This document appears to be an Asbestos Report for Building 24, related to a federal contract opportunity for the BUILDING 24 DISPATCH REMODEL project.

The project consists of remodeling specified areas of Building 24 at the Lolo National Forest Headquarters in Fort Missoula. The work includes remodeling the south wing on the upper floor to accommodate Missoula Dispatch, remodeling the front desk area, a single private office remodel in the north wing, minor exterior work such as gutters, and installing Linc Pass access control to all exterior doors. The solicitation number is 1122499 and the contracting agency is the Department of Agriculture Forest Service. No additional details on response dates, award dates, pricing terms, or set asides are provided in this document.

View the file

Other files for this federal contract opportunity

Show all 18

On GovTribe

Work with this file on GovTribe

  • Download the original file
  • Contacts named in this file
  • Similar government files
  • Ask GovTribe AI about this file

Text version

Project Number: IH 23-107 December 6, 2023

Abatement Contractors of Montana Specializes In:

Asbestos Abatement

Lead Based Paint Removal

Historical Renovation

General Construction & Remodel

Asbestos Inspections

Meth Lab Clean-up

Industrial Hygiene

Certification & Safety Training

Limited Inspection Report For Asbestos Containing Building Materials

Project Number:

IH 23-107

Subject Property:

USFS Building 24 Fort Missoula Rd.

Missoula, Montana 59804

Prepared For:

Mosaic 317 N. Cruse Ave.

Helena, Montana 59601

Prepared By:

Abatement Contractors of Montana

208 Commerce Street Missoula, Montana 59808

(406) 549-8489 www.acm-contracting.com

USFS Building 24 http://www.acm-contracting.com/

APPENDIX I ………………………...REPORT

APPENDIX II ………………………RESULTS

APPENDIX III …………………..DRAWINGS

APPENDIX IV …………….PHOTOGRAPHS

APPENDIX V ………………..CITY LETTER

APPENDIX I

REPORT

ABATEMENT CONTRACTORS OF MONTANA, LLC

208 Commerce St

Missoula, MT 59807 P 406-549-8489

F 406-728-9416

SPECIALTY CONSTRUCTION & ENVIRONMENTAL REMEDIATION SERVICES www.acm-contracting.com

January 2, 2024

Mosaic Attn: Matt Aune 317 N Cruiz Ave. Suite 201 Phone: (406) 459-6271 Helena, MT E-Mail: matta@mosaicarch.com

Subject: ACM Project Number IH-23-107 Limited Asbestos Inspection

USFS Building 24 Fort Missoula Rd.

Dear Mr. Aune:

Abatement Contractors of Montana, LLC (ACM) is pleased to provide this sampling report for a limited asbestos inspection conducted at the USFS Building 24 located at Fort Missoula Road in Missoula, Montana.

The asbestos inspection was performed on October 27 – December 19, 2023, by Brian Betts, MTA-1878, a Montana Department of Environmental Quality (DEQ)-accredited asbestos inspector. The results of this inspection can be found in the enclosed report.

INTRODUCTION

ACM collected a total of Two-Hundred-Eleven (211) bulk samples representing Sixty-Four (64) homogeneous areas (HA) of suspected asbestos-containing building materials (ACBM) in the concerned area(s) that will be impacted during the planned renovation within the subject property. Any materials found to contain greater than one percent (>1%) asbestos by weight are considered to be Asbestos Containing Building Materials (ACBM). This inspection considered all accessible areas of the building and ACM’s scope of work. This inspection was limited only to the materials that were readily accessible and only included those materials based on the information provided by the client during our site visit and/or phone conversations. All samples were collected from previously damaged or inconspicuous locations to help retain the aesthetics of the building for the occupants. Although ACM’s Inspector took every effort to evaluate all of the materials that will be impacted during the renovation, it is possible that other hidden materials may exist. Therefore, any materials that have not been discovered AND have not been specifically evaluated by bulk sampling in this inspection report must be tested and evaluated for asbestos content prior to disturbance of these materials. A complete list of all samples that were collected is located in Table 1.

The detailed laboratory results are presented in Appendix II. A diagram of the building indicating where samples were collected and a map showing where any asbestos containing materials are located is enclosed within Appendix III. Photographs of materials sampled and asbestos containing materials can be found in Appendix VI. The letter to the City of Missoula to obtain the necessary work permits can be found in Appendix V.

Some of the samples tested POSITIVE for asbestos. Positive samples are highlighted in BOLD in Table 1.

SCOPE OF INSPECTION

ACM was contracted by Mr. Aune of Mosaic to conduct a limited asbestos inspection for the planned renovation of the interior of Building 24 at fort Missoula in Missoula Montana.

INSPECTION

http://www.acm-contracting.com/

Inspection Number IH-23-107 Page 2 of 17 December 21, 2023

The limited asbestos inspection was performed in accordance with Occupational Safety and Health Administration 29 Code of Federal Regulations (CFR) 1926.1101(k), the Montana DEQ Administrative Rules of Montana (ARM) 17.74.354 and National Emission Standards for Hazardous Air Pollutants (NESHAP) 40 CFR 61, Subparts A and M, and applicable portions of the currently recognized standard protocol developed for schools under the Asbestos Hazard Emergency Response Act (AHERA) and as promulgated in Title 40, Code of Federal Regulations (40 CFR), Part 763 and as amended in the Federal Register. The SanAir Technologies Laboratory Analysis Report are enclosed for reference.

Representative bulk material samples were collected from the suspect asbestos-containing surfacing (S) materials, thermal system insulation (TSI) materials and miscellaneous (M) materials from each of the assigned homogeneous areas (HAs) that will be impacted at the time of the renovation. The suspect ACBM were visually identified and touched to assess friability prior to sampling. The samples were placed in HA groups using a coding method to classify each suspect ACBM by type, texture, color, era of installation and location. The asbestos inspection included:

Identification of HA suspect ACBM on an area-by-area basis within ACM’s scope of work;

Bulk samples were collected in discrete or previously damaged locations when possible;

Collection and analysis of bulk samples to confirm or deny the presence of asbestos.

Positive Stop methods were utilized in the laboratory analysis

Roofing materials were not sampled during this inspection to avoid any possible leaks and voidance of the roofs warranty

Vermiculite Insulation was assumed to be an asbestos containing material

Fire Doors were assumed to contain asbestos containing material

No other materials were presumed to be asbestos containing materials

Bulk samples were not collected from any materials that are made of 100% metal, wood, foam, glass or rubber.

Vermiculite is present in the attic and also sporadically distributed on top of 2nd floor 2x4 ceiling tiles and 2x4 light fixtures. Ceiling tiles should not be moved/disturbed on the 2nd floor. Due to the nature of Vermiculite and the uncertainties in the variations with testing techniques, it has been assumed that this material contains asbestos. Removal of this material should be accomplished by an accredited abatement contractor who will properly remove the material, containerize it in the recommended containers and dispose of at a certified landfill.

Pipe Insulation (MAG) Sample # AB 182-184 were sampled from debris West of South attic access, the same insulation is present on one pipe approx. 8ft West of attic access encased in wall. Review of previous inspection report dated in 1994 shows this pipe and two pipes encased in wall near North attic access, North Pipes were not located but must be assumed to be still present. Pipe insulation may also be present in other areas such as pipe chases, walls, above ceiling tile.

Floor Tile & mastic multiple samples were positive for asbestos. Entire 2nd floor, North and West Wing of 1st floor, South wing E half basement. This building was occupied at the time of inspection with the inspector taken samples in discreet areas, and as not to cause trip hazards. Additional verifications/ quantities of tile& mastics should be performed prior to remodel. All infilled walls appear to be over tile, also exterior added walls, bottom wall plates should not be removed by general contractor, if walls are to be removed, Ceramic tiles, floor and walls in basement restrooms were not tested.

Vibration Dampeners sample # AB 188-190 cloth dampeners on old Exhaust fan ducting in attic north and south wings, neither of the two fans on the duct work were in operation when the inspector was in the attic.

