14-CSP 26-036KB BP048 Drawings.pdf

PDF 20 MB Posted

Attached to
BP048 HVAC - MEP West Zone 3 Package A
Solicitation number
CSP 26-036KB
Issued by
Fort Bend County, Texas

About this file

This is a complete set of construction drawings and specifications for BP048 HVAC - MEP West Zone 3, a mechanical, electrical, plumbing, and fire protection project for Fort Bend Independent School District (FBISD) at seven school campuses in the Houston area. The project encompasses HVAC upgrades at Austin High School, Bowie Middle School, Crockett Middle School, Garcia Middle School, Hodges Bend Middle School, Travis High School, and Walker Station Elementary School. The scope of work includes replacing central station air handling units with direct digital controls, replacing VAV units on the first and second floors, replacing heating water pumps with variable frequency drives, providing piping insulation on sprinkler piping in critical areas, and replacing the main shut-off valve near the cooling tower. The drawings indicate a phased design development with the schematic design/design development completed July 18, 2025; 50% construction documents dated September 29, 2025; 90% construction documents dated November 12, 2025; and issue for bid dated December 11, 2025. The project encompasses mechanical, electrical, plumbing, and fire protection systems across multiple building levels with comprehensive demolition, new installation, and refurbishment scopes.

The construction documents follow 2015 International Building Code and 2021 International codes for fire, electrical, mechanical, and plumbing with local amendments. The project requires detailed coordination among multiple trade contractors including mechanical, electrical, plumbing, fire protection, and controls contractors. Bidders are instructed to conduct site visits and verify existing conditions prior to submitting bids, with all costs for replacement, repair, relocation, or removal of existing MEP elements included in the base bid. The contractor must provide separate line-item pricing for specific installation tasks including dedicated receptacles, quad receptacles, voice/data outlets, junction boxes, light fixtures, and circuit tracing. A commissioning agent must be retained to commission mechanical and service water heating systems with capacity greater than 80 KBTU/H and lighting control systems, providing preliminary and final commissioning reports within 90 days of certificate of occupancy. The project requires one-year warranty covering all work, materials, and defects, with systems operating without malfunction through at least one full heating and cooling season.

View the file

Other files

Show all 23

On GovTribe

Work with this file

  • Download the original file
  • Contacts named in this file
  • Similar government files
  • Ask GovTribe AI about this file

Text version

A B

C D

DATE

JOB

SHEET

ISSUES

REVISIONS

AFSHI CHARANIA ANGIE WIERZBICKI ANGIE HANAN ADAM SCHOOF DR. SHIRLEY ROSE GILLIAM ADDIE HEYLIGER ARCHITECT MEP ENGINEERKRISTIN K. TASSIN

BOARD OF TRUSTEES

SHEET LIST

KEYPLAN

Date of issue:

PROJECT TEAM

/1

/2

:1 :0

P

M

.COVER

COVER SHEET

12.11.2025

25241.0000

FORT BEND ISD

BP048 HVAC - MEP ZONE 3

ISSUE FOR BID

POSITION 3 POSITION 7 VICE PRESIDENT POSITION 2 SECRETARY POSITION 5 CORGAN ASSOCIATES, INC

16431 Lexington Blvd T: Sugar Land, TX 77479

F: 281.634.5590 CONTACT: Contact: Juan Valdez email: cn_juan.valdez@fortbendisd.gov

POSITION 1 POSITION 4 9 GREENWAY PLAZA, HOUSTON TX, 77046

(ctrl+Enter for 2nd line)

