1387235dwg01of01.pdf
PDF 31 MB Posted
- Solicitation number
- N4008521R1210
View the file
Other files
| File | Type | Posted |
|---|---|---|
| Amendment0008_21R1210.pdf | ||
| Amendment0007_21R1210.pdf | ||
| Revised Price Proposal Form.pdf | ||
| REVISED 23 81 00.pdf | ||
| Amendment0006_21R1210.pdf | ||
| Amendment0005_21R1210.pdf | ||
| Amendment0004_21R1210.pdf | ||
| Amendment0003_21R1210.pdf | ||
| 21R1210 Amendment 0002.pdf | ||
| General Requirements (Rev2).pdf | ||
| 21R1210 Amendment 0001.pdf | ||
| General Requirements (Rev1).pdf | ||
| Attachment C_BASE ACCESS INSTRUCTION.pdf | ||
| General Requirements.pdf | ||
| Attachment G_Price Proposal Form.docx | DOCX document | |
| Attachment F_BLANK DEVGRU SPREADSHEET.xls | XLS spreadsheet | |
| 1387235spc01of01.pdf | ||
| Attachment B_Pre-Proposal Inquiry (PPI) Form.xlsx | XLSX spreadsheet | |
| Attachment E_BLANK SPONSOR VERIFICATION SPREADSHEET.xls | XLS spreadsheet | |
| Attachment D- SECNAV 5512-1 Form.pdf |
Show all 20
On GovTribe
Work with this file
- Download the original file
- Contacts named in this file
- Similar government files
- Ask GovTribe AI about this file
Text version
NAS OCEANA
DAM NECK
ANNEX
IN
TE
RS
TA
TE
VIRGINI
A BEA
CH BL
VD
INTERSTATE 264
LO
ND
ON
B
RI
DG
E
RO
AD
DAM NECK ROAD
GE
N
ER
AL
B
O O
TH
PAC
IFIC
AVE
PROJECT SITE
MAIN GATE
DAM NECK
ROAD
NAVAL AIR STATION OCEANA, DAM NECK ANNEX VIRGINIA BEACH, VIRGINIA
SATISFACTORY TO DATE
APPROVED
ACTIVITY
FOR COMMANDER NAVFAC
SEAL
A/E INFO
A
B
C
D
1 2 3 4 5
1 2 3 4 5
A
B
C
D
SCALE:
CONSTR. CONTR. NO.
SHEET
NAVFAC DRAWING NO.
DES DRW CHK
OF
EPROJECT NO.:
D
EP
AR
TM
EN
T
O F
TH
E
N
AV
Y N
AV
AL
F
AC
IL
IT
IE
S
EN
G
IN
EE
R
IN
G C
O M
M
AN
D
DRAWFORM REVISION: 7 FEBRUARY 2019
PM/DM
BRANCH MANAGER
CHIEF ENG/ARCH
FIRE PROTECTION
NA
VA
L
FA
CI
LI
TI
ES
E
NG
IN
EE
RI
NG
C O
M M
AN
D
M
ID
AT
LA
NT
IC
N
AV
AL
S
TA
TI
O
N
N O
R
FO
LK
, V
A
AS NOTED
G-001
P -Q
S O
F P
H Y
S
IC
A L
S E
C U
R
IT
Y
CO
VE
R
SH
EE
T
MH
12801961
TE AF
10/06/2020
APPROVED BY JOHN TAYLOR WITH
NSWDG, VIA EMAIL
BU
IL
DI
NG
A
DD
IT
IO
N
JB/JH
1387235
VI
RG
IN
IA
B
EA
CH
, V
IR
GI
NI
A
NA
S
OC
EA
NA
D
AM
N
EC
K
AN
NE
X M
ID
LA
N T
C I C
O R
E
EJA
DJD
DSN
10/09/2020
P-Q698 SOF PHYSICAL SECURITY
BUILDING ADDITION
VICINITY MAP LOCATION MAP
NORTH NORTH
(NOT TO SCALE) (NOT TO SCALE)
PREFINAL SUBMITTAL
NAVAL SPECIAL WARFARE DEVELOPMENT GROUP (NSWDG)
EPROJECTS WORK ORDER NUMBER: 1387235
I G
IV R
FOHT
I
NO
M N
EW
A
OM
L
C
TH I ECRC
A T
A
NO. 013034
CLAY C. DILLS
SY
M
DE
S C
RI
PT
I O N
DA
TE
AP
PR
SATISFACTORY TO DATE
APPROVED
ACTIVITY
FOR COMMANDER NAVFAC
SEAL
A/E INFO
A
B
C
D
1 2 3 4 5
1 2 3 4 5
A
B
C
D
SCALE:
CONSTR. CONTR. NO.
SHEET
NAVFAC DRAWING NO.
DES DRW CHK
OF
EPROJECT NO.:
D
EP
AR
TM
EN
T
O F
TH
E
N
AV
Y N
AV
AL
F
AC
IL
IT
IE
S
EN
G
IN
EE
R
IN
G C
O M
M
AN
D
DRAWFORM REVISION: 7 FEBRUARY 2019
PM/DM
BRANCH MANAGER
CHIEF ENG/ARCH
FIRE PROTECTION
NA
VA
L
FA
CI
LI
TI
ES
E
NG
IN
EE
RI
NG
C O
M M
AN
D
M
ID
AT
LA
NT
IC
N
AV
AL
S
TA
TI
O
N
N O
R
FO
LK
, V
A
AS NOTED
G-002
P -Q
S O
F P
H Y
S
IC
A L
S E
C U
R
IT
Y
DR
AW
IN
G
IN
DE
X
MH
12801962
TE AF
10/06/2020
APPROVED BY JOHN TAYLOR WITH
NSWDG, VIA EMAIL
BU
IL
DI
NG
A
DD
IT
IO
N
JB/JH
1387235
VI
RG
IN
IA
B
EA
CH
, V
IR
GI
NI
A
NA
S
OC
EA
NA
D
AM
N
EC
K
AN
NE
X M
ID
LA
N T
C I C
O R
E
EJA
DJD
DSN
10/09/2020
SHEET INDEX
SHEET NO.
NAVFAC DWG. NO. SHEET TITLENO. SHEET
63 A-702 12802023 SECURITY CAGE ELEVATIONS & SIGNAGE DETAILS
INTERIORS
64 I-101 12802024 FF&E FLOOR PLAN
FIRE PROTECTION
65 FA001 12802025 FIRE ALARM GENERAL NOTES AND LEGEND
66 FD101 12802026 FIRE ALARM DEMOLITION
67 FA101 12802027 FIRE ALARM FLOOR PLAN
68 FA501 12802028 FIRE ALARM DETAILS
69 FA502 12802029 FIRE ALARM MOUNTING DETAILS
PLUMBING
70 P-001 12802030 LEGEND AND ABBREVIATIONS
71 PD101 12802031 FLOOR PLAN SANITARY - DEMOLITION
72 PD102 12802032 FLOOR PLAN DOMESTIC WATER - DEMOLITION
73 P-101 12802033 FLOOR PLAN SANITARY - NEW WORK
74 P-102 12802034 FLOOR PLAN DOMESTIC WATER - NEW WORK
75 P-501 12802035 DETAILS
76 P-601 12802036 PLUMBING RISER
MECHANICAL
77 M-001 12802037 LEGEND AND ABBREVIATIONS
78 MD101 12802038 FLOOR PLAN - DEMOLITION
79 M-101 12802039 FLOOR PLAN - NEW WORK DUCTWORK
80 M-102 12802040 FLOOR PLAN - NEW WORK VENTILATION
81 M-103 12802041 FLOOR PLAN - NEW WORK PIPING
82 M-401 12802042 ENLARGED PLAN & SECTION
83 M-501 12802043 DETAILS
84 M-502 12802044 DETAILS
85 M-503 12802045 DETAILS
86 M-504 12802046 DETAILS
87 M-601 12802047 SCHEDULES
88 M-602 12802048 SCHEDULES
89 M-701 12802049 SEQUENCE OF OPERATIONS
90 M-702 12802050 SEQUENCE OF OPERATIONS
91 M-703 12802051 SEQUENCE OF OPERATIONS
92 M-704 12802052 SEQUENCE OF OPERATIONS
93 M-705 12802053 SEQUENCE OF OPERATIONS
ELECTRICAL
94 E-001 12802054 LEGEND AND ABBREVIATIONS
95 ES101 12802055 ELECTRICAL SITE PLAN - DEMOLITION
96 ES102 12802056 ELECTRICAL SITE PLAN - NEW WORK
97 ED101 12802057 LIGHTING AND POWER FLOOR PLAN - DEMOLITION
98 E-101 12802058 LIGHTING PLAN - NEW WORK
99 E-102 12802059 POWER PLAN - NEW WORK
100 E-103 12802060 HVAC POWER PLAN - NEW WORK
101 E-104 12802061 LIGHTNING PROTECTION PLAN - NEW WORK
102 E-401 12802062 ENLARGED POWER PLAN - NEW WORK
103 E-501 12802063 LIGHTING FIXTURE SCHEDULE AND DETAILS
104 E-502 12802064 LIGHTING FIXTURE DETAILS
105 E-503 12802065 LIGHTNING PROTECTION SYSTEM DETAILS
106 E-504 12802066 ELECTRICAL AND GROUNDING DETAILS
107 E-601 12802067 POWER RISER AND GROUNDING SCHEMATIC DIAGRAMS
108 E-602 12802068 LIGHTING CONTROL DIAGRAMS
109 E-603 12802069 PANELBOARD SCHEDULES
110 E-604 12802070 PANELBOARD SCHEDULES
TELECOM
111 T-001 12802071 LEGEND AND ABBREVIATIONS
112 TS101 12802072 TELECOMMUNICATIONS SITE PLAN - DEMOLITION
113 TS102 12802073 TELECOMMUNICATIONS SITE PLAN - DEMOLITION
114 TS103 12802074 TELECOMMUNICATIONS SITE PLAN - NEW WORK
115 TS104 12802075 TELECOMMUNICATIONS SITE PLAN - NEW WORK
116 TD101 12802076 TELECOMMUNICATIONS FLOOR PLAN - DEMOLITION
117 T-101 12802077 TELECOMMUNICATIONS FLOOR PLAN - NEW WORK
118 TY102 12802078 ELECTRONIC SECURITY SYSTEM (ESS) PLAN - NEW WORK
119 TA103 12802079 AV FLOOR PLAN
120 TA201 12802080 AV ELEVATIONS
121 T-401 12802081 PART PLANS
122 TA402 12802082 AV PART PLAN - TRAINING ROOM
123 TS501 12802083 COMMUNICATIONS MANHOLE AND HANDHOLE FOLD-OUTS - EXISTING
124 TS502 12802084 COMMUNICATIONS MANHOLE AND HANDHOLE FOLD-OUTS - NEW WORK
125 T-501 12802085 DETAILS
126 T-502 12802086 DETAILS
127 TA503 12802087 AV SYSTEM ONE-LINE DIAGRAM
128 TY504 12802088 ELECTRONIC SECURITY SYSTEM (ESS) DETAILS
129 T-601 12802089 TELECOMMUNICATIONS RISER DIAGRAM
130 T-602 12802090 TELECOMMUNICATIONS GROUNDING SCHEMATIC DIAGRAM
SHEET NO.