Mastic/ Roofing tar Sample # AB 200-202 Roofing tar that has dripped from the duct roof penetration.

The inspector believes he witnessed the reroofing of building 24 and adjacent building 26 in approx. 2012.

The tar appears to be the original, and it appears now to have a self-adhesive flashing paper round the duct work under the roof tiles.

Inspection Number IH-23-107 Page 3 of 17 December 21, 2023

Fire Doors assumed to contain Asbestos, further investigation May be needed (if the door contains asbestos it is not visible).

Gaskets inspection performed on May 18th 2023 ,ACM 23-046 Showed that boiler room Breaching gaskets (2 EA) contain 80% C Asbestos.

Roofing materials were not sampled during this inspection. These roofing materials can be sampled at a later date under a separate contract when the assistance of the Client’s roofing contractor is available to repair the sample locations to avoid leaks and/or voidance of the current warranty.

A minimum of three (3) suspect ACBM samples were collected from random locations within the subject area. Selected suspect ACBM were limited to HA that will be impacted at the time of the renovation. When possible, suspect ACBM samples were collected from existing damaged areas. These samples were placed in pre-labeled plastic containers for shipment to the laboratory. Although every attempt was made to identify and sample suspect ACBM within ACM’s scope of services, any materials that have not been specifically evaluated by bulk sampling in this inspection must be tested prior to disturbance of these materials.

The samples were shipped, under chain-of-custody protocol for standard analyses, to SanAir Technologies Laboratory (NVLAP Lab # 200870-0) in Pawhatan, Virginia for bulk sample analysis utilizing Polarized Light Microscopy (PLM) coupled with dispersion staining for asbestos identification. The ‘Positive Stop’ method was utilized in the laboratory analysis where if a sample from a single homogenous area, asbestos is present, the rest of the samples for that homogenous area are not analyzed. However, if the sample analysis does not indicate that asbestos is present, the laboratory will continue to analyze the rest of the samples for that homogenous area. The detailed laboratory results are presented in Appendix II.

Materials in the following table that are highlighted in BOLD were found to be asbestos containing.

Table 1. Suspect ACBM that were identified, collected, shipped and analyzed at the laboratory.

Sample Number

Homogenous Area Number

Sample

Description

Location of Sample Collection

Percent of

Asbestos

Condition

Category

Quantity

SF / LF /

EA

Response Action

AB-01 M-1

12x12 Vinyl

Tile Off White with

Black Dots, Mastic Yellow

Basement Lunchroom

ND N/A N/A N/A AB-02 Basement Room 120

AB-03 Basement Lunchroom

AB-04

M-2

Carpet Green and Tan

Speckled, Mastic Yellow

Basement Lunchroom

ND N/A N/A N/A AB-05 Basement Hall by Room 105

AB-06 Basement Hall by Room 123

AB-07

M-3

Carpet Light Green, Basement Room 105 Good

CAT I ~1600 SF

Removal by an

Accredited

Inspection Number IH-23-107 Page 4 of 17 December 21, 2023

Sample Number

Homogenous Area Number

Sample

Description

Location of Sample Collection

Percent of

Asbestos

Condition

Category

Quantity

SF / LF /

EA

Response Action

AB-08

Mastic

Basement Room 127 3% C Mastic

Non- Friable

Abatement Contractor

Prior to Demolition Renovation

AB-09 Basement Room 128

AB-10

M-4 Cove Base

Tan, Mastic

Tan

Basement Lunchroom

ND N/A N/A N/A AB-11 Basement Storage Room

AB-12 Basement Room 120

AB-13

M-5 Carpet Gray, Mastic Yellow

South Wing in Basement

ND N/A N/A N/A AB-14 South Wing in Basement

AB-15 South Wing in Basement

AB-16

M-6 Carpet Tan, Mastic Yellow

South Wing Basement

ND N/A N/A N/A AB-17 South Wing Basement

AB-18 South Wing Basement

AB-19 M-7

Vinyl Floor

Tile Tan, Mastic Yellow

Under MS and M6 in Basement

2% C Vinyl Floor

Good

CAT I

Non-

Friable

~2016 SF

Removal by an

Accredited Abatement Contractor

Prior to Demolition Renovation

AB-20

Under MS and M6 in

Basement

AB-21

Under MS and M6 in

Basement

AB-22

Ceiling Tile, Large Fissure

(Wide) 2x2

South Wing Basement

ND N/A N/A N/A AB-23 South Wing Basement

AB-24 South Wing Basement

Inspection Number IH-23-107 Page 5 of 17 December 21, 2023

Number

Homogenous Area Number

Sample

Description

Location of Sample Collection

Percent of

Asbestos

Condition

Category

Quantity

SF / LF /

EA

Response Action

AB-25

M-9 Ceiling Tile 2x4

Pinholes No Fissures

Basement IT Room South Wing

ND

N/A

N/A N/A AB-26

Basement IT Room South

Wing

AB-27

Basement IT Room South

Wing

AB-28

M-10 Carpet

Squares Mastic

Floor fFill

1st Floor North Wing Over Ceramic

N/A AB-29

1st Floor North Wing Under Ceramic

AB-30

1st Floor North Wing Under

Ceramic

AB-31

M-11 Ceramic Tile

6x6 Red

Under M-10

ND N/A N/A N/A AB-32 Under M-10

AB-33 Under M-10

AB-34

M-12 Grout Gray

N/A N/A AB-35 Under M-10

AB-36 Under M-10

AB-37

M-13 Mortar/

Concrete

N/A N/A N/A AB-38 Under M-10

AB-39 Under M-10

AB-40 M-14

Carpet Blue

Mastic Yellow

North Wing Over M-11, M- 12, M-13

ND N/A N/A N/A

AB-41

North Wing Over M-11, M-

12, M-13

Inspection Number IH-23-107 Page 6 of 17 December 21, 2023

Number

Homogenous Area Number

Sample

Description

Location of Sample Collection

Percent of

Asbestos

Condition

Category

Quantity

SF / LF /

EA

Response Action

AB-42

North Wing Over M-11, M-

12, M-13

AB-43

M-15 Carpet Tan

Mastic yellow

1st Floor North Wing

N/A N/A AB-44 1st Floor North Wing

AB-45 1st Floor North Wing

AB-46

M-16 Floor Tile tan

Mastic Black

Under M-15 3% C

Floor Tile

2% Mastic Black

Good

CAT I

NON-

Friable

~3,256SF

Removal by an

Accredited Abatement Contractor

Prior to Demolition Renovation

AB-47 Under M-15

AB-48 Under M-15

AB-49

M-17

Carpet Mastic Yellow Vinyl Floor

Tile Tan

Mastic Black Fiberboard

1st floor North Wing 3% C

Floor tile

< 1% C black

Good

CAT I

Non-

Friable

Quantity included

With M-16

Removal by an

Accredited Abatement Contractor

Prior to Demolition Renovation

AB-50 1st Floor North Wing

AB-51 1st Floor North Wing

AB-52

M-18

Carpet Square Blue

Mastic Yellow Mastic Black?

on Fiberboard

1st Floor North Wing

2% C Mastic black

Good

CAT I

Non-

Friable

Quantity included

With M-16

Accredited Abatement Contractor

Prior to Demolition Renovation

AB-53 1st Floor North Wing

AB-54 1st Floor North Wing

AB-55

M-19

Carpet Tan Mastic Yellow Vinyl Floor

Tile White

Mastic Black on Fiberboard

1st floor North Wing to West Wing 3% C

Floor tile

2% C

Black

Good

CAT I

Non-

Friable

Quantity included

M-16

Accredited Abatement Contractor

Prior to Demolition Renovation

AB-56

1st Floor North Wing to

West Wing

AB-57

1st Floor North Wing to

West Wing

AB-58

M-20

Cove Base Brown

1st floor North Wing to West Wing Office

ND N/A N/A N/A

Inspection Number IH-23-107 Page 7 of 17 December 21, 2023

Number

Homogenous Area Number

Sample

Description

Location of Sample Collection

Percent of

Asbestos

Condition

Category

Quantity

SF / LF /

EA

Response Action

AB-59

Mastic Brown

1st Floor North Wing to West Wing Office

AB-60

1st Floor North Wing to West

Wing Office

AB-61

M-21

Carpet Squares

Blue Mastic Clear, Yellow Vinyl Floor

Tile White Mastic

Black

West Wing Hall 3% C

Floor tile

2% C Mastic Black

Good

CAT I

Non-

Friable

~2,422SF

Removal by an

Accredited Abatement Contractor

Prior to Demolition Renovation

AB-62 West Wing Office

AB-63 West Wing Office

AB-64

M-22 Fiberboard

Mastic?

