AC PLANT COOLING CALCS and Filter Sizes.xls

XLS spreadsheet 45 KB Posted

Attached to
FY21 RFQ Nancy Foster Drydock Repairs
Solicitation number
1305M220QNMAN0179
Issued by

About this file

This document contains a cooling load summary and specifications for fan coil units and air conditioning units aboard the NOAA ship Nancy Foster. It also includes details of a related federal contract opportunity for FY21 drydock repairs for the Nancy Foster.

The cooling load summary specifies 41 fan coil units and air conditioning units aboard the Nancy Foster, including locations served, models, sizes, cooling capacities, filter sizes, and airflow. It also lists specifications for an air handling unit, bridge modifications, and equipment such as condensers and z-drives. The related federal contract opportunity is a request for quote for FY21 drydock repairs to the Nancy Foster, issued by the Department of Commerce National Oceanic and Atmospheric Administration. The solicitation number is 1305M220QNMAN0179. No further details are provided on response date, award date, pricing terms, or set-asides for the repair work.

View the file

Other files

File Type Posted
FY21 NF DD Repairs Rev-3.pdf PDF
Pricing Schedule Nancy Foster FY 2021-REV 2.xlsx XLSX spreadsheet
Amendment 0006.pdf PDF
Missing Refs FY 21 DD Rev1 1 of 3 524-001 Uncontaminated Scientific Seawater Piping Diagram-20200723T121321Z-001.zip ZIP file
6500863.pdf PDF
6500869.pdf PDF
NF 320-008.pdf PDF
Missing Refs FY 21 DD Rev1 3 of 3 Standard Specifications-20200723T121333Z-001.zip ZIP file
Amendment 0005.pdf PDF
320-004.pdf PDF
6500871.pdf PDF
6500865.pdf PDF
6500867.pdf PDF
Missing Refs FY 21 DD Rev1 2 of 3.zip ZIP file
Joiner Door and Window Schedule.pdf PDF
ARRANGEMENT DRAWING 2001207038 Khz Transducer 1240231.pdf PDF
505-1B rv1.pdf PDF
NF-555-001_K_114072528 (1).pdf PDF
5692OD12.pdf PDF
5692SD12.pdf PDF
01-CMC-031318_Stability Test Report -1.pdf PDF
NF-581-S9581-BP-MMA-010 Anchor Wind Tech Man Part 2.pdf PDF
NF MCT SURVEY 2020 (1).pdf PDF
FY21 DD Package Rev 2.pdf PDF
ES707C Installation Manual.pdf PDF
Amendment 0003.pdf PDF
256-6500974 rv1.pdf PDF
NF-320-008.pdf PDF
EK60installation_manual.pdf PDF
Stability Booklet.PDF PDF
HT-600 Bowthruster Manual (1).pdf PDF
871204718AES707CClampRing.pdf PDF
871204716A ES707CMountingRing.pdf PDF
256-6500974.pdf PDF
5051B.pdf PDF
NANCY FOSTER CR 044 ATT.pdf PDF
Copy of 2566500974.pdf PDF
997-1A.pdf PDF
Amperage Testing Files April 2013.zip ZIP file
Amendment 0004.pdf PDF
(134)Knuckle Boom Crane_Part4.pdf PDF
AC PLANT COOLING CALCS and Filter Sizes July 2018.xls XLS spreadsheet
Copy of 256-6500974.pdf PDF
NF-183-001 FDN.zip ZIP file
EP100 Panel Amperage.xls XLS spreadsheet
6501101.pdf PDF
(134)Knuckle Boom Crane_Part2.pdf PDF
EL101Panel Amperage.xls XLS spreadsheet
EP102 Panel Amperage.xls XLS spreadsheet
P404 Panel Amperage.zip ZIP file
Show 40 more

Latest 50 of 87 listed here. See the rest on GovTribe.

