Attach 7_ADDENDUM 2 _Updates to Plans_Drawings_07242024.pdf
PDF 4 MB Posted
- Attached to
- BUILDING 24 DISPATCH REMODEL Federal contract opportunity
- Solicitation number
- 1122499
- Issued by
- Department of Agriculture Forest Service
About this file
This document is an addendum to a solicitation for the remodel of Building 24 at the Lolo National Forest Headquarters in Missoula, Montana. The remodel work includes updating the south wing on the upper floor to accommodate the Missoula Dispatch operation, remodeling the front desk area, renovating a single private office in the north wing, and installing Linc Pass access control on all exterior doors. The addendum provides updates to the construction drawings, including revisions to the door schedule, electrical one-line diagram, lighting control diagrams, and generator pad details. It also notes that an asbestos report is included as part of the contract documents. The solicitation number is 1122499, and the federal agency involved is the Department of Agriculture Forest Service.
View the file
Other files for this federal contract opportunity
| File | Type | Posted |
|---|---|---|
| A0004_Building 24 Dispatch Remodel.pdf | ||
| A0003_Building 24 Dispatch Remodel.pdf | ||
| A0002_Building 24 Dispatch Remodel.pdf | ||
| Attach 9_Demo Plan South Wing Sheets 2 and 6 of 11.pdf | ||
| Attach 14_Reception Area Remodel Sheets 1 - 3.pdf | ||
| Attach 8_Asbestos Report-Building 24.pdf | ||
| Attach 11_Demolition Plan Sheets 1-5.pdf | ||
| Attach 12_E Sheets E1 - E8.pdf | ||
| Attach 13_M Demo Sheets M1 - M3.pdf | ||
| Attach 10_Demo Plan West Wing Sheets 1-11.pdf | ||
| A0001_Building 24 Dispatch Remodel_S.pdf | ||
| Attch 5 - 100 Percent Construction Documents Volume 2 Specification.pdf | ||
| 1282B124R0054_BUILDING 24.pdf | ||
| Attch 1 SOW.pdf | ||
| Attch 2 -Schedule of Items -SOI.xlsx | XLSX spreadsheet | |
| Attch 3- Plans_Drawings.pdf | ||
| Attch 4 - 100 Percent Construction Documents Volume 1 Specification.pdf | ||
| Attch 6 - Wage Determination.pdf |
Show all 18
On GovTribe
Work with this file on GovTribe
- Download the original file
- Contacts named in this file
- Similar government files
- Ask GovTribe AI about this file
Text version
USFS BLDG 24 REMODEL Addendum #1 page 1 of 2
ADDENDUM NO: 02
DATE: July 24, 2024 PROJECT: USFS BUILDING 24 Dispatch Remodel PROJECT ADDRESS: 24 H Rd., Missoula MT 59804 ARCHITECT: Mosaic Architecture, 317 N. Cruse Ave.,Ste. 201; Helena, Montana 59601 TO: All plan holders of record
The above-numbered solicitation is amended as set forth below. Bidders/Offerors must acknowledge receipt of this amendment prior to the hour and date specified for receipt of bids/proposals, by completing the addendum acknowledgement on the form titled “Bid Proposal”.
ARCHITECTURAL:
DRAWING ITEMS:
1. ALP-101: LINC PASS DOOR COORD
Plan has been updated to show location of basement door (plan west).
ADDITONAL ATTACHMENTS:
1. ASBESTOS REPORT – APPENDIX III DRAWINGS OF SAMPLE LOCATION
-Entire document included as part of the Contract documents. Contact Forest Service CO for complete Report
317 N. Cruse Ave., Ste. 201
Helena, MT 59601
406.449-2013 www.mosaicarch.com
Addendum #2 - Page 1 of 1
ADDENDUM NO. TWO (2)
USFS BLDG 24 Dispatch
Date: 2024.07.23
TO: ALL PLANHOLDERS
The plans and specifications for the above captioned project are hereby modified and/or superseded by this Addendum:
ELECTRICAL
DRAWINGS –
1. Sheet E002
a. One Line Diagram Key Note 1 is changed to refer to Sheet E006.
2. Sheet E005
a. Generator Pad Detail was added.
3. Sheet E006
a. Location of chiller has been adjusted to better show its actual location.
b. Routing of power from the generator to the ATS was adjusted to reflect the location of the chiller.