West Wing Under M-21

2% C Mastic Black

Good

CAT I

Non-

Friable

~2,422SF

Assumed On fir tongue

Groove

Floor

Removal by an

Accredited Abatement Contractor

Prior to Demolition Renovation

AB-65 West Wing Under M-21

AB-66 West Wing Under M-21

AB-67

M-23

Carpet Green

Mastic Yellow Wood

Mastic Black?

Reception

ND N/A N/A N/A AB-68 Reception

AB-69 Reception

AB-70

M-24 Carpet

Squares 12x12

Reception entry E

ND N/A N/A N/A AB-71 Reception entry W

AB-72 Reception Entry W

AB-73

M-25

Carpet Grey Diamond

Pattern, Mastic Yellow, Fiberboard, Black Mastic?, Wood

South Wing

ND N/A N/A N/A AB-74 South Wing

AB-75 South Wing

Inspection Number IH-23-107 Page 8 of 17 December 21, 2023

Number

Homogenous Area Number

Sample

Description

Location of Sample Collection

Percent of

Asbestos

Condition

Category

Quantity

SF / LF /

EA

Response Action

AB-76

M-26

Cove Base White, Mastic

Closet South Wing

ND N/A N/A

AB-77 Men’s Restroom South Wing

AB-78

Women’s Restroom South

Wing

AB-79

M-27

2x4 Ceiling Tile Fat Fissure, Pinhole

South Wing

AB-80 South Wing

AB-81 South Wing

AB-82

M-28

2x4 Ceiling Tile Pinhole No

Fissure

Basement South Side

AB-83 Basement South Side

AB-84 Basement South Side

AB-85

M-29

Ceiling Tile Medium Fissure

West Wing

N/A N/A N/A AB-86 West Wing

AB-87 West Wing

AB-88

M-30

Seam Sealant

HVAC

South Wing

N/A N/A AB-89 West Wing

AB-90 North Wing

AB-91

M-31

Vinyl Sheet Flooring

Off White, South Wing Custodian

ND N/A N/A N/A

AB-92 Men’s Room

Inspection Number IH-23-107 Page 9 of 17 December 21, 2023

Number

Homogenous Area Number

Sample

Description

Location of Sample Collection

Percent of

Asbestos

Condition

Category

Quantity

SF / LF /

EA

Response Action

AB-93

Mastic Yellow Men’s Room

AB-94 M-32

Carpet Tan, Mastic Yellow, Gypcrete

South Wing East End

ND N/A N/A N/A AB-95 South Wing East End

AB-96 South Wing East End

AB-97 M-33

Carpet Blue, Mastic Yellow, Black on Concrete

South Wing Stair to Basement

ND N/A N/A N/A AB-98

South Wing Door to mechanical (No Black Mastic on Ceramic Tile)

AB-99

South Wing Office (No Black

Mastic- Floor Fill Grey)

AB-100 M-34

Carpet Blue, Mastic Yellow, Fiberboard, Wood

Hall

ND N/A N/A N/A AB-101 Hall

AB-102

Hall (With Paper Under

Wood)

AB-103

M-35

Carpet Grey, Mastic Yellow

South Wing Staircase (Landing with Concrete)

ND N/A N/A N/A AB-104

South Wing Staircase (Stairs on Wood)

AB-105

South Wing Staircase (Stairs on Wood)

AB-106 M-36

Carpet (Blue, Brown, Tan Dots), Mastic Yellow, Vinyl Floor

Second Floor North Wing 4% C Floor Tile

2% C Mastic Black

Good

CAT I

Non-

Friable

~14,166

SF

Removal by an

Accredited Abatement Contractor

Prior to Demolition

AB-107 Closet

Inspection Number IH-23-107 Page 10 of 17 December 21, 2023

Number

Homogenous Area Number

Sample

Description

Location of Sample Collection

Percent of

Asbestos

Condition

Category

Quantity

SF / LF /

EA

Response Action

AB-108

Tile, Black Mastic, Fiberboard Hall

AB-109

M-37

Carpet Tan, Yellow, Vinyl Floor Tile, Mastic Black, Fiberboard, Mastic?

Conference Storage Room

3% C Floor Tile

2% C Mastic Black

Good

CAT I

Non-

Friable

Quantity included

M-36

Accredited Abatement Contractor

Prior to Demolition Renovation

AB-110 Conference Storage Room

AB-111

Conference Room Entry

(Carpet Blue)

AB-112

M-38

6 Inch Cove Base Dark

Brown, Mastic Yellow

Second Floor North Wing Curve Wall

ND N/A N/A N/A AB-113

Second Floor North Wing

Curve Wall

AB-114

Second Floor North Wing

Curve Wall

AB-115

M-39

4 Inch Cove Base Brown, Mastic Brown

Storage Room North Wing (Attic Access)

ND N/A N/A N/A AB-116

Storage Room North Wing

(Attic Access)

AB-117

Storage Room North Wing (Attic Access)

AB-118

M-40

9x9 Vinyl Floor Tile, Mastic Black

Storage Room North Wing (Attic Access)

3% C Floor Tile

2% C Mastic Black

Good

CAT I

Non-

Friable

Quantity included

Accredited Abatement Contractor

Prior to Demolition Renovation

AB-119

Storage Room North Wing

(Attic Access)

AB-120

Storage Room North Wing

(Attic Access)

AB-121

M-41

Carpet Tan, Mastic Yellow, White Vinyl Floor Tile, Mastic Black

Second Floor North Wing 2% C Vinyl Floor

Tile

6% C

Black

Good

CAT I

Non-

Friable

Quantity included

Accredited Abatement Contractor

Prior to

AB-122

Second Floor North Wing

(With Fiberboard)

AB-123

Second Floor North Wing

(Closet)

