14-CSP 26-036KB BP048 Drawings.pdf
PDF 20 MB Posted
- Attached to
- BP048 HVAC - MEP West Zone 3 Package A
- Solicitation number
- CSP 26-036KB
- Issued by
- Fort Bend County, Texas
About this file
This is a complete set of construction drawings and specifications for BP048 HVAC - MEP West Zone 3, a mechanical, electrical, plumbing, and fire protection project for Fort Bend Independent School District (FBISD) at seven school campuses in the Houston area. The project encompasses HVAC upgrades at Austin High School, Bowie Middle School, Crockett Middle School, Garcia Middle School, Hodges Bend Middle School, Travis High School, and Walker Station Elementary School. The scope of work includes replacing central station air handling units with direct digital controls, replacing VAV units on the first and second floors, replacing heating water pumps with variable frequency drives, providing piping insulation on sprinkler piping in critical areas, and replacing the main shut-off valve near the cooling tower. The drawings indicate a phased design development with the schematic design/design development completed July 18, 2025; 50% construction documents dated September 29, 2025; 90% construction documents dated November 12, 2025; and issue for bid dated December 11, 2025. The project encompasses mechanical, electrical, plumbing, and fire protection systems across multiple building levels with comprehensive demolition, new installation, and refurbishment scopes.
The construction documents follow 2015 International Building Code and 2021 International codes for fire, electrical, mechanical, and plumbing with local amendments. The project requires detailed coordination among multiple trade contractors including mechanical, electrical, plumbing, fire protection, and controls contractors. Bidders are instructed to conduct site visits and verify existing conditions prior to submitting bids, with all costs for replacement, repair, relocation, or removal of existing MEP elements included in the base bid. The contractor must provide separate line-item pricing for specific installation tasks including dedicated receptacles, quad receptacles, voice/data outlets, junction boxes, light fixtures, and circuit tracing. A commissioning agent must be retained to commission mechanical and service water heating systems with capacity greater than 80 KBTU/H and lighting control systems, providing preliminary and final commissioning reports within 90 days of certificate of occupancy. The project requires one-year warranty covering all work, materials, and defects, with systems operating without malfunction through at least one full heating and cooling season.
View the file
Other files
Show all 23
On GovTribe
Work with this file
- Download the original file
- Contacts named in this file
- Similar government files
- Ask GovTribe AI about this file
Text version
A B
C D
DATE
JOB
SHEET
ISSUES
REVISIONS
AFSHI CHARANIA ANGIE WIERZBICKI ANGIE HANAN ADAM SCHOOF DR. SHIRLEY ROSE GILLIAM ADDIE HEYLIGER ARCHITECT MEP ENGINEERKRISTIN K. TASSIN
BOARD OF TRUSTEES
SHEET LIST
KEYPLAN
Date of issue:
PROJECT TEAM
/1
/2
:1 :0
P
M
.COVER
COVER SHEET
12.11.2025
25241.0000
FORT BEND ISD
BP048 HVAC - MEP ZONE 3
ISSUE FOR BID
POSITION 3 POSITION 7 VICE PRESIDENT POSITION 2 SECRETARY POSITION 5 CORGAN ASSOCIATES, INC
16431 Lexington Blvd T: Sugar Land, TX 77479
F: 281.634.5590 CONTACT: Contact: Juan Valdez email: cn_juan.valdez@fortbendisd.gov
POSITION 1 POSITION 4 9 GREENWAY PLAZA, HOUSTON TX, 77046
(ctrl+Enter for 2nd line)
T: (832) 652-3640
YW-SQUARED
2508 REPPART PLACE, HOUSTON TX 77008
T: (832) 384-4178
BOARD PRESIDENT
POSITION 6
2 09.29.2025 50% CDs
1 07.18.2025 SD / DD
3 11.12.2025 90% CDs
4 12.11.2025 ISSUE FOR BID
.C O
V E
R
C O
V E
R S
H E
E T
12.11.2025
B P
H
V A
C
M E
P Z
O N
E www.corgan.com T: 214.748.2000
SHEET INDEX
Discipline
SHEET
NO. SHEET NAME SD / DD 50% CD 90% CD
ISSUE
FOR BID
01 - GENERAL
01 - GENERAL .COVER COVER SHEET Yes Yes Yes Yes
AUSTIN HIGH SCHOOL
AUSTIN HIGH SCHOOL A-A00.00 COVER SHEET Yes Yes Yes Yes
AUSTIN HIGH SCHOOL A-E00-00 - ELECTRICAL COVER SHEET Yes Yes Yes Yes
AUSTIN HIGH SCHOOL A-E10-01 ELECTRICAL DEMOLITION PLAN - LEVEL 01 - OVERALL Yes Yes Yes Yes
AUSTIN HIGH SCHOOL A-E10-02 ELECTRICAL DEMOLITION PLAN - LEVEL 02 - OVERALL Yes Yes Yes Yes
AUSTIN HIGH SCHOOL A-E20-01 ELECTRICAL POWER PLAN - LEVEL 01 - OVERALL Yes Yes Yes Yes
AUSTIN HIGH SCHOOL A-E20-02 ELECTRICAL POWER PLAN - LEVEL 02- OVERALL Yes Yes Yes Yes
AUSTIN HIGH SCHOOL A-E30-01 ELECTRICAL ENLARGED PLANS - LEVEL 1 No No No Yes
AUSTIN HIGH SCHOOL A-E30-02 ELECTRICAL ENLARGED PLANS - LEVEL 2 No No No Yes
AUSTIN HIGH SCHOOL A-E40-00 ELECTRICAL DETAILS Yes Yes Yes Yes
AUSTIN HIGH SCHOOL A-FP00-00 - FIRE PROTECTION COVER SHEET No Yes Yes Yes
AUSTIN HIGH SCHOOL A-FP20-01 FIRE PROTECTION PLAN - LEVEL 01 - OVERALL Yes Yes Yes Yes
AUSTIN HIGH SCHOOL A-M00-00 MECHANICAL COVER SHEET Yes Yes Yes Yes
AUSTIN HIGH SCHOOL A-M10-01 MECHANICAL DEMOLITION PLAN - LEVEL 01 - OVERALL Yes Yes Yes Yes
AUSTIN HIGH SCHOOL A-M10-02 MECHANICAL DEMOLITION PLAN - LEVEL 02 - OVERALL Yes Yes Yes Yes
AUSTIN HIGH SCHOOL A-M20-01 MECHANICAL PLAN - LEVEL 01 - OVERALL Yes Yes Yes Yes
AUSTIN HIGH SCHOOL A-M20-02 MECHANICAL PLAN - LEVEL 02 - OVERALL Yes Yes Yes Yes
AUSTIN HIGH SCHOOL A-M20-03 MECHANICAL ENLARGED PLANS No No No Yes
AUSTIN HIGH SCHOOL A-M20-04 MECHANICAL ENLARGED PLANS No No No Yes
AUSTIN HIGH SCHOOL A-M20-05 - MECHANICAL ENLARGED PLANS No No No Yes
AUSTIN HIGH SCHOOL A-M30-00 MECHANICAL SCHEDULES Yes Yes Yes Yes
AUSTIN HIGH SCHOOL A-M40-00 MECHANICAL DETAILS Yes Yes Yes Yes
AUSTIN HIGH SCHOOL A-M40-01 MECHANICAL DETAILS No No No Yes
AUSTIN HIGH SCHOOL A-M50-00 MECHANICAL CONTROLS No No No Yes
AUSTIN HIGH SCHOOL A-M50-01 MECHANICAL CONTROLS No No No Yes
AUSTIN HIGH SCHOOL A-M50-02 MECHANICAL CONTROLS No No No Yes
AUSTIN HIGH SCHOOL A-P20-01 PLUMBING PLAN - LEVEL 01 - OVERALL Yes Yes Yes Yes
BOWIE MIDDLE SCHOOL
BOWIE MIDDLE SCHOOL B-A00.00 COVER SHEET Yes Yes Yes Yes
BOWIE MIDDLE SCHOOL B-E00-00 ELECTRICAL COVER SHEET Yes Yes Yes Yes
BOWIE MIDDLE SCHOOL B-E10-01 ELECTRICAL DEMOLITION PLAN - LEVEL 01 - OVERALL Yes Yes Yes Yes
BOWIE MIDDLE SCHOOL B-E20-01 ELECTRICAL POWER PLAN - LEVEL 01 - OVERALL Yes Yes Yes Yes
BOWIE MIDDLE SCHOOL B-E30-01 ELECTRICAL PANEL SCHEDULES No Yes Yes Yes
BOWIE MIDDLE SCHOOL B-E40-00 ELECTRICAL DETAILS Yes Yes Yes Yes
BOWIE MIDDLE SCHOOL B-M00-00 MECHANICAL COVER SHEET Yes Yes Yes Yes
BOWIE MIDDLE SCHOOL B-M10-01 MECHANICAL DEMOLITION PLAN - LEVEL 01 - OVERALL Yes Yes Yes Yes
BOWIE MIDDLE SCHOOL B-M20-01 MECHANICAL PLAN - LEVEL 01 - OVERALL Yes Yes Yes Yes
BOWIE MIDDLE SCHOOL B-M30-00 MECHANICAL SCHEDULES Yes Yes Yes Yes
BOWIE MIDDLE SCHOOL B-M40-00 MECHANICAL DETAILS Yes Yes Yes Yes
CROCKETT MIDDLE SCHOOL
CROCKETT MIDDLE SCHOOL C-A0.00 COVER SHEET Yes Yes Yes Yes
CROCKETT MIDDLE SCHOOL C-E00-00 ELECTRICAL COVER SHEET Yes Yes Yes Yes
CROCKETT MIDDLE SCHOOL C-E10-01 ELECTRICAL DEMOLITION PLAN - LEVEL 01 - OVERALL Yes Yes Yes Yes
CROCKETT MIDDLE SCHOOL C-E20-01 ELECTRICAL POWER PLAN - LEVEL 01 - OVERALL Yes Yes Yes Yes
CROCKETT MIDDLE SCHOOL C-E30-01 ELECTRICAL PANEL SCHEDULES Yes Yes Yes Yes
CROCKETT MIDDLE SCHOOL C-E40-00 ELECTRICAL DETAILS Yes Yes Yes Yes
CROCKETT MIDDLE SCHOOL C-FP00-00 FIRE PROTECTION COVER SHEET No Yes Yes Yes
CROCKETT MIDDLE SCHOOL C-FP20-01 FIRE PROTECTION PLAN - LEVEL 01 - OVERALL No No No Yes
CROCKETT MIDDLE SCHOOL C-FP20-02 FIRE PROTECTION PLAN - LEVEL 02 - OVERALL No Yes Yes Yes
CROCKETT MIDDLE SCHOOL C-M00-00 MECHANICAL COVER SHEET Yes Yes Yes Yes
CROCKETT MIDDLE SCHOOL C-M10-01 MECHANICAL DEMOLITION PLAN - LEVEL 01 - OVERALL Yes Yes Yes Yes
CROCKETT MIDDLE SCHOOL C-M20-01 MECHANICAL PLAN - LEVEL 01 - OVERALL Yes Yes Yes Yes
CROCKETT MIDDLE SCHOOL C-M30-00 MECHANICAL SCHEDULES Yes Yes Yes Yes
CROCKETT MIDDLE SCHOOL C-M40-00 MECHANICAL DETAILS Yes Yes Yes Yes
GARCIA MIDDLE SCHOOL
GARCIA MIDDLE SCHOOL G-A00.00 COVER SHEET Yes Yes Yes Yes
GARCIA MIDDLE SCHOOL G-E00-00 ELECTRICAL COVER SHEET Yes Yes Yes Yes
GARCIA MIDDLE SCHOOL G-E10-01 ELECTRICAL DEMOLITION PLAN - LEVEL 01 - OVERALL Yes Yes Yes Yes