T: (832) 652-3640

YW-SQUARED

2508 REPPART PLACE, HOUSTON TX 77008

T: (832) 384-4178

BOARD PRESIDENT

POSITION 6

2 09.29.2025 50% CDs

1 07.18.2025 SD / DD

3 11.12.2025 90% CDs

4 12.11.2025 ISSUE FOR BID

.C O

V E

R

C O

V E

R S

H E

E T

12.11.2025

B P

H

V A

C

M E

P Z

O N

E www.corgan.com T: 214.748.2000

SHEET INDEX

Discipline

SHEET

NO. SHEET NAME SD / DD 50% CD 90% CD

ISSUE

FOR BID

01 - GENERAL

01 - GENERAL .COVER COVER SHEET Yes Yes Yes Yes

AUSTIN HIGH SCHOOL

AUSTIN HIGH SCHOOL A-A00.00 COVER SHEET Yes Yes Yes Yes

AUSTIN HIGH SCHOOL A-E00-00 - ELECTRICAL COVER SHEET Yes Yes Yes Yes

AUSTIN HIGH SCHOOL A-E10-01 ELECTRICAL DEMOLITION PLAN - LEVEL 01 - OVERALL Yes Yes Yes Yes

AUSTIN HIGH SCHOOL A-E10-02 ELECTRICAL DEMOLITION PLAN - LEVEL 02 - OVERALL Yes Yes Yes Yes

AUSTIN HIGH SCHOOL A-E20-01 ELECTRICAL POWER PLAN - LEVEL 01 - OVERALL Yes Yes Yes Yes

AUSTIN HIGH SCHOOL A-E20-02 ELECTRICAL POWER PLAN - LEVEL 02- OVERALL Yes Yes Yes Yes

AUSTIN HIGH SCHOOL A-E30-01 ELECTRICAL ENLARGED PLANS - LEVEL 1 No No No Yes

AUSTIN HIGH SCHOOL A-E30-02 ELECTRICAL ENLARGED PLANS - LEVEL 2 No No No Yes

AUSTIN HIGH SCHOOL A-E40-00 ELECTRICAL DETAILS Yes Yes Yes Yes

AUSTIN HIGH SCHOOL A-FP00-00 - FIRE PROTECTION COVER SHEET No Yes Yes Yes

AUSTIN HIGH SCHOOL A-FP20-01 FIRE PROTECTION PLAN - LEVEL 01 - OVERALL Yes Yes Yes Yes

AUSTIN HIGH SCHOOL A-M00-00 MECHANICAL COVER SHEET Yes Yes Yes Yes

AUSTIN HIGH SCHOOL A-M10-01 MECHANICAL DEMOLITION PLAN - LEVEL 01 - OVERALL Yes Yes Yes Yes

AUSTIN HIGH SCHOOL A-M10-02 MECHANICAL DEMOLITION PLAN - LEVEL 02 - OVERALL Yes Yes Yes Yes

AUSTIN HIGH SCHOOL A-M20-01 MECHANICAL PLAN - LEVEL 01 - OVERALL Yes Yes Yes Yes

AUSTIN HIGH SCHOOL A-M20-02 MECHANICAL PLAN - LEVEL 02 - OVERALL Yes Yes Yes Yes

AUSTIN HIGH SCHOOL A-M20-03 MECHANICAL ENLARGED PLANS No No No Yes

AUSTIN HIGH SCHOOL A-M20-04 MECHANICAL ENLARGED PLANS No No No Yes

AUSTIN HIGH SCHOOL A-M20-05 - MECHANICAL ENLARGED PLANS No No No Yes

AUSTIN HIGH SCHOOL A-M30-00 MECHANICAL SCHEDULES Yes Yes Yes Yes

AUSTIN HIGH SCHOOL A-M40-00 MECHANICAL DETAILS Yes Yes Yes Yes

AUSTIN HIGH SCHOOL A-M40-01 MECHANICAL DETAILS No No No Yes

AUSTIN HIGH SCHOOL A-M50-00 MECHANICAL CONTROLS No No No Yes

AUSTIN HIGH SCHOOL A-M50-01 MECHANICAL CONTROLS No No No Yes

AUSTIN HIGH SCHOOL A-M50-02 MECHANICAL CONTROLS No No No Yes

AUSTIN HIGH SCHOOL A-P20-01 PLUMBING PLAN - LEVEL 01 - OVERALL Yes Yes Yes Yes

BOWIE MIDDLE SCHOOL

BOWIE MIDDLE SCHOOL B-A00.00 COVER SHEET Yes Yes Yes Yes

BOWIE MIDDLE SCHOOL B-E00-00 ELECTRICAL COVER SHEET Yes Yes Yes Yes

BOWIE MIDDLE SCHOOL B-E10-01 ELECTRICAL DEMOLITION PLAN - LEVEL 01 - OVERALL Yes Yes Yes Yes

BOWIE MIDDLE SCHOOL B-E20-01 ELECTRICAL POWER PLAN - LEVEL 01 - OVERALL Yes Yes Yes Yes

BOWIE MIDDLE SCHOOL B-E30-01 ELECTRICAL PANEL SCHEDULES No Yes Yes Yes

BOWIE MIDDLE SCHOOL B-E40-00 ELECTRICAL DETAILS Yes Yes Yes Yes

BOWIE MIDDLE SCHOOL B-M00-00 MECHANICAL COVER SHEET Yes Yes Yes Yes

BOWIE MIDDLE SCHOOL B-M10-01 MECHANICAL DEMOLITION PLAN - LEVEL 01 - OVERALL Yes Yes Yes Yes

BOWIE MIDDLE SCHOOL B-M20-01 MECHANICAL PLAN - LEVEL 01 - OVERALL Yes Yes Yes Yes

BOWIE MIDDLE SCHOOL B-M30-00 MECHANICAL SCHEDULES Yes Yes Yes Yes

BOWIE MIDDLE SCHOOL B-M40-00 MECHANICAL DETAILS Yes Yes Yes Yes

CROCKETT MIDDLE SCHOOL

CROCKETT MIDDLE SCHOOL C-A0.00 COVER SHEET Yes Yes Yes Yes

CROCKETT MIDDLE SCHOOL C-E00-00 ELECTRICAL COVER SHEET Yes Yes Yes Yes

CROCKETT MIDDLE SCHOOL C-E10-01 ELECTRICAL DEMOLITION PLAN - LEVEL 01 - OVERALL Yes Yes Yes Yes

CROCKETT MIDDLE SCHOOL C-E20-01 ELECTRICAL POWER PLAN - LEVEL 01 - OVERALL Yes Yes Yes Yes

CROCKETT MIDDLE SCHOOL C-E30-01 ELECTRICAL PANEL SCHEDULES Yes Yes Yes Yes

CROCKETT MIDDLE SCHOOL C-E40-00 ELECTRICAL DETAILS Yes Yes Yes Yes

CROCKETT MIDDLE SCHOOL C-FP00-00 FIRE PROTECTION COVER SHEET No Yes Yes Yes

CROCKETT MIDDLE SCHOOL C-FP20-01 FIRE PROTECTION PLAN - LEVEL 01 - OVERALL No No No Yes

CROCKETT MIDDLE SCHOOL C-FP20-02 FIRE PROTECTION PLAN - LEVEL 02 - OVERALL No Yes Yes Yes

CROCKETT MIDDLE SCHOOL C-M00-00 MECHANICAL COVER SHEET Yes Yes Yes Yes

CROCKETT MIDDLE SCHOOL C-M10-01 MECHANICAL DEMOLITION PLAN - LEVEL 01 - OVERALL Yes Yes Yes Yes

CROCKETT MIDDLE SCHOOL C-M20-01 MECHANICAL PLAN - LEVEL 01 - OVERALL Yes Yes Yes Yes

CROCKETT MIDDLE SCHOOL C-M30-00 MECHANICAL SCHEDULES Yes Yes Yes Yes

CROCKETT MIDDLE SCHOOL C-M40-00 MECHANICAL DETAILS Yes Yes Yes Yes

GARCIA MIDDLE SCHOOL

GARCIA MIDDLE SCHOOL G-A00.00 COVER SHEET Yes Yes Yes Yes

GARCIA MIDDLE SCHOOL G-E00-00 ELECTRICAL COVER SHEET Yes Yes Yes Yes

GARCIA MIDDLE SCHOOL G-E10-01 ELECTRICAL DEMOLITION PLAN - LEVEL 01 - OVERALL Yes Yes Yes Yes

GARCIA MIDDLE SCHOOL G-E20-01 ELECTRICAL POWER PLAN - LEVEL 01 - OVERALL Yes Yes Yes Yes

GARCIA MIDDLE SCHOOL G-E40-00 ELECTRICAL DETAILS Yes Yes Yes Yes

GARCIA MIDDLE SCHOOL G-FP00-00 FIRE PROTECTION COVER SHEET No Yes Yes Yes

GARCIA MIDDLE SCHOOL G-FP20-01 FIRE PROTECTION PLAN - LEVEL 01 - OVERALL Yes Yes Yes Yes

GARCIA MIDDLE SCHOOL G-FP20-02 FIRE PROTECTION PLAN - LEVEL 02 - OVERALL Yes No Yes Yes

GARCIA MIDDLE SCHOOL G-M00-00 MECHANICAL COVER SHEET No Yes Yes Yes

GARCIA MIDDLE SCHOOL G-M10-01 MECHANICAL DEMOLITION PLAN - LEVEL 01 - OVERALL No Yes Yes Yes

GARCIA MIDDLE SCHOOL G-M20-01 MECHANICAL PLAN - LEVEL 01 - OVERALL Yes Yes Yes Yes

GARCIA MIDDLE SCHOOL G-M30-00 MECHANICAL SCHEDULES Yes Yes Yes Yes

GARCIA MIDDLE SCHOOL G-M40-00 MECHANICAL DETAILS Yes Yes Yes Yes

HODGES BEND MIDDLE SCHOOL

HODGES BEND MIDDLE SCHOOL H-A0.00 COVER SHEET Yes Yes Yes Yes

HODGES BEND MIDDLE SCHOOL H-E00-00 ELECTRICAL COVER SHEET Yes Yes Yes Yes

HODGES BEND MIDDLE SCHOOL H-E10-01 ELECTRICAL DEMOLITION PLAN - LEVEL 01 - OVERALL Yes Yes Yes Yes

HODGES BEND MIDDLE SCHOOL H-E20-01 ELECTRICAL POWER PLAN - LEVEL 01 - OVERALL Yes Yes Yes Yes

HODGES BEND MIDDLE SCHOOL H-E30-01 ELECTRICAL PANEL SCHEDULES No Yes Yes Yes

HODGES BEND MIDDLE SCHOOL H-E40-00 ELECTRICAL DETAILS Yes Yes Yes Yes

HODGES BEND MIDDLE SCHOOL H-FP00-00 FIRE PROTECTION COVER SHEET No Yes Yes Yes

HODGES BEND MIDDLE SCHOOL H-FP20-01 FIRE PROTECTION PLAN - LEVEL 01 - OVERALL Yes Yes Yes Yes

HODGES BEND MIDDLE SCHOOL H-FP20-02 FIRE PROTECTION PLAN - LEVEL 02 - OVERALL No Yes Yes Yes

HODGES BEND MIDDLE SCHOOL H-M00-00 MECHANICAL COVER SHEET Yes Yes Yes Yes

HODGES BEND MIDDLE SCHOOL H-M10-01 MECHANICAL DEMOLITION PLAN - LEVEL 01 - OVERALL Yes Yes Yes Yes

HODGES BEND MIDDLE SCHOOL H-M20-01 MECHANICAL PLAN - LEVEL 01 - OVERALL Yes Yes Yes Yes

HODGES BEND MIDDLE SCHOOL H-M30-00 MECHANICAL SCHEDULES Yes Yes Yes Yes

HODGES BEND MIDDLE SCHOOL H-M40-00 MECHANICAL DETAILS Yes Yes Yes Yes

HODGES BEND MIDDLE SCHOOL H-P20-01 PLUMBING PLAN - LEVEL 01 - OVERALL Yes Yes Yes Yes

SHEET INDEX

Discipline

SHEET

NO. SHEET NAME SD / DD 50% CD 90% CD

ISSUE

FOR BID

TRAVIS HIGH SCHOOL

TRAVIS HIGH SCHOOL T-A00.00 COVER SHEET Yes Yes Yes Yes

TRAVIS HIGH SCHOOL T-E00-00 ELECTRICAL COVER SHEET Yes Yes Yes Yes

TRAVIS HIGH SCHOOL T-E10-01 ELECTRICAL DEMOLITION PLAN - LEVEL 01 - OVERALL Yes Yes Yes Yes

TRAVIS HIGH SCHOOL T-E10-02 ELECTRICAL DEMOLITION PLAN - LEVEL 02 - OVERALL Yes Yes Yes No

TRAVIS HIGH SCHOOL T-E20-01 ELECTRICAL POWER PLAN - LEVEL 01 - OVERALL Yes Yes Yes Yes

TRAVIS HIGH SCHOOL T-E20-02 ELECTRICAL POWER PLAN - LEVEL 02- OVERALL Yes Yes Yes No

TRAVIS HIGH SCHOOL T-E30-00 ELECTRICAL SCHEDULES & DIAGRAMS Yes Yes Yes Yes

TRAVIS HIGH SCHOOL T-E40-00 ELECTRICAL DETAILS Yes Yes Yes Yes

TRAVIS HIGH SCHOOL T-FP00-00 FIRE PROTECTION COVER SHEET No Yes Yes Yes

TRAVIS HIGH SCHOOL T-FP20-01 FIRE PROTECTION PLAN - LEVEL 01 - OVERALL Yes Yes Yes Yes

TRAVIS HIGH SCHOOL T-M00-00 MECHANICAL COVER SHEET Yes Yes Yes Yes

TRAVIS HIGH SCHOOL T-M10-01 MECHANICAL DEMOLITION PLAN - LEVEL 01 - OVERALL Yes Yes Yes Yes

TRAVIS HIGH SCHOOL T-M10-02 MECHANICAL DEMOLITION PLAN - LEVEL 02 - OVERALL Yes Yes Yes Yes

TRAVIS HIGH SCHOOL T-M20-01 MECHANICAL PLAN - LEVEL 01 - OVERALL No Yes Yes Yes

TRAVIS HIGH SCHOOL T-M20-02 MECHANICAL PLAN - LEVEL 02 - OVERALL No Yes Yes Yes

TRAVIS HIGH SCHOOL T-M30-00 MECHANICAL SCHEDULES No Yes Yes Yes

TRAVIS HIGH SCHOOL T-M40-00 MECHANICAL DETAILS No Yes Yes Yes

TRAVIS HIGH SCHOOL T-M50-00 MECHANICAL CONTROLS No No No Yes

WALKER STATION ELEMENTARY SCHOOL

WALKER STATION ELEMENTARY SCHOOL W-A00.00 COVER SHEET No No No Yes

WALKER STATION ELEMENTARY SCHOOL W-FP00-00 FIRE PROTECTION COVER SHEET No No No Yes

WALKER STATION ELEMENTARY SCHOOL W-FP20-01 FIRE PROTECTION PLAN - LEVEL 01 - OVERALL No No No Yes

FORT BEND ISD 2023 BOND PROGRAM

HVAC MEP WEST ZONE 3

AUSTIN HIGH SCHOOL

3434 PHEASANT CREEK DR, SUGAR LAND, TX 77498

BOWIE MIDDLE SCHOOL

700 PLANTATION DRIVE, RICHMOND TX 77406

CROCKETT MIDDLE SCHOOL

19001 BEECHNUT ST. RICHMOND TX 77407

GARCIA MIDDLE SCHOOL

18550 OLD RICHMOND RD. SUGAR LAND TX 77498

HODGES BEND MIDDLE SCHOOL

16510 BISSONNETT STREET, HOUSTON TX 77083

TRAVIS HIGH SCHOOL

11111 HARLEM ROAD, RICHMOND TX 77046

WALKER STATION ELEMENTARY SCHOOL

6200 HOMEWARD WAY, SUGAR LAND TX 77479

PROJECT MAP

DATE

JOB

SHEET

ISSUES

REVISIONS

SHEET LIST

KEYPLAN

This Document was produced by or under the authority of Registered Architect:

Date of issue:

This document is incomplete and may not be used for regulatory approval, permit or construction.

/2

/2

:5 :0

P

M

COVER SHEET

9.29.2025

25241.000

16431 Lexington Blvd T: Sugar Land, TX 77479

F: 281.634.5590 CONTACT: Contact: Juan Valdez email: cn_juan.valdez@fortbendisd.com

2 09.29.2025 50% CDs

1 07.18.2025 SD / DD

4 12.11.2025 ISSUE FOR BID

C O

V E

R S

H E

E T

9.29.2025

9 GREENWAY PLAZA SUITE 3000

T: HOUSTON, TX 77046

F O

R T

B E

N D

I S

D B

P

H V

A C

M E

P W

E S

T

PROJECT DATA

PROJECT NAME:

PROJECT ADDRESS:

APPLICABLE CODES

LIFE SAFETY INFORMATION

USE OR OCCUPANCY CLASSIFICATION

OCCUPANCY:

TYPE OF CONSTRUCTION

CONSTRUCTION TYPE:

PROJECT SCOPE

OWNER:

BUILDING CODE:

ACCESSIBILITY CODE:

ELECTRICAL CODE:

ENERGY CODE:

FIRE CODE:

MECHANICAL CODE:

PLUMBING CODE:

REGIONAL OR MUNICIPAL CODE:

FORT BEND ISD

BP048 - HVAC MEP WEST 3 - AUSTIN HS

50% CONSTRUCTION DOCUMENTS

A U

S T

IN

H

S

P H

E A

S A

N T

C R

E E

K D

R

S U

G A

R L

A N

D

T X

PROJECT MAP

A-A00.00

BP048 - HVAC - MEP WEST 3

AUSTIN HIGH SCHOOL

3434 PHEASANT CREEK DRIVE SUGAR LAND, TX 77498

FBISD

2015 INTERNATIONAL BUILDING CODE

2012 TEXAS ACCESSIBILTY STANDARDS

2023 STATE OF TEXAS ADOPTED NATIONAL ELECTRICAL CODE

2015 INTERNATIONAL ENERGY CONSERVATIVE CODE

2021 INTERNATIONAL FIRE CODE

2021 INTERNATIONAL MECHANICAL CODE

2015 INTERNATIONAL PLUMBING CODE

FORT BEND COUNTY

E-1 EDUCATION

II B

REPLACE CENTRAL STATION AHUs AND PROVIDE DIRECT DIGITAL CONTROLS

REPLACE VAV UNITS ON THE FIRST AND SECOND FLOOR

REPLACE HEATING WATER PUMPS AND PROVIDE VARIABLE FREQUENCY DRIVE (VFDs)

PROVIDE PIPING INSULATION ON SPRINKLER PIPING IN CRITICAL AREAS5

REPLACE MAIN SHUT OFF VALVE NEAR COOLING TOWER

90% CONSTRUCTION DOCUMENTS

11.12.2025 90% CDs

11.12.2025

11.12.2025

/1

2/

:3

P M

Date of issue:

12.11.2025

FORT BEND ISD

BP048 - HVAC MEP WEST ZONE 3 - AUSTIN HS

ISSUE FOR BID

12.11.2025

/1

2/

:3

P M

/1 1/

1:

