12629 OSP Boiler Plant Fire Escape_Plans.pdf
PDF 5 MB Posted
- Attached to
- OSP Boiler Plant Fire Escape
- Solicitation number
- S-29100-00012629
- Issued by
- Marion County, Oregon
About this file
This is a set of structural engineering drawings and calculations from Windsor Engineers and JBW Consultants for the Oregon Department of Corrections (DOC) Boiler Plant Building Control Room Fire Escape project (#6669) in Salem, Oregon. The project involves installing an exterior emergency egress stairway, creating a new opening and door in the exterior wall, and grading for a new concrete pad at the bottom of the stairway. The drawings include detailed plans for structural steel framing, concrete work, and guardrails, with design loads accounting for wind speeds up to 96 mph and seismic considerations. The design phase occurred through 2024 with schematic design issued February 2024, permit documents in May 2024, and owner revisions in November 2024.
The structural design utilizes hot rolled steel including HSS3x3x3 columns, C10x15.3 channels, and L3x3x4 angle bracing, with an estimated total steel weight of 2,055 pounds. The emergency exit platform is designed with a 10-inch concrete slab and includes safety features like guardrails and non-slip treads. The design calculations account for dead loads, live loads of 100 psf for assembly areas, and wind/seismic forces per ASCE 7-16 requirements. Technical specifications detail requirements for concrete strength of 4,500 psi, welding, bolted connections, and protective coatings with all exposed steel to be painted per DOC standards.
View the file
Other files
| File | Type | Posted |
|---|---|---|
| 12630_Att B_Technical Specs.pdf | ||
| 6964 Contract_Executed.pdf | ||
| ITB~9.pdf | ||
| 12629 OSP Control Room Fire Escape_SOW .pdf | ||
| 6964 NOITA.pdf | ||
| 12629 ADDENDA 2.pdf | ||
| 12629 Plan Holder list.pdf | ||
| 12629 ITB_GTC_SGC_SPECS.pdf | ||
| 12629 ADDENDA 1.pdf | ||
| 12629 Bid Tab.pdf |
On GovTribe
Work with this file
- Download the original file
- Contacts named in this file
- Similar government files
- Ask GovTribe AI about this file
Text version
Ridgefiled, WA.
Duluth + Minneapolis, MN.
www.windsorengineers.com
Copyright 2023 By Windsor Engineers, LLC All Rights Reserved.
LINE IS 1" ON FULL
SCALE DRAWING
CALL 2 BUSINESS DAYS BEFORE YOU DIG.
CAUTION UTILITY INFORMATION IS APPROXIMATE.
VERIFY ALL UTILITIES PRIOR TO CONSTRUCTION.
Revisions: #
Know what's below.
before you dig.Call
R
Issuance Summary:
2024-02-13 SCHEMATIC DESIGN / 30% - ISSUED FOR REVIEW
2024-05-01 PERMIT SET (BUILDING)
2024-05-20 SITE PLAN REVIEW
2024-11-13 OWNER REVISIONS
G001
#6669 Control Room Fire Escape
2605 State St, Salem, OR 97310
COVER SHEET
Project No: 23215.1
DOC BOILER PLANT BUILDING
IMPROVEMENTS
#6669 CONTROL ROOM FIRE ESCAPE
(City Stamp)
FOR
SALEM, OREGON
ENGINEER:
WINDSOR ENGINEERS
CONTACT: TYLER STEWART
PHONE: 218-409-8110
EMAIL: TSTEWART@WINDSORENGINEERS.COM
PREPARED FOR:
OREGON DEPARTMENT OF CORRECTIONS
CONTACT: PETE BELISLE
PHONE: 503-931-1404
EMAIL: PETE.W.BELISLE@DOC.OREGON.GOV
FIRE ESCAPE SHEET LIST
G001 - COVER SHEET
G002 - GENERAL ABBREVIATIONS SYMBOLS AND NOTES
G003 - GENERAL ARRANGEMENT PLAN - OVERALL SITE PLAN
G004 - EXISTING CONDITIONS, DEMOLITION, AND SURVEY CONTROL
G005 - SURVEY
C100 - GRADING EROSION CONTROL ENLARGED PLAN
S0 - STRUCTURAL CONCRETE & STEEL NOTES
S0.1 - STEEL NOTES
S1 - EXTERIOR EGRESS PLATFORM - OVERALL LAYOUT PLAN
S2 - EXTERIOR EGRESS PLATFORM - FRAMING PLANS
S3 - EXTERIOR EGRESS PLATFORM - SECTIONS
S4 - EXTERIOR EGRESS PLATFORM - EXTERIOR DOOR ELEVATIONS
S5 - EXTERIOR EGRESS PLATFORM - DETAILS
S6 - EXTERIOR EGRESS PLATFORM - TYPICAL STAIR DETAILS
S7 - TYPICAL GUARDRAIL DETAILS
S8 - ISOMETRIC VIEWS
1 2024-11-08 OWNER REVISIONS
Expires: 6/30/2026 11-15-2024
EROSION CONTROL NOTES
PUBLIC AND PRIVATE DRAINAGE WAYS SHALL BE PROTECTED
FROM POLLUTION. NO MATERIAL IS TO BE DISCHARGED TO OR
DEPOSITED IN STORMWATER SYSTEMS THAT MAY RESULT IN
VIOLATION OF STATE OR FEDERAL WATER QUALITY
STANDARDS.
EFFECTIVE EROSION CONTROL IS REQUIRED. EROSION
CONTROL DEVICES MUST BE INSTALLED AND MAINTAINED TO
MEET THE CITY REQUIREMENTS.THE GOVERNING JURISDICTION
MAY, AT ANY TIME, ORDER CORRECTIVE ACTION AND STOPPAGE
OF WORK TO ACCOMPLISH EFFECTIVE EROSION CONTROL.
DEMOLITION/PROTECTION NOTES
CONTRACTOR TO VERIFY ALL UTILITY LOCATIONS AND DEPTHS
PRIOR TO CONSTRUCTION. A MINIMUM OF TWO FULL BUSINESS
DAYS PRIOR TO BEGINNING CONSTRUCTION, THE CONTRACTOR
SHALL CALL 811 (UTILITY NOTIFICATION CENTER) FOR LOCATION
MARK-UP OF EXISTING UTILITIES.
CONTRACTOR SHALL PROTECT ALL PROPERTY CORNERS,
SURVEY MONUMENTS AND CONTROL POINTS. SURVEY
MONUMENTS OF THIS TYPE DISTURBED DURING CONSTRUCTION
SHALL BE REPLACED AT CONTRACTOR'S EXPENSE, WITH
APPROPRIATE SURVEYS FILED WITH THE COUNTY SURVEYOR
ALL STRUCTURES, LOTS, SWALES, DITCHES, CURBS, FENCES,
WALLS, MAILBOXES, SIGNS, POLES, GUY WIRES, PIPING, AND
UTILITIES DISTURBED DURING CONSTRUCTION TO BE
RESTORED TO EXISTING CONDITION OR BETTER UNLESS
OTHERWISE SPECIFIED.
THE CONTRACTOR SHALL BE RESPONSIBLE FOR MAINTAINING
THE INTEGRITY OF ADJACENT UTILITIES WHICH MAY INCLUDE,
BUT ARE NOT LIMITED TO, WATER, SANITARY SEWER,
STORMWATER, POWER, TELEPHONE, CABLE TV, GAS,
IRRIGATION, AND STREET LIGHTING. THE CONTRACTOR SHALL
NOTIFY RESIDENTS AND BUSINESSES 48 HOURS IN ADVANCE OF
ANY WORK AFFECTING ACCESS OR SERVICE AND SHALL
MINIMIZE INTERRUPTIONS TO DRIVEWAYS FOR RESIDENTS AND
BUSINESSES ADJACENT TO THE PROJECT.
ALL LAWN AND VEGETATED AREAS DISTURBED WILL BE
RESTORED TO ORIGINAL CONDITION. ANY DISTURBANCE OR
DAMAGE TO OTHER PROPERTY ON ADJACENT PARCELS OR IN
THE PUBLIC RIGHT OF WAY SHALL ALSO BE REPAIRED OR
RESTORED TO ORIGINALCONDITION.
THE TYPES, LOCATIONS, SIZES AND/OR DEPTHS OF EXISTING
UNDERGROUND UTILITIES AND STRUCTURES AS SHOWN ON THE
DRAWINGS ARE APPROXIMATE AND WERE OBTAINED FROM
SOURCES OF VARYING RELIABILITY. THE CONTRACTOR IS
CAUTIONED THAT ONLY ACTUAL EXCAVATION WILL REVEAL THE
TYPES, EXTENT, SIZES, LOCATIONS, AND DEPTHS OF UTILITIES.
A REASONABLE EFFORT HAS BEEN MADE TO LOCATED AND
DELINEATE ALL KNOWN UNDERGROUND UTILITIES. THE
CONTRACTOR SHALL VERIFY THE LOCATION OF AND PROVIDE
PROTECTION FOR ALL UTILITIES AND STRUCTURES.OVERHEAD
UTILITIES ARENOT SHOWN.
EXISTING UTILITIES DAMAGED BY THE CONTRACTOR SHALL BE
REPAIRED BY THE CONTRACTOR OR BY THE UTILITY AT THE
CONTRACTOR'S EXPENSE.
EXCAVATION NOTES
THE CONTRACTOR IS RESPONSIBLE FOR ALL CONSTRUCTION
STAKING.
EXCAVATE FOR SLABS, PAVING, AND OTHER IMPROVEMENTS TO
SIZES AND LEVELS SHOWN OR REQUIRED. ALLOW FOR FORM
CLEARANCE AND FOR PROPER COMPACTION OF REQUIRED
BACKFILLING MATERIAL.
WHERE CONNECTING TO AN EXISTING PIPE, AND PRIOR TO
ORDERING MATERIALS, THE CONTRACTOR SHALL EXPOSE THE END
OF THE EXISTING PIPE VERIFY THE LOCATION, SIZE, AND
ELEVATION. NOTIFY ENGINEER OF ANY DISCREPANCIES.
CONTRACTOR SHALL ADJUST ALL STRUCTURES IMPACTED BY
CONSTRUCTION IMPROVEMENTS TO NEW FINISH GRADES.
BUILDING/SITE UTILITY PIPING NOTES
ALL WATER PIPING SHALL BE CONSTRUCTED WITH 3' MINIMUM
COVER, 1' VERTICAL SEPARATION BETWEEN UTILITIES, AND A
MINIMUM OF 10' HORIZONTAL SEPARATION AND 18" ABOVE SEWER
LINES, UNLESS OTHERWISE NOTED.
DRAWINGS ARE GENERALLY DIAGRAMMATIC. THEY DO NOT SHOW
EVERY OFFSET, BEND OR ELBOW REQUIRED FOR INSTALLATION IN
THE SPACE PROVIDED. THEY DO NOT SHOW EVERY DIMENSION,
COMPONENT PIECE, SECTION, JOINT OR FITTING REQUIRED TO
COMPLETE THE PROJECT. ALL LOCATIONS FOR WORK SHALL BE
CHECKED AND COORDINATED WITH EXISTING CONDITIONS IN THE
FIELD BEFORE BEGINNING CONSTRUCTION. EXISTING
UNDERGROUND UTILITIES LAYING WITHIN THE LIMITS OF
EXCAVATION SHALL BE VERIFIED AS TO CONDITION, SIZE AND
LOCATION BY UNCOVERING, PROVIDING SUCH IS PERMITTED BY
LOCAL PUBLIC AUTHORITIES WITH JURISDICTION, BEFORE
BEGINNING CONSTRUCTION. CONTRACTOR TO NOTIFY ENGINEER IF
THERE ARE ANY DISCREPANCIES.