GARCIA MIDDLE SCHOOL G-E20-01 ELECTRICAL POWER PLAN - LEVEL 01 - OVERALL Yes Yes Yes Yes
GARCIA MIDDLE SCHOOL G-E40-00 ELECTRICAL DETAILS Yes Yes Yes Yes
GARCIA MIDDLE SCHOOL G-FP00-00 FIRE PROTECTION COVER SHEET No Yes Yes Yes
GARCIA MIDDLE SCHOOL G-FP20-01 FIRE PROTECTION PLAN - LEVEL 01 - OVERALL Yes Yes Yes Yes
GARCIA MIDDLE SCHOOL G-FP20-02 FIRE PROTECTION PLAN - LEVEL 02 - OVERALL Yes No Yes Yes
GARCIA MIDDLE SCHOOL G-M00-00 MECHANICAL COVER SHEET No Yes Yes Yes
GARCIA MIDDLE SCHOOL G-M10-01 MECHANICAL DEMOLITION PLAN - LEVEL 01 - OVERALL No Yes Yes Yes
GARCIA MIDDLE SCHOOL G-M20-01 MECHANICAL PLAN - LEVEL 01 - OVERALL Yes Yes Yes Yes
GARCIA MIDDLE SCHOOL G-M30-00 MECHANICAL SCHEDULES Yes Yes Yes Yes
GARCIA MIDDLE SCHOOL G-M40-00 MECHANICAL DETAILS Yes Yes Yes Yes
HODGES BEND MIDDLE SCHOOL
HODGES BEND MIDDLE SCHOOL H-A0.00 COVER SHEET Yes Yes Yes Yes
HODGES BEND MIDDLE SCHOOL H-E00-00 ELECTRICAL COVER SHEET Yes Yes Yes Yes
HODGES BEND MIDDLE SCHOOL H-E10-01 ELECTRICAL DEMOLITION PLAN - LEVEL 01 - OVERALL Yes Yes Yes Yes
HODGES BEND MIDDLE SCHOOL H-E20-01 ELECTRICAL POWER PLAN - LEVEL 01 - OVERALL Yes Yes Yes Yes
HODGES BEND MIDDLE SCHOOL H-E30-01 ELECTRICAL PANEL SCHEDULES No Yes Yes Yes
HODGES BEND MIDDLE SCHOOL H-E40-00 ELECTRICAL DETAILS Yes Yes Yes Yes
HODGES BEND MIDDLE SCHOOL H-FP00-00 FIRE PROTECTION COVER SHEET No Yes Yes Yes
HODGES BEND MIDDLE SCHOOL H-FP20-01 FIRE PROTECTION PLAN - LEVEL 01 - OVERALL Yes Yes Yes Yes
HODGES BEND MIDDLE SCHOOL H-FP20-02 FIRE PROTECTION PLAN - LEVEL 02 - OVERALL No Yes Yes Yes
HODGES BEND MIDDLE SCHOOL H-M00-00 MECHANICAL COVER SHEET Yes Yes Yes Yes
HODGES BEND MIDDLE SCHOOL H-M10-01 MECHANICAL DEMOLITION PLAN - LEVEL 01 - OVERALL Yes Yes Yes Yes
HODGES BEND MIDDLE SCHOOL H-M20-01 MECHANICAL PLAN - LEVEL 01 - OVERALL Yes Yes Yes Yes
HODGES BEND MIDDLE SCHOOL H-M30-00 MECHANICAL SCHEDULES Yes Yes Yes Yes
HODGES BEND MIDDLE SCHOOL H-M40-00 MECHANICAL DETAILS Yes Yes Yes Yes
HODGES BEND MIDDLE SCHOOL H-P20-01 PLUMBING PLAN - LEVEL 01 - OVERALL Yes Yes Yes Yes
SHEET INDEX
Discipline
SHEET
NO. SHEET NAME SD / DD 50% CD 90% CD
ISSUE
FOR BID
TRAVIS HIGH SCHOOL
TRAVIS HIGH SCHOOL T-A00.00 COVER SHEET Yes Yes Yes Yes
TRAVIS HIGH SCHOOL T-E00-00 ELECTRICAL COVER SHEET Yes Yes Yes Yes
TRAVIS HIGH SCHOOL T-E10-01 ELECTRICAL DEMOLITION PLAN - LEVEL 01 - OVERALL Yes Yes Yes Yes
TRAVIS HIGH SCHOOL T-E10-02 ELECTRICAL DEMOLITION PLAN - LEVEL 02 - OVERALL Yes Yes Yes No
TRAVIS HIGH SCHOOL T-E20-01 ELECTRICAL POWER PLAN - LEVEL 01 - OVERALL Yes Yes Yes Yes
TRAVIS HIGH SCHOOL T-E20-02 ELECTRICAL POWER PLAN - LEVEL 02- OVERALL Yes Yes Yes No
TRAVIS HIGH SCHOOL T-E30-00 ELECTRICAL SCHEDULES & DIAGRAMS Yes Yes Yes Yes
TRAVIS HIGH SCHOOL T-E40-00 ELECTRICAL DETAILS Yes Yes Yes Yes
TRAVIS HIGH SCHOOL T-FP00-00 FIRE PROTECTION COVER SHEET No Yes Yes Yes
TRAVIS HIGH SCHOOL T-FP20-01 FIRE PROTECTION PLAN - LEVEL 01 - OVERALL Yes Yes Yes Yes
TRAVIS HIGH SCHOOL T-M00-00 MECHANICAL COVER SHEET Yes Yes Yes Yes
TRAVIS HIGH SCHOOL T-M10-01 MECHANICAL DEMOLITION PLAN - LEVEL 01 - OVERALL Yes Yes Yes Yes
TRAVIS HIGH SCHOOL T-M10-02 MECHANICAL DEMOLITION PLAN - LEVEL 02 - OVERALL Yes Yes Yes Yes
TRAVIS HIGH SCHOOL T-M20-01 MECHANICAL PLAN - LEVEL 01 - OVERALL No Yes Yes Yes
TRAVIS HIGH SCHOOL T-M20-02 MECHANICAL PLAN - LEVEL 02 - OVERALL No Yes Yes Yes
TRAVIS HIGH SCHOOL T-M30-00 MECHANICAL SCHEDULES No Yes Yes Yes
TRAVIS HIGH SCHOOL T-M40-00 MECHANICAL DETAILS No Yes Yes Yes
TRAVIS HIGH SCHOOL T-M50-00 MECHANICAL CONTROLS No No No Yes
WALKER STATION ELEMENTARY SCHOOL
WALKER STATION ELEMENTARY SCHOOL W-A00.00 COVER SHEET No No No Yes
WALKER STATION ELEMENTARY SCHOOL W-FP00-00 FIRE PROTECTION COVER SHEET No No No Yes
WALKER STATION ELEMENTARY SCHOOL W-FP20-01 FIRE PROTECTION PLAN - LEVEL 01 - OVERALL No No No Yes
FORT BEND ISD 2023 BOND PROGRAM
HVAC MEP WEST ZONE 3
AUSTIN HIGH SCHOOL
3434 PHEASANT CREEK DR, SUGAR LAND, TX 77498
BOWIE MIDDLE SCHOOL
700 PLANTATION DRIVE, RICHMOND TX 77406
CROCKETT MIDDLE SCHOOL
19001 BEECHNUT ST. RICHMOND TX 77407
GARCIA MIDDLE SCHOOL
18550 OLD RICHMOND RD. SUGAR LAND TX 77498
HODGES BEND MIDDLE SCHOOL
16510 BISSONNETT STREET, HOUSTON TX 77083
TRAVIS HIGH SCHOOL
11111 HARLEM ROAD, RICHMOND TX 77046
WALKER STATION ELEMENTARY SCHOOL
6200 HOMEWARD WAY, SUGAR LAND TX 77479
PROJECT MAP
DATE
JOB
SHEET
ISSUES
REVISIONS
SHEET LIST
KEYPLAN
This Document was produced by or under the authority of Registered Architect:
Date of issue:
This document is incomplete and may not be used for regulatory approval, permit or construction.
/2
/2
:5 :0
P
M
COVER SHEET
9.29.2025
25241.000
16431 Lexington Blvd T: Sugar Land, TX 77479
F: 281.634.5590 CONTACT: Contact: Juan Valdez email: cn_juan.valdez@fortbendisd.com
2 09.29.2025 50% CDs
1 07.18.2025 SD / DD
4 12.11.2025 ISSUE FOR BID
C O
V E
R S
H E
E T
9.29.2025
9 GREENWAY PLAZA SUITE 3000
T: HOUSTON, TX 77046
F O
R T
B E
N D
I S
D B
P
H V
A C
M E
P W
E S
T
PROJECT DATA
PROJECT NAME:
PROJECT ADDRESS:
APPLICABLE CODES
LIFE SAFETY INFORMATION
USE OR OCCUPANCY CLASSIFICATION
OCCUPANCY:
TYPE OF CONSTRUCTION
CONSTRUCTION TYPE:
PROJECT SCOPE
OWNER:
BUILDING CODE:
ACCESSIBILITY CODE:
ELECTRICAL CODE:
ENERGY CODE:
FIRE CODE:
MECHANICAL CODE:
PLUMBING CODE:
REGIONAL OR MUNICIPAL CODE:
FORT BEND ISD
BP048 - HVAC MEP WEST 3 - AUSTIN HS
50% CONSTRUCTION DOCUMENTS
A U
S T
IN
H
S
P H
E A
S A
N T
C R
E E
K D
R
S U
G A
R L
A N
D
T X
PROJECT MAP
A-A00.00
BP048 - HVAC - MEP WEST 3
AUSTIN HIGH SCHOOL
3434 PHEASANT CREEK DRIVE SUGAR LAND, TX 77498
FBISD
2015 INTERNATIONAL BUILDING CODE
2012 TEXAS ACCESSIBILTY STANDARDS
2023 STATE OF TEXAS ADOPTED NATIONAL ELECTRICAL CODE
2015 INTERNATIONAL ENERGY CONSERVATIVE CODE
2021 INTERNATIONAL FIRE CODE
2021 INTERNATIONAL MECHANICAL CODE
2015 INTERNATIONAL PLUMBING CODE
FORT BEND COUNTY
E-1 EDUCATION
II B
REPLACE CENTRAL STATION AHUs AND PROVIDE DIRECT DIGITAL CONTROLS
REPLACE VAV UNITS ON THE FIRST AND SECOND FLOOR
REPLACE HEATING WATER PUMPS AND PROVIDE VARIABLE FREQUENCY DRIVE (VFDs)
PROVIDE PIPING INSULATION ON SPRINKLER PIPING IN CRITICAL AREAS5
REPLACE MAIN SHUT OFF VALVE NEAR COOLING TOWER
90% CONSTRUCTION DOCUMENTS
11.12.2025 90% CDs
11.12.2025
11.12.2025
/1
2/
:3
P M
Date of issue:
12.11.2025
FORT BEND ISD
BP048 - HVAC MEP WEST ZONE 3 - AUSTIN HS
ISSUE FOR BID
12.11.2025
/1
2/
:3
P M
/1 1/
1:
A
M
FO
R
T
BE
N D
IS
D
B P0
H
V A
C M
E P
W E
S T
Z O
N E
AV AVAV
J
J
TV
C
PP
ABBREVIATIONS
(E) EXISTING TO REMAIN
(ER) EXISTING TO BE RE-CIRCUITED
(N) NEW
(R) ITEM NOTED TO BE RELOCATED
(D) ITEM NOTED TO BE DEMOLISHED
AFF ABOVE FINISHED FLOOR
AD AUTOMATIC DAMPER
AIC AMPERE INTERRUPTING CAPACITY
AL ALUMINUM
AMP AMPERAGE
ATS AUTOMATIC TRANSFER SWITCH
AWG AMERICAN WIRE GAUGE
BKR BREAKER
C CONDUIT
CKT. CIRCUIT
CT CURRENT TRANSFORMER
DC DIRECT CURRENT
DISC. DISCONNECT
EC ELECTRICAL CONTRACTOR
EMT ELECTRICAL METALLIC TUBING
EPO EMERGENCY POWER OFF
FA FIRE ALARM
FACP FIRE ALARM CONTROL PANEL
FC FOOT CANDLE
FLA FULL LOAD AMPS
GC GENERAL CONTRACTOR
GFI GROUND FAULT CIRCUIT INTERRUPTER
GND. GROUND
HD HEAVY DUTY
HOA HAND-OFF-AUTO
HP HORSEPOWER
IG ISOLATED GROUND
KCM THOUSAND CIRCULAR MILS
KW KILOWATT
MC METAL CLAD
MCB MAIN CIRCUIT BREAKER
MH METAL HALIDE
MSB MAIN SWITCHBOARD
MLO MAIN LUG ONLY
NEC NATIONAL ELECTRIC CODE
NEMA NATIONAL ELECTRICAL MANUFACTURES ASSOCIATION
NFPA NATIONAL FIRE PROTECTION ASSOCIATION
NIC NOT IN CONTRACT
NF NON-FUSED
NL NIGHT LIGHT
NTS NOT TO SCALE
PH PHASE
PNL PANEL OR PANELBOARD
PVC POLYVINYL CHLORIDE
RACP REMOTE ANNUNCIATOR CONTROL PANEL
RCP REFLECTED CEILING PLAN
RE: REFERENCE
SFD SMOKE/FIRE DAMPER
SPEC. SPECIFICATIONS
SF SQUARE FEET
TS TIME SWITCH
TTB TELEPHONE TERMINAL BOARD
TYP TYPICAL
UG UNDERGROUND
U.N.O. UNLESS NOTED OTHERWISE
UPS UNINTERRUPTIBLE POWER SUPPLY
V VOLTAGE
VFD VARIABLE FREQUENCY DRIVE
WP WEATHER PROOF
XFMR TRANSFORMER
APPLICABLE CODES & STANDARDS
1. BUILDING CODE - 2015 IBC WITH LOCAL AMENDMENTS
2. FIRE CODE - 2021 IFC WITH LOCAL AMENDMENTS
3. ELECTRICAL CODE - 2023 NEC WITH LOCAL AMENDMENTS
4. MECHANICAL CODE - 2021 IMC WITH LOCAL AMENDMENTS
5. PLUMBING CODE - 2015 IPC WITH LOCAL AMENDMENTS
6. ENERGY CODE - 2015 INTERNATIONAL ENERGY CONSERVATION CODE WITH LOCAL
AMENDMENTS.
