form_SF30_.pdf PDF
B09_Amendment0001_Form_SF30.pdf PDF
B09_Amendment0006_Form_SF30.pdf PDF
B09_Amendment0007_Form_SF30_and_attachment_Released_6-21-19.pdf PDF
B09_Amendment0005_Form_SF30.pdf PDF
B08_Solicitation_Form_1442_-_140P2019R0068_Revised_6-20-2019_Amendment0004.pdf PDF
B11_Pre-Bid_Proposal_Conference_Site_Visit__Sign-in_Sheet.pdf PDF
B08_Solicitation_Form_1442_-_140P2019R0068_Revised_6-7-2019_Amendment0003.pdf PDF
B11_NCRO201409_PreBid_Agenda_Revised_Amendment0003.pdf PDF
B11_NCRO201409_PreBid_Agenda_Revised.pdf PDF
B11_NCRO201409_PreBid_Agenda.pdf PDF
B08_Solicitation_Form_1442_-_140P2019R0068.pdf PDF
B08_Solic_Sec_J_Attachm_3_-PSP_Vol_II_SubKPlanForm_NCRO201409.pdf PDF
Drawings_Volume_I_pgs_175-349.pdf PDF
B08_Solic_Sec_J_Attachm_4_-_DC190002_5-22-19_Wage_Determination.pdf PDF
B08_Solic_Sec_J_Attachm_6_-_PPQ_Form.pdf PDF
Drawings_Volume_II.pdf PDF
Drawings_-_Roof.pdf PDF
Specification_Package_Volume_I_and_Volume_II.pdf PDF
B08_Solic_Sec_J__Attach_1_-_NCRO_Specification_Package.pdf PDF
B08_Solic_Sec_J_Attachm_5_-_Project_Experience_Form.pdf PDF
Show all 36

On GovTribe

Work with this file

  • Download the original file
  • Contacts named in this file
  • Similar government files
  • Ask GovTribe AI about this file

Text version

OR

OR

OR

S

ON

OFF

T

24X48

T T

FD

FD

CLOSET

SC

M

2'0 4' 8'

Level 1

0' - 0"

Level 2

16' - 0"

Level 1

0' - 0"

Level 2

16' - 0"

Level 1

0' - 0"

Level 2

16' - 0"

Level 1

0' - 0"

Level 2

16' - 0"

Level 1

0' - 0"

Level 2

16' - 0"