Inspection Number IH-23-107 Page 11 of 17 December 21, 2023

Number

Homogenous Area Number

Sample

Description

Location of Sample Collection

Percent of

Asbestos

Condition

Category

Quantity

SF / LF /

EA

Response Action

AB-124

M-42

Carpet

Gray Diamond Mastic Yellow Vinyl Floor Tile Mastic Black Fiberboard

2nd Floor W. Wing

ND N/A N/A N/A AB-125 2nd Floor W. Wing

AB-126 2nd Floor W. Wing

AB-127

M-43

Carpet Square

Blue Mastic Yellow Vinyl Floor

Tile White, Green

Stripes Mastic Black Fiberboard

2nd Floor S. Wing

2% C Vinyl Floor

Tile

Good

CAT I

Non-

Friable

Quantity included

Accredited Abatement Contractor

Prior to

AB-128 2nd Floor S. Wing

AB-129 2nd Floor S. Wing

AB-130

M-44

Carpet Blue, Tan, Maroon Mastic Yellow

Vinyl Floor Tile

Rose Mastic

Floor Fill

2nd Floor S. Wing

2% C Vinyl Floor

Tile

Good

CAT I

Non-

Friable

Quantity included

Accredited Abatement Contractor

Prior to

AB-131 2nd Floor S. Wing

AB-132 2nd Floor S. Wing

AB-133

M-45

Glazing Gray

Window 2nd Floor S. Wing

<1% C glazing

N/A N/A Follow

OSHA

Regulations AB-134 Window 2nd Floor W. Wing

AB-135 Window 2nd Floor N. Wing

AB-136

S-1 Drywall

Mud Tape

2nd Floor S. Wing E. End

ND N/A N/A N/A AB-137 2nd Floor S. Wing E. End

AB-138 2nd Floor S. Wing E. End

AB-139

S-2

Drywall Mud

2nd Floor S. Wing W. End ND

Inspection Number IH-23-107 Page 12 of 17 December 21, 2023

Number

Homogenous Area Number

Sample

Description

Location of Sample Collection

Percent of

Asbestos

Condition

Category

Quantity

SF / LF /

EA

Response Action

AB-140

Tape

2nd Floor S. Wing W. End

AB-141 2nd Floor S. Wing W. End

AB-142

S-3 Drywall

Mud Tape

2nd Floor W. Wing

N/A AB-143 2nd Floor W. Wing

AB-144 2nd Floor W. Wing

AB-145

S-4 Drywall

Mud Tape

2nd Floor N. Wing E. End

ND N/A

N/A AB-146 2nd Floor N. Wing E. End

AB-147 2nd Floor N. Wing E. End

AB-148

S-5 Drywall

Mud Tape

Smooth

2nd Floor N. Wing (Hardlid Area)

ND N/A N/A N/A AB-149

2nd Floor N. Wing (Hardlid

Area)

AB-150

2nd Floor N. Wing (Hardlid

Area)

AB-151

S-6 Drywall

Mud Tape

Smooth

2nd Floor N. Wing W. End

ND N/A N/A N/A AB-152 2nd Floor N. Wing W. End

AB-153 2nd Floor N. Wing W. End

AB-154

S-7

Plaster Gray

Skim Coat White

2nd Floor S. Wing

ND N/A N/A N/A AB-155 2nd Floor S. Wing

AB-156 1st Floor N. Wing

Inspection Number IH-23-107 Page 13 of 17 December 21, 2023

Number

Homogenous Area Number

Sample

Description

Location of Sample Collection

Percent of

Asbestos

Condition

Category

Quantity

SF / LF /

EA

Response Action

AB-157 1st floor N. Wing

AB-158 Basement N. Wing

AB-159 Basement S. Wing

AB-160 Boiler room

AB-161

S-8

Drywall, Mud, Tape

1st Floor S. Wing E. End

AB-162 1st Floor S. Wing E. End

AB-163 1st Floor S. Wing E. End

AB-164

S-9

1st Floor S. Wing

N/A N/A N/A AB-165 1st Floor S. Wing

AB-166 Men’s Restroom

AB-167

S-10

1st Floor W. Wing

N/A N/A N/A AB-168 1st Floor W. Wing

AB-169 1st Floor W. Wing

AB-170

S-11

1st Floor N. Wing

N/A N/A

AB-171 1st Floor N. Wing

AB-172 1st Floor N. Wing

AB-173

S-12

Basement W. Wing ND N/A

Inspection Number IH-23-107 Page 14 of 17 December 21, 2023

Number

Homogenous Area Number

Sample

Description

Location of Sample Collection

Percent of

Asbestos

Condition

Category

Quantity

SF / LF /

EA

Response Action

AB-174

Tape

Basement W. Wing

AB-175 Basement W. Wing

AB-176

S-13

Drywall, Mud, Tape

Basement W. Wing

ND N/A N/A N/A AB-177 Basement W. Wing

AB-178 Basement W. Wing

AB-179

S-14

Drywall, Mud, Tape

Basement N. Wing

ND N/A N/A N/A AB-180 Basement N. Wing

AB-181 Basement N. Wing

AB-182

TS1-1

Insulation Pipe Debris

(Mag)

South Attic (N. of Access)

20% A 2% C

Poor

RACM

Friable

Uknown Pipe chases Encased in walls

Removal by an

Accredited Abatement Contractor

Prior to Demolition Renovation

AB-183 South Attic (N. of Access)

AB-184 South Attic (N. of Access)

AB-185

TS1-2

Insulation Pipe Fiberglass, (Newer) Paper, paint

Attic

ND N/A N/A N/A AB-186 Attic

AB-187 Attic

AB-188

M-46

Cloth Vibration

Dampener

South Attic (West of Access)

(also in West attic)

20% C Cloth

Good

CAT I

Non-

Friable

~12 SF

Removal by an

Accredited Abatement Contractor

Prior to Demolition Renovation

AB-189

South Attic (West of

Access)

AB-190

South Attic (West of

Access)

Inspection Number IH-23-107 Page 15 of 17 December 21, 2023

Number

Homogenous Area Number

Sample

Description

Location of Sample Collection

Percent of

Asbestos

Condition

Category

Quantity

SF / LF /

EA

Response Action

AB-191

M-47

Insulation Foil Faced

Attic

ND N/A N/A N/A AB-192 Attic

AB-193 Attic

AB-194

M-48

Insulation Black Paper

Faced

Attic

ND N/A N/A N/A AB-195 Attic

AB-196 Attic

AB-197

M-50 Insulation Fiberglass Tan paper faced

Attic

AB-198 Attic

AB-199 Attic

AB-200

M-50 Sealant

(tar) black

Attic Duct work penetrating roof (dripped down from exterior sealing)

8% C Tar

Sealant

Good

CAT I

Non-

Friable

~10 SF

Removal by an

Accredited Abatement Contractor

Prior to Demolition Renovation

AB-201

Attic Duct work penetrating roof (dripped down from exterior sealing)

AB-202

Attic Duct work penetrating roof (dripped down from exterior sealing)

AB-203

TSI-3

Insulation

Paper wrapped Black mastic fiberglass

Interstitial space between 1st and 2nd floor

ND N/A N/A N/A AB-204

Interstitial space between 1st and 2nd floor

AB-205

Interstitial space between 1st and 2nd floor

AB-206

TSI-4

Insulation Cloth rapped

Interstitial space between 1st and 2nd floor

Inspection Number IH-23-107 Page 16 of 17 December 21, 2023

Number

Homogenous Area Number

Sample

Description

Location of Sample Collection

Percent of

Asbestos

Condition

Category

Quantity

SF / LF /

EA

Response Action

AB-207

fiberglass

Interstitial space between 1st and 2nd floor

AB-208

Interstitial space between 1st and 2nd floor

AB-209

TSI-5

Mudded

Pipe insulation elbow

Interstitial space between 1st and 2nd floor

AB-210

Interstitial space between 1st and 2nd floor

AB-211

Interstitial space between 1st and 2nd floor

Vermiculite Attic and on top of 2nd floor ceiling tiles

Assumed Not tested as per EPA Guidelines

Friable

RACM

~14,166

SF

Removal by an

Accredited Abatement Contractor

Prior to Demolition Renovation

Firedoors Throughout Assumed Not tested

Friable

RACM

Uknown

Removal by an

Accredited Abatement Contractor

Prior to Demolition

10-12

Gasket Breaching Sampled 5-18-2023

ACM IH 23-

Boiler room Breaching 80% C Gasket

Good

CAT I

Non-

Friable

2EA

8 LF

Removal by an

Accredited Abatement Contractor

Prior to Demolition Renovation

LEGEND

ND None Detected N/A Not Applicable LF Linear Feet SF Square Feet EA Each S Surfacing Material M Miscellaneous TSI Thermal System Insulation C Chrysotile A Amosite RACM Regulated Asbestos Containing Material

Our inspection has revealed the presence of ACM at the subject property. This inspection was limited to the materials which will be impacted at the time of renovation and may not have located any potentially hidden ACBM within the subject property. However, we have taken every effort to sample all obvious and accessible suspect materials within the scope of this inspection. Most of these materials appeared to be in a good condition at the time of our inspection.