A

M

FO

R

T

BE

N D

IS

D

B P0

H

V A

C M

E P

W E

S T

Z O

N E

AV AVAV

J

J

TV

C

PP

ABBREVIATIONS

(E) EXISTING TO REMAIN

(ER) EXISTING TO BE RE-CIRCUITED

(N) NEW

(R) ITEM NOTED TO BE RELOCATED

(D) ITEM NOTED TO BE DEMOLISHED

AFF ABOVE FINISHED FLOOR

AD AUTOMATIC DAMPER

AIC AMPERE INTERRUPTING CAPACITY

AL ALUMINUM

AMP AMPERAGE

ATS AUTOMATIC TRANSFER SWITCH

AWG AMERICAN WIRE GAUGE

BKR BREAKER

C CONDUIT

CKT. CIRCUIT

CT CURRENT TRANSFORMER

DC DIRECT CURRENT

DISC. DISCONNECT

EC ELECTRICAL CONTRACTOR

EMT ELECTRICAL METALLIC TUBING

EPO EMERGENCY POWER OFF

FA FIRE ALARM

FACP FIRE ALARM CONTROL PANEL

FC FOOT CANDLE

FLA FULL LOAD AMPS

GC GENERAL CONTRACTOR

GFI GROUND FAULT CIRCUIT INTERRUPTER

GND. GROUND

HD HEAVY DUTY

HOA HAND-OFF-AUTO

HP HORSEPOWER

IG ISOLATED GROUND

KCM THOUSAND CIRCULAR MILS

KW KILOWATT

MC METAL CLAD

MCB MAIN CIRCUIT BREAKER

MH METAL HALIDE

MSB MAIN SWITCHBOARD

MLO MAIN LUG ONLY

NEC NATIONAL ELECTRIC CODE

NEMA NATIONAL ELECTRICAL MANUFACTURES ASSOCIATION

NFPA NATIONAL FIRE PROTECTION ASSOCIATION

NIC NOT IN CONTRACT

NF NON-FUSED

NL NIGHT LIGHT

NTS NOT TO SCALE

PH PHASE

PNL PANEL OR PANELBOARD

PVC POLYVINYL CHLORIDE

RACP REMOTE ANNUNCIATOR CONTROL PANEL

RCP REFLECTED CEILING PLAN

RE: REFERENCE

SFD SMOKE/FIRE DAMPER

SPEC. SPECIFICATIONS

SF SQUARE FEET

TS TIME SWITCH

TTB TELEPHONE TERMINAL BOARD

TYP TYPICAL

UG UNDERGROUND

U.N.O. UNLESS NOTED OTHERWISE

UPS UNINTERRUPTIBLE POWER SUPPLY

V VOLTAGE

VFD VARIABLE FREQUENCY DRIVE

WP WEATHER PROOF

XFMR TRANSFORMER

APPLICABLE CODES & STANDARDS

1. BUILDING CODE - 2015 IBC WITH LOCAL AMENDMENTS

2. FIRE CODE - 2021 IFC WITH LOCAL AMENDMENTS

3. ELECTRICAL CODE - 2023 NEC WITH LOCAL AMENDMENTS

4. MECHANICAL CODE - 2021 IMC WITH LOCAL AMENDMENTS

5. PLUMBING CODE - 2015 IPC WITH LOCAL AMENDMENTS

6. ENERGY CODE - 2015 INTERNATIONAL ENERGY CONSERVATION CODE WITH LOCAL

AMENDMENTS.

7. OTHER - LIFE SAFETY CODE (NFPA 101)

8. OTHER - FEDERAL DEPARTMENT OF JUSTICE AMERICANS WITH DISABILITIES ACT AND TEXAS

ACCESSIBILITY STANDARDS.

9. FIRE ALARM - 2021 NFPA 72 WITH LOCAL AMENDMENTS.

BREAK OUT PRICING

THE CONTRACTOR SHALL PROVIDE SEPARATE LINE-ITEM COST FOR ALL WORK AND MATERIALS ASSOCIATED

WITH EACH OF THE FOLLOWING:

1. INSTALLATION FOR ONE (1) DEDICATED 20-AMP DUPLEX RECEPTACLE.

2. INSTALLATION FOR ONE (1) DEDICATED 20-AMP QUAD RECEPTACLE.

3. INSTALLATION FOR ONE (1) RING AND STRING ROUGH-IN FOR VOICE/DATA OUTLET.

4. INSTALLATION FOR ONE (1) DEDICATED 120-VOLT JUNCTION BOX.

5. INSTALLATION FOR ONE (1) LAY-IN 2'X4' LIGHT FIXTURE ON AN EXISTING 277-VOLT SWITCHED CIRCUIT

WITH 8 FT OF CONDUIT/CONDUCTORS.

6. CIRCUIT TRACE OF ALL EXISTING CIRCUITS IN ALL PANELS USED IN THIS PROJECT. SEE PANEL

SCHEDULES.

PRICES SHALL INCLUDE ALL INSTALLATION COST, INCLUDING CONDUIT(S) AND BRANCH CIRCUIT CONDUCTORS AS REQUIRED. ASSUME 100 FT CONDUIT AND CONDUCTOR LENGTH FROM SOURCE TO LOAD U.N.O.

ELECTRICAL GENERAL NOTES

A. GENERAL PROVISIONS

1. FURNISH AND INSTALL ALL ITEMS, INCLUDING EVERY ARTICLE , DEVICE OR ACCESSORY REASONABLY NECESSARY TO FACILITATE EACH

SYSTEM'S FUNCTIONING AS INDICATED BY THE DESIGN AND THE EQUIPMENT SPECIFIED. ELEMENTS OF THE WORK SHALL INCLUDE, BUT ARE NOT LIMITED TO, MATERIALS, LABOR, SUPERVISIONS, SUPPLIES, EQUIPMENT, TRANSPORTATION, HOISTING/RIGGING, STORAGE, UTILITIES, AND ALL REQUIRED PERMITS AND LICENSES.

2. DRAWINGS ARE SCHEMATIC IN NATURE AND DO NOT NECESSARILY REFLECT ALL WORK REQUIRED TO COMPLETE PROJECT. CONTRACTOR SHALL PROVIDE ALL MATERIALS, LABOR, AND EQUIPMENT AS REQUIRED TO COMPLETE PROJECT WITHIN DESIGN INTENT AT NO ADDITIONAL COST TO OWNER/TENANT. CONTRACTOR SHALL REQUEST ADDITIONAL INFORMATION IN CASES OF DOUBT.

3. WORK SHALL COMPLY WITH THE MOST RECENT VERSION OF ALL APPLICABLE LAWS, RULES, REGULATIONS, AND ORDINANCES OF ALL FEDERAL, STATE, AND LOCAL AUTHORITIES. IN THE EVENT OF CONFLICT BETWEEN THE CONTRACT DOCUMENTS AND THE LOCAL ENFORCING AUTHORITY, THE LATTER SHALL RULE. ANY MODIFICATION RESULTING THEREFROM SHALL BE MADE WITHOUT ADDITIONAL COST TO THE OWNER OR ARCHITECT/ENGINEER. THE CONTRACTOR SHALL REPORT ANY SUCH MODIFICATIONS TO THE ARCHITECT/ENGINEER AND SECURE THEIR APPROVAL BEFORE PROCEEDING. SHOULD THE REQUIREMENTS OF THE CONTRACT DUCMENTS EXCEED THE REQUIREMENTS OF THE CODES, THE CONTRACT DOCUMENTS SHALL TAKE PRECEDENCE PROVIDED THEY ARE NOT IN

CONFLICT WITH THOSE CODES.

4. AREAS OF THE EXISTING BUILDING WILL BE OCCUPIED DURING CONSTRUCTION OF THIS PROJECT. NOISY, DUSTY, AND/OR OTHER CONSTRUCTION OPERATIONS REQUIRED FOR WORK WHICH DISTURB OR CAUSE COMPLAINTS BY THE EXISTING BUILDING OCCUPANTS SHALL NOT BE ACCEPTABLE. ALL AFTER-HOUR OR OVERTIME WORK REQUIRED BY THE CONTRACTOR TO AVOID DISRUPTION OF EXISTING OCCUPANTS WILL BE PROVIDED AT NO COST TO THE OWNER/TENANT. THE CONTRACTOR SHALL USE CONSTRUCTION METHODS AND MATERIALS WHICH SHALL NOT ADVERSELY AFFECT THE INDOOR AIR QUALITY OF THE EXISTING OCCUPIED AREAS.

5. CONSIDERATION SHALL NOT BE GRANTED FOR MISUNDERSTANDING OF THE SCOPE OR AMOUNT OF WORK TO BE PERFORMED. TENDER OF A PROPOSAL CONVEYS FULL CONTRACTOR AGREEMENT OF THE ITEMS AND CONDITIONS SPECIFIED AND/OR INDICATED, SCHEDULED, OR

IMPLIED ON THE CONTRACT DOCUMENTS, AND/OR REQUIRED BY THE NATURE OF THIS WORK.

6. IN THE EVENT OF A CONFLICT BETWEEN DRAWINGS AND/OR SPECIFICATIONS, THE GREATER AMOUNT OF TOTAL COST SHALL BE PRICED.

BRING THE CONFLICT TO THE ATTENTION OF THE ENGINEER AND REQUEST DIRECTION.

B. PRE-CONSTRUCTION

1. BEFORE SUBMITTING A BID, IT WILL BE NECESSARY FOR EACH CONTRACTOR WHOSE WORK IS INVOLVED TO VISIT THE SITE AND ASCERTAIN

FOR THEMSELVES THE CONDITIONS TO BE MET IN INSTALLING THE WORK AND MAKE PROVISIONS FOR THE CONDITIONS IN THEIR FINAL PRICE. FAILURE ON THE PART OF THE CONTRACTOR TO COMPLY WITH THIS REQUIREMENT SHALL NOT BE CONSIDERED JUSTIFICATION FOR THE OMISSION OR FAULTY INSTALLATION OF ANY WORK COVERED BY THE CONTRACT DOCUMENTS.

2. THIS CONTRACTOR SHALL SECURE ALL PERMITS, LICENSES AND INSPECTIONS REQUIRED FOR THEIR WORK, AND SHALL PAY ALL FEES IN

CONNECTION WITH SUCH PERMITS, LICENSES AND INSPECTIONS.

C. DEMOLITION

1. ALL EXISTING CONDUIT AND CONDUCTORS SERVING THE AREA UNDER CONTRACT NOT TO BE RE-USED SHALL BE TERMINATED AT LAST

PORTION OF CIRCUIT REQUIRING ENERGIZATION BEFORE THE DEMOLITION AREA. IF A CIRCUIT SERVICES ONLY THE DEMOLITION AREA, REMOVE ALL CONDUITS AND CONDUCTORS BACK TO THE PANELBOARD OR BASE BUILDING GRID BOX AND DE-ENERGIZE THE CIRCUIT BREAKER, MAKING IT A SPARE. NOTE "SPARE" OR "GRID-SPARE" ACCORDINGLY ON PANELBOARD DIRECTORY.

2. REMOVE ALL ABANDONED LOW VOLTAGE CABLING INCLUDING FIRE ALARM CABLING, TELEPHONE/DATA CABLING, AND SECURITY CABLING.

REMOVE ALL EXISTING CONDUIT AND WIRING THAT IS SUPPORTED FROM THE CEILING GRID. REMOVE ALL EXISTING UNUSED ELECTRICAL

EQUIPMENT, CONTROLS, CONDUIT, HANGERS, WIRING, ETC.

3. RELOCATE AND RECONNECT ACTIVE PORTIONS OF THE ELECTRICAL SYSTEM OUTSIDE OF THE SCOPE OF DEMOLITION, AS REQUIRED TO MAINTAIN A COMPLETE AND OPERATING SYSTEM THAT IS FUNCTIONALLY EQUIVALENT TO THE PRE-EXISTING SYSTEM PRIOR TO

DEMOLITION.