PROVIDE CLEANOUTS AS REQUIRED IN THE CURRENT EDITION OF
THE UNIFORM PLUMBING CODE.
SEE MECHANICAL/PLUMBING DRAWINGS FOR UTILITIES LOCATED
WITHIN THE BUILDING AND TO 5’ OUTSIDE THE BUILDING,
INCLUDING FOUNDATION DRAINAGE AND DOWNSPOUTLEADERS.
DOWNSPOUT LEADERS TO BE 6" AT 2% MIN. UNLESS NOTED
OTHERWISE.
RECOMMENDED SEQUENCE FOR EROSION CONTROL
1. PRE-CONSTRUCTION MEETING.
2. FLAG OR FENCE CLEARING LIMITS
3. POST NOTICE OF CONSTRUCTION ACTIVITY SIGN WITH THE
NAME AND PHONE NUMBER OF EROSION SEDIMENT CONTROL
SUPERVISOR.
4. INSTALL CATCH BASIN PROTECTION, IF REQUIRED.
5. INSTALL PERIMETER PROTECTION (SILT FENCE, BRUSH
BARRIER, ETC.).
6. INSTALL TREE PROTECTION FENCING.7. GRADE AND INSTALL
CONSTRUCTION ENTRANCE(S).
8. CONSTRUCT SEDIMENT POND(S) AND TRAP(S).
9. GRADE AND STABILIZE CONSTRUCTION ROADS.
10. CONSTRUCT SURFACE WATER CONTROLS (INTERCEPT
DIKES, PIPE SLOPE DRAINS, ETC) SIMULTANEOUSLY WITH
CLEARING AND GRADING FOR PROJECT DEVELOPMENT.
11. MAINTAIN EROSION CONTROL MEASURES IN ACCORDANCE
WITH STORMWATER MANAGEMENT MANUAL FOR WESTERN
WASHINGTON AND MANUFACTURER'S RECOMMENDATIONS.
12. RELOCATE SURFACE WATER CONTROLS AND EROSION
CONTROL MEASURE OR INSTALLNEW MEASURES SO THAT AS
SITE CONDITIONS CHANGE THE EROSION AND SEDIMENT
CONTROL IS ALWAYS IN ACCORDANCE WITH THE CLARK
COUNTY EROSION AND SEDIMENT CONTROL STANDARDS.
13. COVER ALL AREAS THAT WILL BE UNWORKED FOR MORE
THAN SEVEN DAYS DURING THE DRY SEASON OR TWO DAYS
DURING THE WET SEASON WITH STRAW, WOOD FIBER MULCH,
COMPOST, PLASTIC SHEETING OR EQUIVALENT.
14. STABILIZE ALL AREAS THAT REACH FINAL GRADE WITHIN
SEVEN DAYS.
15. SEED OR SOD ANY AREAS TO REMAIN UNWORKED FOR
MORE THAN 30 DAYS.
16. ALL DISTURBED PERVIOUS AREAS MUST MEET BMP T5.13 IN
THE 2019 MANUAL. EXISTING TOPSOIL MAY NEED TO BE
AMENDED TO REACH APPROVED RATES, OR IMPORT TOPSOIL
WITH SUFFICIENT ORGANIC CONTENT AND WIDTH.
17. UPON COMPLETION OF THE PROJECT, ALL DISTURBED
AREAS MUST BE STABILIZED AND BEST MANAGEMENT
PRACTICES REMOVED IF APPROPRIATE.
APPLICABLE CODES
THE PROJECT IS DESIGNED IN ACCORDANCE WITH THE FOLLOWING
CODES AND STANDARDS:
• 2021 INTERNATIONAL BUILDING CODE WITH OREGON
AMENDMENTS
• 2021 INTERNATIONAL MECHANICAL CODE WITH OREGON
AMENDMENTS
• 2018 UNIFORM PLUMBING CODE WITH OREGON AMENDMENTS
• 2019 ASHRAE 90.1, 2019 WITH OREGON AMENDMENTS
ACCESS NOTES
CONTRACTOR SHALL MAINTAIN ACCESS TO HOMES AND
BUSINESSES AT ALL TIMES. PROVIDE WRITTEN NOTICE TO ALL
PROPERTY OWNERS AT LEAST TWO BUSINESS DAYS IN ADVANCE
OF WORK ADJACENT TO PROPERTIES.
CONTRACTOR SHALL NOTIFY THE ENGINEER AND OWNER 48 HOURS
BEFORE STARTING CONSTRUCTION, AND 24 HOURS BEFORE
RESUMING WORK AFTER SHUTDOWNS EXCEPT FOR NORMAL
RESUMPTION OF WORK FOLLOWING SATURDAYS, SUNDAYS, OR
HOLIDAYS.
CONTRACTOR SHALL NOTIFY THE ENGINEER A MINIMUM OF 48
HOURS PRIOR TO ANY TESTING OR REQUIRED INSPECTION.
GENERAL SYMBOLS
DETAIL/PLAN CALLOUT
REVISION CLOUD
REVISION TAG
KEYNOTEX
X
XXX
X
NORTH ARROW
N
MATCHLINE
CONTINUATION SYMBOL
ITEM TO BE DEMOLISHED
AREA NOT IN CONTRACT
POINT OF CONNECTION
POINT OF DEMOLITION
AD ANALYZER DRAIN
ALL ALL
BUR BURIED
C CONCRETE
CB CATCH BASIN
CD CONDENSATE DRAIN
CI CAST IRON
CISP CAST IRON SOIL PIPE
CL CENTERLINE
CNS COMPACTED NATIVE SOIL
CO CLEAN OUT
CO COPPER
CPE CORRUGATED POLYETHYLENE
CR CURB RETURN
CS CAUSTIC SODA SOLUTION
CST CARBON STEEL
D DIRT / DRAINAGE
D BUILDING DRAIN
DI CEMENT MORTOR LINED DUCTILE IRON
DR DRAIN
ENC CONCRETE ENCASED
ESXT EXISTING
EXP EXPOSED, INTERIOR
FC FLUSH CURB
FG FINISHED GRADE
FG FINISH GRADE (DEFAULT- IF NOT LABELED)
FH FIRE HYDRANT
FL FLOW LINE
FL FLOWLINE
FL FLOURIDE SOLUTION
FL FLANGED
FM FORCE MAIN
FR FLARED
FW FUSION WELDED
G NATURAL GAS (LOW PRESSURE)
GAL GALVANIZED
GB GRADE BREAK
GB GRADE BREAK
H HYDROSTATIC
HDPE HIGH DENSITY POLYETHYLENE
HP HIGH POINT
HP HIGH POINT
HW HOT WATER
HWC HOT WATER CIRCULATION
LF LINEAR FOOT
LP LOW POINT
LP LOW POINT
MDPE MEDIUM DENSITY POLYETHYLENE
MG NATURAL GAS (MEDIUM PRESSURE)
MG MATCH EXISTING GRADE
MG MATCH GRADE
MH MANHOLE
MJ MECHANICAL JOINT
NA NOT APPLICABLE
NF TEST PER APPROPRIATE NFPA STANDARD
NH NO HUB
NS NATIVE SOIL
NTS NOT TO SCALE
P PNEUMATIC
PC POINT OF CURVATURE
PC TEST PER UNIFORM PLUMBING CODE
PO PUSH ON (GASKET)
POC POINT OF CONNECTION
POS POINT OF SERVICE
PP POWER POLE
PP PROPANE
PPP POLYPROPYLENE PIPE
PPT POLYPROPYLENE TUBING
PPU PROPANE UNDERGROUND
PT POINT OF TANGENCY
PV PAVEMENT
PV PAVEMENT
PVC POLYVINYL CHLORIDE
R RADIUS
RJ PROPRIETARY RESTRAINED JOINT
ROW RIGHT OF WAY
RW RAW WATER
S SLOPE / SANITARY
SA SAMPLE
SAN SEWER SEWER
SD STORM DRAIN
SDCO STORM DRAIN CLEANOUT
SHC SODIUM HYPOCHLORITE SOLUTION
SO SOLDERED
SS SANITARY SEWER
SSMH SANITARY MANHOLE
STA STATION
STM STORM DRAIN
STMH STORM MANHOLE
SW SIDEWALK
SW SOLVENT WELD
TBD TO BE DETERMINED
TBL TO BE RELOCATED BY RESPECTIVE UTILITY
TBR TO BE REMOVED BY CONTRACTOR
TC TOP OF CURB
TC TOP OF CURB
TH THREADED
TM TEMPARED WATER
TOE TOE OF BANK
TOP TOP OF BANK
TP TELEPHONE POLE
TW TREATED WATER
U UNDERGROUND
V SANITARY VENT
VIP VERIFY IN FIELD PRIOR TO CONSTRUCTION
VP PROCESS VENT
W WATER MAIN
W W1 POTABLE WATER
W WELDED
W2 NON POTABLE WATER
ABBREVIATIONS
Ridgefiled, WA.
Duluth + Minneapolis, MN.
www.windsorengineers.com
Copyright 2023 By Windsor Engineers, LLC All Rights Reserved.
LINE IS 1" ON FULL
SCALE DRAWING
CALL 2 BUSINESS DAYS BEFORE YOU DIG.
CAUTION UTILITY INFORMATION IS APPROXIMATE.
VERIFY ALL UTILITIES PRIOR TO CONSTRUCTION.
Revisions: #
Know what's below.
before you dig.Call
R
Issuance Summary:
2024-02-13 SCHEMATIC DESIGN / 30% - ISSUED FOR REVIEW
2024-05-01 PERMIT SET (BUILDING)
2024-05-20 SITE PLAN REVIEW
2024-11-13 OWNER REVISIONS
G002
#6669 Control Room Fire Escape
2605 State St, Salem, OR 97310
GENERAL ABBREVIATIONS SYMBOLS AND
NOTES
Project No: 23215.1
PROJECT ADDRESS
OREGON STATE PENITENTIARY
2605 STATE ST, SALEM, OR 97310
PROJECT DATUM
THE HORIZONTAL DATUM IS OREGON STATE PLANE NORTH ZONE,
NAD83(2011).
THE ELEVATION DATUM IS CITY OF SALEM, OREGON NGVD29 (ADD 3.37 TO
ADJUST TO NAVD 88).
BENCHMARK
SEE FFN SURVEY (G004)
A132
SEE FFN SUREY: A132 FOR DETAIL DESCRIPTION
ELEVATION = 200.01' CITY OF SALEM DATUM
DOC BOILER PLANT
OREGON DEPARTMENT OF CORRECTIONS
3601 STATE ST,
SALEM OR, 97301
PETE.W.BELISLE@DOC.OREGON.GOV
PETE BELISLE
CIVIL ENGINEER
WINDSOR ENGINEERS
27300 NE 10TH AVE
RIDGFIELD WA, 98642
360.335.3642
TYLER STEWART
CONTRACTOR
(CONTRACTOR)
(ADDRESS)
(ADDRESS LINE 2)
(CONTACT INFO)
(NAME)
OWNER
STRUCTURAL ENGINEER
JBW CONSULTANTS
4140 RICHARD AVE SUITE 650
HERMANTOWN, MN 55811
TOM.JOHNSON@JBWCONULT.COM
TOM JOHNSON
PROJECT NARRATIVE
THIS PROJECT INCLUDES MODIFICATIONS TO THE CONTROL ROOM ACCESS
INCLUDING AN EXTERIOR STAIRWAY, A NEW OPENING AND DOOR IN THE
EXTERIOR WALL, AND GRADING FOR A NEW CONCRETE PAD AT THE BOTTOM
OF THE STAIRWAY.