ACM recommends that any materials highlighted in BOLD in Table 1 above shall be removed by an accredited abatement contractor prior to disturbance of these materials. These materials should be handled, Inspection Number IH-23-107 Page 17 of 17 December 21, 2023 containerized and disposed of according to State and Federal Regulations. Quantities of the above mentioned materials are estimates only. The abatement contractor should verify all quantities prior to bidding work.

Limitations

This asbestos inspection summary was prepared based on information gathered during our site visit, phone conversations and interpretations of laboratory results of bulk samples collected during the inspection. The inspection was limited to accessible areas within the structure. All samples were collected from previously damaged or inconspicuous locations to help retain the aesthetics of the building for the occupants. Although ACM’s Inspector took every effort to evaluate all of the materials that will be impacted during the renovation, it is possible that other hidden materials may exist. Therefore, any materials that have not been discovered AND have not been specifically evaluated by bulk sampling in this inspection report must be tested and evaluated for asbestos content prior to disturbance of these materials. Additional sampling may be required if additional HA’s are exposed during material removal, or the scope of work is expanded to include HA’s that have not been inspected or analyzed for asbestos content.

Any ACBM that might be impacted during renovation activities must be addressed prior to start of such activities by a qualified and accredited abatement company.

Abatement Contractors of Montana (ACM) greatly appreciates this opportunity to assist Mosaic and look forward to providing our services to you on future projects. If you have any questions regarding this sampling report, please call us at 406-549-8489. We look forward to working with you in the future.

Sincerely, Brian Betts

Montana DEQ-Accredited Asbestos Inspector: MTA-1878

Enclosures:

SanAir Technologies Laboratory Analysis Report Sample Location Diagrams Positive ACBM Location Diagrams Photographs City Permit Letter

APPENDIX II

ANALYTICAL RESULTS

SanAir ID#: 23068520

Project #: IH23-107 Project Name: USFS Bldg. 24 Report Date: 12/21/2023

Analysis Report prepared for Abatement Contractors of Montana, LLC

Dear Brian Betts, We at SanAir would like to thank you for the work you recently submitted. The 48 sample(s) were received on Thursday, December 14, 2023 via UPS. The final report(s) is enclosed for the following sample(s): AB-01, AB-02, AB-03, AB-04, AB-05, AB-06, AB-07, AB-08, AB-09, AB-10, AB-11, AB-12, AB-13, AB-14, AB-15, AB-16, AB-17, AB-18, AB-19, AB-20, AB-21, AB-22, AB-23, AB-24, AB-25, AB-26, AB-27, AB-28, AB-29, AB-30, AB-31, AB-32, AB-33, AB-34, AB-35, AB-36, AB-37, AB-38, AB-39, AB-40, AB-41, AB-42, AB-43, AB-44, AB-45, AB-46, AB-47, AB-48.

These results only pertain to this job and should not be used in the interpretation of any other job. This report is only complete in its entirety. Refer to the listing below of the pages included in a complete final report.

Sincerely, Maureen Y. Haley Asbestos Laboratory Manager SanAir Technologies Laboratory

Final Report Includes:

- Cover Letter

- Analysis Pages

- Disclaimers and Additional Information

Sample conditions:

- 48 samples in Good condition.

11709 Chesterdale Rd., Cincinnati, OH 45246 | 513.438.6006 | Fax: 804.897.1177 | www.SanAir.com | IAQ@SanAir.com

IH23-107Project Number:

P.O. Number:

Project Name: USFS Bldg. 24

10/27/2023Collected Date:

12/14/2023 12:00:00 PMReceived Date:

12/21/2023 5:26:48 PM

23068520 SanAir ID Number

FINAL REPORT

Abatement Contractors of Montana, LLCName:

Address: 208 Commerce St.

Missoula, MT 59808

406-549-8489Phone:

Analyst: Farnsworth-Pinkerton, Shoshauna

Asbestos Bulk PLM EPA 600/R-93/116 Stereoscopic Components

SanAir ID / Description Appearance % Fibrous % Non-fibrous Asbestos Fibers

AB-01 / 23068520-001

Vinyl Floor Tile 12x12 Mastic Basement Lunch Rm., Floor Tile

Off-White Non-Fibrous

Homogeneous

100% Other None Detected

AB-01 / 23068520-001

Vinyl Floor Tile 12x12 Mastic Basement Lunch Rm., Mastic

Yellow Non-Fibrous

Homogeneous

100% Other None Detected

AB-02 / 23068520-002

Vinyl Floor Tile 12x12 Mastic Basement Rm 120, Floor Tile

Off-White Non-Fibrous

Homogeneous

100% Other None Detected

AB-02 / 23068520-002

Vinyl Floor Tile 12x12 Mastic Basement Rm 120, Mastic

Yellow Non-Fibrous

Homogeneous

100% Other None Detected

AB-03 / 23068520-003

Vinyl Floor Tile 12x12 Mastic Basement Lunch Rm., Floor Tile

Off-White Non-Fibrous

Homogeneous

100% Other None Detected

AB-03 / 23068520-003

Vinyl Floor Tile 12x12 Mastic Basement Lunch Rm., Mastic

Yellow Non-Fibrous

Homogeneous

100% Other None Detected

AB-04 / 23068520-004

Carpet Mastic Basement Lunch Rm., Carpet

Various Fibrous

Homogeneous

80% Synthetic 20% Other None Detected

AB-04 / 23068520-004

Carpet Mastic Basement Lunch Rm., Mastic

Yellow Non-Fibrous

Homogeneous

100% Other None Detected

AB-05 / 23068520-005

Carpet Mastic Basement Hall By Rm. 105, Carpet

Various Fibrous

Homogeneous

80% Synthetic 20% Other None Detected

AB-05 / 23068520-005

Carpet Mastic Basement Hall By Rm. 105, Mastic

Yellow Non-Fibrous

Homogeneous

100% Other None Detected

Analyst:

Analysis Date: 12/21/2023 Date: 12/21/2023

Approved Signatory:

IH23-107Project Number:

P.O. Number:

Project Name: USFS Bldg. 24

10/27/2023Collected Date:

12/14/2023 12:00:00 PMReceived Date:

12/21/2023 5:26:48 PM

23068520 SanAir ID Number

FINAL REPORT

Abatement Contractors of Montana, LLCName:

Address: 208 Commerce St.

Missoula, MT 59808

Stereoscopic Components

SanAir ID / Description Appearance % Fibrous % Non-fibrous Asbestos Fibers

AB-06 / 23068520-006

Carpet Mastic Basement Hall 123, Carpet

Various Fibrous

Homogeneous

80% Synthetic 20% Other None Detected

AB-06 / 23068520-006

Carpet Mastic Basement Hall 123, Mastic

Yellow Non-Fibrous

Homogeneous

100% Other None Detected

AB-07 / 23068520-007

Carpet Basement Rm 105, Carpet

Green Fibrous

Homogeneous

80% Synthetic 20% Other None Detected

AB-07 / 23068520-007

Carpet Basement Rm 105, Mastic

Yellow Non-Fibrous

Homogeneous

100% Other None Detected

AB-08 / 23068520-008

Carpet Basement Rm 127, Carpet

Green Fibrous

Homogeneous

80% Synthetic 20% Other None Detected

AB-08 / 23068520-008

Carpet Basement Rm 127, Mastic

Yellow Non-Fibrous

Homogeneous

100% Other None Detected

AB-09 / 23068520-009

Carpet Basement Rm 128, Carpet

Green Fibrous

Homogeneous

80% Synthetic 20% Other None Detected

AB-09 / 23068520-009

Carpet Basement Rm 128, Mastic

Yellow Non-Fibrous

Homogeneous

100% Other None Detected

AB-09 / 23068520-009

Carpet Basement Rm 128, Mastic

Black Non-Fibrous

Homogeneous

97% Other 3% Chrysotile

AB-10 / 23068520-010

Cove Base, Mastic Basement Lunch Room, Cove Base

Tan Non-Fibrous

Homogeneous

100% Other None Detected

Analyst:

Analysis Date: 12/21/2023 Date: 12/21/2023

Approved Signatory:

11709 Chesterdale Rd., Cincinnati, OH 45246 | 513.438.6006 | Fax: 804.897.1177 | www.SanAir.com | IAQ@SanAir.com

IH23-107Project Number:

P.O. Number:

Project Name: USFS Bldg. 24

10/27/2023Collected Date:

12/14/2023 12:00:00 PMReceived Date:

12/21/2023 5:26:48 PM

23068520 SanAir ID Number

FINAL REPORT

Abatement Contractors of Montana, LLCName:

Address: 208 Commerce St.