7. OTHER - LIFE SAFETY CODE (NFPA 101)
8. OTHER - FEDERAL DEPARTMENT OF JUSTICE AMERICANS WITH DISABILITIES ACT AND TEXAS
ACCESSIBILITY STANDARDS.
9. FIRE ALARM - 2021 NFPA 72 WITH LOCAL AMENDMENTS.
BREAK OUT PRICING
THE CONTRACTOR SHALL PROVIDE SEPARATE LINE-ITEM COST FOR ALL WORK AND MATERIALS ASSOCIATED
WITH EACH OF THE FOLLOWING:
1. INSTALLATION FOR ONE (1) DEDICATED 20-AMP DUPLEX RECEPTACLE.
2. INSTALLATION FOR ONE (1) DEDICATED 20-AMP QUAD RECEPTACLE.
3. INSTALLATION FOR ONE (1) RING AND STRING ROUGH-IN FOR VOICE/DATA OUTLET.
4. INSTALLATION FOR ONE (1) DEDICATED 120-VOLT JUNCTION BOX.
5. INSTALLATION FOR ONE (1) LAY-IN 2'X4' LIGHT FIXTURE ON AN EXISTING 277-VOLT SWITCHED CIRCUIT
WITH 8 FT OF CONDUIT/CONDUCTORS.
6. CIRCUIT TRACE OF ALL EXISTING CIRCUITS IN ALL PANELS USED IN THIS PROJECT. SEE PANEL
SCHEDULES.
PRICES SHALL INCLUDE ALL INSTALLATION COST, INCLUDING CONDUIT(S) AND BRANCH CIRCUIT CONDUCTORS AS REQUIRED. ASSUME 100 FT CONDUIT AND CONDUCTOR LENGTH FROM SOURCE TO LOAD U.N.O.
ELECTRICAL GENERAL NOTES
A. GENERAL PROVISIONS
1. FURNISH AND INSTALL ALL ITEMS, INCLUDING EVERY ARTICLE , DEVICE OR ACCESSORY REASONABLY NECESSARY TO FACILITATE EACH
SYSTEM'S FUNCTIONING AS INDICATED BY THE DESIGN AND THE EQUIPMENT SPECIFIED. ELEMENTS OF THE WORK SHALL INCLUDE, BUT ARE NOT LIMITED TO, MATERIALS, LABOR, SUPERVISIONS, SUPPLIES, EQUIPMENT, TRANSPORTATION, HOISTING/RIGGING, STORAGE, UTILITIES, AND ALL REQUIRED PERMITS AND LICENSES.
2. DRAWINGS ARE SCHEMATIC IN NATURE AND DO NOT NECESSARILY REFLECT ALL WORK REQUIRED TO COMPLETE PROJECT. CONTRACTOR SHALL PROVIDE ALL MATERIALS, LABOR, AND EQUIPMENT AS REQUIRED TO COMPLETE PROJECT WITHIN DESIGN INTENT AT NO ADDITIONAL COST TO OWNER/TENANT. CONTRACTOR SHALL REQUEST ADDITIONAL INFORMATION IN CASES OF DOUBT.
3. WORK SHALL COMPLY WITH THE MOST RECENT VERSION OF ALL APPLICABLE LAWS, RULES, REGULATIONS, AND ORDINANCES OF ALL FEDERAL, STATE, AND LOCAL AUTHORITIES. IN THE EVENT OF CONFLICT BETWEEN THE CONTRACT DOCUMENTS AND THE LOCAL ENFORCING AUTHORITY, THE LATTER SHALL RULE. ANY MODIFICATION RESULTING THEREFROM SHALL BE MADE WITHOUT ADDITIONAL COST TO THE OWNER OR ARCHITECT/ENGINEER. THE CONTRACTOR SHALL REPORT ANY SUCH MODIFICATIONS TO THE ARCHITECT/ENGINEER AND SECURE THEIR APPROVAL BEFORE PROCEEDING. SHOULD THE REQUIREMENTS OF THE CONTRACT DUCMENTS EXCEED THE REQUIREMENTS OF THE CODES, THE CONTRACT DOCUMENTS SHALL TAKE PRECEDENCE PROVIDED THEY ARE NOT IN
CONFLICT WITH THOSE CODES.
4. AREAS OF THE EXISTING BUILDING WILL BE OCCUPIED DURING CONSTRUCTION OF THIS PROJECT. NOISY, DUSTY, AND/OR OTHER CONSTRUCTION OPERATIONS REQUIRED FOR WORK WHICH DISTURB OR CAUSE COMPLAINTS BY THE EXISTING BUILDING OCCUPANTS SHALL NOT BE ACCEPTABLE. ALL AFTER-HOUR OR OVERTIME WORK REQUIRED BY THE CONTRACTOR TO AVOID DISRUPTION OF EXISTING OCCUPANTS WILL BE PROVIDED AT NO COST TO THE OWNER/TENANT. THE CONTRACTOR SHALL USE CONSTRUCTION METHODS AND MATERIALS WHICH SHALL NOT ADVERSELY AFFECT THE INDOOR AIR QUALITY OF THE EXISTING OCCUPIED AREAS.
5. CONSIDERATION SHALL NOT BE GRANTED FOR MISUNDERSTANDING OF THE SCOPE OR AMOUNT OF WORK TO BE PERFORMED. TENDER OF A PROPOSAL CONVEYS FULL CONTRACTOR AGREEMENT OF THE ITEMS AND CONDITIONS SPECIFIED AND/OR INDICATED, SCHEDULED, OR
IMPLIED ON THE CONTRACT DOCUMENTS, AND/OR REQUIRED BY THE NATURE OF THIS WORK.
6. IN THE EVENT OF A CONFLICT BETWEEN DRAWINGS AND/OR SPECIFICATIONS, THE GREATER AMOUNT OF TOTAL COST SHALL BE PRICED.
BRING THE CONFLICT TO THE ATTENTION OF THE ENGINEER AND REQUEST DIRECTION.
B. PRE-CONSTRUCTION
1. BEFORE SUBMITTING A BID, IT WILL BE NECESSARY FOR EACH CONTRACTOR WHOSE WORK IS INVOLVED TO VISIT THE SITE AND ASCERTAIN
FOR THEMSELVES THE CONDITIONS TO BE MET IN INSTALLING THE WORK AND MAKE PROVISIONS FOR THE CONDITIONS IN THEIR FINAL PRICE. FAILURE ON THE PART OF THE CONTRACTOR TO COMPLY WITH THIS REQUIREMENT SHALL NOT BE CONSIDERED JUSTIFICATION FOR THE OMISSION OR FAULTY INSTALLATION OF ANY WORK COVERED BY THE CONTRACT DOCUMENTS.
2. THIS CONTRACTOR SHALL SECURE ALL PERMITS, LICENSES AND INSPECTIONS REQUIRED FOR THEIR WORK, AND SHALL PAY ALL FEES IN
CONNECTION WITH SUCH PERMITS, LICENSES AND INSPECTIONS.
C. DEMOLITION
1. ALL EXISTING CONDUIT AND CONDUCTORS SERVING THE AREA UNDER CONTRACT NOT TO BE RE-USED SHALL BE TERMINATED AT LAST
PORTION OF CIRCUIT REQUIRING ENERGIZATION BEFORE THE DEMOLITION AREA. IF A CIRCUIT SERVICES ONLY THE DEMOLITION AREA, REMOVE ALL CONDUITS AND CONDUCTORS BACK TO THE PANELBOARD OR BASE BUILDING GRID BOX AND DE-ENERGIZE THE CIRCUIT BREAKER, MAKING IT A SPARE. NOTE "SPARE" OR "GRID-SPARE" ACCORDINGLY ON PANELBOARD DIRECTORY.
2. REMOVE ALL ABANDONED LOW VOLTAGE CABLING INCLUDING FIRE ALARM CABLING, TELEPHONE/DATA CABLING, AND SECURITY CABLING.
REMOVE ALL EXISTING CONDUIT AND WIRING THAT IS SUPPORTED FROM THE CEILING GRID. REMOVE ALL EXISTING UNUSED ELECTRICAL
EQUIPMENT, CONTROLS, CONDUIT, HANGERS, WIRING, ETC.
3. RELOCATE AND RECONNECT ACTIVE PORTIONS OF THE ELECTRICAL SYSTEM OUTSIDE OF THE SCOPE OF DEMOLITION, AS REQUIRED TO MAINTAIN A COMPLETE AND OPERATING SYSTEM THAT IS FUNCTIONALLY EQUIVALENT TO THE PRE-EXISTING SYSTEM PRIOR TO
DEMOLITION.