NAVFAC DWG. NO. SHEET TITLENO. SHEET
GENERAL
1 G-001 12801961 COVER SHEET
2 G-002 12801962 DRAWING INDEX
LIFE SAFETY
3 GI001 12801963 LIFE SAFETY GENERAL NOTES AND LEGEND
4 GI002 12801964 FIRE PROTECTION SITE COMPLIANCE PLAN
5 GI101 12801965 LIFE SAFETY FLOOR PLAN
HAZMAT
6 HM001 12801966 HAZMAT GENERAL NOTES AND PHOTOGRAPHS
GEOTECH
7 B-001 12801967 SOIL BORING LOGS - LEGEND, NOTES AND TEST RESULTS
8 B-101 12801968 SOIL BORING LOGS
CIVIL
9 C-001 12801969 LEGEND AND NOTES
10 C-002 12801970 EXISTING UTILITY SCHEDULES AND NOTES
11 CV-101 12801971 EXISTING CONDITIONS PLAN AND CLEAR ZONE
12 CD101 12801972 DEMOLITION AND EROSION CONTROL PLAN
13 CS101 12801973 SITE IMPROVEMENT PLAN
14 CG101 12801974 GRADING, DRAINAGE AND EROSION CONTROL PLAN
15 C-501 12801975 EROSION AND SEDIMENT CONTROL DETAILS AND NOTES
16 C-502 12801976 DETAILS
17 C-503 12801977 DETAILS
18 C-504 12801978 DETAILS
19 C-505 12801979 SECURITY FENCE DETAILS
LANDSCAPE
20 L-101 12801980 LANDSCAPE SITE IMPROVEMENTS PLAN
21 L-102 12801981 LANDSCAPE PLANTING PLAN
22 L-501 12801982 SITE IMPROVEMENTS DETAILS
23 L-502 12801983 PLANTING DETAILS
STRUCTURAL
24 S-001 12801984 STRUCTURAL NOTES
25 S-002 12801985 STRUCTURAL NOTES AND ABBREVIATIONS
26 S-100 12801986 DIMENSION PLAN
27 S-101 12801987 FOUNDATION PLAN
28 S-111 12801988 ROOF FRAMING PLAN
29 S-301 12801989 FOUNDATION SECTIONS
30 S-302 12801990 FOUNDATION SECTIONS
31 S-311 12801991 FRAMING SECTIONS
32 S-312 12801992 FRAMING SECTIONS
33 S-501 12801993 TYPICAL DETAILS
34 S-511 12801994 TYPICAL DETAILS
35 S-512 12801995 TYPICAL DETAILS
ARCHITECTURAL
36 A-001 12801996 PARTITION TYPES, ABBREVIATIONS, SYMBOLS AND LEGENDS
37 AD101 12801997 FLOOR PLAN - DEMOLITION
38 AD102 12801998 REFLECTED CEILING PLAN - DEMOLITION
39 AD103 12801999 ROOF PLAN - DEMOLITION
40 AD201 12802000 BUILDING ELEVATIONS - DEMOLITION
41 A-101 12802001 FLOOR PLAN - NEW WORK
42 A-102 12802002 REFLECTED CEILING PLAN - NEW WORK
43 A-103 12802003 PARTITION PLAN - NEW WORK
44 A-104 12802004 ROOF PLAN - NEW WORK
45 A-201 12802005 BUILDING ELEVATIONS - NEW WORK
46 A-301 12802006 BUILDING SECTIONS
47 A-302 12802007 BUILDING SECTIONS
48 A-303 12802008 WALL SECTIONS
49 A-304 12802009 WALL SECTIONS
50 A-305 12802010 WALL SECTIONS
51 A-306 12802011 WALL SECTIONS
52 A-401 12802012 ENLARGED PLANS AND DETAILS
53 A-501 12802013 COLUMN DETAILS
54 A-502 12802014 DETAILS
55 A-503 12802015 DETAILS
56 A-504 12802016 DETAILS
57 A-601 12802017 DOOR SCHEDULE, STOREFRONT ELEVATIONS AND DETAILS
58 A-602 12802018 DOOR DETAILS
59 A-603 12802019 DOOR AND TRANSITION DETAILS
60 A-604 12802020 FINISH AND COLOR SCHEDULE
61 A-605 12802021 SIGNAGE PLAN, SCHEDULE AND DETAILS
62 A-701 12802022 TOILET ELEVATIONS, CASEWORK ELEVATIONS AND DETAILS
GENERAL PROJECT NOTES
1 WHERE EXISTING CONSTRUCTION IS DAMAGED BY CONSTRUCTION
REQUIRED BY THESE DOCUMENTS. REPAIR THE DAMAGED ITEM(S)
WITH MATERIALS TO MATCH THE ADJACENT MATERIAL, TEXTURE
AND COLOR.
2 FIELD VERIFY EXISTING DIMENSIONS, PRIOR TO ORDERING
MATERIALS OR BEGINNING DEMOLITION.
3 ALL ITEMS NOT SHOWING AS "EXISTING" MUST BE PROVIDED AND
INSTALLED UNDER THE REQUIREMENTS OF THIS CONTRACT.
4 COORDINATE LAY DOWN AREA WITH THE CONTRACTING OFFICER
PRIOR TO THE PRECONSTRUCTION MEETING. THE ALLOWABLE
AREA SIZE MUST BE ESTABLISHED BY THE CONTRACTING
OFFICER.
5 MANUFACTURER'S TRADE NAMES LISTED ARE NOT INTENDED TO
BE PROPRIETARY. PRODUCTS OF OTHER MANUFACTURERS WILL
BE ACCEPTABLE PROVIDED THEY MATCH THE COLOR, FINISHES,
TEXTURES AND PATTERNS OF THE MANUFACTURER LISTED, AND
MEET THE TECHNICAL REQUIREMENTS OF THE SPECIFICATIONS.
6 OBSERVE AND MAINTAIN BUILDING AND COMPOUND SECURITY
REQUIREMENTS AS DIRECTED BY THE CONTRACTING OFFICER.
7 CONSTRUCTION WILL BE ACCOMPLISHED IN AND AROUND AREAS
WHICH WILL REMAIN OPERATIONAL. AVOID INTERFERENCE WITH
THE OPERATIONAL WORK ROUTINE.
8 ALL SUBMITTALS REQUIRED BY THESE DRAWINGS OR
SPECIFICATIONS MUST BE SUBMITTED TO THE CONTRACTING
OFFICER FOR APPROVAL PRIOR TO COMMENCEMENT OF RELATED
WORK.
1. ALL ITEMS INDICATED TO BE REMOVED MUST BE DISPOSED OF
OFF SITE UNLESS OTHERWISE NOTED.
2 ALL MATERIALS MUST BE NEW AND PROVIDED BY THE
CONTRACTOR UNLESS SPECIFICALLY NOTED AS EXISTING OR AS
PROVIDED BY THE GOVERNMENT.
3 ALL WOOD BLOCKING AND MISCELLANEOUS STEEL SHOWN IN
DETAILS AND SECTIONS MUST BE CONTINUOUS UNLESS
SPECIFICALLY NOTED OTHERWISE.
4 VERIFY ALL FIELD CONDITIONS AND DIMENSIONS PRIOR TO
PROCEEDING WITH THE WORK. DIMENSIONS FOR EXISTING WORK
ARE INDICATED AS "±". ALL DISCREPANCIES MUST BE BROUGHT
IN WRITING TO THE IMMEDIATE ATTENTION OF THE CONTRACTING
OFFICER.
5 DEMOLITION OF PLUMBING, MECHANICAL AND ELECTRICAL ITEMS
INDICATED ON THE ARCHITECTURAL DRAWINGS IS NOT INTENDED
TO INCLUDE ALL NECESSARY DEMOLITION WORK FOR THESE ITEMS.
REFER TO PLUMBING, MECHANICAL AND ELECTRICAL DEMOLITION
DRAWINGS FOR ADDITIONAL INFORMATION.
6 DIMENSIONS INDICATED FOR NEW WORK ARE TO FACE OF STUD,
FACE OF MASONRY OR FACE OF EXISTING SURFACES UNLESS
OTHERWISE NOTED.
7 STUDY AND COMPARE THE CONTRACT DOCUMENTS WITH EACH
OTHER, AND AT ONCE, REPORT TO THE CONTRACTING OFFICER
ANY ERRORS AND INCONSISTENCIES OR OMISSIONS DISCOVERED.
ANY CONSTRUCTION ACTIVITY PERFORMED KNOWING IT INVOLVES A
RECOGNIZED ERROR, INCONSISTENCY OR OMISSION IN THE
CONTRACT DOCUMENTS WITHOUT SUCH NOTICE TO THE
CONTRACTING OFFICER, THE CONTRACTOR WILL ASSUME
RESPONSIBILITY FOR SUCH PERFORMANCE AND WILL BEAR THE
AMOUNT OF THE COST OF THE CONSTRUCTION.
GENERAL SHEET NOTES I
G
IV R
FOHT
I
NO
M N
EW
A
OM
L
C
TH I ECRC
A T
A
NO. 013034
CLAY C. DILLS
SY
M
DE
S C
RI
PT
I O N
DA
TE
TD = XX FT
CPT = XX FT
XXX
XXX
XXX
LEGENDAPPLICABLE BUILDING CODES
USE GROUP/OCCUPANCY
FIRE PROTECTION SYSTEMS
CONSTRUCTION TYPE
FIRE RESISTANCE RATING REQUIREMENTS FOR BUILDING ELEMENTS
INTERIOR FIRE RESISTANCE REQUIREMENTS
INTERIOR FINISH CLASSIFICATION
TRAVEL DISTANCES
CAPACITY OF EXITS
ADDITIONAL LIFE SAFETY CRITERIA
MEANS OF EGRESS
ALLOWABLE AREA & HEIGHT
ACTUAL AREA & HEIGHT
EXTERIOR WALLS
REQUIRED EGRESS CAPACITY
PROVIDED EGRESS CAPACITY
TOTAL AREA OF OCCUPANCY CLASS (SQ.FT.)
OCCUPANT LOAD (SQ.FT/PERSON)
NUMBER OF OCCUPANTS
TRAVEL DISTANCE
COMMON PATH OF TRAVEL DISTANCE
1-HR FIRE BARRER
1. IBC INTERNATIONAL BUILDING CODE, 2018
2.
3.
4.
NFPA 13 STANDARD FOR THE INSTALLATION OF SPRINKLER SYSTEMS, 2019
5.
NFPA 70 NATIONAL ELECTRIC CODE, 2017
6.
NFPA 72 NATIONAL FIRE ALARM AND SIGNALING CODE, 2019
7.
NFPA 101 LIFE SAFETY CODE, 2018 (LSC)
UFAS UNIFORM FEDERAL ACCESSIBILITY STANDARDS
ABA ARCHITECTURAL BARRIERS ACT
B (IBC 304.1) / BUSINESS (LSC CHAPTER 38)
S-1 (IBC 311.2) / STORAGE (LSC CHAPTER 42}
FIRE ALARM MASS NOTIFICATION SYSTEM
BUILDING IS NOT SPRINKLERED
BUILDING P-Q698 TYPE II-B
BASED ON B USE GROUP
ALLOWABLE FLOOR AREA B / S-1 (IBC TABLE 506.2 ): 23,000 SF / 17,500 SF
ALLOWABLE STORIES FOR B / S-1 (IBC TABLE 504.4): 3-STORIES / 2 STORIES
ALLOWABLE HEIGHT FOR B / S-1 (IBC TABLE 504.3): 55 FT / 55 FT
TOTAL FOOTPRINT FLOOR AREA 7,765 TOTAL
BUILDING HEIGHT 1-STORY / 25-FT
(IBC TABLE 601, TYPE II-B CONSTRUCTION)
STRUCTURAL FRAME, INCL. COLUMNS, GIRDERS & TRUSSES 0-HR
BEARING WALLS, EXTERIOR 0-HR
BEARING WALLS, INTERIOR 0-HR
NON-BEARING WALLS, INTERIOR & EXTERIOR 0-HR
FLOOR CONSTRUCTION 0-HR
ROOF CONSTRUCTION 0-HR
EXTERIOR FIRE-RESISTANCE RATING BASED ON FIRE SEPARATION DISTANCE (TYPE II-B)
THE DISTANCE BETWEEN BUILDING P-Q698 AND THE CLOSEST ADJACENT BUILDING IS GREATER THAN 20-FT.
AREA OCCUPANCY USE
APPROX.
AREA (SF)
OCCUPANT LOAD
FACTOR
(SF/PERSON)
OCCUPANT
LOAD
(PERSONS)
FIRST FLOOR
LIMITS (BASED ON BUSINESS / STORAGE OCCUPANCY):
EXITS (LSC TABLE A.10.2.2) MINIMUM CLASS B / MINIMUM CLASS B
EXIT ACCESS CORRIDORS (LSC TABLE A.10.2.2 MINIMUM CLASS B / MINIMUM CLASS C
OTHER SPACES (LSC TABLE A.10.2.2) MINIMUM CLASS C / MINIMUM CLASS C
OCCUPANT LOADS (LSC TABLE 7.3.1.2)
BUSINESS 150 SF/PERSON
ASSEMBLY USE 15 SF/PERSON
MEP/GENERAL STORAGE 500 SF/PERSON
CLASSROOM 20 SF/PERSON
LOCKER ROOM 50 SF/PERSON
COMMON PATH OF TRAVEL BUSINESS / STORAGE (LSC TABLE A.7.6): 75-FT/50-FT
DEAD END CORRIDOR BUSINESS / STORAGE (LSC TABLE A.7.6): 20-FT/50-FT
EXIT ACCESS TRAVEL DISTANCE BUSINESS (LSC TABLE A.7.6): 200-FT/200-FT
CAPACITY OF EXITS (LSC TABLE 7.3.3.1):
LEVEL COMPONENTS (WIDTH/PERSON) 0.2 IN/PERSON
STAIRWAYS (WIDTH/PERSON) 0.3 IN/PERSON
NUMBER OF EXITS (LSC 7.4):
2 EXITS FOR AREAS WITH AN OCCUPANT LOAD LESS THAN 500
EMERGENCY LIGHTING SYSTEMS SHALL PROVIDE IN ACCORDANCE WITH LSC 7.9.2.1 & 7.9.2.2 (LSC 238.2.8).