Missoula, MT 59808

Stereoscopic Components

SanAir ID / Description Appearance % Fibrous % Non-fibrous Asbestos Fibers

AB-10 / 23068520-010

Cove Base, Mastic Basement Lunch Room, Mastic

Tan Non-Fibrous

Homogeneous

100% Other None Detected

AB-11 / 23068520-011

Cove Base, Mastic Basement Storage Room, Cove Base

Tan Non-Fibrous

Homogeneous

100% Other None Detected

AB-11 / 23068520-011

Cove Base, Mastic Basement Storage Room, Mastic

Tan Non-Fibrous

Homogeneous

100% Other None Detected

AB-12 / 23068520-012

Cove Base, Mastic Basement Rm 120, Cove Base

Tan Non-Fibrous

Homogeneous

100% Other None Detected

AB-12 / 23068520-012

Cove Base, Mastic Basement Rm 120, Mastic

Tan Non-Fibrous

Homogeneous

100% Other None Detected

AB-13 / 23068520-013

Carpet, Mastic South Wing Basement, Carpet

Gray Fibrous

Homogeneous

90% Synthetic 10% Other None Detected

AB-13 / 23068520-013

Carpet, Mastic South Wing Basement, Mastic

Yellow Non-Fibrous

Homogeneous

100% Other None Detected

AB-14 / 23068520-014

Carpet, Mastic South Wing Basement, Carpet

Gray Fibrous

Homogeneous

90% Synthetic 10% Other None Detected

AB-14 / 23068520-014

Carpet, Mastic South Wing Basement, Mastic

Yellow Non-Fibrous

Homogeneous

100% Other None Detected

AB-15 / 23068520-015

Carpet, Mastic South Wing Basement, Carpet

Gray Fibrous

Homogeneous

90% Synthetic 10% Other None Detected

Analyst:

Analysis Date: 12/21/2023 Date: 12/21/2023

Approved Signatory:

11709 Chesterdale Rd., Cincinnati, OH 45246 | 513.438.6006 | Fax: 804.897.1177 | www.SanAir.com | IAQ@SanAir.com

IH23-107Project Number:

P.O. Number:

Project Name: USFS Bldg. 24

10/27/2023Collected Date:

12/14/2023 12:00:00 PMReceived Date:

12/21/2023 5:26:48 PM

23068520 SanAir ID Number

FINAL REPORT

Abatement Contractors of Montana, LLCName:

Address: 208 Commerce St.

Missoula, MT 59808

Stereoscopic Components

SanAir ID / Description Appearance % Fibrous % Non-fibrous Asbestos Fibers

AB-15 / 23068520-015

Carpet, Mastic South Wing Basement, Mastic

White Non-Fibrous

Homogeneous

100% Other None Detected

AB-16 / 23068520-016

Carpet, Mastic South Wing Basement, Carpet

Tan Fibrous

Homogeneous

90% Synthetic 10% Other None Detected

AB-16 / 23068520-016

Carpet, Mastic South Wing Basement, Mastic

Yellow Non-Fibrous

Homogeneous

100% Other None Detected

AB-17 / 23068520-017

Carpet, Mastic South Wing Basement, Carpet

Tan Fibrous

Homogeneous

90% Synthetic 10% Other None Detected

AB-17 / 23068520-017

Carpet, Mastic South Wing Basement, Mastic

Yellow Non-Fibrous

Homogeneous

100% Other None Detected

AB-18 / 23068520-018

Carpet, Mastic South Wing Basement, Carpet

Tan Fibrous

Homogeneous

90% Synthetic 10% Other None Detected

AB-18 / 23068520-018

Carpet, Mastic South Wing Basement, Mastic

Yellow Non-Fibrous

Homogeneous

100% Other None Detected

AB-19 / 23068520-019

Vinyl Floor Tile, Mastic Under M5 + M6 Basement, Floor Tile

Tan Non-Fibrous

Homogeneous

98% Other 2% Chrysotile

AB-19 / 23068520-019

Vinyl Floor Tile, Mastic Under M5 + M6 Basement, Mastic

Yellow Non-Fibrous

Homogeneous

100% Other None Detected

AB-20 / 23068520-020

Vinyl Floor Tile, Mastic Under M5 + M6 Basement, Floor Tile

Not Analyzed

Analyst:

Analysis Date: 12/21/2023 Date: 12/21/2023

Approved Signatory:

11709 Chesterdale Rd., Cincinnati, OH 45246 | 513.438.6006 | Fax: 804.897.1177 | www.SanAir.com | IAQ@SanAir.com

IH23-107Project Number:

P.O. Number:

Project Name: USFS Bldg. 24

10/27/2023Collected Date:

12/14/2023 12:00:00 PMReceived Date:

12/21/2023 5:26:48 PM

23068520 SanAir ID Number

FINAL REPORT

Abatement Contractors of Montana, LLCName:

Address: 208 Commerce St.

Missoula, MT 59808

Stereoscopic Components

SanAir ID / Description Appearance % Fibrous % Non-fibrous Asbestos Fibers

AB-20 / 23068520-020

Vinyl Floor Tile, Mastic Under M5 + M6 Basement, Mastic

Yellow Non-Fibrous

Homogeneous

100% Other None Detected

AB-21 / 23068520-021

Vinyl Floor Tile, Mastic Under M5 + M6 Basement, Floor Tile

Not Analyzed

AB-21 / 23068520-021

Vinyl Floor Tile, Mastic Under M5 + M6 Basement, Mastic

Yellow Non-Fibrous

Homogeneous

100% Other None Detected

AB-22 / 23068520-022

Ceiling Tile Large Fissure (Wide) 2x2 South Wing Basement

Tan Fibrous

Homogeneous

40% Cellulose 10% Glass

5% Min. Wool

45% Other None Detected

AB-23 / 23068520-023

Ceiling Tile Large Fissure (Wide) 2x2 South Wing Basement

Tan Fibrous

Homogeneous

40% Cellulose 10% Glass

5% Min. Wool

45% Other None Detected

AB-24 / 23068520-024

Ceiling Tile Large Fissure (Wide) 2x2 South Wing Basement

Tan Fibrous

Homogeneous

40% Cellulose 10% Glass

5% Min. Wool

45% Other None Detected

AB-25 / 23068520-025

Ceiling Tile 2x4 Small + Large Pinholes, No Fissures

Tan Fibrous

Homogeneous

40% Cellulose 15% Glass

45% Other None Detected

AB-26 / 23068520-026

Ceiling Tile 2x4 Small + Large Pinholes, No Fissures South

Tan Fibrous

Homogeneous

40% Cellulose 15% Glass

45% Other None Detected

AB-27 / 23068520-027

Ceiling Tile 2x4 Small + Large Pinholes, No Fissures South

Tan Fibrous

Homogeneous

40% Cellulose 15% Glass

45% Other None Detected

AB-28 / 23068520-028

Carpet Squares 2x2, Mastic Floor Fill 1st Floor North Wing, Carpet

Various Fibrous

Homogeneous

90% Synthetic 10% Other None Detected

Analyst:

Analysis Date: 12/21/2023 Date: 12/21/2023

Approved Signatory:

11709 Chesterdale Rd., Cincinnati, OH 45246 | 513.438.6006 | Fax: 804.897.1177 | www.SanAir.com | IAQ@SanAir.com

IH23-107Project Number:

P.O. Number:

Project Name: USFS Bldg. 24

10/27/2023Collected Date:

12/14/2023 12:00:00 PMReceived Date:

12/21/2023 5:26:48 PM

23068520 SanAir ID Number

FINAL REPORT

Abatement Contractors of Montana, LLCName:

Address: 208 Commerce St.