4. ELECTRICAL PLANS INDICATE FINAL WIRING DEVICE, DATA/COMMUNICATIONS OUTLET AND SWITCH LOCATIONS. ALL OTHER EXISTING WIRING DEVICES, DATA/COMMUNICATIONS OUTLETS AND SWITCHES SHALL BE REMOVED AND WALLS SHALL BE PATCHED, UNLESS

OUTSIDE OF SCOPE OR NOTED AS (E).

5. ALL EXISTING JUNCTION BOXES, OUTLETS, PULL BOXES, ETC., LOCATED ABOVE NON-ACCESSIBLE CEILINGS INSTALLED UNDER THIS TENANT IMPROVEMENT PROJECT SHALL BE RELOCATED AS NECESSARY TO A LOCATION ABOVE AN ACCESSIBLE CEILING. WHERE EXISTING JUNCTION BOXES ARE NOT PRACTICAL TO RE-LOCATE, ELECTRICAL CONTRACTOR SHALL NOTIFY ARCHITECT AND ENGINEER PRIOR TO

SUBSTANTIAL START OF CONSTRUCTION.

6. REMOVE ALL EXISTING UNUSED ELECTRICAL EQUIPMENT, CONTROLS, CONDUIT, HANGERS, WIRING, ETC.. FROM ABOVE CEILINGS.

7. REFER TO ARCHITECTURAL DRAWINGS FOR LIGHT FIXTURES TO BE RELOCATED. RELOCATE AND RECIRCUIT FIXTURES AS SHOWN.

PROVIDE ADDITIONAL FIXTURES TO MATCH FIXTURE QUANTITIES SHOWN. FIELD VERIFY EXISTING CONDITIONS.

8. REFER TO ARCHITECTURAL PLANS FOR WALL AND PARTITIONS TO BE REMOVED. CONTRACTOR SHALL PROVIDE ELECTRICAL DEMOLITION

AS PREVIOUSLY DESCRIBED.

9. REFER TO ARCHITECTURAL DRAWINGS FOR RECEPTACLES AND VOICE/DATA OUTLETS TO BE REMOVED. FIELD VERIFY EXISTING

CONDITIONS.

10. CONTRACTOR SHALL REMOVE AND REPLACE ALL WIRING DEVICES NOT CONFORMING TO BUILDING STANDARDS.

11. REMOVE ALL EXISTING CONDUIT AND WIRING THAT IS SUPPORTED FROM THE CEILING GRID VIA CADDY CLIPS, ETC. AND REPLACE EXISTING CONDUIT THAT IS TO BE REUTILIZED WITH MATCHING CONDUIT AND WIRING PROPERLY SUPPORTED FROM STRUCTURE ABOVE.

12. RE-SUPPORT AND/ RE-ROUTE ANY REMAINING PIPING OR DEVICES THAT WERE SUPPORTED BY DEMOLISHED WALLS.

13. ALL ITEMS INSTALLED IN AIR PLENUMS SHALL BE PLENUM RATED.

D. SUBMITTALS

1. ALL EQUIPMENT AND MATERIAL TO BE FURNISHED AND INSTALLED ON THIS PROJECT SHALL BE UL OR ETL LISTED, IN ACCORDANCE WITH

THE AUTHORITY HAVING JURISDICTION, AND SUITABLE FOR ITS INTENDED USE ON THIS PROJECT.

2. THE CONTRACTOR SHALL PROVIDE SUBMITTALS FOR ALL NEW EQUIPMENT, CONTROLS, DEVICES, AND FIXTURES TO BE PROVIDED. SUBMIT

MINIMUM ELECTRONIC SUBMITTALS FOR APPROVAL.

3. MATERIALS AND EQUIPMENT SHALL BE NEW AND IN GOOD CONDITION. THE COMMERCIALLY STANDARD ITEMS OF EQUIPMENT AND THE SPECIFIC NAMES INDICATED ARE INTENDED TO IDENTIFY STANDARDS OF QUALITY AND PERFORMANCE NECESSARY FOR THE PROPER FUNCTIONING OF THE WORK. MATERIALS AND EQUIPMENT, WHICH ARE FOUND TO HAVE FACTORY DEFECTS SHALL BE REPLACED OR REPAIRED IN A MANNER ACCEPTABLE TO THE OWNER/TENANT AND ENGINEER AT NO ADDITIONAL COST TO THE OWNER/TENANT.

4. THE FOLLOWING SUBMITTAL DATA SHALL BE FURNISHED AND SHALL INCLUDE BUT NOT BE LIMITED TO:

A. EQUIPMENT AND MATERIALS SHOP DRAWINGS

B. COORDINATION DRAWINGS

C. RECORD DRAWINGS

D. OPERATING AND MAINTENANCE MANUALS

E. FIRE STOP MATERIALS AND DETAILS

E. PRE-CONSTRUCTION FUNCTIONAL TEST

1. PRIOR TO ANY CONSTRUCTION, THE CONTRACTOR SHALL FUNCTIONALLY TEST ALL ELECTRICAL AND FIRE ALARM EQUIPMENT THAT IS

EXISTING TO REMAIN OR RELOCATED IN THIS PROJECT. THE CONTRACTOR SHALL PROVIDE A WRITTEN DESCRIPTION OF ANY AND ALL DEFICIENCIES TO THE OWNER/TENANT. ANY DEFICIENCIES FOUND AFTER THE START OF CONSTRUCTION SHALL BE REPAIRED OR REPLACED AT NO COST TO THE OWNER/TENANT. THE EQUIPMENT TO BE TESTED INCLUDES, BUT IS NOT LIMITED TO: RECEPTACLES, LIGHT FIXTURES, EXIT SIGNS, OCCUPANCY SENSORS, PANEL BOARDS, TRANSFORMERS, EMERGENCY LIGHTING BATTERY UNITS, AND SWITCHES.

2. FOR EXISTING LIGHT FIXTURES AND EXIT SIGNS WITH BATTERY PACKS, ELECTRICAL CONTRACTOR SHALL ASSUME NEW BATTERY PACKS

WILL BE REQUIRED UNLESS FUNCTIONAL TEST PROVES OTHERWISE.

E. CONSTRUCTION

1. ALL WORK SHALL BE ARRANGED IN A NEAT, WELL ORGANIZED MANNER. ALL SERVICES SHALL BE ROUTED PARALLEL AND PERPENDICULAR

TO THE PRIMARY LINES OF THE BUILDING. LOCATE ALL OPERATING AND CONTROL EQUIPMENT PROPERLY TO PROVIDE EASY ACCESS AND ARRANGE ENTIRE WORK WITH ADEQUATE ACCESS FOR OPERATION AND MAINTENANCE, AND FOR PROPER CODE AND/OR

MANUFACTURERS CLEARANCES.

2. DAMAGE CAUSED DURING CONSTRUCTION TO EXISTING MATERIALS/EQUIPMENT WILL BE REPAIRED OR REPLACED AT NO ADDITIONAL COST TO OWNER. RE-SUPPORT ANY REMAINING PIPING OR DEVICES THAT WERE SUPPORTED BY WALLS BEING REMOVED.

3. THE GENERAL CONTRACTOR AND ALL SUBCONTRACTORS SHALL COORDINATE THE INSTALLATION OF DUCTWORK, PIPING, CONDUIT, CABLE, ETC., WITH LIGHTING FIXTURES, SPECIAL CEILING CONSTRUCTION, AIR DISTRIBUTION EQUIPMENT, AND THE STRUCTURE. PROVIDE ADDITIONAL RISES AND OFFSETS AS REQUIRED. IF, AFTER INSTALLED, NEW DUCTWORK, PIPING, CONDUIT, CABLE, ETC., IS FOUND TO BE IN CONFLICT WITH THE ARCHITECTURE, STRUCTURE OR OTHER TRADE WORK, WHICH IS EITHER EXISTING OR SHOWN ON THE CONTRACT DOCUMENTS, THE DUCTWORK, PIPING, CONDUIT, CABLE, ETC., SHALL BE RELOCATED WITHOUT ADDITIONAL COST TO THE OWNER/TENANT.

COORDINATE ALL WORK COMPLETELY WITH ALL OTHER TRADES PRIOR TO INSTALLATION.

4. ALL BUILDING SERVICES, UTILITIES, POWER, FIRE PROTECTION, AND DOMESTIC COLD AND HOT WATER MAY NOT BE DISRUPTED FOR ANY

REASON WITHOUT PRIOR COORDINATION WITH A REPRESENTATIVE OF BUILDING OPERATIONS.

5. THIS BUILDING MAY HAVE A STRUCTURAL SYSTEM UTILIZING POST-TENSIONED CABLES. THE CONTRACTOR SHALL DETERMINE THE EXISTING STRUCTURAL SYSTEM PRIOR TO CUTTING, DRILLING, OR CORING. THE CONTRACTOR SHALL X-RAY ALL PENETRATIONS PRIOR TO

CUTTING THE FLOOR SLAB.

6. PENETRATIONS THROUGH FLOORS OR FIRE-RATED CONSTRUCTION SHALL BE FIRESAFED TO COMPLY WITH ASTM E-814 (UL 1479), AND THE

LOCAL AUTHORITY HAVING JURISDICTION.

F. PROJECT CLOSE OUT

1. UPON COMPLETION OF THE PROJECT, THE CONTRACTOR SHALL SUBMIT TO THE ENGINEER A COMPLETE SET OF "AS BUILT" DRAWINGS

PORTRAYING ACTUAL SITE CONDITIONS OF THE MECHANICAL, ELECTRICAL, PLUMBING, AND FIRE PROTECTION WORK. SUBMISSION SHALL CONSIST OF ONE SET OF PDF AND ONE SET OF CAD FILES IN AUTOCAD V. 2016 OR REVIT V. 2018 OR NEWER FORMAT WITH THE OWNER'S

STANDARD LAYERING SCHEME.

2. EXISTING CIRCUITRY IS SHOWN FOR INFORMATION ONLY. EXISTING CIRCUITRY INFORMATION TAKEN FROM COMBINATION OF FIELD SURVEY AND PREVIOUS TENANT DRAWINGS. CONTRACTOR SHALL FIELD VERIFY EXACT CIRCUITRY AND INDICATE ANY DEVIATIONS ON THE "AS BUILT" DRAWINGS. "AS BUILT" DRAWINGS SHALL ACCURATELY INDICATE THE LOCATION OF ALL NEW AND EXISTING JUNCTION BOXES WITH

THE RESPECTIVE PANEL AND CIRCUIT NUMBERS.

3. SUBMIT "AS-BUILT" RECORD DRAWINGS INDICATING ACTUAL AS-BUILT CONDITIONS TO THE ARCHITECT/ENGINEER FOR REVIEW. RECORD DRAWINGS SHALL BE STAMPED "AS-BUILT" AND SHALL HAVE THE NAME, ADDRESS, AND TELEPHONE NUMBER OF THE CONTRACTOR. ALL ENGINEERS' SEALS SHALL BE REMOVED FROM THE DRAWINGS. PROVIDE BLACK AND WHITE DIGITAL COPIES AND ONE (1) ELECTRONIC FILE.

4. SUBMIT ELECTRONIC PDF OF OPERATION AND MAINTENANCE MANUALS. THE MANUALS SHALL INCLUDE RATINGS, CAPACITIES, PARTS

LISTS, WIRING DIAGRAMS, SERVICE/MAINTENANCE RECOMMENDATIONS, AND WARRANTIES.

