Exhibit_2_-_NPS_WWII_Equipment__Systems__and_Maintenance_Items_0002.xlsx

XLSX spreadsheet 64 KB Posted

Attached to
NAMA WWII Memorial Operations and Maintenance IDIQ
Solicitation number
140D0424Q0127
Issued by

About this file

This document contains an exhibit listing equipment, systems, and maintenance items for the World War II Memorial along with a related federal contract opportunity solicitation.

The exhibit lists over 150 pieces of equipment across various systems including HVAC, electrical, plumbing, lighting, security, and more. Required maintenance for each item is specified, ranging from daily to annual tasks such as cleaning, inspection, filter replacement, and repairs. The solicitation seeks operations and preventative maintenance services for these systems on an IDIQ basis. The seed task order is for the National Park Service National Capital Region's National Mall and Memorial Parks unit. Services include emergency and non-emergency repairs. The solicitation number is 140D0424Q0127 and was issued by the Interior Business Center within the Department of the Interior Departmental Offices.

View the file

Other files

File Type Posted
QnA_Government_Response_v3_Amend_8_0008_0008.pdf PDF
Sol_140D0424Q0127_Amd_0008.pdf PDF
AMEND_8_140D0424Q0127_0008_0008.pdf PDF
Attch_2_PWS_WWII_Preventative_Maintenance_TO_14May2024_0007.pdf PDF
QnA_Government_Response_v2_1_Amend_7_0007_0007.pdf PDF
Sol_140D0424Q0127_Amd_0007.pdf PDF
Attch_1_PWS_WWII_Memorial_Operations_and_Maintenance_14May2024_0007.pdf PDF
AMEND_7_140D0424Q0127_0007_0007.pdf PDF
QnA_Government_Response_v2_1_Amend_6_0006.pdf PDF
Sol_140D0424Q0127_Amd_0006.pdf PDF
Attch_3_Pricing_Sheet_Amend_6_0006.xlsx XLSX spreadsheet
AMEND_6_140D0424Q0127_0006.pdf PDF
Attch_1_PWS_WWII_Memorial_Operations_and_Maintenance_Amend_5_0005.pdf PDF
Attch_2_PWS_WWII_Preventative_Maintenance_TO_Amend_5_0005.pdf PDF
Sol_140D0424Q0127_Amd_0005.pdf PDF
SOW-INP17PD01351_0005.pdf PDF
AMEND_5_140D0424Q0127_0005.pdf PDF
QnA_Government_Response_v2_Amend_5_0005.pdf PDF
Sol_140D0424Q0127_Amd_0004.pdf PDF
AMEND_4_140D0424Q0127_0004.pdf PDF
WWII_Site_Visit_Sign_In_Sheet__0004.pdf PDF
Sol_140D0424Q0127_Amd_0003.pdf PDF
AMEND_3_140D0424Q0127_SOL_NAMA_WWII_0003.pdf PDF
Attch_9_Site_Visit_Parking_Map_0003.pdf PDF
QnA_Government_Response_Amend_2_0002.pdf PDF
Exhibit_7_Operations_and_Maint_Manuals_List_0002.pdf PDF
Attch_3_Pricing_Sheet_Amend_2_0002.xlsx XLSX spreadsheet
Sol_140D0424Q0127_Amd_0002.pdf PDF
Attch_1_PWS_WWII_Memorial_Operations_and_Maintenance_Amend_2_0002.pdf PDF
Exhibit_9_NPS_Identification_0002.pdf PDF
Exhibit_4_-_NPDES_Discharge_Permit_0002.pdf PDF
AMENDMENT_2_140D0424Q0127_SOL_NAMA_WWII_0002.pdf PDF
Attch_2_PWS_WWII_Preventative_Maintenance_TO_Amend_2_0002.pdf PDF
Exhibit_8_-_Quality_Assurance_Surviellance_Plan_-_WWII_Memorial_0002.pdf PDF
Exhibit_1_Safety_Health_Environ_Plan_0002.pdf PDF
AMEND_1_140D0424Q0127_SOL_NAMA_WWII_0001.pdf PDF
Sol_140D0424Q0127_Amd_0001.pdf PDF
Attch_5_Past_Performance_Questionnaire.docx DOCX document
Attch_4_Limitations_on_Subcontracting_Worksheet.xlsx XLSX spreadsheet
140D0424Q0127_SOL_NAMA_WWII.pdf PDF
Attch_6_QnA_Template.xlsx XLSX spreadsheet
Attch_8_Organizational_Conflict_of_Interest_Certificate.pdf PDF
Attch_7_Wage_Determination_2015-4281.pdf PDF
Attch_2_PWS_WWII_Preventative_Maintenance_TO.pdf PDF
Attch_1_PWS_WWII_Memorial_Operations_and_Maintenance.pdf PDF
Attch_3_Pricing_Sheet.xlsx XLSX spreadsheet
Sol_140D0424Q0127.pdf PDF
Show all 47

