This document contains electrical and telecommunications drawings and specifications for the construction of a visitor center addition at Crab Orchard National Wildlife Refuge in Illinois. The project includes installation of solar panel arrays with a total capacity of 18.8 kW, addition of electrical panels to serve the visitor center and outdoor classroom, upgrades to the main distribution panel, and installation of new data and telecommunications infrastructure including a secure server, wireless access points, routers, and network switches. Relevant specifications require connection of new data jacks in the visitor center to the existing server in the headquarters building and labeling of jacks to indicate routing to either the secure government server or unsecure public server.
The related federal contract opportunity is a solicitation issued by the U.S. Fish and Wildlife Service seeking construction services for the visitor center addition project at the listed refuge in accordance with the specifications provided in the electrical and telecommunications drawings. The solicitation number is 140F0821R0011 and responses are due by the listed date.
View the file
Other files
Show all 35
On GovTribe
Work with this file
- Download the original file
- Contacts named in this file
- Similar government files
- Ask GovTribe AI about this file
Text version
SHEET_____OF_____
BYDESCRIPTIONDATEREVISION
DESIGNED:
CADD:
CHECKED:
DRAWING NO:
DRAWN: DATE:
21-RF-004PROJECT NUMBER:E5.0
UTILITY/INVERTER DISCONNECT(S). LOCATE OUTDOORS IN SAME PEDESTAL AS PHASE 1 SOLAR
DISCONNECT AND UTILITY MAIN SERVICE METER. TOP LUGS OF DISCONNECT TO BE
CONNECTED TO THE ELECTRIC SERVICE AND BOTTOM LUGS TO BE CONNECTED TO INVERTER.
DISCONNECT TO BE LABELED AS SUCH.
JUNCTION BOX.
PANEL "B" TO SERVE VISITOR CENTER BRANCH CIRCUITS. PANEL B FED FROM EXISTING MDP
PANEL IN HQ MECHANICAL ROOM
PROVIDE NEW 400A/3P BRANCH BREAKER TO MATCH EXISTING MDP RATINGS. FEED PANEL B
WITH 2 SETS OF (4) #3/0, #3 GND IN 2-2" CONDUIT
FEED OUTDOOR CLASSROOM PANEL WITH (4) #4, #10 GND IN 2"CONDUIT.
KEY NOTES
UTILITY
POLE
MOUNTED
TRANSFORMER
PANEL
"A"
SOLAR
PANEL
ARRAYS
(PHASE 1)
8.91 KW
CAPACITY
NON-POTABLE
WATER
PUMP
WATER
HEATER
EWH-1
M
METERING
TRANSFORMER
DISCONNECT
PEDESTAL
MAIN DISTR. PANEL "MDP" - 800A, 120/208V, 3PHASE, 4WIRE
65,000 A.I.C.
2P 30A
3P 20A
3P 225A
3P 400A
3P 800A
PANEL
"B"
3P 400A
PANEL
"PP"
11 11
3P 100A
LIFT
STATION
CONTROL
PANEL
13 14
LIFT
STATION
PUMPS
2P 25A
2P 25A
ELECTRIC
HEATER
EH-1
ELECTRIC
HEATER
EH-2
CENTRAL
LTG
INVERTER
"INV"
2P 20A
SOLAR
PANEL
ARRAYS
(PHASE 2)
9.9 KW
CAPACITY
2P 20A
TERMINATOR CAP
INSTALLED ON END
OF CABLE (TYP.)
3P 60A
SPD
ELECTRICAL ONE LINE DIAGRAM
AD/SK
330W SOLAR PV
PANEL (TYP.)
C.T.'S
C.T.'S
M M
M M
M M
M M
ADVANCED
ENERGY
METERING
RECEPT'S
EXTR. LTG.
INTERIOR LTG.
WHOLE
BLD.
PUMPS
FANS
SERVICE WATER HEATING
VRF SYSTEM
NOTE:
1. CONNECT NEW DATA JACKS IN VISITOR CENTER
TO EXISTING MDF SERVER IN HEADQUARTERS.
2. DATA JACKS ON FLOOR PLAN INDICATE "G" FOR
ROUTING TO SECURE/GOVERNMENT SERVER
OR "F" FOR ROUTING TO UNSECURE/FRIEND
SERVER. CONFIRM WITH OWNER PRIOR TO
INSTALLING.
PANEL
"OUTDOOR
CLASSROOM"
1 8-27-21Addendum No. 1 AJL
AutoCAD SHX Text
VISITOR CENTER
AutoCAD SHX Text
WILLIAMSON COUNTY
AutoCAD SHX Text
CRAB ORCHARD NATIONAL WILDLIFE REFUGE
AutoCAD SHX Text
ILLINOIS
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
3R-IL-415-1321
AutoCAD SHX Text
CRO321E2.DWG
AutoCAD SHX Text
KO
AutoCAD SHX Text 6/21
AutoCAD SHX Text
IBC
AutoCAD SHX Text
SWITCH
AutoCAD SHX Text
UNSECURE/FRIEND SERVER (BY FWS)
AutoCAD SHX Text
SWITCH
AutoCAD SHX Text
WAP
AutoCAD SHX Text
ROUTER (BY FWS)
AutoCAD SHX Text
WAP
AutoCAD SHX Text
(BY FWS)
AutoCAD SHX Text
(BY FWS)
AutoCAD SHX Text
(BY FWS)
AutoCAD SHX Text
SECURED DATA OUTLETS (JACKS)
AutoCAD SHX Text
FACP
AutoCAD SHX Text
DDC
AutoCAD SHX Text
PV
AutoCAD SHX Text
PATCH PANEL (BY TCC)
AutoCAD SHX Text
PATCH CORDS (BY TCC)
AutoCAD SHX Text
INCOMING TELEPHONE/INTERNET SERVICE
AutoCAD SHX Text
DEMARK POINT
AutoCAD SHX Text
TELEPHONE BACKBOARD
AutoCAD SHX Text
ALL CABLING TO BE CAT 6E
AutoCAD SHX Text
(BY FWS)
AutoCAD SHX Text
TELE/DATA SERVICE RISER DIAGRAM
AutoCAD SHX Text
AutoCAD SHX Text N.T.S.
AutoCAD SHX Text
SECURE/GOVERNMENT SERVER (BY FWS)
AutoCAD SHX Text
DSL
AutoCAD SHX Text
PATCH PANEL (BY TCC)
AutoCAD SHX Text
TEL/DATA OUTLETS
AutoCAD SHX Text
ELECTRICAL RISER DIAGRAM
AutoCAD SHX Text
AutoCAD SHX Text N.T.S.