5. THE ELECTRICAL CONTRACTOR SHALL PERFORM THE FOLLOWING TASKS UPON PROJECT COMPLETION. ALL REQUIRED REPORTS AND AS- BUILTS SHALL BE SUBMITTED WITHIN TWO (2) WEEKS OF DATE OF SUBSTANTIAL COMPLETION OR OWNER OCCUPANCY.

6. SUBMIT WRITTEN RESPONSE TO ALL FIELD REPORTS INDICATING CORRECTIVE ACTIONS TAKEN AND DATE CORRECTIVE ACTION WAS

TAKEN TO THE ARCHITECT/ENGINEER FOR REVIEW.

G. WARRANTY

1. THE START OF THE CONTRACTOR'S WARRANTY PERIOD SHALL COMMENCE ON THE DATE OF "SUBSTANTIAL COMPLETION" AS AGREED TO

BY THE OWNER/TENANT.

2. THE WARRANTY PERIOD SHALL BE NO LESS THAN ONE (1) FULL YEAR, UNLESS SPECIFIED OTHERWISE AND SHALL INCLUDE AT LEAST ONE

(1) FULL HEATING SEASON AND ONE (1) FULL COOLING SEASON. DURING THE WARRANTY PERIOD THE CONTRACTOR SHALL GUARANTEE

THE FOLLOWING IN A FORM SATISFACTORY TO THE OWNER/TENANT:

A. WORK INSTALLED SHALL BE FREE FROM ANY AND ALL DEFECTS IN WORKMANSHIP AND/OR MATERIALS.

B. APPARATUS WILL DEVELOP CAPACITIES AND PERFORMANCE CHARACTERISTICS SPECIFIED.

C. SYSTEMS SHALL OPERATE WITHOUT MALFUNCTION.REQUIRED SUBMITTALS

ELECTRICAL GEAR

WIRING DEVICES

LIGHTING FIXTURES & CONTROLS

LIGHTING CONTROL SHOP DRAWING

ALL SUBMITTALS SHALL BE SUBMITTED VIA EMAIL TO SUBMITTALS@WYLIEENG.COM

AND COPIED TO THE PROJECT MANAGER.

ALL RFI'S SHALL BE SUBMITTED VIA EMAIL TO RFI@WYLIEENG.COM

AND COPIED TO THE PROJECT MANAGER.

DRAWING INDEX

ELECTRICAL SPECIFICATIONS ELECTRICAL SPECIFICATIONS

1. ALL PANELBOARDS, MOTOR STARTERS, CONTROL PANELS, CONTROL REMOTE STATIONS, DISCONNECT SWITCHES, CIRCUIT BREAKERS OR OTHER EQUIPMENT IN SEPARATE ENCLOSURES SHALL BE EQUIPPED WITH NAMEPLATES. THE NAMEPLATES SHALL BE ENGRAVED RIGID PLASTIC LAMINATE OR APPROVED

EQUAL, WHITE LETTERING ON BLACK BACKGROUND FOR EQUIPMENT 208/120 VOLT AND BLACK

LETTERING ON WHITE BACKGROUND FOR EQUIPMENT 480/277 VOLT, AND BE ATTACHED TO THE

EQUIPMENT SECURELY WITH SCREWS. EACH NAMEPLATE SHALL GIVE THE NUMBER DESIGNATION OF THE EQUIPMENT AS SHOWN ON THE ONE LINE DIAGRAM AND ALSO THE SOURCE. UTILIZE SIMILAR RED

AND WHITE NAMEPLATES FOR ALL EMERGENCY POWERED EQUIPMENT.

2. ALL WIRING DEVICES (EXCLUDING LIGHT SWITCHES) SHALL BE LABELED WITH SELF-ADHESIVE, LAMINATED TAPE INDICATING THE CIRCUIT NUMBER AND PANEL DESIGNATIONS. UTILIZE CLEAR TAPE WITH BLACK LETTERS UNLESS NOTED OTHERWISE. PROVIDE SAMPLE OF LABELS TO ARCHITECT AND

LANDLORD FOR APPROVAL PRIOR TO INSTALLATION.

3. NEW AND EXISTING CIRCUITRY SHALL BE ACCURATELY IDENTIFIED AT THE RESPECTIVE ABOVE CEILING JUNCTION BOXES. THE ASSOCIATED PANEL, CIRCUITS, AND VOLTAGE SHALL BE IDENTIFIED ON ALL JUNCTION BOX COVERS. CIRCUITS LEAVING PANELBOARDS AND DISTIBUTION PANELS SHALL BE

PROVIDED WITH LABEL ON CIRCUITS CONTAINED IN CONDUIT.

4. EXISTING CIRCUITRY IS SHOWN FOR INFORMATION ONLY. EXISTING CIRCUITRY INFORMATION TAKEN FROM COMBINATION OF FIELD SURVEY AND PREVIOUS TENANT DRAWINGS. CONTRACTOR SHALL FIELD VERIFY EXACT CIRCUITRY AND INDICATE ANY DEVIATIONS ON THE "AS BUILT" DRAWINGS. "AS BUILT" DRAWINGS SHALL ACCURATELY INDICATE THE LOCATION OF ALL NEW AND EXISTING JUNCTION BOXES

WITH THE RESPECTIVE PANEL AND CIRCUIT NUMBERS.

LOW VOLTAGE PROVISIONS

IDENTIFICATION/LABELING

BOLD DEVICE/CIRCUITING INDICATES NEW DEVICE/CIRCUITING

OR RELOCATED DEVICE.

SHADED DEVICE/CIRCUITING INDICATES EXISTING TO REMAIN

DASHED DEVICE/CIRCUITING INDICATES DEMOLITION

CONDUIT RUN CONCEALED IN WALLS OR ABOVE CEILING. ARROW

INDICATES HOMERUN TO PANEL. CONDUCTOR DESIGNATIONS ARE AS

FOLLOWS: LONG HATCH INDICATES NEUTRAL, SHORT HATCH

INDICATES PHASE, "DOT" INDICATES INSULATED OR ISOLATED

GROUND, AND NO HATCHES INDICATES TWO CONDUCTORS.

CONDUIT RUN CONCEALED IN FLOOR SLAB, BELOW FLOOR SLAB

OR BELOW GRADE. WIRING SAME AS ABOVE.

LIGHT FIXTURE TAG:

A = FIXTURE TYPE

XX = CIRCUIT NUMBER

a = SWITCH LEG

SIMPLEX RECEPTACLE OUTLET; 20 AMP, 125V., 3 WIRE, GROUNDED TYPE

OR SPECIAL RECEPTACLE OUTLET: SEE DRAWIINGS FOR NEMA

CONFIGURATION AND VOLTAGE.

DUPLEX RECEPTACLE OUTLET; 20 AMP, 125V., 3 WIRE, GROUNDED TYPE.

TWO(2) DUPLEX RECEPTACLE OUTLETS GANGED WITH A COMMON WALL

PLATE; 20 AMP, 125V, 3 WIRE, GROUNDED TYPE EACH.

DUPLEX RECEPTACLE OUTLET LOCATED ABOVE STANDARD HEIGHT;

20 AMP, 125V, 3 WIRE GROUNDED TYPE. REFER TO ARCHITECTURAL

DRAWINGS FOR EXACT HEIGHT.

GFI

DUPLEX RECEPTACLE OUTLET WITH GROUND FAULT INTERRUPTER;

DUPLEX WITH WEATHERPROOF WHILE IN USE COVER AND GFCI

20 AMP, 125V., 3 WIRE GROUNDED TYPE.

EXIT LIGHT. PROVIDE ARROWS AND FACES AS INDICATED ON DRAWINGS.

LEGEND OF ELECTRICAL SYMBOLS

SYMBOL DESCRIPTION

SCREENING SHADE INDICATES FIXTURE CONNECTION ON

EMERGENCY CIRCUIT OR BATTERY BACKUP. SEE PLANS.

A,XX,a

A,XX,a

ESSENTIAL POWER DUPLEX RECEPTACLE OUTLET; 20 AMP, 125V.,

3 WIRE, GROUNDED TYPE.

WP/GFI

1. PROVIDE A 4" X 4" X 2-1/8"D JUNCTION BOX WITH RING AND STRING ABOVE ACCESSIBLE

CEILING FOR ALL LOW VOLTAGE ROUGH-IN LOCATIONS (TYPICAL).

2. FOR WALLS TO DECK OR WALLS WITH INSULATION, PROVIDE A 4" X 4" X 2-1/8"D JUNCTION

BOX WITH 3/4" EMT CONDUIT TO ABOVE ACCESSIBLE CEILING.

3. LOW VOLTAGE SYSTEMS INCLUDE, BUT ARE NOT LIMITED TO: FIRE ALARM, BUILDING

CONTROLS, LIGHTING CONTROLS, DATA, AUDIO/VISUAL, SECURITY.

4. ALL LOW VOLTAGE CABLING IN THIS PROJECT SHALL BE ROUTED IN MINIMUM 3/4" EMT

CONDUIT WHERE EXPOSED TO VIEW OR WHERE ABOVE INACCESSIBLE CEILINGS. PROVIDE

A SHOP DRAWING FOR ARCHITECT REVIEW

COMMISSIONING NOTES

1. COMMISSION MECHANICAL AND SERVICE WATER HEATING SYSTEMS PER IECC C408.2 WITH COMBINED CAPACITY GREATER THAN 480KBTU/H.

A. THE CX AGENT SHALL PROVIDE A COMMISSIONING PLAN PER C408.2.1

B. BALANCE AND ADJUST AIR AND HYDRONIC SYSTEMS AS APPLICABLE PER C408.2.2

C. VERIFY PERFORMANCE AND INTERFACING OF SYSTEMS, CONTROLS, AND ECONOMIZERS FOR ALL MODES AND SEQUENCE OF OPERATIONS PER

C408.2.3

D. PROVIDE A PRELIMINARY COMMISSIONING REPORT PER C408.2.4

E. PROVIDE ALL CX DOCUMENTS TO BUILDING OWNER WITHIN 90 DAYS OF CERTIFICATE OF OCCUPANCY. INCLUDING SYSTEM BALANCING REPORT

AND FINAL CX REPORT

BREAK OUT PRICE - WORK TO BE COMPLETED BY CX AGENT

CONTROLLED DUPLEX RECEPTACLE OUTLET; 20 AMP, 125V., 3 WIRE,

GROUNDED TYPE. SPLIT CONTROLLED DUPLEX- LEGRAND #26352CH OR

EQUAL;

SPECIAL RECEPTACLE OUTLET: SEE DRAWINGS FOR

NEMA CONFIGURATION AND VOLTAGE.

FLUSH MOUNTED FIRE RATED POKE THRU DEVICE W/ RECEPTACLE(S)

AND/OR DATA AND/OR TELEPHONE. SEE DRAWINGS FOR SPECIFICATIONS.

FLUSH MOUNTED FLOOR BOX W/ RECEPTACLE(S) AND/OR DATA AND/OR

TELEPHONE. SEE DRAWINGS FOR SPECIFICATIONS.

POWER POLE. RE: DRAWINGS FOR MORE INFORMATION.

USB DUPLEX RECEPTACLE OUTLET WITH (2) USB RECEPTACLES; 20 AMP,

125V., 3 WIRE GROUNDED TYPE.

CEILING MOUNTED RECEPTACLE OUTLET, DUPLEX/QUAD/SPECIAL. SEE

DRAWINGS FOR SPECIAL OUTLET CONFIGURATION AND VOLTAGE.

TWO(2) DUPLEX OUTLETS UNDER COMMON COVER PLATE.

LEFT DUPLEX CONTROLLED - LEGRAND #26352CD OR EQUAL.