On GovTribe

Work with this file

  • Download the original file
  • Contacts named in this file
  • Similar government files
  • Ask GovTribe AI about this file

Text version

Alarm

EXHIBIT 2

NPS WWII Equipment, Systems, and Maintenance Items

ALARM SYSTEM

EquipmentQtyLocationDescriptionRequired Maintenance
Fire System
*Fire Alarms5PEPCO VaultAudio and Lighted AlarmAnnual - Test Each Smoke Alarm (Contact NPS and DCFD to Schedule test) Annual - Clean Each Fire Alarms As Needed - Replace/Repair Alarms
8Main Vault
3Comfort Station Bathrooms
1Information Center
Security and Fire Control
Control Panels3Engineers OfficeNotifier NSF640 Antronix Alarms Station Voice Evacuation Control Fire WatchAnnual - Test/Troubleshoot/Repair Alarm Malfunctions
Note:
* Fire Alarms in the Tunnel Vault will require scaffolding to reach and test.

Alarm System

Granite Bronze

EXHIBIT 2

NPS WWII Memorial Equipment, Systems, and Maintenance Items

GRANITE AND BRONZE MAINTENANCE
MaterialQtyArea/ItemRequired Maintenance
1Pool Area Caulking5300 LFTotal Caulk (Grey)Prior to Spring Startup - Repair/Caulk Pool Joints Approx. Recaulk 750 LF
Bronze4500Gold Stars and Bronze Panels Behind StarsAnnual - Handwash with Warm Water Annual - Clean and wax Quarterly - Remove Cobwebs
112WreathsOn each columnTri-Annual - Hot wax (every three years)

Semi-annual - Cold wax (twice a year), handwash and remove old wax

Monthly - Remove Cobwebs to include in and around granite.

2BaldacchinosArches (4 eagles & Wreaths)
256Bronze RopesBetween Columns
2Flagpole PedestalPlaza
2MedallionsMemorial Arches
24BAS Relief Panels
248 LFHandrailsQuarterly - Clean with soft cotton rag and mild detergent

As-needed - Touch up paint for chips and scratches

2Gates
Granite Gum RemovalMemorialPlazaGum RemovalActive - Daily with steam cleaner Deactive - monthly with steam cleaner or as approved by the COR
ConcreteBus Drop-offConcrete Sidewalks
Comfort Station
Notes:
1 Caulking and Grouting is weather dependent and should be performed on dry days with adequate temperature in order for the compounds to adequately set.
2 An articulated lift or scaffolding will be required to polish the entire Baldacchinos, can be performed in conjunction with relamping of the arches.
3 Pressure washing should not be directed at lettering on columns. Cleaning techniques will be as directed by the COR.

Granite and Bronze

HVAC

EXHIBIT 2

NPS WWII Equipment, Systems, and Maintenance Items

HVAC

FixtureQtyStructureRoomLocationDescriptionRequired Maintenance
Groundwater Treatment System
ACU-11Tunnels and VaultsMain VaultCeiling UnitTrane GEVB24041AAA10Monthly - Inspect Unit and Replace Filters (6 -20x25x1) Monthly - Inspect and Replace Belt as Needed (B-55) Every 3 Months - Check/Add Refrigerant as Needed Annual - Inspect Contactors, Wiring and Relays, Exercise Shutoff Switch, Clean Condenser Coils
ACU-21Tunnels and VaultsMain VaultCeiling UnitTrane GEVB24041AAA11
ACU-31Tunnels and VaultsMain VaultFloor UnitTrane GEVB24041AAA12
SF-11Tunnels and VaultsMain VaultSupply Fan Greenheck BCF-110-4 (1500CFM)Monthly - Replace Filter (2 - 20x20x1) Every 3 Months - Check Belt Tension Adjust/Replace When Needed (AX43) Annual - Lubricate Motor SAE 20 Electric Motor Oil Annual - Exercise Shutoff Switch
EDH-11Tunnels and VaultsMain VaultElectric Duct Heater INDEECOAnnual - Inspect unit and Clean Coils Annual - Exercise Shutoff Switch
ACC-11Tunnels and VaultsPEPCO VaultCeiling UnitCondenser Unit Stultz Air Tech. Sys. HES-048-CAAMonthly - Inspect unit and Replace Filter (25x25x1) Monthly - Check Belt Tension and Replace as Needed (B45) Annual - Check Condensate Line Annual - Inspect/Tighten Wiring Annual - Clean Unit Annual - Check Refrigerant Level Annual - Exercise Shutoff Switch
ACC-21Tunnels and VaultsPEPCO VaultCeiling UnitCondenser Unit Stultz Air Tech. Sys. HES-060-CAA
AHU-11Tunnels and VaultsPEPCO VaultFloor UnitEvaporator Unit Stultz Air Tech. Sys. OHS-048-ARMonthly - Inspect Unit and Replace Filter (20x16x1) Monthly - check Belt Tension Replace as Needed Every 6 Months - Clean Evaporator Coil Annual - Exercise Shutoff Switch
AHU-21Tunnels and VaultsPEPCO VaultCeiling UnitEvaporator Unit Stultz Air Tech. Sys. COS-060-ARMonthly - Inspect Unit and Replace Filter (24x24x1) Monthly - check Belt Tension Replace as Needed (B43/5L460) Every 6 Months - Clean Evaporator Coil Annual - Exercise Shutoff Switch
1EF-11Tunnels and VaultsMain VaultCeiling UnitExhaust Fan (1500 CFM) Greenheck SP-A125Every 3 Months - Check Belt Tension (Adjust/Replace When Needed) Annual - Lubricate SAE 20 Electric Motor Oil Annual Exercise Shutoff Switch
EF-21Tunnels and VaultsPEPCO VaultSidewall Direct Drive Exhaust Fan Greenheck SE1-8-440-G1Annual - Inspect Fan