MEANS OF EGRESS SHALL BE PROVIDED WITH SIGNS IN ACCORDANCE WITH LSC 7.10 AND UFC 3-600-01 10-2
(LSC 38.2.10). SIGNS MUST HAVE LETTERING ON AN OPAQUE BACKGROUND. INTERNALLY ILLUMINATED
SIGNS MUST BE LIGHT EMITTING DIODE (LED) TYPE, ELECTROLUMINESCENCE (LEC), OR COLD CATHODE
TYPE. INCANDESCENT FIXTURES ARE NOT PERMITTED. RADIOLUMINOUS EXIT SIGNS ARE NOT PERMITTED
(UFC 3-600-01 10-2.2).
FUEL-FIRED HEATER ROOMS 1-HR RATED FIRE BARRIER (LSC 9.7)
FLOOR LEVEL
REQUIRED EXIT
CAPACITY
AVAILABLE EXIT
CAPACITY
NUMBER OF
EXITS REQUIRED
NUMBER OF
EXITS PROVIDED
42680125FIRE SEPARATION DISTANCE (FSD)
FSD < 5-FT
GROUP B
1-HR
5 FT < FSD < 10-FT 1-HR
ROOM REQUIRED SEPARATION
STORAGE ROOMS 1-HR RATED FIRE BARRIER (LSC 9.7)
OFFICE USE BUSINESS 3,163 22150
FIRST FLOOR
TRAINING
BREAK ROOM
BUSINESS 721 4915
BUSINESS 183 1315
TOTAL 7,765 125-
FSD > 10-FT 0-HR
GROUP S
2-HR
1-HR
0-HR
LOCKER ROOMS LOCKER 1,731 3550
WAREHOUSE STORAGE 1,494 5MAX. EXPECTED
MEP / GENERAL STORAGE MEP/GEN. STORAGE 473 1500
MIXED NON-SEPARATED OCCUPANCY
FE 2A:40B:C FIRE EXTINGUISHER
SATISFACTORY TO DATE
APPROVED
ACTIVITY
FOR COMMANDER NAVFAC
SEAL
A/E INFO
A
B
C
D
1 2 3 4 5
1 2 3 4 5
A
B
C
D
SCALE:
CONSTR. CONTR. NO.
SHEET
NAVFAC DRAWING NO.
DES DRW CHK
OF
EPROJECT NO.:
D E
P A
R T
M E
N T
O F
T H
E N
A V
Y N
A V
A L
F A
C
IL
IT
IE
S E
N G
IN
E
E R
IN
G
C O
M M
A N
D
DRAWFORM REVISION: 7 FEBRUARY 2019
PM/DM
BRANCH MANAGER
CHIEF ENG/ARCH
FIRE PROTECTION
N A
V A
L F
A C
IL
IT
IE
S
E N
G
IN
E E
R
IN
G C
O M
M A
N D
M
ID
A
T L A
N T
IC
N
A V
A L
S T
A T
IO
N
N
O R
F O
L K
V
A
AS NOTED
GI001
P -Q
S
O F
P H
Y S
IC
A
L S
E C
U R
IT
Y
LI
F
E S
A
FE
TY
G
E N
E R
A L
N O
TE
S
A N
D L
E G
E N
D
APF
12801963
AEC AEC
10/06/2020
APPROVED BY JOHN TAYLOR WITH
NSWDG, VIA EMAIL
B U
IL
D
IN
G
A D
D
IT
IO
N
JMB/JH
1387235
V
IR
G
IN
IA
B
E A
C H
, V
IR
G
IN
IA
N
A S
O C
E A
N A
D A
M N
E C
K A
N N
E X
M
ID
L A
N T
C I
C O
R E
EJA
DSN
DSN
S Y
M D
E S
C R
IP
T
IO
N
D A
T E
A P
P R
FIRE DEPARTMENT ACCESS (OPEN TO ROAD)
FIRE DEPARTMENT MAIN ENTRANCE
FI
R
E H
Y D
R A
N T
M A
X
IM
U M
D
IS
TA
N
C E
FIRE HYDRANT FOR FD USE
SATISFACTORY TO DATE
APPROVED
ACTIVITY
FOR COMMANDER NAVFAC
SEAL
A/E INFO
A
B
C
D
1 2 3 4 5
1 2 3 4 5
A
B
C
D
SCALE:
CONSTR. CONTR. NO.
SHEET
NAVFAC DRAWING NO.
DES DRW CHK
OF
EPROJECT NO.:
D E
P A
R T
M E
N T
O F
T H
E N
A V
Y N
A V
A L
F A
C
IL
IT
IE
S E
N G
IN
E
E R
IN
G
C O
M M
A N
D
DRAWFORM REVISION: 7 FEBRUARY 2019
PM/DM
BRANCH MANAGER
CHIEF ENG/ARCH
FIRE PROTECTION
N A
V A
L F
A C
IL
IT
IE
S
E N
G
IN
E E
R
IN
G C
O M
M A
N D
M
ID
A
T L A
N T
IC
N
A V
A L
S T
A T
IO
N
N
O R
F O
L K
V
A
AS NOTED
GI002
P -Q
S
O F
P H
Y S
IC
A
L S
E C
U R
IT
Y
F
IR
E P
R O
TE
C
TI
O
N S
IT
E
C O
M P
LI
A
N C
E P
LA
N
APF
12801964
AEC AEC
10/06/2020
APPROVED BY JOHN TAYLOR WITH
NSWDG, VIA EMAIL
B U
IL
D
IN
G
A D
D
IT
IO
N
JMB/JH
1387235
V
IR
G
IN
IA
B
E A
C H
, V
IR
G
IN
IA
N
A S
O C
E A
N A
D A
M N
E C
K A
N N
E X
M
ID
L A
N T
C I
C O
R E
EJA
DSN
DSN
SCALE: NTS
FIRE PROTECTION SITE COMPLIANCE PLAN
S Y
M D
E S
C R
IP
T
IO
N
D A
T E
A P
FE
FE
FE
FE
1,529
1,731
3,128
MAX
5*
FE
TD = 59 FT
CPT = 47 FT
TD = 76 FT
TD = 77 FT
xA x1 x2 x3x3.1 x4 x5 xB xC xD xA.1 x3.2
AA
4.1 5.1
BB
E
F
6 7
WATCH SECTION
WATCH
COMMANDER
ESS OFFICE
WOMEN'S
LOCKERS
MEN'S TOILET
112 JAN.
BREAK ROOM
WOMEN'S TOILET
TRAINING
VEST.
MECH.
MEN'S LOCKERS
ELECT.
WAREHOUSE
CORRIDOR
TELECOM
PRINT/ COPY
PUBLIC TLT.
CORRIDOR
CORRIDOR
MEN'S SHOWERS
WOMEN'S
SHOWER
C P
T
F T
D E
F
T
SATISFACTORY TO DATE
APPROVED
ACTIVITY
FOR COMMANDER NAVFAC
SEAL
A/E INFO
A
B
C
D
1 2 3 4 5
1 2 3 4 5
A
B
C
D
SCALE:
CONSTR. CONTR. NO.
SHEET
NAVFAC DRAWING NO.
DES DRW CHK
OF
EPROJECT NO.:
D E
P A
R T
M E
N T
O F
T H
E N
A V
Y N
A V
A L
F A
C
IL
IT
IE
S E
N G
IN
E
E R
IN
G
C O
M M
A N
D
DRAWFORM REVISION: 7 FEBRUARY 2019
PM/DM
BRANCH MANAGER
CHIEF ENG/ARCH
FIRE PROTECTION
N A
V A
L F
A C
IL
IT
IE
S
E N
G
IN
E E
R
IN
G C
O M
M A
N D
M
ID
A
T L A
N T
IC
N
A V
A L
S T
A T
IO
N
N
O R
F O
L K
V
A
AS NOTED
GI101
P -Q
S
O F
P H
Y S
IC
A
L S
E C
U R
IT
Y
LI
F
E S
A
FE
TY
F
LO
O
R P
LA
N
APF
12801965
AEC AEC
10/06/2020
APPROVED BY JOHN TAYLOR WITH
NSWDG, VIA EMAIL
B U
IL
D
IN
G
A D
D
IT
IO
N
JMB/JH
1387235
V
IR
G
IN
IA
B
E A
C H
, V
IR
G
IN
IA
N
A S
O C
E A
N A
D A
M N
E C
K A
N N
E X
M
ID
L A
N T
C I
C O
R E
EJA
DSN
DSN
SCALE: 1/8" = 1'-0"
LIFE SAFETY FLOOR PLAN
PLAN
NORTH
GRAPHIC SCALE(S)
KEY PLAN
EXISTING
NEW
4' 8' 16'0' 1/8" =1'-0"
PLAN
NORTH
S Y
M D
E S
C R
IP
T
IO
N
D A
T E
A P
TEMPORARY SEEDING SPECIFICATIONS
SEED
APPLICATION DATES SEED SPECIES APPLICATION RATES
SPRING AND FALL ELYMUS VIRGINICUS VIRGINIA
WILD RYE
24 (LBS/ACRE)
FERTILIZER
1. IF REQUIRED, APPLICATION OF FERTILIZER SHOULD BE MINIMIZED AS MUCH AS POSSIBLE;
APPLY DELIBERATELY IN SPECIFIED AREAS ONLY (IE, NEWLY SEEDED AREAS, AREAS RESTORED
POST‐CONSTRUCTION)
2. FERTILIZER SHALL BE APPLIED IN ACCORDANCE WITH MANUFACTURER’S SPECIFICATIONS;
ENVIRONMENTALLY FRIENDLY PRODUCTS RECOMMENDED; PRODUCTS ALREADY APPROVED
FOR USE BY NASO GROUNDS MAINTENANCE CREWS
3. DO NOT OVER‐APPLY, NO APPLICATION OF FERTILIZERS BEFORE A PREDICTED RAIN EVENT
4. KEEP FERTILIZER OFF SIDEWALKS/IMPERVIOUS SURFACES, SWEEP INTO GRASS IMMEDIATELY
5. NO DISCHARGE OF FERTILIZER TO STORM DRAINS, SURFACE WATERS, ETC.
SATISFACTORY TO DATE
APPROVED
ACTIVITY
FOR COMMANDER NAVFAC
SEAL
A/E INFO
A
B
C
D
1 2 3 4 5
1 2 3 4 5
A
B
C
D
SCALE:
CONSTR. CONTR. NO.
SHEET
NAVFAC DRAWING NO.
DES DRW CHK
OF
EPROJECT NO.:
D E
P A
R T
M E
N T
O F
T H
E N
A V
Y N
A V
A L
F A
C
IL
IT
IE
S E
N G
IN
E
E R
IN
G
C O
M M
A N
D
DRAWFORM REVISION: 7 FEBRUARY 2019
PM/DM
BRANCH MANAGER
CHIEF ENG/ARCH
FIRE PROTECTION
N A
V A
L F
A C
IL
IT
IE
S
E N
G
IN
E E
R
IN
G C
O M
M A
N D
M
ID
A
T L A
N T
IC
N
A V
A L
S T
A T
IO
N
N
O R
F O
L K
, V A
AS NOTED
UNCLASSIFIED
UNCLASSIFIED
U N
C
LA
S S
IF
IE
D
S-001
P -Q
S
O F
P H
Y S
IC
A
L S
E C
U R
IT
Y
S
TR
U C
T U
R A
L N
O
TE
S
DWS
12801984
EHI FCS
10/06/2020
APPROVED BY JOHN TAYLOR WITH
HSWDG, VIA EMAIL
B U
IL
D
IN
G
A D
D
IT
IO
N
JB/JH
1387235
VI
R
G
IN
IA
B
EA
C
H , V
IR
G
IN
IA
N
AS
O C
EA
N
A D
AM
N
EC
K
AN
N
EX
M
ID
LA
N
T C
I C
O R
E
EJA
DJD
DSN
SPEIGHT MARSHALL FRANCIS. .