END OF ADDENDUM NO. TWO
USFS BLDG 24 REMODEL Addendum #1 page 2 of 2
ENCLOSURES:
Drawings Specifications Sections Other
ALP-101
APPENDIX III- DRAWINGS OF
SAMPLE LOCATIONS
E002
E005
E006
UP
DN
UP
DN
DN
DN
DN
DN
UP
FD ECBA H
10 10
8 8
7 7
6 6
4 4
3 3
2 2
L124 L125
L123 L121
L122 L120
FRONT ENTRY LEVEL 1
X113
WING ENTRY LEVEL 1
X114
WING ENTRY LEVEL 1
X115
ENTRY LEVEL 1
X117
KG
JFD
IECBA
H
L251
L250LEVEL 2 ENTRY
X116
206A
KG
JFD
IECBA
H
L104 L105
L106
L107
BASEMENT
X110
BASEMENT
X111
BASEMENT
X112
L108
L109
DATE:
SHEET:
317 N. Cruse Ave., Suite 201 Helena, Montana 59601
406.449.2013phone www.mosaicarch.com
D A
T E
S T
A M
P a r c h i t e c t u r e - p l a n n i n g -d e s i g n
/2
/2
:4 :2
A
M
02.26.2024
ALP-101
LINC PASS DOOR
COORD.
26 FORT MISSOULA RD, MISSOULA,
MT
BUILDING 24
REMODEL
C O
N S
T R
U C
T I O
N D
O C
U M
E N
T S
# DATE REVISION
1 3/11/2024 Addendum 1
1/16" = 1'-0"
LEVEL 1 LINC COORD.
1 1/16" = 1'-0"
LEVEL 2 KEY COORD
1/16" = 1'-0"
BASEMENT
DOOR SCHEDULE
MARK ROOM NAME
DOOR
TYPE WIDTH HEIGHT THICKNESS DOOR MAT'L DOOR FINISH
FRAME
TYPE FRAME MAT'L FRAME FINISH DOOR HDWR GROUP FIRE RAT'G COMMENTS Phase Created
102 NEW OFFICE F 2' - 10" 6' - 8" 1 3/4" WD FACT F WD P2 04 NONE New Construction
103 OFFICE HL 2' - 10" 6' - 8" 1 3/4" WD FACT F WD P2 04 NONE New Construction
202 NEW OFFICE F 3' - 0" 6' - 8" 2" WD FACT F WD P2 04 New Construction
203 IT ROOM F 2' - 10" 6' - 8" 2" WD FACT F WD P2 05 NONE New Construction
205 (E) OFFICE F 2' - 10" 6' - 8" 2" WD FACT F WD P2 01 NONE New Construction
206 EXPANDED DISPATCH HL 3' - 0" 6' - 8" 2" WD FACT F WD P2 02 New Construction
206A EXPANDED DISPATCH HL 3' - 0" 6' - 8" 2" WD FACT F WD P2 02 New Construction
207 NEW OFFICE F 2' - 10" 6' - 8" 2" WD FACT F WD P2 04 NONE New Construction
210 NEW OFFICE F 3' - 0" 6' - 8" 2" WD FACT F WD P2 04 New Construction
211 NEW OFFICE F 3' - 0" 6' - 8" 2" WD FACT F WD P2 04 New Construction
212 NEW OFFICE F 3' - 0" 6' - 8" 2" WD FACT F WD P2 04 New Construction
213 BALCONY EXIT F 3' - 0" 6' - 8" 1 3/4" HM PAINT F HM P2 06 PIN/CODE ACCESS New Construction
217 WOMENS F 3' - 0" 6' - 8" 2" WD FACT F WD P2 08 New Construction
218 STORAGE F 2' - 10" 6' - 8" 2" WD FACT F WD P2 05 NONE New Construction