Annual - Lubricate SAE 20 Electric Motor Oil Annual - Exercise Shutoff Switch EF-3A 1 Tunnels and Vaults Storm Vault Sidewall Direct Drive Exhaust Fan Greenheck SE1-8-440-G2 Annual - Inspect Fan Annual - Lubricate SAE 20 Electric Motor Oil Annual - Exercise Shutoff Switch EF-4 1 Tunnels and Vaults Storm Vault Sidewall Direct Drive Exhaust Fan Greenheck SE1-8-440-G3 Annual - Inspect Fan Annual - Lubricate SAE 20 Electric Motor Oil Annual - Exercise Shutoff Switch SF-1 1 Comfort Station Sewage Pump Room Supply Fan Greenheck BCF-110-4 (1500CFM) Monthly - Replace Filter (2 - 20x20x1) Every 3 Months - check Belt Tension Adjust/Replace When Needed (3L410) Annual - Lubricate SAE 20 Electric Motor Oil Annual - Exercise Shutoff Switch SF-2 1 Comfort Station Men's Room Sidewall Direct Drive Supply Fan Greenheck SS-12-432-B6 Annual - Inspect Fan Annual - Lubricate SAE 20 Electric Motor Oil Annual - Exercise Shutoff Switch SF-3 1 Comfort Station Women's Room Sidewall Direct Drive Supply Fan Greenheck SS-12-432-B7 Annual - Inspect Fan Annual - Lubricate SAE 20 Electric Motor Oil Annual - Exercise Shutoff Switch HVAC System

EXHIBIT 2

NPS WWII Equipment, Systems, and Maintenance Items

EF-11Comfort StationSewage Pump RoomCeilingExhaust Fan (1500 CFM) Greenheck SP-A125Every 3 Months - check Belt Tension (Adjust/Replace When Needed) Annual - Lubricate SAE 20 Electric Motor Oil Annual Exercise Shutoff Switch
EF-21Comfort StationSewage Pump RoomSidewall Direct Drive Exhaust Fan Greenheck SE1-8-440-G1Annual - Inspect Fan

Annual - Lubricate SAE 20 Electric Motor Oil Annual - Exercise Shutoff Switch

EDH-11Comfort StationBathroomElectric Duct Heater INDEECOAnnual - Inspect unit and Clean Coils Annual - Exercise Shutoff Switch
UH-11Comfort StationMechanical ClosetWallElectric Duct Heater INDEECOAnnual - Clean Unit Casing, Fan and Motor Annual - Exercise Shutoff Switch
2Comfort StationMaintenance StorageWallElectric Duct Heater INDEECO
2Comfort StationSewage Pump RoomWallElectric Duct Heater INDEECO
1Comfort StationJanitor ClosetWallElectric Duct Heater INDEECO
AC-011Comfort StationEngineers OfficeEvaporator TraneBi-Monthly - Clean/Replace Filter Annual - Exercise Shutoff Switch
CU-011Comfort StationEngineers OfficeRoofCondenser Unit Trane TWE036C140B0/2TTA2Annual - Replace Humidifier Cylinder Annual - Check Condensate Line Annual - Clean Unit; Check/Tighten Wiring Annual - Check Refrigerant Level
EWH-12Comfort StationEngineers OfficeWallElectric Wall Heater INDEECOAnnual - Remove Front Grill and Clean Dust from heater and Grill Annual - Lubricate Motor with SAE No. 10 Annual - Exercise Shutoff Switch
EF-1-011Info Center/Ranger Contact StationBathroomExhaust FanAnnual - Inspect Unit and Clean

Annual - Lubricate SAE 20 Annual - Exercise Shutoff Switch EF-1-02 1 Info Center/Ranger Contact Station Janitor Closet Exhaust Fan Annual - Inspect Unit and Clean Annual - Lubricate SAE 20 Annual - Exercise Shutoff Switch

