TJ_FY23_DS_MCT P2 Repairs.xlsx

XLSX spreadsheet 32 KB Posted

Attached to
Drawings/References for the THOMAS JEFFERSON Dockside Repairs FY23
Solicitation number
1305M222QNMAN0068
Issued by

View the file

Other files

File Type Posted
SNAME Technical and Research Bulletin 4-16_Calculations for Merchant Ship HVAC Design (2015).pdf PDF
NOAA Thomas Jefferson Ships Registry TTS.pdf PDF
NOAA Thomas Jefferson Procedure 1701-09 TJ - Hot Work Operations.pdf PDF
TJ_FY23_DS_Gauge Meter Inventory (Updated 20220601).pdf PDF
MOC-573-2 Overhaul Repair of Hydraulic Cylinders.pdf PDF
Register of Lifting Appliances_fillable.pdf PDF
NAVSEA Standard Item 009-32_Cleaning and Painting Requirements.pdf PDF
Calculations for Merchant Ship HVAC Design (2015).pdf PDF
320-6634679_E Cableway Arrangement and Details - AS BUILT(1).pdf PDF
Document locations.pdf PDF
TJ-152-002B Deck Extension Structure _ Grating Replacement_131148294.pdf PDF
301-001_C_Electrical One Line Dia - AS BUILT.pdf PDF
ABS Marine Vessel Rules.pdf PDF
Appendix I to Part 1918_ Title 29 (up to date as of 6-21-2022).pdf PDF
512-6634850F HVAC Arrangement and Details Engine Room_130758174.pdf PDF
NOAA Form 57-17-09 - Hot Work Permit.pdf PDF
Weight Reporting Spreadsheet.docx DOCX document
NOAA Standard Specifications MOC-300-3_General Requirements for Electrical_Electronic Items.pdf PDF
624-6634931 Joiner Door Schedule.pdf PDF
512-3275003-8 HVAC MODS MN DECK REV B.pdf PDF
TJ-233-03 EMD Engine_Maintenance Instruction_1722 Rev I.pdf PDF
085-6980295E TJ Tank Capacities _ Soundings.pdf PDF
TJ-233-01 Detroit Diesel 6V92.pdf PDF
321-3274004-3A HVAC Elec Control Mods Incdt HVAC Mods.pdf PDF
505-6634825 Standard Piping Details.pdf PDF
321-3274004-2A HVAC Electrical Pwr Mods Incdt HVAC Mods.pdf PDF
NOAA StandardSpecification AMC-505-2_Hydrostatic Pressure Tests.pdf PDF
NOAA Standard Specification AMC-300-1 Overhaul of Electrical Rotating Machinery.pdf PDF
514-3275003-12 Rev A AC PP INSTALL FCSLE DK _ ABV.pdf PDF
514-3275003-6 REV A AC PIPING INSTL 2ND DK _ BLW.pdf PDF
TJ-241-01 Reduction Gear Main Propulstion RS2719S.pdf PDF
512-004_-_HVAC Makeup Air Modifications.pdf PDF
TJ-436-01A - Consilium Salwico CS4000 Operations Manual.pdf PDF
TJ-233-03 EMD Engine 12-645F7B.pdf PDF
985-6634639 REV N Fire Control Plan Final_123787221_123332124.pdf PDF
085-002H Booklet of General Plans.pdf PDF
Mathers Control Drawings.pdf PDF
514-003_-_Refrigerant System and Condensate Piping Modifications.pdf PDF
NOAA Standard Specification AMC-635-2 Thermal Insulation for Compartments.pdf PDF
NF 57-17-09 - Hot Work Permit.pdf PDF
NOAA Standard Specification 000-1H General Requirements for Ship Repair Contract Work.pdf PDF
501-6634837C Reach Rod ARR _ Details.pdf PDF
101-6634906 Structural standards.pdf PDF
NOAA Standard Specification MOC-635-1 Thermal Insulation for Piping.pdf PDF
320-6634679_E Cableway Arrangement and Details - AS BUILT.pdf PDF
514-3275003-11 REV A AC PIPING INSTL MN DK.pdf PDF
803-3275003-10 TJ HVAC Upgrade Engineering Data Package.pdf PDF
NOAA General Technical Requirements (GTR) Rev -.pdf PDF
525-6634754F Fill Vents and Sounds Arrangement _ Details.pdf PDF
TJ-651-02 Grease interceptor Gaylord Hood.pdf PDF
Show 40 more

Latest 50 of 73 listed here. See the rest on GovTribe.