STRUCTURAL ENGINEERS
SM&F Job No:WWW.SMANDF.COM
1228 PERIMETER PARKWAY, SUITE 201
P: 757.427.1020
VIRGINIA BEACH, VIRGINIA 23454
P: 804.464.4111
RICHMOND, VIRGINIA 23294
2821 EMORYWOOD PARKWAY SUITE 300
18.015-J
THE STRUCTURAL DRAWINGS MUST BE USED IN CONJUNCTION WITH THE
ARCHITECTURAL, CIVIL, MECHANICAL, PLUMBING, ELECTRICAL DRAWINGS AND
THE SPECIFICATIONS. THE CONTRACTOR MUST VERIFY THE REQUIREMENTS OF
OTHER TRADES FOR ITEMS TO BE PLACED OR SET IN THE STRUCTURAL WORK.
THIS STRUCTURE HAS BEEN DESIGNED IN ACCORDANCE WITH THE PROVISIONS
OF THE INTERNATIONAL BUILDING CODE, 2018 EDITION, AS ADOPTED BY THE
UNIFIED FACILITIES CRITERIA, AND AS FOLLOWS:
TO HEAVY LOADS
BUILDINGS
THE WORK UNDER THE FOLLOWING SPECIFICATION SECTIONS IS SUBJECT TO
SPECIAL INSPECTIONS AND TESTS AS DESCRIBED IN SECTION 1704 OF THE
INTERNATIONAL BUILDING CODE, 2018 EDITION:
312000 - EARTHWORK
033000 - CAST-IN-PLACE CONCRETE
042000 - UNIT MASONRY
051200 - STRUCTURAL STEEL
052100 - STEEL JOISTS
053100 - STEEL DECK
THE CONTRACTOR MUST BE RESPONSIBLE FOR TEMPORARY SHORING AND
BRACING REQUIRED TO ERECT AND HOLD THE STRUCTURE IN PROPER
ALIGNMENT UNTIL PERMANENT SUPPORTS AND LATERAL BRACING ARE IN PLACE.
BEFORE PROCEEDING WITH WORK WITHIN OR NEAR THE EXISTING STRUCTURE,
THE CONTRACTOR MUST BECOME FAMILIAR WITH THE EXISTING STRUCTURAL
CONDITIONS. THE SHORING AND BRACING SHOWN IS A PARTIAL AND SCHEMATIC
REPRESENTATION OF THAT REQUIRED. THE CONTRACTOR MUST BE
RESPONSIBLE FOR THE DESIGN AND ERECTION OF ALL SAFEGUARDS
NECESSARY TO PROTECT THE EXISTING STRUCTURE FROM DAMAGE.
THE CONTRACTOR MUST FIELD VERIFY THE DIMENSIONS, ELEVATIONS AND
OTHER REQUIREMENTS NECESSARY FOR THE PROPER CONSTRUCTION AND
ALIGNMENT OF THE NEW PORTIONS OF THE STRUCTURE TO THE EXISTING. THE
CONTRACTOR MUST MAKE ALL MEASUREMENTS NECESSARY FOR FABRICATION
AND ERECTION OF STRUCTURAL MEMBERS.
THE PROJECT SPECIFICATIONS ARE NOT SUPERSEDED BY THE STRUCTURAL
NOTES BUT ARE INTENDED TO BE COMPLEMENTARY TO THEM. REFER TO THE
SPECIFICATIONS FOR ADDITIONAL REQUIREMENTS IN EACH SECTION.
SPECIFIC NOTES AND DETAILS ON THE DRAWINGS MUST TAKE PRECEDENCE
OVER STRUCTURAL NOTES AND TYPICAL DETAILS.
CONSULTANTS' DRAWINGS, INCLUDING STRUCTURAL DRAWINGS, ARE
CONSIDERED SUPPLEMENTARY TO THE ARCHITECTURAL DRAWINGS. ANY
OMISSIONS OR CONFLICTS, INCLUDING DIMENSIONS, BETWEEN VARIOUS
ELEMENTS OF THE CONSULTANTS' DRAWINGS AND/OR SPECIFICATIONS MUST BE
BROUGHT TO THE ATTENTION OF THE ARCHITECT PRIOR TO PROCEEDING WITH
THE WORK.
THE DOCUMENTS DEFINING THE STRUCTURE ARE INSTRUMENTS OF SERVICE
PREPARED BY SPEIGHT, MARSHALL AND FRANCIS, P.C. FOR ONE USE ONLY. THE
STRUCTURAL DOCUMENTS MUST NOT BE REPRODUCED, OR COPIED IN WHOLE
OR IN PART BY THE CONTRACTOR OR SUBCONTRACTORS FOR PREPARATION OF
SHOP DRAWINGS OR OTHER SUBMITTALS WITHOUT WRITTEN PERMISSION FROM
THE ARCHITECT.
LOADS USED IN THE DESIGN OF THIS STRUCTURE ARE AS FOLLOWS:
LIVE LOADS:
SNOW DESIGN DATA:
WIND DESIGN DATA:
COMPONENTS AND CLADDING DESIGN PRESSURES
SEISMIC DESIGN DATA:
BASIC SEISMIC-FORCE-RESISTING SYSTEM IS INTERMEDIATE
REINFORCED MASONRY SHEAR WALLS
FORCE PROTECTION:
BUILDING HAS AN OCCUPANCY DESIGNATION OF INHABITED WITH A VERY
LOW LEVEL OF PROTECTIVE AND HAS BEEN DESIGNED IN ACCORDANCE
WITH UFC 4-010-01 ANTITERRORISM PROVISIONS.
DESIGN CRITERIA SERVICE ABILITY LIMITS:
ROOF DEFLECTIONS:
FOUNDATION NOTES:
FOUNDATIONS HAVE BEEN DESIGNED IN ACCORDANCE WITH THE
RECOMMENDATIONS IN THE GEOTECHNICAL EXPLORATION REPORT PREPARED
BY GEOENVIRONMENTAL RESOURCES DATED APRIL 17, 2020.
FOUNDATIONS HAVE BEEN DESIGNED FOR A BEARING PRESSURE OF 2,000 PSF.
PRIOR TO PLACING FOUNDATION CONCRETE, ALL FOUNDATION EXCAVATIONS
MUST BE INSPECTED BY THE GEOTECHNICAL ENGINEER TO EXPLORE THE
EXTENT OF LOOSE, SOFT OR OTHERWISE UNSATISFACTORY SOIL MATERIAL AND
TO VERIFY DESIGN BEARING PRESSURE. THE GEOTECHNICAL ENGINEER WILL
PROVIDE DIRECTION FOR CORRECTIVE ACTION WHERE REQUIRED.
NO UNBALANCED BACKFILLING MAY BE DONE AGAINST WALLS UNLESS WALLS
ARE SECURELY BRACED AGAINST OVERTURNING, EITHER BY TEMPORARY
CONSTRUCTION BRACING OR BY PERMANENT CONSTRUCTION.
CAST-IN-PLACE CONCRETE NOTES:
CAST-IN-PLACE CONCRETE HAS BEEN DESIGNED IN ACCORDANCE WITH THE
AMERICAN CONCRETE INSTITUTE (ACI) "BUILDING CODE REQUIREMENTS FOR
STRUCTURAL CONCRETE (ACI 318-14) AND COMMENTARY (ACI 318R-14)".
CONCRETE MUST BE NORMAL WEIGHT AND MUST OBTAIN 28 DAY COMPRESSIVE
STRENGTHS AS FOLLOWS:
REINFORCING MATERIALS MUST BE AS FOLLOWS:
REINFORCING BARS - ASTM A615, GRADE 60, DEFORMED.
WELDED REINFORCING BARS - ASTM A706, GRADE 60.
FIBER REINFORCING:
SYNTHETIC - ASTM C1116, TYPE III
ALL REINFORCING STEEL AND EMBEDDED ITEMS MUST BE ACCURATELY PLACED
IN THE POSITIONS SHOWN AND ADEQUATELY TIED AND SUPPORTED BEFORE
CONCRETE IS PLACED TO PREVENT DISPLACEMENT BEYOND PERMITTED
TOLERANCES.
MINIMUM CONCRETE COVER FOR REINFORCING STEEL AS INDICATED ON THE
DRAWINGS MUST GOVERN WHEN IN CONFLICT WITH ACI 318-14.
UNLESS OTHERWISE NOTED ON THE STRUCTURAL DRAWINGS:
LAP SPLICE LENGTHS MUST BE 57 BAR DIAMETERS
SPLICES MAY BE MADE WITH MECHANICAL SPLICES (AT CONTRACTOR'S
OPTION). MECHANICAL SPLICES MUST BE:
CAPABLE OF RESISTING 125% OF THE TENSION CAPACITY
POSITIVE-CONNECTING TYPE COUPLERS
SUBMITTED FOR REVIEW
STAGGERED A MINIMUM OF 24" ALONG THE LONGITUDINAL AXIS
OF ADJACENT BARS
STRUCTURAL STEEL NOTES:
STRUCTURAL STEEL HAS BEEN DESIGNED IN ACCORDANCE WITH THE
FOURTEENTH EDITION (AISC 360-16) "SPECIFICATION FOR STRUCTURAL STEEL
BUILDINGS" - ALLOWABLE STRESS DESIGN.
STRUCTURAL STEEL MUST COMPLY WITH THE FOLLOWING SPECIFICATIONS:
STRUCTURAL STEEL W- AND WT-SHAPES - ASTM A992, Fy=50 KSI RECTANGULAR AND SQUARE HSS - ASTM A500, GRADE C, Fy=50 KSI
ANCHOR RODS - ASTM F1554, GRADE 36
HEADED STUDS - ASTM A 108, GRADES 1015 THROUGH 1020, TYPE B,
Fu=65 KSI
ALL OTHER STRUCTURAL STEEL SHAPES, PLATES AND BARS - ASTM A36,
Fy=36 KSI (UNLESS OTHERWISE NOTED)
UNLESS OTHERWISE NOTED, ALL SHEAR CONNECTIONS MUST BE DESIGNED FOR
1/2 OF THE "MAXIMUM TOTAL UNIFORM LOAD" AS SHOWN IN PART 3 OF THE
"STEEL CONSTRUCTION MANUAL", FOR THE BEAM SIZE, SPAN AND GRADE
SPECIFIED.
HIGH STRENGTH BOLTS MAY BE TIGHTENED TO THE "SNUG TIGHT" CONDITION IN
LIEU OF FULL PRETENSIONING.
WELDING MUST BE IN ACCORDANCE WITH AWS D1.1, "STRUCTURAL WELDING
CODE - STEEL". WELD ELECTRODES MUST BE E70XX. CONTINUOUS 3/16" FILLET
WELDS ARE REQUIRED UNLESS OTHERWISE NOTED.
SEE THE ARCHITECTURAL, CIVIL, MECHANICAL, PLUMBING AND ELECTRICAL
DRAWINGS FOR ADDITIONAL STEEL (IF ANY) NOT SHOWN ON THE STRUCTURAL
DRAWINGS.
UNLESS OTHERWISE NOTED, THE TOP OF ALL STEEL COLUMNS MUST HAVE A
STEEL CAP PLATE. UNLESS OTHERWISE DETAILED OR NOTED, MINIMUM CAP
PLATE DIMENSIONS MUST MATCH COLUMN WIDTH AND DEPTH AND MINIMUM
THICKNESS OF CAP PLATE MUST EQUAL COLUMN WEB THICKNESS (1/2" MIN).
STRUCTURAL STEEL NOTED TO BE GALVANIZED MUST CONFORM TO ASTM A123
OR ASTM A153. GALVANIZE STRUCTURAL STEEL AFTER FABRICATION WHERE
PRACTICAL. REPAIR DAMAGED GALVANIZED COATING USING ASTM A780 ZINC-
RICH PAINT.
APPLY NO PAINT OR PRIMER ON STRUCTURAL STEEL SURFACES RECEIVING
SPRAYED FIRE-RESISTIVE MATERIALS. SEE THE ARCHITECTURAL DRAWINGS FOR
EXTENTS OF SPRAYED FIRE RESISTIVE MATERIALS.
STEEL JOIST NOTES:
STEEL JOISTS MUST CONFORM TO THE LATEST EDITION OF THE STEEL JOIST
INSTITUTE (SJI) STANDARD SPECIFICATIONS.