4. ELECTRICAL PLANS INDICATE FINAL WIRING DEVICE, DATA/COMMUNICATIONS OUTLET AND SWITCH LOCATIONS. ALL OTHER EXISTING WIRING DEVICES, DATA/COMMUNICATIONS OUTLETS AND SWITCHES SHALL BE REMOVED AND WALLS SHALL BE PATCHED, UNLESS
OUTSIDE OF SCOPE OR NOTED AS (E).
5. ALL EXISTING JUNCTION BOXES, OUTLETS, PULL BOXES, ETC., LOCATED ABOVE NON-ACCESSIBLE CEILINGS INSTALLED UNDER THIS TENANT IMPROVEMENT PROJECT SHALL BE RELOCATED AS NECESSARY TO A LOCATION ABOVE AN ACCESSIBLE CEILING. WHERE EXISTING JUNCTION BOXES ARE NOT PRACTICAL TO RE-LOCATE, ELECTRICAL CONTRACTOR SHALL NOTIFY ARCHITECT AND ENGINEER PRIOR TO
SUBSTANTIAL START OF CONSTRUCTION.
6. REMOVE ALL EXISTING UNUSED ELECTRICAL EQUIPMENT, CONTROLS, CONDUIT, HANGERS, WIRING, ETC.. FROM ABOVE CEILINGS.
7. REFER TO ARCHITECTURAL DRAWINGS FOR LIGHT FIXTURES TO BE RELOCATED. RELOCATE AND RECIRCUIT FIXTURES AS SHOWN.
PROVIDE ADDITIONAL FIXTURES TO MATCH FIXTURE QUANTITIES SHOWN. FIELD VERIFY EXISTING CONDITIONS.
8. REFER TO ARCHITECTURAL PLANS FOR WALL AND PARTITIONS TO BE REMOVED. CONTRACTOR SHALL PROVIDE ELECTRICAL DEMOLITION
AS PREVIOUSLY DESCRIBED.
9. REFER TO ARCHITECTURAL DRAWINGS FOR RECEPTACLES AND VOICE/DATA OUTLETS TO BE REMOVED. FIELD VERIFY EXISTING
CONDITIONS.
10. CONTRACTOR SHALL REMOVE AND REPLACE ALL WIRING DEVICES NOT CONFORMING TO BUILDING STANDARDS.
11. REMOVE ALL EXISTING CONDUIT AND WIRING THAT IS SUPPORTED FROM THE CEILING GRID VIA CADDY CLIPS, ETC. AND REPLACE EXISTING CONDUIT THAT IS TO BE REUTILIZED WITH MATCHING CONDUIT AND WIRING PROPERLY SUPPORTED FROM STRUCTURE ABOVE.
12. RE-SUPPORT AND/ RE-ROUTE ANY REMAINING PIPING OR DEVICES THAT WERE SUPPORTED BY DEMOLISHED WALLS.
13. ALL ITEMS INSTALLED IN AIR PLENUMS SHALL BE PLENUM RATED.
D. SUBMITTALS
1. ALL EQUIPMENT AND MATERIAL TO BE FURNISHED AND INSTALLED ON THIS PROJECT SHALL BE UL OR ETL LISTED, IN ACCORDANCE WITH
THE AUTHORITY HAVING JURISDICTION, AND SUITABLE FOR ITS INTENDED USE ON THIS PROJECT.
2. THE CONTRACTOR SHALL PROVIDE SUBMITTALS FOR ALL NEW EQUIPMENT, CONTROLS, DEVICES, AND FIXTURES TO BE PROVIDED. SUBMIT
MINIMUM ELECTRONIC SUBMITTALS FOR APPROVAL.
3. MATERIALS AND EQUIPMENT SHALL BE NEW AND IN GOOD CONDITION. THE COMMERCIALLY STANDARD ITEMS OF EQUIPMENT AND THE SPECIFIC NAMES INDICATED ARE INTENDED TO IDENTIFY STANDARDS OF QUALITY AND PERFORMANCE NECESSARY FOR THE PROPER FUNCTIONING OF THE WORK. MATERIALS AND EQUIPMENT, WHICH ARE FOUND TO HAVE FACTORY DEFECTS SHALL BE REPLACED OR REPAIRED IN A MANNER ACCEPTABLE TO THE OWNER/TENANT AND ENGINEER AT NO ADDITIONAL COST TO THE OWNER/TENANT.
4. THE FOLLOWING SUBMITTAL DATA SHALL BE FURNISHED AND SHALL INCLUDE BUT NOT BE LIMITED TO:
A. EQUIPMENT AND MATERIALS SHOP DRAWINGS
B. COORDINATION DRAWINGS
C. RECORD DRAWINGS
D. OPERATING AND MAINTENANCE MANUALS
E. FIRE STOP MATERIALS AND DETAILS
E. PRE-CONSTRUCTION FUNCTIONAL TEST
1. PRIOR TO ANY CONSTRUCTION, THE CONTRACTOR SHALL FUNCTIONALLY TEST ALL ELECTRICAL AND FIRE ALARM EQUIPMENT THAT IS
EXISTING TO REMAIN OR RELOCATED IN THIS PROJECT. THE CONTRACTOR SHALL PROVIDE A WRITTEN DESCRIPTION OF ANY AND ALL DEFICIENCIES TO THE OWNER/TENANT. ANY DEFICIENCIES FOUND AFTER THE START OF CONSTRUCTION SHALL BE REPAIRED OR REPLACED AT NO COST TO THE OWNER/TENANT. THE EQUIPMENT TO BE TESTED INCLUDES, BUT IS NOT LIMITED TO: RECEPTACLES, LIGHT FIXTURES, EXIT SIGNS, OCCUPANCY SENSORS, PANEL BOARDS, TRANSFORMERS, EMERGENCY LIGHTING BATTERY UNITS, AND SWITCHES.
2. FOR EXISTING LIGHT FIXTURES AND EXIT SIGNS WITH BATTERY PACKS, ELECTRICAL CONTRACTOR SHALL ASSUME NEW BATTERY PACKS
WILL BE REQUIRED UNLESS FUNCTIONAL TEST PROVES OTHERWISE.
E. CONSTRUCTION
1. ALL WORK SHALL BE ARRANGED IN A NEAT, WELL ORGANIZED MANNER. ALL SERVICES SHALL BE ROUTED PARALLEL AND PERPENDICULAR
TO THE PRIMARY LINES OF THE BUILDING. LOCATE ALL OPERATING AND CONTROL EQUIPMENT PROPERLY TO PROVIDE EASY ACCESS AND ARRANGE ENTIRE WORK WITH ADEQUATE ACCESS FOR OPERATION AND MAINTENANCE, AND FOR PROPER CODE AND/OR
MANUFACTURERS CLEARANCES.
2. DAMAGE CAUSED DURING CONSTRUCTION TO EXISTING MATERIALS/EQUIPMENT WILL BE REPAIRED OR REPLACED AT NO ADDITIONAL COST TO OWNER. RE-SUPPORT ANY REMAINING PIPING OR DEVICES THAT WERE SUPPORTED BY WALLS BEING REMOVED.
3. THE GENERAL CONTRACTOR AND ALL SUBCONTRACTORS SHALL COORDINATE THE INSTALLATION OF DUCTWORK, PIPING, CONDUIT, CABLE, ETC., WITH LIGHTING FIXTURES, SPECIAL CEILING CONSTRUCTION, AIR DISTRIBUTION EQUIPMENT, AND THE STRUCTURE. PROVIDE ADDITIONAL RISES AND OFFSETS AS REQUIRED. IF, AFTER INSTALLED, NEW DUCTWORK, PIPING, CONDUIT, CABLE, ETC., IS FOUND TO BE IN CONFLICT WITH THE ARCHITECTURE, STRUCTURE OR OTHER TRADE WORK, WHICH IS EITHER EXISTING OR SHOWN ON THE CONTRACT DOCUMENTS, THE DUCTWORK, PIPING, CONDUIT, CABLE, ETC., SHALL BE RELOCATED WITHOUT ADDITIONAL COST TO THE OWNER/TENANT.
COORDINATE ALL WORK COMPLETELY WITH ALL OTHER TRADES PRIOR TO INSTALLATION.
4. ALL BUILDING SERVICES, UTILITIES, POWER, FIRE PROTECTION, AND DOMESTIC COLD AND HOT WATER MAY NOT BE DISRUPTED FOR ANY
REASON WITHOUT PRIOR COORDINATION WITH A REPRESENTATIVE OF BUILDING OPERATIONS.
5. THIS BUILDING MAY HAVE A STRUCTURAL SYSTEM UTILIZING POST-TENSIONED CABLES. THE CONTRACTOR SHALL DETERMINE THE EXISTING STRUCTURAL SYSTEM PRIOR TO CUTTING, DRILLING, OR CORING. THE CONTRACTOR SHALL X-RAY ALL PENETRATIONS PRIOR TO
CUTTING THE FLOOR SLAB.
6. PENETRATIONS THROUGH FLOORS OR FIRE-RATED CONSTRUCTION SHALL BE FIRESAFED TO COMPLY WITH ASTM E-814 (UL 1479), AND THE
LOCAL AUTHORITY HAVING JURISDICTION.
F. PROJECT CLOSE OUT
1. UPON COMPLETION OF THE PROJECT, THE CONTRACTOR SHALL SUBMIT TO THE ENGINEER A COMPLETE SET OF "AS BUILT" DRAWINGS
PORTRAYING ACTUAL SITE CONDITIONS OF THE MECHANICAL, ELECTRICAL, PLUMBING, AND FIRE PROTECTION WORK. SUBMISSION SHALL CONSIST OF ONE SET OF PDF AND ONE SET OF CAD FILES IN AUTOCAD V. 2016 OR REVIT V. 2018 OR NEWER FORMAT WITH THE OWNER'S
STANDARD LAYERING SCHEME.
2. EXISTING CIRCUITRY IS SHOWN FOR INFORMATION ONLY. EXISTING CIRCUITRY INFORMATION TAKEN FROM COMBINATION OF FIELD SURVEY AND PREVIOUS TENANT DRAWINGS. CONTRACTOR SHALL FIELD VERIFY EXACT CIRCUITRY AND INDICATE ANY DEVIATIONS ON THE "AS BUILT" DRAWINGS. "AS BUILT" DRAWINGS SHALL ACCURATELY INDICATE THE LOCATION OF ALL NEW AND EXISTING JUNCTION BOXES WITH
THE RESPECTIVE PANEL AND CIRCUIT NUMBERS.
3. SUBMIT "AS-BUILT" RECORD DRAWINGS INDICATING ACTUAL AS-BUILT CONDITIONS TO THE ARCHITECT/ENGINEER FOR REVIEW. RECORD DRAWINGS SHALL BE STAMPED "AS-BUILT" AND SHALL HAVE THE NAME, ADDRESS, AND TELEPHONE NUMBER OF THE CONTRACTOR. ALL ENGINEERS' SEALS SHALL BE REMOVED FROM THE DRAWINGS. PROVIDE BLACK AND WHITE DIGITAL COPIES AND ONE (1) ELECTRONIC FILE.
4. SUBMIT ELECTRONIC PDF OF OPERATION AND MAINTENANCE MANUALS. THE MANUALS SHALL INCLUDE RATINGS, CAPACITIES, PARTS
LISTS, WIRING DIAGRAMS, SERVICE/MAINTENANCE RECOMMENDATIONS, AND WARRANTIES.