RIGHT DUPLEX NON-CONTROLLED. 20 AMP, 125V., 3W+G, EACH.

TWO(2) DUPLEX OUTLETS UNDER COMMON COVER PLATE.

LEFT DUPLEX CONTROLLED - LEGRAND #26352CD OR EQUAL.

RIGHT DUPLEX NON-CONTROLLED GFI, USB, OR GFI/USB. 20A, 125V., 2W+G

GFI USB GFI, USB

TELEPHONE / DATA / COMBINATION TELEDATA OUTLET

CABLE T.V. OUTLET

SINGLE POLE, 3-WAY, 4-WAY SWITCH: 20 AMP, 120/277V.

KEY SWITCH 120/277V ; DIGITAL KEY SWITCH

EMERGENCY POWER OFF SWITCH (E.P.O.)

JUNCTION BOX MOUNTED ABOVE ACCESSIBLE CEILING.

JUNCTION BOX - WALL MOUNTED/FLOOR; RE: FLOOR PLANS

TELEPHONE TERMINAL BOARD, 8' x 3/4" FIRE RATED PLYWOOD

DIMMER SWITCH. 120/277V. LUTRON "NOVA-T" OR EQUAL

ON/OFF ONLY / WITH RAISE/LOWER - WALL MOUNTED MOTION

SENSOR; 120/277VAC

PUSH BUTTON / BUZZER

DISCONNECT IN A NEMA 1 ENCLOSURE, UNLESS OTHERWISE SPECIFIED.

REFER TO DRAWINGS FOR AMPERAGE, PHASES, & FUSE SIZE.

(IF REQUIRED) VOLTS/AMPS/POLES TO MATCH BREAKER U.N.O.

SINGLE PHASE MOTOR

THREE PHASE MOTOR

MOTOR STARTER / DISCONNECT IN A NEMA 1 ENCLOSURE, UNLESS

OTHERWISE SPECIFIED. REFER TO DRAWINGS FOR AMPERAGE, PHASES,

FUSE SIZE (IF REQUIRED), AND SIZE. VOLT/AMP/POLES TO MATCH

BREAKER U.N.O.

MOTOR STARTER/VFD IN A NEMA 1 ENCLOSURE, UNLESS OTHERWISE

SPECIFIED. REFER TO DRAWINGS FOR AMPERAGE, PHASES, AND SIZE.

TRANSFER SWITCH - REFER TO DRAWINGS

FOR SPECIFICATIONS

CARD READER JUNCTION BOX WITH 3/4"C TO ACCESSIBLE

CEILING U.N.O.

VARIABLE SPEED DRIVE (SUPPLIED BY MECHANICAL CONTRACTOR)VSD

TTB

CR

GROUND BAR

TRANSFORMER W/ NEC CLEARANCES; REFER TO DRAWING

FOR VOLTAGE/kVA

SURFACE PANELBOARD W/ NEC CLEARANCES.

RECESSED PANELBOARD W/ NEC CLEARANCES

MECHANICAL EQUIPMENT CONNECTION POINT. REFER TO SCHEDULE ON

EX.XX FOR CONNECTION INFORMATION.

NETWORK ENABLED CEILING MOTION SENSOR EXTENDED RANGE /

WALKING MOTION

NETWORK ENABLED CEILING MOTION SENSOR STANDARD RANGE /

SITTING MOTION

WIRELESS DEVICE

DOORBELL CHIME; RE: SPECIFICATIONS/PLANS.

GB

LIGHTING CONTROL NETWORK ENABLED GRAPHIC TOUCH SCREEN 3.5"+

8 PRESETS OR 16 ZONES. USE NEAREST 120/277V LTG CKT FOR POWER

SUPPLY

1 ZONE / 2 ZONE DIGITAL NETWORK ENABLED, RAISE/LOWER+ON/OFF.

1 ZONE / 2 ZONE DIGITAL NETWORK ENABLED, ON/OFF SWITCH.

NETWORK ENABLED, WALL MOUNTED, 1 BUTTON, DUAL TECH SENSOR,

ON/OFF

NETWORK ENABLED, WALL MOUNTED, DUAL TECH SENSOR, ON/OFF +

RAISE/LOWER

PHOTOCELL / DAYLIGHT SENSOR

M

M

DS

MS

STD

MS

EXT

K

M

K

3 4

M

CONTROLLED DUPLEX RECEPTACLE OUTLET; 20 AMP, 125V., 3 WIRE,

GROUNDED TYPE. FULL CONTROLLED - LEGRAND #26352CD OR EQUAL.

REFERENCE SPECIFICATIONS FOR MORE INFORMATION

DATE

JOB

SHEET

ISSUES

KEYPLAN

Date of issue:

REVISIONS

25027.00

12/11/2025

/1

/2

:1 :5

P

M

A-E00-00

ELECTRICAL

COVER SHEET

F O

R T

B E

N D

I S

D

B P

H

V A

C M

E P

W E

S T

Z O

N E

S

T E

P H

E N

F A

U S

T

IN

H S

12/11/25

25241.0000

12.11.2025

A -E

-0

E

L E

C T

R

IC

A L C

O V

E R

S H

E E

T

P h e a s a n t C re e k D r.

S u g a r

L a n d

X

2 09.29.2025 50% CONSTRUCTION DOCUMENTS

1 07.18.2025 DESIGN DEVELOPMENT

3 11.11.2025 90% CONSTRUCTION DOCUMENTS

4 12.11.2025 100% CONSTRUCTION DOCUMENTS

SHEET NUMBER SHEET NAME

A-E00-00 ELECTRICAL COVER SHEET

A-E10-01 ELECTRICAL DEMOLITION PLAN - LEVEL 01 - OVERALL

A-E10-02 ELECTRICAL DEMOLITION PLAN - LEVEL 02 - OVERALL

A-E20-01 ELECTRICAL POWER PLAN - LEVEL 01 - OVERALL

A-E20-02 ELECTRICAL POWER PLAN - LEVEL 02- OVERALL

A-E30-01 ELECTRICAL ENLARGED PLANS - LEVEL 1

A-E30-02 ELECTRICAL ENLARGED PLANS - LEVEL 2

A-E40-00 ELECTRICAL DETAILS

D C

B A

1.4

1st

220,527 SF

Main Bldg

220,527 SF

(D)AHU-7

(D)AHU-8

(E)AHU-12

(E)AHU-11

(D)AHU-1

(D)AHU-2

(D)AHU-3

(D)HWP-1

(E)AHU-15

(E)AHU-16

(E)AHU-17

(D)AHU-20

(D)AHU-21

A. CONDUCT ALL DEMOLITION WORK IN SUCH A MANNER AS TO MAINTAIN A SAFE WORK

ENVIRONMENT AND IN ACCORDANCE WITH APPLICABLE SAFETY RULES AND PROCEDURES

WITHIN NEC, NECA AND OSHA REQUIREMENTS.

B. CONTRACTOR SHALL REQUEST AND REVIEW ANY HAZARDOUS MATERIALS SURVEYS FROM

THE OWNER'S REPRESENTATIVE. OBSERVE RECOMMENDED PRECAUTIONS AND VERIFY THE

STATUS OF ANY REMEDIAL WORK RECOMMENDED OR NOTED WITHIN THE HAZARDOUS

MATERIAL SURVEY. NOTIFY THE OWNER'S REPRESENTATIVE IF ANY HAZARDOUS MATERIALS

ARE SUSPECTED OR OBSERVED DURING THE COURSE OF EXECUTING THIS CONTRACT.

C. SURVEYS AREAS OF THE FACILITY SCHEDULED FOR RENOVATION OR PARTIAL DEMOLITION

PRIOR TO ANY WORK BEING PERFORMED. SUBMIT REPORT OF THE PRE-WORK SURVEY

DETAILING ANY UTILIZATION EQUIPMENT OR SYSTEMS THAT ARE NOT IN GOOD WORKING

ORDER IN ADVANCE OF ANY DEMOLITION WORK AND REVIEW WITH THE OWNER'S

REPRESENTATIVE.

D. THE OWNER SHALL HAVE FIRST RIGHT OF REFUSAL FOR SALVAGED MATERIAL. REQUEST

THAT THE OWNER PROVIDE DIRECTION ON DISPOSITION OF SALVAGED MATERIAL FIVE(5)

WORKING DAYS PRIOR TO REMOVAL. IF SO DIRECTED BY THE OWNER, SALVAGED MATERIAL

SHALL REMAIN THE PROPERTY OF THE OWNER AND SHALL BE DELIVERED BY THE

CONTRACTOR TO A LOCATION AS DIRECTED. REMOVE AND DISPOSE ANY SALVAGED

MATERIAL NOT RETAINED BY THE OWNER.

E. DRAWINGS INDICATE APPROXIMATE LOCATION AND QUANTITY OF PANELS, TRANSFORMERS,

DISCONNECTS, ETC. TO BE REMOVED. VERIFY LOCATION AND QUANTITY OF ITEMS TO BE

REMOVED. NO ALLOWANCE WILL BE MADE BECAUSE OF CONTRACTOR'S UNFAMILIARITY WITH

THE SITE.

F. DAMAGED AREAS CAUSED REMOVAL OF ANY OF THE ABOVE ITEMS AND WHICH ARE NOT

CONCEALED BY NEW CONSTRUCTION SHALL BE REPAIRED TO MATCH ADJACENT SURFACES.

OPENINGS CREATED BY THE REMOVAL OF THESE ITEMS THROUGH FIRE RATED WALLS SHALL

BE FIRE STOPPED.

G. REMOVE ABANDONED CONDUIT TO POINT OF CONCEALMENT BEHIND INACCESSIBLE

SURFACES. ENTIRELY REMOVE ABANDONED WIRING.

H. PROVIDE BLANK COVERS AND PLATES AT UNUSED OPENINGS IN BOXES, RACEWAYS,

AUXILIARY GUTTERS, CABINETS, EQUIPMENT CASES AND HOUSINGS SHALL BE CLOSED TO

AFFORD PROTECTION SUBSTANTIALLY EQUIVALENT TO THE EQUIPMENT ENCLOSURE.

I. IF A CONDUIT RUN IS EXPOSED OR A SURFACE RACEWAY LEFT WITHOUT A MOUNTING

SURFACE DUE TO REMOVAL OF A PARTITION, THE RACEWAY SHALL BE REROUTED AS

ACCEPTABLE TO THE OWNER/ARCHITECT.

J. PROTECT ELECTRICAL EQUIPMENT, OUTLETS AND DEVICES THAT ARE SCHEDULED TO BE

RELOCATED. REPAIR, RESTORE OR REPLACE ITEMS DAMAGED WHEN REMOVED TO THE

APPROVAL OF THE OWNER. NOTIFY OWNER/ARCHITECT/ENGINEER OF ANY ELECTRICAL

EQUIPMENT, OUTLETS AND/OR DEVICES WHICH ARE SCHEDULED TO BE RE-USED THAT ARE

FOUND TO BE UNUSABLE.

ELECTRICAL DEMOLITION GENERAL NOTES

DATE

JOB

SHEET

ISSUES

KEYPLAN

Date of issue:

REVISIONS

25027.00

12/11/2025

/1

/2

:1 :5

P

M

A-E10-01

ELECTRICAL

DEMOLITION PLAN

- LEVEL 01 -

OVERALL

F O

R T

B E

N D

I S

D

B P

H

V A

C M

E P

W E

S T

Z O

N E

S

T E

P H

E N

F A

U S

T

IN

H S

12/11/25

25241.0000

12.11.2025

A -E

-0

E

L E

C T

R

IC

A L D

E M

O L

IT

IO

N

P L A

N

L E

V E

L

O V

E R

A L L

P h e a s a n t C re e k D r.