PREPARE AND SUBMIT FOR REVIEW SHOP DRAWINGS SHOWING THE LAYOUT OF
JOIST MEMBERS, SPECIAL CONNECTIONS, JOINING AND ACCESSORIES. INCLUDE
MARK, NUMBER, TYPE, LOCATION AND SPACING OF JOISTS AND BRIDGING.
THE JOIST MANUFACTURER MUST BE RESPONSIBLE FOR CONTINUOUS JOIST
BRIDGING LINES SATISFYING THE REQUIREMENTS OF THE SJI SPECIFICATION
FOR THE TOP AND BOTTOM CHORDS OF ALL STEEL JOISTS, AS WELL AS ANY
ADDITIONAL BRIDGING/BRACING SHOWN OR REQUIRED FOR JOISTS SUBJECTED
TO NET UPLIFT OR OTHER SPECIAL LOADS. ALL REQUIRED JOIST BRIDGING MUST
BE CLEARLY INDICATED ON THE SHOP DRAWINGS. CROSS-BRIDGING IS
REQUIRED AT CHANGES OF JOIST DEPTHS AND ENDS OF ALL BRIDGING LINES,
UNLESS SUCH ENDS ARE PROPERLY ANCHORED INTO INTERSECTING INTERIOR
OR END WALLS. ALL BRIDGING AND BRIDGING ANCHORS MUST BE COMPLETELY
INSTALLED BEFORE PLACING OF ANY CONSTRUCTION LOADS ON THE JOISTS.
ROOF JOISTS MUST BE DESIGNED FOR A NET UPLIFT LOAD (SERVICE / ASD)
WHERE JOIST SPAN EQUALS 40 FEET OR GREATER JOIST MUST BE ERECTION
BOLTED TO STEEL BEAMS, UNLESS PANELIZED JOIST ERECTION IS EMPLOYED.
GENERAL CONTRACTOR MUST COORDINATE BOLT HOLE LOCATIONS REQUIRED
IN STRUCTURAL STEEL MEMBERS.
CONCENTRATED LOADS NOT LOCATED AT JOIST PANEL POINTS MUST BE
REINFORCED PER 'TYPICAL DETAIL AT CONCENTRATED LOADS ON JOISTS'.
UNLESS OTHERWISE NOTED, JOIST SEAT DEPTHS MUST BE AS FOLLOWS:
4-1/2" AT 'K' SERIES JOISTS
APPLY NO PAINT OR PRIMER ON SURFACES OF STEEL JOISTS AND JOIST
ACCESSORIES RECEIVING SPRAYED FIRE-RESISTIVE MATERIALS. SEE THE
ARCHITECTURAL DRAWINGS FOR EXTENTS OF SPRAYED FIRE-RESISTIVE
MATERIALS.
STEEL DECK NOTES:
STEEL DECK MUST CONFORM TO THE LATEST EDITION OF THE AMERICAN IRON
AND STEEL INSTITUTE (AISI), "SPECIFICATION FOR THE DESIGN OF COLD-FORMED
STEEL STRUCTURAL MEMBERS" AND THE STEEL DECK INSTITUTE (SDI), "DESIGN
MANUAL FOR COMPOSITE DECKS, FORM DECKS, AND ROOF DECKS."
STEEL DECK UNITS MUST COMPLY WITH THE FOLLOWING:
1-1/2" ROOF DECK MUST BE 22 GAGE GALVANIZED NON-PAINTED TYPE B
RIB DECK SPANNING PERPENDICULAR TO SUPPORTS UNLESS OTHERWISE
NOTED. ATTACH DECK TO STRUCTURAL STEEL SUPPORTS WITH 5/8"
DIAMETER PUDDLE WELDS AT EVERY RIB, INCLUDING RIBS WHERE
SIDELAPS OCCUR AND FASTEN ADJACENT DECK UNITS WITH #10
SELF-TAPPING HEX HEAD SCREWS AT 1/4 POINTS BETWEEN SUPPORTS
ALONG SIDELAPS AND FASTEN EDGEMOST DECK PANEL TO STEEL FRAMING
WITH 5/8" DIAMETER PUDDLE WELDS AT SAME SPACING AS SIDELAP
FASTENERS.
WELDING MUST BE IN ACCORDANCE WITH AWS D1.3 "STRUCTURAL WELDING
CODE - SHEET STEEL". FIELD WELDS MUST BE WIRE BRUSHED AND PRIMED
PAINTED IN ACCORDANCE WITH THE SPECIFICATIONS.
DECK OPENINGS MEASURING GREATER THAN 12" ON ANY SIDE MUST HAVE
SUPPORTS ON ALL SIDES OF OPENING. SUPPORTS MUST SPAN BETWEEN
ADJACENT BEAMS OR JOISTS ON TWO SIDES. UNLESS OTHERWISE NOTED OR
DETAILED ON THE DRAWINGS, USE 5x5x5/16" ANGLES FOR SPANS EXCEEDING 6'-0" AND 3x3x1/4" ANGLES FOR SPANS LESS THAN 6'-0". COORDINATE OPENING SIZES, LOCATIONS AND DETAILS WITH ARCHITECTURAL, MECHANICAL, PLUMBING AND
ELECTRICAL DRAWINGS.
PERMANENT SUSPENDED LOADS SUCH AS SUSPENDED CEILINGS, LIGHT
FIXTURES, DUCTS, OR OTHER UTILITIES MUST NOT BE SUPPORTED BY STEEL
ROOF DECK.
DURING STEEL DECK ERECTION AND ROOFING OPERATIONS DISTRIBUTE
CONSTRUCTION LOADS TO PREVENT DAMAGE TO DECK. CONCENTRATED
CONSTRUCTION LOADS OF 200 POUNDS OR LESS DISTRIBUTED OVER A 1'-0" WIDE
SECTION OF DECK MUST NOT REQUIRE ANY FURTHER DISTRIBUTION. USE
WORKING PLATFORMS FOR CONCENTRATED CONSTRUCTION LOADS OF OVER
200 POUNDS, SUCH THAT THE RESULTING UNIFORM CONSTRUCTION LOAD ON
THE DECK DOES NOT EXCEED 50 PSF.
PREPARE AND SUBMIT SHOP DRAWINGS FOR REVIEW SHOWING THE LAYOUT AND
TYPES OF DECK UNITS, ANCHORAGE DETAILS AND CONDITIONS REQUIRING
CLOSURE STRIPS, SUPPLEMENTARY FRAMING AND OTHER ACCESSORIES.
TOUCH-UP ALL SCARRED, ABRADED AND RUST AREAS IN STEEL DECK WITH ZINC
RICH PAINT AND IN ACCORDANCE WITH THE SPECIFICATIONS.
1.
2.
3.
4.
5.
6.
7.
8.
9.
10.
11.
12.
13.
UFC 1-200-01 DoD BUILDING CODE
UFC 3-220-01 GEOTECHNICAL ENGINEERING
UFC 3-301-01 STRUCTURAL ENGINEERING
UFC 3-320-06A CONCRETE FLOOR SLABS-ON-GRADE SUBJECTED
UFC 4-010-01 DoD MINIMUM ANTITERRORISM STANDARDS FOR
A.
B.
C.
D.
E.
A.
B.
C.
D.
E.
F.
A.
B.
C.
D.
A.
SLAB-ON-GRADE 100 PSF
WAREHOUSE (UNIFORM) 150 PSF
WAREHOUSE (FORKLIFT) 4,000 LBS
ROOF 20 PSF
GROUND SNOW LOAD 10 PSF
EXPOSURE FACTOR 1.0
SNOW IMPORTANCE FACTOR 1.0
THERMAL FACTOR 1.0
FLAT ROOF SNOW LOAD 7 PSF
ULTIMATE DESIGN WIND SPEED 124 MPH
NOMINAL DESIGN WIND SPEED 96 MPH
RISK CATEGORY II
WIND EXPOSURE C
INTERNAL PRESSURE COEFFICIENT ±0.18
1.
2.
3.
4.
1.
2.
3.
4.
5.
1.
2.
3.
4.
5.
6.
1.
2.
3.
4.
5.
6.
7.
8.
9.
10.
11.
12.
13.
RISK CATEGORY II
SEISMIC IMPORTANCE FACTOR 1.0
SS 0.086g S1 0.046g
SITE CLASS E
SDS 0.136g SD1 0.107g
SEISMIC DESIGN CATEGORY B
DESIGN BASE SHEAR 8.3 KIPS
SEISMIC RESPONSE COEFFICIENT 0.04
RESPONSE MODIFICATION FACTOR 3 1/2
ANALYSIS PROCEDURE EQUIVALENT LATERAL FORCE
A.
LIVE LOAD L/360
TOTAL LOAD L/240
LATERAL LOAD H/400
1.
2.
3.
1.
2.
3.
4.
1.
2.
3.
4.
5.
6.
SLAB-ON-GRADE 3,500 PSI
CONCRETE NOT OTHERWISE NOTED 3,000 PSI
A.
B.
A.
B.
C.
1.
A.
B.
1.
2.
3.
4.
OF THE SPLICED BAR
1.
2.
3.
4.
5.
6.
7.
8.
9.
A.
B.
C.
D.
E.
1.
2.
3.
4.
5.
6.
7.
8.
A.
1.
2.
3.
4.
5.
6.
7.
8.
A.
ONE-THIRD STRESS INCREASE NOT PERMITTED FOR LOAD COMBINATIONS
INVOLVING WIND PER IBC SECTION 1605.3.1.1.
GENERAL NOTES: GENERAL NOTES (CONTINUED):
COMPONENTS AND CLADDING ULTIMATE DESIGN PRESSURES (PSF)
ROOF
ZONE
TRIBUTARY AREA (SQ. FT.)
WALL
ZONE
10 50 250
TRIBUTARY AREA (SQ. FT.)
10 50 250
+32 -43
+32 -35
+29 -36
+29 -32
+25 -29
+25 -29
+16 -85
+16 -57
+16 -51
+16 -45
+16 -65
+16 -43
+16 -34 +16 -32 +16 -26
NOTES:
PLUS AND MINUS SIGNS SIGNIFY PRESSURES ACTING TOWARD OR AWAY
FROM THE SURFACES, RESPECTIVELY.
WIDTH OF COEFFICIENT PRESSURE ZONE, a = 3.6 FEET. SEE ASCE 7 FOR
1.
2.
PRESSURE ZONE LOCATIONS.
CAST-IN-PLACE CONCRETE NOTES (CONTINUED): STEEL JOIST NOTES (CONTINUED):
FOUNDATIONS MUST BEAR ON COMPETENT EXISTING SOIL OR STRUCTURAL
FILL MATERIAL.
OF 25 PSF.
SY
M
D
ES
C R
IP
TI
O N
D
AT
E
CONCRETE MASONRY NOTES:
CONCRETE MASONRY HAS BEEN DESIGNED IN ACCORDANCE WITH THE
AMERICAN CONCRETE INSTITUTE (ACI) "BUILDING CODE REQUIREMENTS FOR
MASONRY STRUCTURES" ACI 530-13 / ASCE 5-13 / TMS 402-13.
CONCRETE MASONRY CONSTRUCTION MUST CONFORM TO THE "SPECIFICATIONS
FOR MASONRY STRUCTURES" ACI 530.1-13 / ASCE 6-13 / TMS 602-13.
CONCRETE MASONRY UNITS MUST CONFORM TO ASTM C90 AND BE MADE WITH
LIGHTWEIGHT AGGREGATE. THE COMPRESSIVE STRENGTH OF MASONRY, F'm, EXPRESSED AS FORCE PER UNIT OF NET CROSS-SECTIONAL AREA, MUST BE
2,000 PSI AT 28 DAYS.
REINFORCING STEEL MUST COMPLY WITH ASTM A615, GRADE 60. SHOP
FABRICATE REINFORCING BARS SHOWN TO BE BENT OR HOOKED.
GROUT MUST COMPLY WITH ASTM C476 OR IBC SECTION 2103.3, AND MUST BE
PROPORTIONED TO OBTAIN A 28 DAY COMPRESSIVE STRENGTH OF 2,000 PSI.
MORTAR MUST COMPLY WITH ASTM C270, TYPE S OR M. AGGREGATE FOR
MORTAR MUST COMPLY WITH ASTM C144. AGGREGATE FAILING TO COMPLY WITH
ASTM C144 GRADATION REQUIREMENTS MAY BE USED PROVIDED THE MORTAR
CAN BE PREPARED TO COMPLY WITH THE AGGREGATE RATIO, WATER
RETENTION AND COMPRESSIVE STRENGTH REQUIREMENTS OF THE PROPERTY
SPECIFICATIONS OF ASTM C270. USE TYPE M BELOW GRADE AND TYPE S ABOVE
GRADE (UNLESS CELLS ARE GROUTED SOLID).
