120488 O3 Solicitation Addendum Q&A Answers.pdf
PDF 197 KB Posted
- Attached to
- Annual Inspections, Testing, Maintenance, and Services of Fire Sprinkler Systems and Fire Extinguishers
- Solicitation number
- 120488 O3
- Issued by
- Blaine County, Nebraska
About this file
This document is a Solicitation Addendum (120488 O3) from the Nebraska Department of Correctional Services (NDCS) dated March 4, 2025, providing questions and answers for a solicitation to be opened on March 25, 2025, at 2:00 p.m. CST. The addendum addresses 22 specific questions related to fire sprinkler system inspections across NDCS facilities, with responses consistently directing bidders to refer to NDCS Attachment B (Annual Fire Sprinkler Inspection Reports) for detailed information. Key clarifications include removing the requirement to inspect heat detectors and confirming that a Cost Proposal has been posted to the website.
The addendum indicates that bidders seeking comprehensive details about fire sprinkler systems should review the Annual Fire Sprinkler Inspection Reports, which will provide specifics on system types, equipment quantities, and associated components such as fire department connections, backflow preventers, fire pumps, and other critical infrastructure. The document notes that the previously provided Excel sheet only indicates basic system types (wet/dry/pre-action/deluge) without providing granular details about system quantities or associated equipment. By referencing the annual inspection reports, potential vendors can obtain a more comprehensive understanding of the inspection requirements across NDCS facilities.
View the file
Other files
Show all 44
On GovTribe
Work with this file
- Download the original file
- Contacts named in this file
- Similar government files
- Ask GovTribe AI about this file
Text version
SPB Form 26 Effective 7-19-2024
SOLICITATION ADDENDUM 120488 O3
QUESTIONS AND ANSWERS
Date: March 4, 2025
To: All Bidders
From: Sam Franklin Nebraska Department of Correctional Services
RE: Addendum for RPF 120488 O3 to be opened March 25, 2025, at 2:00 p.m. CST
Questions and Answers
Following are the questions submitted and answers provided for the above-mentioned solicitation.
The questions and answers are to be considered as part of the solicitation. It is the responsibility of bidders to check the State Purchasing Bureau website for all addenda or amendments.
Question Number
RFP/ITB
Section
Reference
RFP/ITB
Page
Number
Question State Response
1. Total quantity and type of fire sprinkler systems at each facility
Refer to NDCS Attachment B.
Annual Fire Sprinkler Inspection Reports.
2. Are there any anti-freeze loops?
3. Are there any standpipes or hose connections?
4. Quantity of pressure switches (hi/low air)
5. Quantity of flow switches
6. Quantity of valve tamper and supervisory switches
7. V. Project Description and Scope
27-28 Quantity of inspector’s test connections
8. Are there Fire Department
Connections?
9. Quantity of main drains
Refer to NDCS Attachment B:
10. Quantity of gauges
11. Quantity of valves
12. Do the systems have backflow preventers that need to be inspected?
13. Quantity of Post Indicator Valves
14. Do the systems have any fire pumps? If so are they diesel or electric?
15. If there are fire pumps, do we need to include the monthly churn test?
16. Are there any private fire hydrants that need to be inspected?
Will you be able to provide the most recent annual fire sprinkler inspection forms for all the locations?
17. Will you be able to provide a copy of the most recent inspection forms?
Refer to NDCS Attachment B.
18. V. Project description and scope of work
27-28 Is it possible to receive the previous Annual inspection report for the fire sprinkler systems at each location?
This will allow us to know what systems and equipment are at each
Refer to NDCS Attachment B.
This addendum will be incorporated into the solicitation.
location. Equipment that is associated to each fire sprinkler system that would need to be inspected annually should be on each annual inspection report.
The equipment provided in the 120488 03 excel sheet for fire sprinkler systems in each location only provides that there is a wet/dry/pre-action/deluge system. But it does not include how many systems there are, or other equipment associated to the systems, such as FDC’s , backflow preventers, fire pumps, etc. All details would be found in previous annual inspection report.
20. V. Project description and Scope of work
28 The document mentions 17 heat detectors to be inspected. What locations have heat detectors that would need to be inspected at the time of the sprinkler inspection? (This would normally be completed at the time of the fire alarm inspection).
Heat Detectors do not need to be inspected. We have revised the RFP to remove this provision.
22. N. Solicitation requirements
12 In regards to the “cost sheet”, will a cost sheet be provided? Or should the bidder create their own cost sheet? (excel, pdf, etc.)?
The Cost Proposal is now posted to the website