5. THE ELECTRICAL CONTRACTOR SHALL PERFORM THE FOLLOWING TASKS UPON PROJECT COMPLETION. ALL REQUIRED REPORTS AND AS- BUILTS SHALL BE SUBMITTED WITHIN TWO (2) WEEKS OF DATE OF SUBSTANTIAL COMPLETION OR OWNER OCCUPANCY.
6. SUBMIT WRITTEN RESPONSE TO ALL FIELD REPORTS INDICATING CORRECTIVE ACTIONS TAKEN AND DATE CORRECTIVE ACTION WAS
TAKEN TO THE ARCHITECT/ENGINEER FOR REVIEW.
G. WARRANTY
1. THE START OF THE CONTRACTOR'S WARRANTY PERIOD SHALL COMMENCE ON THE DATE OF "SUBSTANTIAL COMPLETION" AS AGREED TO
BY THE OWNER/TENANT.
2. THE WARRANTY PERIOD SHALL BE NO LESS THAN ONE (1) FULL YEAR, UNLESS SPECIFIED OTHERWISE AND SHALL INCLUDE AT LEAST ONE
(1) FULL HEATING SEASON AND ONE (1) FULL COOLING SEASON. DURING THE WARRANTY PERIOD THE CONTRACTOR SHALL GUARANTEE
THE FOLLOWING IN A FORM SATISFACTORY TO THE OWNER/TENANT:
A. WORK INSTALLED SHALL BE FREE FROM ANY AND ALL DEFECTS IN WORKMANSHIP AND/OR MATERIALS.
B. APPARATUS WILL DEVELOP CAPACITIES AND PERFORMANCE CHARACTERISTICS SPECIFIED.
C. SYSTEMS SHALL OPERATE WITHOUT MALFUNCTION.REQUIRED SUBMITTALS
ELECTRICAL GEAR
WIRING DEVICES
LIGHTING FIXTURES & CONTROLS
LIGHTING CONTROL SHOP DRAWING
ALL SUBMITTALS SHALL BE SUBMITTED VIA EMAIL TO SUBMITTALS@WYLIEENG.COM
AND COPIED TO THE PROJECT MANAGER.
ALL RFI'S SHALL BE SUBMITTED VIA EMAIL TO RFI@WYLIEENG.COM
AND COPIED TO THE PROJECT MANAGER.
DRAWING INDEX
ELECTRICAL SPECIFICATIONS ELECTRICAL SPECIFICATIONS
1. ALL PANELBOARDS, MOTOR STARTERS, CONTROL PANELS, CONTROL REMOTE STATIONS, DISCONNECT SWITCHES, CIRCUIT BREAKERS OR OTHER EQUIPMENT IN SEPARATE ENCLOSURES SHALL BE EQUIPPED WITH NAMEPLATES. THE NAMEPLATES SHALL BE ENGRAVED RIGID PLASTIC LAMINATE OR APPROVED
EQUAL, WHITE LETTERING ON BLACK BACKGROUND FOR EQUIPMENT 208/120 VOLT AND BLACK
LETTERING ON WHITE BACKGROUND FOR EQUIPMENT 480/277 VOLT, AND BE ATTACHED TO THE
EQUIPMENT SECURELY WITH SCREWS. EACH NAMEPLATE SHALL GIVE THE NUMBER DESIGNATION OF THE EQUIPMENT AS SHOWN ON THE ONE LINE DIAGRAM AND ALSO THE SOURCE. UTILIZE SIMILAR RED
AND WHITE NAMEPLATES FOR ALL EMERGENCY POWERED EQUIPMENT.
2. ALL WIRING DEVICES (EXCLUDING LIGHT SWITCHES) SHALL BE LABELED WITH SELF-ADHESIVE, LAMINATED TAPE INDICATING THE CIRCUIT NUMBER AND PANEL DESIGNATIONS. UTILIZE CLEAR TAPE WITH BLACK LETTERS UNLESS NOTED OTHERWISE. PROVIDE SAMPLE OF LABELS TO ARCHITECT AND
LANDLORD FOR APPROVAL PRIOR TO INSTALLATION.
3. NEW AND EXISTING CIRCUITRY SHALL BE ACCURATELY IDENTIFIED AT THE RESPECTIVE ABOVE CEILING JUNCTION BOXES. THE ASSOCIATED PANEL, CIRCUITS, AND VOLTAGE SHALL BE IDENTIFIED ON ALL JUNCTION BOX COVERS. CIRCUITS LEAVING PANELBOARDS AND DISTIBUTION PANELS SHALL BE
PROVIDED WITH LABEL ON CIRCUITS CONTAINED IN CONDUIT.
4. EXISTING CIRCUITRY IS SHOWN FOR INFORMATION ONLY. EXISTING CIRCUITRY INFORMATION TAKEN FROM COMBINATION OF FIELD SURVEY AND PREVIOUS TENANT DRAWINGS. CONTRACTOR SHALL FIELD VERIFY EXACT CIRCUITRY AND INDICATE ANY DEVIATIONS ON THE "AS BUILT" DRAWINGS. "AS BUILT" DRAWINGS SHALL ACCURATELY INDICATE THE LOCATION OF ALL NEW AND EXISTING JUNCTION BOXES
WITH THE RESPECTIVE PANEL AND CIRCUIT NUMBERS.
LOW VOLTAGE PROVISIONS
IDENTIFICATION/LABELING
BOLD DEVICE/CIRCUITING INDICATES NEW DEVICE/CIRCUITING
OR RELOCATED DEVICE.
SHADED DEVICE/CIRCUITING INDICATES EXISTING TO REMAIN
DASHED DEVICE/CIRCUITING INDICATES DEMOLITION
CONDUIT RUN CONCEALED IN WALLS OR ABOVE CEILING. ARROW
INDICATES HOMERUN TO PANEL. CONDUCTOR DESIGNATIONS ARE AS
FOLLOWS: LONG HATCH INDICATES NEUTRAL, SHORT HATCH
INDICATES PHASE, "DOT" INDICATES INSULATED OR ISOLATED
GROUND, AND NO HATCHES INDICATES TWO CONDUCTORS.
CONDUIT RUN CONCEALED IN FLOOR SLAB, BELOW FLOOR SLAB
OR BELOW GRADE. WIRING SAME AS ABOVE.
LIGHT FIXTURE TAG:
A = FIXTURE TYPE
XX = CIRCUIT NUMBER
a = SWITCH LEG
SIMPLEX RECEPTACLE OUTLET; 20 AMP, 125V., 3 WIRE, GROUNDED TYPE
OR SPECIAL RECEPTACLE OUTLET: SEE DRAWIINGS FOR NEMA
CONFIGURATION AND VOLTAGE.
DUPLEX RECEPTACLE OUTLET; 20 AMP, 125V., 3 WIRE, GROUNDED TYPE.
TWO(2) DUPLEX RECEPTACLE OUTLETS GANGED WITH A COMMON WALL
PLATE; 20 AMP, 125V, 3 WIRE, GROUNDED TYPE EACH.
DUPLEX RECEPTACLE OUTLET LOCATED ABOVE STANDARD HEIGHT;
20 AMP, 125V, 3 WIRE GROUNDED TYPE. REFER TO ARCHITECTURAL
DRAWINGS FOR EXACT HEIGHT.
GFI
DUPLEX RECEPTACLE OUTLET WITH GROUND FAULT INTERRUPTER;
DUPLEX WITH WEATHERPROOF WHILE IN USE COVER AND GFCI
20 AMP, 125V., 3 WIRE GROUNDED TYPE.
EXIT LIGHT. PROVIDE ARROWS AND FACES AS INDICATED ON DRAWINGS.
LEGEND OF ELECTRICAL SYMBOLS
SYMBOL DESCRIPTION
SCREENING SHADE INDICATES FIXTURE CONNECTION ON
EMERGENCY CIRCUIT OR BATTERY BACKUP. SEE PLANS.
A,XX,a
A,XX,a
ESSENTIAL POWER DUPLEX RECEPTACLE OUTLET; 20 AMP, 125V.,
3 WIRE, GROUNDED TYPE.
WP/GFI
1. PROVIDE A 4" X 4" X 2-1/8"D JUNCTION BOX WITH RING AND STRING ABOVE ACCESSIBLE
CEILING FOR ALL LOW VOLTAGE ROUGH-IN LOCATIONS (TYPICAL).
2. FOR WALLS TO DECK OR WALLS WITH INSULATION, PROVIDE A 4" X 4" X 2-1/8"D JUNCTION
BOX WITH 3/4" EMT CONDUIT TO ABOVE ACCESSIBLE CEILING.
3. LOW VOLTAGE SYSTEMS INCLUDE, BUT ARE NOT LIMITED TO: FIRE ALARM, BUILDING
CONTROLS, LIGHTING CONTROLS, DATA, AUDIO/VISUAL, SECURITY.
4. ALL LOW VOLTAGE CABLING IN THIS PROJECT SHALL BE ROUTED IN MINIMUM 3/4" EMT
CONDUIT WHERE EXPOSED TO VIEW OR WHERE ABOVE INACCESSIBLE CEILINGS. PROVIDE
A SHOP DRAWING FOR ARCHITECT REVIEW
COMMISSIONING NOTES
1. COMMISSION MECHANICAL AND SERVICE WATER HEATING SYSTEMS PER IECC C408.2 WITH COMBINED CAPACITY GREATER THAN 480KBTU/H.
A. THE CX AGENT SHALL PROVIDE A COMMISSIONING PLAN PER C408.2.1
B. BALANCE AND ADJUST AIR AND HYDRONIC SYSTEMS AS APPLICABLE PER C408.2.2
C. VERIFY PERFORMANCE AND INTERFACING OF SYSTEMS, CONTROLS, AND ECONOMIZERS FOR ALL MODES AND SEQUENCE OF OPERATIONS PER
C408.2.3
D. PROVIDE A PRELIMINARY COMMISSIONING REPORT PER C408.2.4
E. PROVIDE ALL CX DOCUMENTS TO BUILDING OWNER WITHIN 90 DAYS OF CERTIFICATE OF OCCUPANCY. INCLUDING SYSTEM BALANCING REPORT
AND FINAL CX REPORT
BREAK OUT PRICE - WORK TO BE COMPLETED BY CX AGENT
CONTROLLED DUPLEX RECEPTACLE OUTLET; 20 AMP, 125V., 3 WIRE,
GROUNDED TYPE. SPLIT CONTROLLED DUPLEX- LEGRAND #26352CH OR
EQUAL;
SPECIAL RECEPTACLE OUTLET: SEE DRAWINGS FOR
NEMA CONFIGURATION AND VOLTAGE.
FLUSH MOUNTED FIRE RATED POKE THRU DEVICE W/ RECEPTACLE(S)
AND/OR DATA AND/OR TELEPHONE. SEE DRAWINGS FOR SPECIFICATIONS.
FLUSH MOUNTED FLOOR BOX W/ RECEPTACLE(S) AND/OR DATA AND/OR
TELEPHONE. SEE DRAWINGS FOR SPECIFICATIONS.
POWER POLE. RE: DRAWINGS FOR MORE INFORMATION.
USB DUPLEX RECEPTACLE OUTLET WITH (2) USB RECEPTACLES; 20 AMP,
125V., 3 WIRE GROUNDED TYPE.
CEILING MOUNTED RECEPTACLE OUTLET, DUPLEX/QUAD/SPECIAL. SEE
DRAWINGS FOR SPECIAL OUTLET CONFIGURATION AND VOLTAGE.
TWO(2) DUPLEX OUTLETS UNDER COMMON COVER PLATE.
LEFT DUPLEX CONTROLLED - LEGRAND #26352CD OR EQUAL.