VERTICAL REINFORCING BARS MUST BE THE GIVEN SIZE AND SPACING SHOWN.
LAP REINFORCING AT ALL SPLICES AS FOLLOWS:
#4 - 25" #5 - 31"
REBAR DOWELS MUST BE THE SAME SIZE AND SPACING AS VERTICAL
REINFORCING FROM FOUNDATION. DOWELS MUST HAVE STANDARD ACI HOOKS.
DISCONTINUE ALL HORIZONTAL REINFORCING AT CONTROL JOINTS EXCEPT FOR
THE BOND BEAMS AT JOIST BEARING ELEVATIONS. HORIZONTAL BOND BEAMS
MUST HAVE CONTINUOUS REINFORCING AS SHOWN IN THE SECTIONS AND
DETAILS.
HORIZONTAL JOINT REINFORCING MUST BE STANDARD 9 GAGE LADDER TYPE IN
CMU WALLS AT 16" ON-CENTER. JOINT REINFORCING MUST COMPLY WITH ASTM
A951 AND MUST BE HOT-DIPPED GALVANIZED ACCORDING TO ASTM A153, CLASS B.
GROUT ALL CELLS SOLID BELOW FINISHED FIRST FLOOR.
VERTICAL REINFORCING MUST HAVE BAR POSITIONERS AT SPACING NOT TO
EXCEED 200 BAR DIAMETERS, AT GROUT LIFT HEIGHTS OR BAR SPLICE
LOCATIONS, WHICHEVER IS LESS.
1.
2.
3.
4.
5.
6.
7.
8.
9.
10.
11.
12.
A.
B.
COLD-FORMED METAL FRAMING NOTES:
COLD-FORMED METAL FRAMING HAS BEEN DESIGNED IN ACCORDANCE WITH THE
AMERICAN IRON AND STEEL INSTITUTE (AISI) "COLD-FORMED STEEL DESIGN
MANUAL".
COLD-FORMED METAL FRAMING MEMBERS MUST BE FORMED OF CORROSION-
RESISTANT STEEL CONFORMING TO ASTM A653 WITH A MINIMUM YIELD
STRENGTH OF 33 KSI FOR TRACKS AND RUNNERS AND 50 KSI FOR 54 MILS AND
HEAVIER FOR ALL OTHER MEMBERS.
COLD-FORMED METAL FRAMING MEMBER SIZES AND GAGES INDICATED ARE IN
ACCORDANCE WITH THE STEEL STUD MANUFACTURERS ASSOCIATION (SSMA)
NOMENCLATURE.
1.
2.
3.
SATISFACTORY TO DATE
APPROVED
ACTIVITY
FOR COMMANDER NAVFAC
SEAL
A/E INFO
A
B
C
D
1 2 3 4 5
1 2 3 4 5
A
B
C
D
SCALE:
CONSTR. CONTR. NO.
SHEET
NAVFAC DRAWING NO.
DES DRW CHK
OF
EPROJECT NO.:
D E
P A
R T
M E
N T
O F
T H
E N
A V
Y N
A V
A L
F A
C
IL
IT
IE
S E
N G
IN
E
E R
IN
G
C O
M M
A N
D
DRAWFORM REVISION: 7 FEBRUARY 2019
PM/DM
BRANCH MANAGER
CHIEF ENG/ARCH
FIRE PROTECTION
N A
V A
L F
A C
IL
IT
IE
S
E N
G
IN
E E
R
IN
G C
O M
M A
N D
M
ID
A
T L A
N T
IC
N
A V
A L
S T
A T
IO
N
N
O R
F O
L K
, V A
AS NOTED
UNCLASSIFIED
UNCLASSIFIED
U N
C
LA
S S
IF
IE
D
S-002
P -Q
S
O F
P H
Y S
IC
A
L S
E C
U R
IT
Y
S
TR
U C
T U
R A
L N
O
TE
S A
N D
A B
B R
E V
IA
T
IO
N
S
DWS
12801985
EHI FCS
10/06/2020
APPROVED BY JOHN TAYLOR WITH
HSWDG, VIA EMAIL
B U
IL
D
IN
G
A D
D
IT
IO
N
JB/JH
1387235
VI
R
G
IN
IA
B
EA
C
H , V
IR
G
IN
IA
N
AS
O C
EA
N
A D
AM
N
EC
K
AN
N
EX
M
ID
LA
N
T C
I C
O R
E
EJA
DJD
DSN
STRUCTURAL ABBREVIATION LIST:
WITH
PLUS/MINUS
CENTERLINE
ON CENTER
ANCHOR BOLT
ARCHITECT or ARCHITECTURAL
BOTTOM
BAR DIAMETER
BUILDING
BEAM
BRACING
BRIDGING
CENTER OF GRAVITY
CAST IN PLACE
CLEAR
CONCRETE MASONRY UNIT
COLUMN
CONCRETE
CONTINUOUS
COORDINATE
DETAIL
DIAMETER
DRAWING
EACH FACE
EACH WAY
EACH
ELEVATION
ELECTRICAL
ELEVATOR or ELEVATION
EXISTING
EXPANSION
FACE OF
FIRST RISER
FINISH or FINISHED
FLOOR
FOOTING
HOLLOW CORE
HOOK
HORIZONTAL
JOIST BEARING ELEVATION
JOINT
KIPS
KIPS PER SQUARE FOOT
KIPS PER SQUARE INCH
LONG
LONG LEG HORIZONTAL
LONG LEG OUTSTANDING
MIDDLE OF SLAB
MIDDLE OF WALL
MANUFACTURER or
MATERIAL
MECHANICAL
METAL
PRECAST
PRE-STRESSED
POUNDS PER SQUARE FOOT
POUNDS PER SQUARE INCH
PLUMBING
RADIUS
REINFORCED or REINFORCING
REQUIRED
SLAB ON GRADE
STEPPED FOOTING
SECTION
SHEET
STANDARD
STIRRUP
STEEL
STRUCTURAL
TOP
TOP OF STEEL
TEMPERATURE
TYPICAL
UNLESS OTHERWISE NOTED
VERTICAL
WORKING POINT
WELDED WIRE FABRIC
CMU
ELEV.
J.B.E.
K.S.F.
K.S.I.
MANUF.
PSF
PSI
REINF.
U.O.N.
VERT.
W.P.
W.W.F.
S.O.G.
S.F.
SECT.
SHT.
STD.
STIR.
STL.
STRUCT.
T.
T.O.S.
TEMP.
TYP.
M.O.S.
M.O.W.
MATL.
MECH.
MTL.
P.C.
P.S.
PLUMB.
R.
REQD.
FLR.
FTG.
H.C.
HK.
HORIZ.
JT.
K
LG.
LLH
LLO
DET.
DIA.
DWG.
E.F.
E.W.
EA.
EL.
ELEC.
EXIST.
EXP.
F.O.
F.R.
FIN.
B.
B.D.
BLDG.
BM.
BRCG.
BRDG.
C.G.
C.I.P.
CLR.
COL.
CONC.
CONT.
COORD.
w/ o/c
A.B.
ARCH.
MANUFACTURER'S
ACI
ASTM
AMERICAN CONCRETE INSTITUTE
AMERICAN SOCIETY FOR
TESTING AND MATERIALS
CANT. CANTILEVER
Pc PIECE
SCHED. SCHEDULE
GALV.
GD.
GALVANIZED
GRADE
DWL. DOWEL
ENG. ENGINEER
AISC AMERICAN INSTITUTE OF
STEEL CONSTRUCTION
BTWN. BETWEEN
SIM. SIMILAR
SL. SLOPE
MAX.
MIN.
MAXIMUM
MINIMUM
N.T.S.
OPP.
NOT TO SCALE
OPPOSITE
D.
DBL.
DIAG.
DEEP or DEPTH
DOUBLE
DIAGONAL
EMB. EMBED or EMBEDMENT
W. WIDE or WIDTH
STIFF. STIFFENER
REF. REFERENCE
PROJ. PROJECTION
EQ. EQUAL
SPA. SPACE
B.E.J. BUILDING EXPANSION JOINT
G.C. GENERAL CONTRACTOR
F.L. FULL LENGTH
ga GAGE
ADJ. ADJACENT
BRG. BEARING
REVISIONREV.
C.J.P. COMPLETE JOINT PENETRATION
LSH
LSV
LONG SIDE HORIZONTAL
LONG SIDE VERTICAL
EQUIV. EQUIVALENT
LONG LEG VERTICALLLV
SHORT LEG OUTSTANDINGSLO
POWDER ACTUATED FASTENERPAF
STEEL JOIST INSTITUTES.J.I.
PRE-ENGINEERED BUILDINGP.E.B.
S.D.I. STEEL DECK INSTITUTEE.O. EDGE OF
CONN. CONNECT or CONNECTION
P.T. PRESSURE TREATED
MASONRYMAS.
STRUCTURAL STEEL
ARCHITECTURALLY EXPOSEDAESS
SEISMIC EXPANSION JOINTS.E.J.
A.R. ANCHOR ROD
DECK ASSEMBLY
SLOPED INTEGRAL ROOFS.I.R.D.A.
POST-TENSIONEDP/T
CL
INSULATED CONCRETE FORMICF
SPEIGHT MARSHALL FRANCIS. .
STRUCTURAL ENGINEERS
SM&F Job No:WWW.SMANDF.COM
1228 PERIMETER PARKWAY, SUITE 201
P: 757.427.1020
VIRGINIA BEACH, VIRGINIA 23454
P: 804.464.4111
RICHMOND, VIRGINIA 23294
2821 EMORYWOOD PARKWAY SUITE 300
18.015-J
SY
M
D
ES
C R
IP
TI
O N
D
AT
E x1 x2 x3 x4 x5 x5x3.1 xA xB xC xD
A.1
3.2 6
4.1
AA
BB
F
'-2
/4
7'
-6
9' -1
0"
'-2
/8
'-3
/8
5.1
E
34'-0" 8'-3 3/4"
13'-0 3/4" F.O. BLDG.
AT FOUNDATION
4' -8
1'
-7
10"±
F.O. BLDG. F.O. BLDG.
AT FOUNDATION
'-4
/8
F.O. BLDG.
1'-3 3/4"± 23'-5 3/4"
11'-6"
6' -7
/8
3/
4"
'-0
/4
7'-4 7/8"± 3'-5 1/2"±
'-7
'-3
/4
5' -1
/4
2'
-2
'-0
/2
1'
-6
2' -5
'-1
1/ 2"
2' -5
1'-6"± 18'-7"±1'-7"± 23'-7"± 25'-0"±
11 1/4"±
7'-6 3/4"± 15'-6"± 1'-0 1/4"
1" B
.E .J
1" B
.E .J
1" B.E.J.
1" B.E.J.
1" B
.E .J
2'-0"
ARCH. DWGS.
SEE THE
SE
E
TH
E
AR
C
H . D
W G
S.
SATISFACTORY TO DATE
APPROVED
ACTIVITY
FOR COMMANDER NAVFAC
SEAL
A/E INFO
A
B
C
D
1 2 3 4 5
1 2 3 4 5
A
B
C
D
SCALE:
CONSTR. CONTR. NO.
SHEET
NAVFAC DRAWING NO.