M4.3

M4.3

M4.3

RHVAV-3

500 CFM

RHVAV-1

225 CFM

RHVAV-2

350 CFM

RHVAV-1

225 CFM

RHVAV-4

650 CFM

RHVAV-3

500 CFM

RHVAV-5

900 CFM

RHVAV-1

225 CFM

RHVAV-5

900 CFM

RHVAV-1

225 CFM

RHVAV-1

225 CFM

RHVAV-4

650 CFM

RHVAV-2

350 CFM

RHVAV-4

650 CFM

RHVAV-2

350 CFM

RHVAV-5

900 CFM

RHVAV-2

350 CFM

RHVAV-4

650 CFM

RHVAV-6

1050 CFM

RHVAV-2

350 CFM

RHVAV-6

1050 CFM

RHVAV-2

350 CFM

RHVAV-4

650 CFM

RHVAV-1

225 CFM

RHVAV-2

350 CFM

RHVAV-1

225 CFM

RHVAV-5

900 CFM

RHVAV-6

1050 CFM

RHVAV-5

900 CFM

RHVAV-4

650 CFM

RHVAV-2

350 CFM

RHVAV-1

225 CFM

RHVAV-5

900 CFM

RHVAV-1

255 CFM

RHVAV-1

225 CFM

RHVAV-4

650 CFM

RHVAV-3

500 CFM

RHVAV-1

225 CFM

RHVAV-1

225 CFM

RHVAV-6

1050 CFM

RHVAV-1

225 CFM

RHVAV-5

900 CFM

RHVAV-1

225 CFM

RHVAV-1

225 CFM

RHVAV-4

650 CFM

RHVAV-1

225 CFM

RHVAV-5

900 CFM

RHVAV-1

225 CFM

RHVAV-3

500 CFM

RHVAV-2

350 CFM

RHVAV-5

900 CFM

RHVAV-4

650 CFM

RHVAV-2

350 CFM

RHVAV-5

900 CFM

RHVAV-2

350 CFM

RHVAV-4

650 CFM

RHVAV-5

900 CFM

RHVAV-3

500 CFM

RHVAV-2

350 CFM

RHVAV-5

900 CFM

RHVAV-4

650 CFM

RHVAV-5

900 CFM

RHVAV-1

255 CFM

RHVAV-1

255 CFM

RHVAV-2

350 CFM

RHVAV-2

350 CFM

RHVAV-5

900 CFM

RHVAV-2

350 CFM

RHVAV-1

225 CFM

RHVAV-3

500 CFM

RHVAV-5

900 CFM

RHVAV-7

1400 CFM

RHVAV-6

1050 CFM

RHVAV-4

650 CFM

RHVAV-3

500 CFM

RHVAV-6

1050 CFM

RHVAV-5

900 CFM

RHVAV-5

900 CFM

RHVAV-5

900 CFM

RHVAV-7

1400 CFM

RHVAV-5

900 CFM

RHVAV-5

900 CFM

RHVAV-5

900 CFM

RHVAV-2

350 CFM

RHVAV-3

500 CFM

RHVAV-5

900 CFM

RHVAV-6

1050 CFM

RHVAV-5

900 CFM

RHVAV-5

900 CFM

RHVAV-5

900 CFM

RHVAV-3

500 CFM

RHVAV-5

900 CFM

RHVAV-5

900 CFM

RHVAV-3

500 CFM

RHVAV-4

650 CFM

RHVAV-4

650 CFM

RHVAV-2

350 CFM

RHVAV-3

500 CFM

RHVAV-5

900 CFM

RHVAV-5

900 CFM

RHVAV-5

900 CFM

RHVAV-3

500 CFM

RHVAV-5

900 CFM

RHVAV-5

900 CFM

RHVAV-6

1050 CFM

RHVAV-3

500 CFM

RHVAV-5

900 CFM

RHVAV-1

225 CFM

RHVAV-6

1050 CFM

RHVAV-3

500 CFM

RHVAV-5

900 CFM

RHVAV-7

1400 CFM

RHVAV-5

900 CFM

RHVAV-4

650 CFM

RHVAV-2

350 CFM

RHVAV-5

900 CFM

RHVAV-2

350 CFM

RHVAV-3

500 CFM

RHVAV-4

650 CFM

RHVAV-2

350 CFM

RHVAV-2

350 CFM

RHVAV-3

500 CFM

RHVAV-2

350 CFM

RHVAV-6

1050 CFM

RHVAV-3

500 CFM

RHVAV-1

225 CFM

RHVAV-6

1050 CFM

RHVAV-6

1050 CFM

RHVAV-5

900 CFM

RHVAV-3

500 CFM

RHVAV-3

500 CFM

W W

PIPE

SIZE

TYPE 5 HANGER

SUPPORT SPACING (FT)

SCH 40 SCH 80

1-1/4 4 4

1-1/2 4 4.5

2 4 5

2-1/2 5 5.5

3 5 5.5

4 5.5 6.5

5 7 8

6 7.5 9

HANGER ROD SCHEDULE

PIPE SIZE ROD SIZE PIPE SIZE ROD SIZE

UP TO 2" 3/8" DIA. 4" THRU 5" 5/8" DIA.

2 1/2" THRU 3" 1/2" DIA. 6" THRU 12" 7/8" DIA.