219 HALL AT DISPATCH F 3' - 0" 6' - 8" 1 3/4" HM PAINT F HM FACT 07 PIN/CODE ACCESS New Construction
221 OFFICE HL 3' - 0" 7' - 0" 1 3/4" WD PAINT F WD P2 04 New Construction
231 FRONT ENTRY FH 3' - 0" 3' - 6" 2" WD FACT HF WD STAIN 03 HALF DOOR- SECURITY GATE- STAIN TO MATCH
SURROUNDING WOOD CONSTRUCTION
New Construction
L104 BASEMENT FD 6' - 0" 7' - 0" 1 3/4" (E) (E) (E) (E) (E) EX-03.02 LINC PASS DOOR Existing
L105 BASEMENT HLD 6' - 0" 7' - 0" 1 3/4" (E) (E) (E) (E) (E) EX-03.02 LINC PASS DOOR Existing
L106 BASEMENT FD 6' - 0" 7' - 0" 1 3/4" (E) (E) (E) (E) (E) EX-03.02 LINC PASS DOOR Existing
L107 BASEMENT F 3' - 0" 6' - 8" 1 3/4" (E) (E) (E) (E) (E) EX-03 LINC PASS DOOR Existing
L108 BASEMENT HL 3' - 0" 6' - 8" 1 3/4" (E) (E) (E) (E) (E) EX-03 LINC PASS DOOR Existing
L109 BASEMENT FD 6' - 0" 7' - 0" 1 3/4" (E) (E) (E) (E) (E) EX-03.01 LINC PASS DOOR Existing
L110 BASEMENT 3' - 0" 6' - 8" 1 3/4" Existing
L120 FRONT ENTRY HLD 5' - 4" 7' - 0" 1 3/8" (E) (E) (E) (E) (E) EX-01 LINC PASS DOOR Existing
L121 ENTRY LEVEL 1 HL 3' - 0" 7' - 0" 1 3/4" (E) (E) (E) (E) (E) EX-02 LINC PASS DOOR Existing
L122 FRONT ENTRY LEVEL 1 HLD 5' - 0" 6' - 8" 2" (E) (E) (E) (E) (E) EX-01 NONE LINC PASS DOOR Existing
L123 FRONT ENTRY LEVEL 1 HL 3' - 0" 7' - 0" 1 3/4" (E) (E) (E) (E) (E) EX-03 LINC PASS DOOR Existing
L124 WING ENTRY LEVEL 1 HL 3' - 0" 7' - 0" 1 3/4" (E) (E) (E) (E) (E) EX-03 LINC PASS DOOR Existing
L125 WING ENTRY LEVEL 1 HL 3' - 0" 7' - 0" 1 3/4" (E) (E) (E) (E) (E) EX-03 LINC PASS DOOR Existing
L250 BALCONY EXIT HL 3' - 0" 6' - 8" 1 3/4" HM PAINT F HM P2 EX-03 LINC PASS DOOR Existing
L251 LEVEL 2 ENTRY HL 3' - 0" 6' - 8" 1 3/4" (E) (E) (E) (E) (E) EX-03 LINC PASS DOOR Existing
OPTION ITEM 3
LINC PASS DOORS
APPENDIX III
DRAWINGS OF SAMPLE
LOCATIONS
KEY NOTES:#
1. REPLACE PANEL MP AS SHOWN ON SHEET E006. CONTRACTOR SHALL
MODIFY, EXTEND, OR REPLACE FEEDER AS REQUIRED TO ACCOMMODATE
RELOCATION OF PANEL MP.
2. EXISTING PANELS 2LP AND 4LP1 WERE SWAPPED OUT RECENTLY AND WILL
REMAIN.
3. PROVIDE NEW GENERATOR WITH BONDED NEUTRAL (NON-SEPARATELY
DERIVED SYSTEM). PROVIDE GENERATOR AUXILIARY CIRCUITS (BATTERY
CHARGER, BLOCK HEATER, ETC.) CIRCUITED FROM PANEL 5EP1.