DES DRW CHK
OF
EPROJECT NO.:
D E
P A
R T
M E
N T
O F
T H
E N
A V
Y N
A V
A L
F A
C
IL
IT
IE
S E
N G
IN
E
E R
IN
G
C O
M M
A N
D
DRAWFORM REVISION: 7 FEBRUARY 2019
PM/DM
BRANCH MANAGER
CHIEF ENG/ARCH
FIRE PROTECTION
N A
V A
L F
A C
IL
IT
IE
S
E N
G
IN
E E
R
IN
G C
O M
M A
N D
M
ID
A
T L A
N T
IC
N
A V
A L
S T
A T
IO
N
N
O R
F O
L K
, V A
AS NOTED
UNCLASSIFIED
UNCLASSIFIED
U N
C
LA
S S
IF
IE
D
S-100
P -Q
S
O F
P H
Y S
IC
A
L S
E C
U R
IT
Y
D
IM
E N
S
IO
N P
LA
N
DWS
12801986
EHI FCS
10/06/2020
APPROVED BY JOHN TAYLOR WITH
HSWDG, VIA EMAIL
B U
IL
D
IN
G
A D
D
IT
IO
N
JB/JH
1387235
VI
R
G
IN
IA
B
EA
C
H , V
IR
G
IN
IA
N
AS
O C
EA
N
A D
AM
N
EC
K
AN
N
EX
M
ID
LA
N
T C
I C
O R
E
EJA
DJD
DSN
NORTH 1/8" = 1'-0" (FOR PLAN NOTES AND LEGEND SEE SHEET S-101)
DIMENSION PLAN
THE INFORMATION REGARDING THE EXISTING CONSTRUCTION WAS OBTAINED FROM
THE RECORD DRAWINGS PREPARED BY NAVY PUBLIC WORKS CENTER DATED
NOVEMBER 8TH, 2000 AND BY FIELD INVESTIGATION. ALL INFORMATION SPECIFYING
EXISTING CONDITIONS MUST BE VERIFIED BY THE GENERAL CONTRACTOR. THE
AFOREMENTIONED DRAWINGS WILL BE MADE AVAILABLE TO THE CONTRACTOR UPON
REQUEST.
SPEIGHT MARSHALL FRANCIS. .
STRUCTURAL ENGINEERS
SM&F Job No:WWW.SMANDF.COM
1228 PERIMETER PARKWAY, SUITE 201
P: 757.427.1020
VIRGINIA BEACH, VIRGINIA 23454
P: 804.464.4111
RICHMOND, VIRGINIA 23294
2821 EMORYWOOD PARKWAY SUITE 300
18.015-J
SPEIGHT MARSHALL FRANCIS. .
STRUCTURAL ENGINEERS
SM&F Job No:WWW.SMANDF.COM
1228 PERIMETER PARKWAY, SUITE 201
P: 757.427.1020
VIRGINIA BEACH, VIRGINIA 23454
P: 804.464.4111
RICHMOND, VIRGINIA 23294
2821 EMORYWOOD PARKWAY SUITE 300
18.015-J
1/8" = 1' - 0" 0 5' 10' 15' 30'
1/8" = 1' - 0" 0 5' 10' 15' 30'
GRAPHIC SCALE:
SY
M
D
ES
C R
IP
TI
O N
D
AT
E x1 x2 x3 x4 x5x3.1 xA xB xC xD
(E) WF2.0
(E) WF2.0
CF5.0
A.1
3.2 6
HSS4x4x1/4
CBP-1 HSS6x6x1/4
CBP-1
HSS3x3x1/4 (G
ALV.)
CBP-1
HSS4x4x1/4
CBP-1
4.1
WF2.5 (TYP. U.O.N.)
WF3.0
WF3.0
AA
BB
F
(E ) P
EB C
OLU
MN
(TYP.)
DCJ DCJ DCJ
DCJDCJDCJDCJ
DCJ
D C
J
D C
J
D C
J D
C J
D C
J
D C
J D
C J
D C
J
D C
J
CJ OR KCJ
(TYP.)
F2
F1
F2
F1
F1F1
C1 S-301
C3 S-301
C3 S-301
A1 S-301
A2 S-301
C4 S-301
F3
SF
F7 SF
F7
F8
F7
SF
F5
C1 S-301
F7
F7
SF
1" B
.E .J
1" B
.E .J
WF3.0
W F
.0
HSS3x3x1/4 (G
ALV.)
CBP-1
HSS3x3x1/4 (GALV.)CBP-1
5.1
SF
2'
-0
2'
-8
( -2'-8" )
( -3'-0" )
F8
F8
F8
F8 SF
WF3.0
CF5.0 CF5.0
SF
SF
SF
SF
2'
-0
2'
-8
3'
-4
( -2'-0" )
( -2'-8" )
( -4'-0" )
( -2'-0" )
(E) CF6.0
( -3'-0" ±)
(E) CF6.0
(E) CF6.0
(E) CF6.0
(E) CF6.0
( -3'-0" ±)
(E) CF6.0
3'-
4"
3'
-4
E
(E) WF3.0A
3'
-1 0"
3'
-0
( -3'-10" ±)
( -5'-6" ±)
-5
'-6
( -5 '-6" )
3'
-4
(E) CF6.0 (E) CF6.0
(E) CF9.0
(E) CF6.0
(E) CF6.0(E) CF6.0
(E) CF10.0
(E) CF10.0
(E) WF3.0
(E) WF3.0
(E ) W
F3 .0
(E ) W
F3 .0
(E ) W
F3 .0
(E) WF3.0 (E) WF3.0A
(E ) W
F3 .0
A
(E) WF3.0A
(E ) W
F3 .0
A (E
) W F3
.0 A
(E) CF9.0
WF3.0
W F
.0
( -3'-0" ±)
A3 S-301
C2 S-302
C1 S-302
F9
W F
.0
( -3 '-4" )
W F
.0
( -3'-4" )
2'
-0
W F2
.0
F8
WF2.0
F10 F11
F12
(TYP.)
F7
F13
F7
WF3.0
( -3'-0" ±)
( -5'-6" ±)
F1
(E) SF
(E) SF
W
F .0
(E) SF
F1
F14 F15 F1
A4 S-301
A3
S-301
F14
KC
J
KC
J
(E) WF3.0
1" B.E.J.
1" B.E.J.
0" B.E.J.
F1
SIM. TO
GENERAL FOUNDATION PLAN NOTES :
A. SEE THE CIVIL DRAWINGS FOR ACTUAL FINISHED FLOOR ELEVATION TOP OF
SLAB EQUALS FINISHED FLOOR ELEVATION AND MUST SERVE AS THE
REFERENCE ELEVATION 0'-0".
B. FOR THE STRUCTURAL NOTES AND ABBREVIATIONS SEE SHEETS S-001 AND
S-002.
C. SEE THE DIMENSION PLAN ON SHEET S-100 AND THE ARCHITECTURAL
DRAWINGS FOR DIMENSIONS NOT SHOWN. SEE THE ARCHITECTURAL
DRAWINGS FOR LOCATIONS OF MASONRY CONTROL JOINTS.
FOUNDATION WALL
EQUAL (U.O.N.)EQUAL (U.O.N.)
'D
'W'
CONTINUOUS
BOTTOM
REINFORCING
FOOTING TIES
WALL FOOTING DIAGRAM
FOUNDATION PLAN LEGEND :
KCJ = SLAB-ON-GRADE KEYED CONSTRUCTION
JOINT - SEE TYPICAL DETAIL ON SHEET S-501
CJ = SLAB-ON-GRADE CONTROL JOINT - SEE
TYPICAL DETAIL ON SHEET S-501
DCJ = SLAB-ON-GRADE DOWELED CONSTRUCTION
JOINT - SEE TYPICAL DETAIL ON SHEET S-501
= INDICATES SLAB-ON-GRADE JOINT (CONTROL
JOINT UNLESS OTHERWISE REQUIRED)
= INDICATES TOP OF SLAB ELEVATION -
MEASURED FROM REFERENCE ELEVATION 0'-0"
-XX"
= INDICATES EXTENT OF SLAB SLOPE - SEE
ARCH. DWGS. FOR EXACT LOCATION
WFX.X = WALL FOOTING MARK - SEE SCHEDULE ON THIS
SHEET
CFX.X = COLUMN FOOTING MARK - SEE SCHEDULE ON
THIS SHEET
SF = STEPPED FOOTING - SEE TYPICAL DETAIL ON
SHEET S-501
(-X'-X")
= TOP OF FOOTING ELEVATION - MEASURED FROM
REFERENCE ELEVATION 0'-0"
X = COLUMN GRID MARK
± = APPROXIMATE DIMENSION OR ELEVATION
(FIELD VERIFY)
(E) SF = EXISTING STEP FOOTING
± = EXISTING DIMENSION OR ELEVATION
(FIELD VERIFY)
= SANITARY SEWER OR STORM WATER PIPING
BELOW SLAB - COORDINATE WITH THE
PLUMBING DRAWINGS (PIPING PARTIALLY
SHOWN) SEE THE PLUMBING DRAWINGS FOR
ADDITIONAL PIPING NOT SHOWN
= COLUMN AND COLUMN BASE PLATE MARK - SEE
COLUMN BASE PLATE DETAIL ON SHEET S-501
COLUMN SIZE
CBP-X
(E) WFX.X = EXISTING WALL FOOTING MARK - SEE SCHEDULE
ON THIS SHEET
(E) CFX.X = EXISTING COLUMN FOOTING MARK - SEE
SCHEDULE ON THIS SHEET
(E) SF = EXISTING STEPPED FOOTING
(-X'-X")
= EXISTING TOP OF FOOTING ELEVATION - MEASURED
FROM REFERENCE ELEVATION 0'-0"
X = EXISTING COLUMN GRID MARK
(E) = EXISTING
F# = FOUNDATION KEY NOTES MARK
SATISFACTORY TO DATE
APPROVED
ACTIVITY
FOR COMMANDER NAVFAC
SEAL
A/E INFO
A
B
C
D
1 2 3 4 5
1 2 3 4 5
A
B
C
D
SCALE:
CONSTR. CONTR. NO.
SHEET
NAVFAC DRAWING NO.
DES DRW CHK
OF
EPROJECT NO.:
D E
P A
R T
M E
N T
O F
T H
E N
A V
Y N
A V
A L
F A
C
IL
IT
IE
S E
N G
IN
E
E R
IN
G
C O
M M
A N
D
DRAWFORM REVISION: 7 FEBRUARY 2019
PM/DM
BRANCH MANAGER
CHIEF ENG/ARCH
FIRE PROTECTION
N A
V A
L F
A C
IL
IT
IE
S
E N
G
IN
E E
R
IN
G C
O M
M A
N D
M
ID
A
T L A
N T
IC
N
A V
A L
S T
A T
IO
N
N
O R
F O
L K
, V A
AS NOTED
UNCLASSIFIED
UNCLASSIFIED
U N
C
LA
S S
IF
IE
D
S-101
P -Q
S
O F
P H
Y S
IC
A
L S
E C
U R
IT
Y
F O
U N
D A
T
IO
N P
LA
N
DWS
12801987
EHI FCS
10/06/2020
APPROVED BY JOHN TAYLOR WITH
HSWDG, VIA EMAIL
B U
IL
D
IN
G
A D
D
IT
IO
N
JB/JH
1387235
VI
R
G
IN
IA
B
EA
C
H , V
IR
G
IN
IA
N
AS
O C
EA
N
A D
AM
N
EC
K
AN
N
EX
M
ID
LA
N
T C
I C
O R
E
EJA
DJD
DSN
NORTH 1/8" = 1'-0"
FOUNDATION PLAN
FOUNDATION KEYNOTES
F1 FIRST FLOOR MUST BE AN 4" THICK FIBRILLATED SYNTHETIC FIBER REINFORCED
CONCRETE SLAB-ON-GRADE, OVER 15 MIL. VAPOR RETARDER MINIMUM, OVER 10"
MINIMUM AND 12" MAXIMUM DEPTH OF POROUS FILL. FIBER DOSAGE RATE MUST
BE 1 1/2 POUNDS PER CUBIC YARD. FILL BELOW POROUS FILL MUST BE
EXPANDED POLYSTYRENE FOAM MATERIAL (EPS).
F2 FIRST FLOOR MUST BE AN 8" THICK CONCRETE SLAB-ON-GRADE, REINFORCED
WITH #4 AT 12" ON-CENTER EACH WAY, OVER 15 MIL. VAPOR RETARDER MINIMUM,
OVER 4" DEPTH OF POROUS FILL.
F3 TOP OF ALL FOOTINGS MUST BE 3'-4" BELOW REFERENCE ELEVATION 0'-0",
UNLESS OTHERWISE NOTED.
F4 WALL FOOTINGS MUST BE CENTERED ON TOTAL WIDTH OF THE FOUNDATION
WALL, UNLESS OTHERWISE NOTED.
F5 COLUMNS AND COLUMN FOOTINGS MUST BE CENTERED ON GRIDS IN BOTH
DIRECTIONS, UNLESS OTHERWISE NOTED.
F6 STEP FOOTING FOR PIPING TO RUN ABOVE TOP OF FOOTING. ALL UNDERGROUND
PIPES ARE NOT SHOWN ON PLAN. FOR PIPE INVERT ELEVATIONS AND
LOCATIONS, SEE WITH THE PLUMBING AND CIVIL DRAWINGS.