0,0
VERT
0,0
VERT
GG
CC
AA
DD
HH
BB
EE
FF
C100
LOCATION OF
BOILER PLANT
Ridgefiled, WA.
Duluth + Minneapolis, MN.
www.windsorengineers.com
Copyright 2023 By Windsor Engineers, LLC All Rights Reserved.
LINE IS 1" ON FULL
SCALE DRAWING
CALL 2 BUSINESS DAYS BEFORE YOU DIG.
CAUTION UTILITY INFORMATION IS APPROXIMATE.
VERIFY ALL UTILITIES PRIOR TO CONSTRUCTION.
Revisions: #
Know what's below.
before you dig.Call
R
Issuance Summary:
2024-02-13 SCHEMATIC DESIGN / 30% - ISSUED FOR REVIEW
2024-05-01 PERMIT SET (BUILDING)
2024-05-20 SITE PLAN REVIEW
2024-11-13 OWNER REVISIONS
G003
#6669 Control Room Fire Escape
2605 State St, Salem, OR 97310
GENERAL ARRANGEMENT PLAN / OVERALL
SITE PLAN
Project No: 23215.1
N
SCALE: 1" = 10'-0"
SITE PLAN - GENERAL ARRANGEMENT PLAN
SEE STRUCTURAL SHEETS FOR EXIT STAIRS
NOT TO SCALE
VICINITY MAP
0,0
VERT
GG
C
C
AA
DD
HH
B
B
EE
FF
EX. BULK
STORAGE TANK
EX. BULK
STORAGE TANK
EXISTING PAVEMENT EDGES
EXISTING WALL (NOT SHOWN)
50 FT FROM BUILDING
130' - 0"
Ridgefiled, WA.
Duluth + Minneapolis, MN.
www.windsorengineers.com
Copyright 2023 By Windsor Engineers, LLC All Rights Reserved.
LINE IS 1" ON FULL
SCALE DRAWING
CALL 2 BUSINESS DAYS BEFORE YOU DIG.
CAUTION UTILITY INFORMATION IS APPROXIMATE.
VERIFY ALL UTILITIES PRIOR TO CONSTRUCTION.
Revisions: #
Know what's below.
before you dig.Call
R
Issuance Summary:
2024-02-13 SCHEMATIC DESIGN / 30% - ISSUED FOR REVIEW
2024-05-01 PERMIT SET (BUILDING)
2024-05-20 SITE PLAN REVIEW
2024-11-13 OWNER REVISIONS
G004
#6669 Control Room Fire Escape
2605 State St, Salem, OR 97310
EXISTING CONDITIONS, DEMOLITION, AND
SURVEY CONTROL
Project No: 23215.1 Author
SCALE: 1" = 10'-0"
SITE PLAN - EXISTING CONDITIONS AND DEMOLITION
N
TANK AND FENCE RELOCATED
BY OTHERS
EXISTING DRAIN LINE RELOCATED BY OTHERS
SHEET NOTES:
1. SEE G003 - GENERAL ARRANGMENT PLAN FOR OVERALL
PROJECT SITE AND AREA.
2. PROPERTY LINES ARE GREATER THAN 200 FT AWAY
FROM THESE BUILDING IMPROVEMENTS. REFERENCE
G003 FOR PROPERTY LINE LOCATIONS.
3. SITE IS RELATIVLY FLAT. REFERNCE G005 - SURVEY
AND C100 - EMERGENCY EXIT GRADING, EROSION
CONTROL ENLARGED PLAN FOR CONTOURS.
1 2024-11-08 OWNER REVISIONS
T O P O G R A P H
IC
S U R V E Y
F O R O .S .P B O
IL
E R
B U
IL
D
IN
G
F F
N S
U R
V E
Y
IN
G
IN
T H E
S W
1/
O F
S E C T
IO
N
T .7 S
R .3 W
W .M
C
IT
Y
O F
S A
LE
M M A R
IO
N
C O U N T Y O R E G O N
N O
D A T E
D E S C R
IP
T
IO
N
R E V
IS
IO
N S
SHEET
JOB NO.
23-451 rd S tr ee t S
E
T u rn er O
R
P (5
-3
E in fo ff n su rv ey in g .c o m
S E P
IN
IT
IA
L R E
LE
A S E
20'0' 40'
SCALE: 1 INCH = 20 FEET
WVT
EB
U
UVT
TVB
TFM
WV
BOL
RD
NOTES
LEGEND
1. BASIS OF BEARINGS AND COORDINATE SYSTEM IS BASED ON
OREGON STATE PLANE NORTH ZONE, NAD83(2011), EPOCH
2010.00. ALL DISTANCES SHOWN HEREON ARE GROUND DISTANCES.
2. ELEVATIONS WERE ESTABLISHED BY GPS RTK OBSERVATIONS TO
CITY OF SALEM BENCHMARK "A132". MARK IS A 2" ALUMINUM
DISK SET IN THE CURB AT THE SOUTHERLY END OF THE
ROBERTS HIGH SCHOOL PROPERTY AT 3630 STATE STREET SE.
PER NOAA'S VERTCON UTILITY, ADD 3.37 FEET TO OBTAIN
NAVD88 DATUM. ALL ELEVATIONS SHOWN HEREON ARE CITY OF
SALEM DATUM, NGVD29.
"A132" ELEVATION = 200.01' (CITY OF SALEM DATUM, NGVD29)
3. THE LOCATION OF UTILITIES SHOWN HEREON ARE FROM
OBSERVED VISIBLE EVIDENCE OF ABOVE GROUND
APPURTENANCES ALONG WITH SURFACE UTILITY MARKINGS BY
OTHERS. ALL UNDERGROUND UTILITIES SHOWN WERE MARKED ON
THE SURFACE BY AN UNKNOWN ENTITY. IN ADDITION TO SAID
MARKINGS, ADDITIONAL DATA WAS PROVIDED BY WESTECH
ENGINEERING FOR PREVIOUSLY LOCATED LINES AND ARE SHOWN
AS "ASBUILT" LINES HEREON. SURVEYOR MAKES NO GUARANTEE
AS TO THE ACCURACY OF SAID MARKINGS, HOWEVER, THEY ARE
LOCATED AS ACCURATELY AS THEY ARE MARKED ON THE
GROUND.
4. PER ORS 209.150, ANY SURVEY MONUMENT REMOVED,
DISTURBED OR DESTROYED SHALL BE REPLACED BY A
PROFESSIONAL LAND SURVEYOR WITHIN 90 DAYS AT THE EXPENSE
OF THE PERSON OR PUBLIC AGENCY RESPONSIBLE FOR SAID
REMOVAL, DISTURBANCE OR DESTRUCTION.
5. FIELD SURVEYED SEPTEMBER, 2023.
FOUND MONUMENT
CATCH BASIN
CATCH BASIN ROUND
CULVERT
WATER VALVE
WATER VAULT
ELECTRICAL BOX
UTILITY MANHOLE
UTILITY STUB UP
UTILITY VAULT
COMMUNICATION BOX
SIGN
BOLLARD
STORM LINE UNDERGROUND
WATERLINE UNDERGROUND
GAS LINE UNDERGROUND
ELECTRICAL LINE UNDERGROUND
FENCE LINE
CONCRETE
FINISH FLOOR
CONC
FF
ELECTRICAL TRANSFORMER
ROOF DRAIN
UNKNOWN LINE UNDERGROUND
CONCRETE
GRAVEL
ASPHALT
COMMUNICATION LINE ASBUILT DATA
ELECTRICAL LINE ASBUILT DATA
GAS LINE ASBUILT DATA
WATERLINE ASBUILT DATA
U
VT
U U
EB
TFM
TFM
UVT
UVT
WVT
E B
TV
B
E B
186.3
186.2
186.4 186.5
186.5 186.2
186.3
186.2
186.2
186.0
186.2
186.2
186.3
186.2
185.6
185.8
185.9
185.8
186.0 186.1
186.1
186.9
186.6
187.0
187.7
186.8
186.3
186.3
186.9
187.4
187.7 187.1
185.9
186.5
186.1
186.6
185.8
180.2
182.3
179.8
181.4
182.2
186.6
186.5
187.2
187.6
187.3
188.3
187.6
189.0
188.9
188.8
188.1
188.3
188.6
189.1
189.3
189.6
189.6
189.5 189.2
189.0
189.0
189.0
189.0 188.9
188.6
187.1
186.7
188.7
188.9
187.4
188.3
188.9
186.3186.4
186.4
186.4
186.6
186.8
186.9
186.7
186.8
187.1
187.1
187.8
187.1
186.9
188.4
188.7
188.9
BOL
BOL
BOL
BOL
BOL
RD
BOL
BOL
BOL
BOL
BOL
BOL
BOL
BOL
BOL
BOL
RD
BOL
BOL
RD
BOL
BOL
BOL
BOL
BOL
BOL
BOL
BOL
BOL
BOL
BOL
BOL
BOL
BOL
BOL
BOL
BOL
BOL
BOL
BOL BOL
BOL
BOL
BOL
BOL
BOL
BOL
BOL
BOL
BOL
BOL
BOL
WV
WV
BOL
RD
RD
BOL
BOL
RD
1 8
3 18
1 8
5 30"CONC
IE:178.1
CB RIM=185.09
IE (4"PVC,E) 184.5
CB RIM=189.67
IE (6"CONC,N) 185.9
UTILITY
TRENCH
ELEV:186.96'
ELEV:186.97'
C O N C
P A D
C O N C
P A D
C O N C
W A
LL
C O N C
W A
LL
C O N C
W A
LL
EXISTING BUILDING
EXISTING BUILDING
FF:186.96'
PROPANE TANK
T A N K
TANK
20'0' 40'
SCALE: 1 INCH = 20 FEET
WVT
EB
U
UVT
TVB
TFM
WV
BOL
RD
NOTES
LEGEND
1. BASIS OF BEARINGS AND COORDINATE SYSTEM IS BASED ON
OREGON STATE PLANE NORTH ZONE, NAD83(2011), EPOCH
2010.00. ALL DISTANCES SHOWN HEREON ARE GROUND DISTANCES.
2. ELEVATIONS WERE ESTABLISHED BY GPS RTK OBSERVATIONS TO
CITY OF SALEM BENCHMARK "A132". MARK IS A 2" ALUMINUM
DISK SET IN THE CURB AT THE SOUTHERLY END OF THE
ROBERTS HIGH SCHOOL PROPERTY AT 3630 STATE STREET SE.
PER NOAA'S VERTCON UTILITY, ADD 3.37 FEET TO OBTAIN
NAVD88 DATUM. ALL ELEVATIONS SHOWN HEREON ARE CITY OF
SALEM DATUM, NGVD29.