Missoula, MT 59808

Stereoscopic Components

SanAir ID / Description Appearance % Fibrous % Non-fibrous Asbestos Fibers

AB-28 / 23068520-028

Carpet Squares 2x2, Mastic Floor Fill 1st Floor North Wing, Mastic

Yellow Non-Fibrous

Homogeneous

100% Other None Detected

AB-28 / 23068520-028

Carpet Squares 2x2, Mastic Floor Fill 1st Floor North Wing, Leveling Compound

Gray Non-Fibrous

Homogeneous

100% Other None Detected

AB-28 / 23068520-028

Carpet Squares 2x2, Mastic Floor Fill 1st Floor North Wing, Mastic

Tan Non-Fibrous

Homogeneous

100% Other None Detected

AB-28 / 23068520-028

Carpet Squares 2x2, Mastic Floor Fill 1st Floor North Wing, Leveling Compound

White Non-Fibrous

Homogeneous

100% Other None Detected

AB-29 / 23068520-029

Carpet Squares 2x2, Mastic Floor Fill 1st Floor North Wing, Carpet

Various Fibrous

Homogeneous

90% Synthetic 10% Other None Detected

AB-29 / 23068520-029

Carpet Squares 2x2, Mastic Floor Fill 1st Floor North Wing, Mastic

Yellow Non-Fibrous

Homogeneous

100% Other None Detected

AB-29 / 23068520-029

Carpet Squares 2x2, Mastic Floor Fill 1st Floor North Wing, Leveling Compound

Gray Non-Fibrous

Homogeneous

100% Other None Detected

AB-29 / 23068520-029

Carpet Squares 2x2, Mastic Floor Fill 1st Floor North Wing, Mastic

Tan Non-Fibrous

Homogeneous

100% Other None Detected

AB-29 / 23068520-029

Carpet Squares 2x2, Mastic Floor Fill 1st Floor North Wing, Leveling Compound

White Non-Fibrous

Homogeneous

100% Other None Detected

Analyst:

Analysis Date: 12/21/2023 Date: 12/21/2023

Approved Signatory:

11709 Chesterdale Rd., Cincinnati, OH 45246 | 513.438.6006 | Fax: 804.897.1177 | www.SanAir.com | IAQ@SanAir.com

IH23-107Project Number:

P.O. Number:

Project Name: USFS Bldg. 24

10/27/2023Collected Date:

12/14/2023 12:00:00 PMReceived Date:

12/21/2023 5:26:48 PM

23068520 SanAir ID Number

FINAL REPORT

Abatement Contractors of Montana, LLCName:

Address: 208 Commerce St.

Missoula, MT 59808

Stereoscopic Components

SanAir ID / Description Appearance % Fibrous % Non-fibrous Asbestos Fibers

AB-30 / 23068520-030

Carpet Squares 2x2, Mastic Floor Fill 1st Floor North Wing, Carpet

Various Fibrous

Homogeneous

90% Synthetic 10% Other None Detected

AB-30 / 23068520-030

Carpet Squares 2x2, Mastic Floor Fill 1st Floor North Wing, Mastic

Yellow Non-Fibrous

Homogeneous

100% Other None Detected

AB-30 / 23068520-030

Carpet Squares 2x2, Mastic Floor Fill 1st Floor North Wing, Leveling Compound

Gray Non-Fibrous

Homogeneous

100% Other None Detected

AB-30 / 23068520-030

Carpet Squares 2x2, Mastic Floor Fill 1st Floor North Wing, Mastic

Tan Non-Fibrous

Homogeneous

100% Other None Detected

AB-30 / 23068520-030

Carpet Squares 2x2, Mastic Floor Fill 1st Floor North Wing, Felt

Brown Non-Fibrous

Heterogeneous

15% Glass 85% Other None Detected

AB-31 / 23068520-031

Ceramic Tile 6x6 1st Floor Under M10

Red Non-Fibrous

Homogeneous

100% Other None Detected

AB-32 / 23068520-032

Ceramic Tile 6x6 1st Floor Under M10

Red Non-Fibrous

Homogeneous

100% Other None Detected

AB-33 / 23068520-033

Ceramic Tile 6x6 1st Floor Under M10

Red Non-Fibrous

Homogeneous

100% Other None Detected

AB-34 / 23068520-034

Grout (6x6 Tile Grout) 1st Floor Under M10, Grout

Gray Non-Fibrous

Homogeneous

100% Other None Detected

AB-34 / 23068520-034

Grout (6x6 Tile Grout) 1st Floor Under M10, Leveling Compound

White Non-Fibrous

Homogeneous

100% Other None Detected

Analyst:

Analysis Date: 12/21/2023 Date: 12/21/2023

Approved Signatory:

11709 Chesterdale Rd., Cincinnati, OH 45246 | 513.438.6006 | Fax: 804.897.1177 | www.SanAir.com | IAQ@SanAir.com

IH23-107Project Number:

P.O. Number:

Project Name: USFS Bldg. 24

10/27/2023Collected Date:

12/14/2023 12:00:00 PMReceived Date:

12/21/2023 5:26:48 PM

23068520 SanAir ID Number

FINAL REPORT

Abatement Contractors of Montana, LLCName:

Address: 208 Commerce St.

Missoula, MT 59808

Stereoscopic Components

SanAir ID / Description Appearance % Fibrous % Non-fibrous Asbestos Fibers

AB-34 / 23068520-034

Grout (6x6 Tile Grout) 1st Floor Under M10, Mastic

Yellow Non-Fibrous

Homogeneous

100% Other None Detected

AB-35 / 23068520-035

Grout (6x6 Tile Grout) 1st Floor Under M10, Grout

Gray Non-Fibrous

Homogeneous

100% Other None Detected

AB-35 / 23068520-035

Grout (6x6 Tile Grout) 1st Floor Under M10, Leveling Compound

White Non-Fibrous

Homogeneous

100% Other None Detected

AB-35 / 23068520-035

Grout (6x6 Tile Grout) 1st Floor Under M10, Mastic

Yellow Non-Fibrous

Homogeneous

100% Other None Detected

AB-36 / 23068520-036

Grout (6x6 Tile Grout) 1st Floor Under M10

Gray Non-Fibrous

Homogeneous

100% Other None Detected

AB-37 / 23068520-037

Mortar, Concrete? 1st Floor Under M10

Tan Non-Fibrous

Heterogeneous

100% Other None Detected

AB-38 / 23068520-038

Mortar, Concrete? 1st Floor Under M10

Tan Non-Fibrous

Heterogeneous

100% Other None Detected

AB-39 / 23068520-039

Mortar, Concrete? 1st Floor Under M10

Tan Non-Fibrous

Heterogeneous

100% Other None Detected

AB-40 / 23068520-040

Carpet, Mastic 1st Floor Over M-11-13 North Wing, Carpet

Gray Fibrous

Homogeneous

90% Synthetic 10% Other None Detected

AB-40 / 23068520-040

Carpet, Mastic 1st Floor Over M-11-13 North Wing, Mastic

Yellow Non-Fibrous

Homogeneous

100% Other None Detected

Analyst:

Analysis Date: 12/21/2023 Date: 12/21/2023

Approved Signatory:

11709 Chesterdale Rd., Cincinnati, OH 45246 | 513.438.6006 | Fax: 804.897.1177 | www.SanAir.com | IAQ@SanAir.com

IH23-107Project Number:

P.O. Number:

Project Name: USFS Bldg. 24

10/27/2023Collected Date:

12/14/2023 12:00:00 PMReceived Date:

12/21/2023 5:26:48 PM

23068520 SanAir ID Number

FINAL REPORT

Abatement Contractors of Montana, LLCName:

Address: 208 Commerce St.