CLEVIS HANGERCLEVIS HANGER

PIPE STAND SIZES

PIPE SIZE

PIPE STAND

DIA SIZE

(SCH 40)

PIPE

STAND

HEIGHT

BASE PLATE

SIZE

8"Ø AND

SMALLER

2" 2" 6"x6"x3/8"

0'-2 1/2" "

3" 14" & UP "

10'Ø TO

16"Ø

2-1/2" 6" 10"x10"x1/2"

3" 10" "

4" 14" & UP "

MAXIMUM ALLOWABLE HANGER

LOAD

STRAPS LBS RODS LBS

2-1"x22 GA 520 2-1/4" Ø 540

2-1"x20 GA 640 2-3/8" Ø 1360

2-1"x18 GA 840 2-1/2" Ø 2500

2-1"x16 GA 1400 2-5/8" Ø 4000

MAXIMUM ALLOWABLE

TRAPEZE ANGLE LOAD

L 2"X2"X1/4" 2-1/2"x2-1/2"x1/4"

36" 1200 LBS 1940 LBS

48" 1160 LBS 1900 LBS

60" 1060 LBS 1800 LBS

72" 900 LBS 1640 LBS

84" 660 LBS 1400 LBS

96" 320 LBS 1060 LBS

SINGLE RECTANGULAR DUCT

MULTIPLE DUCT RUNS ON TRAPEZE HANGERS

ROUND DUCT

MEDIUM AND HIGH PRESSURE DUCTWORK (2" WG TO 10" WG)

LEGENDS:

METER

WATER

AIR HANDLING UNIT (AHU-1)AIR HANDLING UNIT (AHU-2)AIR HANDLING UNIT (AHU-3)

E H

TO BAS VIA

BACNET

BOILER

CONTROLLER

TO BAS VIA

BACNET

DDC CONTROLLER INPUT/OUTPUT SUMMARY

EXHAUST FAN (EF -1, 2, 3 & 4) CONTROL DIAGRAM

EXHAUST FAN (EF -5, 6, 7 & 8) CONTROL DIAGRAM

BOILER ROOM VENTILATION CONTROL DIAGRAM

B A

C N

E T

M S

/T P

S P

A C

E

TE

M P

E R

A

TU

R E

S E

N S

O R

S U

P P

LY

F

A N

S

TA

R T/

S

TO

P

E

LE

C

TR

IC

H

E A

T C

O N

TA

C

TO

R

S U

P P

LY

F

A N

S

TA

R T/

S

TO

P

S U

P P

LY

F

A N

S

TA

TU

S

CB AI DO DO DO DI

1. THE SCOPE OF THIS PROJECT INCLUDES PROVIDING A COMPLETELY SUPERVISED,

MULTIPLEXED, INTELLIGENT, ANALOG, ADDRESSABLE FIRE DETECTION AND ALARM

SYSTEM IN THE NATIONAL CAPITAL REGION (NCR) HEADQUARTERS (WINGS A, B, AND

C) AND UNITED STATES PARK POLICE HEADQUARTERS (USPP) BUILDING (WING D) AS

SHOWN ON THE DRAWINGS AND ACCOMPANYING SPECIFICATIONS. THE SYSTEM

SHALL INCLUDE ALL NEW WIRING, RACEWAYS, PULL BOXES, TERMINAL CABINETS,

OUTLET AND MOUNTING BOXES, CONTROL EQUIPMENT, ALARM AND SUPERVISORY

SIGNALS, INITIATING DEVICES, ALARM NOTIFICATION APPLIANCES, NOTIFICATION

APPLIANCE BOOSTER PANELS, INTERFACE EQUIPMENT, AND ALL OTHER

ACCESSORIES AND MISCELLANEOUS ITEMS INCLUDING SOFTWARE, SYSTEM

PROGRAMMING, TESTING AND CONSTRUCTION PERMITS REQUIRED FOR A

COMPLETE OPERATING SYSTEM EVEN THOUGH EACH ITEM IS NOT SPECIFICALLY

MENTIONED OR DESCRIBED. ALL EQUIPMENT PROVIDED BY THE CONTRACTOR

SHALL BE UL LISTED FOR THE INTENDED PURPOSE.