EWH-11Info Center/Ranger Contact StationBathroomWallElectric Wall Heater INDEECOAnnual - Remove Front Grill and Clean Dust from heater and Grill Annual - Lubricate Motor with SAE No. 10 Annual - Exercise Shutoff Switch
AHU-11Info Center/Ranger Contact StationBathroomTrane Air Handling Unit AC HeatMonthly - Replace Filter (20x20x1) Annual - Exercise Shutoff Switch
CU-011Info Center/Ranger Contact StationBathroomBackCondenser Unit Trane TWE036C140B0/2TTA2Annual - Check Condensate Line Annual - Clean Unit; Check/Tighten Wiring Annual - Check Refrigerant Level
COP-11Tunnels and VaultsMain Vault7.5HP w/inline strainerEvery 3 Months - Grease Pump (5FG High Perf Grease NLGI #2) Annual - Clean In-Line Strainers
COP-21Tunnels and VaultsMain Vault7.5HP w/inline strainer
HEP-11Tunnels and VaultsMain Vault7.5HP w/inline strainer
HEP-21Tunnels and VaultsMain Vault7.5HP w/inline strainer
HE-11Tunnels and VaultsMain VaultHeat Exchanger Bell & Gossett P20-40-TLAAnnual - Backflush
ET-1Tunnels and VaultsMain VaultExpansion TankAnnual - Inspect for Corrosions and Leaks
AS-11Tunnels and VaultsMain VaultAir Separator for ACU Pipe Loop Bell & Gossett A85524Annual -Strainer Servicing
Notes:
1 Servicing EF-1 in Main Vault require scaffolding or other system to reach (35ft).

HVAC System

Fountain

EXHIBIT 2

NPS WWII Equipment, Systems, and Maintenance Items

FOUNTAIN SYSTEM

Equipment idQtyStructureRoomDescriptionRequired Maintenance
Pumps
FP-11Tunnels and VaultsMain VaultBaldor 75HP Motor/PumpPer O&M - Grease pump (5FG High Perf Grease NLGI #2) Maintain Pressure Differential Switches
FP-21Tunnels and VaultsMain VaultBaldor 15HP Motor/PumpAs Needed - Clean Inline Strainer (Daily) Per O&M - Grease pump (5FG High Perf Grease NLGI #2) Maintain Pressure Differential Switches Annual - Lubricate and/or Replace O-Rings on Strainers
DP-11Tunnels and VaultsMain VaultBaldor 40HP Motor/PumpPer O&M - Grease pump (5FG High Perf Grease NLGI #2) Maintain Pressure Differential Switches Maintain Auto Air Vent
DP-21Tunnels and VaultsMain VaultGE 125HP Motor/PumpPer O&M - Grease pump (5FG High Perf Grease NLGI #2) Maintain Pressure Differential Switches Maintain Auto Air Vent
DP-31Tunnels and VaultsMain VaultGE 100HP Motor/PumpPer O&M - Grease pump (5FG High Perf Grease NLGI #2) Maintain Pressure Differential Switches Maintain Auto Air Vent
DP-41Tunnels and VaultsMain VaultGE 75HP Motor/PumpPer O&M - Grease pump (5FG High Perf Grease NLGI #2) Maintain Pressure Differential Switches Maintain Auto Air Vent
DP-51Tunnels and VaultsMain VaultBaldor 15HP Motor/PumpAs Needed - Clean Inline Strainer (Daily) Per O&M - Grease pump (5FG High Perf Grease NLGI #2) Maintain Auto Air Vent Annual - Lubricate and/or Replace O-Rings on Strainers
DP-61Tunnels and VaultsMain VaultBaldor 15HP Motor/PumpAs Needed - Clean Inline Strainer (Daily) Per O&M - Grease pump (5FG High Perf Grease NLGI #2) Maintain Pressure Differential Switches Annual - Clean/Replace Auto Air Vent
DP-71Tunnels and VaultsMain VaultBaldor 50HP Motor/PumpPer O&M - Grease pump (5FG High Perf Grease NLGI #2) Maintain Pressure Differential Switches Maintain Auto Air Vent
Filtration Tanks
FA-1,2,3,4,55Tunnels and VaultsMain VaultFilter Tanks, Model BMF-60 Tower Water Automatic 316 SSAnnual - Visual Inspection of tank/media for condition assessment Backwash as needed Maintain guages, flow meters, and air vents
Flowmeters5Tunnels and VaultsMain VaultFilter TanksAs Needed - Unclog (Take Apart and Clean/Repair)
Sand Filter Air Vents5Tunnels and VaultsMain VaultFilter TanksAnnual - Unclog (Take Apart and Clean/Repair)
Water Treatment
Chlorine Feeder1Tunnels and VaultsMain VaultAccu Tab Model 3500Maintain Accu-Tab chlorine feeders and automated controllers in main vault.
Chlorine Feeder1Tunnels and VaultsMain VaultAccu Tab Model 3150Maintain Accu-Tab chlorine feeders and automated controllers in main vault.
Ascorbic Acid Feeder1Tunnels and VaultsStorm VaultHach Cl-17Maintain chlorine analyzer, float system and pumps.