"A132" ELEVATION = 200.01' (CITY OF SALEM DATUM, NGVD29)
3. THE LOCATION OF UTILITIES SHOWN HEREON ARE FROM
OBSERVED VISIBLE EVIDENCE OF ABOVE GROUND
APPURTENANCES ALONG WITH SURFACE UTILITY MARKINGS BY
OTHERS. ALL UNDERGROUND UTILITIES SHOWN WERE MARKED ON
THE SURFACE BY AN UNKNOWN ENTITY. IN ADDITION TO SAID
MARKINGS, ADDITIONAL DATA WAS PROVIDED BY WESTECH
ENGINEERING FOR PREVIOUSLY LOCATED LINES AND ARE SHOWN
AS "ASBUILT" LINES HEREON. SURVEYOR MAKES NO GUARANTEE
AS TO THE ACCURACY OF SAID MARKINGS, HOWEVER, THEY ARE
LOCATED AS ACCURATELY AS THEY ARE MARKED ON THE
GROUND.
4. PER ORS 209.150, ANY SURVEY MONUMENT REMOVED,
DISTURBED OR DESTROYED SHALL BE REPLACED BY A
PROFESSIONAL LAND SURVEYOR WITHIN 90 DAYS AT THE EXPENSE
OF THE PERSON OR PUBLIC AGENCY RESPONSIBLE FOR SAID
REMOVAL, DISTURBANCE OR DESTRUCTION.
5. FIELD SURVEYED SEPTEMBER, 2023.
FOUND MONUMENT
CATCH BASIN
CATCH BASIN ROUND
CULVERT
WATER VALVE
WATER VAULT
ELECTRICAL BOX
UTILITY MANHOLE
UTILITY STUB UP
UTILITY VAULT
COMMUNICATION BOX
SIGN
BOLLARD
STORM LINE UNDERGROUND
WATERLINE UNDERGROUND
GAS LINE UNDERGROUND
ELECTRICAL LINE UNDERGROUND
FENCE LINE
CONCRETE
FINISH FLOOR
CONC
FF
ELECTRICAL TRANSFORMER
ROOF DRAIN
UNKNOWN LINE UNDERGROUND
CONCRETE
GRAVEL
ASPHALT
COMMUNICATION LINE ASBUILT DATA
ELECTRICAL LINE ASBUILT DATA
GAS LINE ASBUILT DATA
WATERLINE ASBUILT DATA
U
VT
U U
EB
TFM
TFM
UVT
UVT
WVT
E B
TV
B
E B
186.3
186.2
186.4 186.5
186.5 186.2
186.3
186.2
186.2
186.0
186.2
186.2
186.3
186.2
185.6
185.8
185.9
185.8
186.0 186.1
186.1
186.9
186.6
187.0
187.7
186.8
186.3
186.3
186.9
187.4
187.7 187.1
185.9
186.5
186.1
186.6
185.8
180.2
182.3
179.8
181.4
182.2
186.6
186.5
187.2
187.6
187.3
188.3
187.6
189.0
188.9
188.8
188.1
188.3
188.6
189.1
189.3
189.6
189.6
189.5 189.2
189.0
189.0
189.0
189.0 188.9
188.6
187.1
186.7
188.7
188.9
187.4
188.3
188.9
186.3186.4
186.4
186.4
186.6
186.8
186.9
186.7
186.8
187.1
187.1
187.8
187.1
186.9
188.4
188.7
188.9
BOL
BOL
BOL
BOL
BOL
RD
BOL
BOL
BOL
BOL
BOL
BOL
BOL
BOL
BOL
BOL
RD
BOL
BOL
RD
BOL
BOL
BOL
BOL
BOL
BOL
BOL
BOL
BOL
BOL
BOL
BOL
BOL
BOL
BOL
BOL
BOL
BOL
BOL
BOL BOL
BOL
BOL
BOL
BOL
BOL
BOL
BOL
BOL
BOL
BOL
BOL
WV
WV
BOL
RD
RD
BOL
BOL
RD
1 8
3 18
1 8
5 30"CONC
IE:178.1
CB RIM=185.09
IE (4"PVC,E) 184.5
CB RIM=189.67
IE (6"CONC,N) 185.9
UTILITY
TRENCH
ELEV:186.96'
ELEV:186.97'
C O N C
P A D
C O N C
P A D
C O N C
W A
LL
C O N C
W A
LL
C O N C
W A
LL
EXISTING BUILDING
EXISTING BUILDING
FF:186.96'
PROPANE TANK
T A N K
TANK
20'0' 40'
SCALE: 1 INCH = 20 FEET
WVT
EB
U
UVT
TVB
TFM
WV
BOL
RD
NOTES
LEGEND
1. BASIS OF BEARINGS AND COORDINATE SYSTEM IS BASED ON
OREGON STATE PLANE NORTH ZONE, NAD83(2011), EPOCH
2010.00. ALL DISTANCES SHOWN HEREON ARE GROUND DISTANCES.
2. ELEVATIONS WERE ESTABLISHED BY GPS RTK OBSERVATIONS TO
CITY OF SALEM BENCHMARK "A132". MARK IS A 2" ALUMINUM
DISK SET IN THE CURB AT THE SOUTHERLY END OF THE
ROBERTS HIGH SCHOOL PROPERTY AT 3630 STATE STREET SE.
PER NOAA'S VERTCON UTILITY, ADD 3.37 FEET TO OBTAIN
NAVD88 DATUM. ALL ELEVATIONS SHOWN HEREON ARE CITY OF
SALEM DATUM, NGVD29.
"A132" ELEVATION = 200.01' (CITY OF SALEM DATUM, NGVD29)
3. THE LOCATION OF UTILITIES SHOWN HEREON ARE FROM
OBSERVED VISIBLE EVIDENCE OF ABOVE GROUND
APPURTENANCES ALONG WITH SURFACE UTILITY MARKINGS BY
OTHERS. ALL UNDERGROUND UTILITIES SHOWN WERE MARKED ON
THE SURFACE BY AN UNKNOWN ENTITY. IN ADDITION TO SAID
MARKINGS, ADDITIONAL DATA WAS PROVIDED BY WESTECH
ENGINEERING FOR PREVIOUSLY LOCATED LINES AND ARE SHOWN
AS "ASBUILT" LINES HEREON. SURVEYOR MAKES NO GUARANTEE
AS TO THE ACCURACY OF SAID MARKINGS, HOWEVER, THEY ARE
LOCATED AS ACCURATELY AS THEY ARE MARKED ON THE
GROUND.
4. PER ORS 209.150, ANY SURVEY MONUMENT REMOVED,
DISTURBED OR DESTROYED SHALL BE REPLACED BY A
PROFESSIONAL LAND SURVEYOR WITHIN 90 DAYS AT THE EXPENSE
OF THE PERSON OR PUBLIC AGENCY RESPONSIBLE FOR SAID
REMOVAL, DISTURBANCE OR DESTRUCTION.
5. FIELD SURVEYED SEPTEMBER, 2023.
FOUND MONUMENT
CATCH BASIN
CATCH BASIN ROUND
CULVERT
WATER VALVE
WATER VAULT
ELECTRICAL BOX
UTILITY MANHOLE
UTILITY STUB UP
UTILITY VAULT
COMMUNICATION BOX
SIGN
BOLLARD
STORM LINE UNDERGROUND
WATERLINE UNDERGROUND
GAS LINE UNDERGROUND
ELECTRICAL LINE UNDERGROUND
FENCE LINE
CONCRETE
FINISH FLOOR
CONC
FF
ELECTRICAL TRANSFORMER
ROOF DRAIN
UNKNOWN LINE UNDERGROUND
CONCRETE
GRAVEL
ASPHALT
COMMUNICATION LINE ASBUILT DATA
ELECTRICAL LINE ASBUILT DATA
GAS LINE ASBUILT DATA
WATERLINE ASBUILT DATA
U
VT
U U
EB
TFM
TFM
UVT
UVT
WVT
E B
TV
B
E B
186.3
186.2
186.4 186.5
186.5 186.2
186.3
186.2
186.2
186.0
186.2
186.2
186.3
186.2
185.6
185.8
185.9
185.8
186.0 186.1
186.1
186.9
186.6
187.0
187.7
186.8
186.3
186.3
186.9
187.4
187.7 187.1
185.9
186.5
186.1
186.6
185.8
180.2
182.3
179.8
181.4
182.2
186.6
186.5
187.2
187.6
187.3
188.3
187.6
189.0
188.9
188.8
188.1
188.3
188.6
189.1
189.3
189.6
189.6
189.5 189.2
189.0
189.0
189.0
189.0 188.9
188.6
187.1
186.7
188.7
188.9
187.4
188.3
188.9
186.3186.4
186.4
186.4
186.6
186.8
186.9
186.7
186.8
187.1
187.1
187.8
187.1
186.9
188.4
188.7
188.9
BOL
BOL
BOL
BOL
BOL
RD
BOL
BOL
BOL
BOL
BOL
BOL
BOL
BOL
BOL
BOL
RD
BOL
BOL
RD
BOL
BOL
BOL
BOL
BOL
BOL
BOL
BOL
BOL
BOL
BOL
BOL
BOL
BOL
BOL
BOL
BOL
BOL
BOL
BOL BOL
BOL
BOL
BOL
BOL
BOL
BOL
BOL
BOL
BOL
BOL
BOL
WV
WV
BOL
RD
RD
BOL
BOL
RD
1 8
3 18
1 8
5 30"CONC
IE:178.1
CB RIM=185.09
IE (4"PVC,E) 184.5
CB RIM=189.67
IE (6"CONC,N) 185.9
UTILITY
TRENCH
ELEV:186.96'
ELEV:186.97'
C O N C
P A D
C O N C
P A D
C O N C
W A
LL
C O N C
W A
LL
C O N C
W A
LL
EXISTING BUILDING
EXISTING BUILDING
FF:186.96'
PROPANE TANK
T A N K
TANK
20'0' 40'
SCALE: 1 INCH = 20 FEET
G005 1
0,0
VERT
GG
CC
DD
HH
BB
EE
FF
4' - 0"
5'
5%
5%
6' - 0"
7'
SHEET NOTES
1. PUBLIC AND PRIVATE DRAINAGE WAYS SHALL BE PROTECTED
FROM POLLUTION. NO MATERIAL IS TO BE DISCHARGED TO OR
DEPOSITED IN STORMWATER SYSTEMS THAT MAY RESULT IN
VIOLATION OF STATE OR FEDERAL WATER QUALITY
STANDARDS.
2. EFFECTIVE EROSION CONTROL IS REQUIRED. EROSION
CONTROL DEVICES MUST BE INSTALLED AND MAINTAINED TO
MEET THE CITY REQUIREMENTS. THE GOVERNING
JURISDICTION MAY, AT ANY TIME, ORDER CORRECTIVE ACTION
AND STOPPAGE OF WORK TO ACCOMPLISH EFFECTIVE
EROSION CONTROL.
3. CONTRACTOR TO PROVIDE APPROVED MULCH AND STRAW IN
DISTURBANCE AREAS.
4. CONTRACTOR TO FURNISH AN ESPC GRASS SEED MIX THAT IS
OREGON CERTIFIED SEED.
5. SUBGRADE SHALL BE SHAPED AND COMPACTED TO A FIRM
EVEN SURFACE.
6. ALL SOFT AND YIELDING MATERIAL SHALL BE REMOVED AND
REPLACED WITH ACCEPTABLE MATERIAL.
7. FINISH GRADE CONTOURS ARE TO TOP OF FINISHED SURFACE
IN IMPERVIOUS AREAS AND TOP OF REPLACED STRIPPINGS IN
PERVIOUS AREAS.
8. CONTRACTOR TO REMOVE OFF SITE AND DISPOSE OF FILL,
SOD AND OTHER DEBRIS CAUSED BY THE SCOPE OF WORK.