RIGHT DUPLEX NON-CONTROLLED. 20 AMP, 125V., 3W+G, EACH.
TWO(2) DUPLEX OUTLETS UNDER COMMON COVER PLATE.
LEFT DUPLEX CONTROLLED - LEGRAND #26352CD OR EQUAL.
RIGHT DUPLEX NON-CONTROLLED GFI, USB, OR GFI/USB. 20A, 125V., 2W+G
GFI USB GFI, USB
TELEPHONE / DATA / COMBINATION TELEDATA OUTLET
CABLE T.V. OUTLET
SINGLE POLE, 3-WAY, 4-WAY SWITCH: 20 AMP, 120/277V.
KEY SWITCH 120/277V ; DIGITAL KEY SWITCH
EMERGENCY POWER OFF SWITCH (E.P.O.)
JUNCTION BOX MOUNTED ABOVE ACCESSIBLE CEILING.
JUNCTION BOX - WALL MOUNTED/FLOOR; RE: FLOOR PLANS
TELEPHONE TERMINAL BOARD, 8' x 3/4" FIRE RATED PLYWOOD
DIMMER SWITCH. 120/277V. LUTRON "NOVA-T" OR EQUAL
ON/OFF ONLY / WITH RAISE/LOWER - WALL MOUNTED MOTION
SENSOR; 120/277VAC
PUSH BUTTON / BUZZER
DISCONNECT IN A NEMA 1 ENCLOSURE, UNLESS OTHERWISE SPECIFIED.
REFER TO DRAWINGS FOR AMPERAGE, PHASES, & FUSE SIZE.
(IF REQUIRED) VOLTS/AMPS/POLES TO MATCH BREAKER U.N.O.
SINGLE PHASE MOTOR
THREE PHASE MOTOR
MOTOR STARTER / DISCONNECT IN A NEMA 1 ENCLOSURE, UNLESS
OTHERWISE SPECIFIED. REFER TO DRAWINGS FOR AMPERAGE, PHASES,
FUSE SIZE (IF REQUIRED), AND SIZE. VOLT/AMP/POLES TO MATCH
BREAKER U.N.O.
MOTOR STARTER/VFD IN A NEMA 1 ENCLOSURE, UNLESS OTHERWISE
SPECIFIED. REFER TO DRAWINGS FOR AMPERAGE, PHASES, AND SIZE.
TRANSFER SWITCH - REFER TO DRAWINGS
FOR SPECIFICATIONS
CARD READER JUNCTION BOX WITH 3/4"C TO ACCESSIBLE
CEILING U.N.O.
VARIABLE SPEED DRIVE (SUPPLIED BY MECHANICAL CONTRACTOR)VSD
TTB
CR
GROUND BAR
TRANSFORMER W/ NEC CLEARANCES; REFER TO DRAWING
FOR VOLTAGE/kVA
SURFACE PANELBOARD W/ NEC CLEARANCES.
RECESSED PANELBOARD W/ NEC CLEARANCES
MECHANICAL EQUIPMENT CONNECTION POINT. REFER TO SCHEDULE ON
EX.XX FOR CONNECTION INFORMATION.
NETWORK ENABLED CEILING MOTION SENSOR EXTENDED RANGE /
WALKING MOTION
NETWORK ENABLED CEILING MOTION SENSOR STANDARD RANGE /
SITTING MOTION
WIRELESS DEVICE
DOORBELL CHIME; RE: SPECIFICATIONS/PLANS.
GB
LIGHTING CONTROL NETWORK ENABLED GRAPHIC TOUCH SCREEN 3.5"+
8 PRESETS OR 16 ZONES. USE NEAREST 120/277V LTG CKT FOR POWER
SUPPLY
1 ZONE / 2 ZONE DIGITAL NETWORK ENABLED, RAISE/LOWER+ON/OFF.
1 ZONE / 2 ZONE DIGITAL NETWORK ENABLED, ON/OFF SWITCH.
NETWORK ENABLED, WALL MOUNTED, 1 BUTTON, DUAL TECH SENSOR,
ON/OFF
NETWORK ENABLED, WALL MOUNTED, DUAL TECH SENSOR, ON/OFF +
RAISE/LOWER
PHOTOCELL / DAYLIGHT SENSOR
M
M
DS
MS
STD
MS
EXT
K
M
K
3 4
M
CONTROLLED DUPLEX RECEPTACLE OUTLET; 20 AMP, 125V., 3 WIRE,
GROUNDED TYPE. FULL CONTROLLED - LEGRAND #26352CD OR EQUAL.
REFERENCE SPECIFICATIONS FOR MORE INFORMATION
DATE
JOB
SHEET
ISSUES
KEYPLAN
Date of issue:
REVISIONS
25027.00
12/11/2025
/1
/2
:1 :5
P
M
A-E00-00
ELECTRICAL
COVER SHEET
F O
R T
B E
N D
I S
D
B P
H
V A
C M
E P
W E
S T
Z O
N E
S
T E
P H
E N
F A
U S
T
IN
H S
12/11/25
25241.0000
12.11.2025
A -E
-0
E
L E
C T
R
IC
A L C
O V
E R
S H
E E
T
P h e a s a n t C re e k D r.
S u g a r
L a n d
X
2 09.29.2025 50% CONSTRUCTION DOCUMENTS
1 07.18.2025 DESIGN DEVELOPMENT
3 11.11.2025 90% CONSTRUCTION DOCUMENTS
4 12.11.2025 100% CONSTRUCTION DOCUMENTS
SHEET NUMBER SHEET NAME
A-E00-00 ELECTRICAL COVER SHEET
A-E10-01 ELECTRICAL DEMOLITION PLAN - LEVEL 01 - OVERALL
A-E10-02 ELECTRICAL DEMOLITION PLAN - LEVEL 02 - OVERALL
A-E20-01 ELECTRICAL POWER PLAN - LEVEL 01 - OVERALL
A-E20-02 ELECTRICAL POWER PLAN - LEVEL 02- OVERALL
A-E30-01 ELECTRICAL ENLARGED PLANS - LEVEL 1
A-E30-02 ELECTRICAL ENLARGED PLANS - LEVEL 2
A-E40-00 ELECTRICAL DETAILS
D C
B A
1.4
1st
220,527 SF
Main Bldg
220,527 SF
(D)AHU-7
(D)AHU-8
(E)AHU-12
(E)AHU-11
(D)AHU-1
(D)AHU-2
(D)AHU-3
(D)HWP-1
(E)AHU-15
(E)AHU-16
(E)AHU-17
(D)AHU-20
(D)AHU-21
A. CONDUCT ALL DEMOLITION WORK IN SUCH A MANNER AS TO MAINTAIN A SAFE WORK
ENVIRONMENT AND IN ACCORDANCE WITH APPLICABLE SAFETY RULES AND PROCEDURES
WITHIN NEC, NECA AND OSHA REQUIREMENTS.
B. CONTRACTOR SHALL REQUEST AND REVIEW ANY HAZARDOUS MATERIALS SURVEYS FROM
THE OWNER'S REPRESENTATIVE. OBSERVE RECOMMENDED PRECAUTIONS AND VERIFY THE
STATUS OF ANY REMEDIAL WORK RECOMMENDED OR NOTED WITHIN THE HAZARDOUS
MATERIAL SURVEY. NOTIFY THE OWNER'S REPRESENTATIVE IF ANY HAZARDOUS MATERIALS
ARE SUSPECTED OR OBSERVED DURING THE COURSE OF EXECUTING THIS CONTRACT.
C. SURVEYS AREAS OF THE FACILITY SCHEDULED FOR RENOVATION OR PARTIAL DEMOLITION
PRIOR TO ANY WORK BEING PERFORMED. SUBMIT REPORT OF THE PRE-WORK SURVEY
DETAILING ANY UTILIZATION EQUIPMENT OR SYSTEMS THAT ARE NOT IN GOOD WORKING
ORDER IN ADVANCE OF ANY DEMOLITION WORK AND REVIEW WITH THE OWNER'S
REPRESENTATIVE.
D. THE OWNER SHALL HAVE FIRST RIGHT OF REFUSAL FOR SALVAGED MATERIAL. REQUEST
THAT THE OWNER PROVIDE DIRECTION ON DISPOSITION OF SALVAGED MATERIAL FIVE(5)
WORKING DAYS PRIOR TO REMOVAL. IF SO DIRECTED BY THE OWNER, SALVAGED MATERIAL
SHALL REMAIN THE PROPERTY OF THE OWNER AND SHALL BE DELIVERED BY THE
CONTRACTOR TO A LOCATION AS DIRECTED. REMOVE AND DISPOSE ANY SALVAGED
MATERIAL NOT RETAINED BY THE OWNER.
E. DRAWINGS INDICATE APPROXIMATE LOCATION AND QUANTITY OF PANELS, TRANSFORMERS,
DISCONNECTS, ETC. TO BE REMOVED. VERIFY LOCATION AND QUANTITY OF ITEMS TO BE
REMOVED. NO ALLOWANCE WILL BE MADE BECAUSE OF CONTRACTOR'S UNFAMILIARITY WITH
THE SITE.
F. DAMAGED AREAS CAUSED REMOVAL OF ANY OF THE ABOVE ITEMS AND WHICH ARE NOT
CONCEALED BY NEW CONSTRUCTION SHALL BE REPAIRED TO MATCH ADJACENT SURFACES.
OPENINGS CREATED BY THE REMOVAL OF THESE ITEMS THROUGH FIRE RATED WALLS SHALL
BE FIRE STOPPED.
G. REMOVE ABANDONED CONDUIT TO POINT OF CONCEALMENT BEHIND INACCESSIBLE
SURFACES. ENTIRELY REMOVE ABANDONED WIRING.
H. PROVIDE BLANK COVERS AND PLATES AT UNUSED OPENINGS IN BOXES, RACEWAYS,
AUXILIARY GUTTERS, CABINETS, EQUIPMENT CASES AND HOUSINGS SHALL BE CLOSED TO
AFFORD PROTECTION SUBSTANTIALLY EQUIVALENT TO THE EQUIPMENT ENCLOSURE.
I. IF A CONDUIT RUN IS EXPOSED OR A SURFACE RACEWAY LEFT WITHOUT A MOUNTING
SURFACE DUE TO REMOVAL OF A PARTITION, THE RACEWAY SHALL BE REROUTED AS
ACCEPTABLE TO THE OWNER/ARCHITECT.
J. PROTECT ELECTRICAL EQUIPMENT, OUTLETS AND DEVICES THAT ARE SCHEDULED TO BE
RELOCATED. REPAIR, RESTORE OR REPLACE ITEMS DAMAGED WHEN REMOVED TO THE
APPROVAL OF THE OWNER. NOTIFY OWNER/ARCHITECT/ENGINEER OF ANY ELECTRICAL
EQUIPMENT, OUTLETS AND/OR DEVICES WHICH ARE SCHEDULED TO BE RE-USED THAT ARE
FOUND TO BE UNUSABLE.
ELECTRICAL DEMOLITION GENERAL NOTES
DATE
JOB
SHEET
ISSUES
KEYPLAN
Date of issue:
REVISIONS
25027.00
12/11/2025
/1
/2
:1 :5
P
M
A-E10-01
ELECTRICAL
DEMOLITION PLAN
- LEVEL 01 -
OVERALL
F O
R T
B E
N D
I S
D
B P
H
V A
C M
E P
W E
S T
Z O
N E
S
T E
P H
E N
F A
U S
T
IN
H S
12/11/25
25241.0000
12.11.2025
A -E
-0
E
L E
C T
R
IC
A L D
E M
O L
IT
IO
N
P L A
N
L E
V E
L
O V
E R
A L L
P h e a s a n t C re e k D r.