On GovTribe

Work with this file

  • Download the original file
  • Contacts named in this file
  • Similar government files
  • Ask GovTribe AI about this file

Text version

SUMMARY

BTU/HGPM
FCU TOTAL19,6004
ACU TOTAL11916023.8
NEW TOTALS138,76027.8
(TONS)11.56
ORIGINAL LOAD00
(TONS)0.00
NEW ADDITIONAL LOAD00
(TONS)0
% INCREASE0.00%0.00%

&C&"Arial,Bold"&12NOAA SHIP NANCY FOSTER

COOLING LOAD SUMMARY

FCU

FCU NO.LOCATIONSPACE(S) SERVEDSIZEMODELQTYFILTER SIZECOOLING CAP.CFMGPM
101-24-13AE S/R2Carrier Model 42 CGB02ALCE5AKFV110x33x13,5401600.7
201-36-22AE S/R #142Carrier Model 42 CGB02ARCE5AKFV110x33x13,5401600.7
302-19-2XO S/R2Carrier Model 42 CGB02ALCE5AKFV110x33x13,5401600.7
402-26-202 PWAY FWD2Carrier Model 42 CGB02ALCE5AKFV110x33x13,5401600.7
502-26-1S/R 42Carrier Model 42 CGB02ALCE5AKFV110x33x13,5401600.7
602-23-1S/R 32Carrier Model 42 CGB02ALCE5AKFV110x33x13,5401600.7
702-19-1CO S/R2Carrier Model 42 CGB02ALCE5AKFV110x33x13,5401600.7
801-35-21AE S/R #152Carrier Model 42 CGB02ALCE5AKFV110x33x13,5401600.7
901-24-2CME S/R #132Carrier Model 42 CGB02ALCE5AKFV110x33x13,5401600.7
1001-17-2S/R 10 JUE/BGL2Carrier Model 42 CGB02ALCE5AKFV110x33x13,5401600.7
1101-18-001 PWAY2Carrier Model 42CGB02ALCA5AKFV110x24x11,3712000.3
1201-14-0S/R 8 CB2Carrier Model 42 CGB02ALCE5AKFV110x33x13,5401600.7
1301-22-2S/R 112Carrier Model 42 CGB02ALCE5AKFV110x33x13,5401600.7
1401-17-0S/R 92Carrier Model 42 CGB02ALCE5AKFV110x33x13,5401600.7
1501-26-2S/R 122Carrier Model 42 CGB02ALCE5AKFV110x33x13,5401600.7
161-55-2MACHINE SHOP3Carrier Model 42 CGB03ALCE5AKFV-MAR110x33x16,6162951.3
171-49-2MACHINE SHOP3Carrier Model42 CGB03ALCE5AKFV-MAR110x33x16,6162951.3
181-43-2UPS RM4Carrier Model 42 CGB04ALCE5AKFV-MAR110X56X110,5984952.1
191-36-1ET SHACK8Carrier Model 42 DF114X48X148,01722009.6
201-25-2S/R 182Carrier Model 42 CGB02ALCE5AKFV110x33x13,5401600.7
211-20-2S/R 172Carrier Model 42 CGB02ALCE5AKFV110x33x13,5401600.7
221-16-2S/R 162Carrier Model 42 CGB02ALCE5AKFV110x33x13,5401600.7
231-26-2FWD MAIN PWAY3Carrier Model 42 CGB03ALCE5AKFV-MAR110X40X12,7582400.6
241-16-1SHIP OFFICE3Carrier Model 42 CG110X40X13,1572200.6
251-20-1MESS6Carrier Model 42 CEA06BLCM5AKY4YE120X20X119,6006004
261-31-3GALLEY3Carrier Model 42 CGB03ALCE5AKFV-MAR110x33x15,2692301
271-31-1GALLEY3Carrier Model 42 CGB03ARCE5AKFV-MAR110x33x15,2692301
281-37-1DRY LABSpacepak Model WCS3642GH01Fabricated36,000
