This document is an equipment data sheet for a 60-ton air-cooled chiller, model 30RAP060F-0C104. The unit is ready for operation with minimal setup and features a complete microprocessor control center with single-point power connection. It is forkliftable and capable of operating in low ambient temperatures down to -20°F and high ambient temperatures up to 125°F, with an optional brine mode for operation to 15°F.

The chiller has a water volume capacity of 10 gallons with 4" 150 lb RF flanges for water connections and maximum pressure ratings of 150 psig (with a 300 psig option available). It operates on 460V, 3-phase, 60-hertz power with a 150-amp disconnect and requires a 120/126 amp full load/maximum current. The unit contains 2 circuits and 4 compressors, uses R410a refrigerant with a charge of 17-18 lbs, and POE oil with 13.8 pints per circuit. Water flow ranges from 70 to 260 gallons per minute, with corresponding pressure drops detailed in the performance table. The shipping weight is 5,005 lbs with dimensions of 11' length by 8'-4" width by 7'-8" height, requiring leveling within 1" per 8 feet and installed clearances of 6 feet on sides and 4 feet for electrical access. Cooling capacity ranges from 28 to 74 tons depending on leaving water temperature and ambient air temperature conditions.

View the file

Other files

File Type Posted
C04_12639526Q0269.pdf PDF
C04_Attachment 1 SOI.pdf PDF
C04_Attachment 2 Statement of Work.pdf PDF
C04_Attachment 2 Statement of Work.pdf PDF
C04_12639526Q0269.pdf PDF
C04_Attachment 1 SOI.pdf PDF
C04_Attachment 3 Building SPECS.pdf PDF
C04_Attachment 2 Statement of Work.pdf PDF
C04_12639526Q0269.pdf PDF
C04_Attachment 1 SOI.pdf PDF

On GovTribe

Work with this file

  • Download the original file
  • Contacts named in this file
  • Similar government files
  • Ask GovTribe AI about this file

Text version

GENERAL DESCRIPTION AND FEATURES EQUIPMENT DATA

Ready for operation with minimal setup Model(s) 30RAP060F-0C104

Complete microprocessor control center

Single point power connection SHIPPING DATA

Forkliftable Shipping Weight 5,005 lbs

Low ambient temperature operation to -20°F Dimensions 11’ L x 8’-4” W x 7’-8” H

High ambient temperature operation to 125°F Leveling Required Within 1” per 8 ft.

Brine mode to 15°F (option) Installed Clearances 6’ (sides), 4’ (electrical)

MECHANICAL DATA ELECTRICAL DATA (SINGLE DISCONNECT)

Water Connections 4” 150 lb RF flange in/out Voltage 460 V / 3 phase / 60 hertz

Water Volume 10 gallons Disconnect Size 150 amps

Water Max. pressure 150 psig (300 psig option) Connection Leviton Series 16 Camlock

Minimum Load 6 tons Cables 1/0 - (1) Set, (1) Ground

Min / Max Water Flow 70 / 260 gpm FLA / MCA 120 / 126 amps

Circuits / Compressors 2 / 4

Refrigerant / Charge R410a / 17 / 18 lbs

Oil / Charge POE / 13.8 pints per ckt.

Leaving Water Temp.

Leaving Brine Temp.

Capacity in Tons Chiller Barrel Flow VS Pressure Drop Ambient Air Temperature Flow

(GPM) Pressure Drop * (PSID) 85° F 95° F 105° F 115° F 55° F 74 70 66 61 70 Min. 2.2 50° F 70 65 62 56 100 3.5 45° F 63 60 56 51 150 std. 7.4 40° F 58 54 51 46 200 13.9

35° F 52 48 46 41 250 20.3 30° F 44 41 38 34 260 Max. 23.8 25° F 35 32 30 28

Water Limits: 60°F to 40°F / Brine: 15°F *Cooler only