2. FIRE ALARM SYSTEM IN WINGS A, B, AND C SHALL BE PROVIDED WITH A VOICE FIRE

ALARM SYSTEM BASED ON NPS-NCR FIRE PROTECTION SYSTEM REQUIREMENTS

WHICH REQUIRES A VOICE SYSTEM FOR ANY BUILDING WITH AN OCCUPANT LOAD

GREATER THAN 300 OCCUPANTS. WING D WILL BE PROVIDED WITH A HORN SYSTEM.

BOTH SYSTEMS WILL BE FULLY ADDRESSABLE.

3. FIRE ALARM SYSTEM IN WINGS A, B, AND C SHALL NOT BE REMOVED UNTIL NEW

SYSTEM IS FULLY TESTED AND ACCEPTED. ALL NEW APPLIANCES AND CIRCUITS

SHALL BE INSTALLED IN WING D BEFORE THE EXISTING FIRE ALARM CONTROL

PANEL IS RELOCATED. CONTRACTOR IS RESPONSIBLE FOR PROVIDING A FIRE

WATCH AND COORDINATING WITH COR IF AT ANY TIME THE BUILDING IS NOT

PROTECTED WITH A FIRE ALARM SYSTEM. ALL EXISTING FIRE ALARM APPLIANCES

(WHETHER OR NOT CONNECTED TO THE EXISTING PANEL), INCLUDING CIRCUITS,

SMOKE SENSORS, HEAT SENSORS, VISUAL AND AUDIO INDICATING APPLIANCES

(STROBE, HORNS, BELLS) AND MANUAL PULL STATIONS SHALL BE REMOVED. REFER

TO DEMO SERIES DRAWINGS.

4. ALL WORK AND INSTALLATION SHALL CONFORM WITH THE APPLICABLE CODES AND

STANDARDS INCLUDING:

NFPA 70: NATIONAL ELECTRIC CODE (2011).

NFPA 72: NATIONAL FIRE ALARM (2010).

NPS-NCR FIRE PROTECTION SYSTEM REQUIREMENTS rev 9/30/2014.

5. AN ADDRESSABLE FIRE ALARM CONTROL PANEL SHALL BE PROVIDED BASED ON

SILENT KNIGHT MODEL #SK5808 OR APPROVED EQUIVALENT WITH 127

ADDRESSABLE POINTS FOR WINGS A, B, AND C. WING D SILENT KNIGHT FIRE ALARM

CONTROL PANEL MODEL #SK5820 SHALL BE EXISTING TO REMAIN AND RELOCATED

WITHIN THE BUILDING PER THE DRAWINGS. FACP SHALL CONTAIN A BUILT IN DIGITAL

ALARM COMMUNICATOR TRANSMITTER FOR COMMUNICATION OF FIRE ALARM

SIGNALS SIGNALS TO TWO SEPARATE CENTRAL STATION SERVICES.

6. THERE ARE TWO CENTRAL STATIONS THAT ALL REPORTABLE FIRE ALARM SIGNALS

SHALL BE TRANSMITTED TO:

6.1. USPP COMMUNICATIONS SECTION/DISPATCH CENTER LOCATED IN

WASHINGTON DC AT THE ANACOSTIA OPERATIONS FACILITY IN ANACOSTIA

PARK.

6.2. NCR COMMUNICATIONS CENTER LOCATED IN HAGERSTOWN, MD

FIRE ALARM SIGNALS SHALL BE TRANSMITTED TO BOTH CENTRAL STATIONS WITH

THE USPP COMMUNICATION SECTION/DISPATCH CENTER CONSIDERED THE

PRIMARY CENTER.

7. ALL FIRE ALARM CIRCUITS SHALL BE SUPERVISED AS FOLLOWS IN ACCORDANCE

WITH NFPA 72:

INITIATING - CLASS B, STYLE B

NOTIFICATION APPLIANCES - CLASS B, STYLE Y, SYNCHRONIZED

CONTROL - CLASS B

SIGNALING LINE CIRCUITS - CLASS B, STYLE 4

8. VISUAL NOTIFICATION (STROBES) SHALL BE PROVIDED IN ALL PUBLIC/COMMON

AREAS AS INDICATED ON THE DRAWINGS. UNLESS NOTED OTHERWISE, THE

STROBES SHALL BE MOUNTED WITH THE LENS BETWEEN 80 AND 96 INCHES ABOVE

FINISHED FLOOR. AUDIO NOTIFICATION APPLIANCES (HORNS) SHALL BE PROVIDED

THROUGHOUT THE USPP BUILDING AND AUDIO NOTIFICATION APPLIANCE

(SPEAKERS) SHALL BE PROVIDED THROUGHOUT THE NCR BUILDING.