S u g a r

L a n d

2 09.29.2025 50% CONSTRUCTION DOCUMENTS

1 07.18.2025 DESIGN DEVELOPMENT

3 11.11.2025 90% CONSTRUCTION DOCUMENTS

4 12.11.2025 100% CONSTRUCTION DOCUMENTS

D C

B A

1/32" = 1'-0"1

ELECTRICAL DEMOLITION PLAN - LEVEL 01

ELECTRICAL KEYED NOTES

1 EXISTING HVAC AIR HANDLER EQUIPMENT TO BE REPLACED. FIELD VERIFY

EXISTING CONDITION OF CIRCUITS, RACEWAYS & CONDUITS SERVING AIR

HANDLER. NOTIFY ENGINEER IF EXISTING AHU CIRCUIT NEEDS TO BE

REPLACED. REFER TO NEW WORK PLANS.

2 EXISTING HVAC TERMINAL TO BE REPLACED. FIELD VERIFY EXISTING CONDITION

OF CIRCUITS, RACEWAYS & CONDUITS SERVING TERMINAL. NOTIFY ENGINEER IF

EXISTING TERMINAL CIRCUIT NEEDS TO BE REPLACED. REFER TO NEW WORK

PLANS.

3 EXISTING HVAC PUMP EQUIPMENT TO RE REPLACED. DEMO EXISTING CIRCUITS,

DISCONNECTS, DRIVE HARDWARE, RACEWAYS & CONDUITS, AND OTHER

ELECTRICAL APPURTENANCES. DEMO EXISTING BREAKERS IN DISTRIBUTION

EQUIPMENT ASSOCIATED WITH THESE PUMPS, AND PREPARE BREAKER SPACES

FOR INSTALLATION OF NEW BREAKERS. REFER TO NEW WORK PLANS.

4 EXISTING HVAC AIR HANDLER EQUIPMENT TO REMAIN AND BE REFURBISHED.

NEW VFD HARDWARE BY DIVISION 23 SHALL BE PROVIDED. VERIFY POWER AND

GROUNDING CONNECTIONS, RE. MECHANICAL PLANS.

G

GG

G GG

DW

HC

HC

E

E

E

G

E

G

E

G

E

EE

EE

EE

E

E

E

HC

E

HC

G

G

EE

E

E

G

EE

EEE EEE

C CC

C CC

2nd Floor 2nd Floor

74,135 SF

TYP.15

(D)AHU-9

(D)AHU-10

(D)AHU-4

(D)AHU-5

(E)AHU-13

(D)AHU-6

(D)AHU-18

(D)AHU-19

A. CONDUCT ALL DEMOLITION WORK IN SUCH A MANNER AS TO MAINTAIN A SAFE WORK

ENVIRONMENT AND IN ACCORDANCE WITH APPLICABLE SAFETY RULES AND PROCEDURES

WITHIN NEC, NECA AND OSHA REQUIREMENTS.

B. CONTRACTOR SHALL REQUEST AND REVIEW ANY HAZARDOUS MATERIALS SURVEYS FROM

THE OWNER'S REPRESENTATIVE. OBSERVE RECOMMENDED PRECAUTIONS AND VERIFY THE

STATUS OF ANY REMEDIAL WORK RECOMMENDED OR NOTED WITHIN THE HAZARDOUS

MATERIAL SURVEY. NOTIFY THE OWNER'S REPRESENTATIVE IF ANY HAZARDOUS MATERIALS

ARE SUSPECTED OR OBSERVED DURING THE COURSE OF EXECUTING THIS CONTRACT.

C. SURVEYS AREAS OF THE FACILITY SCHEDULED FOR RENOVATION OR PARTIAL DEMOLITION

PRIOR TO ANY WORK BEING PERFORMED. SUBMIT REPORT OF THE PRE-WORK SURVEY

DETAILING ANY UTILIZATION EQUIPMENT OR SYSTEMS THAT ARE NOT IN GOOD WORKING

ORDER IN ADVANCE OF ANY DEMOLITION WORK AND REVIEW WITH THE OWNER'S

REPRESENTATIVE.

D. THE OWNER SHALL HAVE FIRST RIGHT OF REFUSAL FOR SALVAGED MATERIAL. REQUEST

THAT THE OWNER PROVIDE DIRECTION ON DISPOSITION OF SALVAGED MATERIAL FIVE(5)

WORKING DAYS PRIOR TO REMOVAL. IF SO DIRECTED BY THE OWNER, SALVAGED MATERIAL

SHALL REMAIN THE PROPERTY OF THE OWNER AND SHALL BE DELIVERED BY THE

CONTRACTOR TO A LOCATION AS DIRECTED. REMOVE AND DISPOSE ANY SALVAGED

MATERIAL NOT RETAINED BY THE OWNER.

E. DRAWINGS INDICATE APPROXIMATE LOCATION AND QUANTITY OF PANELS, TRANSFORMERS,

DISCONNECTS, ETC. TO BE REMOVED. VERIFY LOCATION AND QUANTITY OF ITEMS TO BE

REMOVED. NO ALLOWANCE WILL BE MADE BECAUSE OF CONTRACTOR'S UNFAMILIARITY WITH

THE SITE.

F. DAMAGED AREAS CAUSED REMOVAL OF ANY OF THE ABOVE ITEMS AND WHICH ARE NOT

CONCEALED BY NEW CONSTRUCTION SHALL BE REPAIRED TO MATCH ADJACENT SURFACES.

OPENINGS CREATED BY THE REMOVAL OF THESE ITEMS THROUGH FIRE RATED WALLS SHALL

BE FIRE STOPPED.

G. REMOVE ABANDONED CONDUIT TO POINT OF CONCEALMENT BEHIND INACCESSIBLE

SURFACES. ENTIRELY REMOVE ABANDONED WIRING.

H. PROVIDE BLANK COVERS AND PLATES AT UNUSED OPENINGS IN BOXES, RACEWAYS,

AUXILIARY GUTTERS, CABINETS, EQUIPMENT CASES AND HOUSINGS SHALL BE CLOSED TO

AFFORD PROTECTION SUBSTANTIALLY EQUIVALENT TO THE EQUIPMENT ENCLOSURE.

I. IF A CONDUIT RUN IS EXPOSED OR A SURFACE RACEWAY LEFT WITHOUT A MOUNTING

SURFACE DUE TO REMOVAL OF A PARTITION, THE RACEWAY SHALL BE REROUTED AS

ACCEPTABLE TO THE OWNER/ARCHITECT.

J. PROTECT ELECTRICAL EQUIPMENT, OUTLETS AND DEVICES THAT ARE SCHEDULED TO BE

RELOCATED. REPAIR, RESTORE OR REPLACE ITEMS DAMAGED WHEN REMOVED TO THE

APPROVAL OF THE OWNER. NOTIFY OWNER/ARCHITECT/ENGINEER OF ANY ELECTRICAL

EQUIPMENT, OUTLETS AND/OR DEVICES WHICH ARE SCHEDULED TO BE RE-USED THAT ARE

FOUND TO BE UNUSABLE.

ELECTRICAL DEMOLITION GENERAL NOTES

DATE

JOB

SHEET

ISSUES

KEYPLAN

Date of issue:

REVISIONS

25027.00

12/11/2025

/1

/2

:1 :5

P

M

A-E10-02

ELECTRICAL

DEMOLITION PLAN

- LEVEL 02 -

OVERALL

F O

R T

B E

N D

I S

D

B P

H

V A

C M

E P

W E

S T

Z O

N E

S

T E

P H

E N

F A

U S

T

IN

H S

12/11/25

25241.0000

12.11.2025

A -E

-0

E

L E

C T

R

IC

A L D

E M

O L

IT

IO

N

P L A

N

L E

V E

L

O V

E R

A L L

P h e a s a n t C re e k D r.

S u g a r

L a n d

2 09.29.2025 50% CONSTRUCTION DOCUMENTS

1 07.18.2025 DESIGN DEVELOPMENT

3 11.11.2025 90% CONSTRUCTION DOCUMENTS

4 12.11.2025 100% CONSTRUCTION DOCUMENTS

D C

B A

1/32" = 1'-0"1

ELECTRICAL DEMOLITION PLAN - LEVEL 02

ELECTRICAL KEYED NOTES

1 EXISTING HVAC AIR HANDLER EQUIPMENT TO BE REPLACED. FIELD VERIFY

EXISTING CONDITION OF CIRCUITS, RACEWAYS & CONDUITS SERVING AIR

HANDLER. NOTIFY ENGINEER IF EXISTING AHU CIRCUIT NEEDS TO BE

REPLACED. REFER TO NEW WORK PLANS.

2 EXISTING HVAC TERMINAL TO BE REPLACED. FIELD VERIFY EXISTING

CONDITION OF CIRCUITS, RACEWAYS & CONDUITS SERVING TERMINAL.

NOTIFY ENGINEER IF EXISTING TERMINAL CIRCUIT NEEDS TO BE REPLACED.

REFER TO NEW WORK PLANS.

3 EXISTING HVAC AIR HANDLER EQUIPMENT TO REMAIN AND BE REFURBISHED.

NEW VFD HARDWARE BY DIVISION 23 SHALL BE PROVIDED. VERIFY POWER

AND GROUNDING CONNECTIONS, RE. MECHANICAL PLANS.

1st

220,527 SF

Main Bldg

220,527 SF

A-E30-01

A-E30-01

A-E30-01

A-E30-01

A-E30-01

A-E30-01

2 (N)VFD-HWP-1

(N)HWP-1

A-E30-01

A. ALL CONDUITS THAT COULD BE VIEWED BY THE PUBLIC OR EMPLOYEES SHALL BE

INSTALLED IN WALLS OR IN THE SLAB.

B. CONDUIT LINES ARE DIAGRAMMATIC. CONTRACTOR SHALL FIELD VERIFY CONDITIONS AND

CHOOSE APPROPRIATE CONDUIT ROUTING. IN THE EVENT THAT THE APPROXIMATE

CONDUIT ROUTING SHOWN ON PLANS IS NOT FEASIBLE CONTRACTOR SHALL NOTIFY

ARCHITECT/ENGINEER.

C. RECEPTACLES LOCATED WITHIN 6' OF ANY PLUMBING FIXTURE, IN BREAK ROOMS, AT THE

EXTERIOR, IN THE PARKING GARAGE OR OTHERWISE EXPOSED TO WATER SHALL BE TYPE

GFCI. "WP" INDICATES A WEATHERPROOF "WHILE-IN-USE" COVER.

D. ALL WIRING DEVICES ARE NEW UNLESS NOTED OTHERWISE.

E. ALL ELECTRICAL EQUIPMENT IS EXISTING TO REMAIN UNLESS NOTED OTHERWISE.

F. COORDINATE DISCONNECT SWITCHES, VFDS AND STARTER LOCATIONS WITH EQUIPMENT

INSTALLERS TO MAINTAIN PROPER MAINTENANCE AND CODE REQUIRED CLEARANCES.

G. COORDINATE RECEPTACLE AND DATACOM LOCATIONS SO THAT DEVICES ON SIMILAR

WALLS ARE ADJACENT TO ONE ANOTHER.

H. REFERENCE EQUIPMENT CONNECTION SCHEDULE FOR REQUIREMENTS AND ADDITIONAL

INFORMATION OF TAGGED EQUIPMENT SHOWN ON PLAN DRAWING.

I. PROVIDE 120V POWER TO EACH HVAC DDC CONTROL PANEL. COORDINATE EXACT

LOCATIONS AND QUANTITIES WITH MECHANICAL DRAWINGS.