Fountain System

Electrical

EXHIBIT 2

NPS WWII Equipment, Systems, and Maintenance Items

ELECTRICAL SYSTEM

IDQtyLocationRoomDescriptionRequired Maintenance
System
Electrical System1Memorial, Tunnels and Vaults, Information Center, Comfort Station, Pools, Plaza, WalkwaysDisplay and Control Panels, Fixtures, Electrical Panels Wiring, Sensors, VFD'sAS NEEDED - A licensed electrician should be available to troubleshoot and repair electrical malfunctions.
Panels
PP1Tunnels and VaultsMain Vault100 Amp Panel / 33 breakersAnnual - Vacuum/Clean Dust from Panel Annual - Exercise Breakers Annual - Inspect for Loose Connections and Tighten Perform a comprehensive Inspection every year and perform an infrared inspection annually
FLA1Tunnels and VaultsMain Vault400 Amp Panel / 42 breakers
FLB1Tunnels and VaultsMain Vault225 Amp Panel / 32 breakers
DPP1Tunnels and VaultsMain Vault800 Amp Main Feeder Panel / 5 breakers
PPA1Tunnels and VaultsMain Vault400 Amp Panel / 20 breakers
PPB1Tunnels and VaultsMain Vault100 Amp Panel / 8 breakers
PST1Tunnels and VaultsPEPCO Vault100 Amp / 34 breakers
DPS1Tunnels and VaultsPEPCO Vault400 Amp / 10 breakers
DPS-A1Tunnels and VaultsPEPCO Vault250 Amp / 26 breakers
PIC1Information CenterPEPCO Vault225 Amp / 28 breakers / 150 Main
PCS1Comfort StationPanel Room400 Amp / 42 breakers
PCSA1Comfort StationPanel Room225 Amp Panel / 35 breakers
Lighting Racks
Dimmer Rack #11Tunnels and VaultsMain Vault48 Breaker -Strand lighting RackEvery 3 Months - Remove and Clean Breaker Modules
Dimmer Rack #21Tunnels and VaultsMain Vault48 Breaker -Strand lighting RackEvery 3 Months - Check Fans and Clean Ventilation Filters
Dimmer Rack #31Tunnels and VaultsPEPCO Vault48 Breaker -Strand lighting RackEvery 3 Months - Vacuum Dust from Panel and Exercise Breakers
Motor Control Center
DP-11Tunnels and VaultsMain VaultWall Mounted Control Panels w/ Digital ControlSemi-Annual - Open Control Panel and Clean
DP-21Tunnels and VaultsMain Vault
DP-31Tunnels and VaultsMain Vault
DP-41Tunnels and VaultsMain Vault
DP-51Tunnels and VaultsMain Vault
DP-51Tunnels and VaultsMain Vault
DP-61Tunnels and VaultsMain Vault
DP-71Tunnels and VaultsMain Vault
FP-11Tunnels and VaultsMain Vault
FP-21Tunnels and VaultsMain Vault
350 Amp Breaker1Tunnels and VaultsMain Vault350 Amp Break on Motor Control CenterAnnual - Exercise Breaker Switch
Emergency Battery Power System
IBPA1Tunnels and VaultsMain Vault4 Battery Power BankMonthly- Check Batteries Monthly and Replace if Needed As Needed - Clean Battery Terminal and Vacuum Panel Annual - Inspect Wiring and Tighten/Repair as Needed
IBPB1Tunnels and VaultsPEPCO Vault4 Battery Power Bank
GFCI
GFCI Rack57Tunnels and VaultsMain VaultLighting GFCI PanelSemi-Annual - Check and Exercise Breaker Switches Replace GFCI when needed
GFCI4Tunnels and VaultsPEPCO VaultGFCI Switches (next to Dimmer Rack #3)
GFCI ReceptaclesTunnels and VaultsThroughoutGFCI OutletsAnnual - Check and Exercise Replace GFCI when needed

Electrical System

Computer

EXHIBIT 2

NPS WWII Equipment, Systems, and Maintenance Items

COMPUTER CONTROL SYSTEM

EquipmentDescriptionRequired Maintenance
Lighting Computer System
Computer SystemLighting Control System (Lutron)Maintain System

Quarterly PM by authorized service representative

Computer Control System

BMS

EXHIBIT 2

NPS WWII Equipment, Systems, and Maintenance Items

BUILDING MANAGEMENT SYSTEM

EquipmentQtyLocationDescriptionRequired Maintenance
Computer Control
All BMS Components1Engineers OfficeSiemens Building Technology 215068Maintain System Quarterly PM by authorized service representative

Building Management System

PoolTreatment

EXHIBIT 2

NPS WWII Equipment, Systems, and Maintenance Items

POOLWATER TREATMENT SYSTEM

FixtureQtyStructureRoomDescriptionRequired Maintenance
DeScalamatic
DeScalamatic2Tunnels and VaultsMain Vault800GPMAnnual - Clean Units
DeScalamatic1Tunnels and VaultsMain Vault300 GPM
Pools
1Rainbow Pool1Exterior Pools2335 m² AreaPools must be kept free of debris/algae at all times.