9. MANUAL PULL STATIONS SHALL BE PROVIDED WITHIN 5 FEET OF THE ENTRANCE TO

EACH EXIT. ALL PULL STATIONS SHALL BE MOUNTED BETWEEN 42 AND 48 INCHES

ABOVE FINISHED FLOOR.

10. ARRANGE STROBE NAC POWER REQUIREMENTS AND CONDUCTOR SIZES NOT TO

EXCEED A 10% (2.4v) VOLTAGE DROP. EACH VISUAL NOTIFICATION APPLIANCE

CIRCUIT SHALL NOT EXCEED 80% OF ITS RATED OUTPUT.

11. ALL COVER PLATES AND APPLIANCES SHALL BE LABELED WITH THEIR

ADDRESS/CIRCUIT NUMBER UTILIZING LABELING TAPE.

12. ALL FIRE ALARM APPLIANCES PROVIDED IN LAY-IN ACOUSTICAL TILE CEILINGS

SHALL BE CENTER OF TILE. PROVIDE TILE BRIDGE TO SUPPORT APPLIANCE.

13. THE PROJECT ELECTRICAL CONDUIT STANDARD IS ELECTRICAL METALLIC TUBING

(EMT) AND SHALL BE PROVIDED THROUGHOUT THE PROJECT. REFERENCE TO

CONDUIT SHALL MEAN EMT. MINIMUM CONDUIT SIZE IS 3/4 INCH. ALL WIRING SHALL

BE PROVIDED IN CONDUIT.

14. CONDUIT SHALL BE INSTALLED AS UNOBTRUSIVELY AS POSSIBLE, AS CLOSE AS

POSSIBLE TO FLOOR/CEILING SLAB AND PARALLEL AND AT RIGHT ANGLES TO

STRUCTURAL ELEMENTS. THESE DRAWINGS ARE DIAGRAMMATIC TO SHOW DESIGN

INTENT ONLY.

15. EXPOSED CONDUIT SHALL BE PAINTED TO MATCH SURROUNDING ADJACENT WALL

OR CEILING SURFACE, AND RED ENAMEL BANDS 4 INCHES WIDE SHALL BE PAINTED

AT 10 FOOT INTERVALS. THIS PAINTING REQUIREMENT (EXCLUDING THE RED

ENAMEL BANDS) APPLIES TO THE PULL BOXES, JUNCTION BOXES, MOUNTING BOXES

AND EXTENSIONS.

16. ELECTRICAL BOXES SHALL BE PROVIDED AS FOLLOWS: U.N.O. CAST METAL BELL

TYPE BOXES WITH THREADED HUBS SHALL BE PROVIDED ON EXPOSED WORK,

EXCEPT WHERE FACTORY BOXES ARE PROVIDED. CONCEALED BOXES MAY BE

STAMPED STEEL BOXES. TERMINAL CABINETS SHALL BE OF SOLID WALL

CONSTRUCTION WITH NO FACTORY CONDUIT KNOCK OUTS. ALL BOX COVERS SHALL

BE PAINTED RED.