Missoula, MT 59808

Stereoscopic Components

SanAir ID / Description Appearance % Fibrous % Non-fibrous Asbestos Fibers

AB-41 / 23068520-041

Carpet, Mastic 1st Floor Over M-11-13 North Wing, Carpet

Gray Fibrous

Homogeneous

90% Synthetic 10% Other None Detected

AB-41 / 23068520-041

Carpet, Mastic 1st Floor Over M-11-13 North Wing, Mastic

Yellow Non-Fibrous

Homogeneous

100% Other None Detected

AB-42 / 23068520-042

Carpet, Mastic 1st Floor Over M-11-13 North Wing, Carpet

Gray Fibrous

Homogeneous

90% Synthetic 10% Other None Detected

AB-42 / 23068520-042

Carpet, Mastic 1st Floor Over M-11-13 North Wing, Mastic

Yellow Non-Fibrous

Homogeneous

100% Other None Detected

AB-43 / 23068520-043

Carpet, Mastic 1st Floor North Wing, Carpet

Tan Fibrous

Homogeneous

90% Synthetic 10% Other None Detected

AB-43 / 23068520-043

Carpet, Mastic 1st Floor North Wing, Mastic

Yellow Non-Fibrous

Homogeneous

100% Other None Detected

AB-44 / 23068520-044

Carpet, Mastic 1st Floor North Wing, Carpet

Tan Fibrous

Homogeneous

90% Synthetic 10% Other None Detected

AB-44 / 23068520-044

Carpet, Mastic 1st Floor North Wing, Mastic

Various Non-Fibrous

Homogeneous

100% Other None Detected

AB-45 / 23068520-045

Carpet, Mastic 1st Floor North Wing, Carpet

Tan Fibrous

Homogeneous

90% Synthetic 10% Other None Detected

AB-45 / 23068520-045

Carpet, Mastic 1st Floor North Wing, Mastic

Yellow Non-Fibrous

Homogeneous

100% Other None Detected

Analyst:

Analysis Date: 12/21/2023 Date: 12/21/2023

Approved Signatory:

11709 Chesterdale Rd., Cincinnati, OH 45246 | 513.438.6006 | Fax: 804.897.1177 | www.SanAir.com | IAQ@SanAir.com

IH23-107Project Number:

P.O. Number:

Project Name: USFS Bldg. 24

10/27/2023Collected Date:

12/14/2023 12:00:00 PMReceived Date:

12/21/2023 5:26:48 PM

23068520 SanAir ID Number

FINAL REPORT

Abatement Contractors of Montana, LLCName:

Address: 208 Commerce St.

Missoula, MT 59808

Stereoscopic Components

SanAir ID / Description Appearance % Fibrous % Non-fibrous Asbestos Fibers

AB-46 / 23068520-046

Floor Tile, Mastic 1st Floor N.

Wing Under M15 (Partition, Floor Tile

White Non-Fibrous

Homogeneous

97% Other 3% Chrysotile

AB-46 / 23068520-046

Floor Tile, Mastic 1st Floor N.

Wing Under M15 (Partition, Mastic

Black Non-Fibrous

Homogeneous

96% Other 4% Chrysotile

AB-47 / 23068520-047

Floor Tile, Mastic 1st Floor N.

Wing Under M15 (Partition, Floor Tile

Not Analyzed

AB-47 / 23068520-047

Floor Tile, Mastic 1st Floor N.

Wing Under M15 (Partition, Mastic

Not Analyzed

AB-48 / 23068520-048

Floor Tile, Mastic 1st Floor N.

Wing Under M15 (Partition, Floor Tile

Not Analyzed

AB-48 / 23068520-048

Floor Tile, Mastic 1st Floor N.

Wing Under M15 (Partition, Mastic

Not Analyzed

Analyst:

Analysis Date: 12/21/2023 Date: 12/21/2023

Approved Signatory:

11709 Chesterdale Rd., Cincinnati, OH 45246 | 513.438.6006 | Fax: 804.897.1177 | www.SanAir.com | IAQ@SanAir.com

IH23-107Project Number:

P.O. Number:

Project Name: USFS Bldg. 24

10/27/2023Collected Date:

12/14/2023 12:00:00 PMReceived Date:

12/21/2023 5:26:48 PM

23068520 SanAir ID Number

FINAL REPORT

Abatement Contractors of Montana, LLCName:

Address: 208 Commerce St.

Missoula, MT 59808

Disclaimer

The final report cannot be reproduced, except in full, without written authorization from SanAir. This report is the sole property of the client named on the SanAir Technologies Laboratory chain-of-custody (COC). Results in the report are confidential information intended only for the use by the client named on the COC. Neither results nor reports will be discussed with or released to any third party without our client's written permission to assure that parts of the report are not taken out of context and to maintain client confidentiality. The information provided in this report applies only to the samples submitted in the condition they were received at the laboratory and is relevant only for the date, time, and location of sampling. Samples were received in good condition unless otherwise noted on the report. Fibers smaller than 5 microns cannot be seen with this method due to scope limitations. The accuracy of the results is dependent upon the client’s sampling procedure and information provided to the laboratory by the client, which includes the project name, project number, po number, sample collection dates, special instructions, samples collected by, sample numbers, sample identifications/ location, sample type, selected analysis type, and total area or volume that may affect the validity of the results. SanAir assumes no responsibility for the sampling procedure and will provide evaluation reports based solely on the sample and information provided by the client. SanAir assumes no responsibility or liability for the manner in which results are used or interpreted. This report does not constitute and shall not be used to claim product certification, approval, or endorsement by NVLAP, NIST, AIHA LAP, LLC or any other agency of the U.S. government. Samples are held for a period of 60 days.

Polarized- light microscopy is not consistently reliable in detecting asbestos in floor covering and similar non-friable organically bound materials. Quantitative transmission electron microscopy is currently the only method that can be used to determine if this material can be considered or treated as non-asbestos containing.

Asbestos Accreditations, Licenses, or Certificates NVLAP Lab Code 600227-0

State of Rhode Island Department of Health, Certification Number: PLM00144, TEM00144 State of West Virginia Bureau for Public Health, Analytical Laboratory Number: LT000637

Rev#01 2/3/2023 Page 13 of 18

P a g e o f g e o f g e o f g e o f

SanAir ID#: 23068874

Project #: IH23-107 Project Name: USFS Bldg 24 Report Date: 12/19/2023

Analysis Report prepared for Abatement Contractors of Montana, LLC

Dear Brian Betts, We at SanAir would like to thank you for the work you recently submitted. The 72 sample(s) were received on Monday, December 18, 2023 via UPS. The final report(s) is enclosed for the following sample(s): AB-49, AB-50, AB-51, AB-52, AB-53, AB-54, AB-55, AB-56, AB-57, AB-58, AB-59, AB-60, AB-61, AB-62, AB-63, AB-64, AB-65, AB-66, AB-67, AB-68, AB-69, AB-70, AB-71, AB-72, AB-73, AB-74, AB-75, AB-76, AB-77, AB-78, AB-79, AB-80, AB-81, AB-82, AB-83, AB-84, AB-85, AB-86, AB-87, AB-88, AB-89, AB-90, AB-91, AB-92, AB-93, AB-94, AB-95, AB-96, AB-97, AB-98, AB-99, AB-100, AB-101, AB-102, AB-103, AB-104, AB-105, AB-106, AB-107, AB-108, AB-109, AB-110, AB-111, AB-112, AB-113, AB-114, AB-115, AB-116, AB-117, AB-118, AB-119, AB-120.

These results only pertain to this job and should not be used in the interpretation of any other job. This report is only complete in its entirety. Refer to the listing below of the pages included in a complete final report.

Sincerely, Sandra Sobrino Asbestos & Materials Laboratory Manager SanAir…