Ridgefiled, WA.
Duluth + Minneapolis, MN.
www.windsorengineers.com
Copyright 2023 By Windsor Engineers, LLC All Rights Reserved.
LINE IS 1" ON FULL
SCALE DRAWING
CALL 2 BUSINESS DAYS BEFORE YOU DIG.
CAUTION UTILITY INFORMATION IS APPROXIMATE.
VERIFY ALL UTILITIES PRIOR TO CONSTRUCTION.
Revisions: #
Know what's below.
before you dig.Call
R
Issuance Summary:
2024-02-13 SCHEMATIC DESIGN / 30% - ISSUED FOR REVIEW
2024-05-01 PERMIT SET (BUILDING)
2024-05-20 SITE PLAN REVIEW
2024-11-13 OWNER REVISIONS
C100
#6669 Control Room Fire Escape
2605 State St, Salem, OR 97310
EMERGENCY EXIT - GRADING, EROSION
CONTROL - ENLARGED PLAN
Project No: 23215.1
SCALE: 1/4" = 1'-0"
SITE PLAN - EMERGENCY EXIT - ENLARGED PLAN
N
EMERGENCY EXIT STAIRWAY,
REFER TO STRUCTURAL SHEETS
187'
8'
7'
8'
TANK AND FENCE RELOCATED
BY OTHERS
EXISTING DRAIN LINE TO
BE RELOCATED IN A
SEPARATE CONTRACT BY
OTHERS.
MULCH AND SEED ALL DISTURBED GRASSY AREAS.
238 SY
EXISTING EDGE OF PAVEMENT
10% PROPOSED
4% EXISTING
EXISTING CONC PAD
REFER TO STRUCTURAL
SHEETS FOR CONCRETE PAD
AND FOOTING DETAILS
EXISTING BOILER PLANT BUILDING
EXISTING WALL (NOT SHOWN) 50
FT AWAY FROM BUILDING
CONCRETE AND REINFORCING NOTES
1. DESIGN, MATERIALS, AND WORKMANSHIP SHALL BE IN ACCORDANCE WITH THE FOLLOWING STANDARDS:
A. ACI 301 – SPECIFICATION FOR STRUCTURAL CONCRETE
B. ACI 318-11 – BUILDING CODE REQUIREMENTS FOR REINFORCED CONCRETE
C. SP66 – ACI DETAILING MANUAL
D. CRSI – RECOMMENDED PRACTICE FOR PLACING REINFORCING STEEL
2. CONCRETE MATERIALS SHALL CONFORM TO THE LATEST REVISION OF ACI 318 SPECIFICATIONS AND PROJECT
INCLUDING:
A. AGGREGATES, PER ASTM C33
B. CEMENT, PER ASTM C150, TYPE I/II, UNLESS NOTED OTHERWISE
C. DEFORMED REINFORCING BARS, PER A615, GRADE 60
D. WELDED WIRE FABRIC, PER ASTM A185, GRADE 64
3. ANCHOR BOLTS SHALL CONFORM WITH ASTM F-1554, GRADE 55, HOT-DIP GALVANIZED, UNC THREADS, C/W
ASTM A563 HEAVY HEX GRADE DH NUTS AND ASTM F436 HARDENED STEEL WASHERS
4. CONCRETE SHALL BE NORMAL WEIGHT CONCRETE WITH THE FOLLOWING STRENGTHS AT 28 DAYS:
A. SLABS ON GRADE – 4500 PSI
5. CONCRETE WORK ON THIS PROJECT SHALL CONFORM TO THE REQUIREMENTS OF ACI 301 SECTIONS 1 THRU 5
AND 11, AND ACI 306.1.
6. CONTRACTOR IS RESPONSIBLE FOR OBTAINING AND REFERRING TO ACI 301 AND ACI 306.1, AS THE PROVISIONS
AND REQUIREMENTS THEREIN, IN ADDITION TO, OR AS MODIFIED BY, THE PROVISIONS AND REQUIREMENTS IN
THESE NOTES, ARE HEREBY INCORPORATED INTO THE CONTRACT REQUIREMENTS FOR THIS PROJECT.
7. CONCRETE CONSTRUCTION LOCATIONS AND ELEVATIONS SHALL BE VERIFIED BY FIELD SURVEYORS PRIOR TO THE
PLACEMENT OF CONCRETE.
8. SUBMITTAL REVIEW AND ACCEPTANCE OF CONCRETING PROCEDURES FOR COLD- WEATHER CONDITIONS SHALL
BE REQUIRED.
9. REINFORCEMENT SUPPORTS SHALL BE PLASTIC.
10. CALCIUM CHLORIDE SHALL NOT BE USED IN ANY FORM.
11. ALL REINFORCEMENT SHALL BE BENT COLD. REINFORCEMENT PARTIALLY EMBEDDED IN CONCRETE SHALL NOT
BE FIELD BENT UNLESS APPROVED BY THE STRUCTURAL ENGINEER OF RECORD. HOOKS SHALL BE ACI STANDARD
HOOKS
12. PROVIDE 1” CHAMFER ON ALL EXPOSED CONCRETE EDGES.
13. CONTRACTOR SHALL PREPARE AND SUBMIT REINFORCEMENT SHOP DRAWINGS TO THE STRUCTURAL ENGINEER
FOR REVIEW PRIOR TO FABRICATION. THE SHOP DRAWINGS SHALL CLEARLY SHOW REINFORCEMENT LENGTHS
AND BENDS, LOCATIONS OF BARS, METHODS OF SUPPORT, DETAILS OF PLACEMENT AND PLACEMENT
COORDINATION WITH FORMWORK, EMBEDMENTS, CONCRETE VIBRATION AND CONSTRUCTION JOINTS. THE
DRAWINGS SHALL ALSO INDICATE OPENINGS, SLEEVES, CURBS AND CONCRETE DIMENSIONS IN ACCORDANCE
WITH ACI 315. PROVIDE, AT MINIMUM WALL, COLUMN AND BEAM ELEVATIONS: WALL, COLUMN AND BEAM
SECTIONS, MATERIAL SCHEDULES, BAR LAP SCHEDULES AND LOCATIONS.
14. CONTRACTOR SHALL TIE REINFORCING STEEL SECURELY IN PLACE PRIOR TO PLACING CONCRETE AND PROVIDE
SUFFICIENT SUPPORTS TO MAINTAIN THE POSITION OF REINFORCING WITHIN SPECIFIED TOLERANCES DURING
ALL CONSTRUCTION ACTIVITIES. INSERTING DOWELS INTO WET CONCRETE IS NOT PERMITTED.
15. CONTRACTOR SHALL PROVIDE CONTINUOUS REINFORCEMENT WHEREVER POSSIBLE; USE SPLICE LENGTHS AS
NOTED. DOWELS SHALL MATCH THE SIZE AND SPACING OF THE SPECIFIED REINFORCEMENT AND SHALL BE
LAPPED WITH TENSION SPLICES, UNLESS NOTED OTHERWISE.
16. HOOKED BARS SHALL BE STANDARD 90 DEGREE HOOKS PER ACI UNLESS NOTED OTHERWISE ON THE DRAWINGS.
17. MINIMUM LAP SPLICE SHALL BE STANDARD 90 DEGREE HOOKS PER ACI UNLESS NOTED OTHERWISE ON THE
DRAWINGS.
18. APPROVED REBAR COUPLERS MAY BE USED TO AID PLACEMENT OF DOWELS THROUGH FORMS. MECHANICAL
SPLICES SHALL DEVELOP 125% OF THE TENSILE STRENGTH OF THE REBAR.
19. PRIOR TO PLACING CONCRETE TOPPING, MECHANICALLY ROUGHEN, THEN THOROUGHLY CLEAN AND DE-GREASE
EXISTING CONCRETE SURFACES. SOAK EXISTING CONCRETE SURFACES FOR MINIMUM 12 HOURS. PLACE A
CONCRETE-SLURRY OF CEMENT AND WATER WITHIN 1 HOUR OF TOPPING PLACEMENT.
20. NON-SHRINK GROUT SHALL CONFORM TO ASTM C1107. GROUT SHALL BE PREMIXED, NON-SHRINK, NON-
CATALYZED NATURAL AGGREGATE GROUT WITH A MINIMUM 7-DAY COMPRESSIVE STRENGTH OF 7,000 PSI
PLASTIC, 6,000 PSI FLOWABLE, AND 5,000 PSI FLUID CONSISTENCY.
21. REINFORCING STEEL, ANCHOR RODS AND EMBED PLACEMENT SHALL BE INSPECTED, PRIOR TO PLACEMENT OF
CONCRETE, IN ACCORDANCE WITH ACI 318 AND CODE REQUIRED SPECIAL INSPECTION BY QUALIFIED INSPECTOR
PRIOR. THESE INSPECTIONS ARE NOT INCLUDED IN THE BASIC SERVICES OF THE STRUCTURAL ENGINEER OF
RECORD.
1. SUBMITTALS:
A. FIELD CONTROL TEST REPORTS: MAINTAIN AND SUBMIT RECORD OS QUALITY CONTROL TEST AND
INSPECTION REPORTS.
B. PLACEMENT NOTIFICATION: SUBMIT NOTIFICATION OF CONCRETE PLACEMENT AT LEAST 24 HOURS
PRIOR.
C. REPAIR METHODS: WHEN STAINS, RUST, EFFLORESCENCE, AND SURFACE DEPOSITS MUST BE REMOVED
AS DESCRIBED IN ACI 301, SUBMIT THE PROPOSED METHOD OF REMOVAL.
D. CURING METHOD: IF A MOISTURE-PREVENTING METHOD OTHER THAN THOSE SPECIFIED IN ACI 301 IS
PROPOSED, SUBMIT REQUEST FOR ACCEPTANCE OF THE PROPOSED METHOD.
E. THE PERIOD FOR PROTECTION AGAINST FREEZING AS REFERENCE IN ACI 306.1 SECTION 3.4.4 SHALL BE
4 DAYS.
2. FINISHING FORMED SURFACES:
A. AS CAST FINISHES:
a. SURFACE FINSISH-1.0 (SF-1.0) (USE FOR FORMED SURFACES NOT EXPOSED TO VIEW
• PATCH VOIDS LARGER THAN 1 1/2" WIDE OR 1/2" DEEP
• REMOVE PROJECTIONS LARGER THAN 1"
B. SURFACE TOLERANCE CLASS d AS SPECIFIED IN ACI 117 SHALL PERTAIN
a. SURFACE FINISH-2.0 (SF-2.0) (USE FOR FORMED SURFACES EXPOSED TO VIEW OTHER THAN
FLATWORK
• PATCH VOIDS LARGER THAN 3/4" WIDE OR 1/2" DEEP
• REMOVE PROJECTIONS LARGER THAN 1/4"
• PATCH TIE HOLES
• SURFACE TOLERANCE CLASS B AS SPECIFIED IN ACI 117
3. FINISHING UNFORMED SURFACES:
A. FLOAT FINISH
a. PLACE, CONSOLIDATE, STRIKE OFF, AND LEVEL CONCRETE.
b. CUT HIGH SPOTS AND FILL LOW SPOTS. DO NOT WORK WITH CONCRETE FURTHER UNTIL IT IS
READY FOR FLOATING.
c. BEGIN FLOATING WITH A HAND FLOAT, A BLADED POWER FLOAT EQUIPPED WITH FLOAT SHOES, OR A POWERED DISC FLOAT WHEN THE BLEED WATER SHEEN HAS DISAPPEARED AND THE
SURFACE HAS STIFFENED SUFFICIENTLY TO PERMIT OPERATION OF THE SPECIFIC FLOAT
APPARATUS.
d. PRODUCE A FINISH THAT WILL MEET TOLERANCE REQUIREMENTS OF ACI 117 FOR A
CONVENTIONAL SURFACE.