4. REPLACE EXISTING PANEL ONE-FOR-ONE IN THE SAME LOCATION.
5. TIE GENSET CHASIS TO GROUND, BUT DO NOT BOND NEUTRAL TO GROUND.
6. PROVIDE NEW THREE-POLE AUTOMATIC TRANSFER SWITCH.
(EX)MSB
800A, 208/120V, 3PH, 4W
18,828 AIC
SPACE
SPACE
SPACE
SPACE
MP
600A, 208/120V, 3PH, 4W
EX
PANEL
5RP
EX
PANEL
8RP
EX
PANEL
6RP
EX
PANEL
T
EX
PANEL
BP2
EX
PANEL
3RP
EX
PANEL
2RP
EX
PANEL
1RP
EX
PANEL
4RP
EX
PANEL
CP
EX
PANEL
3RP1
EX
COMP
ROOM
AC UNIT
J
M
(EX)METER BASE PER
UTILITY REQUIREMENTS
(EX)CT CABINET
(EX) UTILITY
TRANSFORMER
(EX) 800A/3P SERVICE DISCONNECT
M
(EX) 600A/3P CHILLER
DISCONNECT
PANEL
BP
J
PANEL
1LP
M
(EX)
ELEVATOR
PANEL
3LP
PANEL
5LP
EX
PANEL
2LP
PANEL
4LP
PANEL
6LP
NEW
PANEL
5EP1
EXIT
SIGNS
(EX)MSB
800A, 208/120V, 3PH, 4W
18,828 AIC
SPACE
SPACE
SPACE
SPACE
(EX)MP
600A, 208/120V, 3PH, 4W
EX
PANEL
5RP
EX
PANEL
8RP
EX
PANEL
6RP
EX
PANEL
T
EX
PANEL
BP2
EX
PANEL
3RP
EX
PANEL
2RP
EX
PANEL
1RP
EX
PANEL
4RP
EX
PANEL
CP
EX
PANEL
3RP1
EX
COMP
ROOM
AC UNIT
J
M
(EX)METER BASE PER
UTILITY REQUIREMENTS
(EX)CT CABINET
(EX) UTILITY TRANSFORMER
(EX) 800A/3P SERVICE DISCONNECT
M
(EX) 600A/3P CHILLER
DISCONNECT
EX
PANEL
BP
J
EX
PANEL
1LP
M
(EX)
ELEVATOR
EX
PANEL
3LP
EX
PANEL
5LP
EX
PANEL
2LP
EX
PANEL
4LP
EX
PANEL
6LP
EX
PANEL
4LP1
EXIT
SIGNS
4 4
4 4 4 42
(EX) CONDUIT IS
1-1/2"
M
208Y/120V, 3-PHASE
75KW NATURAL GAS
GENERATOR IN
WEATHERPROOF SOUND
ATTENUATED ENCLOSURE
150A
ATS
(EX)CHILLER
1.5N
1.5N
1.5N 1.5N 1.5N 1.5N 1.5N 1.5N
1.5N
1.5N
6.0N
AFC: 17,264
1.5N 1.5N
EX
PANEL
4LP1
SPACE
ROOM
CONTROLLER
LMRC-102
NEUTRAL WHT
HOT BLK
120/277
LIGHTING LOAD
(a)
LIGHTING LOAD
(b)
LMDC-100
OCCUPANCY
SENSOR
AS NEEDED
DLM WALL
SWITCH
LMSW-102
RJ45 (TYP)
LMRJ SERIES
PRE-TERMINATED
CABLES.
SEQUENCE OF OPERATION:
DEVICES ARE PRESET FOR PLUG n' GO OPERATION
ALL ROOMS ARE STAND ALONE.
NUMBER OF ZONES ("a" "b" ETC) INDICATED NUMBER OF RELAYS
REQUIRED IN A ROOM
SWITCH:
$LV# - # INDICATES NUMBER OF BUTTONS
$LVD# - # INDICATES NUMBER OF BUTTONS
OFFICE:
• THE ROOM CONTROLLER DEFAULTS TO MULTI-LEVEL
AUTOMATIC-ON/AUTOMATIC OFF. LOAD (A) TURNS ON
AUTOMATICALLY AND LOAD (B) DEFAULTS TO MANUAL-ON
CONTROL; BOTH LOADS TURN AUTOMATICALLY OFF.
PROVIDE A TWO BUTTON LOW VOLTAGE SWITCH FOR LOAD (A)
AND (B).
HALLWAYS:
• THE ROOM CONTROLLER DEFAULTS TO MULTI-LEVEL
AUTOMATIC-ON/AUTOMATIC OFF. LOAD (A) REMAINS ON AT ALL
TIMES AND LOAD (B) DEFAULTS TO OCCUPANCY SENSOR
CONTROL; LOAD (B).
• THE ROOM CONTROLLER DEFAULTS TO AUTOMATIC-
ON/AUTOMATIC OFF. LOAD (A) TURNS ON AUTOMATICALLY.
THE EXHAUST FANS; LOAD (B) DEFAULTS TO AUTOMATIC-
ON/AUTOMATIC OFF; BOTH LOADS TURN AUTOMATICALLY OFF.
EXHAUST FAN SHALL BE 1/4 HP OR SMALLER.
NOTE:
FOR AREAS WITH ONLY (1) ZONE,
PROVIDE A LMRC-101 FOR CONTROL
OF THE SINGLE LOAD. ALL EMERGENCY
FIXTURES REQUIRE AN UNSWITCHED
HOT LEG. FOR RESTROOMS WITH THIS
CONFIGURATION, THERE ARE NO
MANUAL SWITCHES. UTILIZE THE
SECOND CONTACT FOR EXHAUST FAN.