S u g a r
L a n d
2 09.29.2025 50% CONSTRUCTION DOCUMENTS
1 07.18.2025 DESIGN DEVELOPMENT
3 11.11.2025 90% CONSTRUCTION DOCUMENTS
4 12.11.2025 100% CONSTRUCTION DOCUMENTS
D C
B A
1/32" = 1'-0"1
ELECTRICAL DEMOLITION PLAN - LEVEL 01
ELECTRICAL KEYED NOTES
1 EXISTING HVAC AIR HANDLER EQUIPMENT TO BE REPLACED. FIELD VERIFY
EXISTING CONDITION OF CIRCUITS, RACEWAYS & CONDUITS SERVING AIR
HANDLER. NOTIFY ENGINEER IF EXISTING AHU CIRCUIT NEEDS TO BE
REPLACED. REFER TO NEW WORK PLANS.
2 EXISTING HVAC TERMINAL TO BE REPLACED. FIELD VERIFY EXISTING CONDITION
OF CIRCUITS, RACEWAYS & CONDUITS SERVING TERMINAL. NOTIFY ENGINEER IF
EXISTING TERMINAL CIRCUIT NEEDS TO BE REPLACED. REFER TO NEW WORK
PLANS.
3 EXISTING HVAC PUMP EQUIPMENT TO RE REPLACED. DEMO EXISTING CIRCUITS,
DISCONNECTS, DRIVE HARDWARE, RACEWAYS & CONDUITS, AND OTHER
ELECTRICAL APPURTENANCES. DEMO EXISTING BREAKERS IN DISTRIBUTION
EQUIPMENT ASSOCIATED WITH THESE PUMPS, AND PREPARE BREAKER SPACES
FOR INSTALLATION OF NEW BREAKERS. REFER TO NEW WORK PLANS.
4 EXISTING HVAC AIR HANDLER EQUIPMENT TO REMAIN AND BE REFURBISHED.
NEW VFD HARDWARE BY DIVISION 23 SHALL BE PROVIDED. VERIFY POWER AND
GROUNDING CONNECTIONS, RE. MECHANICAL PLANS.
G
GG
G GG
DW
HC
HC
E
E
E
G
E
G
E
G
E
EE
EE
EE
E
E
E
HC
E
HC
G
G
EE
E
E
G
EE
EEE EEE
C CC
C CC
2nd Floor 2nd Floor
74,135 SF
TYP.15
(D)AHU-9
(D)AHU-10
(D)AHU-4
(D)AHU-5
(E)AHU-13
(D)AHU-6
(D)AHU-18
(D)AHU-19
A. CONDUCT ALL DEMOLITION WORK IN SUCH A MANNER AS TO MAINTAIN A SAFE WORK
ENVIRONMENT AND IN ACCORDANCE WITH APPLICABLE SAFETY RULES AND PROCEDURES
WITHIN NEC, NECA AND OSHA REQUIREMENTS.
B. CONTRACTOR SHALL REQUEST AND REVIEW ANY HAZARDOUS MATERIALS SURVEYS FROM
THE OWNER'S REPRESENTATIVE. OBSERVE RECOMMENDED PRECAUTIONS AND VERIFY THE
STATUS OF ANY REMEDIAL WORK RECOMMENDED OR NOTED WITHIN THE HAZARDOUS
MATERIAL SURVEY. NOTIFY THE OWNER'S REPRESENTATIVE IF ANY HAZARDOUS MATERIALS
ARE SUSPECTED OR OBSERVED DURING THE COURSE OF EXECUTING THIS CONTRACT.
C. SURVEYS AREAS OF THE FACILITY SCHEDULED FOR RENOVATION OR PARTIAL DEMOLITION
PRIOR TO ANY WORK BEING PERFORMED. SUBMIT REPORT OF THE PRE-WORK SURVEY
DETAILING ANY UTILIZATION EQUIPMENT OR SYSTEMS THAT ARE NOT IN GOOD WORKING
ORDER IN ADVANCE OF ANY DEMOLITION WORK AND REVIEW WITH THE OWNER'S
REPRESENTATIVE.
D. THE OWNER SHALL HAVE FIRST RIGHT OF REFUSAL FOR SALVAGED MATERIAL. REQUEST
THAT THE OWNER PROVIDE DIRECTION ON DISPOSITION OF SALVAGED MATERIAL FIVE(5)
WORKING DAYS PRIOR TO REMOVAL. IF SO DIRECTED BY THE OWNER, SALVAGED MATERIAL
SHALL REMAIN THE PROPERTY OF THE OWNER AND SHALL BE DELIVERED BY THE
CONTRACTOR TO A LOCATION AS DIRECTED. REMOVE AND DISPOSE ANY SALVAGED
MATERIAL NOT RETAINED BY THE OWNER.
E. DRAWINGS INDICATE APPROXIMATE LOCATION AND QUANTITY OF PANELS, TRANSFORMERS,
DISCONNECTS, ETC. TO BE REMOVED. VERIFY LOCATION AND QUANTITY OF ITEMS TO BE
REMOVED. NO ALLOWANCE WILL BE MADE BECAUSE OF CONTRACTOR'S UNFAMILIARITY WITH
THE SITE.
F. DAMAGED AREAS CAUSED REMOVAL OF ANY OF THE ABOVE ITEMS AND WHICH ARE NOT
CONCEALED BY NEW CONSTRUCTION SHALL BE REPAIRED TO MATCH ADJACENT SURFACES.
OPENINGS CREATED BY THE REMOVAL OF THESE ITEMS THROUGH FIRE RATED WALLS SHALL
BE FIRE STOPPED.
G. REMOVE ABANDONED CONDUIT TO POINT OF CONCEALMENT BEHIND INACCESSIBLE
SURFACES. ENTIRELY REMOVE ABANDONED WIRING.
H. PROVIDE BLANK COVERS AND PLATES AT UNUSED OPENINGS IN BOXES, RACEWAYS,
AUXILIARY GUTTERS, CABINETS, EQUIPMENT CASES AND HOUSINGS SHALL BE CLOSED TO
AFFORD PROTECTION SUBSTANTIALLY EQUIVALENT TO THE EQUIPMENT ENCLOSURE.
I. IF A CONDUIT RUN IS EXPOSED OR A SURFACE RACEWAY LEFT WITHOUT A MOUNTING
SURFACE DUE TO REMOVAL OF A PARTITION, THE RACEWAY SHALL BE REROUTED AS
ACCEPTABLE TO THE OWNER/ARCHITECT.
J. PROTECT ELECTRICAL EQUIPMENT, OUTLETS AND DEVICES THAT ARE SCHEDULED TO BE
RELOCATED. REPAIR, RESTORE OR REPLACE ITEMS DAMAGED WHEN REMOVED TO THE
APPROVAL OF THE OWNER. NOTIFY OWNER/ARCHITECT/ENGINEER OF ANY ELECTRICAL
EQUIPMENT, OUTLETS AND/OR DEVICES WHICH ARE SCHEDULED TO BE RE-USED THAT ARE
FOUND TO BE UNUSABLE.
ELECTRICAL DEMOLITION GENERAL NOTES
DATE
JOB
SHEET
ISSUES
KEYPLAN
Date of issue:
REVISIONS
25027.00
12/11/2025
/1
/2
:1 :5
P
M
A-E10-02
ELECTRICAL
DEMOLITION PLAN
- LEVEL 02 -
OVERALL
F O
R T
B E
N D
I S
D
B P
H
V A
C M
E P
W E
S T
Z O
N E
S
T E
P H
E N
F A
U S
T
IN
H S
12/11/25
25241.0000
12.11.2025
A -E
-0
E
L E
C T
R
IC
A L D
E M
O L
IT
IO
N
P L A
N
L E
V E
L
O V
E R
A L L
P h e a s a n t C re e k D r.
S u g a r
L a n d
2 09.29.2025 50% CONSTRUCTION DOCUMENTS
1 07.18.2025 DESIGN DEVELOPMENT
3 11.11.2025 90% CONSTRUCTION DOCUMENTS
4 12.11.2025 100% CONSTRUCTION DOCUMENTS
D C
B A
1/32" = 1'-0"1
ELECTRICAL DEMOLITION PLAN - LEVEL 02
ELECTRICAL KEYED NOTES
1 EXISTING HVAC AIR HANDLER EQUIPMENT TO BE REPLACED. FIELD VERIFY
EXISTING CONDITION OF CIRCUITS, RACEWAYS & CONDUITS SERVING AIR
HANDLER. NOTIFY ENGINEER IF EXISTING AHU CIRCUIT NEEDS TO BE
REPLACED. REFER TO NEW WORK PLANS.
2 EXISTING HVAC TERMINAL TO BE REPLACED. FIELD VERIFY EXISTING
CONDITION OF CIRCUITS, RACEWAYS & CONDUITS SERVING TERMINAL.
NOTIFY ENGINEER IF EXISTING TERMINAL CIRCUIT NEEDS TO BE REPLACED.
REFER TO NEW WORK PLANS.
3 EXISTING HVAC AIR HANDLER EQUIPMENT TO REMAIN AND BE REFURBISHED.
NEW VFD HARDWARE BY DIVISION 23 SHALL BE PROVIDED. VERIFY POWER
AND GROUNDING CONNECTIONS, RE. MECHANICAL PLANS.
1st
220,527 SF
Main Bldg
220,527 SF
A-E30-01
A-E30-01
A-E30-01
A-E30-01
A-E30-01
A-E30-01
2 (N)VFD-HWP-1
(N)HWP-1
A-E30-01
A. ALL CONDUITS THAT COULD BE VIEWED BY THE PUBLIC OR EMPLOYEES SHALL BE
INSTALLED IN WALLS OR IN THE SLAB.
B. CONDUIT LINES ARE DIAGRAMMATIC. CONTRACTOR SHALL FIELD VERIFY CONDITIONS AND
CHOOSE APPROPRIATE CONDUIT ROUTING. IN THE EVENT THAT THE APPROXIMATE
CONDUIT ROUTING SHOWN ON PLANS IS NOT FEASIBLE CONTRACTOR SHALL NOTIFY
ARCHITECT/ENGINEER.
C. RECEPTACLES LOCATED WITHIN 6' OF ANY PLUMBING FIXTURE, IN BREAK ROOMS, AT THE
EXTERIOR, IN THE PARKING GARAGE OR OTHERWISE EXPOSED TO WATER SHALL BE TYPE
GFCI. "WP" INDICATES A WEATHERPROOF "WHILE-IN-USE" COVER.
D. ALL WIRING DEVICES ARE NEW UNLESS NOTED OTHERWISE.
E. ALL ELECTRICAL EQUIPMENT IS EXISTING TO REMAIN UNLESS NOTED OTHERWISE.
F. COORDINATE DISCONNECT SWITCHES, VFDS AND STARTER LOCATIONS WITH EQUIPMENT
INSTALLERS TO MAINTAIN PROPER MAINTENANCE AND CODE REQUIRED CLEARANCES.
G. COORDINATE RECEPTACLE AND DATACOM LOCATIONS SO THAT DEVICES ON SIMILAR
WALLS ARE ADJACENT TO ONE ANOTHER.
H. REFERENCE EQUIPMENT CONNECTION SCHEDULE FOR REQUIREMENTS AND ADDITIONAL
INFORMATION OF TAGGED EQUIPMENT SHOWN ON PLAN DRAWING.
I. PROVIDE 120V POWER TO EACH HVAC DDC CONTROL PANEL. COORDINATE EXACT
LOCATIONS AND QUANTITIES WITH MECHANICAL DRAWINGS.