HANDLING, PLACING & CONSTRUCTING CONCRETE
SLAB CONSTRUCTION NOTES
1. BACKFILL AND COMPACTION PROCESSES SHALL BE OBSERVED BY A QUALIFIED GEOTECHNICAL ENGINEER
LICENSED IN THE STATE OF OREGON OR THEIR DESIGNATED REPRESENTATIVE. TESTING AND
OBSERVATION TO BE AT THE DISCRETION OF THE OWNER.
2. THE CONTRACTOR SHALL PROVIDE SHORING AND UNDERPIN AS NECESSARY TO COMPLETE THE WORK IN
A SAFE MANNER
3. THE CONTRACTOR SHALL ENSURE THAT EXCAVATIONS ARE DOWN TO COMPETENT SOIL OR BEDROCK
AND ARE DRAINED TO MINIMIZE DISTURBANCE TO THE EXPOSED SOILS. THE EXCAVATIONS SHALL BE
SLOPED OR PROPERLY DRAINED TO THE LOWEST POINT IN ORDER TO COLLECT WATER WHICH SHALL BE
REMOVED IMMEDIATELY THROUGH A DEWATERING SYSTEM.
4. THE CONTRACTOR SHALL BACKFILL AS SOON AS REASONABLY POSSIBLE AFTER THE FOUNDATION AND
ASSOCIATED WORK ARE INSPECTED AND APPROVED BY THE OWNER OR THEIR REPRESENTATIVE.
5. BACKFILL SHALL ONLY BE PLACED AFTER THE CONCRETE FOUNDATIONS AND STRUCTURE HAVE ACHIEVED
THE SPECIFIED DESIGN CONCRETE COMPRESSIVE STRENGTH.
6. ALL THE DENSITY MEASUREMENTS OF FILL SHALL BE MEASURED ACCORDING TO ITS MAXIMUM DRY
DENSITY BY THE MODIFIED PROCTOR TEST IN ACCORDANCE WITH ASTM D1557. THE DENSITY AND
MOISTURE CONTENT OF THE BACKFILL AND FILL MATERIALS SHALL BE MEASURED EVERY 50 LINEAR FEET, 2500 SQUARE FEEL, 60 CUBIC YARDS, OR 16 INCHES OF FILL WHICHEVER IS MOST FREQUENT.
7. THE CONTRACTOR SHALL CAREFULLY PLACE AND COMPACT FILL NEXT TO STRUCTURES WITHOUT USING
LARGE EQUIPMENT. THE FILL SHALL BE ADDED UNIFORMLY ON EACH SIDE OF THE STRUCTURE WITH NO
MORE THAN 1 FOOT DIFFERENCE AND COMPACTED PRIOR TO ERECTING ANY EQUIPMENT, STRUCTURES, OR MATERIAL SUPPORTED BY THE STRUCTURE.
8. STRUCTURAL FILL:
A. STRUCTURAL FILL SHALL BE SAND WITH 100 PERCENT OF ITS PARTICLES PASSING THE 3-INCH SIEVE
AND LESS THAN 5 PERCENT OF PARTICLES PASSING THE #200 SIEVE.
B. STRUCTURAL FILL SHALL NOT VARY BY MORE THAN 2% OF THE OPTIMUM MOISTURE CONTENT IN
ACCORDANCE WITH ASTM D1557.
C. STRUCTURAL FILL SHALL BE PLACED IN MAXIMUM 8-INCH LIFTS AND COMPACTED TO 98% OF ITS
MAXIMUM DRY DENSITY, UNLESS NOTED OTHERWISE, IN ACCORDANCE WITH MODIFIED PROCTOR
TEST ASTM D1557.
EXPOSURE CLASS: F1
CEMENT TYPE: 1
MAX. SIZE COARSE AGGREGATE: 3/4"
MAXIMUM WATER/CEMENT RATIO: 0.45
AIR ENTRAINMENT: 6.0% +/- 1.5%
MIN. 28 DAY COMPRESSIVE STRENGTH: 4,500 PSI
SLUMP: 3" +/- 1"
CONCRETE PROPERTIES
A. REMOVE ALL UNUSED MATERIALS.
B. STRUCTURAL CONTRACTOR IS RESPONSIBLE FOR FIELD VERIFYING, PRIOR
TO CONSTRUCTION, EXISTING CONDITIONS FOR WORK WITHIN THE SPACE
AND WITHIN CLOSE PROXIMITY OF THE SPACE.
C. CONTRACTOR SHALL BE FAMILIAR WITH ALL CONDITIONS, EXISTING AND
THOSE ILLUSTRATED BY DRAWINGS AS WELL AS THOSE WHICH CAN BE
REASONABLY ANTICIPATED INCLUDING, BUT NOT LIMITED TO
ARCHITECTURAL, ELECTRICAL, FIRE PROTECTION, STRUCTURAL, AND OTHER
SYSTEMS INVOLVED IN THIS PROJECT.
D. THESE NOTES SPECIFY THE REQUIREMENTS FOR THE DESIGN REPRESENTED
IN THESE DOCUMENTS.
E. THE CONSTRUCTION AND MATERIALS SHALL COMPLY WITH ALL THE
PERTINENT CODES AND REFERENCES, PLANS, AND DETAILS.
F. THE CONTRACTOR SHALL VERIFY ALL DIMENSIONS AND EXISTING
CONDITIONS IN THE FIELD THAT AFFECT CONSTRUCTION PRIOR TO
COMMENCING WORK ON THE AFFECTED ELEMENT OR SHOP DRAWING
SUBMITTALS.
G. THE CONTRACT STRUCTURAL DRAWINGS REPRESENT THE COMPLETED
STRUCTURE.
H. THE CONTRACTOR IS RESPONSIBLE FOR BRACING AND SHORING (WITHOUT
OVERSTRESSING) ALL STRUCTURAL ELEMENTS AS NECESSARY AT ANY
STAGE OF CONSTRUCTION UNTIL COMPLETION OF THE PROJECT.
I. THE STRUCTURAL ENGINEER IS NOT RESPONSIBLE FOR THE CONTRACTOR’S
MEANS, METHODS, SEQUENCES OR PROCEDURES OF CONSTRUCTION.
J. CONTRACTOR SHALL RECOGNIZE AND CONSIDER EFFECTS OF THERMAL
MOVEMENTS OF STRUCTURAL ELEMENTS DURING CONSTRUCTION PERIOD.
THE CONTRACTOR IS SOLELY RESPONSIBLE FOR SITE SAFETY INCLUDING ALL
TEMPORARY PRECAUTIONARY MEASURES AND SAFETY PROGRAMS.
K. SITE OBSERVATION VISITS BY THE STRUCTURAL ENGINEER DO NOT INCLUDE
REVIEW OF THE CONTRACTOR’S SAFETY PRECAUTIONS.
L. INFORMATION SHOWN IN THE STRUCTURAL DRAWINGS REGARDING EXISTING
CONDITIONS REPRESENTS THE CURRENT AND GENERAL FIELD CONDITIONS
RELATED TO THE NEW WORK, TO THE BEST OF OUR KNOWLEDGE.
M. REPORT ALL DISCREPANCIES (UNFORESEEN CONDITIONS) FOR RESOLUTION
PRIOR TO PERFORMING RELATED NEW WORK.
N. REQUESTS FOR INFORMATION SHALL BE SUBMITTED IN WRITING AND SHALL
REFERENCE THE PART OF THE CONSTRUCTION DOCUMENTS THAT IS IN
QUESTION.
A. THROUGHOUT THE COURSE OF THE WORK, THE BUILDING OWNER MAY
REQUEST MINOR CHANGES AND ADJUSTMENTS TO THE PLANS AND
SPECIFICATIONS. THE CONTRACTOR SHALL MAKE SUCH ADJUSTMENTS
WITHOUT ADDITIONAL COST TO THE BUILDING OWNER, WHERE SUCH
ADJUSTMENTS ARE NECESSARY FOR THE PROPER INSTALLATION AND
OPERATION OF THE SYSTEMS, AND WITHIN THE INTENT OF THE CONTRACT
DOCUMENTS.
B. IT IS THE INTENT OF THE PLANS AND SPECIFICATIONS TO FORM A GUIDE
FOR THE COMPLETION AND SUCCESSFUL OPERATION OF THE WORK,
WHETHER OR NOT DEFINITELY SPECIFIED OR INDICATED WITHOUT
ADDITIONAL COST TO THE BUILDING OWNER. THE STRUCTURAL
CONTRACTOR SHALL VERIFY ALL DIMENSIONS PRIOR TO INSTALLATION.
C. NOTWITHSTANDING ANY OTHER PROVISIONS OF THE CONTRACT
DOCUMENTS, THE CONTRACTOR BEARS ULTIMATE RESPONSIBILITY FOR
COMPLIANCE OF THE INSTALLATION WITH THE REQUIREMENTS OF THE
BUILDING OWNER AND OF THE LOCAL AUTHORITY HAVING JURISDICTION.
IF ANY ERRORS, DISCREPANCIES, OR OMISSIONS APPEAR IN THE
DRAWINGS, SPECIFICATIONS, OR OTHER CONTRACT DOCUMENTS, THE
CONTRACTOR SHALL NOTIFY THE ENGINEER IN WRITING OF SUCH ERROR OR
OMISSION. IN THE EVENT OF THE CONTRACTOR FAILING TO GIVE SUCH
NOTICE BEFORE CONSTRUCTION OR FABRICATION OF THE WORK, THE
CONTRACTOR WILL BE HELD RESPONSIBLE FOR THE RESULTS OF ANY SUCH
ERRORS, DISCREPANCIES, OR OMISSIONS AND THE ASSOCIATED COST OF
RECTIFYING.
CONTRACTOR SHALL COMPLY WITH THE REQUIREMENTS OF ALL STATE
AND LOCAL CODES REGULATING THIS WORK. HOWEVER, THIS SHALL
NOT BE CONSTRUED AS RELIEVING THE CONTRACTOR FROM
COMPLYING WITH ANY REQUIREMENTS OF THE DRAWINGS AND
SPECIFICATIONS THAT MAY BE IN EXCESS OF ANY GOVERNING CODES.
CONTRACTOR SHALL PAY ALL FEES AND RELATED CHARGES FOR PERMITS,
LICENSES, ETC., REQUIRED FOR INSTALLATION DESIGN SPECIFICATIONS
ALL CONSTRUCTION WORK SHALL BE PERFORMED IN A FIRST-CLASS
WORKMANLIKE MANNER AND SHALL BE IN GOOD AND USABLE CONDITION AT
THE DATE OF COMPLETION. CONTRACTOR SHALL REQUIRE PERSONS
PERFORMING SUCH WORK TO GUARANTEE THE SAME TO BE FREE FROM
DEFECTS IN WORKMANSHIP AND MATERIALS FOR ONE YEAR FROM THE DATE
OF COMPLETION THEREOF. CONTRACTOR SHALL ALSO REQUIRE ANY
SUCH PERSONS TO BE RESPONSIBLE FOR THE REPLACEMENT OR REPAIR
WITHOUT ADDITIONAL COST TO ANY AND ALL WORK DONE OR FURNISHED
BY OR THROUGH SUCH PERSONS WHICH SHALL BECOME DEFECTIVE WITHIN
ONE YEAR AFTER SUBSTANTIAL COMPLETION OF WORK. THE CORRECTION
OF SUCH WORK SHALL INCLUDE WITHOUT ADDITIONAL COST ALL EXPENSES
AND DAMAGES IN CONNECTION WITH SUCH REMOVAL, REPLACEMENT OR
REPAIR OF ANY PART OF THE WORK WHICH MAY BE DAMAGED OR
DISTURBED THEREBY.