LMDC-100
OCCUPANCY
SENSOR AS
NEEDED
AT WALL BELOW GRADE AT WALL OR FLOOR ABOVE GRADE
PACK WITH LINK SEAL
OR RUBBER SEALANT
CONCRETE WALL
GALVANIZED STEEL PIPE
SLEEVE W/ SEEP RING
UNDERGROUND
CONDUIT
CONDUIT
GALV. STL. PIPE
SLEEVE- I.D. LARGER
THAN CONDUIT O.D.
INSULATION AS
REQ'D TO FILL CAVITY
GALV. SHEET METAL
ESCUTCHEON ON
MECHANICAL ROOM SIDE
OF PENETRATION
CONC. WALL OR FLOOR
M
IN
O .D
O
F C
O N
D U
IT
P
L U
S
M
IN
Red
NEUTRAL WHT Yel
Blu
V io
G ry
Vio Gry
Vio Gry
Vio Gry
V io
G ry V io G ry
CLASS 2 0-10 VOLT
CONTROL WIRING
0-10VDC DIMMING
BALLAST
REQUIRED.
RJ45 PORT
(TYPICAL)
LMRJ SERIES PRE-TERMINATED CABLES OR CAT5E.
FREE TOPOLOGY & SPLITTER ACCEPTABLE
UNSWITCHED
HOT BLK
120/277
LMRC-213 TRIPLE RELAY ON/OFF/0-10V
DIMMING ROOM CONTROLLER
LMDM-101 DIGITAL
DIMMING
SWITCH
AS
NEEDED
RJ45
(TYP.)
LMRJ-C8
COUPLER
LMDC-100
OCCUPANCY
SENSOR
LIGHTING LOAD
(a)
LIGHTING LOAD
(b)
LIGHTING LOAD
(c)
LMDC-100
OCCUPANCY
SENSOR AS
NEEDED
SEQUENCE OF OPERATION:
DEVICES ARE PRESET FOR PLUG n' GO OPERATION.
ALL ROOMS ARE STAND ALONE.
NUMBER OF ZONES ("a" "b" ETC) INDICATED NUMBER OF RELAYS
REQUIRED IN A ROOM.
SWITCH:
$LV# - # INDICATES NUMBER OF BUTTONS
$LVD# - # INDICATES NUMBER OF BUTTONS
OFFICE:
• THE ROOM CONTROLLER DEFAULTS TO MULTI-LEVEL
AUTOMATIC-ON/AUTOMATIC OFF. LOAD (A) & (B) TURNS ON
AUTOMATICALLY.
CONTROL; BOTH LOADS TURN AUTOMATICALLY OFF.
PROVIDE A TWO BUTTON LOW VOLTAGE SWITCH FOR LOAD (A)
AND (B).
HALLWAYS:
• THE ROOM CONTROLLER DEFAULTS TO MULTI-LEVEL
AUTOMATIC-ON/AUTOMATIC OFF. LOAD (A) REMAINS ON AT ALL
TIMES AND LOAD (B) DEFAULTS TO OCCUPANCY SENSOR
CONTROL; LOAD (B)
• THE ROOM CONTROLLER DEFAULTS TO AUTOMATIC-
ON/AUTOMATIC OFF. LOAD (A) TURNS ON AUTOMATICALLY. THE
EXHAUST FANS; LOAD (B) DEFAULTS TO AUTOMATIC-
ON/AUTOMATIC OFF; BOTH LOADS TURN AUTOMATICALLY OFF.
EXHAUST FAN SHALL BE 1/4 HP OR SMALLER
DATE:
SHEET:
317 N. Cruse Ave. Suite 201
Helena, Montana
59601
406.449.2013 www.mosaicarch.com
D A
T E
S T
A M
P a r c h i t e c t u r e - p l a n n i n g - d e s i g n
/2
/2
:5
:5
02.26.2024
E002
ELECTRICAL DETAILS
26 FORT MISSOULA RD, MISSOULA, MT
BUILDING 24
REMODEL
C O
N S
T R
U C
T I O
N D
O C
U M
E N
T S
N.T.S.1
DEMOLITION AND REMODEL ONE LINE DIAGRAM
N.T.S.3
LIGHTING CONTROL DIAGRAM - SINGLE OCCUPANCY
N.T.S.4
CONDUIT PENETRATION DETAIL
FEEDER NUMBER KEY:
A = ALUMINUM CONDUCTORS
N = INCLUDES NEUTRAL CONDUCTOR
S = SINGLE PHASE
NOTE: GROUNDING CONDUCTOR IS SIZED ACCORDING TO NEC 250.122 TABLE,
UNLESS FEEDER NUMBER IS FOLLOWED BY AN ASTERISK (*) INDICATING THAT
THE GROUNDING CONDUCTOR IS SIZED ACCORDING TO NEC 250.66 TABLE.