On GovTribe

Work with this file

  • Download the original file
  • Contacts named in this file
  • Similar government files
  • Ask GovTribe AI about this file

Text version

Report

Customer:Roxtec Services
Asset:NOAA Thomas Jefferson
IMO# or facility ID:8892033
TRANSIT IDENTIFICATIONArea Classif.
DrawingLocationIDProductExLast transit
NumbercommentQR codeNumbertypeOpeningStatusLast recorded commentFireWaterGasEMCInfo tagsupdateUpdated byProposed SOW
Kolumn1Kolumn2Kolumn22Kolumn3Kolumn4Kolumn42Kolumn5Kolumn6Kolumn7Kolumn8Kolumn9Kolumn10Kolumn102Kolumn11Kolumn12Kolumn13
Main deck146541-89-1- stb deck ac outletGlandA1P2Weather tight only. Need to install appropriate gland when able.X2022-03-09David HigginsDisconnect cable from most convenient location, remove existing conduit gland and replace with appropriate, ABS appproved solution. Conduit may also need to be replaced
Pilothouse Top - Bridge deck03-36-0 CHART ROOM1694104-43-0-B-K-WTHR-3GlandA1P2Stuffing tube needs new packing materialA-02021-12-13Tom LayneRepack stuffing tube with appropriate packing material.
Upper deck - Forecastle deck01-61-0 HPU ENCLOSURE1112501-61-2-B-K-AGlandA1P2packing not sufficient to secure cable in gland.A-02021-12-12Tom LayneRepack stuffing tube with appropriate packing material.
Lower deck2-22-2 SCIENTIFIC STORAGE131392-33-4-D-B-A-2R 150A1P2A-02022-02-05D HigginsRemove existing modules and RMCP, cutting RMCP to free from cables. Replace exisitng with Roxtec "RO 150 AISI 316 Opne Frame". Install, repack and tighten per manufactuer's instructions. Existing packing consists of (5) RM 20, (3) RM 20/0, (2) RM 40, (2) RM 10/0x12 and can be reused if in good condition.
Upper deck - Forecastle deck01-17-0 PASSAGEWAY1111201-21-0-B-O-BGlandA1P2no means to stop cable chafingA-60Gas/smoketight2021-12-12Tom LayneRemove insulation and install approved sleeve/penetration into B-class boundary, re-install insulation.
Lower deck4-55-0 ENGINE ROOM169792-64-1-D-B-AW-1Other MCT rectangular 8X2A1P2nelsonA-602022-02-04David HigginsOpening A1: Remove end packing, install (1) missing stayplate (Nelson)
Lower deck4-55-0 ENGINE ROOM169792-64-1-D-B-AW-1Other MCT rectangular 8X2A2P2mixed modulesA-602022-02-04David HigginsOpening A2: Incorrect module configuration. Remove modules and reconfigure to manufacturer approval instructions
Pilothouse Top - Bridge deck03-27-0 PILOT HOUSE1695204-35-2-D-K-WTHRR 100A1P2roxtec modules in nelson frame repackA-602021-12-13Tom LayneRemove Modules and RMCP. Replace with Roxtec "RO 100 AISI 316 Open Frame". Install Roxtec (2) RM 30 and (2) RM 30/0 modules and tighten per manufacturer's instructions.
Lower deck4-55-0 ENGINE ROOM169932-73-1-D-B-AWS 8X2A1P2A-602022-02-04David HigginsRemove packing modules and compression system and replace with approved components. Packing Modules, compression system and stayplates must be of the same manufacurer.
Lower deck4-55-0 ENGINE ROOM169932-73-1-D-B-AWS 8X2A2P2A-602022-02-04David HigginsRemove packing modules and compression system and replace with approved components. Packing Modules, compression system and stayplates must be of the same manufacurer.
Main deck4-55-0 ENGINE ROOM131511-56-1-D-B-AWOther MCT Round 4"A1P2metal trim plate not over module edgeA-02021-12-14Tom Layne
Lower deck2-22-2 SCIENTIFIC STORAGE131402-33-6-D-B-AS 6X1A1P2open ended cables to be removedA-02022-02-05D HigginsRemove dead ended cables and replace entire row of modules with appropriate sized modules. Modules extending beyond stayplate edge must be correctly repositioned. Current packing configuration consists of (10) RM 20, (8) RM 20/0, (8) RM 30, (2) RM 60/0, (6) Stayplate 120 galv, (1) Roxtec Wedge galv