ELECTRICAL POWER GENERAL NOTES
DATE
JOB
SHEET
ISSUES
KEYPLAN
Date of issue:
REVISIONS
25027.00
12/11/2025
/1
/2
:1 :0
P
M
A-E20-01
ELECTRICAL
POWER PLAN -
LEVEL 01 -
OVERALL
F O
R T
B E
N D
I S
D
B P
H
V A
C M
E P
W E
S T
Z O
N E
S
T E
P H
E N
F A
U S
T
IN
H S
12/11/25
25241.0000
12.11.2025
A -E
-0
E
L E
C T
R
IC
A L P
O W
E R
P L A
N
L E
V E
L
O V
E R
A L L
P h e a s a n t C re e k D r.
S u g a r
L a n d
2 09.29.2025 50% CONSTRUCTION DOCUMENTS
1 07.18.2025 DESIGN DEVELOPMENT
3 11.11.2025 90% CONSTRUCTION DOCUMENTS
4 12.11.2025 100% CONSTRUCTION DOCUMENTS
D C
B A
1/32" = 1'-0"1
ELECTRICAL POWER PLAN - LEVEL 01
ELECTRICAL KEYED NOTES
1 NEW HVAC TERMINAL. CONNECT TO EXISTING CIRCUIT SERVING PREVIOUS
EQUIPMENT BEING REPLACED, VERIFY AMPACITY. COORDINATE WITH
ARCHITECTURAL AND MECHANICAL FOR EXACT LOCATION AND CONNECTION
REQUIREMENTS.
2 NEW HVAC PUMP EQUIPMENT. REUSE EXISTING CIRCUIT, VERIFY AMPACITY.
PROVIDE MOTOR DRIVE EQUIPMENT PER MECHANICAL SCHEDULE AND DIVISION
23. COORDINATE WITH ARCHITECTURAL AND MECHANICAL FOR EXACT
LOCATION AND CONNECTION REQUIREMENTS.
G
GG
G GG
DW
HC
HC
E
E
E
G
E
G
E
G
E
EE
EE
EE
E
E
E
HC
E
HC
G
G
EE
E
E
G
EE
EEE EEE
C CC
C CC
2nd Floor 2nd Floor
74,135 SF
TYP.15
A-E30-02
A-E30-02
A-E30-02
(N)AHU-18
(N)AHU-19
A-E30-02
AHU-22
(N)VFD-AHU-22
AHU-23
(N)VFD-AHU-19
(N)VFD-AHU-18
A. ALL CONDUITS THAT COULD BE VIEWED BY THE PUBLIC OR EMPLOYEES SHALL BE
INSTALLED IN WALLS OR IN THE SLAB.
B. CONDUIT LINES ARE DIAGRAMMATIC. CONTRACTOR SHALL FIELD VERIFY CONDITIONS AND
CHOOSE APPROPRIATE CONDUIT ROUTING. IN THE EVENT THAT THE APPROXIMATE
CONDUIT ROUTING SHOWN ON PLANS IS NOT FEASIBLE CONTRACTOR SHALL NOTIFY
ARCHITECT/ENGINEER.
C. RECEPTACLES LOCATED WITHIN 6' OF ANY PLUMBING FIXTURE, IN BREAK ROOMS, AT THE
EXTERIOR, IN THE PARKING GARAGE OR OTHERWISE EXPOSED TO WATER SHALL BE TYPE
GFCI. "WP" INDICATES A WEATHERPROOF "WHILE-IN-USE" COVER.
D. ALL WIRING DEVICES ARE NEW UNLESS NOTED OTHERWISE.
E. ALL ELECTRICAL EQUIPMENT IS EXISTING TO REMAIN UNLESS NOTED OTHERWISE.
F. COORDINATE DISCONNECT SWITCHES, VFDS AND STARTER LOCATIONS WITH EQUIPMENT
INSTALLERS TO MAINTAIN PROPER MAINTENANCE AND CODE REQUIRED CLEARANCES.
G. COORDINATE RECEPTACLE AND DATACOM LOCATIONS SO THAT DEVICES ON SIMILAR
WALLS ARE ADJACENT TO ONE ANOTHER.
H. REFERENCE EQUIPMENT CONNECTION SCHEDULE FOR REQUIREMENTS AND ADDITIONAL
INFORMATION OF TAGGED EQUIPMENT SHOWN ON PLAN DRAWING.
I. PROVIDE 120V POWER TO EACH HVAC DDC CONTROL PANEL. COORDINATE EXACT
LOCATIONS AND QUANTITIES WITH MECHANICAL DRAWINGS.
ELECTRICAL POWER GENERAL NOTES
DATE
JOB
SHEET
ISSUES
KEYPLAN
Date of issue:
REVISIONS
25027.00
12/11/2025
/1
/2
:1 :0
P
M
A-E20-02
ELECTRICAL
POWER PLAN -
LEVEL 02-
OVERALL
F O
R T
B E
N D
I S
D
B P
H
V A
C M
E P
W E
S T
Z O
N E
S
T E
P H
E N
F A
U S
T
IN
H S
12/11/25
25241.0000
12.11.2025
A -E
-0
E
L E
C T
R
IC
A L P
O W
E R
P L A
N
L E
V E
L
O V
E R
A L L
P h e a s a n t C re e k D r.
S u g a r
L a n d
2 09.29.2025 50% CONSTRUCTION DOCUMENTS
1 07.18.2025 DESIGN DEVELOPMENT
3 11.11.2025 90% CONSTRUCTION DOCUMENTS
4 12.11.2025 100% CONSTRUCTION DOCUMENTS
D C
B A
1/32" = 1'-0"1
ELECTRICAL POWER PLAN - LEVEL 02
ELECTRICAL KEYED NOTES
1 NEW HVAC TERMINAL. CONNECT TO EXISTING CIRCUIT SERVING PREVIOUS
EQUIPMENT BEING REPLACED, VERIFY AMPACITY. COORDINATE WITH
ARCHITECTURAL AND MECHANICAL FOR EXACT LOCATION AND CONNECTION
REQUIREMENTS.
2 ELECTRICAL CONTRACTOR TO INSTALL NEW COMBINATION VFD/DISCONNECT
AND CONNECT TO EXISTING CIRCUIT FOR NEW AIR HANDLING UNIT. RE. PANEL
SCHEDULES FOR CIRCUIT INFORMATION. COORDINATE LOCATION OF VFD WITH
MECHANICAL CONTRACTOR.
3 EXISTING REFURBISHED AIR HANDLER: NEW VFD BY DIVISION 23, MAKE
CONNECTIONS TO CIRCUIT AND HVAC EQUIPMENT AS REQUIRED. VERIFY
POWER AND GROUNDING CONNECTIONS, RE. MECHANICAL PLANS.
'LCC'
'CP3' 'LB'
'LB2'
'HB'
'X3' 'XB'
'FACP' 'TLCCD'
(N)AHU-8
(N)AHU-7
(N)VFD-AHU-7
(N)VFD-AHU-8
GFI
LB2-1
'HC''LC''LC2'
'XFMR''XFMR'
'CP2''CP2'
'DC'
(E)AHU-12
(E)AHU-11
(N)VFD-AHU-11
(N)VFD-AHU-12
GFI
LC2-2
'XFMR'
'HK' 'CP4' 'LR' 'LQ'
'DD'
'MCC'
'LN'
'XFMR'
(E)AHU-15
(N)VFD-AHU-15
LQ-34
GFI
NOTE: EXISTING ELEC
EQUIPMENT LOCATED
IN MECH MEZZANINE
'LH'
'HH'
'LC2'
'XH'
'DB'
(N)AHU-20
(N)AHU-21
(N)VFD-AHU-20
(N)VFD-AHU-21
LG-2
GFI
'HA'
'LA' 'LA2'
'DA'
'XFMR'
'CPI'
'LCA'
'LCB'
'X1'
(N)AHU-1
(N)AHU-2
(N)AHU-3
(N)VFD-AHU-3
(N)VFD-AHU-2
(N)VFD-AHU-1
LA-21
GFI
'LCE'
'LL'
'LM'
'XFMR'
'XFMR'
'XFMR'
(E)AHU-16
(E)AHU-17
(N)VFD-AHU-17
(N)VFD-AHU-16
LQ-2
GFI
A. ALL CONDUITS THAT COULD BE VIEWED BY THE PUBLIC OR EMPLOYEES SHALL BE
INSTALLED IN WALLS OR IN THE SLAB.
B. CONDUIT LINES ARE DIAGRAMMATIC. CONTRACTOR SHALL FIELD VERIFY CONDITIONS AND
CHOOSE APPROPRIATE CONDUIT ROUTING. IN THE EVENT THAT THE APPROXIMATE
CONDUIT ROUTING SHOWN ON PLANS IS NOT FEASIBLE CONTRACTOR SHALL NOTIFY
ARCHITECT/ENGINEER.
C. RECEPTACLES LOCATED WITHIN 6' OF ANY PLUMBING FIXTURE, IN BREAK ROOMS, AT THE
EXTERIOR, IN THE PARKING GARAGE OR OTHERWISE EXPOSED TO WATER SHALL BE TYPE
GFCI. "WP" INDICATES A WEATHERPROOF "WHILE-IN-USE" COVER.
D. ALL WIRING DEVICES ARE NEW UNLESS NOTED OTHERWISE.
E. ALL ELECTRICAL EQUIPMENT IS EXISTING TO REMAIN UNLESS NOTED OTHERWISE.
F. COORDINATE DISCONNECT SWITCHES, VFDS AND STARTER LOCATIONS WITH EQUIPMENT
INSTALLERS TO MAINTAIN PROPER MAINTENANCE AND CODE REQUIRED CLEARANCES.
G. COORDINATE RECEPTACLE AND DATACOM LOCATIONS SO THAT DEVICES ON SIMILAR
WALLS ARE ADJACENT TO ONE ANOTHER.
H. REFERENCE EQUIPMENT CONNECTION SCHEDULE FOR REQUIREMENTS AND ADDITIONAL
INFORMATION OF TAGGED EQUIPMENT SHOWN ON PLAN DRAWING.
I. PROVIDE 120V POWER TO EACH HVAC DDC CONTROL PANEL. COORDINATE EXACT
LOCATIONS AND QUANTITIES WITH MECHANICAL DRAWINGS.
ELECTRICAL POWER GENERAL NOTES
AHU-14
AHU-25
(N)VFD-AHU-14
(N)VFD-AHU-25
GFI
LP-12
DATE
JOB
SHEET
ISSUES
KEYPLAN
Date of issue:
REVISIONS
25027.00
12/11/2025
/1
/2
:1 :0
P
M
A-E30-01
ELECTRICAL
ENLARGED PLANS
- LEVEL 1
F O
R T
B E
N D
I S
D
B P
H
V A
C M
E P
W E
S T
Z O
N E
S
T E
P H
E N
F A
U S
T
IN
H S
12/11/25
25241.0000
12.11.2025
A -E
-0
E
L E
C T
R
IC
A L E
N L A
R G
E D
P L A
N S
L E
V E
L
P h e a s a n t C re e k D r.
S u g a r
L a n d
2 09.29.2025 50% CONSTRUCTION DOCUMENTS
1 07.18.2025 DESIGN DEVELOPMENT
3 11.11.2025 90% CONSTRUCTION DOCUMENTS
4 12.11.2025 100% CONSTRUCTION DOCUMENTS
D C
B A
1/4" = 1'-0"1
ELECTRICAL…
This is the start of the file's text. The full file is on GovTribe.