SCHEDULE IS BASED ON 75 DEGREE COPPER CONDUCTORS IN NEC 310.60 TABLE.
FEEDER SCHEDULE - COPPER
FEEDER
NUMBER AMPERAGE
SETS IN
PARALLEL
CONDUIT
SIZE
PHASE WIRE
QTY PHASE AWG
NEUTRAL
QTY
NEUTRAL
AWG GROUND AWG
1.5N 150 A 1 2 3 1/0 1 1/0 6
6.0N 600 A 2 3 3 300KCMIL 1 300 1
N.T.S.2
LIGHTING CONTROL DIAGRAM - MULTIPLE OCCUPANCY
I S S
E F
O R
P
LAN
O EN
G
IN
E E R
ON
T
M
AN
A
LICENSE
D
GARTH L.
STEVENS
No. 11492 PE
# DATE REVISION
2 07/23/2024 ADDENDUM 2
6"
(TYP.)
M
IN
B
U R
Y
PROVIDE SUFFICIENT LENGTH
ON CONDUIT AND CONDUCTORS
FOR CONNECTION IN GENERATOR
#4 BAR, 12" O.C. EACH
WAY. TOP COURSE 2"
FROM TOP OF SLAB
GENERATOR
(SEE ONE-LINE DIAGRAM AND
SITE PLAN FOR GENERATOR INFO)
BOND 1#4 GND TO MINIMUM 20 FT. SECTION OF #5 A36
ROD. JOINT WILL BE MADE BY EXOTHERMIC
WELDING PROCESS. WIRE TIE ROD TO REBAR. BAR
CAN BE BENT TO FIT INTO SLAB. SLEEVE IN 3/4" C. TO
GENERATOR GROUNDING POINT.
PAD THICKNESS: 8" OR ANCHOR IMBED PLUS 3",
WHICHEVER IS GREATER
CONCRETE PAD SHALL BE 4500 PSI MIX
WITH 1" MAX AGGREGATE AND MAX
WATER TO CEMENT RATION OF 0.45
NOTE:
• IF CONCRETE THICKNESS IS GREATER THAN 9 INCHES,
CONTACT ENGINEER FOR REVISED REINFORCEMENT.
DATE:
SHEET:
317 N. Cruse Ave. Suite 201
Helena, Montana
59601
406.449.2013 www.mosaicarch.com
D A
T E
S T
A M
P a r c h i t e c t u r e - p l a n n i n g - d e s i g n
/2
/2
:5
:5
02.26.2024
E005
ELECTRICAL SCHEDULES
26 FORT MISSOULA RD, MISSOULA, MT
BUILDING 24
REMODEL
C O
N S
T R
U C
T I O
N D
O C
U M
E N
T S
Notes:
Total Est. Demand: 0 A
Total Conn.: 0 A
Total Est. Demand: 0 VA
Total Conn. Load: 0 VA
Load Classification Connected Load Demand Factor Estimated Demand Panel Totals
Legend:
Total Amps: 0 A 0 A 0 A
Total Load: 0 VA 0 VA 0 VA
41 SPARE -- 20 A 1 0 0 1 20 A -- SPARE 42
39 SPARE -- 20 A 1 0 0 1 20 A -- (EX) LIGHTS 40
37 0 0 1 20 A -- SPARE 38
SPARE -- 30 A 2
0 0 1 20 A -- SPARE 36
33 (EX) RCPT - ROOM 124 -- 20 A 1 0 0 34
31 SPARE -- 20 A 1 0 0
2 20 A -- (EX) LAMINATOR
29 (EX) RCPT - ROOM 124 -- 20 A 1 0 0 1 20 A -- (EX) RCPT - BATH 30
27 (EX) LIGHTS -- 20 A 1 0 0 1 20 A -- SPARE 28
25 (EX) RCPT - ROOM 125 -- 20 A 1 0 0 1 20 A -- (EX) RCPT - ROOM 128 26
23 SPARE -- 20 A 1 0 0 1 20 A -- (EX) RCPT - ROOM 127 24
21 (EX) RCPT - ROOM 124 -- 20 A 1 0 0 1 20 A -- SPARE 22