A. CONTRACTOR RESPONSIBLE FOR ALL DEMOLITION IN ACCORDANCE WITH AND AS
REASONABLY IMPLIED WITHIN THE DRAWINGS TO PROVIDE A COMPLETE SYSTEM
INSTALLATION, AND SHALL VISIT THE SITE PRIOR TO BID TO CONFIRM DEMOLITION.
B. CONTRACTOR SHALL DISPOSE OF DEMOLISHED ITEMS PER DOC.
1. STRUCTURAL AND MISCELLANEOUS STEEL TO BE FURNISHED, FABRICATED, AND
ERECTED IN ACCORDANCE WITH THE APPLICABLE REQUIREMENTS OF THE AISC
SPECIFICATIONS FOR DESIGN, FABRICATION, AND ERECTION OF STRUCTURAL STEEL
BUILDING, 15TH EDITION, MANUAL OF STEEL CONSTRUCTION, AND THE AISC CODE
OF STANDARD PRACTICE.
2. ALL CONNECTIONS, JOINTS, AND FASTENERS UNLESS NOTED OTHERWISE SHALL
MEET THE REQUIREMENTS OF AISC SPECIFICATIONS FOR DESIGN, FABRICATION,
AND ERECTION OF STRUCTURAL BUILDINGS, 15TH EDITION, MANUAL OF STEEL
CONSTRUCTION, USING ASD, AND THE AISC CODE OF STANDARD PRACTICE.
3. STRUCTURAL AND MISCELLANEOUS STEEL:
a. WIDE FLANGE SHAPES & TEES CUT FROM WIDE FLANGE SHAPES - ASTM
A992 GRADE 50.
b. S-SHAPES, M-SHAPES, CHANNELS AND ANGLES - ASTM A572 GRADE 50.
c. PLATES - ASTM A572 GRADE 50.
d. STRUCTURAL TUBING - ASTM A500 GRADE C, 50 KSI.
e. HIGH STRENGTH BOLTS 3/4" DIAMETER - ASTM A325 TYPE 1, ASTM A563
GRADE DH HEAVY HEX NUTS, AND ASTM F436 TYPE STEEL WASHERS WITH A
HARDNESS OF 38 TO 45 H.C.. BOLTS, NUTS, AND WASHERS TO BE HOT DIP
GALVANIZED IN ACCORDANCE WITH ASTM F2329.
4. UNLESS NOTED OTHERWISE ALL BOLTED CONNECTIONS SHALL BE A325N BEARING
TYPE "N" CONNECTIONS IN ACCORDANCE WITH AISC 14TH EDITION HANDBOOK WITH
THREADS INTERCEPTED IN THE SHEAR PLANE. ALL BOLTED CONNECTIONS SHALL BE
PRE-TENSIONED USING THE TURN-OF-NUT METHOD. STANDARD SIZE HOLES SHALL
BE USED UNLESS NOTED OTHERWISE.
5. IN ALL CASES MINIMUM CONNECTION FOR POST, HANGER, OR BRACING SHALL BE:
a. TWO BOLTS FOR SINGLE ANGLES
b. THREE BOLTS FOR TEES (WEB CONNECTIONS)
c. FOUR BOLTS FOR TEES (FLANGE CONNECTIONS)
d. FOUR BOLTS PER FLANGE FOR WIDE FLANGE BRACING AND FOUR BOLTS FOR
WIDE FLANGE WEB CONNECTIONS.
e. TWO BOLTS IN DOUBLE SHEAR AND FOUR BOLTS IN SINGLE SHEAR FOR
DOUBLE ANGLES.
6. STRUCTURAL AND MISCELLANEOUS STEEL TO BE PAINTED IN ACCORDANCE WITH CLIENT
STANDARDS.
7. ALL WELD BACK UP BARS SHALL BE REMOVED AND GROUND SMOOTH AFTER WELD
IS COMPLETED, UNLESS NOTED OTHERWISE.
8. ALL WELDS INDICATED SHALL MEET THE MINIMUM WELD SIZE SPECIFIED BY THE AISC
MANUAL OF STEEL DESIGN (SINGLE PASS REQUIRED).
9. ALL WELDS SHALL BE PERFORMED BY QUALIFIED WELDERS IN ACCORDANCE WITH
A.W.S. SPECIFICATIONS, LATEST EDITIONS. ALL WELDING ELECTRODES SHALL
CONFORM TO A.W.S. A5.1 GRADE E-70. BARE ELECTRODES AND GRANULAR FLUX
SHALL CONFORM TO A.W.S. A5.17, F70 A.W.S. FLUX CLASSIFICATION.
10. ALL HOLES AND CUTS SHALL BE SHOWN ON THE SHOP DRAWINGS AND MADE IN THE
SHOP. CUTS OR BURNING OF HOLES IN STRUCTURAL STEEL MEMBERS IN THE FIELD
WILL NOT BE PERMITTED.
11. PROVIDE MINIMUM 1.5 INCHES OF NON-SHRINK, NON-METALLIC GROUT UNDER
BASE PLATES, UNLESS NOTED OTHERWISE.
12. FIELD WELDING SHALL BE IN ACCORDANCE WITH A.W.S. D1.1:2015 BY THE
AMERICAN WELDING SOCIETY.
13. PLATFORM GRATING
a. ERECTOR SHALL PURCHASE ENOUGH BAR GRATING MATERIAL, ACCESSORIES, AND APPURTENANCES TO PROVIDE QUANTITIES AND INSTALL
AS SHOWN IN THE DRAWINGS.
b. GRATING SPECIFICATION: MCNICHOLS BAR GRATING ITEM 6407310132 OR
APPROVED EQUAL.
c. STAIR TREAD SPECIFICATION: MCNICHOLS HEAVY-DUTY GRIP STRUT 2-DIAMOND
(9-1/4” WIDTH) 10 GAUGE WITH CP-PG-220-HD CARRIER PLATES.
14. STEEL SHOP DRAWING SUBMITTAL: SUBMIT DETAILED STRUCTURAL SET.
PROJECT GENERAL NOTES
PLANS AND SPECIFICATIONS
SHOP DRAWINGS
MODIFICATIONS
CODE COMPLIANCE
PERMITS, FEES, LICENSES
WARRANTY
DEMOLITION
DESIGN CODES AND STANDARDS
DESIGN LOADS
PAINT
2021 INTERNATIONAL BUILDING CODE, AS AMENDED AND ADOPTED BY THE STATE
OREGON.
A. ALL STEEL TO BE PAINTED OR GALVANIZED PER OREGON DOC STANDARDS.
B. ALL FRAMING SHALL BE PAINTED WHITE, TOE KICKS, HANDRAILS, AND
GUARDS SHALL BE PAINTED SAFETY RED.
FLOOR LIVE LOADS:
ASSEMBLY AREAS – PLATFORMS: 100 PSF
MECHANICAL EQUIPMENT - SEE PLAN FOR LOCATION AND MAGNITUDE.
GUARDRAILS - 50 PLF UNIFORM LOAD OR 200 LB CONCENTRATED LOAD.
STRUCTURAL STEEL NOTES
A. THESE DRAWINGS ARE NOT INTENDED FOR USE AS STEEL FABRICATORS "SHOP DRAWINGS."
THE CONTRACTOR SHALL OBTAIN QUALIFIED STEEL DETAILING SERVICES FOR SHOP
DRAWING PREPARATION IN ACCORDANCE WITH AISC'S CODE OF STANDARD PRACTICE FOR
STEEL BUILDINGS AND BRIDGES, AND WITH THE AISC STEEL CONSTRUCTION MANUAL, 15TH
EDITION. SHOP DRAWINGS SHALL BE SUBMITTED TO THE OWNER FOR REVIEW AND
APPROVAL PRIOR TO THE START OF FABRICATION.
B. SUBMIT SHOP DRAWING SCHEDULE WITH CONSTRUCTION SCHEDULE THAT INCLUDES
CONSIDERATION FOR REVIEW PERIOD.
C. GENERAL CONTRACTOR SHALL SUBMIT SHOP DRAWINGS IN DIGITAL FORMAT FOR
STRUCTURAL REVIEW. DIGITAL DRAWING SHALL MEET THE FOLLOWING REQUIREMENTS.
a. ADOBE EXTENSION (.PDF)
b. ALL PAGES ARE ROTATED, PRINTED TO SCALE.
c. ALL TRANSMITTALS SHALL BE LOCATED AS THE FIRST PAGE OF THE SUBMITTAL OR AS A
SEPARATE FILE WITHIN ONE DIGITAL PACKAGE.
d. CONTRACTOR DIGITAL REVIEW COMMENTS AND THEIR DIGITAL STAMP SHALL BE
ATTACHED. OUR REVIEW WILL NOT OCCUR UNTIL THE CONTRACTOR HAS REVIEWED,
COORDINATED WITH OTHER TRADES AND PROVIDED SHOP STAMP.
e. STRUCTURAL ENGINEER WILL MARK-UP THE DIGITAL SET IN RED AND RETURN A DIGITAL
FILE VIA EMAIL, FTP SITE OR OTHER MEANS.
C
D
Ridgefiled, WA.
Duluth + Minneapolis, MN.
www.windsorengineers.com
Copyright 2023 By Windsor Engineers, LLC All Rights Reserved.
LINE IS 1" ON FULL
SCALE DRAWING
CALL 2 BUSINESS DAYS BEFORE YOU DIG.
CAUTION UTILITY INFORMATION IS APPROXIMATE.
VERIFY ALL UTILITIES PRIOR TO CONSTRUCTION.