291-44-1WET LAB FWD2Carrier Model 42 CGB02ARCE5AYFV110X33X13,5401600.7
301-53-1WET LAB AFT2Carrier Model 42 CGB02ARCE5AYFV110X33X13,5401600.7
311-16-1MESS DECKLanco Upright FCU Model V10X411R00114X30X136,000
321-50-0AFT MAIN PWAY3Carrier Model 42 CGB03ALCE5AKFV-MAR110X40X12,7112880.5
332-34-2MULTIPURPOSE6Carrier Model 42 CG110X40X16,0006004.2
342-41-2MULTIPURPOSE6Carrier Model 42 CG110X40X16,0006004.2
352-41-1LOUNGE6Carrier Model 42 CG110X40X16,0006004.2
362-22-2DIVE LOCKER5Carrier Model 42 CG110X56X120,0001008
372-26-2MSD SPACE5Carrier Model 42 CGB02ARCE5AKFV110x33x13,5401600.7
382-24-1DRY STORES5Carrier Model 42 CG110X56X128,00010008
3902-29-1S/R 5 (02-29-1)2Carrier 42CGB02ALCA5AKFV110x33x13,5401600.7
4002-32-2S/R 7 (02-32-2)2Carrier 42CGB02ALCA5AKFV110x33x13,5401600.7
4102-34-1S/R 6 (02-34-1)2Carrier 42CGB02ALCA5AKFV110x33x13,5401600.7
4202-38-002 PWAY AFT2Carrier 42CGB02ALCA5AKFV110x33x13,5401600.7
43EOSEOSCarrier 42VFA6BRCY5BKYMYQ18X14X13,540
44EOSEOSCarrier 42VFA6BRCY5BKYMYQ18X14X13,540
45EOSEOS6Carrier 42 CEA06BLCM5AKY4YE110x33x119,6006004
461-54-1WET LAB SPACEPAKSpacepak WCSP-3642G1Fabricated36,000
AHU101 PlenumMU Air for all FCU'sCarrier Model 39BA-050-D-15120x30x2119,1601800
46 FCU's total
498,512 Total BTU's
41.5 Max Tons
ET ShackET ShackET ShackSamsung Unit, 3 Ton1
1 PORTBRIDGEBRIDGE CONDENSERCarrier 40 KMQ-301, 3 Ton123x23x1
1 STBDBRIDGEBRIDGE CONDENSERCarrier 40 KMQ-301, 3 Ton123x23x1
AFT PORTPort Z Drive220x20x2
AFT STBDStbd Z Drive220x20x2
AFT PORTPort Z Drive120x25x2
AFT STBDStbd Z Drive120x25x2

&C&"Arial,Bold"&12NOAA SHIP NANCY FOSTER

FCU COOLING LOAD

Bridge Mod

FCU NO.LOCATIONSPACE(S) SERVEDMODELSIZECOOLING CAP. (BTU)CFMGPMKW HtrCOMMENTS
103-28-2BRIDGECarrier Model 42 CG824,47711007.145
203-24-1BRIDGECarrier Model 42 CG36,7002851.52
2903-22-2BRIDGECarrier Model 42 DF839,71518407.92
Existing BTU70,892322595.9 Tons
25% increase88,6154031.257.3 Tons
Total Tons required7.3845833333
Unit Installed=7.5 * 12,000 = 90,000 BTU300016.57.5 Tons
27% increase a/c
plus dehumidifier feature

ACU

ACU NO.LOCATIONSPACE(S) SERVEDMODELCOOLING CAPACITYGPMCOMMENTS
(BTU/H)
1FAN ROOM 01-19-1Carrier Central Station Type "D"119,16023.8
0
0
0
0
0
0
0
119,16023.8

&C&"Arial,Bold"&12NOAA SHIP NANCY FOSTER

ACU COOLING LOAD

File details come from the government source that posted it. Updated .