F7 STEP FOOTING TO MATCH EXISTING FOOTING ELEVATION. SEE 'TYPICAL DETAIL
AT INTERSECTION OF NEW AND EXISTING FOOTINGS' ON SHEET S-501.
F8 SEE THE ARCHITECTURAL DRAWINGS FOR MASONRY WALL DEMOLITION. EXTEND
WALL DEMOLITION APPROXIMATELY 8" BELOW EXISTING FLOOR AT DOOR
OPENINGS AND FILL SOLID WITH CONCRETE FROM TOP OF REMAINING WALL TO
TOP OF EXISTING SLAB. REINFORCE CONCRETE AND ANCHOR TO WALL AS
INDICATED IN SECTION A4/S-301.
F9 REINFORCE JAMB BETWEEN OPENINGS WITH 2 - #5 VERTICAL BARS (ONE BAR IN
EACH CELL).
F10 EXISTING 8"+/- THICK CONCRETE SLAB REINFORCED WITH #4 AT 12"± CENTER
EACH WAY.
F11 EXISTING 6"+/- THICK CONCRETE SLAB REINFORCED WITH WELDED WIRE
REINFORCEMENT.
F12 REMOVE AND REPLACE EXISTING CONCRETE SLAB. SLAB REMOVAL IS
SCHEMATICALLY SHOWN AND MUST BE COORDINATED WITH INSTALLATION OF
NEW UTILITIES. REFER TO 'TYPICAL DETAIL OF REMOVAL AND REPAIR OF
EXISTING SLAB-ON-GRADE' ON SHEET S-511.
F13 EXISTING CONCRETE STAIR AND LANDING.
F14 8" CMU WALL WITH #5 AT 8" ON-CENTER VERTICAL WALL REINFORCEMENT. DRILL
AND EPOXY INTO EXISTING FOOTING WITH 5" EMBEDMENT.
F15 2'-0" LONG 8" CMU FOUNDATION WALL.
WALL FOOTING SCHEDULE
MARK WIDTH 'W' DEPTH 'D'
REINFORCING
COMMENTS
CONTINUOUS TIES
WF2.0 2'-0" 1'-0" 3 - #4 #4 AT 4'-0"o/c WF2.5 2'-6" 1'-0" 4 - #4 #4 AT 4'-0"o/c WF3.0 3'-0" 1'-0" 4 - #4 #4 AT 4'-0"o/c
THE INFORMATION REGARDING THE EXISTING CONSTRUCTION WAS OBTAINED FROM
THE RECORD DRAWINGS PREPARED BY NAVY PUBLIC WORKS CENTER DATED
NOVEMBER 8TH, 2000 AND BY FIELD INVESTIGATION. ALL INFORMATION SPECIFYING
EXISTING CONDITIONS MUST BE VERIFIED BY THE GENERAL CONTRACTOR. THE
AFOREMENTIONED DRAWINGS WILL BE MADE AVAILABLE TO THE CONTRACTOR UPON
REQUEST.
COLUMN FOOTING SCHEDULE
MARK
DIMENSIONS REINFORCING
(BOTTOM) COMMENTS
WIDTH LENGTH DEPTH
CF5.0 5' - 0" 5' - 0" 1' - 0" 7 - #4 EACH WAY
F#
EXISTING WALL FOOTING SCHEDULE
MARK WIDTH DEPTH COMMENTS
(E) WF2.0± 2'-0" 1'-0"
(E) WF3.0A± 3'-0" 2'-0"
(E) WF3.0± 3'-0" 1'-0"
EXISTING COLUMN FOOTING SCHEDULE
MARK
DIMENSIONS
COMMENTS
WIDTH LENGTH DEPTH
(E) CF6.0± 6' - 0" 6' - 0" 2' - 0"
(E) CF9.0± 9' - 0" 9' - 0" 2' - 0"
(E) CF10.0± 10' - 0" 10' - 0" 2' - 0"
SPEIGHT MARSHALL FRANCIS. .
STRUCTURAL ENGINEERS
SM&F Job No:WWW.SMANDF.COM
1228 PERIMETER PARKWAY, SUITE 201
P: 757.427.1020
VIRGINIA BEACH, VIRGINIA 23454
P: 804.464.4111
RICHMOND, VIRGINIA 23294
2821 EMORYWOOD PARKWAY SUITE 300
18.015-J
1/8" = 1' - 0" 0 5' 10' 15' 30'
GRAPHIC SCALE:
SY
M
D
ES
C R
IP
TI
O N
D
AT
E x1 x2 x3 x4 x5x3.1 xA xB xC xD
A.1
3.2 6
W18x35
W16x26 W16x26
4.1
L-
1/ 4"
AA
BB
(E) ROOF EAVE (TYP.)
(E ) P
EB
G
IR
D
ER
(E) ROOF RIDGE
(E) 9"± Z - PURLIN (E) 9"± Z - PURLIN
(E) 9"± Z - PURLIN (E) 9"± Z - PURLIN
(E) 9"± Z - PURLIN
(E ) P
EB
G
IR
D
ER
(E ) P
EB
G
IR
D
ER
(E ) P
EB
G
IR
D
ER
(E ) P
EB
G
IR
D
ER
F
ROOF EAVE
(TYP. U.O.N.)
W x2
C2 S-311
C1 S-311
C3 S-311
5.1
W 6x
'-1
1"
W6
W6
W x5
10K1
10K1
10K1
10K1
10K1
10K1
10K1
10K1
C2 S-311
C1 S-311
SIM TO
C1 S-311
HSS3
HSS3
W 6 W
W
W
W6
W6
W6
W6
C6x8.2
C6x8.2
W6
OPEN
C4 S-311
B2 S-311
B3 S-311
B1 S-311
B4 S-311
A2 S-311
A3 S-311
C6x8.2
C 6x
8.
W6
W6
W6
W6
W6
A1 S-311
W
W
C1 S-312
C6x8.2
C2 S-312
A1 S-312
E
+12ʻ-4"
5'-6"
+13ʻ-8 3/8"
+13ʻ-5 1/2"
+12ʻ-4"
BP-2
BP-2
+1 8ʻ
-9
/2
+1 9ʻ
-2
/8
K4
L-
L-3
L-
L-3
L-3
B1 S-312
C6x8.2
K4
K4
K4
K4
K4
K4
K4
K4
K4
1" B.E.J.
B.E.J.
3/4"
1" B
.E .J
1" B
.E .J
B4 S-312
B2 S-312
K4
K4
K4
K4
K4
K4
HSS8 HSS8
C6x8.2
W
W
FRAMING PLAN LEGEND :
= JOIST BEARING ELEVATION (J.B.E) - MEASURED
FROM REFERENCE ELEVATION 0'-0"
+XX'-XX"
= TOP OF STEEL (T.O.S.) ELEVATION - MEASURED
FROM REFERENCE ELEVATION 0'-0"
(HI = HIGH; LO = LOW; SL = SLOPE)
= CANTILEVERED BEAM CONNECTION - SEE
TYPICAL DETAIL ON SHEET S-512
X = COLUMN GRID MARK
± = APPROXIMATE DIMENSION OR ELEVATION
(FIELD VERIFY)
(E) = EXISTING
± = EXISTING DIMENSION OR ELEVATION
(FIELD VERIFY)
L-X = LINTEL MARK - SEE DETAILS ON SHEET S-512
BP-X = BEAM BEARING PLATE MARK - SEE
SCHEDULE AND TYPICAL DETAILS ON
SHEET S-511 (BP-1 TYP. U.O.N.)
(+XX'-XX")
= WORKING POINT
= ROOF RIDGE, HIP OR VALLEY LINE - SEE THE
ARCHITECTURAL DRAWINGS
= CHANGE IN ROOF ELEVATION - SEE THE
ARCHITECTURAL DRAWINGS
X = EXISTING COLUMN GRID MARK
W6 = W6x9
HSS3 = GALVANIZED HSS3x3x1/4
HSS8 = HSS8x6x3/8 (LLH)
GENERAL ROOF FRAMING PLAN NOTES :
A. SEE THE DIMENSION PLAN ON SHEET S-100 AND THE ARCHITECTURAL
DRAWINGS FOR DIMENSIONS NOT SHOWN. SEE THE ARCHITECTURAL
DRAWINGS FOR LOCATIONS OF MASONRY CONTROL JOINTS.
B. FOR THE STRUCTURAL NOTES AND ABBREVIATIONS SEE SHEETS S-001 AND
S-002.
C. FOR JOIST BEARING ELEVATIONS NOT SHOWN ON PLAN INTERPOLATE
LINEARLY BETWEEN GIVEN ELEVATIONS.
SATISFACTORY TO DATE
APPROVED
ACTIVITY
FOR COMMANDER NAVFAC
SEAL
A/E INFO
A
B
C
D
1 2 3 4 5
1 2 3 4 5
A
B
C
D
SCALE:
CONSTR. CONTR. NO.
SHEET
NAVFAC DRAWING NO.
DES DRW CHK
OF
EPROJECT NO.:
D E
P A
R T
M E
N T
O F
T H
E N
A V
Y N
A V
A L
F A
C
IL
IT
IE
S E
N G
IN
E
E R
IN
G
C O
M M
A N
D
DRAWFORM REVISION: 7 FEBRUARY 2019
PM/DM
BRANCH MANAGER
CHIEF ENG/ARCH
FIRE PROTECTION
N A
V A
L F
A C
IL
IT
IE
S
E N
G
IN
E E
R
IN
G C
O M
M A
N D
M
ID
A
T L A
N T
IC
N
A V
A L
S T
A T
IO
N
N
O R
F O
L K
, V A
AS NOTED
UNCLASSIFIED
UNCLASSIFIED
U N
C
LA
S S
IF
IE
D
S-111
P -Q
S
O F
P H
Y S
IC
A
L S
E C
U R
IT
Y
R O
O F
F R
A M
IN
G
P
LA
N
DWS
12801988
EHI FCS
10/06/2020
APPROVED BY JOHN TAYLOR WITH
HSWDG, VIA EMAIL
B U
IL
D
IN
G
A D
D
IT
IO
N
JB/JH
1387235
VI
R
G
IN
IA
B
EA
C
H , V
IR
G
IN
IA
N
AS
O C
EA
N
A D
AM
N
EC
K
AN
N
EX
M
ID
LA
N
T C
I C
O R
E
EJA
DJD
DSN
NORTH 1/8" = 1'-0"
ROOF FRAMING PLAN
ROOF FRAMING KEYNOTES
01 ROOF JOISTS AND OTHER ROOF DECK SUPPORTS MUST BE SPACED EQUALLY
BETWEEN GIVEN LOCATIONS, WITH A MAXIMUM SPACING OF 5'-0" ON-CENTER,
UNLESS OTHERWISE NOTED.
02 MASONRY WALL OPENING BELOW - SEE THE ARCHITECTURAL DRAWINGS FOR
SIZE AND LOCATION. SEE 'TYPICAL BOND BEAM LINTEL DETAILS' ON SHEET
S-511 FOR BOND BEAM REQUIREMENTS.
03 HSS 6x6x3/8 SHIM BETWEEN HIGH AND LOW BEAM.
04 CONNECT CHANNEL TO CMU WALL AS DETAILED IN SECTION A1/S-312
THE INFORMATION REGARDING THE EXISTING CONSTRUCTION WAS OBTAINED FROM
THE RECORD DRAWINGS PREPARED BY NAVY PUBLIC WORKS CENTER DATED
NOVEMBER 8TH, 2000 AND BY FIELD INVESTIGATION. ALL INFORMATION SPECIFYING
EXISTING CONDITIONS MUST BE VERIFIED BY THE GENERAL CONTRACTOR. THE
AFOREMENTIONED DRAWINGS WILL BE MADE AVAILABLE TO THE CONTRACTOR UPON
REQUEST.
SPEIGHT MARSHALL FRANCIS. .
STRUCTURAL ENGINEERS
SM&F Job No:WWW.SMANDF.COM
1228 PERIMETER PARKWAY, SUITE 201
P: 757.427.1020
VIRGINIA BEACH, VIRGINIA 23454
P: 804.464.4111
RICHMOND, VIRGINIA 23294
2821 EMORYWOOD PARKWAY SUITE 300
18.015-J
1/8" = 1' - 0" 0 5' 10' 15' 30'
GRAPHIC SCALE:
SY
M
D
ES
C R
IP
TI
O N
D
AT
E
8"
C1 S-301
SECTION
3/4" = 1'-0"
AT WINDOWS
8" CMU - GROUT SOLID
TOP OF…