17. ALL CONDUIT INCLUDING RISERS UP TO 2 INCHES IN DIAMETER SHALL UTILIZE

COMPRESSION TYPE STEEL FITTINGS AND CONNECTORS. UNLESS SPECIFIED

DIFFERENTLY BY FIRE ALARM EQUIPMENT MANUFACTURER PROVIDE SOLID COPPER

WIRING CONDUCTORS INSTALLED IN CONDUIT FOR THE FOLLOWING CIRCUITS (AT

MINIMUM):

INITIATING NO 16/2 AWG,

VISUAL NOTIFICATION APPLIANCES - 12/2 AWG, MINIMUM

AUDIO NOTIFICATION APPLIANCES - 16/2 AWG, TWISTED PAIR, MINIMUM

CONTROL 16/2 AWG

SIGNALING LINE CIRCUITS, 18/2 AWG, TWISTED PAIR

120 VAC - 12 AWG WITH NO 12 AWG EQUIPMENT GROUND, 600VAC RATED,

MINIMUM

18. ANY INFORMATION CONFLICTS BETWEEN THE SPECIFICATIONS AND DRAWINGS

SHALL BE BROUGHT TO THE ATTENTION OF THE COR. THE CONTRACTOR SHALL NOT

PROCEED WITH ANY WORK, EXCEPT AT THEIR OWN RISK, UNTIL CLARIFICATIONS OF

THE CONFLICTS ARE ISSUED TO THE CONTRACTOR BY THE COR.

19. ALL DIMENSIONS AND CONDITIONS SHALL BE VERIFIED AT JOB SITE CONCERNING

THE WORK BEFORE PROCEEDING WITH EITHER FABRICATION OR INSTALLATION OF

NEW WORK. LOCATION OF SYSTEMS, PIPING, RISERS AND SPRINKLERS ARE

APPROXIMATE. IT SHALL BE THE RESPONSIBILITY OF THE CONTRACTOR TO VERIFY

THE LOCATION OF ALL SYSTEM COMPONENTS. ANY DISCREPANCIES WITH THESE

DRAWINGS SHALL BE REPORTED TO THE COR IMMEDIATELY.

20. CONTRACTOR SHALL BE RESPONSIBLE FOR AVOIDING CONFLICTS WITH LIGHTS,

FIXTURES, DIFFUSERS, GRILLS, DUCTS, PIPING, CONDUIT, STRUCTURAL MEMBERS

AND OTHER OBSTRUCTIONS ENCOUNTERED. THE CONTRACTOR IS ADVISED SOME

AREAS REQUIRE EXTENSIVE COORDINATION OF SPRINKLER PIPE WITH EXISTING

CONDITIONS, SUCH AS MECHANICAL EQUIPMENT, DUCTS, PIPING, CONDUIT,

STRUCTURAL MEMBERS, WIRE TROUGH, ETC.

21. ALL DAMAGE TO WALLS, CEILINGS, FLOORS, AND STRUCTURAL MEMBERS FROM

PENETRATIONS, INSTALLATIONS OR OTHER ACTIONS OF THE CONTRACTOR SHALL

BE PATCHED, REPAIRED AND PAINTED WITH NEW MATERIALS BY THE CONTRACTOR

TO MATCH ADJACENT WORK, WHETHER SPECIFICALLY NOTED OR NOT. WHERE

CEILINGS ARE DISTURBED PAINTING CORNER TO CORNER MAY BE NECESSARY TO

MATCH PRE-INSTALLATION CONDITIONS.

22. CONTRACTOR SHALL NOT CUT, DRILL OR BURN ANY STRUCTURAL MEMBERS. THE

CONTRACTOR SHALL NOT CUT OR PATCH STRUCTURAL WORK IN A MANNER THAT

WOULD RESULT IN A REDUCTION OF LOAD-CARRYING OR LOAD-DEFLECTION RATIO.

23. ALL WORK SHALL BE COORDINATED WITH THE COR, INCLUDING ACCESS TO THE

SITE. SCHEDULE WORK TO MINIMIZE DISRUPTION TO OCCUPANTS. WORK SHALL BE

PROPERLY SECURED WITH BARRIERS SO AS NOT TO CREATE A SAFETY HAZARD.

MATERIALS SUCH AS TOOLS, LADDERS AND INSTALLATION MATERIAL SHALL BE

KEPT TO A MINIMUM.