Contractor will be required to:

-Skim debris and trash out daily, higher frequencies required during high wind and spring and fall Elm tree debris drop -Vacuum pool floor-Clean/Clear return grates -Chemical treatment of water -Pressure washing prior to spring startup and at winter shut down -Brush walls and floors to prevent mineral deposit build-up and algae growth

1Ceremonial Pool3Exterior PoolsUpper428 m² Area
Lower
Star
Falls
1Arch Pool North1Exterior Pools172 m² Area
1Arch Pool South1Exterior Pools172 m² Area
Notes:
1 Pools may be required to be drawn down for maintenance or other event. During drawdown, additional maintenance/cleaning should be scheduled. Coins collected during poolwater
treatment must be collected and turned into the NPS.
A chemical Application Log detailing chemical treatment dates and amount should be maintained.
Chemical quantities should be within limits proposed in the applied EPA process permit for the fountains.

Poolwater Treatment System

Plumbing

EXHIBIT 2

NPS WWII Equipment, Systems, and Maintenance Items

PLUMBING SYSTEM

EquipmentQtyStructureLocationDescriptionRequired Maintenance
Sewer System
Sewage Pit1GroundsBehind Comfort StationAnnual - Vacuum/Clean out Maintain Control Panel
Sewage Ejector Pumps2Comfort StationSewage Pump Room30MVpp300-4-Self Priming Non-Clog V-BeltAs Needed - Unclog Pumps (Frequent) Semi-Annual - Grease Pumps and check Belts (GE D6A2CS) Semi-Annual - Clean/Replace Auto Air vent Maintain Control panel
Backflow Preventer1Comfort StationSewage Pump RoomAnnual - Test, Calibrate, and Certify by Certified Backflow Technician and repair as needed
Sewer and Storm Forced MainGroundsAs needed - Unclog Sewer Lines As Needed - Repair Main Breaks
Lavatory Waste ArmsComfort Station/Info CenterAs needed - Unclog/Snake
Fixtures
Urinals2Comfort StationMen's RoomStd. Commercial FixturesMaintain Fixture As needed - Unclog Fixtures and Repair Valves etc. Annual Rebuild Flushometers (Sloan)
Water Closets2Comfort StationMen's RoomMaintain Fixture Weekly -Tighten Seats As Needed - Unclog and Valves etc. Annual Rebuild Flushometers (Sloan)
8Comfort StationWomen's Room
1Info Center/Ranger Contact StationRestroom
1Comfort StationFamily Room
Lavatories4Comfort StationMen's RoomMaintain Fixture As Needed - Unclog and Repair Faucet Annual - rebuild Faucet
4Comfort StationWomen's Room
1Info Center/Ranger Contact StationRestroom
1Comfort StationFamily Room
Slop Sink1Comfort StationMen's RoomMaintain Fixture As Needed - Unclog and Repair and/or rebuild Faucet
1Comfort StationWomen's Room
Drinking Fountains4Various LocationsHaws 6518.2FR Frost-Proof Drinking FountainsMaintain Fixture with no longer than a 24 hour down time during the active season As Needed - Unclog and Repair Valves faucets, etc. Every 6 Months - Rebuild Regulators
Insta-Hot1Info Center/Ranger Contact StationRestroomIn-line Hot Water HeaterMaintain Fixture As Needed - Repair/Replace Annually - Replace Filter
DWH-11Comfort StationMechanical Room55 gallon Electric Water HeaterMaintain Hot Water Heater Annual - Inspect Unit and Replace Anode Rod As Needed
Area Drains3Comfort StationFloor Area DrainsAs Needed - Unclog/snake
4Tunnels and VaultsFloor Area Drains
SensorsComfort Station/Info CenterAs needed - Maintain Sensors
Memorial Drainage
Comfort Station Gutters246.1Comfort StationPerimeterCopper Roof GutterBi-Monthly - Clean Gutters and Strainers Semi-Annual - Inspect/Repair Standing Sea, As Needed - Clear Debris
Info Station Gutters147.6Info Station
Roof DrainsComfort StationRoof DrainBi-Monthly - Clean Roof Drain As Needed - Clear Debris
Bronze Ground Drainage GratesWWII MemorialThroughoutRainbow Pool Cast Bronze Trench GratingMonthly - (Rotating around Memorial) - Unscrew, Lift, Clear and Clean Grates Monthly - Clean out Drainage trench of debris and trash