Pilothouse Top - Bridge deck03-27-0 PILOT HOUSE1119003-29-0-D-B-A-1S 6X2A1P2missing 10 mill packingA-602022-01-26David HigginsOpening missing 10mm of (Brattburg) packing material, gaps visible between modules & cable. Ensure that modules are correct size for cable, remove all packing material and relubricate frame and modules. Re-Install with additional 10mm of packing and compress per Manufacturer's instructions. ALL material in ransit window must be of the same manufacturer.
Pilothouse Top - Bridge deck03-27-0 PILOT HOUSE1119003-29-0-D-B-A-1S 6X2A2P2missing 10 mil packingA-602022-01-26David HigginsOpening missing 10mm of (Brattburg) packing material, gaps visible between modules & cable. Ensure that modules are correct size for cable, remove all packing material and relubricate frame and modules. Re-Install with additional 10mm of packing and compress per Manufacturer's instructions. ALL material in ransit window must be of the same manufacturer.
Lower deck2-22-2 SCIENTIFIC STORAGE131382-33-4-D-B-AOther MCT RoundA1Cmetal keeper plates not covering module edgeA-02022-02-05D HigginsUpon further review, the installaiton is correct. The RMCP Flanges are affixed in their proper location
Lower deck4-55-0 ENGINE ROOM169882-73-3-D-K-AW-1S 8X2A1P2unable to inspect, mixed manufA-602022-02-04David HigginsRemove old modules and replace with approved system of a consistant manufacturer
Lower deck4-55-0 ENGINE ROOM169882-73-3-D-K-AW-1S 8X2A2P2unable to inspect, mixed manufA-602022-02-04David HigginsRemove old modules and replace with approved system of a consistant manufacturer
Lower deck131432-33-2-D-R-AWOther MCT RoundA1P2A-604 bar2022-03-29David HigginsModules protruding too from frame. Needs to select appropriate 20mm sized modules (x4) and replace following manufacturer's instructions (Nelson) If replacing entire system with Roxtec use (1) R 75 AISI 316 and (4) RM 20 modules.
Pilothouse Top - Bridge deck03-36-0 CHART ROOM1318003-45-0-D-B-WTHRR 200A1P2flange plate not over modules, mixed manufacturersA-602022-01-26David HigginsRMCP and Modules not of the same manufacturer. Replace modules with appropriate sized (Nelson) module or replace RMCP frame with Roxtec "RO 200 AISI 316 Open Frame". Roxtec modules may also be replaced for ease of instalation. Existing Roxtec modules configuration consists of (3) RM 20w40, (8) RM 30, (3) RM 40
Lower deck2-25-0 PASSAGEWAY131442-26-1-B-O-BGlandA1P2A-602021-12-14Tom LayneRemove insulation and install approved sleeve/penetration into B-class boundary, re-install insulation.
Main deckabove door to hospital small cable gland over full, cannot access rest side146021-46-1-B-O-AGlandA1P2A-602022-03-10David HigginsReplace stuffing tube with appropriate, approved MCT.
Main deck4-87-0 STEERING GEAR ROOM146531-94-2-D-K-WTHRW-2GlandA1P2not suitable solution for open deck, spoke with engineer, low risk plan on replacing in future.X2022-02-18David HigginsRemove existing gland and replace with approved gland

Legend

STATUS
TCTransit created
HDHole cut done
HRHole cut done - needs rework
HAHole cut done and approved
FDFrame/sleeve installation done
FRFrame/sleeve is installed - needs rework
FAFrame/sleeve is installed and approved
COOpening is open, work in progress
CDOpening is closed, work done
CROpening is closed- needs rework
CAOpening is closed and approved
M2Maintenance or repair work finished, opening closed but not inspected/approved
M1Intended or started maintenance or repairwork
NIMark at opening level, some openings in a transit could be inspectable, and some not. Note in comment field reason.
P1Immediate maintenance recommended (Transit open or risk for blow out)
P2Maintenance recommended soonest possible
P3Installation deviations found, (the openings safety performance acceptable by product experience, tests and verifications)
CCorrectly installed
APFinal verification done and approved
--

image1.png

File details come from the government source that posted it. Updated .