19 BOILER CIRCUIT -- 20 A 1 0 0 1 20 A -- (EX) BOILER CONTACTS 20
17 0 0 18
15 0 0 16
(EX) AHU 2 -- 20 A 3
0 0
3 40 A -- (EX) AHU 1
11 SPARE -- 20 A 1 0 0 12
9 SPARE -- 20 A 1 0 0 10
7 (EX) BOILER CONTROL -- 20 A 1 0 0
3 50 A -- (EX) AHU 3
5 0 0 6
3 0 0 4
(EX) PUMP BOILER -- 50 A 3
0 0
3 70 A -- (EX) PANEL 1LP
CKT Circuit Description Load
Classification Trip Poles A B C Poles Trip Load
Classification Circuit Description CKT
Notes:
Enclosure: Type 1
Mounting: Recessed Wires: 4 Mains Rating: 225 A
Supply From: Phases: 3 Mains Type: MCB
Location: BASEMENT X111 Volts: 120/208 Wye A.I.C. Rating: 20,442
Branch Panel: BP
# DATE REVISION
2 07/23/2024 ADDENDUM 2
Notes:
Total Est. Demand: 0 A
Total Conn.: 0 A
Total Est. Demand: 0 VA
Total Conn. Load: 0 VA
Load Classification Connected Load Demand Factor Estimated Demand Panel Totals
Legend:
Total Amps: 0 A 0 A 0 A
Total Load: 0 VA 0 VA 0 VA
41 SPARE -- 20 A 1 0 0 1 20 A -- SPARE 42
39 SPARE -- 20 A 1 0 0 1 20 A -- SPARE 40
37 SPARE -- 20 A 1 0 0 1 20 A -- SPARE 38
35 SPARE -- 20 A 1 0 0 1 20 A -- SPARE 36
33 (EX) LOAD -- 20 A 1 0 0 1 20 A -- SPARE 34
31 (EX) LOAD -- 20 A 1 0 0 1 20 A -- SPARE 32
29 (EX) LOAD -- 20 A 1 0 0 1 20 A -- (EX) LOAD 30
27 (EX) LOAD -- 20 A 1 0 0 1 20 A -- (EX) LOAD 28
25 (EX) LOAD -- 20 A 1 0 0 1 20 A -- (EX) LOAD 26
23 (EX) LOAD -- 20 A 1 0 0 1 20 A -- (EX) LOAD 24
21 (EX) LOAD -- 20 A 1 0 0 1 20 A -- (EX) LOAD 22
19 (EX) LOAD -- 20 A 1 0 0 1 20 A -- (EX) LOAD 20
17 (EX) LOAD -- 20 A 1 0 0 1 20 A -- (EX) LOAD 18
15 (EX) LOAD -- 20 A 1 0 0 1 20 A -- (EX) LOAD 16
13 (EX) LOAD -- 20 A 1 0 0 1 20 A -- (EX) LOAD 14
11 (EX) LOAD -- 20 A 1 0 0 1 20 A -- (EX) LOAD 12
9 (EX) LOAD -- 20 A 1 0 0 1 20 A -- (EX) LOAD 10
7 (EX) LOAD -- 20 A 1 0 0 1 20 A -- (EX) LOAD 8
5 (EX) LOAD -- 20 A 1 0 0 1 20 A -- (EX) LOAD 6
3 (EX) LOAD -- 20 A 1 0 0 1 20 A -- (EX) LOAD 4
1 (EX) LOAD -- 20 A 1 0 0 1 20 A -- (EX) LOAD 2
CKT Circuit Description Load
Classification Trip Poles A B C Poles Trip Load
Classification Circuit Description CKT
Notes:
Enclosure: Type 1
Mounting: Recessed Wires: 4 Mains Rating: 225 A
Supply From: Phases: 3 Mains Type: MLO
Location: Volts: 120/208 Wye A.I.C. Rating: 8,306
Branch Panel: 3LP
I S S
E F
O R
P
LAN
O EN
G
IN
E E R
ON
T
M
AN
A
LICENSE
D
GARTH L.