Plumbing System

EXHIBIT 2

NPS WWII Equipment, Systems, and Maintenance Items

Backflow Preventers
RP-41Tunnels and VaultsMain VaultFountain System Backflow PreventerAnnual - Test, Calibrate, and Certify by Certified Backflow Technician Annual - Bleed Air Annual - Inspect and Clean
Irrigation Backflow Preventer1Tunnels and VaultsPEPCO VaultIrrigation System backflow Preventer
Sump Pits
Floor Drain Sump1Tunnels and VaultsSouth Stairwell
Floor Drain Sump1Tunnels and VaultsMain Vault
Floor Drain Sump1Tunnels and VaultsNorth Stairwell
Tidal Basin DischargeTunnels and VaultsStorm Vault
Plumbing System

Groundwater

EXHIBIT 2

NPS WWII Equipment, Systems, and Maintenance Items

GROUNDWATER SYSTEM

FixtureQtyStructureRoomLocationRequired Maintenance
Groundwater Treatment System
Chlorinator Pumps2Tunnels and VaultsStorm VaultQuarterly - Check Pumps as per O&M
Chlorine Sensors2Tunnels and VaultsStorm VaultBi-Monthly - Clean/Unclog Sensors Annual - Calibrate Probes
Chlorinator Tank60 galTunnels and VaultsStorm VaultEvery 3 Months - Check Chlorine Level and Replenish Solution (12.5% Chlorine Solution)
1Sedimentation Basins3Tunnels and VaultsStorm VaultTwice per year - Cleanout
2Oil Separator1ExteriorStorm VaultManholeTwice per year - Check Level / Empty and Clean
Gauge Log1Comfort StationEngineers OfficeWeekly - Record Flow and Maintain Gauge Log
Filtration Vessel6Tunnels and VaultsStorm VaultAnnual Inspection per the manufactures O&M
Notes:
1 The sedimentation basin has limited direct outside access and is 50 ft below Grade (50 ft head draw). Basins are permit-required confined spaces.
2 Disposal of oil separator discharge should be done in accordance with all necessary environmental regulations.

Groundwater System

Lighting

EXHIBIT 2

NPS WWII Equipment, Systems, and Maintenance Items

LIGHTING

FixtureQtyStructureRoomLocationDescriptionRequired Maintenance
Interior Lights
wall/ceiling mounted 4 ft fluorescent fixtures (2 tubes per fixture)
FA10Tunnels and VaultsPEPCO Vault2 x Fluorescent TubeMaintain Fixture and Re-lamp when outage occurs.
FA3Tunnels and VaultsStorm Vault
FA26Tunnels and VaultsTunnels
FA4Tunnels and VaultsNorth Storage Room
FA4Tunnels and VaultsSouth Storage Room
1FA16Tunnels and VaultsMain Vault
FA1Comfort StationMen's RoomJanitors Closet
FA1Comfort StationWomen's RoomJanitors Closet
FA3Comfort StationEngineers Room
FA11Comfort StationSewage Pump Room
FA3Comfort StationMechanical ClosetCeiling
FA4Comfort StationMaint. Storage AreaCeiling
FA1Info Center/Ranger Contact StationElectric Panel Room
Total87
wall/ceiling mounted 4 ft fluorescent fixtures (1 tubes per fixture)
FC9Tunnels and VaultsNorth Storage Room/North StairsFluorescent TubeMaintain Fixture and Re-lamp when outage occurs.
FC9Tunnels and VaultsSouth Storage Room/South Stairs
Total18
single 4ft tube fluorescent/staggered
FD10Comfort StationMen's RoomAbove Ceiling GratesSingle Fluorescent StaggeredMaintain Fixture and Re-lamp when outage occurs.
FD12Comfort StationWomen's RoomAbove Ceiling GratesSingle Fluorescent Staggered
FD8Comfort StationFamily RoomAbove Ceiling GratesSingle Fluorescent Staggered
Total30
single 4ft tube fluorescent/staggered
FE7Comfort StationMen's RoomCeilingCompact FluorescentMaintain Fixture and Re-lamp when outage occurs.
FE8Comfort StationWomen's RoomCeilingCompact Fluorescent
FE2Comfort StationFamily RoomCeilingCompact Fluorescent
FE10Comfort StationVestibuleCeiling Outside of BathroomsCompact Fluorescent
FE10Info Center/Ranger Contact StationCeiling/OverhangCompact Fluorescent
Total37
compact fluorescent ceiling lights
FF4Comfort StationVestibuleCeiling outside of Engr. Office2 x Fluorescent TubeMaintain Fixture and Re-lamp when outage occurs.
FF5Info Center/Ranger Contact StationRanger AreaCeiling
FF2Info Center/Ranger Contact StationBathroomCeiling
Total11