24. CONTRACTOR SHALL MAINTAIN THE BUILDING IN A FULLY FUNCTIONAL CONDITION

THROUGHOUT THE CONSTRUCTION PERIOD. CONTRACTOR IS RESPONSIBLE FOR A

FIRE WATCH DURING RELOCATION OF THE FIRE ALARM CONTROL PANEL IN WING D

FOR AS LONG AS BUILDING DOES NOT HAVE A FULLY FUNCTIONAL SYSTEM. TAKE

ALL PRECAUTIONS NECESSARY TO PROTECT THE BUILDING DURING

CONSTRUCTION.

25. CONTRACTOR SHALL BE RESPONSIBLE FOR PROTECTING ALL EQUIPMENT,

FURNISHINGS, FIXTURES AND CONTENTS OF THE SPACE FROM DAMAGE, DUST

WATER AND DEBRIS ASSOCIATED WITH WORK. CONTRACTOR IS RESPONSIBLE FOR

DAILY CLEAN UP, INCLUDING REMOVAL OF ALL TRASH, DEBRIS AND CONSTRUCTION

MATERIALS ON A DAILY BASIS, AND RESTORING TO PRE-CONSTRUCTION CONDITION

AS WORK IS COMPLETED.

26. DUCT SMOKE SENSORS SHALL BE PROVIDED PER THE IMC. PROVIDE DUCT SENSOR

AT RETURN SIDE OF ANY AIR HANDLING UNIT WITH A CAPACITY GREATER THAN 2,000

CFM. PROVIDE DUCT SENSOR AT EACH STORY LOCATED UPSTREAM OF THE

CONNECTION WITH THE RETURN RISER AND ANY AIR DUCTS OR PLENUMS OF ANY

AIR HANDLING UNIT SERVING TWO OR MORE STORIES AND WITH A CAPACITY

GREATER THAN 15,000 CFM. WHEN DUCT SMOKE SENSOR IS LOCATED ABOVE A

CEILING PROVIDE INDICATION (SUCH AS SIGNAGE) ON CEILING DIRECTLY BELOW

SMOKE SENSOR. PROVIDE REMOTE TEST STATION FOR EACH DUCT SMOKE SENSOR

PROVIDED.

27. ANY NEW CORES IN EXISTING REINFORCED CONCRETE SLABS SHALL BE LOCATED

TO AVOID CUTTING JOISTS, BEAMS OR REBAR. CONTRACTOR IS REQUIRED TO

LOCATE BY GPR SCAN OR SIMILAR INVESTIGATION AND MARK LOCATIONS ON

FLOOR. CORES SHALL BE PLACED TO AVOID CUTTING EXISTING REBAR. IF IT IS NOT

FEASIBLE TO AVOID CUTTING REBAR THAN CONTRACTOR IS REQUIRED SUBMIT

SKETCHES INDICATING REBAR LOCATIONS ALONG WITH SUGGESTED OPENING

LOCATIONS TO CONTRACTING OFFICIAL FOR APPROVAL. ALLOW 2 WEEKS FOR

REVIEW. FOR OPENINGS IN ROOF DECK OR COMPOSITE SLAB ON DECK REFER TO

TYPICAL DETAILS.

28. ALL NECESSARY INSPECTIONS AND FINAL SYSTEM ACCEPTANCE TESTING SHALL BE

SECURED AND/OR PERFORMED.

29. THE TERM "PROVIDE" SHALL MEAN THE CONTRACTOR SHALL FURNISH, INSTALL AND

CONNECT FOR A COMPLETE AND OPERATIONAL SYSTEM.

30. THE TERM "REMOVE" SHALL MEAN THE CONTRACTOR SHALL DISCONNECT AND

REMOVE FROM SITE.