Revisions: #
Know what's below.
before you dig.Call
R
Issuance Summary:
2024-02-13 SCHEMATIC DESIGN / 30% - ISSUED FOR REVIEW
DULUTH, MN
218-491-6059
GILLETTE, WY
307-257-6275 info@jbwconsult.com www.jbwconsult.com
REMOVING BARRIERS
2024-02-23 DESIGN DEVELOPMENT / 90% - ISSUED FOR REVIEW
2024-02-29 CD / ISSUED FOR PERMIT / CONSTRUCTION
2024-04-12 CD / RE-ISSUED FOR PERMIT / CONSTRUCTION
S0
DOC OREGON BOILER BUILDING -
EXTERIOR EGRESS STAIRS
SALEM, OREGON
STRUCTURAL CONCRETE & STEEL NOTES
Project No: 23002.28 CAJ
JAR
EXTERIOR EGRESS STAIRS - SHEET LIST
SHEET NUMBER NAME REV DATE DESCRIPTION
S0 STRUCTURAL CONCRETE & STEEL NOTES D 11/08/24 OWNERS REVISIONS
S0.1 STEEL NOTES CONT'D A 04/12/24 RE-ISSUED FOR PERMIT/CONSTRUCTION
S1 EXTERIOR EGRESS PLATFORM - OVERALL LAYOUT PLAN D 11/08/24 OWNERS REVISIONS
S2 EXTERIOR EGRESS PLATFORM - FRAMING PLANS D 11/08/24 OWNERS REVISIONS
S3 EXTERIOR EGRESS PLATFORM - SECTIONS C 02/29/24 ISSUED FOR PERMIT/CONSTRUCTION
S4 EXTERIOR EGRESS PLATFORM - EXTERIOR DOOR ELEVATIONS C 11/08/24 OWNERS REVISIONS
S5 EXTERIOR EGRESS PLATFORM - DETAILS B 02/29/24 ISSUED FOR PERMIT/CONSTRUCTION
S6 EXTERIOR EGRESS PLATFORM - TYPICAL STAIR DETAILS B 02/29/24 ISSUED FOR PERMIT/CONSTRUCTION
S7 TYPICAL GUARDRAIL DETAILS B 02/29/24 ISSUED FOR PERMIT/CONSTRUCTION
S8 ISOMETRIC VIEWS B 02/29/24 ISSUED FOR PERMIT/CONSTRUCTION
C
A 02/23/24 ISSUED FOR 90% REVIEW
B 02/29/24 ISSUED FOR PERMIT/CONSTRUCTION
C 04/12/24 RE-ISSUED FOR PERMIT/CONSTRUCTION
D 11/08/24 OWNERS REVISIONS
D
D
D
11/12/2024
EXP. 12/31/2024
TABLE 1705.2 REQUIRED VERIFICATION AND
INSPECTION OF STEEL CONSTRUCTION
1. MATERIAL VERIFICATION OF HIGH-STRENGTH BOLTS, NUTS AND
WASHERS:
VERIFICATION AND INSPECTION CONTINUOUS PERIODIC REFERENCED STANDARDa
X
AISC 360, SECTION A3.3 AND APPLICABLE
ASTM MATERIAL STANDARDS
----- X -----
a. IDENTIFICATION MARKINGS TO CONFORM TO ASTM
STANDARDS AND SPECIFIED IN THE APPROVED
CONSTRUCTION DOCUMENTS
b. MANUFACTURER'S CERTIFICATE OF COMPLIANCE
REQUIRED.
2. INSPECTION OF HIGH-STRENGTH BOLTING:
----- X
AISC 360,
SECTION M2.5
----- X
a. SNUG-TIGHT JOINTS.
b. PRETENSIONED AND SLIP-CRITICAL JOINTS USING TURN-
OF-NUT WITH MATCHMARKING, TWIST-OFF BOLT OR
DIRECT TENSION INDICATOR METHODS OF INSTALLATION.
c. PRETENSIONED AND SLIP-CRITICAL JOINTS USING TURN-
OF-NUT WITHOUT MATCHMAKING OR CALIBRATED
WRENCH METHODS OF INSTALLATION.
X ----
3. MATERIAL VERIFICATION OF STRUCTURAL STEEL:
----- X
APPLICABLE ASTM MATERIAL STANDARDS----- X
a. FOR STRUCTURAL STEEL, IDENTIFICATION MARKINGS TO
CONFORM TO AISC 360.
b. FOR OTHER STEEL, IDENTIFICATION MARKINGS TO
CONFORM TO ASTM STANDARDS SPECIFIED IN THE
APPROVED CONSTRUCTION DOCUMENTS.
c. MANUFACTURER'S CERTIFIED TEST REPORTS. ----- X
4. MATERIAL VERIFICATION OF COLD-FORMED STEEL DECK:
----- Xa. MANUFACTURE'S CERTIFIED TEST REPORTS.
AISC 360,
SECTION N2.1
5. MATERIAL VERIFICATION OF WELD FILLER MATERIALS:
----- X
a. IDENTIFICATION MARKINGS TO CONFORM TO AWS
SPECIFICATION IN THE APPROVED CONSTRUCTION
DOCUMENTS.
b. MANUFACTURE'S CERTIFICATE OF COMPLIANCE REQUIRED. ----- X
AISC 360, SECTION A3.5 AND APPLICABLE
AWS A5 DOCUMENTS
6. INSPECTION OF WELDING:
a. STRUCTURAL STEEL AND COLD-FORMED STEEL DECK:
1. COMPLETE AND PARTIAL JOINT PENETRATION GROOVE
WELDS.
2. MULTIPASS FILLET WELDS.
3. SINGLE-PASS FILLET WELDS > 5/16"
4. PLUG AND SLOT WELDS
5. SINGLE-PASS FILLET WELDS > 5/16"
6. FLOOR AND ROOF DECK WELDS
a. REINFORCING STEEL:
1. VERIFICATION OF WELDABILITY OF REINFORCING STEEL
OTHER THAN ASTM A706.
2. REINFORCING STEEL RESISTING FLEXURAL AND AXIAL
FORCES IN INTERMEDIATE AND SPECIAL MOMENT
FRAMES, AND BOUNDARY ELEMENTS OF STRUCTURAL
WALLS OF CONCRETE AND SHEAR REINFORCEMENT.
3. SHEAR REINFORCEMENT.
X ----
AWS D1.1
X ----
X ----
X ----
---- X
---- X AWS D1.3
X ----
AWS D1.4
ACI 318 SECTION 26.6.4X ----
X ----
Ridgefiled, WA.
Duluth + Minneapolis, MN.
www.windsorengineers.com
Copyright 2023 By Windsor Engineers, LLC All Rights Reserved.
LINE IS 1" ON FULL
SCALE DRAWING
CALL 2 BUSINESS DAYS BEFORE YOU DIG.
CAUTION UTILITY INFORMATION IS APPROXIMATE.
VERIFY ALL UTILITIES PRIOR TO CONSTRUCTION.
Revisions: #
Know what's below.
before you dig.Call
R
Issuance Summary:
2024-02-13 SCHEMATIC DESIGN / 30% - ISSUED FOR REVIEW
DULUTH, MN
218-491-6059
GILLETTE, WY
307-257-6275 info@jbwconsult.com www.jbwconsult.com
REMOVING BARRIERS
2024-02-23 DESIGN DEVELOPMENT / 90% - ISSUED FOR REVIEW
2024-02-29 CD / ISSUED FOR PERMIT / CONSTRUCTION
2024-04-12 CD / RE-ISSUED FOR PERMIT / CONSTRUCTION
S0.1
DOC OREGON BOILER BUILDING -
EXTERIOR EGRESS STAIRS
SALEM, OREGON
STEEL NOTES CONT'D
Project No: 23002.28 CAJ
JAR
A 04/12/24 RE-ISSUED FOR PERMIT/CONSTRUCTION
4/12/2024
GG
HH
CC
BB
1'-0" 128'-0"
1'-0"
130'-0"
EXISTING
BUILDING
(N) EXT. EGRESS
STAIRS
S2
FF
DD
F.1
S4
1'-1"
(N) COLUMN GRID
(E) EDGE OF BUILDING
(E) EDGE OF BUILDING
CORNER OF (E)
BUILDING (FV)
(N) COLUMN
GRID
S2
Ridgefiled, WA.
Duluth + Minneapolis, MN.
www.windsorengineers.com
Copyright 2023 By Windsor Engineers, LLC All Rights Reserved.
LINE IS 1" ON FULL
SCALE DRAWING
CALL 2 BUSINESS DAYS BEFORE YOU DIG.
CAUTION UTILITY INFORMATION IS APPROXIMATE.
VERIFY ALL UTILITIES PRIOR TO CONSTRUCTION.
Revisions: #
Know what's below.
before you dig.Call
R
Issuance Summary:
2024-02-13 SCHEMATIC DESIGN / 30% - ISSUED FOR REVIEW
DULUTH, MN
218-491-6059
GILLETTE, WY
307-257-6275 info@jbwconsult.com www.jbwconsult.com
REMOVING BARRIERS
2024-02-23 DESIGN DEVELOPMENT / 90% - ISSUED FOR REVIEW
2024-02-29 CD / ISSUED FOR PERMIT / CONSTRUCTION
2024-04-12 CD / RE-ISSUED FOR PERMIT / CONSTRUCTION
S1
DOC OREGON BOILER BUILDING -
EXTERIOR EGRESS STAIRS
SALEM, OREGON
EXTERIOR EGRESS PLATFORM - OVERALL
LAYOUT PLAN
Project No: 23002.28 CAJ
JAR
SCALE 3/16" = 1'-0"
EXTERIOR STAIR OVERALL LAYOUT PLANN
TRUE
NORTH
N
PLAN
NORTH
A 02/13/24 ISSUED FOR 30% REVIEW
B 02/23/24 ISSUED FOR 90% REVIEW
C 02/29/24 ISSUED FOR PERMIT/CONSTRUCTION
D 11/08/24 OWNERS REVISIONS
D
19 20
C
S3
B
S3
A
S3
D
S3
/2
10" 3'-6" 1'-8"
17 18
10" CONCRETE SLAB
3" CLR
6'-0" 14'-5" 4'-0"
4" CONCRETE SLAB
E Q
E Q
9" 3'-3"
1'-0" 1'-1"
F.1
F.2 H
SS3X3X3/16
(TYP)
(E) BUILDING
T/SLAB= ( 186' - 11" )
T/BUILDING F.F. = ( 187' - 0" )
TYP
S5
A
S2
T/SLAB= ( 186' - 11" )
19 20
C
S3
B
S3
A
S3
D
S3
17 18
F.1
F.2
1'-0" 1'-1" 3'-6"
C10X15.3
C X
.3
C X
.3
C10X15.3
H
SS
3X 3X
3/
(T
YP
, B
EL
O W
DN
(O U
T T
O O
U T
/8
/2
/2
(E) BUILDING
(N) EXT DOOR -SEE
/DTL B SHT S4
T/MEZZANINE F.F. = ( 198' - 8" )
1 3/4" E/W SERRATED HDG GRATING
24 SF
SPAN
GRATING
T/STEEL = ( 198' - 6 1/4" )
D
D
S4
SLOPE AWAY FROM
SLAB (TYP)
SECTION
12" NON-FROST-SUSCEPTIBLE FILL
NATIVE SOIL OR
NON-FROST-SUSCEPTIBLE FILL
CONCRETE SLAB
-SEE PLAN FOR SIZE
SEE PLAN
T/SLAB
SEE PLAN
TYP
2" CLR
CONCRETE SLAB R/W #4
@ 1'-0" EA WAY
CENTERED IN SLAB
-SEE PLAN FOR SIZE
P L A
N
S E E
T Y P
M
IN
SHEET NOTES:
1. FOR TYPICAL STEEL CONNECTION DETAILS.
2. FOR STRUCTURAL STEEL NOTES.
3. FOR TYPICAL STAIR DETAILS.
4. FOR TYPICAL GUARDRAIL DETAILS.
SEE SHT S5
SEE SHT S0
SEE SHT S6
SEE SHT S7
Ridgefiled, WA.
Duluth + Minneapolis, MN.
www.windsorengineers.com
Copyright 2023 By Windsor Engineers, LLC All Rights Reserved.
LINE IS 1" ON FULL
SCALE DRAWING
CALL 2 BUSINESS DAYS BEFORE YOU DIG.
CAUTION UTILITY INFORMATION IS APPROXIMATE.
VERIFY ALL UTILITIES PRIOR TO CONSTRUCTION.
Revisions: #
Know what's below.
before you dig.Call
R
Issuance Summary:
2024-02-13 SCHEMATIC DESIGN / 30% - ISSUED FOR REVIEW
DULUTH, MN
218-491-6059
GILLETTE, WY
307-257-6275…