Lighting System

EXHIBIT 2

NPS WWII Equipment, Systems, and Maintenance Items

wall mounted incandescent
FJ1Info Center/Ranger Contact StationBathroomOver SinkIncandescent BulbMaintain Fixture and Re-lamp when outage occurs.
single sided exit lights
FX-18Tunnels and VaultsTunnelExit LampMaintain Fixture and Re-lamp when outage occurs.
FX-11Comfort StationMen's RoomOver Entrance
FX-11Comfort StationWomen's RoomOver Entrance
Total10
double sided exit light
FX-21Tunnels and VaultsTunnelExit LampMaintain Fixture and Re-lamp when outage occurs.
Exterior Lights
Submersible - Bronzelight (61-25-RGA-TCO)
F-120Outside/MemorialCeremonial Falls120V 120W PAR38/FLMaintain Fixture with no more than 5% outage at any given time
F-122Outside/MemorialCeremonial Pool of Stars
F-122Outside/MemorialNorth and South Arch Pools
Total64
In Ground -Exterieur - Vent (ICARE SPIC-90 Incandescent+LHIC-S)
F38Outside/MemorialCeremonial Entrance/Arches120V 60W PAR38 IncandescentMaintain Fixture with no more than 5% outage at any given time
F3-A108Outside/MemorialCeremonial Entrance/Ceremonial Pool/Outer Rampart Perimeter
Total116
Submersible - Bronzelight (6050RG)
F499Outside/MemorialIn Rainbow Pool120V 300W PAR56Maintain Fixture with no more than 5% outage at any given time
Antique Street Lamps (PI-C24 10.5 ANBK) - Lights on photo cells in conjunction with computer controlled clock - checked when dark
2F738Outside/MemorialNorth and South Along Sidewalks/Washington Globes120V MH-50WMaintain Fixture with no more than 5% outage at any given time
Submersible - Hydrel (4427)
F816Outside/MemorialRainbow Pool North and South Arch Cluster Jets120V 500W PAR64Maintain Fixture with no more than 5% outage at any given time
Sculpture Lighting - BK Lighting (LS Lite-Star Series)
3F916Outside/MemorialIn Arches/Eagles Wings and Wreaths120/12V 50W MR-16Maintain Fixture with no more than 5% outage at any given time

Lighting System

EXHIBIT 2

NPS WWII Equipment, Systems, and Maintenance Items

Flagpole Perimeter Lights - Exterieur-Vert (ICAR-SPIT-70-10-.1-ICHRB)
F108Outside/MemorialAt Flag Poles120V 70W/T6/830Maintain Fixture with no more than 5% outage at any given time
Wall Mounter - Bega (2012)
F122Outside/MemorialBronze Door Entrance at north and South Vault Stairwell120V 100W A-19Maintain Fixture with no more than 5% outage at any given time
Rope Lights - Light Project
F13108Outside/MemorialPlaza/Upper Bench Lights Under Trench GratesRope Lights, 360FT, 120V 2W/FT, 0.05A, 10 circuitsMaintain Fixture with no more than 5% outage at any given time
Recessed - Sterner (Custom Fixtures)
F1456Outside/MemorialInner Rampart2 x 120V 50W AR-11 PAR36Maintain Fixture with no more than 5% outage at any given time
Arch Lights - Exterieur Vert (PHENIX D4SC2R)
F1632Outside/MemorialFloor of Arches120V 50W MR-16Maintain Fixture with no more than 5% outage at any given time
3F16-A16Outside/MemorialCeiling of Arches120V 50W MR-16
Total48
Bench Lights - Light Project(Louvre 3 IP54)
F17112Outside/MemorialUnder Lower benches in Plaza13 x 12V 5W XenonMaintain Fixture with no more than 5% outage at any given time
Flagpole Base - Cooper Lighting (Lumiere - BOCA 633-120 BK 2CTP)
F186Outside/MemorialFlag Pole Bases in Pedestals120V 50W MR-16Maintain Fixture with no more than 5% outage at any given time
Notes:
BALLAST SHOULD BE REPLACED ON ALL APPLICABLE LAMPS AS NEEDED DURING RELAMPING
1 Some fluorescent fixture in the main vault will require a tall (35 ft) extension ladder or scaffolding in order to service.
2 Lights on photo cells in conjunction with computer controlled clock, must be checked when dark.
3 An Articulated man-lift is required to service lamps. Permission from NPS required to use onsite lift.
Lighting System

Misc.

EXHIBIT 2

NPS WWII Equipment, Systems, and Maintenance Items

EMERGENCY GENERATOR AND MAN LIFT SERVICE

SystemDescriptionRequired Maintenance
Emergency Generator
Emergency GeneratorCumminsQuarterly - Service and Diagnostic (refer to O&M) Quarterly - Testing of Emergency Power System Annual - Load Test

Miscellaneous System

File details come from the government source that posted it. Updated .