ELECTRICAL POWER GENERAL NOTES

DATE

JOB

SHEET

ISSUES

KEYPLAN

Date of issue:

REVISIONS

25027.00

12/11/2025

/1

/2

:1 :0

P

M

A-E20-01

ELECTRICAL

POWER PLAN -

LEVEL 01 -

OVERALL

F O

R T

B E

N D

I S

D

B P

H

V A

C M

E P

W E

S T

Z O

N E

S

T E

P H

E N

F A

U S

T

IN

H S

12/11/25

25241.0000

12.11.2025

A -E

-0

E

L E

C T

R

IC

A L P

O W

E R

P L A

N

L E

V E

L

O V

E R

A L L

P h e a s a n t C re e k D r.

S u g a r

L a n d

2 09.29.2025 50% CONSTRUCTION DOCUMENTS

1 07.18.2025 DESIGN DEVELOPMENT

3 11.11.2025 90% CONSTRUCTION DOCUMENTS

4 12.11.2025 100% CONSTRUCTION DOCUMENTS

D C

B A

1/32" = 1'-0"1

ELECTRICAL POWER PLAN - LEVEL 01

ELECTRICAL KEYED NOTES

1 NEW HVAC TERMINAL. CONNECT TO EXISTING CIRCUIT SERVING PREVIOUS

EQUIPMENT BEING REPLACED, VERIFY AMPACITY. COORDINATE WITH

ARCHITECTURAL AND MECHANICAL FOR EXACT LOCATION AND CONNECTION

REQUIREMENTS.

2 NEW HVAC PUMP EQUIPMENT. REUSE EXISTING CIRCUIT, VERIFY AMPACITY.

PROVIDE MOTOR DRIVE EQUIPMENT PER MECHANICAL SCHEDULE AND DIVISION

23. COORDINATE WITH ARCHITECTURAL AND MECHANICAL FOR EXACT

LOCATION AND CONNECTION REQUIREMENTS.

G

GG

G GG

DW

HC

HC

E

E

E

G

E

G

E

G

E

EE

EE

EE

E

E

E

HC

E

HC

G

G

EE

E

E

G

EE

EEE EEE

C CC

C CC

2nd Floor 2nd Floor

74,135 SF

TYP.15

A-E30-02

A-E30-02

A-E30-02

(N)AHU-18

(N)AHU-19

A-E30-02

AHU-22

(N)VFD-AHU-22

AHU-23

(N)VFD-AHU-19

(N)VFD-AHU-18

A. ALL CONDUITS THAT COULD BE VIEWED BY THE PUBLIC OR EMPLOYEES SHALL BE

INSTALLED IN WALLS OR IN THE SLAB.

B. CONDUIT LINES ARE DIAGRAMMATIC. CONTRACTOR SHALL FIELD VERIFY CONDITIONS AND

CHOOSE APPROPRIATE CONDUIT ROUTING. IN THE EVENT THAT THE APPROXIMATE

CONDUIT ROUTING SHOWN ON PLANS IS NOT FEASIBLE CONTRACTOR SHALL NOTIFY

ARCHITECT/ENGINEER.

C. RECEPTACLES LOCATED WITHIN 6' OF ANY PLUMBING FIXTURE, IN BREAK ROOMS, AT THE

EXTERIOR, IN THE PARKING GARAGE OR OTHERWISE EXPOSED TO WATER SHALL BE TYPE

GFCI. "WP" INDICATES A WEATHERPROOF "WHILE-IN-USE" COVER.

D. ALL WIRING DEVICES ARE NEW UNLESS NOTED OTHERWISE.

E. ALL ELECTRICAL EQUIPMENT IS EXISTING TO REMAIN UNLESS NOTED OTHERWISE.

F. COORDINATE DISCONNECT SWITCHES, VFDS AND STARTER LOCATIONS WITH EQUIPMENT

INSTALLERS TO MAINTAIN PROPER MAINTENANCE AND CODE REQUIRED CLEARANCES.

G. COORDINATE RECEPTACLE AND DATACOM LOCATIONS SO THAT DEVICES ON SIMILAR

WALLS ARE ADJACENT TO ONE ANOTHER.

H. REFERENCE EQUIPMENT CONNECTION SCHEDULE FOR REQUIREMENTS AND ADDITIONAL

INFORMATION OF TAGGED EQUIPMENT SHOWN ON PLAN DRAWING.

I. PROVIDE 120V POWER TO EACH HVAC DDC CONTROL PANEL. COORDINATE EXACT

LOCATIONS AND QUANTITIES WITH MECHANICAL DRAWINGS.

ELECTRICAL POWER GENERAL NOTES

DATE

JOB

SHEET

ISSUES

KEYPLAN

Date of issue:

REVISIONS

25027.00

12/11/2025

/1

/2

:1 :0

P

M

A-E20-02

ELECTRICAL

POWER PLAN -

LEVEL 02-

OVERALL

F O

R T

B E

N D

I S

D

B P

H

V A

C M

E P

W E

S T

Z O

N E

S

T E

P H

E N

F A

U S

T

IN

H S

12/11/25

25241.0000

12.11.2025

A -E

-0

E

L E

C T

R

IC

A L P

O W

E R

P L A

N

L E

V E

L

O V

E R

A L L

P h e a s a n t C re e k D r.

S u g a r

L a n d

2 09.29.2025 50% CONSTRUCTION DOCUMENTS

1 07.18.2025 DESIGN DEVELOPMENT

3 11.11.2025 90% CONSTRUCTION DOCUMENTS

4 12.11.2025 100% CONSTRUCTION DOCUMENTS

D C

B A

1/32" = 1'-0"1

ELECTRICAL POWER PLAN - LEVEL 02

ELECTRICAL KEYED NOTES

1 NEW HVAC TERMINAL. CONNECT TO EXISTING CIRCUIT SERVING PREVIOUS

EQUIPMENT BEING REPLACED, VERIFY AMPACITY. COORDINATE WITH

ARCHITECTURAL AND MECHANICAL FOR EXACT LOCATION AND CONNECTION

REQUIREMENTS.

2 ELECTRICAL CONTRACTOR TO INSTALL NEW COMBINATION VFD/DISCONNECT

AND CONNECT TO EXISTING CIRCUIT FOR NEW AIR HANDLING UNIT. RE. PANEL

SCHEDULES FOR CIRCUIT INFORMATION. COORDINATE LOCATION OF VFD WITH

MECHANICAL CONTRACTOR.

3 EXISTING REFURBISHED AIR HANDLER: NEW VFD BY DIVISION 23, MAKE

CONNECTIONS TO CIRCUIT AND HVAC EQUIPMENT AS REQUIRED. VERIFY

POWER AND GROUNDING CONNECTIONS, RE. MECHANICAL PLANS.

'LCC'

'CP3' 'LB'

'LB2'

'HB'

'X3' 'XB'

'FACP' 'TLCCD'

(N)AHU-8

(N)AHU-7

(N)VFD-AHU-7

(N)VFD-AHU-8

GFI

LB2-1

'HC''LC''LC2'

'XFMR''XFMR'

'CP2''CP2'

'DC'

(E)AHU-12

(E)AHU-11

(N)VFD-AHU-11

(N)VFD-AHU-12

GFI

LC2-2

'XFMR'

'HK' 'CP4' 'LR' 'LQ'

'DD'

'MCC'

'LN'

'XFMR'

(E)AHU-15

(N)VFD-AHU-15

LQ-34

GFI

NOTE: EXISTING ELEC

EQUIPMENT LOCATED

IN MECH MEZZANINE

'LH'

'HH'

'LC2'

'XH'

'DB'

(N)AHU-20

(N)AHU-21

(N)VFD-AHU-20

(N)VFD-AHU-21

LG-2

GFI

'HA'

'LA' 'LA2'

'DA'

'XFMR'

'CPI'

'LCA'

'LCB'

'X1'

(N)AHU-1

(N)AHU-2

(N)AHU-3

(N)VFD-AHU-3

(N)VFD-AHU-2

(N)VFD-AHU-1

LA-21

GFI

'LCE'

'LL'

'LM'

'XFMR'

'XFMR'

'XFMR'

(E)AHU-16

(E)AHU-17

(N)VFD-AHU-17

(N)VFD-AHU-16

LQ-2

GFI

A. ALL CONDUITS THAT COULD BE VIEWED BY THE PUBLIC OR EMPLOYEES SHALL BE

INSTALLED IN WALLS OR IN THE SLAB.

B. CONDUIT LINES ARE DIAGRAMMATIC. CONTRACTOR SHALL FIELD VERIFY CONDITIONS AND

CHOOSE APPROPRIATE CONDUIT ROUTING. IN THE EVENT THAT THE APPROXIMATE

CONDUIT ROUTING SHOWN ON PLANS IS NOT FEASIBLE CONTRACTOR SHALL NOTIFY

ARCHITECT/ENGINEER.

C. RECEPTACLES LOCATED WITHIN 6' OF ANY PLUMBING FIXTURE, IN BREAK ROOMS, AT THE

EXTERIOR, IN THE PARKING GARAGE OR OTHERWISE EXPOSED TO WATER SHALL BE TYPE

GFCI. "WP" INDICATES A WEATHERPROOF "WHILE-IN-USE" COVER.

D. ALL WIRING DEVICES ARE NEW UNLESS NOTED OTHERWISE.

E. ALL ELECTRICAL EQUIPMENT IS EXISTING TO REMAIN UNLESS NOTED OTHERWISE.

F. COORDINATE DISCONNECT SWITCHES, VFDS AND STARTER LOCATIONS WITH EQUIPMENT

INSTALLERS TO MAINTAIN PROPER MAINTENANCE AND CODE REQUIRED CLEARANCES.

G. COORDINATE RECEPTACLE AND DATACOM LOCATIONS SO THAT DEVICES ON SIMILAR

WALLS ARE ADJACENT TO ONE ANOTHER.

H. REFERENCE EQUIPMENT CONNECTION SCHEDULE FOR REQUIREMENTS AND ADDITIONAL

INFORMATION OF TAGGED EQUIPMENT SHOWN ON PLAN DRAWING.

I. PROVIDE 120V POWER TO EACH HVAC DDC CONTROL PANEL. COORDINATE EXACT

LOCATIONS AND QUANTITIES WITH MECHANICAL DRAWINGS.

ELECTRICAL POWER GENERAL NOTES

AHU-14

AHU-25

(N)VFD-AHU-14

(N)VFD-AHU-25

GFI

LP-12

DATE

JOB

SHEET

ISSUES

KEYPLAN

Date of issue:

REVISIONS

25027.00

12/11/2025

/1

/2

:1 :0

P

M

A-E30-01

ELECTRICAL

ENLARGED PLANS

- LEVEL 1

F O

R T

B E

N D

I S

D

B P

H

V A

C M

E P

W E

S T

Z O

N E

S

T E

P H

E N

F A

U S

T

IN

H S

12/11/25

25241.0000

12.11.2025

A -E

-0

E

L E

C T

R

IC

A L E

N L A

R G

E D

P L A

N S

L E

V E

L

P h e a s a n t C re e k D r.

S u g a r

L a n d

2 09.29.2025 50% CONSTRUCTION DOCUMENTS

1 07.18.2025 DESIGN DEVELOPMENT

3 11.11.2025 90% CONSTRUCTION DOCUMENTS

4 12.11.2025 100% CONSTRUCTION DOCUMENTS

D C

B A

1/4" = 1'-0"1

ELECTRICAL…

This is the start of the file's text. The full file is on GovTribe.