STEVENS
No. 11492 PE
N.T.S.1
GENERATOR PAD DETAIL
A T
S
J
J
KG
JFD
IECBA
H
(EX)MP MP
(EX)BP2
(E X
)2 R
P
(E X
)8 R
P
(EX)T
(EX)2LP
BP
1LP
(EX)MSB
2 3
GENERATOR
PROPOSED ROUTING FOR
NEW GENERATOR FEEDER
COORDINATE ROUTING TO
AVOID CONFLICTS WITH
CONCRETE AND OTHER
UTILITIES
TRANSITION FROM BELOW
GRADE TO ABOVE
ACCESSIBLE CEILING ON
EXTERIOR OF BUILDING.
(EX) CHILLER
(EX)METER
SOCKET
(EX)T-7(EX)T-9
BLOCK HEATER
BATTERY CHARGER
(EX)BP2-25
(EX)BP2-27
DATE:
SHEET:
317 N. Cruse Ave. Suite 201
Helena, Montana
59601
406.449.2013 www.mosaicarch.com
D A
T E
S T
A M
P a r c h i t e c t u r e - p l a n n i n g - d e s i g n
/2
/2
:5
:5
02.26.2024
E006
BASEMENT - OVERALL
ELECTRICAL PLAN
26 FORT MISSOULA RD, MISSOULA, MT
BUILDING 24
REMODEL
C O
N S
T R
U C
T I O
N D
O C
U M
E N
T S
1/8" = 1'-0"
BASEMENT - OVERALL ELECTRICAL PLAN
A. IT IS ABSOLUTELY NECESSARY FOR ALL TRADES INVOLVED TO COORDINATE
WITH EACH OTHER AND VERIFY THAT THERE ARE NO CONFLICTS IN
LOCATION OF DUCTS, CONDUITS, DIFFUSERS, BOXES, AND OTHER ITEMS
THROUGHOUT THIS PROJECT BEFORE FINAL PLACEMENT OF MATERIALS.
B. ELECTRICAL CONTRACTOR IS RESPONSIBLE FOR ALL CUTTING OF FLOORS,
WALLS, CEILINGS, AND ROOFS TO PERFORM THE REQUIRED WORK
DEPICTED IN THESE DOCUMENTS. THE CONTRACTOR IS RESPONSIBLE FOR
ALL PATCHING OF HOLES TO THE SATISFACTION OF THE C.O.
C. LOW VOLTAGE CABLES (LIGHTING CONTROLS) ABOVE ACCESSIBLE CEILINGS
SHALL BE SUPPORTED USING J-HOOKS AT INTERVALS NOT TO EXCEED 48"
OC, UNO.
POWER PLAN
GENERAL NOTES
1. REPLACE EXISTING PANEL ONE-FOR-ONE. COORDINATE WITH GENERAL
CONTRACTOR TO OPEN EXISTING WALL TO ALLOW FOR INSTALLATION OF
NEW PANEL AS REQUIRED. ADJUST EXISTING FEEDER AND BRANCH CIRCUIT
CONDUITS AS REQUIRED. RECONNECT ALL EXISTING FEEDER AND BRANCH
CIRCUITS. COORDINATE WITH GENERAL CONTRACTOR TO PATCH AND
REFINISH WALL AS REQUIRED.
2. REMOVE EXISTING PANEL MP. NOTE THAT ALL BRANCH CIRCUITS WILL BE
RECIRCUITED TO NEW PANEL LOCATION. REUSE OF EXISTING CONDUITS IS
ACCEPTABLE, BUT AREA SHALL HAVE A CLEAN APPEARANCE AT COMPLETION
OF WORK.
3. PROVIDE NEW DISTRIBUTION PANEL MP. REUSE EXISTING FEEDER AND
BRANCH CIRCUIT CONDUITS AND WIRES WHEREVER FEASIBLE.
4. COORDINATE FINAL LOCATION OF GENERATOR WITH EXISTING SITE AND C.O.
PRIOR TO ROUGH-IN.
5. PROVIDE NEW 20A, 1-POLE BREAKER IN EXISTING SQUARE D LOAD CENTER
TO SERVE NEW CIRCUITS.
KEY NOTES:#
N
I S S
E F
O R
P
LAN
O EN
G
IN
E E R
ON
T
M
AN
A
LICENSE
D
GARTH L.
STEVENS
No. 11492 PE
# DATE REVISION
2 07/23/2024 ADDENDUM 2
File details come from the government source that posted it. Updated .