AFF

AI

AWG

BM

BFC

BOS

COR

DN

EMT

EOL

EQUIP

FACP

FL

FT

GYP

IDC

IN

LAT

MECH

NAC

NAP

NEC

NFPA

NTS

PLS

RM

SLC

SPL

STR

TC

TYP

UNO

VAC

VDC

W

ZN

ABOVE FINISHED FLOOR

ADDRESSABLE INTERFACE

AMERICAN WIRE GAUGE

BEAM

BELOW FINISHED CEILING

BOTTOM OF STEEL

CONTRACTING OFFICER'S REPRESENTATIVE

DOWN

ELECTRICAL METALLIC TUBING

END OF LINE SUPERVISION DEVICE

EQUIPMENT

FIRE ALARM CONTROL PANEL

FLOOR

FEET

GYPSUM BOARD

INITIATING DEVICE CIRCUIT

INTERFACE

LAY-IN ACOUSTICAL TILE

MECHANICAL

NOTIFICATION APPLIANCE CIRCUIT

NOTIFICATION APPLIANCE PANEL

NATIONAL ELECTRICAL CODE - NFPA 70

NATIONAL FIRE PROTECTION ASSOCIATION

NOT TO SCALE

PLASTER CEILING

ROOM

SIGNALING LINE CIRCUIT

SINGLE POLE, DOUBLE THROW

STAIR

TERMINAL CABINET

TYPICAL

UNLESS NOTED OTHERWISE

VOLTS ALTERNATING CURRENT

VOLTS DIRECT CURRENT

WATT

ZONE

C

W

CEILING MOUNTED

WALL MOUNTED

LINE TYPE - EXISTING DEVICE TO REMAIN

LINE TYPE - EXISTING TO BE REMOVED

LINE TYPE - NEW DEVICE

MANUAL PULL STATION

VISUAL NOTIFICATION APPLIANCE

HORN/STROBE NOTIFICATION DEVICE

XX=CANDELA RATING, X=MOUNTING LOCATION

HORN NOTIFICATION DEVICE

SPEAKER APPLIANCE

X=MOUNTING LOCATION

SPEAKER/STROBE APPLIANCE

XX=CANDELA RATING, X-MOUNTING LOCATION

VALVE TAMPER SWITCH CONNECTION

WATER FLOW SWITCH CONNECTION

HIGH/LOW AIR PRESSURE SWITCH, CONNECTION ONLY

PRESSURE SWITCH, CONNECTION ONLY

ADDRESSABLE MONITOR MODULE

ADDRESSABLE RELAY MODULE

GENERATOR RUN, CONNECTION ONLY

GENERATOR FAULT, CONNECTION ONLY

120 VAC DEDICATED POWER CIRCUIT

SMOKE DETECTOR, X=MOUNTING LOCATION

SMOKE DETECTOR, ELEVATOR INTERFACE,

X=MOUNTING LOCATION

SMOKE DETECTOR, DUCT MOUNTED WITH REMOTE TEST

STATION

HEAT DETECTOR-RATE OF RISE/FIXED TEMPERATURE

X=MOUNTING LOCATION

HEAT DETECTOR-RATE OF RISE/FIXED TEMPERATURE,

ELEVATOR INTERFACE, X=MOUNTING LOCATION

FIRE ALARM ELECTRONIC BELL

AMPLIFIER CABINET

FIRE ALARM CONTROL PANEL

NOTIFICATION APPLIANCE BOOSTER PANEL

TRANSIENT VOLTAGE SURGE SUPPRESSOR

DIGITAL ALARM COMMUNICATION TRANSMITTER

ELEVATOR TERMINAL CABINET RECALL FUNCTION

ELEVATOR TERMINAL CABINET SHUNT TRIP FUNCTION

KEY NOTE INDICATOR

CEILING TYPE/HEIGHT INDICATOR

FIRE ALARM ZONE IDENTIFICATION

ZONE-ID=ZONE NUMBER

DETAIL NUMBER

DETAIL IDENTIFICATION BUBBLE

SHEET DETAIL IS SHOWN ON

SHEET DETAIL IS TAKEN FROM

ELEVATION NUMBER

ELEVATION IDENTIFICATION BUBBLE

SHEET ELEVATION IS SHOWN ON

SHEET ELEVATION IS TAKEN FROM

X

XX

X

A

T C

H L I N

E M

A T

C H

L I N

E M

A T

C H

L I N

E

1. ALL EXISTING FIRE ALARM APPLIANCES, INCLUDING

ASSOCIATED CIRCUITS AND CONDUITS, SHALL BE REMOVED.